Remote Display Panel - Eng
Remote Display Panel - Eng
SW: ZAMPMH02
Ref:SP719ZAM.DOC
First issue: 29.08.06 MB
Revision 3 of 03.04.08 MB
INDEX
1. OBJECT 4
2. SYSTEM ARCHITECTURE 4
2.1 STANDARD CONNECTION FOR SERIAL LINKED UNIT 6
2.1.1 WIRING DIAGRAM 7
2.2 CONNECTION FOR SERIAL LINKED UNIT WITH THREE SERIAL GATEWAY 8
3. HARDWARE OVERVIEW 9
3.1 HARDWARE FEATURES 9
3.2 I/O CHANNELS 13
3.2.1 ANALOG INPUT 13
3.2.2 DIGITAL OUTPUT 13
3.2.3 ANALOG OUTPUT 14
3.2.4 DIGITAL INPUT 14
4. PROGRAMMING INSTRUCTION 15
4.1 PROGRAMMING BY SERIAL LINE 15
4.2 PROGRAMMING BY HARDWARE KEY (HKEY) 15
6. SOFTWARE SPECIFICATIONS 21
6.1 OPERATIONS 21
6.1.1 PUMPS ONLY MODE 21
7. REVISION HISTORY 75
1. OBJECT
The object of this specification is the Remote Control Unit, a controller that allows:
1. the control and monitoring of the Serial Linked Units (SLU), connected through a serial line
(RS485); the followings operations are possible:
o display data
o get access to setup parameters
o set the demand to each unit
2. the control of the Digital Linked Units (DLU), connected though digital output;
3. the control of the pumps
2. SYSTEM ARCHITECTURE
The system architecture is as follows:
• user interface “CO1” with LCD display;
• one master controller board “SB2” with an user interface “CO1” connected via serial bus
(RS485) to COM1;
• Remote Chillers with:
- until a maximum of 8 Serial Linked Units (SLU) connected via serial bus (RS485) to
COM3;
- until a maximum of 8 Digital Linked Units (DLU) activated by digital output DLUn
(n=1..8).
• A Process Pumps Group (GPP) activated by digital output PUn (n=1..4);
• A Circulating Pumps Group (GPR) activated by digital output PUR;
• A Water Accumulator (ACC);
• A Free Cooling Group (GFC) with Ecodry (ED), Fans and 3 Way valve.
ED
TA
L
PUR O
GPP A
PU#1 D
PU#2 PS
SLU#n
PU#3
(n=1..8)
PU#4
LWT
DLU#n
PUn
(N=1..8)
LWT, RWT
TE, TA
Remote SLUn FAN PS, PR
Chillers
COM1 AOUT AIN
DLUn
C USER
O (CO1/CO2)
PUn M
D MOTHER BOARD (SB2) 3
PUR O
U
3W T C OnBoard/
O TelePE
M
2
• Remote Display Panel is connected to remote units via serial bus (RS485) by PEMS
protocol;
• all the functionality available on the local user of the single unit are replicated on the
Remote Display;
• the COM3 port of Remote Display Panel is connected to the first remote unit by means
IS485 adapter inserted on COM2 port (X56) of SB2 master board;
• the COM1 port of Remote Display Panel is connected to Remote Display (CO1 or CO2
selectable with dipswitch#1 of S2).
RS485
Remote
COM3 COM1 Display
(CO1/CO2)
GND
GND
GND
GND
WIRE WIRE
COM3
+
-
GND
REMOTE
L
230 VAC
N 230VAC DISPLAY
PE
EARTH
PANEL
Rev. 3 of 03.04.08
Ref: ZAMPMH02.DOC
7/75
Ref: ZAMPMH02.DOC
Rev. 3 of 03.04.08
2.2 Connection for Serial Linked Unit with Three Serial Gateway
When Three Serial Gateway is used, the system architecture is as follows:
• Micro Panel Heavy is connected to remote units via serial bus (RS485), by PEMS
protocol, using Three Serial Gateway;
• if the communication with GSM modem is disabled, then all the functionality available on
the local user of the single unit are replicated on the Micro Panel Heavy;
• the COM3 port of Micro Panel Heavy is connected to COM1 port (485) of Three Serial
Gateway;
• the COM1 port of Micro Panel Heavy is connected to Remote Display (CO1 or CO2
selectable with dipswitch#1 of S2);
• the COM4 port (485) of Three Serial Gateway is connected to the first remote unit by
means IS485 adapter inserted on COM2 port (X56) of SB2 master board;
RS485
Gateway (M11)
Remote
COM3 COM1 Dispaly
(CO1/CO2)
IS485 on COM2
3. HARDWARE OVERVIEW
• code: SB2;
• dimensions mm. 291X137;
• Power supply: 24 Vac ±10% 50/60Hz, 20 VA protected by 5x20mm fuse 1.6AT;
• Microprocessor Renesas M30624;
• Temperature range 0÷70°C for code 01SB2ZAM0; 0÷60°C for code 01SB2GEO0;
• 10 bit A/D converter on-board;
• 18 DIG-OUT relays;
• 4 ANALOG-OUT
• 20 DIG-IN alarms 115 VAC;
• 12 ANALOG-IN
• serial interface for User board (485)
• serial interface option for Remote Monitoring System / micro programming (With 485 /
232 adapter)
• serial interface for EEV board connection (485)
• serial interface for Power line analyzer (485)
• serial interface for Hardware Key (SPI)
[Gnd, -, +]
On/Off
Set Menu
PROJECT ENGINEERING
REMOTE DISPLAY PANEL
Sw Ver: FRIPMH00.00 Esc
On/Off Set
PROJECT ENGINEERING
REMOTE DISPLAY PANEL
Sw Ver: FRIPMH00.00
Esc Menu
4. PROGRAMMING INSTRUCTION
1) storing in the HKEY the program and all the setup parameters from the BOARD;
2) programming the BOARD from a HKEY;
The HKEY may be used to update software and to program several boards in a short time. In order
to do that, it is necessary to store the new software version on the hardware key and then to
program the controllers.
