Instructions For Installation and Operation High Pressure Compressed Air Refrigeration Dryer Drypoint RS 25-1010 HP50
Instructions For Installation and Operation High Pressure Compressed Air Refrigeration Dryer Drypoint RS 25-1010 HP50
Instructions For Installation and Operation High Pressure Compressed Air Refrigeration Dryer Drypoint RS 25-1010 HP50
1
Dear customer,
Thank you for deciding in favour of the DRYPOINT® RS 25-1010 HP50 high pressure compressed-air refrigeration
dryer. Please read these installation and operating instructions carefully before mounting and starting up the
DRYPOINT® RS 25-1010 HP50 and follow our directions. Perfect functioning of the DRYPOINT® RS 25-1010 HP50
and thus reliable compressed-air drying can only be guaranteed when the provisions and notes stipulated here are
strictly adhered to.
2 Safety instructions
Pos: 2 /Beko Technische Dokumentation/Globale Texte/Allgemeiner Hinweis BM @ 0\mod_1183615737313_6.doc @ 4004
Pos: 3 /Beko Technische Dokumentation/Sicherheit/Hinweis Anleitung BEKO @ 0\mod_1184147787557_6.doc @ 5758
Please check whether or not these instructions correspond to the device type.
Please adhere to all advice given in these operating instructions. They include essential information
which must be observed during installation, operation and maintenance. Therefore, it must be ensured
that these operating instructions are read by the fitter and the responsible operator / certified skilled
personnel prior to installation, start-up and maintenance.
The operating instructions must be accessible at all times at the place of application of the DRYPOINT®
RS 25-1010 HP50 high pressure compressed-air refrigeration dryer.
In addition to these operating instructions, local and national regulations need to be observed, where
required .
Ensure that operation of the DRYPOINT® RS 25-1010 HP50 high pressure compressed-air refrigeration
dryer only takes place within the permissible limit values indicated on the name plate. Any deviation from
these limit values involves a risk for persons and for the material, and may result in malfunction or a
breakdown.
After installing the device correctly and in accordance with the instructions in this manual, the dryer is
ready to operate, further settings are not required. Operation is fully automatic and maintenance is
limited to several examinations and cleaning measures which are described in the following chapters.
This manual must be available at all times for future reference and is a constituent part of the dryer.
If you have any queries regarding these installation and operating instructions, please contact BEKO
TECHNOLOGIES GMBH.
Supply voltage
Hot surfaces
Non-breathable air
Maintenance works or controlling measures must only be carried out by qualified personnel1
Do not smoke
Note
ARIA
AIR
LUFT Connection point compressed-air inlet
AIR
ARIA
AIR
LUFT Connection point compressed-air outlet
AIR
1
Certified skilled personnel are persons who are authorised by the manufacturer, with experience and technical training, who are
well-grounded in the respective provisions and laws and capable of carrying out the required works and of identifying and avoiding
any risks during the machine transport, installation, operation and maintenance.
Qualified and authorised operators are persons who are instructed by the manufacturer regarding the handling of the refrigeration
system, with experience and technical training, and who are well-grounded in the respective provisions and laws.
Works can be carried out by the operator of the plant, provided that they are skilled accordingly2.
NOTE: Text that contains important specifications to be considered – does not refer to safety precautions.
The device was carefully designed with particular attention paid to environmental protection:
CFC-free refrigerants
CFC-free insulation material
Energy-saving design
Limited acoustic emissions
Dryer and packaging comprise reusable materials
This symbol advises the user to observe the environmental aspects and comply with the recommendations
connected with this symbol.
2
Certified skilled personnel are persons who are authorised by the manufacturer, with experience and technical training, who are
well-grounded in the respective provisions and laws and capable of carrying out the required works and of identifying and avoiding
any risks during the machine transport, installation, operation and maintenance.
Qualified and authorised operators are persons who are instructed by the manufacturer regarding the handling of the refrigeration
system, with experience and technical training, and who are well-grounded in the respective provisions and laws.
Imminent hazard
Danger!
Consequences of non-observance: serious injury or death
Potential hazard
Warning!
Consequences of non-observance: possible serious injury or death
Imminent hazard
Caution!
Consequences of non-observance: possible injury or property damage
Potential hazard
Notice!
Consequences of non-observance: possible injury or property damage
Additional advice, info, hints
Important!
Consequences of non-observance: disadvantages during operation and maintenance, no danger
Danger!
Compressed air!
Risk of serious injury or death through contact with quickly or suddenly escaping compressed
air or through bursting and/or unsecured plant components.
Compressed air is a highly dangerous energy source.
Never work on the dryer when the system is under pressure.
Never direct the compressed-air outlet or condensate drain hoses at persons.
The user is responsible for the proper installation of the dryer. Non-observance of the instructions in the
"Installation" chapter leads to the expiration of the guarantee. Improper installation may result in
dangerous situations for the personnel and/or the device.
Pos: 5 /Beko Technische Dokumentation/Sicherheit/Maßnahmen Druckluft BM @ 0\mod_1184148284291_6.doc @ 5812
Pos: 6 /Beko Technische Dokumentation/Sicherheit/Gefahr Netzspannung @ 0\mod_1184148186948_6.doc @ 5794
Danger!
