FusionModule Series FusionModudle2000 Smart Modular Data Center

FusionModule2000
Smart Modular Data Center Soluton
INTRODUCTION
Huawei FusionModule2000 is a new generation smart modular data center
solution, which dedicated to providing customers with simple, efficient, and
reliable data center solutions.
It's a modular-designed, highly integrated solution which comprises power
supply system, cooling system, rack & structure system, cabling system,
management system within a module, meeting the requirements for quick
delivery and on-demand deployment.
Furthermore, the Huawei smart module uses the i3 intelligent management
system to comprehensively improve the reliability and efficiency of power
supply and cooling systems. This significantly improves data center availability,
Standard Dual- row
and O&M efficiency.

APPLICATION SCENARIOS
• The FusionModule2000 uses an air-cooled cooling system and is mainly
applicable to small- and medium-sized data centers. The solution features
simple design and high building adaptability, lowering the requirements of
room height and reconstruction. It meets the data center deployment
requirements of various sectors such as enterprise headquarters or large
branches, bank headquarters and secondary branches, governments, carriers,
education, and healthcare.
FEATURES
Simple
• Modular design,one module one DC,on-demand deployment and flexible
expansion Standard Dual-row Smart
Green Screen Version*
• iCooling intelligent optimization*, reducing the energy consumption of
cooling system by 8% to 15%
• SmartLi Inside* supports Huawei smart lithium batteries deployed in the
module. Compared with traditional lead-acid batteries, footprint is
reduced by 70% under the same load and same backup time
• Wet film humidification*:Compared with traditional electrode humidifiers,
wet film humidifiers reduce energy consumption by 95%
• Industry's first air-cooled smart modular DC PUE test and certification,
The annual average PUE is as low as 1.245 @Beijing
Smart
• iManager: Space, Power, Cooling (SPC) visualization, automatic asset
management simplified O&M.
• 3D view* clear display of key information and alarms about power
distribution and cooling system, automatic management of assets*,
automatic asset tracking, and no manual counting.
• Local 43-inch smart screen * intuitive display of intelligent features,
simplifying O&M
Reliable
• iPower: Visualization of power supply chain, fault auto-locating and auto Simplified Single-row
shutdown for proactive protection;
• SmartLi Inside* :Three-layer BMS ensure the reliability of lithium batteries.
• Innovative intelligent refrigerant leakage detection prevents cooling
capacity decrease or air conditioner breakdown. *OptionalFeatures
FusionModule Series FusionModudle2000 Smart Modular Data Center

SPECIFICATIONS

Item Specifications
Single row (with aisle containment) (L×W×H):
L×2400×2410mm;L×1350×2410mm;L×1600×2300mm
Dimensions
Dual row (with aisle containment) (L×W×H): L×3600×2410mm; L×3400×2410mm;
L×3600×2610mm
Cabinets per module Single row≤24 cabinets; dual row: ≤48 cabinets
Power supply 380/400/415Vac, 50/60Hz, 3Ph+N+PE
Micro Module 125kW (with integrated UPS)/ 145kW (with integrated PDC)/ 310kW (with New main
Max IT load per module
way)/ 235kW (with precision PDC)
Ultra low temperature condition: -40ºC to 45ºC(Need low-temp kit)
Operation condition
T1 condition: -20ºC to 45ºC; T3 condition: -5ºC to 55ºC(Need T3 outdoor unit)
Cable routing Routed in/out through the top of cabinets
Installation Installing on concrete floor or raised floor
2000mm×600/800mm×1200mm; 2000mm×600mm×1100mm;
Dimensions (H×W×D)
2200mm×600/800mm×1200mm

Cabinet Space available 42U/47U


Cabinet Porosity Front and rear doors: hexagonal mesh door design, porosity rate ≥ 75%
Protection level IP20
Cooling capacity 25kW/35kW/46kW
25kW:2000mm×300mm×1100mm;
Air-cooled In-row Dimensions (H×W×D)
35kW:2000mm×600mm×1200mm;
air conditioner 46kW:2000mm×600mm×1200mm;(Simplified Single-row can only support 46kW)
Power supply 380V AC~415V AC 50/60Hz, 3Ph+N+PE
Refrigerant R410A
Input voltage 380/400/415Vac, 50/60Hz, 3Ph+N+PE
Input 250/400A MCCB (single input); 250A/400A ATS (dual input)
Input power factor Full load > 0.99, Half load > 0.98

