Symbio 700 Acc-Apg001a-En - 06102020

Download as pdf or txt
Download as pdf or txt
You are on page 1of 44

Application Guide

Symbio™ 700 Controller


with Odyssey Split Systems

SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning
equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person
could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that
are attached to the equipment.

June 2020 ACC-APG001A-EN


Introduction
Read this manual thoroughly before operating or servicing this unit.

Warnings, Cautions, and Notices


Safety advisories appear throughout this manual as required. Your personal safety and the
proper operation of this machine depend upon the strict observance of these precautions.

The three types of advisories are defined as follows:

Indicates a potentially hazardous situation which, if not avoided, could result in


WARNING death or serious injury.

Indicates a potentially hazardous situation which, if not avoided, could result in


CAUTION minor or moderate injury. It could also be used to alert against unsafe practices.

Indicates a situation that could result in equipment or property-damage only


NOTICE accidents.

WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury.
All field wiring MUST be performed by qualified personnel. Improperly installed and
grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards,
you MUST follow requirements for field wiring installation and grounding as described in
NEC and your local/state/national electrical codes.

WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death or serious
injury.
Technicians, in order to protect themselves from potential electrical, mechanical, and
chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and
labels, as well as the instructions below:

• Before installing/servicing this unit, technicians M UST put on all PPE required for
the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves,
safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash
clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA
guidelines for proper PPE.
• When working with or around hazardous chemicals, ALWAYS refer to the
appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and
Labelling of Chemicals) guidelines for information on allowable personal exposure
levels, proper respiratory protection and handling instructions.
• If there is a risk of energized electrical contact, arc, or flash, technicians MUST put
on all PPE in accordance with OSHA, NFPA 70E, or other country-specific
requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM
ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER
ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND
EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.

©2020 Trane ACC-APG001A-EN


Introduction

WARNING
Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.

• All Trane personnel must follow the company’s Environmental, Health and Safety
(EHS) policies when performing work such as hot work, electrical, fall protection,
lockout/tagout, refrigerant handling, etc. Where local regulations are more
stringent than these policies, those regulations supersede these policies.
• Non-Trane personnel should always follow local regulations.

Copyright
This document and the information in it are the property of Trane, and may not be used or
reproduced in whole or in part without written permission. Trane reserves the right to revise this
publication at any time, and to make changes to its content without obligation to notify any
person of such revision or change.

Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.

ACC-APG001A-EN 3
Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Additional Documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Symbio 700 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Field Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Unit Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Onboard User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Mobile Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Startup Sequence. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Conventional Thermostat Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Space Temperature Control Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Constant Volume and Multi-Speed Fan Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . 16
Normal Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Supply Fan Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Single Zone Variable Air Volume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
General Support Sequences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Fan Setpoints with VFD-driven Fan Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Compressor Minimum Runtime . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Refrigeration Circuit Management. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Compressor Proof of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Compressor Low Pressure Cutout Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Heat Pump Support Sequences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Heat Pump Switchover Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Demand Defrost Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Evaporator Defrost Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Building Automation System Support Sequences . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Occupancy Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Timed Override . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Supply Air Tempering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Unit Stop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Capacity Limit Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Remote Capacity Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Emergency and Ventilation Override . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Ventilation Override (Future) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Emergency Override. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Service Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27


Service Test Timeout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

4 ACC-APG001A-EN
Table of Contents

Leaving Service Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27


Constant Volume Supply Fan Service Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Multi-Speed Supply Fan Service Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Variable Speed Supply Fan Service Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Device Tracker. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Compressor Proving Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Diagnostic: Compressor X Proving Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Diagnostic: Compressor X Proving Lockout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Diagnostic: Compressor X Contactor Failure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Diagnostics – Low Pressure Cutout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Diagnostic: Circuit X LPC Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Diagnostic: Circuit X LPC Lockout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Diagnostics – Alarm Indicator Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Reset Diagnostic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Power-Up Reset or Exception/Override Mode Transition. . . . . . . . . . . . . . . . . . . . 33
Reset Diagnostic Point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Heat Cool Mode Transition Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Reset Diagnostic Point – Active to Inactive Transition. . . . . . . . . . . . . . . . . . . . . . . 33

Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Unit Communication Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Sensor Fault. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Compressor Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
VFD Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Defrost Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Appendix A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Supply Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Multi-Speed/VFD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Variable Speed/VFD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Compressor Staging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Thermostat Staging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Cooling Only (Electric Heat) – CVZT & VVZT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Heat Pump – CVZT & VVZT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Condenser Fan Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Thermostat, CVZT, & VVZT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
CVZT & VVZT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Diagnostics and Alarm Indicator Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Emergency and Ventilation Override . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

ACC-APG001A-EN 5
Table of Contents

Internal and External Space Setpoint Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

6 ACC-APG001A-EN
Introduction
The Symbio 700 installed on Odyssey split systems is a factory installed and programmed
controller, providing digital control and protection of the equipment.
The Symbio 700 has two model options:
• S t a n d a r d C o n f i g u r a t i o n — provides standard troubleshooting via on-board user interface
(UI) and access to the Symbio Service and Installation mobile app.
• A d v a n c e d C o n f i g u r a t i o n — introduces additional troubleshooting tools and Building
Automation System interface via BACnet® (ANSI/ASHRAE Standard 135-2016) or LonTalk™.
The Symbio 700 offers multiple equipment configuration options regardless of controller model.
The Odyssey split system can be configured as the following system types:
• Conventional Thermostat Control (T-Stat)
• Space Temperature Control Constant Volume (CVZT)
• Space Temperature Control Single Zone Variable Air Volume (VVZT)
These configurations can be used with standard cooling or heat pump systems.
This guide provides information about the configuration, control capabilities and
troubleshooting of the Odyssey system with Symbio 700 controller.

Additional Documentation
• Symbio Service and Installation Quick Start Guide - BAS-SVN043
• Symbio 700 User Guide - BAS-SVU054
• Symbio 700 BACnet Integration Guide - ACC-SVP001
• Symbio 700 LonTalk Integration Guide - ACC-SVP002
• Odyssey General Installation, Operation, and Maintenance Guide - SSA-SVX06
• Odyssey Cooling Installation, Operation, and Maintenance Guide -SS-SVX001
• Odyssey Heat Pump Installation, Operation, and Maintenance Guide - SSP-SVX001

ACC-APG001A-EN 7
Symbio 700 Overview
Field Connection
The Symbio 700 controller optimizes inputs and outputs (I/O) for multiple applications. For initial
installation of an Odyssey with Symbio 700, the field landed inputs are outlined below.
Figure 1. Symbio 700 Field Connections

Table 1. Field Connections


Connector Function Pin # Signal

1 24VAC
Demand Shed/Demand Limit
J16 Demand Shed/Demand Limit
Connection 2
Input
1 BACnet +

BACnet Communication 2 BACnet -


J17
Connections 3 BACnet +

4 BACnet -

Equipment Shutdown Input 1 24VAC


J18
Connections 2 Equipment Shutdown Input

1 Zone Temperature

2 GND

3 Cool Setpoint

J19 Zone Sensor Connections 4 Mode

5 Heat Setpoint

6 GND

7 24VAC

1 24VAC
J20 Occupancy Connections
2 Occupancy Switch

8 ACC-APG001A-EN
Symbio 700 Overview

Table 1. Field Connections (continued)


Connector Function Pin # Signal

1 24VAC

2 Y1

3 W1/O

4 G

J21 Thermostat Connections 5 W2

6 Y2

7 X2

8 1.5K Ohms Pull-down

9 GND

1 24Vdc Out

J22 CO2 2 CO2 In

3 Common

1 24Vdc Out

J23 Space Humidity 2 Space Humidity

3 Common

Unit Configuration
The Odyssey system can be configured via an onboard user interface or via the Symbio Service
and Installation mobile app.

Onboard User Interface


The onboard user interface provides a 2 x 16 Backlit LCD display and navigational buttons. This
allows the user to view status, configure, and troubleshoot the unit without additional tools.
Figure 2. Symbio 700 Onboard User Interface

The interface provides an intuitive menu structure: alarms, status, service, settings, and utilities.
Configuration of the unit is accomplished under the utilities menu item. A complete list of
functions is outlined in the Symbio 700 User Guide - BAS-SVU054.

ACC-APG001A-EN 9
Symbio 700 Overview

To configure the unit, navigate to the utilities menu and press “Enter”. Once in the utilities menu
the user has additional submenu options. This allows the user to navigate and configure the
appropriate setting quickly and easily.