1. Insert the HKEY in the connector called SPI (between the PRG and SLAVE connectors);
2. Press the MENU key;
3. Scroll the menus by the UP/DOWN keys until “HW KEY” is displayed and then press SET key;
4. Enter the required password which is the same of the MANUFACTURER SETUP menu;
HW KEY PROGRAMMING
Sw BOARD=FRIMGVxx.xx
Sw HKEY =FRIMGVyy.yy
This screen gives information about the software versions stored into the devices:
• The second line displays the software version currently installed on the BOARD;
• The third line displays the software version stored into the HKEY.
If the HKEY has no software stored in it, the next screen will be displayed.
HKEY PROGRAMMING
Sw BOARD=FRIMGVxx.xx
Sw HKEY= HKEY is NEW
If no HKEY is connected, the next screen will be displayed and it is impossible to enter in the next
pages.
HKEY PROGRAMMING
Sw BOARD=FRIMGVxx.xx
No Comm with HKEY
5. Press the UP ARROW key and the next screen will be displayed.
HKEY PROGRAMMING
Setup HK=FRIMGVxx.xx
Chk Setup HK= nnnn
Chk Setup MC= mmmm
6. Press the UP ARROW key and the next screen will be displayed.
HKEY PROGRAMMING
From BOARD to HKEY
Only Setup Parameter
NO
To store all the setup parameters into the HKEY it is necessary to set “YES”.
When the fourth line shows “NO” again, it will mean the data transfer is finished. The data transfer
can take up to 15 seconds.
If the HKEY has no software stored in it, it is impossible to enter here.
7. Press the UP ARROW key and the next screen will be displayed.
HKEY PROGRAMMING
From BOARD to HKEY
Only Program Code
NO
To store only the code of the program into the HKEY it is necessary to set “YES”.
When the fourth line is again “NO”, it will mean that the data transfer is finished. The data transfer
can take up to 15 seconds.
If the HKEY has no software stored in it, it is impossible to enter here.
8. Press the UP ARROW key and the next screen will be displayed.
HKEY PROGRAMMING
From BOARD to HKEY
Setup + Program Code
NO
To store all the setup parameters and the program into the HKEY it is necessary to set “YES”.
When the fourth line is again “NO”, it will mean that the data transfer is finished. The data transfer
can take up to 15 seconds.
If the HKEY has no software stored in it, it is impossible to enter here.
9. Press the UP ARROW key and the next screen will be displayed.
HKEY PROGRAMMING
From HKEY to BOARD!!
Only Setup Parameter
NO
To store only the setup parameters into the BOARD by the HKEY it is necessary to set “YES”. At
the end of the data transfer the microcontroller will reset itself automatically. The data transfer can
take up to 15 seconds.
If the HKEY has no software stored in it, it is impossible to enter here.
10. Press the UP ARROW key and the next screen will be displayed.
HKEY PROGRAMMING
From HKEY to BOARD!!
Only Program Code
NO
To store only the code of the program into the BOARD by the HKEY it is necessary to set “YES”.
At the end of the data transfer the microcontroller will reset itself automatically. The data transfer
can take up to 15 seconds.
If the HKEY has no software stored in it, it is impossible to enter here.
11. Press the UP ARROW key and the next screen will be displayed.
HKEY PROGRAMMING
From HKEY to BOARD!!
Setup + Program Code
NO
To store all the setup parameters and the program code into the BOARD by the HKEY it is
necessary to set “YES”. At the end of the data transfer the microcontroller will reset itself
automatically. The data transfer can take up to 15 seconds.
If the HKEY has no software stored in it, it is impossible to enter here.
REMARK:
- During the data transfer the HKEY must be inserted and the board must be powered (a loss of
power supply during programming of BOARD may need standard programming from PC).
The right working of User Interface required the following settings on Master board (SB2):
NOTES
1) User board CO1 should have line terminated, i.e. TU1 and TD1 jumpers closed, TL1 open;
2) User board CO2 does not need any jumper setting, it is already terminated in factory.
• RH jumpers
All of these jumpers must be positioned on the mA position as follows:
JU14, 16 and 17 jumper PIN 2 and 3 shorted for 4÷20mA operation;
• Be sure that the conducting area around boards support holes (on main, auxiliary and user
boards) are very well grounded to the mounting plates through conducting studs, screws
and spacers.
