05 AIB ME BOQ Rev AF

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 14

AWASH BANK BUKBULA AREA BRANCH AND OFFICE COMPLEX BUILD.

HVAC SYSTEM BILL OF QUANTITY WITH ENGINEERING COST ESTIMATE


UNIT TOTAL
ITEM DESCRIPTION UNIT QTY. PRICE PRICE
HVAC SYSTEM BILL OF QUANTITY
1 VENTILLATION
1.1 SUPPLY & EXTRACTING FANS
1.1.1 AIR SUPPLY FANS AND ACCESSORIES
1.1.1.1 Duct-in mounted fresh air supply fans and accessories

Supply,install,test and commission IN-LINE fresh air


supply fan according to where shown on respective drawings,
to be mounted on slab complete with electrical control
facility, flexible connecton on suction and delivery ends,
washable(cleanable) filter, sound attenuator of the same size
as the duct before and after the fan, min. length of sound
attenuator 1.5x width of duct, isolater switch, support with
vibration isolator and all required mechanical works for
complete installation. Fan shall be rated for project spacific.
Price shall include all works required to install,test and
commission the system.

a) I-SF/01
i) Fan Capacity
Type = DYNAIR or equivalent
Capacity: 364Liter/second
External static head ... 35mmH2O No 9 233,740.00 2,103,660.00

ii) Supply and install noise attenuator of approved quality


after fresh air supply fan all as shown on the respective
drawing and manufacturers instruction.
Q = 364Lit./sec.
No 9 70,905.00 638,145.00

iii) Supply and install approved quality washable filter.


Q =364Lit./sec. No 9 80,620.00 725,580.00

iv) Supply, fix, test and commission intake air louver.The


frame and blades from high quality extruded aluminium
profile.
Type = Air master or Equivalent
Size: 500x400mm No 9 27,405.00 246,645.00

HVAC BILL OF QUANTITY 1


AWASH BANK BUKBULA AREA BRANCH AND OFFICE COMPLEX BUILD.

HVAC SYSTEM BILL OF QUANTITY WITH ENGINEERING COST ESTIMATE


UNIT TOTAL
ITEM DESCRIPTION UNIT QTY. PRICE PRICE

b) I-SF/02
i) Fan Capacity
Type = DYNAIR or equivalent
Capacity: 170Liter/second
External static head ... 30mmH2O No 1 203,435.00 203,435.00

ii) Supply and install noise attenuator of approved quality


after fresh air supply fan all as shown on the respective
drawing and manufacturers instruction.
Q = 170Lit./sec.
No 1 70,905.00 70,905.00

iii) Supply and install approved quality washable filter.


Q =170Lit./sec. No 1 80,620.00 80,620.00

iv) Supply, fix, test and commission intake air louver.The


frame and blades from high quality extruded aluminium
profile.
Type = Air master or Equivalent
Size: 300x300mm No 1 24,795.00 24,795.00

1.1.1.2 ROOF MOUNTED FRESH AIR SUPPLY FAN


Supply, fix, test and comission centrifugal fresh air supply fan
all as shown on the respective drawings and consisting of but
not limited to the following

-Washable filter
-Shall be rated for project specific
-Shall be mounted on vibration isolator

-Electrical control system and with all necessary accessories.


a) FAF/01
Type :……. DYNAIR or equivalent
Capacity : Exhaust air =700Lit./sec.
Exter. Static pressure =350pa. No 1 365,255.00 365,255.00

HVAC BILL OF QUANTITY 2


AWASH BANK BUKBULA AREA BRANCH AND OFFICE COMPLEX BUILD.

HVAC SYSTEM BILL OF QUANTITY WITH ENGINEERING COST ESTIMATE


UNIT TOTAL
ITEM DESCRIPTION UNIT QTY. PRICE PRICE
1.1.2 EXHAUST AIR FANS AND ACCESSORIES
1.1.2.1 Duct-in mounted exhaust air fans and accessories
Supply,install,test and commission IN-LINE exhaust air fan
according to where shown on respective drawings, to be
mounted on slab complete with electrical control facility,
flexible connecton on suction and delivery ends, sound
attenuator of the same size as the duct before and after the
fan, min. length of sound attenuator 1.5x width of duct,
isolater switch, support with vibration isolator and all required
mechanical works for complete installation. Fan shall be rated
for project spacific. Price shall include all works required to
install, test and commission the system.