Mobile Application
The Trane Symbio™ Service and Installation mobile app is required to setup, edit, and confirm
the communication protocol and associated settings.
The free download of Trane Symbio Service and Installation mobile app is available on the App
Store® for iOS, and on Google Play® for Android™.
Figure 3. Trane Symbio™ Service and Installation mobile app

Bluetooth Pairing
Quick Connection Instructions
Follow these instructions to quickly connect the mobile app to the Symbio 700 controller:

Connecting to the Symbio 700 controller


1. Enable B l u e t o o t h on your smart device.

2. Press on Symbio 700 keyboard/display to turn on Bluetooth.


3. Confirm the status of Bluetooth communications.

10 ACC-APG001A-EN
Symbio 700 Overview

Blue LED Display Description

Off NOT CONNECTED Bluetooth Off

Blinking WAITING... Bluetooth On — Not Paired


Press for On/Off
Bluetooth On — Connected/
On Solid CONNECTED
Paired

Figure 4. Symbio 700 Bluetooth status

4. Start the mobile app on your smart device.


5. On the login screen, press S k i p in the lower right-hand corner of the screen. Or Trane
personnel can login using their Trane Connect username and password.
6. On the Unit List page, select the Symbio 700 controller that you want to pair with. If the
controller is not listed, press the refresh arrow in the upper right-hand corner of the screen.
7. When prompted, pair the app to the Symbio 700 controller. A popup message displays a 6-
digit random number. The same number is shown on the display of the Symbio 700
controller until the pairing is complete, allowing the user to confirm connection to the
intended controller.
Figure 5. Bluetooth pairing

8. P r e s s on the Symbio 700 on-board keyboard/display to complete the connection.

ACC-APG001A-EN 11
Symbio 700 Overview

I m p o r t a n t : To keep the list of previously-connected devices manageable, the Bluetooth smart


devices list is limited to 10 devices. When 10 or more Bluetooth devices are defined
on the smart device, connection to the Symbio 700 controller is not allowed.
• i O S d e v i c e s - delete any unused devices until there are less than 10 items.
• A n d r o i d d e v i c e s - the devices list is automatically limited to 10 items.
The Symbio Installation and Service tool is required to view and configure the following:
• Building Automation System configuration (Advanced Controller Configuration)
– BACnet over Zigbee® (Air-Fi™ Wireless)
– BACnet IP (Internet Protocol)
– BACnet MS/TP
– LonTalk
• Historical Alarms
• Firmware Updates
• Backup & Restore
For more detailed information on the Symbio Service and Installation Mobile Application, refer to
the Quick Start Guide for Symbio Service and Installation - BAS-SVN043.

12 ACC-APG001A-EN
Startup Sequence
Under normal conditions, the Symbio 700 will startup over approximately 60 seconds once
power is applied to the system. During this process, the controller checks that a valid system
configuration is present and proceeds to normal control operation. After startup, the system will
begin to respond to operational requests.

ACC-APG001A-EN 13
Conventional Thermostat Sequence of Operation
When the Odyssey system is configured to operate with a conventional thermostat, the controller
provides protection for the system (see General Support Sequence section) and continues to
provide insight to operating conditions. A conventional thermostat can be applied with constant
volume cooling only, heat pump, and single zone 2-speed fan configured systems. While not
recommended, a conventional thermostat can be applied to single zone variable volume
configured systems, but the system is limited to staged fan control instead of a fully variable
sequence.
When under conventional thermostat control, the equipment responds directly to operating
requests from the thermostat device. Each thermostat input corresponds to a specific unit
function, as described in the following tables. Equipment protection functions and compressor
minimum on/off timers remain in-control, even when under conventional thermostat control.
Table 2. Cooling only/electric heat systems
Inputs Outputs
Supply Compres- Auxiliary
Supply Heat Cool
Fan On/ sor Cool Heat
X Y1 Y2 W1/O W2 G Fan Speed Mode
Off Stage Stage
Request Status
Request Request Request
NA OPEN OPEN OPEN OPEN CLOSED ON Min None None Fan Only

NA OPEN OPEN CLOSED OPEN X ON Max None Stage 1 Heat

NA OPEN OPEN X CLOSED X ON Max None Full Stage Heat

NA CLOSED OPEN OPEN OPEN X ON Min Stage 1 None Cool

NA OPEN CLOSED OPEN OPEN X ON Min Stage 1 None Cool

NA CLOSED CLOSED OPEN OPEN X ON Max Full Stage None Cool

NA X X X X X OFF 0 None None OFF

X=ignored by controller

14 ACC-APG001A-EN
Table 3. Heat pump systems
Inputs Outputs
Supply Compres- Compres- Auxiliary
Supply Heat Cool
Fan On/ sor Cool sor Heat Heat
X Y1 Y2 W1/O W2 G Fan Speed Mode
Off Stage Stage Stage
Request Status
Request Request Request Request

ACC-APG001A-EN
CLOSED OPEN OPEN OPEN OPEN X ON Max None None Full Stage Em Heat

OPEN CLOSED OPEN OPEN OPEN X ON Max None Stage 1 None Heat

OPEN OPEN CLOSED OPEN OPEN X ON Max None Stage 1 None Heat

OPEN CLOSED CLOSED OPEN OPEN X ON Max None Full Stage None Heat

OPEN CLOSED OPEN OPEN CLOSED X ON Max None Stage 1 Full Stage Heat

OPEN OPEN CLOSED OPEN CLOSED X ON Max None Stage 1 Full Stage Heat

OPEN CLOSED CLOSED OPEN CLOSED X ON Max None Full Stage Full Stage Heat

OPEN X X OPEN CLOSED X ON Max None None Full Stage Heat

OPEN OPEN OPEN CLOSED OPEN OPEN OFF 0 None None None Cool

OPEN CLOSED OPEN CLOSED OPEN X ON Min Stage 1 None None Cool

OPEN OPEN CLOSED CLOSED OPEN X ON Min Stage 1 None None Cool

OPEN CLOSED CLOSED CLOSED OPEN X ON Max Full Stage None None Cool

OPEN OPEN OPEN X OPEN CLOSED ON Min None None None Fan Only

X X X X X X OFF 0 None None None OFF

X=ignored by controller
Conventional Thermostat Sequence of Operation

15
Space Temperature Control Sequence of Operation
Constant Volume and Multi-Speed Fan Configuration
Normal Operation
The Symbio 700 has a single-loop (space temperature only) control sequence. The sequence is
PI-based (proportional, integral) and strives to maintain space temperature within 1F of the active
cooling and heating setpoints.
• When Space Temperature Active > Space Temp Cooling Setpoint Status, the algorithm
calculates a need for cooling capacity to be energized.
• When Space Temperature Active < Space Temp Heating Setpoint Status, the algorithm
calculates a need for heating capacity to be energized.
• When Space Temp Heating Setpoint Status ≤ Space Temperature Active ≤ Space Temp
Cooling Setpoint Status:
– The algorithm calculates a reduction in need for any active cooling or heating capacity if
ON.
– If no cooling or heating capacity is active, cooling and heating capacity remains inactive.

Supply Fan Control


The supply fan is controlled “ON” 5 seconds before heating or cooling capacity is energized.
When heating or cooling capacity is de-energized, a supply fan off delay is applied based on
active capacity. For single-speed supply fan configured systems, the supply fan is controlled
“ON” during all cooling and heating sequences.
For multi-speed supply fan configured systems, the fan operates per the following:
• Low speed when the supply fan is ON without active capacity (unless ON due to an override
function)
• Low speed when the unit is operating at its minimum cooling stage
• High speed when the unit is operating at its maximum cooling stage or while any heating
stages are active.

16 ACC-APG001A-EN
Space Temperature Control Sequence of Operation

Figure 6. Multi-speed fan sequence of operation

Single Zone Variable Air Volume


When configured for VVZT (also known as SZVAV) control, the sequence is only applicable when
the following are true; otherwise, the CVZT sequence is leveraged:
• When Occupancy Status is Occupied and
• When Supply Fan Configuration Status is Continuous and
• When Discharge Air Temperature sensor is not in an Alarm state and
• The unit is operating under a cooling demand (VVZT heating is not applicable with staged
heat for Odyssey)
The sequence is PI-based (proportional, integral) and strives to maintain space temperature
within 1F of the Active Cooling and Heating setpoints.
When Space Temperature Active > Space Temp Cooling Setpoint status, the algorithm calculates
a need for cooling capacity to be energized. A discharge air temperature setpoint calculates
lower to determine proper compressor staging needs. The minimum value of this calculated
setpoint for temperature control can be adjusted by the Discharge Air Temperature Minimum
Cool Limit setpoint.
When Space Temperature Active < Space Temp Cooling Setpoint status, the algorithm calculates
a reduction in need for cooling capacity to be energized. A discharge air temperature setpoint
calculates higher to determine proper compressor staging needs. The maximum value of this
calculated setpoint for temperature control can be adjusted by the Discharge Air Temperature
Maximum Cool Limit setpoint.
Different from the CVZT sequence, compressors are staged to maintain the discharge air
temperature at the Discharge Air Temperature Setpoint Active setpoint.

VVZT DAT Control Mode


With the Symbio 700 VVZT control sequence, the end user can choose to use the internally
derived Discharge Air Temperature Setpoint Active or to override the value with their own.

ACC-APG001A-EN 17
Space Temperature Control Sequence of Operation

If the VVZT DAT Control Mode – Active point is set to "Auto", the VVZT control algorithm will use
the internally derived Discharge Air Temperature Setpoint Active, as described above, for all
cooling capacity output control.
If the VVZT DAT Control Mode – Active point is set to "Manual", the VVZT control algorithm will
use the Discharge Air Cooling Setpoint (Target) – Active as upper limit for the Discharge Air
Temperature Setpoint calculation. Typically this is set to a low value (i.e 50-55F) to drive longer
compressor runtimes. When this override is active, if the space temperature is 2° F below the
Space Temp Cooling Setpoint Status value or 1° F above the Space Temp Heating Setpoint
Status value, the controller will pause the override sequence until the space temperature
recovers to above the Space Temp Cooling Setpoint status.

