The document provides specifications for a single slope industrial building with the following key details: - Dimensions of 12m width and 107m length with a clear height of 9.1m - Steel frame construction with non-expandable rigid frames at the front and back - Roof sheeting of 0.47mm thick galvalume and 0.5mm thick wall cladding - Includes two canopies, louvers along one 107m long side wall, and the ability to support three 5MT cranes running the length of the building - Loads and design criteria specified according to applicable Indian codes and standards

Uploaded by

SuryaSingh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
202 views1 page

QRF 1246

The document provides specifications for a single slope industrial building with the following key details: - Dimensions of 12m width and 107m length with a clear height of 9.1m - Steel frame construction with non-expandable rigid frames at the front and back - Roof sheeting of 0.47mm thick galvalume and 0.5mm thick wall cladding - Includes two canopies, louvers along one 107m long side wall, and the ability to support three 5MT cranes running the length of the building - Loads and design criteria specified according to applicable Indian codes and standards

Uploaded by

SuryaSingh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Location: Jamshepur

QRF-1246 Quantity of Buildings: One


Building - 1 TOTAL Area -
Sr. No Parameters Description
1 Type Single Slope
2 Width (m) 12 m O/O of Steel Column Refer attached drawing.
3 Length (m) 107 m O/O of Steel Column , Refer attached drawing.
4 Clear Height (m) 9.1m Clear Height from FFL.
5 Bay spacing (m) As per attached drawings.and Specification
6 Roof Slope 01:20
7 Width Module (m) As per attached drawings.
Front: Non Expandable Rigid Frame
8 Type of End Frames
Back: Non Expandable Rigid Frame
Rod / Angle Bracing as per Design, Portal to be considered upto 5.0M
9 Bracing type
height
10 Roof sheeting 0.47 mm TCT Bare Galvalume Roof Sheeting Screw Down profile.
11 Wall Cladding 0.50 mm TCT Color Galvalume Wall Sheeting profile.
Sheeted gable ends of main building.(Both Gable),0.55 mm TCT
12 Gable ends
Color Galvalume Wall Sheeting Hi-Rib profile.
13 Brick Wall 3.5 m from FFL. And above Cladding.
14 Canopy (without soffit) 2Nos @ 2.4M wide,4.5m Length X Height 6.5m
15 Framed Opening As per drawing to be considered
Eave Gutter (0.5mm Galvalume) & PVC Downtake as per location
16 Gutter and Down takes
rainfall size to be considered.
FOR wall- 2mm thick strip Polycarbonate sheets total length wall and
17 Day light sheet
end wall
All material i.e. column & rafter duly cleaned to SA2.5 then applied
18 Primer and Painting
with One Coat primer followed by 2 coats of synthetic paint
19 Accessories All Galvalume Trims & flashing as per design is considered.
20 Turbovent Not Applicable
21 Insulation Not Applicable
22 Louvers 1.4m wide x 107m Side Wall Length.Applicable As per Industrail
23 Ridge Vent Not Applicable
24 Anchor Bolts Black (Unpainted) Considered.
25 Building Design Condition Enclosed
5MT @ 3Nos. Crane running will throughout the Length of Building
26 Crane (EOT) (107 M) Please note that Two Cranes can come in One bay.(Refer to
Drawinfg and Specification)
27 Fascia Not Applicable
28 Mezzanine Not applicable
Design Loads: (Refer to Section 2 ‘Applicable Codes’ of this offer).
1 Design Dead Load (kg/m2) on roof As per Design
2 Design Live Load (kg/m2) on roof Refer to Drawinfg and Specification
3 Wind Speed (kmph) Refer to Drawinfg and Specification
4 Collateral Load (kN/m2) Consider 20kg/sqm for solar to be considered on roof.
5 Earthquake Zone As per loaction to be considered.
Deflection criteria:
1 Main Frame Vertical IS 800-2007
2 Main Frame Lateral IS 800-2007
3 Purlins / Girts IS 800-2007
4 Crane Beam Deflection IS 800-2007
Design & Manufacturing Codes:
1 Hot Rolled & Builtup Sections IS 800-2007
2 Cold Form Members IS 800-2007
3 Loads Calculations & Combinations IS 800-2007
4 Manufacturing Tolerance MBMA (Metal Building Manufacturer's Association)
5 Welding Code AWS, D1.1 (American Welding Society)
Material Consideration:
1 Builtup Members 345 Mpa (minimum - 5mm)
2 Cold Form Members 345 Mpa
3 Sheeting 550 Mpa
4 Connection Bolts 8.8 Grade
5 Other Members As per Design Requirement
Important Points
1 Drawing and Specification attached for reference.
2 Please refer Specifiaction with Drawings for Design Codes
Note: Please be noted that one side full length columns are considered to take load for similar kind of building in
3
future ie: Side wise Future expansion.
Loads we have to take as per IS for design we are flexible so that the tonnes can be optimise.
5 Louver we have consider full length of side wall (107 M). Please refer the drawing to insure kind of louver required.
6 flexible regarding the sheet considering economical between the both.
7 Take only solar Panels Load in design.
8 Crane running will throughout the Length of Building (107 M) Please note that Two Cranes can come in One bay.
9
10
11
12