Symbio 700 Acc-Apg001a-En - 06102020
Symbio 700 Acc-Apg001a-En - 06102020
Symbio 700 Acc-Apg001a-En - 06102020
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning
equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person
could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that
are attached to the equipment.
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury.
All field wiring MUST be performed by qualified personnel. Improperly installed and
grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards,
you MUST follow requirements for field wiring installation and grounding as described in
NEC and your local/state/national electrical codes.
WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death or serious
injury.
Technicians, in order to protect themselves from potential electrical, mechanical, and
chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and
labels, as well as the instructions below:
• Before installing/servicing this unit, technicians M UST put on all PPE required for
the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves,
safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash
clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA
guidelines for proper PPE.
• When working with or around hazardous chemicals, ALWAYS refer to the
appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and
Labelling of Chemicals) guidelines for information on allowable personal exposure
levels, proper respiratory protection and handling instructions.
• If there is a risk of energized electrical contact, arc, or flash, technicians MUST put
on all PPE in accordance with OSHA, NFPA 70E, or other country-specific
requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM
ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER
ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND
EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.
WARNING
Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.
• All Trane personnel must follow the company’s Environmental, Health and Safety
(EHS) policies when performing work such as hot work, electrical, fall protection,
lockout/tagout, refrigerant handling, etc. Where local regulations are more
stringent than these policies, those regulations supersede these policies.
• Non-Trane personnel should always follow local regulations.
Copyright
This document and the information in it are the property of Trane, and may not be used or
reproduced in whole or in part without written permission. Trane reserves the right to revise this
publication at any time, and to make changes to its content without obligation to notify any
person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
ACC-APG001A-EN 3
Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Additional Documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Symbio 700 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Field Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Unit Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Onboard User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Mobile Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Startup Sequence. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Conventional Thermostat Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Space Temperature Control Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Constant Volume and Multi-Speed Fan Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . 16
Normal Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Supply Fan Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Single Zone Variable Air Volume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
General Support Sequences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Fan Setpoints with VFD-driven Fan Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Compressor Minimum Runtime . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Refrigeration Circuit Management. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Compressor Proof of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Compressor Low Pressure Cutout Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Heat Pump Support Sequences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Heat Pump Switchover Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Demand Defrost Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Evaporator Defrost Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Building Automation System Support Sequences . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Occupancy Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Timed Override . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Supply Air Tempering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Unit Stop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Capacity Limit Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Remote Capacity Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Emergency and Ventilation Override . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Ventilation Override (Future) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Emergency Override. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4 ACC-APG001A-EN
Table of Contents
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Device Tracker. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Compressor Proving Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Diagnostic: Compressor X Proving Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Diagnostic: Compressor X Proving Lockout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Diagnostic: Compressor X Contactor Failure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Diagnostics – Low Pressure Cutout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Diagnostic: Circuit X LPC Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Diagnostic: Circuit X LPC Lockout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Diagnostics – Alarm Indicator Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Reset Diagnostic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Power-Up Reset or Exception/Override Mode Transition. . . . . . . . . . . . . . . . . . . . 33
Reset Diagnostic Point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Heat Cool Mode Transition Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Reset Diagnostic Point – Active to Inactive Transition. . . . . . . . . . . . . . . . . . . . . . . 33
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Unit Communication Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Sensor Fault. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Compressor Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
VFD Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Defrost Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Appendix A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Supply Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Multi-Speed/VFD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Variable Speed/VFD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Compressor Staging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Thermostat Staging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Cooling Only (Electric Heat) – CVZT & VVZT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Heat Pump – CVZT & VVZT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Condenser Fan Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Thermostat, CVZT, & VVZT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
CVZT & VVZT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Diagnostics and Alarm Indicator Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Emergency and Ventilation Override . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
ACC-APG001A-EN 5
Table of Contents
6 ACC-APG001A-EN
Introduction
The Symbio 700 installed on Odyssey split systems is a factory installed and programmed
controller, providing digital control and protection of the equipment.