Supply Fan Control


For the VVZT control sequence to be active, the Supply Fan Configuration Status must be ON/
Continuous.
The fan speed is continuously variable on VVZT systems. The fan remains at minimum speed
(based on active compressor stages) until the space demand requires additional airflow.
All heating is accomplished with the CVZT control sequence, and the fan is controlled at
maximum speed.
Figure 7. Supply fan sequence of operation

18 ACC-APG001A-EN
General Support Sequences
Fan Setpoints with VFD-driven Fan Types
When a system is equipped with a VFD, the minimum and maximum VFD parameters can be
adjusted to tune the airflow to meet the application requirements.
In addition to this, the Symbio 700 supports setpoints that can adjust airflow as needed:
• Supply Fan Maximum Speed Setpoint
– Range: 67-100%
– Operation: This setpoint “trims” the maximum fan speed, based on the configured
maximum VFD speed
– Example: VFD Max = 60Hz
• Supply Fan Maximum Speed Setpoint @ 75% yields a maximum of 45Hz VFD output.
• Effective VFD Max (to be used in Supply Fan Minimum Speed Setpoint application)
will be set to 45Hz
• Supply Fan Minimum Speed Setpoint
– Range: 0-100%
– Operation: 0-100% over minimum to effective maximum VFD configured fan speed
– Example: VFD Min = 30Hz, Effective VFD Max = 60Hz
• Supply Fan Minimum Speed Setpoint @ 50% yields 45Hz VFD output.
• Minimum and Maximum Speed Setpoints interact to ensure that the minimum defined fan
speed at a given equipment operating condition is maintained.

Compressor Minimum Runtime


Under all normal running conditions, a 3–minute minimum ON and OFF timer is maintained for
each compressor. Once a compressor is turned ON, it remains on for a minimum of 3 minutes.
Once a compressor is turned OFF, it remains off for a minimum of 3 minutes. System overrides
that require immediate shutdown of the equipment, test modes, and compressor diagnostics/
protection functions can override these 3–minute timers. However for normal temperature and
thermostatic-based control, these minimum ON/OFF timers are maintained.

Refrigeration Circuit Management


There are two refrigeration configurations that the controller will use to determine proper
response to refrigeration system faults:
• When the unit is configured with a M a n i f o l d refrigeration system, if any compressor
protection device or function trips for a given compressor, all compressors associated with
the circuit on which the protection device or functions trips will be commanded to OFF.
• When the unit is configured with an I n d e p e n d e n t refrigeration system, if any compressor
protection device or function trips, for a given compressor, only the compressor associated
with the protection device or function that tripped will be commanded to OFF.

Compressor Proof of Operation


For each compressor. a Compressor Proving binary input is used to monitor the state of an
auxiliary switch that is used to indicate compressor motor contactor status. Under normal
operation, detected operation indicates that all safety devices within the compressor safety
circuit are in their normal state. The switch operates as OPEN when the compressor motor is OFF
and CLOSED when the compressor motor is ON.
Refer to the Diagnostics section below for specific diagnostics that are generated based on the
Compressor Proving signals.

ACC-APG001A-EN 19
General Support Sequences

Compressor Low Pressure Cutout Control


For each compressor/circuit, a normally CLOSED low pressure cutout input is monitored for
equipment protection on the Symbio 700. When a low pressure event is active, the input
becomes OPEN and diagnostics are generated as described below. Refer to the Diagnostics
section below for specific diagnostics that are generated based on the circuit Low Pressure
Cutout inputs.

20 ACC-APG001A-EN
Heat Pump Support Sequences
Heat Pump Switchover Valve
The Switchover Valve function is only applicable to Heat Pump units. Depending on the
refrigeration system configuration for a unit, it may have one or two switchover valves.
Additionally, some units with two switchover valves could control each valve independently
while others will control in tandem.
In normal unit operation, the Unit Mode will determine the operation of the switchover valve.
Unit Mode COOL will turn the switchover valve ON while Unit Mode HEAT will turn the
switchover valve OFF.
If the unit is in active Heat Pump Heating (switchover valve is OFF) and then enters defrost, the
switchover valve will be turned ON for the duration of defrost. When leaving active defrost, the
switchover valve transition to OFF is delayed 5 seconds.

Demand Defrost Control


There are two schemes in common usage for heat pump outdoor coil defrosting: Demand
Defrost and time temperature defrost. Demand Defrost is more efficient because defrost cycles
are initiated only when necessary, compared with initiation based on operating time below the
threshold temperature.
Outdoor coil defrosting occurs only when operating in heating mode with outdoor ambient
temperature below 52° F and the outdoor coil temperature below 33° F. The first defrost cycle
after power-up is initiated based on operating time at the required conditions. Shortly after
completion of the defrost cycle, the temperature difference between the outdoor coil and outdoor
air is calculated and is used as an indicator of unit performance at dry coil conditions.
Over time, as moisture and frost accumulate on the coil, the coil temperature will drop,
increasing the temperature difference. When the temperature difference reaches 1.8 times the
dry coil temperature differential (ΔT), a defrost cycle is initiated. While defrosting, the reversing
valve is in the cooling position, outdoor fans are off, and the compressors continue to operate.
The defrost cycle is terminated when the coil temperature rises high enough to indicate that the
frost has been eliminated. Termination of the defrost cycle includes a soft start delay. At the end
of each defrost cycle, the outdoor fan comes on 5 seconds before the reversing valve is de-
energized. This reduces stress on the compressor and makes for a quieter defrost.
Figure 8. Typical Demand Defrost cycle

During the defrost cycle, the Switchover Valve is turned ON, the Condenser Fan is turned OFF,
and auxiliary heat is turned ON regardless of their prior operating status while maintaining

ACC-APG001A-EN 21
Heat Pump Support Sequences

compressor operation. The defrost cycle is terminated based on the defrost termination
temperature calculation using the outdoor temperature (ODT) +47°F. The defrost termination
temperature (DTT) will be limited between 57° F and 72° F.

Evaporator Defrost Control


To prevent frost build-up on the indoor coil during low ambient conditions, compressor
operation is monitored and controlled accordingly, relative to outdoor air temperature.
Evaporator Defrost Control can be initiated through two means, based on configuration.
• If configured for Evaporator Defrost Control Enabled:
– When the unit is operating in a “Cool” mode with a valid Outdoor Air Temperature, the
EDC function will keep track of the amount of time that at least one compressor in the unit
is commanded ON and the Outdoor Air Temperature Active is less than the low ambient
temperature defined in table 3. If the Accumulated Compressor On Time reaches 10
minutes, the EDC function will cause the Compressor Output(s) to de-energize for three
minutes. The supply fan continues to operate during this three-minute interval at 100%
capacity. After the three-minute EDC timer has expired, the EDC function is ended and
compressors are allowed to operate as requested by the algorithm.
– Low Ambient Temperature Sepoints:
• Single Compressor Systems: 55° F
• Multi-Compressor Systems: 40° F
• If configured for FroStat Installed:
– A FroStat input can also be used to directly request the Evaporator Defrost Control
function
– When the unit is running in an effective “Cool” mode, the FroStat input will directly
control the FroStat diagnostic. If the FroStat input CLOSES, the diagnostic will be
annunciated.
– When the unit is running in an effective “Heat” mode, and the Refrigeration System ==
Heat Pump, the FroStat diagnostic will be controlled “Inactive” until the following are
true:
• FroStat input is CLOSED
• One or More Compressors have been active for Heat Pump Heating for more than 30
seconds.
Once the above two conditions are met, the FroStat Diagnostic will become Active.
– The FroStat diagnostic is an Auto-Reset diagnostic such that it will be reset when the
FroStat input is OPEN in either effecting unit mode.
– If the FroStat diagnostic becomes active, the Compressor Output(s) will de-energize until
the FroStat diagnostic is cleared. The supply fan continues to operate during the FroStat
diagnostic, so long as it is still requested by a heating or cooling function.
FroStat and Evaporator Defrost Control can both be configured on a unit, although in most cases,
only one should be necessary.

22 ACC-APG001A-EN
Building Automation System Support Sequences
Occupancy Mode
During expected occupied periods, the system will control to the user selected cooling and
heating setpoints.
• The unoccupied setpoint temperatures are often adjusted higher for cooling (setup) and
lower for heating (setback) to reduce building operating cost.
• Regardless of how the (occupied) fan mode is set, the supply fan mode is forced to AUTO
during unoccupied periods to reduce supply fan operating costs.
There are two mechanisms available to control when units should switch between occupied and
unoccupied modes:
• Building controllers provide signals to the unit to request occupied or unoccupied operation.
Time-of-day scheduling within building controllers typically determine when the switching
should occur.
• Stand Alone Unoccupied control is initiated by a contact closure that causes the unit to begin
unoccupied control. In this mode, the controller will use the Unoccupied Cooling and Heating
setpoints to determine capacity control needs. Stand Alone Unoccupied control is only
applicable when the unit is not being controlled by a conventional thermostat interface.