Supply voltage!
Contact with non-insulated parts carrying supply voltage involves the risk of an electric shock
resulting in injuries and death.
Only qualified and skilled personnel are authorised to run electrically-operated devices. Prior to
undertaking maintenance measures at the device, the following requirements must be met:
Make sure that the power supply is switched off and that the device is off and marked for maintenance
measures. Please also ensure that the power supply cannot be re-established during the works.
Pos: 7 /Beko Technische Dokumentation/Sicherheit/Maßnahmen Netzspannung BM 31/32/33 @ 0\mod_1216898430699_6.doc @ 11319
Caution!
Refrigerant!
The compressed-air refrigeration dryer uses HFC-containing refrigerants as a coolant.
Please observe the corresponding paragraph entitled "Maintenance works at the refrigeration cycle".
Warning!
Refrigerant leak!
A refrigerant leak involves the danger of serious injury and damage to the environment.
The DRYPOINT® RS 25-1010 HP50 high pressure compressed-air refrigeration dryer contains
fluorinated greenhouse gas/refrigerant.
Installation, repair and maintenance works at the refrigeration system must only be carried out by
certified skilled personnel (specialists). A certification in accordance with EC regulation 303/2008 must
be available.
The requirements of the EC 842/2006 directive must be met under all circumstances.
Please refer to the indications on the name plate as regards the type and amount of refrigerant.
Comply with the following protective measures and rules of conduct:
Storage: Keep the container tightly closed. Keep it in a cool and dry place. Protect it against heat
and direct sunlight. Keep it away from ignition sources.
Handling: Take measures against electrostatic charging. Ensure good ventilation/suction at the
workplace. Check fittings, connections and ducts for tightness. Do not inhale the gas. Avoid contact
with the eyes or the skin.
Prior to carrying out works on refrigerant-carrying parts, remove the refrigerant to such an extent
that safe working is possible.
Do not eat, drink or smoke during work. Keep out of the reach of children.
Breathing protection: ambient-air-independent respirator (at high concentrations).
Eye protection: sealing goggles.
Hand protection: protective gloves (e.g. made of leather).
Personal protection: protective clothing.
Skin protection: use protective cream.
In addition, the safety data sheet for the refrigerant needs to be observed!
Caution!
Hot surfaces!
During operation, several components can reach surface temperatures of more than +60°C.
There is the risk of burns.
All components concerned are installed inside of the closed housing. The housing must only be
opened by certified skilled personnel3.
Caution!
Improper use!
The device is intended for the separation of water in compressed air. The dried air cannot be used for
breathing-air purposes and is not suitable for the direct contact with food.
This dryer is not suitable for the treatment of contaminated air or of air containing solids.
3
Certified skilled personnel are persons who are authorised by the manufacturer, with experience and technical training, who are
well-grounded in the respective provisions and laws and capable of carrying out the required works and of identifying and avoiding
any risks during the machine transport, installation, operation and maintenance.
Qualified and authorised operators are persons who are instructed by the manufacturer regarding the handling of the refrigeration
system, with experience and technical training, and who are well-grounded in the respective provisions and laws.
Note!
Contaminated intake air!
In the event that the intake air is strongly contaminated (ISO 8573.1 class 3.-3 or poorer quality), we
recommend the additional installation of a prefilter (e.g. CLEARPOINT HP50S040), to avoid clogging of
the heat exchanger.
Caution!
Heating-up through fire!
In the event of a heating-up through fire, the containers and pipes of the refrigerant system can
burst.
In this case, please proceed as follows:
Switch off the refrigeration plant.
Switch off the mechanical ventilation of the machinery compartment.
Use ambient-air-independent respirators.
Containers and plants which are filled with refrigerant can burst violently in the event of fire.
The refrigerants themselves are incombustible, but they are degraded to very toxic products at high
temperatures.
Remove the container/plant from the fire zone, as there is the risk of bursting!
Cool down containers and bottles via a directed water jet from a safe position.
In the event of fire, please use an approved fire extinguisher. Water is not a suitable agent to
extinguish an electrical fire.
This must only be carried out by persons who are trained and informed about the hazards emanating
from the product.
Caution!
Unauthorised intervention!
Unauthorised interventions may endanger persons and plants and lead to malfunction.
Unauthorised interventions, modification and abuse of the pressure devices are prohibited.
The removal of sealings and leadings at safety devices is prohibited.
Operators of the devices must observe the local and national pressure equipment regulations in the
country of installation.
Pos: 8 /Beko Technische Dokumentation/Sicherheit/Sicherheitshinweise, weitere BM (nicht Ex) @ 0\mod_1183616103770_6.doc @ 4009os: 9 /Beko Technische Dokumentation/Sicherheit/Zusatz Sicherheitshinweise BM33 @ 0\mod_1231926887620_6.doc @ 12829s: 10 /Beko Technische Dokumentation/Sicherheit/Vorsicht Fehlfunktion @ 0\mod_1214378096290_6.doc @ 9359
Note!
