Areva P139 Vol.2
Areva P139 Vol.2
Areva P139 Vol.2
P139/EN M/R-h8-A
Technical Manual
Volume 2 of 2
P139
A1 Function Groups
CS Cyber Security
DVICE Device
IDMT4
MP Motor protection
PC PC link
SCDD1
SCDD2
SFMON Self-monitoring
A2 Internal Signals
ARC: Trip time HSR elaps. Vol. 1, Fig. 3-181, (p. 3-245)
Vol. 1, Fig. 3-182, (p. 3-246)
Vol. 1, Fig. 3-183, (p. 3-247)
Vol. 1, Fig. 3-184, (p. 3-248)
Vol. 1, Fig. 3-185, (p. 3-248)
ARC: Trip time TDR elaps. Vol. 1, Fig. 3-182, (p. 3-246)
Vol. 1, Fig. 3-183, (p. 3-247)
Vol. 1, Fig. 3-184, (p. 3-248)
Vol. 1, Fig. 3-185, (p. 3-248)
COMM1: Motor rel. mon. trg. Vol. 1, Fig. 3-352, (p. 3-444)
MAIN: Bl. timer st. IN,neg Vol. 1, Fig. 3-85, (p. 3-130)
MAIN: Sel. meas. loop A-B Vol. 1, Fig. 3-118, (p. 3-165)
MAIN: Sel. meas. loop A-G Vol. 1, Fig. 3-118, (p. 3-165)
MAIN: Sel. meas. loop B-C Vol. 1, Fig. 3-118, (p. 3-165)
MAIN: Sel. meas. loop B-G Vol. 1, Fig. 3-118, (p. 3-165)
MAIN: Sel. meas. loop C-A Vol. 1, Fig. 3-118, (p. 3-165)
MAIN: Sel. meas. loop C-G Vol. 1, Fig. 3-118, (p. 3-165)
SOTF: Bl. ARC by close cmd Vol. 1, Fig. 3-171, (p. 3-231)
A3 Glossary
Modules
A: Communication module
L: MMI module
P: Processor module
T: Transformer module
Symbols
Symbol Description
Components of a symbol
A symbol consists of a contour or contour combination and one or
more qualifiers.
Control block
A control block contains an input function common to several
symbols. It is used for the collective setting of several trigger
elements, for example.
D5Z08X3B
Output block
An output block contains an output function common to several
symbols.
D5Z08X4B
MAIN:
The 6 digits in square brackets represent the address under
Inom device
[ 010 003 ] which the function shown in the text is implemented.
D5Z08X5B
5.0
The text below the symbol assigns the corresponding unit or
1.0: 1.0 A meaning to each setting.
5.0: 5.0 A
D5Z08X6B
Static input
Only the state of the binary input variable is effective.
D5Z08XBB
Dynamic input
Only the transition from value 0 to value 1 is effective.
D5Z08XAB
Negation of an output
The value up to the border line is negated at the output.
D5Z08X8B
Negation of an input
The input value is negated before the border line.
D5Z08X7B
D5Z08X9B
AND element
& The output variable will be 1 only if all input variables are 1.
D5Z08XCB
OR element
The output variable will be 1 only if at least one input variable is
D5Z08XDB 1.
Threshold element
The output variable will be 1 only if at least two input variables
D5Z08XEB are 1. The number in the symbol may be replaced by any other
number.
(m out of n) element
The output variable will be 1 only if just one input variable is 1.
D5Z08XFB
The number in the symbol may be replaced by any other number
if the number of inputs is increased or decreased accordingly.
Delay element
t1 t2
The transition from value 0 to 1 at the output occurs after a time
D5Z08XGB delay of t1 relative to the corresponding transition at the input.
The transition from value 1 to 0 at the output occurs after a time
delay of t2 relative to the corresponding transition at the input.
t1 and t2 may be replaced by the actual delay values (in seconds
or strobe ticks).
Monostable flip-flop
1 The output variable will be 1 only if the input variable changes to
100ms
D5Z08XHB 1. The output variable will remain 1 for 100 ms, regardless of the
duration of the input value 1 (non-retriggerable).
Without a 1 in the function block, the monostable flip-flop is
retriggerable.
The time is 100 ms in this example, but it may be changed to any
other duration.
Analog-digital converter
An analog input signal is converted to a binary signal.
D5Z08XJB
Subtractor
The output variable is the difference between the two input
D5Z08XKB variables.