Timed Override
Exceptions to the time-of-day scheduling are required when unusual or difficult to schedule
events cause a space to become occupied during a scheduled unoccupied period. The Timed
Override function provides a mechanism for an occupant to signal the system that the space is
actually occupied and override the time-of-day schedule to provide occupied control for some
limited time period. It also provides a mechanism to return the system to unoccupied mode
when the space is no longer occupied.
There are two methods of requesting or terminating timed override on a Symbio 700 control
system:
• BAS
– Timed Override Request value can be set to 3 discrete values:
• I d l e [ 1 ] — Controller will not override Unoccupied Mode.
• O n [ 2 ] — When the value is changed from Idle to On, the controller overrides
Unoccupied Mode and the unit operates in Occupied Mode. The Occupied Bypass
Timer and the Timed Override Timer is Active is set to ‘Active’. The controller remains
in Timed Override for the duration of the Occupied Bypass Time.
• C a n c e l [ 3 ] — When value is changed from On to Cancel, the unit’s unoccupied status
is no longer overridden and the Occupied Bypass Timer will be set to 0.
• Zone Sensor Initiate/Terminate buttons – Some zone sensors have a Timed Override Initiate
and Terminate buttons.
When Timed Override is initiated by any of the above methods, the controller starts a timer using
the user selected Occupied Bypass Time to control the duration of the Timed Override event. The
range for Occupied Bypass Time is 0-240 minutes with a default of 120 minutes.
When the unit is operating in Occupied Bypass mode, the Occupied Bypass Timer duration can
be extended by initiating a Timed Override Request again. This extends the Occupied Bypass
Timer duration by the value of the user selected Occupied Bypass Time.
When Timed Override is terminated by any of the above methods, the controller will exit
Occupied Bypass and will again begin to use unoccupied control setpoints.

Supply Air Tempering


If the Supply Air Tempering function is configured and the Discharge Air Temperature local
sensor is valid, the Space Temperature Control algorithm manages the Supply Air Tempering

ACC-APG001A-EN 23
Building Automation System Support Sequences

function to prevent excessively cold discharge air from being supplied from the unit. The
sequence for VVZT systems are consistent with CVZT systems, utilizing single-speed, and full
airflow operation.
Supply Air Tempering is not applicable when a Conventional TStat is configured as the Space
Controller.
The following requirements must be met to allow Supply Air Tempering on a Staged Heat unit:
• The supply fan is ON.
• The unit is in Occupied mode.
• The unit is in any heating mode, including Heat, Emergency Heat, Morning Warmup, Max
Heat but is not actively heating OR
• The unit is in any cooling mode except night purge, but not actively cooling and cooling
capacity has been OFF for 5 minutes.
If the discharge air temperature drops to the Discharge Air Temperature Minimum Cool Limit -
Active and the Space Temperature is less than the Active Space Temp Cooling Setpoint Status –
0.5°F and if there are no stages of heat on, the Supply Air Tempering function will bring ON one
stage of available staged auxiliary heat.
N o t e : Heat Pump units will energize 1 stage of auxiliary Heat in order to meet the Supply Air
Tempering request; compressor-based heating will not be used to satisfy Supply Air
Tempering.
Once Supply Air Tempering is active, the stage of heat will be turned OFF if the Discharge Air
Temperature rises to 10°F ABOVE the Discharge Air Temperature Minimum Cool Limit - Active,
or the Space Temperature rises to the Space Temp Cooling Setpoint Status. Additionally, if the
Space Heat Control function determines that 1 or more stages of Heat are required to meet the
Space Temp Heating Setpoint Status, Tempering will be discontinued and the unit will stage
heating to meet the current space demand.

Unit Stop
The Unit Stop feature allows for immediate shutdown of all devices in the equipment when
initiated. When a Unit Stop request is received, the following actions are taken:
• All equipment control binary outputs are de-energized
– Indoor fan
– Compressors
– Condenser fans
– Unloader solenoids
– Heat stages
• All equipment control analog outputs are set to their minimum/off command values.
• All communicating devices, such as Supply fan VFD, are commanded to their Off state.
• All control algorithms are initialized to their normal startup values and held until the stop
request is released.
The Unit Stop request can be initiated from the following sources:
• Unit Stop Command
• Equipment Shutdown Input
• Emergency Override BAS
• Phase Monitor
If a Unit Stop is initiated, the source of the Unit Stop can be determined by the Unit Stop Source
Point and other status/diagnostic points.

Capacity Limit Control


There are three sources for capacity limitation provided by the Symbio700:

24 ACC-APG001A-EN
Building Automation System Support Sequences

• BAS Lockout Function


• BAS Capacity Enable function
• Demand Limit Function
Depending on how the controller application is configured, different portions of the capacity limit
control can be active at any time. Because of this, a priority scheme is built into the capacity
limitation function.
If cooling is allowed from “Cooling Lockout BAS – Active” and if Demand Management is
configured for Demand Limit, “Cooling Demand Limit Capacity Enable Setpoint – Active” or
“Heating Demand Limit Capacity Enable Setpoint – Active” will be used to limit the unit capacity
if it is active and “Cooling Capacity Enable – Active” is not limiting capacity. If “Cooling Capacity
Enable – Active” is set to a value less than 100, “Cooling Capacity Enable – Active” has priority.
For capacity limiting values for user selected values, refer to the Appendix section of this
document.

Remote Capacity Control


The Symbio 700 controls support the Remote Capacity Control function, which allows a user to
directly control the unit capacity rather than allowing the internal algorithm to provide control.
The following features/functions can be requested directly via points, rather than relying on
internal temperature or thermostat control sequences:
• Supply Fan Speed
• Cooling Capacity
• Heating Capacity
For Thermostat Controlled equipment, the Thermostat Inputs must be "OPEN" i.e. requesting
"OFF" mode before the Cooling or Heating Capacity requests will be honored.
For Space Temperature controlled equipment, the Heat Cool Mode Request must be set to "Fan
Only" before the Cooling or Heating Capacity requests will be honored.
For each entity, there is an "Enable" point to enable or disable the remote capacity control, and
an analog value point to allow the user to request an analog capacity value. The analog value is
translated to the appropriate value per function.
Supply Fan Speed Command overrides will be honored in all non-Heat or Off modes. When
Supply Fan Speed Command is enabled, and the Supply Fan Speed Command value is 0%, the
system will interpret as an "OFF" mode request, and all active capacity will be set to "Off"; fan,
heating, and cooling.
All equipment safeties and limitations will be in-place while the Remote Capacity Control
functions are being leveraged:
• Minimum fan speeds as defined per active capacity will be maintained
• Compressor Minimum ON/OFF times will be maintained
• All system diagnostics will be maintained.

Emergency and Ventilation Override


This feature has two options for initiating an override request, either through the optional
(future) hardwired Ventilation Override terminals, or by initiating a request through the
Emergency Override Command point, a priority scheme is required to ensure proper equipment
operation.

Ventilation Override (Future)


When configured for the Ventilation Override option, applying 24 volts to one of the three
Ventilation Override inputs manually activates Ventilation Override. Three inputs are provided to
support Ventilation Override functionality:
• Pressurize mode
• Purge mode

ACC-APG001A-EN 25
Building Automation System Support Sequences

• Exhaust mode
If more than one mode is requested at the same time, the Pressurize request will have priority
followed by Purge, and then Exhaust. When Any Ventilation Override mode is active, all heating
and cooling is turned off. For the case where the unit is required to turn Off via hardwired
interface, the Equipment Shutdown input is used.

Emergency Override
All units with Symbio 700 support the remote Emergency Override Command functionality.
Within this point, there are addition enumerations versus the hardware Ventilation Override
interface:
• 1 = EMERG_NORMAL
• 2 = EMERG_PRESSURIZE
• 3 = EMERG_DEPRESSURIZE
• 4 = EMERG_PURGE
• 5 = EMERG_SHUTDOWN
• 6 = EMERG_FIRE
Pressurize, Depressurize, and Purge map to their respective Ventilation Override Modes directly. ,
Emerg_Shutdown and Emerg_Fire are unique to Emergency Override. Both of those are treated
as a remote shutdown request for the equipment.
Equipment Operation
Emergency and Ventilation Override requests/actions will take priority over normal equipment
timing events, such as compressor minimum ON/OFF/Inter-stage timers.
During an Emergency or Ventilation Override sequence, all temperature control algorithms are
initialized to an inactive state until the Emergency or Ventilation Override request is cleared. For
each override request, the unit will operate in a pre-determined state until override requests are
cleared.
For detailed unit operation during Emergency or Ventilation Override, refer to the Appendix
section of this document.

26 ACC-APG001A-EN
Service Test Mode
Service Test Mode can be used to initiate certain operating modes of the equipment. Refer to the
following sections for more details associated with this feature.

Service Test Timeout


Service Test Timeout (Minute) is a user selected time value. Once Service Test Mode has been
initiated, and this timer expires, the controls are forced to leave Service Test Mode and return to
normal unit operation.
• M i n i m u m v a l u e — 1 minute
• M a x i m u m v a l u e — 120 minute
• D e f a u l t v a l u e — 60 minutes
T i m e r I n i t i a t e : When any value for Service Test State Request is chosen other than Inactive, the
controller sets the Service Test Timeout to the user selected value and the unit begins to operate
as described in the tables below. It continues in operation until the Service Test Timeout Timer
reaches 0 O R until the user chooses a different Service Test State Request.
T i m e r T e r m i n a t e : if the Service Test Timeout timer has reached 0, the controls sets the Service
Test Stage Request to Inactive and the unit returns to normal unit operation. If the Service Test
Timeout Timer has not reached 0, the user can set the Service Test Stage Request to Inactive to
exit the active Service Test State Request and return to normal unit operation.
T i m e r R e s e t : if the Service Test Timeout timer has not reached 0, the user can select the Service
Test Stage Request to any value other than Inactive. The controller resets the Service Test
Timeout Timer to the user selected value and the unit operates as describe in the tables below for
the new request.