a) I-EF/01
i) Fan Capacity
Type = DYNAIR or equivalent
Capacity: 100Liter/second
External static head ... 20mmH2O No 1 175,305.00 175,305.00

ii) Supply and install noise attenuator of approved quality


after fresh air supply fan all as shown on the respective
drawing and manufacturers instruction.
Q = 100Lit./sec.
No 1 70,905.00 70,905.00

iii) Supply, fix, test and commission discharge air louver.The


frame and blades from high quality extruded aluminium
profile.
Type = Air master or Equivalent
Size: 250x250mm No 1 23,055.00 23,055.00

1.1.2.2 KITCHEN HOOD WITH ACCESSORIES


a) KITCHEN HOODs
Supply, fix, test and commission stainless steel kitchen hoods
consisting of but not limited to the following

- Washable grease filter


- Condenser water trap
- Hangers / Support structures
- Fire suppresion system
- Canopy light
- Control switch with 20 min. over run

HVAC BILL OF QUANTITY 3


AWASH BANK BUKBULA AREA BRANCH AND OFFICE COMPLEX BUILD.

HVAC SYSTEM BILL OF QUANTITY WITH ENGINEERING COST ESTIMATE


UNIT TOTAL
ITEM DESCRIPTION UNIT QTY. PRICE PRICE
- kitchen fans & accessories which shall be able to resist
temperature
/Listed hoodofsizes
up toand
min.quantity
300ºc are preliminary/

i) Hood……...Size : [3.6x1.8] meters


Type : Single Island canopy No 1 668,885.00 668,885.00

b) EXHAUST FANSs
Supply, fix, test and comission two speed kitchen exhaust fans
consisting of but not limited to the following

- Fire rated (300 degree celcious for two hours)


- Concrete pad with vibration isolator
- Very coarse metal cleanable grease filter

-Equiped with fire rated flexible connection to duct work


- Shall be rated for project specific

a) K-EF/1
Type :……. DYNAIR or equivalent
Capacity : Exhaust air =2500Lit./sec.
Exter. Static pressure =450pa. No 1 567,385.00 567,385.00

1.1.2.3 Twin toilet extracting air fans and accessories


Supply,fix ,test & commission Twin toilet extraction fans
according to where shown on respective drawings,complete
with electrical control facility, isolator switch flexible
connecton on suction and delivery ends, concrete pad with
vibration isolator and all required mechanical works for
complete installation. Fans shall be of the twin type with the
option for alternate operation in time programmable
manner.Fan shall be rated for project spacific. Price shall
include all works required to install,test and commission the
system.

a) TEF/01& 02
Type -DYNAIR or equivalent
Capacity : Exhaust air =1880 liter/second
External static head ... 48mmH2O No 2 433,405.00 866,810.00

b) TEF/03
Type -DYNAIR or equivalent
Capacity : Exhaust air =2025 liter/second
External static head ... 45mmH2O No 1 480,385.00 480,385.00

HVAC BILL OF QUANTITY 4


AWASH BANK BUKBULA AREA BRANCH AND OFFICE COMPLEX BUILD.

HVAC SYSTEM BILL OF QUANTITY WITH ENGINEERING COST ESTIMATE


UNIT TOTAL
ITEM DESCRIPTION UNIT QTY. PRICE PRICE

1.1.2.4 ROOF MOUNTED EXHAUST FAN


Supply, fix, test and comission centrifugal exhaust air fan all
as shown on the respective drawings and consisting of but not
limited to the following

-Shall be rated for project specific


-Shall be mounted on vibration isolator

-Electrical control system and with all necessary accessories.


a)EF/01
Type :……. DYNAIR or equivalent
Capacity : Exhaust air =700Lit./sec.
Exter. Static pressure =250pa. No 1 365,255.00 365,255.00

1.1.2.5 BASEMENT CAR PARKING EXTRACTING FANS


a) Supply, install, test and commission a complete
installation of two speed axial extracting fan unit ,including
all accessories as specified in the munufacturer's instruction
and shown on the drawing & as per recognized/approved fire
safety standards.

- All extracting fans shall fullfill the requirments


stated in BS-7346 - part 2-1990.

- At low speed the extracting fans cover normal


extraction of the parking at low noise level & in case of fire
the fan should run at high speed automaticaly to extract
smoke.
- Electrical supply wire to the extracting fans shall be fire
resistant min. for two hours & electric supply shall be from an
independent protected source as shown on the electrical
design.

