Temperature Controller E5Cwt: Ordering Information
Temperature Controller E5Cwt: Ordering Information
Ordering Information
E5CWT E5CWT
■ Ratings
Supply voltage 110/220 VAC,50/60Hz
Operating voltage range 85% to 110% of rated supply voltage
Power consumption 110/220 VAC:Approx,8VA(2 alarm)
:Approx,7VA(1 alarm)
Input Thermocouple(K/J) or platinum resistance thermometer(Pt100)
Control output Contact output:SPST-NO;3 A at 250 VAC (resistive load)
Voltage output(for SSR):20 mA at 12 VDC(with short-circuit protection
Control mode ON/OFF or PID control with auto-tuning
Alarm output Relay output: independent SPST-NO contacts;1 A at 250 VAC(resistive load)
Setting method Digital setting via Up and Down Keys
Display method Digital (PV color-red, SV color-green)
■ Characteristics
Setting and display ±0.5% full scale ±1 digit max.(The setting and display temperatures coincide
because there is no relative error between them.)
Hysteresis 0.2% of full scale (during ON/OFF operation)
Proportional band 0% to 99%
Integral time(Reset time) 0 to 99 minutes
Derivative time(Rate time) 0 to 9.9 minutes
Anti-reset windup(ARW) 0% to 99%
Alarm output setting range 0 to full-scale for all alarm modes except the absolute-value alarm mode
Proportional period 2s/20s (switch-selectable)
Sampling period 500ms(Output change period: 2s, Indication change period: 2s)
Insulation resistance 20MΩ min.(at 500 VDC)
Dielectric strength 2,000 VDC, 50/60 Hz for 1 minute between current-carrying terminals of different
polarity
Vibration Malfunction durability: 2 to 55 Hz,2G 10 minutes each in X,Y, and Z directions
Mechanical durability: 10 to 55 Hz,0.75 mm double 2hrs each in X,Y, and Z
directions
Shock Malfunction durability: 100m/s2 3 times each in 6 directions
Mechanical durability: 300m/s2 3 times each in 6 directions
Life expectancy Mechanical:10,000,000 operations min.(Contact Output Types)
Electrical:100,000 operations min.( Contact Output Types)
Ambient operating temperature -10。 To 55 (with no icing)
。
Ambient storage temperature -25 To 65 (with no icing)
Ambient humidity 35% to 85%(with no condensation)
Enclosure rating Front Panel: IEC lP50
Rear Panel : IEC IP20
Terminals : IEC IP00
E5CWT E5CWT
E5CWT E5CWT
Installation
■Wiring
The voltage output(20mA,12VDC)is not electrically insulated from internal circuits.
1 Alarm Type
2 Alarm Type
Note: The voltage output(20mA at 12VDC)is not insulated from the internal circuitry. When using a
thermocouple temperature sensor that incorporates a ground terminal, do not connect terminal
7 or 8 to the ground terminal or accurate temperature control will not be possible due to the
short-circuited current that will flow between the ground terminal and terminal 7 or 8.