Leaving Service Test Mode


There are three ways to leave Service Test Mode:
• When the Service Test Timeout timer expires, the unit will leave Service Test Mode.
• Service Test State Request is set to “Inactive”.
• The controller goes through a power cycle or reset.

Constant Volume Supply Fan Service Test Mode


The tables below provide unit operation for each stage of service test depending on the unit
configuration.
The tables describe the service test mode states and expected unit response. For all service test
mode operation, “IN CONTROL” refers to Symbio 700 control algorithms controlling the unit. For
instance, in all service test mode states, the Condenser Fan will be controlled as needed to
ensure safe unit operation.
Table 4. Cooling Only
Service Test Service Test Service Test Service Test
Service Test Supply Fan Compressor Auxiliary Condenser Heat Cool
State #
State Request On/Off Cool Stage Heat Stage Fan Stage Mode Status
Request Request1,2 Request 3 Request 4
1 Inactive IN CONTROL IN CONTROL IN CONTROL IN CONTROL IN CONTROL

2 Fan On ON 0 0 IN CONTROL TEST

3 Cool 1 ON 1 0 IN CONTROL TEST

4 Cool 2 ON 2 0 IN CONTROL TEST

5 Heat 1 ON 0 1 IN CONTROL TEST

6 Heat 2 ON 0 2 IN CONTROL TEST

7 Heat 3 ON 0 3 IN CONTROL TEST

ACC-APG001A-EN 27
Service Test Mode

Table 4. Cooling Only (continued)


1 Inactive IN CONTROL IN CONTROL IN CONTROL IN CONTROL IN CONTROL

8 Heat 4 ON 0 4 IN CONTROL TEST

9 Defrost OFF 0 0 IN CONTROL TEST

10 Emergency Heat ON 0 2 IN CONTROL TEST


Notes:
1. Supply fan speed will operate the same as in normal cooling/heating operations. The minimum speeds can be found
in the Appendix of this document.
2. Compressor cool stages are defined within the Appendix of this document.
3. Available auxiliary heat stages are defined within the Appendix of this document.
4. Condenser Fan stages are defined within the Appendix of this document.

Table 5. Heat Pump


Service Test Service Test Service Test Service Test Service Test
Service Test Supply Fan Compressor Compressor Auxiliary Condenser Heat Cool
State #
State Request On/Off Cool Stage Heat Stage Heat Stage Fan Stage Mode Status
Request Request 1 Request 2 Request 3 Request 4
1 Inactive IN CONTROL IN CONTROL IN CONTROL IN CONTROL IN CONTROL IN CONTROL

2 Fan On ON 0 0 0 IN CONTROL TEST

3 Cool 1 ON 1 0 0 IN CONTROL TEST

4 Cool 2 ON 2 0 0 IN CONTROL TEST

5 Heat 1 ON 0 1 0 IN CONTROL TEST

6 Heat 2 ON 0 2 0 IN CONTROL TEST

7 Heat 3 ON 0 3 1 IN CONTROL TEST

8 Heat 4 ON 0 4 2 IN CONTROL TEST

9 Defrost7 ON 0 2 1 IN CONTROL TEST

10 Emergency Heat ON 0 0 2 IN CONTROL TEST


Notes:
1. Supply fan speed will operate the same as in normal cooling/heating operations. The minimum speeds can be found in the Appendix of
this document.
2. Compressor cool stages are defined within the Appendix of this document.
3. Compressor heat stages are defined within the Appendix of this document.
4. Available auxiliary heat stages are defined within the Appendix of this document.
5. Condenser Fan stages are defined within the Appendix of this document.
6. During Defrost, the unit will run Defrost operation until defrost terminate point is reached. After active defrost is terminated, the unit
will run in active Heat mode but will return to Defrost if it is determined to be needed by the controls.
7. Reversing Valve operation can be found in the Reversing Valve section of this document.

Multi-Speed Supply Fan Service Test Mode


Table 6. Cooling only
Service Test Service Test Service Test Service Test Service Test
Service Test Supply Fan Supply Fan Compressor Auxiliary Condenser Heat Cool
State #
State Request On/Off Speed Cool Stage Heat Stage Fan Stage Mode Status
Request Request 1 Request 2 Request 3 Request 4
1 Inactive IN CONTROL IN CONTROL IN CONTROL IN CONTROL IN CONTROL IN CONTROL

2 Fan On ON IN CONTROL 0 0 IN CONTROL TEST

3 Cool 1 ON IN CONTROL 1 0 IN CONTROL TEST

4 Cool 2 ON IN CONTROL 2 0 IN CONTROL TEST

5 Heat 1 ON IN CONTROL 0 1 IN CONTROL TEST

6 Heat 2 ON IN CONTROL 0 2 IN CONTROL TEST

7 Heat 3 ON IN CONTROL 0 3 IN CONTROL TEST

8 Heat 4 ON IN CONTROL 0 4 IN CONTROL TEST

9 Defrost OFF IN CONTROL 0 0 IN CONTROL TEST

28 ACC-APG001A-EN
Service Test Mode

Table 6. Cooling only (continued)


1 Inactive IN CONTROL IN CONTROL IN CONTROL IN CONTROL IN CONTROL IN CONTROL

10 Emergency Heat ON IN CONTROL 0 2 IN CONTROL TEST


Notes:
1. Supply fan speed will operate the same as in normal cooling/heating operations. The minimum speeds can be found in the Appendix of
this document.
2. Compressor cool stages are defined within the Appendix of this document.
3. Available auxiliary heat stages are defined within the Appendix of this document.
4. Condenser Fan stages are defined within the Appendix of this document.

Table 7. Heat pump


Service Test Service Test Service Test Service Test Service Test Service Test
Service Test Supply Fan Supply Fan Compressor Compressor Auxiliary Condenser Heat Cool
State #
State Request On/Off Speed Cool Stage Heat Stage Heat Stage Fan Stage Mode Status
Request Request 1 Request 2 Request 3 Request 4 Request 5
1 Inactive IN CONTROL IN CONTROL IN CONTROL IN CONTROL IN CONTROL IN CONTROL IN CONTROL

2 Fan On ON IN CONTROL 0 0 0 IN CONTROL TEST

3 Cool 1 ON IN CONTROL 1 0 0 IN CONTROL TEST

4 Cool 2 ON IN CONTROL 2 0 0 IN CONTROL TEST

5 Heat 1 ON IN CONTROL 0 1 0 IN CONTROL TEST

6 Heat 2 ON IN CONTROL 0 2 0 IN CONTROL TEST

7 Heat 3 ON IN CONTROL 0 2 1 IN CONTROL TEST

8 Heat 4 ON IN CONTROL 0 2 2 IN CONTROL TEST

9 Defrost7 ON IN CONTROL 2 0 1 IN CONTROL TEST

10 Emergency Heat ON IN CONTROL 0 0 2 IN CONTROL TEST


Notes:
1. Supply fan speed will operate the same as in normal cooling/heating operations. The minimum speeds can be found in the Appendix of this document.
2. Compressor cool stages are defined within the Appendix of this document.
3. Compressor heat stages are defined within the Appendix of this document.
4. Available auxiliary heat stages are defined within the Appendix of this document.
5. Condenser Fan stages are defined within the Appendix of this document.
6. During Defrost, the unit will run Defrost operation until defrost terminate point is reached. After active defrost is terminated, the unit will run in active
Heat mode but will return to Defrost if it is determined to be needed by the controls.
7. Reversing Valve operation can be found in the Reversing Valve section of this document.

Variable Speed Supply Fan Service Test Mode


Table 8. Cooling only
Service Test Service Test Service Test Service Test Service Test
Service Test Supply Fan Supply Fan Compressor Auxiliary Condenser Heat Cool
State #
State Request On/Off Speed Cool Stage Heat Stage Fan Stage Mode Status
Request Request 1 Request 2 Request 3 Request 4
1 Inactive IN CONTROL IN CONTROL IN CONTROL IN CONTROL IN CONTROL IN CONTROL

2 Fan On ON IN CONTROL 0 0 IN CONTROL TEST

3 Cool 1 ON IN CONTROL 1 0 IN CONTROL TEST

4 Cool 2 ON IN CONTROL 2 0 IN CONTROL TEST

5 Heat 1 ON IN CONTROL 0 1 IN CONTROL TEST

6 Heat 2 ON IN CONTROL 0 2 IN CONTROL TEST

7 Heat 3 ON IN CONTROL 0 3 IN CONTROL TEST

8 Heat 4 ON IN CONTROL 0 4 IN CONTROL TEST

9 Defrost OFF IN CONTROL 0 0 IN CONTROL TEST

ACC-APG001A-EN 29
Service Test Mode

Table 8. Cooling only (continued)


1 Inactive IN CONTROL IN CONTROL IN CONTROL IN CONTROL IN CONTROL IN CONTROL

10 Emergency Heat ON IN CONTROL 0 2 IN CONTROL TEST


Notes:
1. Supply fan speed will operate the same as in normal cooling/heating operations. The minimum speeds can be found in the Appendix of
this document.
2. Compressor cool stages are defined within the Appendix of this document.
3. Available auxiliary heat stages are defined within the Appendix of this document.
4. Condenser Fan stages are defined within the Appendix of this document.