Ambient conditions!
In the event that the dryer is not installed under suitable ambient conditions, the ability of the device to
condense refrigerant gas is impaired. This can result in a higher load of the refrigerating compressor,
and in a loss of efficiency and performance of the dryer.
This in turn leads to overheated condenser fan motors, to malfunction of electric components and to a
breakdown of the dryer. Failures of this type will affect warranty considerations.
Do not install the dryer in an environment in which chemicals with a corrosive effect, explosive gases,
toxic gases, evaporation heat, high ambient temperatures or extreme dust and dirt can be found.
Note!
Improper use!
The device is intended for the separation of water in compressed air. The dried air cannot be used for
breathing-air purposes and is not suitable for the direct contact with food.
This dryer is not suitable for the treatment of contaminated air or of air containing solids.
For the examination prior to the start-up and for periodic inspections, the national regulations need to be observed,
such as the industrial safety regulation in the Federal Republic of Germany. In countries outside the EU, the respective
regulations in force there need to be adhered to.
The proper use of pressure devices is the basic requirement for safe operation. As regards pressure devices, the
following points need to be observed:
The DRYPOINT® RS 25-1010 HP50 high pressure compressed-air refrigeration dryer must only be employed
within the pressure and temperature range limits indicated by the manufacturer on the name plate.
No welding must be carried out on the pressure parts.
The DRYPOINT® RS 25-1010 HP50 high pressure compressed-air refrigeration dryer must neither be installed in
insufficiently ventilated rooms nor near heat sources or inflammable substances.
To avoid fractures resulting from material fatigue, the refrigeration dryer should not be exposed to vibrations during
operation.
The maximum operating pressure indicated by the manufacturer on the name plate must not be exceeded. It is the
installer's responsibility to install the appropriate safety and control devices. Prior to the start-up of the DRYPOINT®
RS 25-1010 HP50 high pressure compressed-air refrigeration dryer, the connected pressure generator
(compressor etc.) must be set to the max. permissible operating pressure. The integrated safeguard needs to be
checked by an approved inspection agency.
The documents related to the DRYPOINT® RS 25-1010 HP50 high pressure compressed-air refrigeration dryer
(manual, operating instructions, manufacturer's declaration etc.) must be kept safe for future reference.
No objects whatsoever must be installed at or placed on the DRYPOINT® RS 25-1010 HP50 high pressure
compressed-air refrigeration dryer and the connecting lines.
Installation of the plant in frost-free places only.
Operation of the plant is only permissible with fully closed and intact housing and cover panels. Operation of the
plant with damaged housing/cover panels is prohibited.
7 Storage
Keep the device away from extreme weather conditions
even when packaged.
Keep the dryer in an upright position, also while it is
stored. Tilting the device or turning it upside down can
cause irreparable damage to some components.
When the dryer is not in use, it can be stored in its
packaging in a dust-free and protected place at a
temperature of +1°C … +50°C and at a specific humidity
of max. 90%. If the storage period exceeds 12 months,
you should contact the manufacturer.
SCC0001
The packaging material is recyclable. Dispose of the material in accordance with the
directives and provisions in force in the country of destination
Note!
Ambient conditions!
In the event that the dryer is not installed under suitable ambient conditions, the ability of the device to
condense refrigerant gas is impaired. This can result in a higher load of the refrigerating compressor, and in
a loss of efficiency and performance of the dryer.
This in turn leads to overheated condenser fan motors, to malfunction of electric components and to a
breakdown of the dryer. Failures of this type will affect warranty considerations.
Do not install the dryer in an environment in which chemicals with a corrosive effect, explosive gases, toxic
gases, evaporation heat, high ambient temperatures or extreme dust and dirt can be found.
Note!
Dryers models RS 25 – 135 can be wall-mounted. See fixing dimensions on dimensional drawings in the
appendices section.
The hanging mounting inevitably causes the obstruction of the ventilation grid positioned on the panel
facing the wall fixing. This obstruction, in any case, does not prejudge the efficiency of the ventilation
inside the dryer which is guaranteed by other grids on the other panels.
1 Air compressor
2 Aftercooler
3 Condensate separator
4 Prefilter
5 Bypass group
6 Dryer
7 Compressed-air tank
8 Final filter
9 Bekomat condensate drain
Installation type A is recommended when the total consumption corresponds to the throughput rate of the compressor.
Installation type B is recommended when the air consumption constantly varies, with peak values which considerably
exceed the throughput rate of the compressor. The storage capacity of the tank must be dimensioned in such a way
that a possible short-term high air demand (peak air consumption) can be compensated.
Actual air throughput = air throughput acc. to planning x factor (F1) x factor (F2) x factor (F3) x factor (F4)
Example:
The DRYPOINT RS 180 HP50 has a planned nominal capacity of 180 m³/h. The highest achievable air
mass under the following operating conditions is:
Actual air throughput = 180 x 0.94 x 0.90 x 0.69 x 1.37 = 144 m³/h
144 m³/h is the maximum flow rate of the dryer under the aforementioned operating conditions.