• Low voltage lines like transducers, serial lines, board power supply must be wired far from
high voltage lines like power and auxiliary;
• Connecting shield to ground minimize shield length (max 10/15 mm).
6. SOFTWARE SPECIFICATIONS
6.1 OPERATIONS
Hardware configuration
from setup
error
SLUn (n=1..8)
Set point CONTROLLER Demand
given by PID ACTUATOR (0-100%)
user Control algorithm
DLUn (n=1..8)
Status
(On/Off)
Actual temperature Required chiller
read by controller power (0÷100%)
The PID controller works with the difference between controlled temperature (LWT if M20=0 or
RWT if M20=1) and the set point (M17) and use the following parameters:
- M18 is the Proportional Band;
- M19 is the Integral Time.
The actuator decides, in base to units enable parameters (M21..M36) and the units run time, the
status (On/Off) of Digital Linked Unit (DLU) and the demand (0-100%) of Serial Linked Unit (SLU).
Example
n.2 SLU are present (M21=50KW, M22=100KW)
n.2 DLU are present (M29=25KW, M30=125KW)
All the others units are not present
Demand (%)
100
DLU#2 On
58.3
50 DLU#1 On
SLU#2 On
16.6
SLU#1 On
Involved parameters:
M107: Sequencer presence:
0= no;
1= yes with two threshold for each unit;
2= yes with four threshold for each unit.
M108: Minimum units capacity used in the sequencer.
MASTER side
If a SLU is not present (i.e. M21..M36=0), then the MASTER not sends any command to the
relative SLU and in the SLU screen is showed “---“.
If a SLU is present (i.e. M21..M36>0) but disabled (i.e. M37..M44=YES), then the MASTER
send the command to stopping the SLAVE. This allows to switch off all the devices of SLU and
disabled the alarms.
If a SLU is present (i.e. M21..M36>0) and enabled (i.e. M37..M44=NO), then the MASTER
send to SLU the Demand computed by actuator and it read the status of alarms in each SLU.
Also, the MASTER checks the following alarm conditions:
o Serial communication with SLU;
o SLU in OFF;
o SLU (DLU) in alarm
SLAVE side
In each SLAVE should be present a setup parameter (Mxx) to enable the Remote Control mode:
If Mxx=0 then the SLU works in Standard Mode computing the unit demand in base to the
actual value of his LWT/RWT and not respond to the remote commands sent from MASTER.
If Mxx=1 then the SLU works in Remote Mode and following operations are executed:
o SLU respond to remote commands sent from MASTER;
o Unit Demand is passed from the MASTER;
o On the screen is showed “REM” instead of setpoint;
o On the 7 segments display is showed “rct” instead the value of controlled temperature;
o If SLU not receive any remote commands for more 30 seconds then all the
compressors are switched off without pump down procedure.
NOTES
1) If the SLU Chillers using ZAM2CH sw then, for the correctly working, it is required to install
ZAM2CH38.00 sw version or later.
2) To check the compatibility with the others SLU chillers, contact Project Engineering.
3) If the SLU Chillers using ZAM2CH39.00 sw (or later) then must be installed ZAMPMH02.00 sw
(or later), otherwise is always showed the warning SLU not in Remote Mode.
Demand limit of plant power is upper limited by user setup parameter M12 when open loop control
is disabled (M13=0).
If M12=100 then demand limit of plant is not upper limited.
If user setup parameter M13 > 0 and the system is ON, then open loop control is enabled and
demand percentage is set to M13 value.
On the main mask the display shows: OPEN LOOP CTR: value %
Press the SET key.
On the main mask the display shows: OPEN LOOP SET: value %
Press UP to increase the value, DOWN to decrease.
To switch to the normal use of UP and DOWN keys (to see the other masks) just press the SET
key.
Remark:
In the open loop mode control all the timing are used as the normal control.
PS
M61+M62
M61-M62
The Setpoint (M61) is upward limited by the value: M66-1-M62 (note: 1 is in PSI).
The Setpoint (M61) is downward limited by the value: M87+1+M62 (note: 1 is in PSI).
Every M65 hours the less used pump is switched on and after (M64-3) seconds the more used
pump is switched off; this allows the pumps hours equalization.
If a pump should be switched on and the one less used is in alarm then the control will switch
on, if available, the less used pump not in alarm.
If a pump switched on go in alarm then it will be switched off and another pump (the less used),
If the pressure PS starts to oscillate with oscillations over the “Neutral Zone” then the pumps
configuration becomes instable.
To avoid the oscillation problem, the control execute the following algorithm:
The Oscillation Protection algorithm is activated after 2 oscillations over the “Neutral Zone”
and, in this case:
o the pumps configuration is blocked to the one with bigger number of the pumps for M67
minutes;
o on the GPP screen is showed the status “OSC-PROT”.
If the Oscillation Protection algorithm is activated and the pressure PS go below the “Neutral
Zone” then a pump will be switched on. The new pumps configuration is blocked until the
pressure PS is into or over the “Neutral Zone”, otherwise another pump (if available) is
switched on.
The Oscillation Protection algorithm is deactivated after M67 minutes after the activation or
when the pressure PS remain into “Neutral Zone” for more M68 minutes.