A summing element is obtained by changing the minus sign to
a plus sign at the symbol input.
Memory, general
Storage of a binary or analog signal.
D5Z08XMB
Non-stable flip-flop
When the input variable changes to 1, a pulse sequence is
D5Z08XNB generated at the output.
The ! to the left of the G indicates that the pulse sequence starts
with the input variable transition (synchronized start).
If there is a ! to the right of the G, the pulse sequence ends with
the ending of the 1 signal at the input (synchronized stop).
Amplifier
The output variable is 1 only if the input variable is also 1.
D5Z08XOB
Counter
+
At the + input the input variable transitions from 0 to 1 are
R
D5Z08YFB counted and stored in the function block.
At the R(eset) input a transition of the input variable from 0 to 1
resets the counter to 0.
D5Z08YGB
D5Z08XRB
Phase identifiers for current inputs:
● for A: A1 and A2
● for B: B1 and B2
● for C: C1 and C2
● for N: N1 and N2
Item identifiers
● for current transformers:
o for A: T1
o for B: T2
o for C: T3
o for N: T4
● for voltage transformer 1:
o for A: T5
o for B: T6
o for C: T7
o for N: T8
● for VG-N transformer: T90
● for voltage transformer 2:
o for A: T15
Change-over contact
with item identifier
D5Z08XSB
Special symbol
Output relay in normally-energized arrangement (“closed-circuit
D5Z08XTB operation”).
PC interface
−12V
with pin connections
9
+12V 1
0V 5
RXD 3
V24
TXD 2
D5Z08XVB
Multiplier
The output variable is the result of the multiplication of the two
D5Z08XWB input variables.
Divider
The output variable is the result of the division of the two input
D5Z08XXB variables.
Comparator
The output variable becomes 1 only if the input variable(s) are
equal to the function in the function block.
D5Z08XYB
Formula block
The output variable becomes 1 only if the input variable(s) satisfy
2.5
the equation in the function block
D5Z08XZB
Symbols Used
Symbol Meaning
t Time duration
V̲ Complex voltage
I Electrical current
I̲ Complex current
Z̲ Complex impedance
f Frequency
δ Temperature in °C
Σ Sum, result
α Angle
τ Time constant
ΔT Temperature difference in K
A4 Telecontrol Interfaces
A4.1.1 Interoperability
This application-based standard (companion standard) specifies parameter sets
and other options from which subsets are to be selected in order to implement
specific telecontrol systems. Certain parameters such as the number of bytes
(octets) in the COMMON ADDRESS of the ASDU are mutually exclusive. This
means that only one value of the defined parameter is allowed per system. Other
parameters, such as the listed set of different process information in the
command and monitor direction, permit definition of the total number or of
subsets that are suitable for the given application. This section combines the
parameters given in the previous sections in order to facilitate an appropriate
selection for a specific application. If a system is made up of several system
components supplied by different manufacturers, then it is necessary for all
partners to agree on the selected parameters.
The boxes for the selected parameters should be checked [see National Preface
of EN 60870-5-101].
The overall definition of a system may also require individual selection of certain
parameters for specific parts of a system such as individual selection of scaling
factors for individually addressable measured values.
[✓] Structured
[✓] Unstructured
Frame Length
[✓] <10> = Measured value, normalized value with time tag M_ME_TA_1
[✓] <12> = Measured value, scaled value with time tag M_ME_TB_1
[ ] <14> = Measured value, short floating point value with time tag M_ME_TC_1
[✓] <18> = Packed start events of protection equipment with time ME_EP_TB_1
tag
[ ] <50> = Set point command, short floating point value C_SE_NC_1
[ ] <112> = Parameter of measured value, short floating point value P_ME_NC_1
[ ] <122> = Call directory, select file, call file, call section F_SC_NA_1
[✓] Global
[ ] Direct set point command [ ] Select and execute set point
transmission command
[ ] Short pulse duration (Execution duration determined by a system parameter in the
outstation)
[ ] Long pulse duration (Execution duration determined by a system parameter in the
outstation)
A4.2.1 Interoperability
Note: EIA RS 485 defines the loads in such a way that 32 of such loads can be
operated on one line. For detailed information see EIA RS 485, Section 3.
INF Description
[✓] <19> LED reset (021 010) MA IN: Res et in dicat. USER
[✓] <20> Blocking of monitor direction (037 075) C OMM1 : Si g./meas .val. blo ck.