Selection of the best suitable model in accordance with the operating conditions:
Requ. air throughput
Air throughput acc. to planning =
Factor (F1) x Factor (F2) x Factor (F3) x Factor (F4)
Example:
The following operating parameters are known:
Required air mass = 200 m3/h
Factor (F1) = 0.94
Air inlet pressure = 35 bar(g)
Factor (F2) = 0.90
Ambient temperature = 35°C Factor (F3) = 0.69
Air inlet temperature = 45°C Factor (F4) = 1.37
Pressure dew point = 10°C
To find out the correct dryer version, the required air mass must be divided by the correction factors of the
parameters indicated above:
200
Air throughput acc. to planning = = 250 m³/h
0.94 x 0.90 x 0.69 x 1.37
The suitable model for these requirements is DRYPOINT RS 320 HP50 (with a spec. nominal capacity of 315 m³/h).
Danger!
Compressed air!
All works must only be carried out by qualified skilled personnel.
Never work on compressed-air systems which are under pressure.
The operator or the user must ensure that the dryer is never operated with a pressure exceeding the
maximum pressure value indicated on the name plate.
Exceeding the maximum operating pressure can be dangerous for the operator but also for the device.
The air temperature and the air flow at the inlet of the dryer must lie within the limit values indicated on the name plate.
The connecting lines must be free from dust, iron rust, shards and other contaminations and correspond to the flow
rate of the dryer. Should air with a very high temperature be treated, the installation of an aftercooler may be
necessary. For the implementation of maintenance works, the installation of a bypass system is recommended.
Note!
Pulsation and vibrations!
Pulsations and vibrations must be eliminated from the compressed air and IN/OUT piping to avoid
possible fatigue failure.
Do not use the dryer to treat air containing corrosive substances for copper and its alloys..
===== Ende der Stückliste =====
Note!
Contaminated intake air!
In the event that the intake air is strongly contaminated (ISO 8573.1 class 3.-3) or poorer quality, we
recommend the additional installation of a prefilter (e.g. CLEARPOINT HP50S040), to avoid clogging of
the heat exchanger.
Danger!
Compressed air and unqualified personnel!
All works must only be carried out by qualified skilled personnel.
Never work on compressed-air systems which are under pressure.
The user must ensure that the dryer is never operated with a pressure exceeding the nominal values.
Possible overpressure can be dangerous for the operator but also for the device.
The temperature and the amount of cooling water need to correspond to the limit values indicated on the name plate.
The cross-section of the connecting lines, which should preferably be flexible, must be free from dust, iron rust, shards
and other contaminations. We recommend employing connecting lines (flexible hoses, vibration-inhibiting fittings etc.)
which protect the dryer against possible vibrations in the pipework.
Note!
Contaminated intake water!
In the event that the intake water is strongly contaminated we recommend the additional installation of a
prefilter (500 micron), to avoid clogging of the heat exchanger.
Note: (1) – Other temperatures upon request – check the data on the name plate.
(2) – Other pressures upon request – check the data on the name plate.
(3) – Pressure difference at the water connection of the dryer at maximum water flow.
Other delivery pressures upon request.
CAUTION!
During the piping of the dryer, the inlet and outlet connections need to be supported as is shown in the
illustration.
Non-observance will cause damage.
Danger!
Supply voltage!
The connection to the electric mains should only be carried out by qualified skilled personnel and must
correspond to the legal provisions in force in your region.
Prior to connecting the device, please check the name plate to avoid exceeding the indicated values. The voltage
tolerance is +/- 10%.
Dryers are supplied with a VDE 16A standard power cord and safety plug (two-pole and earth connection) or with a
junction box on the back plate.
Make sure that suitable fuses or circuit breakers in accordance with the indications on the name plate are available.
A residual-current device (RCD) with In =0.03A is suggested. The cross-section of the power supply cable must
correspond to the power consumption of the dryer. In this respect, the ambient temperature, the cable laying
conditions, the length of the cables and the requirements of the local electricity supplier need to be considered.
Danger!
Supply voltage and missing earth connection!
Important: ensure that the plant is connected to earth.
Do not use plug adapters at the power plug.
Possible replacement of the power plug must only be carried out by a qualified electrician.
8.8 Condensate drain
Danger!
Compressed air and condensate under pressure!
The condensate is discharged at system pressure.
The drain pipe needs to be secured.
Never direct the condensate drain pipe at persons.
The dryer is delivered with an already integrated electronically level-controlled BEKOMAT condensate drain. Connect
the condensate drain with a collection system or container by properly screwing it on.
Do not connect the drain with pressurised plants.
It is advisable to install a water-oil separator, to which the total amount of condensate from the
compressors, dryers, tanks, filters etc. is supplied.
We recommend ÖWAMAT oil-water separators for dispersed compressor condensate and BEKOSPLIT
emulsion-splitting plants for emulsified condensate.
Note!
Exceeding of the operating parameters!
Ensure that the operating parameters comply with the nominal values indicated on the name plate of the
dryer (voltage, frequency, air pressure, air temperature, ambient temperature etc.).