The Symbio 700 has two model options:
• S t a n d a r d C o n f i g u r a t i o n — provides standard troubleshooting via on-board user interface
(UI) and access to the Symbio Service and Installation mobile app.
• A d v a n c e d C o n f i g u r a t i o n — introduces additional troubleshooting tools and Building
Automation System interface via BACnet® (ANSI/ASHRAE Standard 135-2016) or LonTalk™.
The Symbio 700 offers multiple equipment configuration options regardless of controller model.
The Odyssey split system can be configured as the following system types:
• Conventional Thermostat Control (T-Stat)
• Space Temperature Control Constant Volume (CVZT)
• Space Temperature Control Single Zone Variable Air Volume (VVZT)
These configurations can be used with standard cooling or heat pump systems.
This guide provides information about the configuration, control capabilities and
troubleshooting of the Odyssey system with Symbio 700 controller.
Additional Documentation
• Symbio Service and Installation Quick Start Guide - BAS-SVN043
• Symbio 700 User Guide - BAS-SVU054
• Symbio 700 BACnet Integration Guide - ACC-SVP001
• Symbio 700 LonTalk Integration Guide - ACC-SVP002
• Odyssey General Installation, Operation, and Maintenance Guide - SSA-SVX06
• Odyssey Cooling Installation, Operation, and Maintenance Guide -SS-SVX001
• Odyssey Heat Pump Installation, Operation, and Maintenance Guide - SSP-SVX001
ACC-APG001A-EN 7
Symbio 700 Overview
Field Connection
The Symbio 700 controller optimizes inputs and outputs (I/O) for multiple applications. For initial
installation of an Odyssey with Symbio 700, the field landed inputs are outlined below.
Figure 1. Symbio 700 Field Connections
1 24VAC
Demand Shed/Demand Limit
J16 Demand Shed/Demand Limit
Connection 2
Input
1 BACnet +
4 BACnet -
1 Zone Temperature
2 GND
3 Cool Setpoint
5 Heat Setpoint
6 GND
7 24VAC
1 24VAC
J20 Occupancy Connections
2 Occupancy Switch
8 ACC-APG001A-EN
Symbio 700 Overview
1 24VAC
2 Y1
3 W1/O
4 G
6 Y2
7 X2
9 GND
1 24Vdc Out
3 Common
1 24Vdc Out
3 Common
Unit Configuration
The Odyssey system can be configured via an onboard user interface or via the Symbio Service
and Installation mobile app.
The interface provides an intuitive menu structure: alarms, status, service, settings, and utilities.
Configuration of the unit is accomplished under the utilities menu item. A complete list of
functions is outlined in the Symbio 700 User Guide - BAS-SVU054.
ACC-APG001A-EN 9
Symbio 700 Overview
To configure the unit, navigate to the utilities menu and press “Enter”. Once in the utilities menu
the user has additional submenu options. This allows the user to navigate and configure the
appropriate setting quickly and easily.
Mobile Application
The Trane Symbio™ Service and Installation mobile app is required to setup, edit, and confirm
the communication protocol and associated settings.
The free download of Trane Symbio Service and Installation mobile app is available on the App
Store® for iOS, and on Google Play® for Android™.
Figure 3. Trane Symbio™ Service and Installation mobile app
Bluetooth Pairing
Quick Connection Instructions
Follow these instructions to quickly connect the mobile app to the Symbio 700 controller:
10 ACC-APG001A-EN
Symbio 700 Overview
ACC-APG001A-EN 11
Symbio 700 Overview
12 ACC-APG001A-EN
Startup Sequence
Under normal conditions, the Symbio 700 will startup over approximately 60 seconds once
power is applied to the system. During this process, the controller checks that a valid system
configuration is present and proceeds to normal control operation. After startup, the system will
begin to respond to operational requests.