[✓] <32> Measurand supervision I (040 087) MCMON: Mea s. circ. I faulty
[✓] <33> Measurand supervision V (038 023) MCMON: Mea s. circ. V fault y
[✓] <35> Phase sequence supervision (038 049) MCMON: Ph ase se qu. V f aul ty
[✓] <36> Trip circuit supervision (041 200) SFMON: Rel ay K xx faulty
(The message content is
formed from the OR operation
of the individual signals.)
[✓] <38> VT fuse failure (004 061) MA IN: M.c. b. trip V EXT
[✓] <47> Group alarm (004 065) MA IN: Blocke d/f aul ty
[✓] <51> Earth fault forward, i.e. line (041 088) MA IN: Gnd. f aul t f orw./LS
[✓] <52> Earth fault reverse, i.e. busbar (041 089) MA IN: Gnd. f aul t backw ./BS
[✓] <68> General trip (036 071) MA IN: Gen . tri p command 1
[✓] <73> Fault location X in ohms (004 029) F T_DA : F aul t re act., pri m.
[✓] <74> Fault forward/line (036 018) SCDD1 : F aul t P forw ard
[✓] <77> Teleprotection signal received (037 029) P SI G: R ece ive (s ignal )
[✓] <84> General starting (040 000) MA IN: Gen eral startin g
[✓] <90> Trip I> (040 042) MA IN: Tri pSi g. tI>/tI refP >
[✓] <91> Trip I>> (040 011) D TOC : Trip s ignal tI>2
[✓] <92> Trip IN> (040 043) MA IN: Tri pSig tIN>/tIre fN>
[✓] <93> Trip IN>> (040 028) DTOC : Tri p sign al tIN>2
[✓] <147> Measurands IN, VEN (005 011) MA IN: Current Σ ( IP ) p.u.
(only with setting (005 013) MAI N: V olt. Σ( VP G)/√3 p.u.
C OM M1 : Tran sm.en ab.cycl
.dat to ASDU 3.4 per IEC)
[✓] <148> Measurands IA,B,C, VA,B,C, P, Q, f (005 041) MAI N: Cu rre nt A p.u.
(only with setting (006 041) MAIN: Curren t B p.u .
C OMM1 : Transm.e nab.cycl (007 041) MAI N: Cu rre nt C p. u.
.dat to ASDU 9 per IEC) (005 043) MAIN: V ol tage A-G p.u .
(006 043) MA IN: Voltage B-G p.u .
(007 043) MA IN: Voltage C-G p. u.
(004 051) MA IN: Act ive power P p.u.
(004 053) MAIN: Re ac. powe r Q p.u.
(004 040) MAIN: Fre que ncy f
INF Description
INF Description
[✓] <17> Teleprotection on/off (015 004) P SIG: Gen eral en abl e USER
[✓] <19> LED reset (021 010) MA IN: Res et in dicat. U SER
[✓] <23> Activate characteristic 1 (003 060) P SS: Param .s u bs. se l. USE R
(Switches
PSS: Pa ram.su bs. se l .
USE R to Parameter subset
1.)
[✓] <24> Activate characteristic 2 (003 060) P SS: Param .s u bs. se l. USE R
(Switches
PSS: Pa ram.su bs. se l .
USE R to Parameter subset
2.)
[✓] <25> Activate characteristic 3 (003 060) P SS: Param .s u bs. se l. USE R
(Switches
PSS: Pa ram.su bs. se l .
USE R to Parameter subset
3.)
[✓] <26> Activate characteristic 4 (003 060) P SS: Param .s u bs. se l. USE R
(Switches
PSS: Pa ram.su bs. se l .
USE R to Parameter subset
4.)
INF Description
A4.2.1.3.6 Miscellaneous
Measured values are transmitted both with ASDU 3 and ASDU 9. As defined in
Sec. 7.2.6.8, the maximum MVAL can be either 1.2 or 2.4 times the rated value.
In ASDU 3 and ASDU 9, different ratings may not be used; in other words, there is
only one choice for each measurand.