Output power factor 1.0


30~125kVA:
Integrated UPS IT Load ≤ 120 kW, power modules ≤ 4, the capacity of a single power module is 30kVA
(UPS inside) Rated capacity IT Load > 120 kW, power modules ≥5, the capacity of a single power module is derated to 25kVA
Output IT: 40A/1P×24×2; A/C: 40A or 63A/3P×8; lighting: 10A/1P×3
Efficiency ≥ 96% (Linear Load)
AC SPD 5kA, 8/20μs
Input voltage 380/400/415Vac, 50/60Hz, 3Ph+N+PE

Integrated Input IT: 160/250A MCCB; A/C: 160/250A MCCB (single/dual input)
power Rated input current IT: 160A/250A, Air conditioner: 160A/250A
distribution Output IT: 40A/1P×24×2; A/C: 63A/3P×16; lighting: 10A/1P×3
cabinet (UPS
AC SPD 20kA, 8/20μs
outside)

Precision power Input voltage 380/400/415Vac,50/60Hz,3Ph+N+PE


distribution Input 160/250/400A MCCB (single/dual input)
cabinet (UPS
Output 40A/1P, max 144 routes
outside)
Input voltage 380/400/415Vac,50/60Hz,3Ph+N+PE
Smart busway Input 250/400A MCCB (single input)
(UPS outside) 40/63A 1P (6 branches in one Power Distribution Unit, can be expanded with the length of
Output
cabinet)
Contains 16 battery modules. Two battery strings are connected in parallel, and
Single Lithium battery
cabinet each battery string contains eight battery modules connected in series.
SmartLi Inside Number of Lithium
battery cabinets 2N scenario: ≤ 4 battery cabinets; N+1 scenario: ≤ 2 battery cabinets

Typical backup time The backup time can be 15 minutes, 30 minutes, or 1 hour
FusionModule Series FusionModudle2000 Smart Modular Data Center

Recommended Configurations—UPS Inside the Module

R24 Dual-Row Module with Lithium Batteries in Row

Smart Cooling

Smart Cooling

Smart Cooling
IT IT IT IT IT IT IT IT IT IT IT IT IT

Aisle Containment
Battery cabinet

Battery cabinet
Integrated UPS

Smart Cooling

Smart Cooling
IT IT IT IT IT IT IT IT IT IT IT

R24 Tyapical Layout of the UPS and Lithium


Dual-Row Cabinet Scenario
Batteries in Row

IT Load (kW) Power Supply Redundancy A/C Configuration Battery

30 25kW×2

40 25kW×3

60 35kW×3 In-row (Battery


Integrated UPS N+ 1/ 2N cabinet)/Outsi
80 35kW×4 de Installation

100 46kW×4

125 46kW×5
FusionModule Series FusionModudle2000 Smart Modular Data Center

Recommended Configurations——UPS Outside the Module

UPS Outside the Module(Pricison PDC ) UPS Inside the Module(Smart Busway)
Cooling
Smart
Cooling
Smart

Cooling
Smart

Cooling
Smart
Cooling
Smart

Cooling
Smart
IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT

R24-140kW R24-140kW
(aisle) (aisle)
Cooling
Smart
Cooling
Smart

Cooling
Smart

Cooling
Smart
Cooling
Smart

Cooling
Smart
PDC
Pricision

IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT

R24 Typical Layout of Dual-Row (Precision PDC) R24 Typical Layout of Dual-Row (Smart Busway)

IT Load (kW) IT Power Supply AC Power Supply Redundancy AC Configuration


20 25kW×2

30 35kW×2
Integrated PDC/ Integrated PDC/
40 25kW×3
Precision Power
60 PDC/Smart Distribution 35kW×3
Busway Box
90 35kW×4

120 46kW×4
N+1/2N
145
Smart 46kW×5
160
Busway/Pre
Power Distribution 46kW×6
198 cision PDC
Box
235 Precision PDC 46kW×7

Copyright © Huawei Technologies Co., Ltd. 2021. All rights reserved.