-Price shall also incude mounting feet, supports and all


necessary control systems.

- The fans shall be capable of operating min. up to


300ºc for two hours as per BS 5588-part 4: 1998.

HVAC BILL OF QUANTITY 5


AWASH BANK BUKBULA AREA BRANCH AND OFFICE COMPLEX BUILD.

HVAC SYSTEM BILL OF QUANTITY WITH ENGINEERING COST ESTIMATE


UNIT TOTAL
ITEM DESCRIPTION UNIT QTY. PRICE PRICE
a) AXIAL EXTRACTING FAN
i) For 2nd basement
Type :……. DYN AIR or equivalent
Capacity : Extract air Qmax.=11565 liter/sec.
Qmin.=6939 Lit./sec.
Exter. Static pressure Hmax. =42.8mm H2O,
Hmin.10.7mm H2O No 1 1,033,850.00 1,033,850.00

b) INDUCTION JET FANS


Supply, install, test and commission induction jet fans in car
parking complete with CO sensor,over ride switch interlock
with basement extracting fan and all required accessories all
as per munufacturer's instruction and as shown on the
drawing. .

i)Fan capacity
Type :……. DYN AIR or equivalent
Capacity : 1.5/0.75CMS No 8 812,000.00 6,496,000.00

1.2 EXHAUST AIR INLETS AND ACCESSORIES


All exhaust air grilles, registers,diffusers and door grills
(transfer grills) shall be approved quality and located to
ensure the correct air distribution pattern without stagnant
regions or draughts occuring in the room that they are serving.
Price shall include dampers,sealing gaskets and all necessary
accessories and connecting pieces for the proper functioning
of the systems.

1.2.1 Exhuast air grills /Ceiling mounted/


Supply, install, test and comission exhaust air grilles with
uninsulated factory made plenum box. The frame shall be
made from high quality extruded aluminium profile and
standard (30mm) flange width.

i - Capacity =25 &30liter/sec / Eg-1


Size: 150x150mmxmm
Type: air master or equivalent
Model: ARG-HA
Colour: As per the Architect's preference No 231 18,705.00 4,320,855.00

HVAC BILL OF QUANTITY 6


AWASH BANK BUKBULA AREA BRANCH AND OFFICE COMPLEX BUILD.

HVAC SYSTEM BILL OF QUANTITY WITH ENGINEERING COST ESTIMATE


UNIT TOTAL
ITEM DESCRIPTION UNIT QTY. PRICE PRICE
ii - Capacity =50liter/sec / Eg-2
Size: 200 x200mmxmm
Type: air master or equivalent
Model: ARG-HA
Colour: As per the Architect's preference No 2 22,620.00 45,240.00

1.2.2 Supply air registers /Ceiling mounted/


Supply, install, test and comission supply air registers with
uninsulated factory made plenum box. The frame shall be
made from high quality extruded aluminium profile and
standard (30mm) flange width.

i - Capacity =40,42.5,52,60liter/sec / SR-1


Size: 200x200mmxmm
Type: air master or equivalent
Model: ASR-H
Colour: As per the Architect's preference No 68 21,750.00 1,479,000.00

1.2.3 Door grills


Supply, fix, test and commission door grills with double
frame.All frame blades shall be high quality extruded
aluminium profiled construction with the advantages of
corrosion resistance and rigidity./ Dg /.

Coordinate color & size of door grills with the architects/

i - Capacity =75,100liter/sec / Dg-1


Size: 400x200mmxmm
Type: air master or equivalent
Model: ADG-2
Colour: As per the Architect's preference No 43 27,405.00 1,178,415.00

ii- Capacity =225,250liter/sec / Dg-2


Size: 600x300mmxmm
Type: air master or equivalent
Model: ADG-2
Colour: As per the Architect's preference No 6 27,985.00 167,910.00

1.3 INTAKE AND DISCHARGE AIR LOUVERS


Supply, fix, test and commission UL Listed intake air louvers
with cleanable coarse filter complete with all required
accessories.
• Type = Air master or Equivalent
Size : 2500x500mmxmm No 1 41,470.00 41,470.00

HVAC BILL OF QUANTITY 7


AWASH BANK BUKBULA AREA BRANCH AND OFFICE COMPLEX BUILD.