PS
M61+M62
M61-M62
Free Cooling
Status
ON
OFF
If the probes RWT/TA (used for Free Cooling activation) or probe TE (used for Fan control) go
in underflow or overflow condition then:
- Free cooling control is switched off ;
- Message:” ALARM MASTER XXX TR. OUT OF RANGE”.
100
M78
M79
The first 5 seconds after the Remote Display Panel is switched on, the display shows the
following page with the software version information:
GEOCLIMA
REMOTE DISPLAY PANEL
Sw Ver: FRIPMH00.00
Then, the main page is displayed; on this page, the operator can select the address of the
board to be controlled:
GEOCLIMA
Address Board: 1
Select with UP/DOWN
Confirm with SET
The 3-digit LED display and the second row of the LCD display show the address of the board
WAIT
CONNECTION
IN
PROGRESS
CHILLER CONTROL
If dipswitch#2 (Ref. S2 on SB2 board) is in ON position and no button is pressed for more 15
seconds then, and every 15 seconds, it is showed the following message for 4 seconds:
GEOCLIMA
Press <ESC> 5 seconds
to go to Main Menu
If dipswitch#1 (Ref. S2 on SB2 board) is in OFF position then any message is showed.
COMMUNICATION
ERROR
If the <ESC> button is pressed then the main page is displayed and a new address can be
selected.
Remark: Before connecting the Remote Display Panel to other kind of unit you have to
contact the manufacturer for further instructions.
6.7 ALARMS
Alarms are handled only if the controller is in ‘on’ status. In case of system failure, the controller
displays on the U.I. LCD the relevant error messages complete with the faulty circuit number. Once
the alarm condition has been reset, the error message disappears automatically or, in some
particular cases, remains until the ESC key is pressed (as shown in the display).
When an alarm is present the General Alarm Indication relay (ALL) is activated.
Probes Alarm
If the probes LWT go in underflow (short circuit) or overflow condition (open circuit) then:
• Message: "ALARM MASTER TR. LWT OUT OF RANGE";
• Switch on the general alarm indication relay;
• If the probe is used for temperature control (M20=0) then all the Remote Chillers are
switched off, forcing the Cooling demand to 0%;
• Manual reset through the ESC key.
If the probes RWT go in underflow (short circuit) or overflow condition (open circuit) then:
• Message: "ALARM MASTER TR. RWT OUT OF RANGE";
• Switch on the general alarm indication relay;
• If the probe is used for temperature control (M20=1) then all the Remote Chillers are
switched off, forcing the Cooling demand to 0%;
• The Free Cooling (if enabled) is forced in OFF;
• Manual reset through the ESC key.
If the probe PS go in underflow (short circuit) or overflow condition (open circuit) then:
• Message: "ALARM MASTER TR. PS OUT OF RANGE";
• Switch on the general alarm indication relay;
• All the available pumps of GPP are switched on;
• Manual reset through the ESC key.
Notes
The alarm bypassed when the PS probe is not present (M82=NO).
If the probes TA/TE go in underflow (short circuit) or overflow condition (open circuit) then:
• Message: "ALARM MASTER TR. XXX OUT OF RANGE";
• Switch on the general alarm indication relay;
• The Free Cooling (if enabled) is forced in OFF;
• Manual reset through the ESC key.
Notes
TE probe alarm is bypassed when TE probe is not present (M80=NO).
TA probe alarm is bypassed when TA probe is not present (M81=NO).
If the probe PR go in underflow (short circuit) or overflow condition (open circuit) then:
• Message: "ALARM MASTER TR. PR OUT OF RANGE";
• Switch on the general alarm indication relay;
• Manual reset through the ESC key.
Notes
PR probe alarm is bypassed when PR probe is not present (M83=NO).
If M96 > 99 (i.e. XXYY) then the alarm is bypassed on the first XX seconds after machine switch
on and the delay time for alarm indication is YY seconds (example: if M96=1005 then alarm is
bypassed for 10 seconds after machine switch on and the delay time for alarm indication is 5
seconds).
The alarm is bypassed when M94=0 or when Evaporator water pressure monitoring is disabled
(M93=NO).
If M96 > 99 (i.e. XXYY) then the alarm is bypassed on the first XX seconds after machine switch
on and the delay time for alarm indication is YY seconds (example: if Errore. L'origine riferimento
non è stata trovata.=1005 then alarm is bypassed for 10 seconds after machine switch on and the
delay time for alarm indication is 5 seconds).
The alarm is bypassed when M95=0 or when Evaporator water pressure monitoring is disabled
(M93=NO).
then:
• Message: ” ALARM MASTER SIM NOT READY”;
• All the Remote Chillers are locked, forcing the Cooling demand to -1 (i.e. Chillers locked
from remote controller);
• Pumps, if used, are switched off;
• Free Cooling (if enabled) is forced in OFF;
• Automatic reset 30 second after the end of alarm condition.
PEMS-SMS requests are stopped by the Gateway when IMSI-SIM code is not correct or not any
response from GSM modem (modem not connected to Gateway) for at least 5 minute or GSM
signal level < M104 (signal level is between 0 – 31) for at least 30 minutes.
The alarm not active General alarm Relay (R8) and is not registered on alarm history.
The alarm is bypassed when M106=M105.