Table 9. Heat pump


Service Test Service Test Service Test Service Test Service Test Service Test
Service Test Supply Fan Supply Fan Compressor Compressor Auxiliary Heat Condenser Fan Heat Cool
State #
State Request On/Off Speed Request Cool Stage Heat Stage Stage Stage Mode Status
Request 1 Request 2 Request 3 Request 4 Request 5
1 Inactive IN CONTROL IN CONTROL IN CONTROL IN CONTROL IN CONTROL IN CONTROL IN CONTROL

2 Fan On ON IN CONTROL 0 0 0 IN CONTROL TEST

3 Cool 1 ON IN CONTROL 1 0 0 IN CONTROL TEST

4 Cool 2 ON IN CONTROL 2 0 0 IN CONTROL TEST

5 Heat 1 ON IN CONTROL 0 1 1 IN CONTROL TEST

6 Heat 2 ON IN CONTROL 0 2 2 IN CONTROL TEST

7 Heat 3 ON IN CONTROL 0 2 3 IN CONTROL TEST

8 Heat 4 ON IN CONTROL 0 2 4 IN CONTROL TEST

9 Defrost OFF IN CONTROL 0 0 0 IN CONTROL TEST

10 Emergency Heat ON IN CONTROL 0 0 2 IN CONTROL TEST


Notes:
1. Supply fan speed will operate the same as in normal cooling/heating operations. The minimum speeds can be found in the Appendix of this document.
2. Compressor cool stages are defined within the Appendix of this document.
3. Compressor heat stages are defined within the Appendix of this document.
4. Available auxiliary heat stages are defined within the Appendix of this document.
5. Condenser Fan stages are defined within the Appendix of this document.
6. During Defrost, the unit will run Defrost operation until defrost terminate point is reached. After active defrost is terminated, the unit will run in active
Heat mode but will return to Defrost if it is determined to be needed by the controls.
7. Reversing Valve operation can be found in the Reversing Valve section of this document.

30 ACC-APG001A-EN
Diagnostics
Device Tracker
Symbio 700 will keep statistical data of the unit for component starts and component run times
(in hours) for the following unit components:
• Compressor 1
• Compressor 2
• Condenser Fan 1
• Condenser Fan 2
• Supply Fan
• Electric Heat Stage 1
• Electric Heat Stage 2
• Filter (Runtime only)
If the Filter Runtime hours exceed the value set by the user for the Filter Runtime Hours Setpoint,
the Symbio 700 controller activates the Diagnostic: Maintenance Required point.
If for any reason it is required to reset the component statistical data, the Run Time Reset or
Starts Reset points can be accessed through the Symbio Service and Installation mobile app.. If
the reset points are set to Reset, the Component Run Time and Starts are reset to 0 and the
associated reset points are set back to inactive. In the case of the Diagnostic: Maintenance
Required point, it will also be reset to Inactive if Filter Timer Reset point is set.

Compressor Proving Diagnostics


There are three diagnostics that can be generated based on the compressor proving input.

Diagnostic: Compressor X Proving Trip


When a compressor output is commanded ON and it has been running for more than 5 seconds,
if the associated proving input opens, the controls generate the Diagnostic: Comp X Proving Trip
and the following will occur:
• Command the associated compressor output OFF immediately.
• Command any compressor output OFF that is on the same refrigeration circuit as the
compressor which had the proving input trip.
• The Circuit is disabled for 15 minutes.
After the 15 minute compressor proving timeout has expired, if the unit is not under a
“Diagnostic: Compressor 1 Proving Lockout” event
• The Diagnostic: Comp X Proving Trip diagnostic is reset
• If the cooling stage is still requested ON, the circuit is allowed to stage again

Diagnostic: Compressor X Proving Lockout


There are two cases that can cause a Diagnostic: Compressor X Proving Lockout:
• If a refrigeration circuit accumulates 4 consecutive Diagnostic: Comp X Proving Trips during
the same compressor operating cycle, a Diagnostic: Compressor X Proving Lockout is
generated.
N o t e : If the call for the compressor operation terminates, the counter is set to zero.
• If a compressor’s associated proving input does not CLOSE within 5 seconds of the
compressor startup.
If a Diagnostic: Compressor X Proving Lockout is generated the following will occur:
• All compressors on the associated circuit are de-energized immediately and they are locked
out until a Reset Diagnostic action is initiated.

ACC-APG001A-EN 31
Diagnostics

• The “Diagnostic: Compressor X Proving Lockout” diagnostic point is activated and the alarm
output is activated.

Diagnostic: Compressor X Contactor Failure


If a compressor proving input becomes Active for 5 continuous seconds when the associated
compressor command output is Inactive, a Diagnostic: Compressor X Contactor Failure is
generated and the following occurs:
• All compressors on the associated circuit are de-energized immediately and they are locked
out until a Reset Diagnostic is initiated.
The “Compressor X Contactor Failure” diagnostic point is activated and the alarm output is
activated.

Diagnostics – Low Pressure Cutout


The following operation is enforced based on the state of the circuit’s LPC input:
Prior to Compressor Startup:
• If a compressor output is Off and its circuit’s LPC input is open, compressor operation is not
inhibited, and the D i a g n o s t i c : C i r c u i t X L P C T r i p point will not be annunciated.
After Compressor Startup:
An LPC Bypass Delay function delays the setting of a low pressure cutout after compressor
startup on a circuit until a pre-determined amount of time passes in low ambient conditions. The
length of the delay is determined based on ambient temperature:
• If the Outdoor Air Temperature Active is less than 40°F, the LPC Bypass Delay is set to 60
seconds
• If the Outdoor Air Temperature Active is between 40°F and 50°F, the LPC Bypass Delay is set
to 30 seconds
• If the Outdoor Air Temperature Active is greater than 50°F, the LPC Bypass Delay is 0 seconds
There are two diagnostics that can be generated based on the Compressor Low Pressure Cutout
input:

Diagnostic: Circuit X LPC Trip


• All Compressors Outputs on the effected circuit are commanded OFF
• The Diagnostic: Circuit X LPC Trip point is annunciated
• The circuit is disabled for 3 minutes
• The circuit’s LPC trip counter is incremented
After the 3 minute low pressure event timeout has expired, if the unit is not under a lockout
event,
• The Diagnostic: Circuit X LPC Trip point is reset
• If the stage is still requested ON, the circuit is allowed to stage again
• If the Circuit runs for 3 minutes, its LPC Trip Count is reset to 0.
On Heat Pumps, if the Outdoor Air Temperature is less than 0° F or if the unit is in active defrost,
the low pressure cutout input state is ignored.

Diagnostic: Circuit X LPC Lockout


If a circuit’s LPC trip counter accumulates 4 low pressure events without the circuit running for
the 3 minute minimum on time (counter is not reset), a Diagnostic: Circuit X LPC Lockout” is
generated.
Once a Diagnostic: Circuit X LPC Lockout has been generated, the following occurs:
• All compressors on the associated circuit are de-energized immediately and they are locked
out until a Reset Diagnostic is initiated.
• The Diagnostic: Circuit X LPC Lockout point is activated and the alarm output is activated.

32 ACC-APG001A-EN
Diagnostics

Diagnostics – Alarm Indicator Status


The Symbio 700 will support an Alarm Indicator Status point that if configured, drives the state of
a relay output on the Customer Connection Module. This point is set to active when a failure
occurs that functionally stops a critical component within the HVAC system.
For a list of all supported Symbio 700 Diagnostics and if it sets the Alarm Indicator, refer to the
Appendix section of this document.

Reset Diagnostic
A Reset Diagnostic function is responsible for ensuring that the Reset Diagnostic point is set to
the right value under normal application control. The below sections describes how the Reset
Diagnostic point is set to Active and Inactive.

Power-Up Reset or Exception/Override Mode Transition


At power-up or after the unit leaves an Exception or Override mode, all diagnostics are cleared,
and the application starts over.

Reset Diagnostic Point


Diagnostic Resets throughout the controller application are triggered by the state of the Reset
Diagnostic Point. The Reset Diagnostic point is setup as a last-write-wins point type, so it can be
controlled by the local UI on the Symbio 700 or can be communicated.

Heat Cool Mode Transition Reset


When the unit is controlled by a zone sensor, a transition from System Mode Switch Local = OFF
to System Mode Switch Local ≠ OFF triggers a Reset Diagnostic request.

Reset Diagnostic Point – Active to Inactive Transition


When the diagnostic reset function detects the state of the Reset Diagnostic point is Active, after
5 seconds, the Diagnostic Reset function sets the Reset Diagnostic point to Inactive.

