D3 - FTA Calc Numbers Main Body

This document presents a fault tree analysis for a high temperature safety instrumented function (SIF). The fault tree shows the system can fail to shut off feed flow due to failures in the logic solver, valves failing to close, or temperature sensors failing to detect a high temperature. Component failure rates are provided and the average probability of failure on demand (PFDavg) is calculated as 6.48x10-3, resulting in a risk reduction factor (RRF) of 154, classifying it as SIL 2.

Uploaded by

Amaury Freire
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
159 views2 pages

D3 - FTA Calc Numbers Main Body

This document presents a fault tree analysis for a high temperature safety instrumented function (SIF). The fault tree shows the system can fail to shut off feed flow due to failures in the logic solver, valves failing to close, or temperature sensors failing to detect a high temperature. Component failure rates are provided and the average probability of failure on demand (PFDavg) is calculated as 6.48x10-3, resulting in a risk reduction factor (RRF) of 154, classifying it as SIL 2.

Uploaded by

Amaury Freire
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

7/27/2012

High Temperature SIF


Safety Availability Fault Tree Construction

High Temperature

Fail to shut-off Logic Solver Fail to Detect


Feed Flow Failure Hi Temp

Valves 1oo2 TS 1oo2

Fail to Close Fail to Close


Block Valve SV1 Block Valve SV2

TS-1 TS-2
VALVE-SOV 2oo2 VALVE-SOV 2oo2
3.3 E-2 3.3 E-2

l =3*10-5f/h
T= 3 months (2190 h)
SV-1 SOL-1 SV-2 SOL-2 PFDavg= l *T/2 = 3 *10-5 * 2190/2
= 3285 * 10-5 = 3.3 * 10-2

High Temperature SIF


Safety Availability Fault Tree Construction

High Temperature PFDavg= 6.48 * 10-3


SIL X (Low – Med – High) ?
……
RRF = ?
Fail to shut-off Logic Solver Fail to…...
Detect
Feed Flow Failure Hi Temp

Valves 1oo2 TS 1oo2

Fail to Close Fail to Close


Block Valve SV1 Block Valve SV2

TS-1 TS-2
VALVE-SOV 2oo2 VALVE-SOV 2oo2
3.3 E-2 3.3 E-2

l =9.041*10-6f/h
SV-1 SOL-1 SV-2 SOL-2
T= 3 months (2190 h)
PFDavg= l *T/2 = 9.041 *10-6 * 2190/2
9.9 E-3 9.9 E-3 9.9 E-3 = 9899 * 10-6 = 9.9 * 10-3
9.9 E-3

1
7/27/2012

High Temperature SIF


Safety Availability Fault Tree Construction
High Temperature PFDavg= 6.48 * 10-3
RRF= 154 SIL 2 (Low)
3.92 E-4 5.0 E-3 10.89 E-4
Fail to shut-off Logic Solver Fail to Detect
Feed Flow Failure Hi Temp

1.98 E-2 Valves 1oo2 1.98 E-2 TS 1oo2

Fail to Close Fail to Close


Block Valve SV1 Block Valve SV2

TS-1 TS-2
VALVE-SOV 2oo2 VALVE-SOV 2oo2
3.3 E-2 3.3 E-2

SV-1 SOL-1 SV-2 SOL-2

9.9 E-3 9.9 E-3 9.9 E-3 9.9 E-3