Technical features
Power-Supply Voltage supply 85-265 Vac / 50...60 Hz
95-300 Vdc
CVM-C5
Measure Voltage 300 Vac ph-n / 520 Vac ph-ph 50...60 Hz
Current ... /5A & /1 A
MC: ... /250 mA
Sampling rate 64 samples/cycle
Accuracy V, I, kW 0,5% Basic & affordable
Output
Energies
1 built-in digital output
1%
S0 interface
multifunction Multimeter
Configurable to 1000 impulses
by kWh, kVarh, etc.
(24 Vdc max, 50 mA, 5 imp/s,
Max Ton /Toff (configurable))
Input 1 built-in digital input Tariff selection The new generation of CVM
NPN, optoinsulated
Safety Protection Degree Frontal protection: IP51
Terminals: IP20
Class III category / EN 61010
Double-insulated electric shock protection class II
Standards IEC 664, VDE 0110, UL 94, IEC 801, IEC 348,
IEC 571-1, EN 61000-6-3, EN 61000-6-1,
EN 61010-1, CE, according to UL