ACC-APG001A-EN 13
Conventional Thermostat Sequence of Operation
When the Odyssey system is configured to operate with a conventional thermostat, the controller
provides protection for the system (see General Support Sequence section) and continues to
provide insight to operating conditions. A conventional thermostat can be applied with constant
volume cooling only, heat pump, and single zone 2-speed fan configured systems. While not
recommended, a conventional thermostat can be applied to single zone variable volume
configured systems, but the system is limited to staged fan control instead of a fully variable
sequence.
When under conventional thermostat control, the equipment responds directly to operating
requests from the thermostat device. Each thermostat input corresponds to a specific unit
function, as described in the following tables. Equipment protection functions and compressor
minimum on/off timers remain in-control, even when under conventional thermostat control.
Table 2. Cooling only/electric heat systems
Inputs Outputs
Supply Compres- Auxiliary
Supply Heat Cool
Fan On/ sor Cool Heat
X Y1 Y2 W1/O W2 G Fan Speed Mode
Off Stage Stage
Request Status
Request Request Request
NA OPEN OPEN OPEN OPEN CLOSED ON Min None None Fan Only
X=ignored by controller
14 ACC-APG001A-EN
Table 3. Heat pump systems
Inputs Outputs
Supply Compres- Compres- Auxiliary
Supply Heat Cool
Fan On/ sor Cool sor Heat Heat
X Y1 Y2 W1/O W2 G Fan Speed Mode
Off Stage Stage Stage
Request Status
Request Request Request Request
ACC-APG001A-EN
CLOSED OPEN OPEN OPEN OPEN X ON Max None None Full Stage Em Heat
OPEN CLOSED OPEN OPEN OPEN X ON Max None Stage 1 None Heat
OPEN OPEN CLOSED OPEN OPEN X ON Max None Stage 1 None Heat
OPEN CLOSED CLOSED OPEN OPEN X ON Max None Full Stage None Heat
OPEN CLOSED OPEN OPEN CLOSED X ON Max None Stage 1 Full Stage Heat
OPEN OPEN CLOSED OPEN CLOSED X ON Max None Stage 1 Full Stage Heat
OPEN CLOSED CLOSED OPEN CLOSED X ON Max None Full Stage Full Stage Heat
OPEN OPEN OPEN CLOSED OPEN OPEN OFF 0 None None None Cool
OPEN CLOSED OPEN CLOSED OPEN X ON Min Stage 1 None None Cool
OPEN OPEN CLOSED CLOSED OPEN X ON Min Stage 1 None None Cool
OPEN CLOSED CLOSED CLOSED OPEN X ON Max Full Stage None None Cool
OPEN OPEN OPEN X OPEN CLOSED ON Min None None None Fan Only
X=ignored by controller
Conventional Thermostat Sequence of Operation
15
Space Temperature Control Sequence of Operation
Constant Volume and Multi-Speed Fan Configuration
Normal Operation
The Symbio 700 has a single-loop (space temperature only) control sequence. The sequence is
PI-based (proportional, integral) and strives to maintain space temperature within 1F of the active
cooling and heating setpoints.
• When Space Temperature Active > Space Temp Cooling Setpoint Status, the algorithm
calculates a need for cooling capacity to be energized.
• When Space Temperature Active < Space Temp Heating Setpoint Status, the algorithm
calculates a need for heating capacity to be energized.
• When Space Temp Heating Setpoint Status ≤ Space Temperature Active ≤ Space Temp
Cooling Setpoint Status:
– The algorithm calculates a reduction in need for any active cooling or heating capacity if
ON.
– If no cooling or heating capacity is active, cooling and heating capacity remains inactive.
16 ACC-APG001A-EN
Space Temperature Control Sequence of Operation
ACC-APG001A-EN 17
Space Temperature Control Sequence of Operation
If the VVZT DAT Control Mode – Active point is set to "Auto", the VVZT control algorithm will use
the internally derived Discharge Air Temperature Setpoint Active, as described above, for all
cooling capacity output control.