Prior to delivery, this dryer was thoroughly tested, packed and checked. Please verify the soundness of the dryer
during the initial start-up and check the perfect functioning during the first operating hours.
The operator and the user must ensure that the dryer is not operated without panels.
Note!
The dryer must not be started up more than six times an hour. Wait at least five minutes prior to
every restart.
The user is responsible for the compliance with these provisions. Irreparable damage can be caused by
starting up the device too often.
The method below should be applied during the first start-up, after longer downtimes or subsequent to
maintenance works.
The start-up must be carried out by certified skilled personnel.
RS 320-1010 3phase - during short-term inactivity (max. two to three days), it is advisable to leave the
dryer and the control panel connected to the supply current circuit. Otherwise, it would be necessary at a
restart of the dryer to wait two hours, until the crankcase heater of the compressor has heated up the oil
in the compressor.
Shut down (see Section 11.1 "Control panel")
• Ensure that the dew point temperature indicated on the electronic control unit is stable.
• Interrupt the compressed-air supply.
• After a few minutes, stop the dryer by switching off the main switch on the control panel (pos. 1).
Restart (see Section 11.1 "Control panel")
• Remove the jumper between terminals 1 and 2 of the terminal strip and wire a potential-free contact (see electric
diagram).
• Switch ON the main switch - pos. 1 on the control panel.
• Close the contact at terminals 1 and 2 to switch on the dryer.
• Open the contact at terminals 1 and 2 to switch off the dryer.
Only use potential-free contacts that are suitable for 230 Vac. Ensure the sufficient insulation of
potentially dangerous voltage-carrying components.
Caution!
Automatic restart / remote control ON/OFF. The unit may start up without any active influence!
The user will be responsible for the installation of proper protections for possible sudden power
restoration to the dryer.
During the operation, the refrigerating compressor runs continuously. The dryer needs to be switched on during the
entire compressed-air usage time, even if the compressed-air compressor works periodically.
Note!
RS 25-70 - A dew point included in the green operating area of the electronic control unit is considered to
be correct according to the possible operating conditions (flow rate, air inlet temperature, ambient
temperature etc.).
RS 90-1010 - A dew point between 0°C and +10°C displayed on the electronic control unit is considered
to be correct according to the possible operating conditions (flow rate, air inlet temperature, ambient
temperature etc.).
Note!
The dryer must not be started up more than six times an hour. Wait at least five minutes prior to
every restart. The user is responsible for the compliance with these provisions. Irreparable damage can
be caused when starting up the device too often.
RS 25 – 70 RS 90 – 240
1 1
ON DMC35
0 0
sec - min
Set Set
1 K 1 K
PQS0119
PQS0120
2 3 2 3
1
I
ON
0
Set
Set 3
K K
PQS0121
T4 T3
3
T2
1 2
T1
A Main switch
1 ON-OFF switch
PQS0122
2 Electronic instrument
3 Air and refrigerant flow diagram
Refrigeration cycle – The refrigerant is conducted through the compressor and reaches a condenser under high
pressure. There, cooling-down takes place, making the refrigerant condense to a liquid state which is under high
pressure. The liquid is pressed through a capillary tube where the resulting pressure drop ensures that the refrigerant
evaporates at a defined temperature. The liquid refrigerant which is under low pressure is led into the heat exchanger,
where it expands. The cold resulting from the expansion serves to cool down the compressed air in the heat exchanger.
During this process, the refrigerant evaporates. The low-pressure gas is resupplied to the compressor, where it is
compressed again. It then re-enters the cycle. In phases of a reduced compressed-air load, the excess refrigerant is
resupplied automatically to the compressor via the hot gas bypass valve.
VLY0001
+
(position A on the drawing) until the following value is reached:
Hot gas setting : R134.a pressure 2.0 barg (+0.1 / -0 bar)
R407C pressure 4.5 barg (+0.1 / -0 bar)
conditions are reached again. Unscrew the cover (see pos. 1 in the illustration)
and press the reset button (see position 2 in the illustration).
PQS0005
ON Led – Power ON
Led - Drain ON
sec - min
Led – Condenser fan ON
PQS0091
Set
Set Button – Setup menu access
The DMC35 displays DewPoint temperature, controls the condenser fan activation, controls the timed drainer and keep
record of the total hours of operation of the dryer.
Led and display 1st (left) and 10th (right) led Failure BT1 (DewPoint) temperature probe.
are flashing
Failure BT2 / BP2 (fan control) probe.
Led and led are flashing NOTE : fan is forced always ON.
DewPoint too low
Led and display 1st (left) led are flashing (lower than -1°C / 30°F).
Press button, led is lit and a certain numbers of leds of dew point indication bar are light up. The
number of leds lit define the 2nd digit of hour counter (ie : n.3 leds lit 2nd digit = 3)
Press button, led is lit and a certain numbers of leds of dew point indication bar are light up. The
number of leds lit define the 3rd digit of hour counter (ie : n.8 leds lit 3rd digit = 8)
Total operating hours : 0 3 8 x 100 (fixed multiplying ratio) = 3800 hours
Press button repeatedly to scroll the displaying of 3 digits again.