HVAC SYSTEM BILL OF QUANTITY WITH ENGINEERING COST ESTIMATE


UNIT TOTAL
ITEM DESCRIPTION UNIT QTY. PRICE PRICE

1.4 VENTILATION DUCTS


Supply, fix, test and commission galvanized steel air
distribution ducts as where shown on the drawing. All duct
construction,duct thickness and installation shall follow
standards and recommendations given on SMACNA(Sheet
Metal and Air Conditioning Contractors National Association,
INC) and EBCS 11. Provide flexible connction on duct
crossing expansion joint.

Price shall include all the necessary duct fittings,


reinforcement, hot dipped galvanized steel support roads,
brackets,fixing clamps angle,iron walls, vanes, etc and all the
necessary fittings and civil assistance works.

Minimum thickness of rectangular duct construction shall be


as given below:
Duct longer size Sheet metal
(mm) thickness (mm)

Up to 350 mm 0.6 mm
400 to 660 mm 0.7 mm
670 to 910 mm 0.9 mm
920 to 1270 mm 1.0 mm
1280 to 1520 mm 1.3 mm
1530 to 2130 mm 1.5 mm

1.4.1 Exhaust and supply air duct


a) Toilet extract air duct/low velocity
Size: 100 x 100 mmxmm ml 275 1,044.00 287,100.00
150 x 150 mmxmm ml 55 1,566.00 86,130.00
200 x 150 mmxmm ml 100 1,827.00 182,700.00
200 x 200 mmxmm ml 30 2,088.00 62,640.00
250 x 200 mmxmm ml 160 2,349.00 375,840.00
250 x 250 mmxmm ml 35 2,610.00 91,350.00
300 x 300 mmxmm ml 5 3,132.00 15,660.00
350 x 350 mmxmm ml 5 3,654.00 18,270.00
400 x 300 mmxmm ml 5 3,654.00 18,270.00
400 x 400 mmxmm ml 5 4,176.00 20,880.00
450 x 250 mmxmm ml 15 3,654.00 54,810.00
450 x 300 mmxmm ml 15 3,915.00 58,725.00
500 x 350 mmxmm ml 5 4,437.00 22,185.00
500 x 400 mmxmm ml 10 4,698.00 46,980.00

HVAC BILL OF QUANTITY 8


AWASH BANK BUKBULA AREA BRANCH AND OFFICE COMPLEX BUILD.

HVAC SYSTEM BILL OF QUANTITY WITH ENGINEERING COST ESTIMATE


UNIT TOTAL
ITEM DESCRIPTION UNIT QTY. PRICE PRICE
500 x 500 mmxmm ml 10 5,220.00 52,200.00
550 x 500 mmxmm ml 5 5,481.00 27,405.00
600 x 500 mmxmm ml 35 5,742.00 200,970.00
600 x 600 mmxmm ml 10 6,264.00 62,640.00
650 x 600 mmxmm ml 5 6,525.00 32,625.00
700 x 600 mmxmm ml 15 6,786.00 101,790.00
750 x 600 mmxmm ml 20 7,047.00 140,940.00

b) Fresh air duct/low velocity


Size: 150 x 150 mmxmm ml 225 1,566.00 352,350.00
200 x 150 mmxmm ml 125 1,827.00 228,375.00
200 x 200 mmxmm ml 125 2,088.00 261,000.00
250 x 200 mmxmm ml 95 2,349.00 223,155.00
300 x 200 mmxmm ml 75 2,610.00 195,750.00
300 x 250 mmxmm ml 225 2,871.00 645,975.00
450 x 300 mmxmm ml 20 3,915.00 78,300.00

1.4.2 Aluminium flexible duct(uninsulated)


Dia.100mm ml 200 1,450.00 290,000.00
" 150mm ml 80 2,175.00 174,000.00

1.4.4 BLACK STEEL SHEET AIR DUCT

Supply,fabricate, fix,test and commission Kitchen Extract


Ducting - 1.5 mm MS sheet of welded construction with
50mm thick wool Insulation, fire rated.All duct construction
and installation shall follow standards and recommendations
given on SMACNA(Sheet Metal and Air Conditioning
Contractors National Association, INC) and EBCS 11.
a) kitchen extract air duct
Duct size: 400 x 400 mmxmm ml 10 4,176.00 41,760.00
650 x 500 mmxmm ml 75 6,003.00 450,225.00

1.5 DAMPERS AND ACCESSORIES


All dampers and accessories shall be manufactured as per
recognized codes and standard.

HVAC BILL OF QUANTITY 9


AWASH BANK BUKBULA AREA BRANCH AND OFFICE COMPLEX BUILD.