If the VVZT DAT Control Mode – Active point is set to "Manual", the VVZT control algorithm will
use the Discharge Air Cooling Setpoint (Target) – Active as upper limit for the Discharge Air
Temperature Setpoint calculation. Typically this is set to a low value (i.e 50-55F) to drive longer
compressor runtimes. When this override is active, if the space temperature is 2° F below the
Space Temp Cooling Setpoint Status value or 1° F above the Space Temp Heating Setpoint
Status value, the controller will pause the override sequence until the space temperature
recovers to above the Space Temp Cooling Setpoint status.
18 ACC-APG001A-EN
General Support Sequences
Fan Setpoints with VFD-driven Fan Types
When a system is equipped with a VFD, the minimum and maximum VFD parameters can be
adjusted to tune the airflow to meet the application requirements.
In addition to this, the Symbio 700 supports setpoints that can adjust airflow as needed:
• Supply Fan Maximum Speed Setpoint
– Range: 67-100%
– Operation: This setpoint “trims” the maximum fan speed, based on the configured
maximum VFD speed
– Example: VFD Max = 60Hz
• Supply Fan Maximum Speed Setpoint @ 75% yields a maximum of 45Hz VFD output.
• Effective VFD Max (to be used in Supply Fan Minimum Speed Setpoint application)
will be set to 45Hz
• Supply Fan Minimum Speed Setpoint
– Range: 0-100%
– Operation: 0-100% over minimum to effective maximum VFD configured fan speed
– Example: VFD Min = 30Hz, Effective VFD Max = 60Hz
• Supply Fan Minimum Speed Setpoint @ 50% yields 45Hz VFD output.
• Minimum and Maximum Speed Setpoints interact to ensure that the minimum defined fan
speed at a given equipment operating condition is maintained.
ACC-APG001A-EN 19
General Support Sequences
20 ACC-APG001A-EN
Heat Pump Support Sequences
Heat Pump Switchover Valve
The Switchover Valve function is only applicable to Heat Pump units. Depending on the
refrigeration system configuration for a unit, it may have one or two switchover valves.
Additionally, some units with two switchover valves could control each valve independently
while others will control in tandem.
In normal unit operation, the Unit Mode will determine the operation of the switchover valve.
Unit Mode COOL will turn the switchover valve ON while Unit Mode HEAT will turn the
switchover valve OFF.
If the unit is in active Heat Pump Heating (switchover valve is OFF) and then enters defrost, the
switchover valve will be turned ON for the duration of defrost. When leaving active defrost, the
switchover valve transition to OFF is delayed 5 seconds.
During the defrost cycle, the Switchover Valve is turned ON, the Condenser Fan is turned OFF,
and auxiliary heat is turned ON regardless of their prior operating status while maintaining
ACC-APG001A-EN 21
Heat Pump Support Sequences
compressor operation. The defrost cycle is terminated based on the defrost termination
temperature calculation using the outdoor temperature (ODT) +47°F. The defrost termination
temperature (DTT) will be limited between 57° F and 72° F.
22 ACC-APG001A-EN
Building Automation System Support Sequences
Occupancy Mode
During expected occupied periods, the system will control to the user selected cooling and
heating setpoints.
• The unoccupied setpoint temperatures are often adjusted higher for cooling (setup) and
lower for heating (setback) to reduce building operating cost.
• Regardless of how the (occupied) fan mode is set, the supply fan mode is forced to AUTO
during unoccupied periods to reduce supply fan operating costs.
There are two mechanisms available to control when units should switch between occupied and
unoccupied modes:
• Building controllers provide signals to the unit to request occupied or unoccupied operation.
Time-of-day scheduling within building controllers typically determine when the switching
should occur.
• Stand Alone Unoccupied control is initiated by a contact closure that causes the unit to begin
unoccupied control. In this mode, the controller will use the Unoccupied Cooling and Heating
setpoints to determine capacity control needs. Stand Alone Unoccupied control is only
applicable when the unit is not being controlled by a conventional thermostat interface.