Press Set button to exit total hours display (if no button is pressed after 30 seconds the menu is exited
automatically).
Only qualified personnel must be allowed to access to the setup menu. The manufacturer is not
responsible for malfunctioning or failure due to modification to the operating parameters.
With dryer ON press button Set for at least 2 seconds to enter the setup menu.
Access to the menu is confirmed by led ON flashing.
Keep Set pressed and use arrows to change the value. Release the button Set to confirm
the value. Press shortly Set to skip to following parameter.
Press to exit setup menu (if no button is pressed after 2 minutes the menu is exited automatically).
Standard
Display Description Limits Resolution
setup
Synchronous flashing TON – drain time ON : time ON
1 … 6 sec 1 sec 2
led ON + led condensate drain valve (1)
NOTE : parameter values are displayed on the 10 led display where 1st (left) led is the lowest limit and 10th (right) is
the highest limit.
NOTE (1) : TON set at the 10th led (right) keep drain output always powered and led always off (used if
electronic drainer is installed)
Led - Temperature in °C
Led - Temperature in °F
Led – Drain ON
Led – Fan ON
Led – Alarm/Service
Set
Condensing
Button – Decrease / Service
DISPLAY Button – Increase / Drain test
The DMC34 displays DewPoint temperature, controls the condenser fan activation, handles a service reminder and
keep record of the total hours of operation of the dryer.
NOTE : with led on temperatures are in °C and pressure in barg; with led on temperatures are in °F
and pressure in psig.
The total hours of operation and the hours until the next service are shown in the field 0…999 hours and
in thousands of hours from 01.0 hours on (example : if the display shows number 35 it means 35 hours;
if the display shows number 3.5 it means 3500 hours).
Only qualified personnel must be allowed to access to the setup menu. The manufacturer is not
responsible for malfunctioning or failure due to modification to the operating parameters.
With dryer ON simultaneously press buttons Set + for at least 5 seconds to enter the setup menu.
Access to the menu is confirmed by message on the display (first parameter of menu).
Keep Set pressed to display the value of the selected parameter and use arrows and to
change the value. Release the button Set to confirm the value and skip to following parameter.
Press + to exit setup menu (if no button is pressed after 2 minutes the menu is exited
automatically).
Standard
ID Description Limits Resolution
setup
Ton – drain time ON : time ON condensate drain valve ON
1 sec 2
ON = Electronic drainer installed 00 … 20 sec
ToF - drain time OFF : pause time for condensate drain
1 … 20 min 1 min 1
valve
HdS – High DewPoint Setting : Alarm threshold for a high 0.0…25.0 °C 0.5 °C 20
DewPoint (the alarm disappears when the temperature drop or or or
1°C / 2°F below alarm point) 32 … 77 °F 1 °F 68
Hdd - High DewPoint Delay : high DewPoint alarm enable 01 … 20
1 min 15
delay minutes
0.5
SrV - Service Setting: setting of service warning timer. 00.0 … 20.0
(x1000) 08.0
00 = service warning timer disabled. (x 1000) hours
hours
SrC – Service Contact : configuration of the alarm dry
contact for the service warning timer.
YES / NO - YES
YES = activate the contact / NO = NOT activate the
contact
SCL - Scale: display scale of temperatures and pressure (°C
= temperatures in °C and pressure in barg; °F = °C … °F - °C
temperatures in °F and pressure in psig)
Note!
These BEKOMAT condensate drains were designed in particular for the operation in a DRYPOINT RS
HP50 refrigeration dryer. The installation in other compressed-air processing systems or the replacement
with another drain brand can lead to malfunction. The maximum operating pressure (see name plate)
must not be exceeded!
Ensure that the upstream valve is open when the dryer starts operation.
Danger!
Compressed air!
Risk of serious injury or death through contact with quickly or suddenly escaping compressed
air or through bursting and/or unsecured plant components.
Compressed air is a highly dangerous energy source.
Never work on the dryer when the system is under pressure.
Never direct the compressed-air outlet or condensate drain hoses at persons.
The user is responsible for the proper maintenance of the dryer. Non-observance of the instructions in
the "Installation" and "Maintenance, troubleshooting, spare parts and dismantling" chapters leads to the
expiration of the guarantee. Improper maintenance may result in dangerous situations for the personnel
and/or the device.
Danger!
Supply voltage!
Contact with non-insulated parts carrying supply voltage involves the risk of an electric shock
resulting in injuries and death.
Only qualified and skilled personnel are authorised to run electrically-operated devices. Prior to
undertaking maintenance measures at the device, the following requirements must be met:
Make sure that the power supply is switched off and that the device is off and marked for maintenance
measures. Please also ensure that the power supply cannot be re-established during the works.
Prior to carrying out maintenance works at the dryer, switch it off and wait for at least 30 minutes.
Caution!
Hot surfaces!
During operation, several components can reach surface temperatures of more than +60°C.
There is the risk of burns.
All components concerned are installed inside of the closed housing. The housing must only be opened
by certified skilled personnel.
Some components can reach high temperatures during operation. Avoid any contact until the system or
the component has cooled down.