ACC-APG001A-EN 33
Troubleshooting
The Symbio 700 controller provides system shutdown, operational default operation, and
communication error handling of the Odyssey unit. The list of fault conditions below will stop
normal operation or change the operation of the unit to a default condition. Faults are indicated
in the Active Alarm menu of the onboard user interface and the Symbio Service and Installation
mobile app.

Unit Communication Fault


The maximum time for the inter-module communications (IMC) bus is 15 seconds. If 15 seconds
passes with no valid communications received from any of the Options modules, the Symbio 700
takes the following actions:

Module Symbio 700 Response Response Type

Symbio 700 Onboard I/O Auto Reset


• Set Diagnostic: Unit Communications Failure
• On-Board I/O Communication Status = Not
Communicating
• All unit functions will be shut down and I/O
will go to their comm. loss state

Customer Options Module Auto Reset


• Set Diagnostic: Unit Communications Failure
• Customer Options Module Communication
Status = Not Communicating
• All unit functions that have dependencies on
data from other modules will be discontinued
– Ventilation Override functionality is
discontinued
– Alarm Indicator function is discontinued

Indoor Options Module Auto Reset


• Set Diagnostic: Unit Communications Failure
• Indoor Options Module Communication Status
= Not Communicating
• All unit functions that have dependencies on
data from other modules will be discontinued
– All Electric Heat operation is discontinued
– Discharge Air Temperature dependent
control discontinued (SZVAV)

Sensor Fault
On Symbio 700, if a sensor value goes outside of its minimum or maximum range, the point goes
into an Alarm State. If the point in the Alarm State, we consider the sensor failed and take the
following actions:

Fault Symbio 700 Response Response Type

Space Temperature Active Auto Reset


• Annunciated in the Active Alarm list.
• For specific unit operational response, see
Space Temperature Control (CVZT/VVZT)
section of this document.

Discharge Air Temperature Local Auto Reset


• Annunciated in the Active Alarm list.
• For specific unit operational response, see
Space Temperature Control (CVZT/VVZT)
section of this document.

Outdoor Air Temperature Active Auto Reset


• Annunciated in the Active Alarm list.
• Heat Pump Low Ambient functionality is
disabled.

34 ACC-APG001A-EN
Troubleshooting

Fault Symbio 700 Response Response Type

Coil Temperature Sensor 1 Auto Reset


• Annunciated in the Active Alarm list.
• If Outdoor Air Temperature < 52° F, Demand
Defrost will be disabled and timed defrost will
be used.

Coil Temperature Sensor 2 Auto Reset


• Annunciated in the Active Alarm list.
• If Outdoor Air Temperature < 52°F, Demand
Defrost will be disabled and timed defrost will
be used.

Space Humidity Sensor Annunciated in the Active Alarm list. Auto Reset

Space CO2 Sensor Annunciated in the Active Alarm list. Auto Reset

Compressor Fault
Symbio 700 supports compressor safety functionality to keep the compressors from operating in
an undesirable condition. If a compressor safety failure occurs, the following actions occur:

Fault Symbio 700 Response Response Type

LPC Lockout For specific operation associated with the LPC Manual Reset
diagnostics, refer to the Compressor Protection
section of this document.

Proving Lockout For specific operation associated with the proving Manual Reset
diagnostics, refer to the Compressor Protection
section of this document.

Contactor Failure For specific operation associated with the proving Manual Reset
diagnostics, refer to the Compressor Protection
section of this document.

VFD Fault
The following failures are derived either through direct data monitoring from the Modbus device,
or through a combination of Modbus data and additional failure criteria:

Fault Fault Detection Symbio 700 Response Response Type

Diagnostic: Supply Fan If while the Supply Fan Manual Reset


• Diagnostic: Supply
Failure VFD is requested to run,
Fan Failure will be set
the VFD Running Status
to Active
from the drive is set to
False for 40 continuous • All unit functions will
seconds, this failure will be be shut down
detected immediately

Diagnostic: VFD Fault When Active All unit functions will be Auto Reset
Supply Fan – 1 shut down immediately

Diagnostic: VFD Supply When Active All unit functions will be Auto Reset
Fan Ground Fault – 1 shut down immediately

Diagnostic: VFD Supply When Active All unit functions will be Auto Reset
Fan Motor Current shut down immediately
Overload – 1

Diagnostic: VFD Supply When Active All unit functions will be Auto Reset
Fan Short Circuit – 1 shut down immediately

Supply Fan VFD If continual loss of Manual Reset


• Supply Fan VFD
Communication Status communication between
Communication
the controller and the VFD
Status will be set to
has occurred for a 30-
Not Communicating
second period, this failure
will be detected. • All unit functions will
be shut down

ACC-APG001A-EN 35
Troubleshooting

Defrost Fault
The below list of diagnostics are associated with the Demand Defrost Function.

Fault Fault Detection Symbio 700 Response Response


Type

Diagnostic: Demand Manual


• Set Diagnostic: • Set Diagnostic: Demand Defrost
Defrost Disabled Reset
Demand Defrost Disabled
Diagnostic: Demand Disabled with any
• For Independent Circuit Heat Pump
Defrost Disabled Ckt 1 Demand Defrost Fault
units, set Diagnostic Demand
on non-independent
Defrost Disable Ckt X (depending
Diagnostic: Demand circuit heat pumps.-
on the associated circuit)
Defrost Disabled Ckt 2 • Set Diagnostic
• Revert to Default Defrost operation.
Demand Defrost
Disable Ckt X with • See Demand Defrost Faults below
any Demand Defrost
Fault on any circuit for
independent
condenser systems.

Diagnostic: Demand ∆T is below minimum Manual


• Initiate Defrost
Defrost Fault A value 12 minutes after Reset
defrost is terminated. • If Low ∆T > 2 hours:
Diagnostic: Demand
Defrost Fault A Ckt 1 – Set Diagnostic: Demand
Defrost Disabled
Diagnostic: Demand – Set Diagnostic: Default
Defrost Fault A Ckt 2 Defrost Fault A
• For Independent Circuit Heat Pump
units, set Diagnostic: Demand
Defrost Disable Ckt X
• Set Diagnostic: Default Defrost
Fault A CKt X
• Initiate Defrost
Reset timer if ∆T returns within bounds

Diagnostic: Demand Defrost terminated on If defrost is terminated on time Manual


Defrost Fault B time requirement requirement (vs differential temp) Reset

Diagnostic: Demand • Set Diagnostic: Default Defrost


Defrost Fault B Ckt 1 Fault B
• For Independent Circuit Heat Pump
Diagnostic: Demand units, set Diagnostic: Default
Defrost Fault B Ckt 2 Defrost Fault B Ckt X
• Increment Demand Defrost Fault B
counter
After counter = 10
Set Diagnostic: Demand
Defrost Disabled
or for Indepentent Circuit unit
• For Independent Circuit Heat Pump
units, set Diagnostic: Demand
Defrost Disable Ckt X

Diagnostic: Demand ∆T is above Maximum Manual


• Set Diagnostic: Default Defrost
Defrost Fault C Value 12 minutes after Reset
Fault C
defrost is terminated
Diagnostic: Demand or for Independent Circuit units, set
Defrost Fault C Ckt 1 Diagnostic: Default Defrost Fault C
Ckt X
Diagnostic: Demand • Initiate Defrost Increment Demand
Defrost Fault C Ckt 2 Defrost Fault C counter
• After counter = 16
• Set Diagnostic: Demand Defrost
Disabled
or for Independent Circuit units
• Set Diagnostic: Demand Defrost
Disable Ckt X

36 ACC-APG001A-EN
Troubleshooting

Fault Fault Detection Symbio 700 Response Response


Type

Diagnostic: Demand ∆T does not change by 2°F Manual


• Initiate Defrost
Defrost Fault D in 1 hour, starting 12 Reset
minutes after defrost is • Set Diagnostic: Demand Defrost
terminated and ∆T is less Disabled
than or equal to 6 but
• Set Diagnostic: Default Defrost
greater than Low ∆T
Fault D
degrees 12 minutes after
defrost is terminated.

ACC-APG001A-EN 37
Appendix A
Supply Fan
Multi-Speed/VFD
Table 10. Multi-speed minimum supply fan speeds

Unit Operation Supply Fan Speed

Off 0%

Fan Only 41.7%

Cooling Stage 1 41.7%

Cooling Stage 2 100%

Heat Pump Heating 100%

Electric/Auxiliary Heating 100%

Variable Speed/VFD
Table 11. Variable speed minimum supply fan speeds

Unit Operation Supply Fan Speed

Off 0%

Fan Only 58%

Cooling Stage 1 58%

Cooling Stage 2 80%

Heat Pump Heating 100%

Electric/Auxiliary Heating 100%

Compressor Staging
Thermostat Staging
For equipment staging response to a conventional thermostat signals, refer to the Conventional
Thermostat sequence of operation above.