GSM signal level value is showed on the fourth row of screen alarm:
- if GSM signal level = -1 then any response from modem (i.e. modem not connected /
without power supply);
- if GSM signal level = -2 then the response from modem is not correct (i.e. modem not
compatible with software or serial errors).
High PS pressure
If the pressure PS > M86 for more than 5 seconds then:
• Message: ”ALARM MASTER HIGH PRESS. PS”;
• Switch on the general alarm indication relay;
• Automatic reset.
Notes
The alarm is bypassed when M86=0.
Low PS pressure
If the pressure PS < M87 for more than M88 seconds and all the pumps not in alarm of GPP are
switched on then:
• Message: ”ALARM MASTER LOW PRESS. PS”;
• Switch on the general alarm indication relay;
• Automatic reset.
Notes
The alarm is bypassed when M87=0.
High PR pressure
If the pressure PR > M90 for more than 5 seconds then:
• Message: ”ALARM MASTER HIGH PRESS. PR”;
• Switch on the general alarm indication relay;
• Automatic reset.
Notes
The alarm is bypassed when M90=0.
Low PR pressure
If the pressure PR < M91 for more than M88 seconds then:
• Message: ”ALARM MASTER LOW PRESS. PR”;
• Switch on the general alarm indication relay;
• Automatic reset.
Notes
The alarm is bypassed when M91=0.
Fans failure
If the digital input FAN_AL is high for more than 1 second:
• Message: ”ALARM MASTER FAN FAILURE”;
• Switch on the general alarm indication relay;
• Automatic reset.
SLAVE
If a slave (SLU) doesn’t receive any remote message for 30 seconds:
• LED increases lamp frequency.
• all the compressors are switched off.
• Automatic reset.
SLU in Alarm
If a Serial Linked Unit #N (N=1..8) is in alarm (status transmitted via serial line) then:
• Message: ”ALARM REMOTE CHILLER SLU#N ALARM ACTIVE”;
• Switch on the general alarm indication relay;
• Automatic reset.
DLU in Alarm
If a Digital Linked Unit #N (N=1..8) is in alarm (status transmitted by digital input DLUN_AL) then:
• Message: ”ALARM REMOTE CHILLER DLU#N ALARM ACTIVE”;
• Switch on the general alarm indication relay;
• Automatic reset.
SLU in OFF
If a Serial Linked Unit #N (N=1..8) is OFF then:
• Message: ”ALARM REMOTE CHILLER SLU#N MACHINE OFF”;
• Switch on the general alarm indication relay;
• Demand percentage is set to 0%;
• Automatic reset.
Notes
The alarm is bypassed when the SLU is locked from master with demand percentage = -1 (i.e.
Low Evaporators Drop or High Evaporators Drop alarms are active).
The controlled temperature (LWT/RWT selected by M20) is continuously displayed on the 3 digit
LED display.
WAIT
and next:
ALARM
POWER OFF
Sw Ver: FRIPMHXX.YY Software version
WAIT 180sec TO START
ALARM
POWER OFF
Sw Ver: FRIPMHXX.YY Software version
PRESS <ON> TO START
• If system On:
CONTROL ON LWT/RWT
RT: xxxxxh Run Time of Unit
TE:xx.x TA:xx.x °C TE=Eco Dry Outlet Temp.
(showed if M80=YES)
TA=Ambient Temp.
(showed if M81=YES)
PS:xx.x PR:xx.x BAR PS=Leaving Water Press.
(showed if M82=YES)
PR=Circulating Pumps Press.
(showed if M83=YES)
If UP key is pressed we show others information about the Serial Linked Unit (SLU):
If UP key is pressed we show others information about the Digital Linked Unit (DLU):
If UP key is pressed and GPP control is enabled (M55=YES) we show others information about the
Process Pumps Group (GPP):
If UP key is pressed and GPR control is enabled (M69=YES) we show others information about the
Circulating Pumps Group (GPR):
If UP key is pressed and Free Cooling control is enabled (M71=YES) we show others information
about the Free Cooling:
If UP key is pressed and Evaporator Water Pressure monitoring is enabled (M93=YES) then we
show others information about the water pressures on the Evaporator:
When an alarm is active, the following page is displayed. When there is more than 1 alarm, the
information is changed every 5 seconds.
ALARM
Compressor N
Description
If the alarm gets off and it needs manual reset, the LCD display shows this page:
ALARM
Compressor N
Description
Press <ESC> to reset
ALARM DESCRIPTION
POWER FAILURE
HIGH WATER TEMP.
LOW WATER LEVEL
TR. LWT OUT OF RANGE
TR. RWT OUT OF RANGE
TR. PS OUT OF RANGE
TR. PR OUT OF RANGE
TR. TA OUT OF RANGE
TR. TE OUT OF RANGE
HIGH WATER TEMP.
LOW WATER LEVEL
HIGH PRESS. PS
LOW PRESS. PS
GPP PUMP1 FAULT
GPP PUMP2 FAULT
GPP PUMP3 FAULT
GPP PUMP4 FAULT
HIGH PRESS. PR
LOW PRESS. PR
GPR PUMP FAULT
FAN FAILURE
LOW EVAP. DROP
HIGH EVAP. DROP
SLU#N SERIAL COMM.