Timed Override
Exceptions to the time-of-day scheduling are required when unusual or difficult to schedule
events cause a space to become occupied during a scheduled unoccupied period. The Timed
Override function provides a mechanism for an occupant to signal the system that the space is
actually occupied and override the time-of-day schedule to provide occupied control for some
limited time period. It also provides a mechanism to return the system to unoccupied mode
when the space is no longer occupied.
There are two methods of requesting or terminating timed override on a Symbio 700 control
system:
• BAS
– Timed Override Request value can be set to 3 discrete values:
• I d l e [ 1 ] — Controller will not override Unoccupied Mode.
• O n [ 2 ] — When the value is changed from Idle to On, the controller overrides
Unoccupied Mode and the unit operates in Occupied Mode. The Occupied Bypass
Timer and the Timed Override Timer is Active is set to ‘Active’. The controller remains
in Timed Override for the duration of the Occupied Bypass Time.
• C a n c e l [ 3 ] — When value is changed from On to Cancel, the unit’s unoccupied status
is no longer overridden and the Occupied Bypass Timer will be set to 0.
• Zone Sensor Initiate/Terminate buttons – Some zone sensors have a Timed Override Initiate
and Terminate buttons.
When Timed Override is initiated by any of the above methods, the controller starts a timer using
the user selected Occupied Bypass Time to control the duration of the Timed Override event. The
range for Occupied Bypass Time is 0-240 minutes with a default of 120 minutes.
When the unit is operating in Occupied Bypass mode, the Occupied Bypass Timer duration can
be extended by initiating a Timed Override Request again. This extends the Occupied Bypass
Timer duration by the value of the user selected Occupied Bypass Time.
When Timed Override is terminated by any of the above methods, the controller will exit
Occupied Bypass and will again begin to use unoccupied control setpoints.
ACC-APG001A-EN 23
Building Automation System Support Sequences
function to prevent excessively cold discharge air from being supplied from the unit. The
sequence for VVZT systems are consistent with CVZT systems, utilizing single-speed, and full
airflow operation.
Supply Air Tempering is not applicable when a Conventional TStat is configured as the Space
Controller.
The following requirements must be met to allow Supply Air Tempering on a Staged Heat unit:
• The supply fan is ON.
• The unit is in Occupied mode.
• The unit is in any heating mode, including Heat, Emergency Heat, Morning Warmup, Max
Heat but is not actively heating OR
• The unit is in any cooling mode except night purge, but not actively cooling and cooling
capacity has been OFF for 5 minutes.
If the discharge air temperature drops to the Discharge Air Temperature Minimum Cool Limit -
Active and the Space Temperature is less than the Active Space Temp Cooling Setpoint Status –
0.5°F and if there are no stages of heat on, the Supply Air Tempering function will bring ON one
stage of available staged auxiliary heat.
N o t e : Heat Pump units will energize 1 stage of auxiliary Heat in order to meet the Supply Air
Tempering request; compressor-based heating will not be used to satisfy Supply Air
Tempering.
Once Supply Air Tempering is active, the stage of heat will be turned OFF if the Discharge Air
Temperature rises to 10°F ABOVE the Discharge Air Temperature Minimum Cool Limit - Active,
or the Space Temperature rises to the Space Temp Cooling Setpoint Status. Additionally, if the
Space Heat Control function determines that 1 or more stages of Heat are required to meet the
Space Temp Heating Setpoint Status, Tempering will be discontinued and the unit will stage
heating to meet the current space demand.
Unit Stop
The Unit Stop feature allows for immediate shutdown of all devices in the equipment when
initiated. When a Unit Stop request is received, the following actions are taken:
• All equipment control binary outputs are de-energized
– Indoor fan
– Compressors
– Condenser fans
– Unloader solenoids
– Heat stages
• All equipment control analog outputs are set to their minimum/off command values.
