Stair Check

This document provides design information and allowable load values for specific anchor models installed in grout-filled masonry walls. It includes two tables with specifications for nominal anchor diameter, embedment depth, critical and minimum spacing and edge distances, allowable tension and shear loads, and load reduction factors. Installation is allowed between the minimum and critical spacing and edge distance values listed, with load values reduced using the specified factors if less than critical. Combined loading equations are also provided.

Uploaded by

dnl_vicars
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
49 views1 page

Stair Check

This document provides design information and allowable load values for specific anchor models installed in grout-filled masonry walls. It includes two tables with specifications for nominal anchor diameter, embedment depth, critical and minimum spacing and edge distances, allowable tension and shear loads, and load reduction factors. Installation is allowed between the minimum and critical spacing and edge distance values listed, with load values reduced using the specified factors if less than critical. Combined loading equations are also provided.

Uploaded by

dnl_vicars
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

DESIGN INFORMATION IN MASONRY

Table 30 — A
 llowable tension loads for Hilti KH-EZ, KH-EZ P, KH-EZ PM, KH-EZ PL, KH-EZ C
and KH-EZ CRC installed in grout-filled masonry walls (lb)1,2,3,4,5
Spacing Edge distance
Nominal
anchor Load Critical - ccr
diameter Embedment Loads @ Critical - scr Minimum - smin reduction Minimum- cmin
in. in.6 ccr and scr in.7 in.7 factor at smin8 in.9
1-5/8 53010 2 0.70
1/4 4 4
2-1/2 91011 4 1.00
1-5/8 53511 4 2 0.70
3/8 2-1/2 895 4
6 4 0.80
3-1/4 1,210
2-1/4 710 4 2
1/2 3 1,110 0.60 4
8 4
4-1/4 1,515
3-1/4 1,155
5/8 10 4 0.60 4
5 1,735
4 1,680
3/4 12 4 0.60 4
6-1/4 2,035

Table 31 — A
 llowable shear loads for Hilti KH-EZ, KH-EZ P, KH-EZ PM, KH-EZ PL, KH-EZ C and KH-EZ CRC installed
in grout-filled masonry walls (lb)1,2,3,4,5
Spacing Edge distance
Nominal Load reduction factor at cmin
anchor Load
diameter Embedment Load at ccr Critical - scr Minimum - smin reduction Critical - ccr Minimum - cmin perpendicular parallel
in. in.6 and scr in.7 in.7 factor at smin8 in.9 in.9 to edge to edge
1-5/8 67510 1.00 1.00
1/4 4 4 1.00 4 4
2-1/2 840 11
1.00 1.00
1-5/8 1,14011 0.61 1.00
3/8 2-1/2 1,165 6 4 0.94 6 4 0.70 1.00
3-1/4 1,190 0.70 1.00
2-1/4 1,845 6" 0.94 0.50 1.00
1/2 3 2,055 8 4 0.88 8 4 0.45 0.94 combined = 0.84
4-1/4 2,745 0.40 0.89 adjusted =
2x0.84x2745=4611
3-1/4 3,040 0.36 0.82 use this
5/8 10 4 0.36 10 4
5 3,485 6" 0.57 0.34 0.92
combined = 0.52
4 3,040 0.36 0.82 adjusted =
3/4 10 4 0.36 10 4
6-1/4 3,485 0.34 0.92 2x0.52x3485=3.6
1 All values are for anchors installed in fully grouted masonry with minimum masonry prism strength of 1,500 psi. Concrete masonry units may be lightweight, medium-weight or normal-
weight.
2 Anchors may not be installed within one inch in any direction of a vertical joint.
3 Linear interpolation of load values between minimum spacing smin and critical spacing scr and between minimum edge distance cmin and critical edge distance
ccr is permitted. 3.7k
( )( )
Tapplied Vapplied Tapplied 5/3
Vapplied 5/3

4 For combined loading: For 1/4-in. - + ≤ 1 For 3/8- through 3/4-in. - + ≤ 1


Tallowable Vallowable Tallowable Vallowable
5 See Figure 5 on Page 21 of this document for anchor locations for anchor locations.
6 Embedment depth is measured from the outside face of the concrete masonry embedment.
7 Critical spacing scr is the anchor spacing where full load values may be used. The minimum spacing smin is the minimum spacing for which values are available and installation is
recommended. Spacing is measured from the center of one anchor to the center of the adjacent anchor.
2x1/2"Øx5" kwik hus-ez @ 6" ga
8 Load reduction factors are multiplicative, both spacing and edge distance load reduction factors must be considered. Load values for anchors installed at less than ccr or scr must be
centered in grout filled cells each
multiplied by the appropriate load reduction factor based on actual edge distance (c) or spacing (s).
9 The critical edge distance ccr
end of channel
is the edge distance where full load values may be used. The minimum edge distance c is the minimum edge distance for which values are available and
min
installation is recommended. For tension, ccr equals cmin. Edge distance is measured from the center of the anchor to the closest edge.
10 Load values must be reduced by 21% for installations within 1-1/4 inches of the bed joint.