SLU#N ALARM ACTIVE
DLU#N ALARM ACTIVE
SLU#N MACHINE OFF
If a setup parameter is changed (by user or TelePE) then this event is notified on the alarm history
and the description of alarm/event shows:
All parameters are stored in a menu structure with different level of password access.
WARNING
In multi-boards system, if one or more setup parameters are changed then restart the system for
update parameters change.
MEN
USER
SETU
MANUFACTURE
R
I/O
SETU
ALARM
HISTOR
HW
KE
TIMER
SETU
TIME
AND
DATE
• User setup
• Manufacturer setup
• I/O setup
• Alarm history
• Hardware Key
• Timer setup
To enter into every single setup menu to change some parameters, you have to press the SET
key. To store a modified parameter, you have to press the SET key, but if you press the ESC key,
you’ll come back to the previous menu with no storing.
MAIN MENU
Please select the
Menu program
USER SETUP
If the parameter S1 has to be changed, the desired menu will have to be selected and then the
SET key have to be pressed.
In this case will appear:
USER SETUP
Insert Password
Modify 0
By pressing the UP/DOWN ARROW key a password have to be entered; if the entered password
is correct and the SET key is pressed, then it will be shown:
USER SETUP S 1
SET POINT FOR
TEMPERATURE CONTROL
40 °F
By pressing the UP/DOWN ARROW key it’s possible to scroll the different parameters. In this case
“Upper demand limit” is the third parameter so it’s sufficient to press twice the UP ARROW key to
obtain the following screen:
USER SETUP S 3
UPPER DEMAND LIMIT
(100=DISABLED)
100 %
To change the value that’s indicated at the bottom line of the screen, the SET key has to be
pressed and the value will start to blink.
To set a different value the UP/DOWN ARROW key have to be pressed. If, for example, a value of
98% has to be set, the DOWN ARROW key will have to be pressed twice and the following screen
will appear:
USER SETUP S 3
UPPER DEMAND LIMIT
(100=DISABLED)
Modify 98 %
To store the new value the SET key has to be pressed. If the ESC key is pressed, the new value
isn’t stored and the screen will be the following:
USER SETUP S 3
UPPER DEMAND LIMIT
(100=DISABLED)
100 %
By pressing the ESC key the “USER MENU” will appear again.
MAIN MENU
Please select the
Menu program
USER SETUP
MAIN MENU
Please select the
Menu program
USER SETUP
If the string parameter “CALL NUMBER 1 FOR ALARM NOTIFICATION” (ex. M101) has to be
changed, the desired menu will have to be selected (by pressing the UP/DOWN ARROW) and
then the SET key have to be pressed.
In this case will appear:
MANUFACTURER SETUP
Insert Password
Modify 0
By pressing the UP/DOWN ARROW key a password have to be entered; if the entered password
is correct and the SET key is pressed, then it will be shown:
MANUFACTURER M 1
USER PASSWRD
By pressing the UP/DOWN ARROW key it’s possible to scroll the different parameters. In this case
press the UP ARROW key until it is reach M101 parameters and to obtain the following screen:
MANUFACTURER M101
CALL NUMBER 1 FOR
ALARM NOTIFICATION
+3934011223344
To change the string that’s indicated at the bottom line of the screen, the SET key has to be
pressed and the first character of the string will start to blink.
To change first character the UP/DOWN ARROW key have to be pressed. If, for example, the
character “-“ has to be set, the UP ARROW key will have to be pressed twice and the following
screen will appear:
MANUFACTURER M101
CALL NUMBER 1 FOR
ALARM NOTIFICATION
-3934011223344
To store the new value the SET or ON/OFF key has to be pressed. If the ESC key is pressed, the
new value isn’t stored and the screen will be the following:
MANUFACTURER M101
CALL NUMBER 1 FOR
ALARM NOTIFICATION
+3934011223344
If the ON/OFF key is pressed, the second character of the string will start to blink.
To change this character the UP/DOWN ARROW key have to be pressed. To store the new value
the SET or ON/OFF key has to be pressed.
If the ON/OFF key is pressed twice, the fourth character of the string will start to blink.
To change this character the UP/DOWN ARROW key have to be pressed. If, for example, the
character “5“ has to be set, the UP ARROW key will have to be pressed twice and the following
screen will appear:
MANUFACTURER M101
CALL NUMBER 1 FOR
ALARM NOTIFICATION
-3954011223344
MAIN MENU
Please select the
Menu program
MANUFACTURER SETUP
The second and the third line of the display are on the “LCD Display Description” column of the
following list of parameters.
The first line of the display shows the type of setup menu, “USER SETUP” in this case, on the
corner there is the IdCode of the parameter.
The fourth line shows the current value of the displayed parameter.
Use the UP/DOWN ARROW keys to scroll all the parameters. To go back to the previous menu
you have to press the ESC key.
S1 Set point for Temperature Control SET POINT FOR -60.0 90.0 40.0 °F
TEMPERATURE CONTROL
S2 Language: LANGUAGE 0 2 0
0=English, 0=EN 1=DE 2=IT
1=Deutsch,
2=Italian.