1.2 or 2.4
● Type of bay
o A – Feeder bays
o L – Bus sectionalizer bay
o Q –Bus coupler bay
o K – Bus coupler and sectionalizer bay
o M – Busbar measurement bay
o E – Busbar grounding bay
o X – Other bay type
● Number of busbars
o 1 – Single busbar
o 2 – Double busbar
o 9 – Without busbar / other configurations
● Equipment
o 1 – Bays with switch truck or withdrawable switchgear assembly
o 2 – Bays with two circuit breakers or switch disconnectors on switch
trucks or withdrawable switchgear assembly
o 3 – Bays with stationary switchgear units
o 5 – Bays with stationary switchgear units and three-position disconnector
o 9 – Other bay types
Key
Bay Type No.: This number indicates the value to be set at MAIN: Type of
b ay (Menu branch Par/Conf) in order to configure the unit for the selected bay
type.
The interlock equations are stored at substation control level, not at unit level.
A5.2.1.1 Bay type No. 2: Feeder bay with circuit breaker, single busbar
A11.100.R01
Close(d) U A04 / Q0
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.1.2 Bay type No. 3: Feeder bay with circuit breaker, single busbar
A11.100.R02
Switchgear
Control O/C Interlock equation
unit
X0 Open (Q0=0)
Close(d) (Q0=0)
Tab. A5-5: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
X0 Open (Q0=0)
Close(d) (Q0=0)
Tab. A5-6: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.3 Bay type No. 546: Feeder bay with circuit breaker, single busbar, direct
motor control
A11.101.M03
Switchgear
Control O/C Interlock equation
unit
Q8 Close(d) (X0=0)
X0 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q8 Close(d) (X0=0)
X0 Open (Q0=0)
A5.2.1.4 Bay type No. 4: Feeder bay with circuit breaker, single busbar
A11.101.R01
Close(d) U A04 / Q0
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.1.5 Bay type No. 5: Feeder bay with circuit breaker, single busbar
A11.101.R02
Switchgear
Control O/C Interlock equation
unit
X0 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
X0 Open (Q0=0)
A5.2.1.6 Bay type No. 6: Feeder bay with circuit breaker, single busbar
A11.101.R03
Switchgear
Control O/C Interlock equation
unit
Q8 Close(d) (X0=0)
X0 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q8 Close(d) (X0=0)
X0 Open (Q0=0)
A5.2.1.7 Bay type No. 523: Feeder bay with circuit breaker, single busbar
A11.108.R01
Close(d) U A04 / Q0
Close(d) U A06 /
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.1.8 Bay type No. 549: Feeder bay with circuit breaker, single busbar, direct
motor control
A11.109.M03
Close(d) U B02 /
Switchgear
Control O/C Interlock equation
unit
Q8 Close(d) (X0=0)
X0 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q8 Close(d) (X0=0)
X0 Open (Q0=0)
A5.2.1.9 Bay type No. 244: Feeder bay with circuit breaker, single busbar
A11.109.R01
Close(d) U A04 / Q0
Close(d) U C02 /
Tab. A5-25: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.1.10 Bay type No. 544: Feeder bay with circuit breaker, single busbar
A11.109.R03
Close(d) U B02 /
Tab. A5-28: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q8 Close(d) (X0=0)
X0 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q8 Close(d) (X0=0)
X0 Open (Q0=0)
A5.2.1.11 Bay type No. 567: Feeder bay with circuit breaker, single busbar
A11.132.R01
Close(d) U B04 /
Tab. A5-31: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.1.12 Bay type No. 521: Feeder bay with circuit breaker, single busbar
A11.134.R02.1
Q0
Close(d) U A04 /
Q81
Q1 (DEV03) Open U A05 K A05 Q1
Q82
Close(d) U A06 K A06
Close(d) U B02 /
Close(d) U B04 /
Tab. A5-34: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(X0=X) & /(Q1=X) & (Q82=0) & /(FctBl1=I) & /(FctBl2=I)
Q1 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(X0=X) & /(Q1=X) & (Q82=0) & /(FctBl1=I) & /(FctBl2=I)
Q1 Open (Q0=0)
A5.2.1.13 Bay type No. 519: Feeder bay with circuit breaker, single busbar
A11.135.R02.1
Q82
Close(d) U A06 K A06
Close(d) U B02 /
Close(d) U B04 /
Close(d) U B06 /
Tab. A5-37: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(X0=X) & /(Q1=X) & (Q15=0) & (Q82=0) & /(FctBl1=I) & /(FctBl2=I)
Q1 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(X0=X) & /(Q1=X) & (Q15=0) & (Q82=0) & /(FctBl1=I) & /(FctBl2=I)
Q1 Open (Q0=0)