4
Certified skilled personnel are persons who are authorised by the manufacturer, with experience and technical training, who are
well-grounded in the respective provisions and laws and capable of carrying out the required works and of identifying and avoiding
any risks during the machine transport, installation, operation and maintenance.
Qualified and authorised operators are persons who are instructed by the manufacturer regarding the handling of the refrigeration
system, with experience and technical training, and who are well-grounded in the respective provisions and laws.
DAILY:
• Check whether the dew point indicated on the electronics is correct.
• Ensure that the condensate drain system functions properly.
• Make sure that the condenser is clean.
EVERY 200 HOURS OR MONTHLY
• Clean the condenser using an air jet (max. 2 bar / 30 psig) inside out. Make
sure not to damage the aluminium lamellae of the cooling package.
• Finally, verify the operation of the device.
EVERY YEAR
• Clean housing and valve of BEKOMAT
• Replace BEKOMAT wearing parts
12.2 Troubleshooting
Danger!
Supply voltage!
Contact with non-insulated parts carrying supply voltage involves the risk of an electric shock resulting
in injuries and death.
Only qualified and skilled personnel are authorised to run electrically-operated devices. Prior to
undertaking maintenance measures at the device, the following requirements must be met:
Make sure that the power supply is switched off and that the device is off and marked for maintenance
measures. Please also ensure that the power supply cannot be re-established during the works.
Prior to carrying out maintenance works at the dryer, switch it off and wait for at least 30 minutes.
Caution!
Hot surfaces!
During operation, several components can reach surface temperatures of more than +60°C. There is
the risk of burns.
All components concerned are installed inside of the closed housing. The housing must only be opened
by certified skilled personnel.
Some components can reach high temperatures during operation. Avoid any contact until the system or
the component has cooled down.
The dryer does not The shut-off valve at the condensate outlet is closed – open it.
drain the condensate. Check the electric cabling.
The dew point is too low – the condensate is frozen – see the corresponding point.
The BEKOMAT condensate drain does not work properly (see BEKOMAT MANUAL).
Failure during the Please read the separate BEKOMAT installation and operating instructions.
condensate discharge.
Water in the line. The dryer does not start – see the corresponding point.
If installed - untreated air flows through the bypass unit – close the bypass.
The dryer does not drain condensate – see the corresponding point.
Dew point too high – see the corresponding point.
HPS high-pressure Check which of the following reasons is responsible for the triggering:
switch has triggered. 1. The ambient temperature is too high or the room ventilation insufficient – ensure sufficient
ventilation (air-cooled).
2. The condenser is dirty – please clean it (air-cooled).
3. The condenser fan does not work – see the corresponding point (air-cooled).
4. The cooling water is too hot – re-establish the nominal conditions (water-cooled).
5. The cooling-water flow is insufficient – re-establish the nominal conditions (water-cooled).
Reset the pressure switch by pressing the button on the controller itself – check the proper
functioning of the dryer.
The HPS pressure switch is defective – contact a BEKO service technician for the
replacement.
If installed: There is a leak in the refrigeration cycle – please contact a BEKO service technician.
the LPS low-pressure The pressure switch is automatically reset as soon as the normal conditions are re-
switch was triggered. established – check the dryer for proper functioning.
If installed: Check which of the following reasons is responsible for the triggering:
the TS safety 1. Excess thermal load – re-establish the standard operating conditions.
temperature switch 2. The inlet air is too hot – re-establish the nominal conditions.
was triggered. 3. The ambient temperature is too high or the room ventilation insufficient – ensure sufficient
ventilation.
4. The condenser unit is dirty – please clean it.
5. The fan does not work – see the corresponding point.
6. The hot-gas bypass valve needs to be re-adjusted – contact a specialist for refrigerating
plants to have the nominal calibration re-established.
7. The cooling-water temperature is too low – re-establish the nominal conditions (water-
cooled).
8. The adjusting valve for the cooling-water flow needs to be re-adjusted – contact a specialist
to have the nominal calibration re-established (water-cooled).
9. There is a leak in the refrigeration cycle – please contact a BEKO service technician.
Reset the temperature switch by manually pushing the button on the temperature switch –
check the perfect functioning of the dryer.
The TS temperature switch is defective – replace it.
DMC35 - Led Verify the electric wiring of BT1 DewPoint probe.
The BT1 DewPoint probe is faulty - replace it.
and display 1st
The electronic controller is faulty - replace it.
(left) and 10th (right) led
are flashing.
DMC35 - Leds Verify the electric wiring of BT2 / BP2 fan control probe.
The BT2 / BP2 fan control probe is faulty - replace it.
and are
The electronic controller is faulty - replace it.
flashing
DMC35 Led DewPoint too low - see specific point.
The BT1 DewPoint probe is faulty - replace it.
and display 1st
The electronic controller is faulty - replace it.
(left) led are flashing
DMC35 DewPoint too high - see specific point.
The last led of the display The BT1 DewPoint probe is faulty - replace it.
is flashing The electronic controller is faulty - replace it.
DMC34 – Led is Verify the electric wiring of BP2 fan control probe.
flashing + display The BP2 fan control probe is faulty - replace it.