S3 Upper demand limit of plant power UPPER DEMAND LIMIT 1 100 100 %
(100 = no upper limit) (100=DISABLED)
S4 Set point for GPP control. SET POINT FOR 0.0 250.0 43.0 PSI
GPP CONTROL
S5 Pumps Only mode activation. PUMPS ONLY MODE NO YES NO
After typing the correct password, the display will show the following mask
MANUFACTURER Myyy
XXXX
XXXX
CURRENT VALUE
The second and the third line of the display are on the “LCD Display Description” column of the
following list of parameters.
The first line of the display shows the type of setup menu, “MANUFACTURER” in this case, on the
corner there is the IdCode of the parameter.
The fourth line shows the current value of the displayed parameter.
Use the UP/DOWN ARROW keys to scroll all the parameters. To go back the previous menu you
have to press the ESC key.
List parameters in MANUFACTURER SETUP (NOTE: °F = °C x 1.8 + 32; PSI = Bar x 14.5):
M53. Minimum time between the insertion of MIN TIME BETWEEN INS 0 300 30 sec
different Remote Units. OF DIFFERENT UNITS
M54. Rotation time for the Remote Units ROTATION TIME FOR 0 250 48 hours
(0=units rotation disabled). UNITS(0=NO ROTATION)
M55. GPP control enable. GPP CONTROL NO YES NO
ENABLE
M56. Pump#1 enable. PUMP#1 NO YES NO
(*) ENABLE
M57. Pump#2 enable. PUMP#2 NO YES NO
(*) ENABLE
M58. Pump#3 enable. PUMP#3 NO YES NO
(*) ENABLE
M59. Pump#4 enable. PUMP#4 NO YES NO
(*) ENABLE
M60. Pumps Only mode activation. PUMPS ONLY MODE NO YES NO
(*)
M61. Set point for GPP control. SET POINT FOR 0.0 250.0 43.0 PSI
GPP CONTROL
M62. Delta pressure for GPP control (i.e. DELTA PRESSURE FOR 0.0 435.0 29.0 PSI/10
neutral band). GPP CONTROL
M63. Calling time to switch on a pump of GPP. CALL TIME FOR 4 255 10 sec
PUMPS SWITCH ON
M64. Calling time to switch off a pump of GPP. CALL TIME FOR 4 255 10 sec
PUMPS SWITCH OFF
M65. Rotation time for the pumps of GPP ROTATION TIME GPP 0 255 48 hours
(0=no rotation). PUMPS(0=NO ROTATION)
M66. Max value of GPP pumps curve. MAX VALUE OF GPP -15 435 54 PSI
PUMPS CURVE
M67. Time of fixed configuration when TIME OF FIXED CONFIG 0 255 240 min
Oscillation Protection is activated. IN OSCILLAT.PROTECT.
NOTE
To extract the serial number of inserted
SIM and store it, press <SET> key and
then <MENU> key.
M104. GSM signal level for low signal alarm. GSM SIGNAL LEVEL FOR 0 31 10
LOW SIGNAL ALARM
(*) = parameter showed when you enter in SERVICE SETUP with service password.
(***) = if the notification of setup parameters changes is enabled (M9=YES) then the new value is
not showed on ALARM HISTORY and on the notification SMS send by SMS protocol.
After typing the correct password, the display will show the following mask
The second and the third line of the display are on the “LCD Display Description” column of the list
of parameters.
The first line of the display shows the type of setup menu, “SERVICE SETUP” in this case, on the
corner there is the IdCode of the parameter.
The fourth line shows the current value of the displayed parameter.
Use the UP/DOWN ARROW keys to scroll all the parameters. To go back the previous menu you
have to press the ESC key.
After typing the correct password, the display will show the following mask
The second and the third line of the display are on the “LCD Display Description” column of the
following list of parameters.
The first line of the display shows the type of setup menu, “I/O SETUP” in this case, on the corner
there is the IdCode of the parameter.
The fourth line shows the current value of the displayed parameter.
Use the UP/DOWN ARROW keys to scroll all the parameters.
I1. Board 1, compensation offset probe S1 BOARD 1 - PROBE S1 -100 100 0 PSI
COMPENSATION OFFSET
I2. Board 1, compensation offset probe D1 BOARD 1 - PROBE D1 -100 100 0 PSI
COMPENSATION OFFSET
I3. Board 1, compensation offset probe O1 BOARD 1 - PROBE O1 -100 100 0 A
COMPENSATION OFFSET
I4. Board 1, compensation offset probe ST1 BOARD 1 - PROBE ST1 -100 100 0 °F
COMPENSATION OFFSET
I5. Board 1, compensation offset probe BOARD 1 - PROBE TOUT -100 100 0 °F
TOUT COMPENSATION OFFSET
I6. Board 1, compensation offset probe S2 BOARD 1 - PROBE S2 -100 100 0 PSI
COMPENSATION OFFSET
I7. Board 1, compensation offset probe D2 BOARD 1 - PROBE D2 -100 100 0 PSI
COMPENSATION OFFSET
I8. Board 1, compensation offset probe O2 BOARD 1 - PROBE O2 -100 100 0 A
COMPENSATION OFFSET
I9. Board 1, compensation offset probe ST2 BOARD 1 - PROBE ST2 -100 100 0 °F
COMPENSATION OFFSET
I10. Board 1, compensation offset probe TIN BOARD 1 - PROBE TIN -100 100 0 °F
COMPENSATION OFFSET
I11. Board 1, compensation offset probe TAE BOARD 1 - PROBE TAE -100 100 0 °F
COMPENSATION OFFSET
I12. Board 1, compensation offset probe RH BOARD 1 - PROBE RH -100 100 0 °F
COMPENSATION OFFSET
I13. Board 1, min. value for 4÷20mA probe S1 BOARD 1 – PROBE S1 -20 750 -7 PSI
MIN VALUE FOR 4÷20mA
NOTES
(1): If the digital input is Normally Closed (NC) then the action related to the input (ex. Alarm) is executed
when the power supply is not present on the input. If the digital input is Normally Open (NO) then the action
related to the input (ex. Alarm) is executed when the power supply is present on the input.