A5.2.1.14 Bay type No. 7: Feeder bay with switch disconnector, single busbar
A11.200.R01
Close(d) U A04 / Q0
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.1.15 Bay type No. 8: Feeder bay with switch disconnector, single busbar
A11.200.R02
Switchgear
Control O/C Interlock equation
unit
X0 Open (Q0=0)
Close(d) (Q0=0)
Tab. A5-44: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
X0 Open (Q0=0)
Close(d) (Q0=0)
Tab. A5-45: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.16 Bay type No. 9: Feeder bay with switch disconnector, single busbar
A11.201.R01
Close(d) U A04 / Q0
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.1.17 Bay type No. 10: Feeder bay with switch disconnector, single busbar
A11.201.R02
Switchgear
Control O/C Interlock equation
unit
X0 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
X0 Open (Q0=0)
A5.2.1.18 Bay type No. 11: Feeder bay with switch disconnector, single busbar
A11.201.R03
Switchgear
Control O/C Interlock equation
unit
Q8 Close(d) (X0=0)
X0 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q8 Close(d) (X0=0)
X0 Open (Q0=0)
A5.2.1.19 Bay type No. 12: Feeder bay with switch disconnector / fuse unit, single
busbar
A11.400.R01
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.1.20 Bay type No. 13: Feeder bay with switch disconnector / fuse unit, single
busbar
A11.400.R02
Switchgear
Control O/C Interlock equation
unit
X0 Open (Q0=0)
Close(d) (Q0=0)
Tab. A5-59: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
X0 Open (Q0=0)
Close(d) (Q0=0)
Tab. A5-60: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.21 Bay type No. 14: Feeder bay with switch disconnector / fuse unit, single
busbar
A11.401.R01
Q8
Close(d) U A06 /
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.1.22 Bay type No. 15: Feeder bay with switch disconnector / fuse unit, single
busbar
A11.401.R02
Q8
Close(d) U A06 /
Switchgear
Control O/C Interlock equation
unit
X0 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
X0 Open (Q0=0)
A5.2.1.23 Bay type No. 16: Feeder bay with switch disconnector / fuse unit, single
busbar
A11.401.R03
Q8
Close(d) U A06 K A06
Switchgear
Control O/C Interlock equation
unit
Q8 Close(d) (X0=0)
X0 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q8 Close(d) (X0=0)
X0 Open (Q0=0)
A5.2.1.24 Bay type No. 17: Feeder bay with other switchgear unit, single busbar
A11.900.R01
X0
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-71: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-72: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.25 Bay type No. 504: Feeder bay with other switchgear unit, single busbar
A11.901.R00
Close(d) U A04 /
BB1
Close(d) U A06 /
Q8
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-74: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-75: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.26 Bay type No. 541: Feeder bay with circuit breaker, single busbar
A13.104.R01
Close(d) U A04 / Q0
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.1.27 Bay type No. 18: Feeder bay with circuit breaker, single busbar, direct
motor control
A13.105.M03
Switchgear
Control O/C Interlock equation
unit
Q1 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q1 Open (Q0=0)
A5.2.1.28 Bay type No. 19: Feeder bay with circuit breaker, single busbar
A13.105.R01
Close(d) U A04 / Q0
Close(d) U A06 /
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.1.29 Bay type No. 20: Feeder bay with circuit breaker, single busbar
A13.105.R02
Close(d) U A06 /
Switchgear
Control O/C Interlock equation
unit
Q1 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q1 Open (Q0=0)
A5.2.1.30 Bay type No. 21: Feeder bay with circuit breaker, single busbar
A13.105.R03
Switchgear
Control O/C Interlock equation
unit
Q1 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q1 Open (Q0=0)
A5.2.1.31 Bay type No. 557: Feeder bay with circuit breaker, single busbar
A13.106.R03
Q0
Close(d) U A04 K A04
Q9
Q9 (DEV03) Open U A05 K A05
Switchgear
Control O/C Interlock equation
unit
Q1 Open (Q0=0)
Close(d) (Q0=0)
Q9 Open (Q0=0)
Close(d) (Q0=0)
Tab. A5-92: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q1 Open (Q0=0)
Close(d) (Q0=0)
Q9 Open (Q0=0)
Close(d) (Q0=0)