• All communicating devices, such as Supply fan VFD, are commanded to their Off state.
• All control algorithms are initialized to their normal startup values and held until the stop
request is released.
The Unit Stop request can be initiated from the following sources:
• Unit Stop Command
• Equipment Shutdown Input
• Emergency Override BAS
• Phase Monitor
If a Unit Stop is initiated, the source of the Unit Stop can be determined by the Unit Stop Source
Point and other status/diagnostic points.
24 ACC-APG001A-EN
Building Automation System Support Sequences
ACC-APG001A-EN 25
Building Automation System Support Sequences
• Exhaust mode
If more than one mode is requested at the same time, the Pressurize request will have priority
followed by Purge, and then Exhaust. When Any Ventilation Override mode is active, all heating
and cooling is turned off. For the case where the unit is required to turn Off via hardwired
interface, the Equipment Shutdown input is used.
Emergency Override
All units with Symbio 700 support the remote Emergency Override Command functionality.
Within this point, there are addition enumerations versus the hardware Ventilation Override
interface:
• 1 = EMERG_NORMAL
• 2 = EMERG_PRESSURIZE
• 3 = EMERG_DEPRESSURIZE
• 4 = EMERG_PURGE
• 5 = EMERG_SHUTDOWN
• 6 = EMERG_FIRE
Pressurize, Depressurize, and Purge map to their respective Ventilation Override Modes directly. ,
Emerg_Shutdown and Emerg_Fire are unique to Emergency Override. Both of those are treated
as a remote shutdown request for the equipment.
Equipment Operation
Emergency and Ventilation Override requests/actions will take priority over normal equipment
timing events, such as compressor minimum ON/OFF/Inter-stage timers.
During an Emergency or Ventilation Override sequence, all temperature control algorithms are
initialized to an inactive state until the Emergency or Ventilation Override request is cleared. For
each override request, the unit will operate in a pre-determined state until override requests are
cleared.
For detailed unit operation during Emergency or Ventilation Override, refer to the Appendix
section of this document.
26 ACC-APG001A-EN
Service Test Mode
Service Test Mode can be used to initiate certain operating modes of the equipment. Refer to the
following sections for more details associated with this feature.
ACC-APG001A-EN 27
Service Test Mode
28 ACC-APG001A-EN
Service Test Mode
ACC-APG001A-EN 29
Service Test Mode
30 ACC-APG001A-EN
Diagnostics
Device Tracker
Symbio 700 will keep statistical data of the unit for component starts and component run times
(in hours) for the following unit components:
• Compressor 1
• Compressor 2
• Condenser Fan 1
• Condenser Fan 2
• Supply Fan
• Electric Heat Stage 1
• Electric Heat Stage 2
• Filter (Runtime only)
If the Filter Runtime hours exceed the value set by the user for the Filter Runtime Hours Setpoint,
the Symbio 700 controller activates the Diagnostic: Maintenance Required point.
If for any reason it is required to reset the component statistical data, the Run Time Reset or
Starts Reset points can be accessed through the Symbio Service and Installation mobile app.. If
the reset points are set to Reset, the Component Run Time and Starts are reset to 0 and the
associated reset points are set back to inactive. In the case of the Diagnostic: Maintenance
Required point, it will also be reset to Inactive if Filter Timer Reset point is set.
ACC-APG001A-EN 31
Diagnostics
• The “Diagnostic: Compressor X Proving Lockout” diagnostic point is activated and the alarm
output is activated.
32 ACC-APG001A-EN
Diagnostics
Reset Diagnostic
A Reset Diagnostic function is responsible for ensuring that the Reset Diagnostic point is set to
the right value under normal application control. The below sections describes how the Reset
Diagnostic point is set to Active and Inactive.