By pressing the UP/DOWN ARROW keys you can screen one at a time the occurred alarms and
their description. To go back to the previous menu you have to press the ESC key.
By pressing together DOWN and ESC keys, the alarm history is cleared.
As the “HW KEY PROGRAMMING” is selected, the manufacturer or service password are
requested to get access to this menu.
After typing the correct password, the display (for example) will show the following mask:
HW KEY PROGRAMMING
Sw BOARD=ZAM2CHxx.xx
Sw HKEY =ZAM2CHyy.yy
For details about the use of the HW KEY see par. 4.2.
To go back to the previous menu you have to press the ESC key.
After typing the correct password, the display will show the following mask
The second and the third line of the display are on the “LCD Display Description” column of the
following list of parameters.
The first line of the display shows the type of setup menu, “TIMER SETUP” in this case, on the
corner there is the IdCode of the parameter.
The fourth line shows the current value of the displayed parameter.
Use the UP/DOWN ARROW keys to scroll all the parameters. To go back to the previous menu
you have to press the ESC key.
To reset the timer value:
- press SET key;
- press MENU key;
- press SET key.
As the TIME AND DATE is selected, the manufacturer or service password is requested to get
access to this menu.
After typing the correct password, the display will show (for example) the following mask:
Cod. Description
After the <SET> button is pressed, then the following message is displayed for 5 seconds:
WAIT
CONNECTION
IN
PROGRESS
CHILLER CONTROL
If dipswitch#2 (Ref. S2 on SB2 board) is in ON position and no button is pressed for more 15
seconds then, and every 15 seconds, it is showed the following message for 4 seconds:
GEOCLIMA
Press <ESC> 5 seconds
to go to Main Menu
If dipswitch#2 (Ref. S2 on SB2 board) is in OFF position then the message is not showed.
COMMUNICATION
ERROR
If the <ESC> button is pressed then the main page is displayed and a new address can be
selected.
Remark: Before connecting the Micro Panel Heavy to other kind of unit you have to contact
the manufacturer for further instructions.
6.10.3 ALARMS
INGLESE TEDESCO ITALIANO
ALARM ALARM ALLARME
Compressor N VERDICHTER N. COMPRESSORE N
or oder o
MASTER MASTER MASTER
Description Beschreibung Description
NO
1. RELAY ROTATION
• all relay will switch on and off with 1 second delay one after the other;
• analog output will swing from 0 to 10 V one after the other;
2. ALL RELAY ON
• all digital output relay are energized;
• analog output are at 10 V
4. ANALOG INPUT
• The screen shows the values of Analog Input channels;
• The values are shown in the following order:
second row: S1, D1, O1, ST1
third row: S2, D2, O2, ST2
fourth row: TAE, RH, TOUT, TIN
5. RTC TEST
• The screen shows the actual parameters of Real Time Clock (RTC)
6. HW KEY TEST
• The screen displays the information about the communication with HKEY external
module.
7. USER TEST
• All led are switched on, display shows “8.8.8.” and every pixel of LCD display is black;
the board will act as a master with address #1, and the user interface is active, but the unit can not
be switched on.
During software test mode all Eeprom parameter can be changed. The analog input values are
shown with no final calibration, so temperatures are measured in ohm (like output of PTC probe)
and pressures are measured in 0-100% from the 4÷20mA of the input range.
The numbers AAA….III are stored in RAM and then they values are lose when machine shut-down
is made.
7. REVISION HISTORY
Rev.0 of 29.08.06 MB – ZAMPMH00.XX
First issue
Rev.1 of 18.12.06 MB – ZAMMPH01.XX
Update description of Remote Chillers Alarms.
Added description of SLU not in Remote Mode alarm.
Update description of Actuator details.
Update description of ANALOG INPUT.
Added description of EVAPORATOR MONITORING.
Added description of Low Evaporators Drop alarm.
Added description of High Evaporators Drop alarm.
Added description of SIM not ready alarm.
Added description of GSM low signal level alarm.
Update description of DATA DISPLAYED.
Added description of DEBUGGING FEATURES.
Added setup parameters M93..M106.
Rev.2 of 23.02.07 MB – ZAMMPH02.XX
Added description of Sequence controller.
Added setup parameters M107, M108.
Update description of SLU control details.
Update description of Connection for Serial Linked Unit with Three Serial Gateway.