Tab. A5-93: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.32 Bay type No. 22: Feeder bay with circuit breaker, single busbar, direct
motor control
A13.107.M04
Q0
Close(d) U A04 K A04
Q9
Q9 (DEV03) Open U A05 K A05
Q8
Close(d) U A06 K A06
Switchgear
Control O/C Interlock equation
unit
Q1 Open (Q0=0)
Close(d) (Q0=0)
Q8 Close(d) (Q9=0)
Q9 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q1 Open (Q0=0)
Close(d) (Q0=0)
Q8 Close(d) (Q9=0)
Q9 Open (Q0=0)
A5.2.1.33 Bay type No. 23: Feeder bay with circuit breaker, single busbar
A13.107.R01
Q0
Close(d) U A04 /
Q9
Q9 (DEV03) Open U A05 /
Q8
Close(d) U A06 /
Close(d) U B02 /
Tab. A5-97: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.1.34 Bay type No. 24: Feeder bay with circuit breaker, single busbar
A13.107.R03
Q0
Close(d) U A04 K A04
Q9
Q9 (DEV03) Open U A05 K A05
Q8
Close(d) U A06 K A06
Close(d) U B02 /
Tab. A5-100: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q1 Open (Q0=0)
Close(d) (Q0=0)
Q9 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q1 Open (Q0=0)
Close(d) (Q0=0)
Q9 Open (Q0=0)
A5.2.1.35 Bay type No. 25: Feeder bay with circuit breaker, single busbar
A13.107.R04
Q0
Close(d) U A04 K A04
Q9
Q9 (DEV03) Open U A05 K A05
Q8
Close(d) U A06 K A06
Switchgear
Control O/C Interlock equation
unit
Q1 Open (Q0=0)
Close(d) (Q0=0)
Q8 Close(d) (Q9=0)
Q9 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q1 Open (Q0=0)
Close(d) (Q0=0)
Q8 Close(d) (Q9=0)
Q9 Open (Q0=0)
A5.2.1.36 Bay type No. 508: Feeder bay with circuit breaker, single busbar
A13.111.R03
Close(d) U B02 /
Tab. A5-106: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & (Q8=0) & (Q15=0) & /(FctBl1=I) & /(FctBl2=I)
Q1 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & (Q8=0) & (Q15=0) & /(FctBl1=I) & /(FctBl2=I)
Q1 Open (Q0=0)
A5.2.1.37 Bay type No. 26: Feeder bay with switch disconnector, single busbar
A13.200.R01
Q0
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-110: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-111: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.38 Bay type No. 27: Feeder bay with switch disconnector, single busbar,
direct motor control
A13.201.M02
Switchgear
Control O/C Interlock equation
unit
Q8 Close(d) (Q0=0)
Tab. A5-113: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q8 Close(d) (Q0=0)
Tab. A5-114: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.39 Bay type No. 28: Feeder bay with switch disconnector, single busbar
A13.201.R01
Close(d) U A04 /
Q8
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.1.40 Bay type No. 29: Feeder bay with switch disconnector, single busbar
A13.201.R02
Switchgear
Control O/C Interlock equation
unit
Q8 Close(d) (Q0=0)
Tab. A5-119: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q8 Close(d) (Q0=0)
Tab. A5-120: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.41 Bay type No. 30: Feeder bay with switch disconnector, single busbar,
direct motor control
A13.205.M03
Switchgear
Control O/C Interlock equation
unit
Q1 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q1 Open (Q0=0)
A5.2.1.42 Bay type No. 31: Feeder bay with switch disconnector, single busbar
A13.205.R01
Close(d) U A04 / Q0
Close(d) U A06 /
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.1.43 Bay type No. 32: Feeder bay with switch disconnector, single busbar
A13.205.R02
Close(d) U A06 /
Switchgear
Control O/C Interlock equation
unit
Q1 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q1 Open (Q0=0)
A5.2.1.44 Bay type No. 33: Feeder bay with switch disconnector, single busbar
A13.205.R03
Switchgear
Control O/C Interlock equation
unit
Q1 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q1 Open (Q0=0)
A5.2.1.45 Bay type No. 34: Feeder bay with switch disconnector / fuse unit, single
busbar
A13.400.R01
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-134: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-135: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.46 Bay type No. 35: Feeder bay with switch disconnector / fuse unit, single
busbar, direct motor control
A13.401.M02
Switchgear
Control O/C Interlock equation
unit
Q8 Close(d) (Q0=0)
Tab. A5-137: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q8 Close(d) (Q0=0)