HVAC SYSTEM BILL OF QUANTITY WITH ENGINEERING COST ESTIMATE


UNIT TOTAL
ITEM DESCRIPTION UNIT QTY. PRICE PRICE
1.5.1 Volume Dampers
Supply, fix, test and commission volume control dampers.The
frame shall be constructed from galvanized steel sheet and
coated with aluminium spray.Price shall include all the
necessary accessories and connecting pieces.

I - On extract duct
For duct Size: 100 x 100 mmxmm/ VD No 231 23,635.00 5,459,685.00
200 x 200 mmxmm/ VD No 1 24,795.00 24,795.00
250 x 200 mmxmm/ VD No 23 26,535.00 610,305.00
250 x 250 mmxmm/ VD No 3 26,825.00 80,475.00
400 x 400 mmxmm/ VD No 3 27,695.00 83,085.00
450 x 250 mmxmm/ VD No 2 28,275.00 56,550.00

II - On supply duct
For duct Size: 150 x 150 mmxmm/ VD No 68 25,520.00 1,735,360.00
300 x 200 mmxmm/ VD No 4 27,985.00 111,940.00

1.6 ACCESS HATCHES FOR EQUIPMENTS/ON CEILING


Brand: ELECKTROTEKNIK
Model:AD100-101
600x400 mm Pc 15 92,655.00 1,389,825.00

2 AIR CONDITIONING
2.1 PRE INSULATED DUCT WORK
2.1.1 Fabricate, test and commission Polyisocyanurate Foam
Panel(PAL PIR Panel) with 45kg/m3 density, 20mm thicknes
and protected on both sides with 80microns aluminum facing
embossed with corrosion resistant polyser varnish for internal
installation.Duct works shall be in accordance with SMACNA
provisions.Provide flexible connction on duct crossing
expansion joint.Price shall include all the neccessary
equipments/materials for duct fabrication and installation.

Supply and Return air duct


a) Supply air duct
Size: 450 x 300 mmxmm ml 40 3,915.00 156,600.00

b) Return air duct


Size: 450 x 250 mmxmm ml 35 3,654.00 127,890.00
500 x 300 mmxmm ml 10 4,176.00 41,760.00

HVAC BILL OF QUANTITY 10


AWASH BANK BUKBULA AREA BRANCH AND OFFICE COMPLEX BUILD.

HVAC SYSTEM BILL OF QUANTITY WITH ENGINEERING COST ESTIMATE


UNIT TOTAL
ITEM DESCRIPTION UNIT QTY. PRICE PRICE
2.2 FOUR WAY CEILING DIFFUSERS
All supply and return air ceiling diffusers shall be approved
quality and located to ensure the correct air distribution
pattern without stagnant regions or draughts occuring in the
room that they are serving. Price shall include sealing
gaskets,all necessary accessories and connecting pieces for the
proper functioning of the systems.

2.2.1 Supply air diffusers /Ceiling mounted/


Supply, install, test and comission supply air diffusers. The
frame shall be made from high quality extruded aluminium
profile and standard (33mm) flange width.

i - Capacity =350Liter/sec / 4SAD-1


N.Size: 375x375mmxmm
Type: air master or equivalent
Model: ACD4+D
Colour: As per the Architect's preference No 8 27,985.00 223,880.00

2.2.2 Return air diffusers /Ceiling mounted/


Supply, install, test and comission return air diffusers. The
frame shall be made from high quality extruded aluminium
profile and standard (33mm) flange width.

i - Capacity =260Liter/sec / 4RAD-1


N.Size: 375x375mmxmm
Type: air master or equivalent
Model: ACD4
Colour: As per the Architect's preference No 8 27,985.00 223,880.00

2.2.3 Exhaust air diffusers /Ceiling mounted/


Supply, install, test and comission exhaust air diffusers. The
frame shall be made from high quality extruded aluminium
profile and standard (33mm) flange width.

i - Capacity =350Liter/sec / 4EAD-1


N.Size: 375x375mmxmm
Type: air master or equivalent
Model: ACD4
Colour: As per the Architect's preference No 2 27,985.00 55,970.00

HVAC BILL OF QUANTITY 11


AWASH BANK BUKBULA AREA BRANCH AND OFFICE COMPLEX BUILD.