. The electronic controller is faulty - replace it.
DMC34 – Led is Service reminder timer has expired – dryer requires service.
flashing + display Perform the proper service to the dryer.
. Reset the service reminder timer.
Caution!
Refrigerant!
Maintenance and repair works at refrigeration systems must only be carried out by BEKO service
technicians in accordance with the local provisions.
The total amount of refrigerant in the system must be collected for recycling purposes, resource recovery
or disposal.
The refrigerant must not be discharged into the environment.
When delivered, the dryer is ready to operate and filled with a refrigerant of the R134a or R407C type.
Should you detect a refrigerant leak, please contact a BEKO service technician. Prior to any intervention,
the room needs to be ventilated.
When the refrigeration cycle needs to be refilled, please also contact a BEKO service technician.
You will find the refrigerant type and amount on the name plate of the dryer.
Part Material
Refrigerant fluid R407C, R134a, Oil
Canopy and supports Carbon steel, Epoxy paint
Refrigerating compressor Steel, Copper, Aluminium, Oil
Heat exchanger Stainless steel, Copper
Condensate separator Stainless steel
Condenser unit Aluminium, Copper, Carbon steel
Pipe Copper
Fan Aluminium, Copper, Steel
Valve Brass, Steel
Electronic level drain PVC, Aluminium, Steel
Insulation material Synthetic rubber without CFC, Polystyrene, Polyurethane
Electric cable Copper, PVC
Electric parts PVC, Copper, Brass
We recommend observing the safety provisions in force for the disposal of each material type.
The refrigerant contains lubricating-oil droplets which are released by the compressor.
The refrigerant must not be discharged into the environment. It must to be sucked off from the dryer
using a suitable device, and then needs to be supplied to a collection point.
MC : Compressor
KT : Compressor thermal protection
KR : Compressor starting relay (if installed)
CS : Compressor starting capacitor (if installed)
CR : Compressor operating capacitor (if installed)
MV : Condenser fan
CV : Fan starting capacitor (if installed)
DMC35 : DMC35 electronic instrument – air dryer control
BT1 : T1 Temperature probe – dew point
BT2 : T2 Temperature probe – fan control
DMC34 : DMC14 Electronic Instrument - Air Dryer Controller
BT1 : T1 Temperature probe – dew point
BP2 : Pressure transducer - fan control
HPS : Pressure switch – compressor discharge side (HIGH PRESSURE)
LPS : Pressure switch – compressor suction side (LOW PRESSURE)
TS : Safety temperature switch
ELD : BEKOMAT drain
S1 : ON/OFF switch
QS : Main switch with locking device
RC : Compressor crankcase heater
BOX : Electrical connection
BN = BROWN OR = ORANGE
BU = BLUE RD = RED
BK = BLACK WH = WHITE
YG = YELLOW/GREEN WH/BK = WHITE/BLACK
GERMANY
EU-Konformitätserklärung
Wir erklären hiermit, dass die nachfolgend bezeichneten Produkte den Anforderungen der einschlägigen Richtlinien
und technischen Normen entsprechen. Diese Erklärung bezieht sich nur auf die Produkte in dem Zustand, in dem
sie von uns in Verkehr gebracht wurden. Nicht vom Hersteller angebrachte Teile und/oder nachträglich
vorgenommene Eingriffe bleiben unberücksichtigt.
Produktbezeichnung: DRYPOINT® RS
Modelle: 25 HP 50, 45 HP 50, 70 HP 50, 90 HP 50, 135 HP 50,
180 HP 50, 240 HP 50, 320 HP 50, 450 HP 50, 620 HP 50,
810 HP 50
Spannungsvarianten: 230 VAC
Max. Betriebsdruck: 50 bar (g)
Produktbeschreibung und Funktion: Kältetrockner zur Herabsetzung des Drucktaupunkts in
Druckluft
Maschinen-Richtlinie 2006/42/EG
Angewandte harmonisierte Normen: EN 14119, EN 14120, EN 12100, EN 13849-1; EN 60204-1
Name des Dokumentationsbevollmächtigten: Jürgen Hütter Im Taubental 7, 41468 Neuss, Deutschland
Druckgeräte-Richtlinie 2014/68/EG
Angewandte harmonisierte Normen: ASME VIII Div. 1, EN 378-2, EN 10028-3, EN 12451
Angewandtes
Konformitätsbewertungsverfahren: Modul A
Die Produkte 25 HP 50 – 240 HP 50 fallen in keine Druckgerätekategorie und sind gemäß Artikel 4 Absatz 3 in
Übereinstimmung mit der in den Mitgliedstaaten geltenden guten Ingenieurspraxis ausgelegt und werden dieser
entsprechend hergestellt.
Niederspannungs-Richtlinie 2014/35/EU
Angewandte harmonisierte Normen: EN 60204-1
EMV-Richtlinie 2014/30/EU
Angewandte harmonisierte Normen: EN 61000-6-2:2016, EN 61000-6-4:2018
Der Hersteller trägt die alleinige Verantwortung für die Ausstellung dieser Konformitätserklärung.