Cooling Only (Electric Heat) – CVZT & VVZT


Table 12. Single compressor cooling staging

Unit Operation Unit Response

Cooling Stage 1 Compressor 1 Output ON

Table 13. Dual compressor cooling staging (manifold or independent)

Unit Operation Unit Response

Cooling Stage 1 Compressor 1 Output ON

Cooling Stage 2 Compressor 1 Output ON + Compressor 2


Output ON

38 ACC-APG001A-EN
Appendix A

Table 14. Dual unloading compressor cooling staging


Unit Operation Unit Response

Cooling Stage 1 Compressor 1 Output ON + Compressor 2


Output ON

Cooling Stage 2 Compressor 1 Output ON +Compressor 1


Unloader Solenoid ON + Compressor 2 Output
ON +Compressor 2 Unloader Solenoid ON

Heat Pump – CVZT & VVZT


Table 15. Single compressor cooling staging

Unit Operation Unit Response

Cooling Stage 1 Compressor 1 Output ON

Table 16. Dual compressor cooling staging (manifold or independent)

Unit Operation Unit Response

Cooling Stage 1 Comrpessor 1 Output ON

Cooling Stage 2 Compressor 1 Output ON + Compressor 2


Output ON

Condenser Fan Operation


Thermostat, CVZT, & VVZT
Table 17. Single condenser fan systems (cooling only and heat pump)

Unit Operation Unit Response

Compressor 1 Output ON Condenser Fan Output 1 ON

Compressor 2 Output ON Condenser Fan Output 1 ON

Compressor 1 Output ON + Condenser Fan Output 1 ON


Compressor 2 Output ON

N o t e : If Defrost is active on Heat Pump units, then Condenser Fan Output 1 OFF.
Table 18. Dual condenser fan - shared airstream (cooling only)

Unit Operation Unit Response

Compressor 1 Output ON Condenser Fan Output 1 ON +Condenser Fan


Output 2 ON

Compressor 2 Output ON Condenser Fan Output 1 ON +Condenser Fan


Output 2 ON

Compressor 1 Output ON + Condenser Fan Output 1 ON +Condenser Fan


Compressor 2 Output ON Output 2 ON

Table 19. Dual condenser fan - independent airstream (cooling only and heat pump)

Unit Operation Unit Response

Compressor 1 Output ON Condenser Fan Output 1 ON

Compressor 2 Output ON Condenser Fan Output 2 ON

Compressor 1 Output ON + Condenser Fan Output 1 ON +Condenser Fan


Compressor 2 Output ON Output 2 ON

ACC-APG001A-EN 39
Appendix A

Notes:
• If Defrost is active on Heat Pump refrigeration circuit 1, then unit response is
Condenser Fan Output 1 OFF.
• If Defrost is active on Heat Pump refrigeration circuit 2, then unit response is
Condenser Fan Output 2 OFF.

Electric Heat
CVZT & VVZT
Table 20. Electric heat staging

Unit Operation Unit Response

Electric Heat Stage 1 Electric Heat Stage 1 Output ON

Electric Heat Stage 2 Electric Heat Stage 1 and 2 Outputs ON

Diagnostics and Alarm Indicator Status


Table 21. Odyssey supported diagnostics and alarm relay functionality

Diagnostic/Alarm Alarm Indicator

Diagnostic: Unit Communications Failure Y

On-Board I/O Communication Status Y

Customer Options Module Communication Status Y

Indoor Options Module Communication Status Y

Heat Options Module Communication Status Y

Supply Fan VFD Communication Status Y

Diagnostic: Demand Defrost Disabled N

Diagnostic: Demand Defrost Disabled Ckt 1 N

Diagnostic: Demand Defrost Disabled Ckt 2 N

Diagnostic: Demand Defrost Fault A N

Diagnostic: Demand Defrost Fault A Ckt 1 N

Diagnostic: Demand Defrost Fault A Ckt 2 N

Diagnostic: Demand Defrost Fault B N

Diagnostic: Demand Defrost Fault B Ckt 1 N

Diagnostic: Demand Defrost Fault B Ckt 2 N

Diagnostic: Demand Defrost Fault C N

Diagnostic: Demand Defrost Fault C Ckt 1 N

Diagnostic: Demand Defrost Fault C Ckt 2 N

Diagnostic: Demand Defrost Fault D N

Diagnostic: VFD Fault Supply Fan - 1 Y

Diagnostic: VFD Supply Fan Ground Fault - 1 Y

Diagnostic: VFD Supply Fan Motor Current Overload - 1 Y

Diagnostic: VFD Supply Fan Short Circuit - 1 Y

Diagnostic: Circuit 1 LPC Lockout Y

40 ACC-APG001A-EN
Appendix A

Table 21. Odyssey supported diagnostics and alarm relay functionality (continued)

Diagnostic/Alarm Alarm Indicator

Diagnostic: Circuit 2 LPC Lockout Y

Diagnostic: Compressor 1 Proving Lockout Y

Diagnostic: Compressor 2 Proving Lockout Y

Diagnostic: Compressor 1 Contactor Failure Y

Diagnostic: Compressor 2 Contactor Failure Y

Diagnostic: Circuit 1 LPC Trip N

Diagnostic: Circuit 2 LPC Trip N

Diagnostic: Comp 1 Proving Trip N

Diagnostic: Comp 2 Proving Trip N

Diagnostic: Maintenance Required N

Coil Temperature Sensor 1 N

Coil Temperature Sensor 2 N

Coil Temperature Sensor 3 N

Discharge Air Temperature Local N

Outdoor Air Temperature Active N

Outdoor Air Humidity Active N

Space CO2 Concentration Active N

Space Humidity Active N

Space Temperature Active N

Emergency and Ventilation Override


Table 22. Emergency and ventilation override

Inputs Outputs

EOM EOM EOM EOM EOM


Supply Supply Compres- Compres- Auxiliary Heat Cool
Emergency Override
Fan On/ Fan sor Cool sor Heat Heat Mode
BAS
Off Speed Stage Stage Stage Status
Request Request Request Request Request

Point State % Value Value Value Point

2 = EMERG_
ON 100 0 0 0 Fan Only
PRESSURIZE

3 = EMERG_
OFF 0 0 0 0 Fan Only
DEPRESSURIZE

4 = EMERG_PURGE ON 100 0 0 0 Fan Only

5 = EMERG_SHUTDOWN OFF 0 0 0 0 OFF

6 = EMERG_FIRE OFF 0 0 0 0 OFF

1 = EMERG_NORMAL Auto Auto Auto Auto Auto Auto

ACC-APG001A-EN 41
Appendix A

Internal and External Space Setpoint Adjustment


Zone sensors with an internal or external setpoint adjustment provide the controller with a local
setpoint (50° F to 85° F or 10° C to 29.4° C). The internal setpoint adjustment is concealed under
the zone sensor cover. To access the setpoint adjustment, remove the zone sensor cover. Some
external setpoints (when present) are displayed on the digital display zone sensor front cover.
When the local setpoint adjustment is used to determine the setpoints, all unit setpoints are
calculated based on the local setpoint value, the configured setpoints, and the active mode of the
controller. The controller determines the effective space setpoint based on the following:
• Local setpoint input (SET)
• The local setpoint calibration (configured)
• Whether or not the local setpoint adjustment can be used or not (configured)
• Communicated setpoint input
• Default setpoints (configured)
• Occupancy mode
• Heating or cooling mode (space demand)
• Space setpoint high and low limits (configured)
Heat mode:
• Occupied mode: Space Temperature Setpoint Active = Space Temperature Setpoint
(arbitrated) - Occupied Offset
• Occupied standby mode: Space Temperature Setpoint Active = Space Temperature Setpoint
(arbitrated) - Standby Offset
• Unoccupied mode: Space Temperature Setpoint Active = Unoccupied Heating Setpoint Cool
mode
Cool mode:
• Occupied mode: Space Temperature Setpoint Active = Space Temperature Setpoint
(arbitrated) + Occupied Offset
• Occupied standby mode: Space Temperature Setpoint Active = Space Temperature Setpoint
(arbitrated) + Standby Offset
• Unoccupied mode: Space Temperature Setpoint Active = Unoccupied Cooling setpoint
When a building automation system or other controller communicates a setpoint to the
controller, the controller ignores the local setpoint input and uses the communicated value. The
exception is when the system is in unoccupied mode and the controller always uses the
unoccupied setpoints. After the controller completes all setpoint calculations, the calculated
occupied setpoint is validated against the following configured space setpoint limits:
• Heating setpoint high limit
• Heating setpoint low limit
• Cooling setpoint high limit
• Cooling setpoint low limit
These setpoint limits apply only to the occupied and occupied standby, heating, and cooling
setpoints. They do not apply to the unoccupied heating and cooling setpoints. When the
controller is in the unoccupied mode, it always uses the unoccupied heating and cooling
setpoints. Unit configuration enables or disables the local setpoint. This parameter provides
additional flexibility to allow you to apply communicated, local, or default setpoints without
making physical changes to the unit. Similar to local setpoints, the effective setpoint value for a
communicated setpoint is determined based on the stored default setpoints, configuration
values, and the controller occupancy mode.

42 ACC-APG001A-EN
Notes

ACC-APG001A-EN 43
Trane - by Trane Technologies (NYSE: TT), a global innovator - creates comfortable, energy efficient
indoor environments for commercial and residential applications. For more information, please visit
trane.com or tranetechnologies.com.

Trane has a policy of continuous product and product data improvements and reserves the right to change design and specifications without
notice. We are committed to using environmentally conscious print practices.

ACC-APG001A-EN 10 Jun 2020


Supersedes (New) ©2020 Trane

You might also like