Spec Sheet - 17
Spec Sheet - 17
Spec Sheet - 17
Diesel
generator set
QSX15 series
engine
364 kVA–550 kVA 50 Hz
409 kW–500 kW 60 Hz
Description
This Cummins® Power Generation Cooling system – Standard integral set-
commercial generator set is a fully integrated mounted radiator system, designed and tested
power generation system, providing optimum for rated ambient temperatures, simplifies facility
performance, reliability, and versatility for design requirements for rejected heat.
stationary standby and prime power.
Control system – The PowerCommand®
electronic control is standard equipment and
Features provides total genset system integration,
Cummins® heavy-duty engine – Rugged including auto remote start/stop, precise
4-cycle industrial diesel delivers reliable frequency and voltage regulation, alarm and
power, low emissions and fast response to status message display, AmpSentry protection
load changes. and output metering.
Engine specifications
Design 4 cycle, in-line, turbo charged, charge air cooled
Bore 137 mm (5.39 in.)
Stroke 169 mm (6.65 in.)
Displacement 15 liter (912 in3)
Cylinder block Cast iron, 6 cylinder
Battery capacity 100 AH
Battery charging alternator 35 amps
Starting voltage 24 volt, negative ground
Fuel system Direct injection
Fuel filter Spin on fuel filters with water separator
Air cleaner type Dry replaceable element with restriction indicator
Lube oil filter type(s) Spin on full flow filter
Standard cooling system 122 °F (50 °C) ambient radiator
Alternator specifications
Design Brushless, single bearing, revolving field
Stator 2/3 pitch
Rotor Single bearing, flexible disc
Insulation system Class H
Standard temperature rise Standby 125-163 °C
Exciter type Self excited (PMG optional)
Phase rotation A (U), B (V), C (W)
Alternator cooling Direct drive centrifugal blower fan
AC waveform total harmonic distortion (THDV) No load < 1.5%. Non distorting balanced linear load < 5%
Telephone influence factor (TIF) < 50 per NEMA MG1
Telephone harmonic factor (THF) < 2%
Available voltages
50 Hz Line–Neutral/Line–Line 60 Hz Line–Neutral/Line–Line
• 110/190 • 220/380 • 110/190 • 220/380
• 115/200 • 230/400 • 115/200 • 230/400
• 120/208 • 240/416 • 120/208 • 240/416
• 127/220 • 255/440 • 127/220 • 255/440
• 139/240 • 277/480
C
load for the duration of power interruption of a reliable
utility source. Emergency standby power (ESP) is
in accordance with ISO 8528. Fuel stop power in
accordance with ISO 3046, AS 2789, DIN 6271 and
BS 5514. A B
C
Prime power (PRP):
Applicable for supplying power to varying electrical
load for unlimited hours. Prime power (PRP) is in
A B
accordance with ISO 8528. Ten percent overload
capability is available in accordance with ISO 3046,
AS 2789, DIN 6271 and BS 5514. This outline drawing is to provide representative configuration
details for Model series only.
Base load (continuous) power (COP):
See respective model data sheet for specific model outline
Applicable for supplying power continuously to
drawing number.
a constant electrical load for unlimited hours.
Continuous power (COP) in accordance with
ISO 8528, ISO 3046, AS 2789, DIN 6271 and BS 5514. Do not use for installation design
Certifications
This generator set is designed in facilities
This generator set is available with
certified to ISO 9001 and manufactured in
CE certification.
facilities certified to ISO 9001 or ISO 9002.
This generator set conforms to former EU This generator set has been
Emissions
compliance
Stage II emission levels (50 Hz) and EPA ISO 8528 designed to comply with
Tier 2 (60 Hz) emissions regulations. ISO 8528 regulation.