HVAC SYSTEM BILL OF QUANTITY WITH ENGINEERING COST ESTIMATE


UNIT TOTAL
ITEM DESCRIPTION UNIT QTY. PRICE PRICE
2.3 AIR COOLED CHILLERS/ HYDRONIC MODULE
Supply, fix, test and commision air cooled liquid chillers as
per the manufacturer's specification and instruction including
but not limited to the following accessories.

- Concrete pedestal with vibration isolator


- All valves such as isolation valves, strainers thermometer,
pressure guage, flow switch, flexible connection, one way
valves.

- Chiller shall be with integirate hydraulic module (dual


pump,one duity and one standby)
- Chiller shall be rated for project specific

- Chiller operating with environmental friendly gas


- Chiller shall have interface to building automation system
(BAS)
- Pressurized water supply for chiller

- Pump head and flow rate shall be adequate for the


connected load and shall consider altitude conditions
a ) ACC-1
Type: YORK or equivalent
Cooling capacity =48kw No 1 2,610,000.00 2,610,000.00

HVAC BILL OF QUANTITY 12


AWASH BANK BUKBULA AREA BRANCH AND OFFICE COMPLEX BUILD.

HVAC SYSTEM BILL OF QUANTITY WITH ENGINEERING COST ESTIMATE


UNIT TOTAL
ITEM DESCRIPTION UNIT QTY. PRICE PRICE
2.4 FAN COIL UNITS
With the following requirements, the fan coil unit shall be
complete with fan and chilled water cooling, the cooling shall
be controlled by a room mounted thermostat that will control
a three way valve.The fan coil unit shall be provided with a
galvanized drip tray and condensate shall be piped to the
nearest storm water drain pipe with a smell trap, an isolator
switch shall be provided for each fan coil unit and shall be
installed near the fan coil/max. 0.5meter/ unit to facilitate
maintenance of each unit as required, each fan coil unit shall
be connected to the chilled water system through a supply and
return piping line which shall be branched from a chilled
water supply and return riser , the ceiling type fan coil units
shall be connected to the fresh air supply fan through fresh air
ducting, all services connection to the fan coil units shall be
through flexible joints,strainers shall be provided before each
fan coil units & fan coil unit shall have three speed and there
shall be a possibility for speed selection the fan coil unit shall
be selected at the medium speed. Fan coil unit shall be rated
for project specific.

Price shall include provision of plenum box before and after


the fancoil as necessary, provision of acoustic lining to fancoil
units, provision of shock absorber while installing the hanging
roads, connecting to condensate drain line, connecting to
power line,chilled water line,room theromstat and all required
works for complete installation.The following type, model
and quantity of fan coil units are required on each floor.

2.7.2 Horizontal ducted


i) Type: YORK or equivalent.
Model: RFHP44
Cooling capacities=12.89Kw No 4 68,055.00 272,220.00

HVAC BILL OF QUANTITY 13


AWASH BANK BUKBULA AREA BRANCH AND OFFICE COMPLEX BUILD.

HVAC SYSTEM BILL OF QUANTITY WITH ENGINEERING COST ESTIMATE


UNIT TOTAL
ITEM DESCRIPTION UNIT QTY. PRICE PRICE

2.5 CHILLED WATER SUPPLY PIPES AND VALVES


2.5.1 Supply, test and install insulated ABS[DURA] pipes for
chilled water system/CSWP & CRWP/as where shown on the
drawing.complete with with flexible fittings at expansion
joints,support & all required accessories.

a) In concealed Spaces
Price shall include factory made insulation as per the
technical specification requirment with all accessories.

- With 32mm thick insulation


Dia. 32mm ml 60 2,755.00 165,300.00
" 50mm ml 20 5,075.00 101,500.00
" 63mm ml 6 13,195.00 79,170.00

b) On exposed Spaces
Price shall include factory made insulation including
aluminium cladding on exposed to weather .

- With 50mm thick insulation & aluminum foil gasket


Dia. 63mm ml 20 13,195.00 263,900.00

2.5.2 Valves & accessories


Supply,test,fix and commission approved quality valves &
accessories on chilled water piping before as where shown on
the drawing.
a - Gate Valves /PN-16/
Dia. 25mm No 8 1,030.00 8,240.00

b - Automatic air release valve No 1 6,670.00 6,670.00

2.6 CONDENSATE PIPES


Supply and install uPVC condensate drain pipe with trap as
appropriate as where shown on the drawing, complete with all
necessary accessories & 25mm insulation.

Dia. 25mm ml 50 812.00 40,600.00


TOTAL 41,270,365