ACC-APG001A-EN 33
Troubleshooting
The Symbio 700 controller provides system shutdown, operational default operation, and
communication error handling of the Odyssey unit. The list of fault conditions below will stop
normal operation or change the operation of the unit to a default condition. Faults are indicated
in the Active Alarm menu of the onboard user interface and the Symbio Service and Installation
mobile app.
Sensor Fault
On Symbio 700, if a sensor value goes outside of its minimum or maximum range, the point goes
into an Alarm State. If the point in the Alarm State, we consider the sensor failed and take the
following actions:
34 ACC-APG001A-EN
Troubleshooting
Space Humidity Sensor Annunciated in the Active Alarm list. Auto Reset
Space CO2 Sensor Annunciated in the Active Alarm list. Auto Reset
Compressor Fault
Symbio 700 supports compressor safety functionality to keep the compressors from operating in
an undesirable condition. If a compressor safety failure occurs, the following actions occur:
LPC Lockout For specific operation associated with the LPC Manual Reset
diagnostics, refer to the Compressor Protection
section of this document.
Proving Lockout For specific operation associated with the proving Manual Reset
diagnostics, refer to the Compressor Protection
section of this document.
Contactor Failure For specific operation associated with the proving Manual Reset
diagnostics, refer to the Compressor Protection
section of this document.
VFD Fault
The following failures are derived either through direct data monitoring from the Modbus device,
or through a combination of Modbus data and additional failure criteria:
Diagnostic: VFD Fault When Active All unit functions will be Auto Reset
Supply Fan – 1 shut down immediately
Diagnostic: VFD Supply When Active All unit functions will be Auto Reset
Fan Ground Fault – 1 shut down immediately
Diagnostic: VFD Supply When Active All unit functions will be Auto Reset
Fan Motor Current shut down immediately
Overload – 1
Diagnostic: VFD Supply When Active All unit functions will be Auto Reset
Fan Short Circuit – 1 shut down immediately
ACC-APG001A-EN 35
Troubleshooting
Defrost Fault
The below list of diagnostics are associated with the Demand Defrost Function.
36 ACC-APG001A-EN
Troubleshooting
ACC-APG001A-EN 37
Appendix A
Supply Fan
Multi-Speed/VFD
Table 10. Multi-speed minimum supply fan speeds
Off 0%
Variable Speed/VFD
Table 11. Variable speed minimum supply fan speeds
Off 0%
Compressor Staging
Thermostat Staging
For equipment staging response to a conventional thermostat signals, refer to the Conventional
Thermostat sequence of operation above.
38 ACC-APG001A-EN
Appendix A
N o t e : If Defrost is active on Heat Pump units, then Condenser Fan Output 1 OFF.
Table 18. Dual condenser fan - shared airstream (cooling only)
Table 19. Dual condenser fan - independent airstream (cooling only and heat pump)
ACC-APG001A-EN 39
Appendix A
Notes:
• If Defrost is active on Heat Pump refrigeration circuit 1, then unit response is
Condenser Fan Output 1 OFF.
• If Defrost is active on Heat Pump refrigeration circuit 2, then unit response is
Condenser Fan Output 2 OFF.
Electric Heat
CVZT & VVZT
Table 20. Electric heat staging
40 ACC-APG001A-EN
Appendix A
Table 21. Odyssey supported diagnostics and alarm relay functionality (continued)
Inputs Outputs
2 = EMERG_
ON 100 0 0 0 Fan Only
PRESSURIZE
3 = EMERG_
OFF 0 0 0 0 Fan Only
DEPRESSURIZE
ACC-APG001A-EN 41
Appendix A
42 ACC-APG001A-EN
Notes
ACC-APG001A-EN 43
Trane - by Trane Technologies (NYSE: TT), a global innovator - creates comfortable, energy efficient
indoor environments for commercial and residential applications. For more information, please visit
trane.com or tranetechnologies.com.
Trane has a policy of continuous product and product data improvements and reserves the right to change design and specifications without
notice. We are committed to using environmentally conscious print practices.