Tab. A5-138: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.47 Bay type No. 36: Feeder bay with switch disconnector / fuse unit, single
busbar
A13.401.R01
Close(d) U A04 / F
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.1.48 Bay type No. 37: Feeder bay with switch disconnector / fuse unit, single
busbar
A13.401.R02
Switchgear
Control O/C Interlock equation
unit
Q8 Close(d) (Q0=0)
Tab. A5-143: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q8 Close(d) (Q0=0)
Tab. A5-144: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.49 Bay type No. 38: Feeder bay with switch disconnector / fuse unit, single
busbar, direct motor control
A13.405.M03
Q0
Close(d) U A04 K A04
F
Q8 (DEV03) Open U A05 K A05
Q8
Close(d) U A06 K A06
Switchgear
Control O/C Interlock equation
unit
Q1 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q1 Open (Q0=0)
A5.2.1.50 Bay type No. 39: Feeder bay with switch disconnector / fuse unit, single
busbar
A13.405.R01
Q0
Close(d) U A04 /
F
Q8 (DEV03) Open U A05 /
Q8
Close(d) U A06 /
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.1.51 Bay type No. 40: Feeder bay with switch disconnector / fuse unit, single
busbar
A13.405.R02
Q0
Close(d) U A04 K A04
F
Q8 (DEV03) Open U A05 /
Q8
Close(d) U A06 /
Switchgear
Control O/C Interlock equation
unit
Q1 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q1 Open (Q0=0)
A5.2.1.52 Bay type No. 41: Feeder bay with switch disconnector / fuse unit, single
busbar
A13.405.R03
Q0
Close(d) U A04 K A04
F
Q8 (DEV03) Open U A05 K A05
Q8
Close(d) U A06 K A06
Switchgear
Control O/C Interlock equation
unit
Q1 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q1 Open (Q0=0)
A5.2.1.53 Bay type No. 503: Feeder bay with switch disconnector / fuse unit,
single busbar
A13.432.R02
Switchgear
Control O/C Interlock equation
unit
Q8 Close(d) (Q0=0)
Tab. A5-158: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q8 Close(d) (Q0=0)
Tab. A5-159: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.54 Bay type No. 507: Feeder bay with switch disconnector / fuse unit,
single busbar
A13.433.R02
Close(d) U A06 /
Switchgear
Control O/C Interlock equation
unit
Q8 Close(d) (Q0=0)
Tab. A5-161: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q8 Close(d) (Q0=0)
Tab. A5-162: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.55 Bay type No. 220: Feeder bay with circuit breaker, single busbar, direct
motor control
A15.105.M02
Close(d) U A06 /
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Q1 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Q1 Open (Q0=0)
A5.2.1.56 Bay type No. 42: Feeder bay with circuit breaker, single busbar, direct
motor control
A15.105.M03
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Q1 Open (Q0=0)
Q8 Open (Q0=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Q1 Open (Q0=0)
Q8 Open (Q0=I)
A5.2.1.57 Bay type No. 43: Feeder bay with circuit breaker, single busbar
A15.105.R01
Close(d) U A04 /
Q8
Q8 (DEV03) Open U A05 / Q0
Close(d) U A06 /
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
A5.2.1.58 Bay type No. 221: Feeder bay with circuit breaker, single busbar
A15.105.R02
Close(d) U A06 /
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Q1 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Q1 Open (Q0=0)
Close(d) (Q0=0)
Tab. A5-174: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.59 Bay type No. 44: Feeder bay with circuit breaker, single busbar
A15.105.R03
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Q1 Open (Q0=0)
Q8 Open (Q0=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Q1 Open (Q0=0)
Close(d) (Q0=0)
Q8 Open (Q0=I)
A5.2.1.60 Bay type No. 45: Feeder bay with circuit breaker, double busbar, direct
motor control
A21.104.M04
Q0
Q2 (DEV03) Open U A05 K A05
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
A5.2.1.61 Bay type No. 46: Feeder bay with circuit breaker, double busbar
A21.104.R01
Close(d) U A04 / X0
Q0
Q2 (DEV03) Open U A05 /
Close(d) U A06 /
Close(d) U B02 /
Tab. A5-181: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-182: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-183: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.62 Bay type No. 47: Feeder bay with circuit breaker, double busbar
A21.104.R03
Q0
Q2 (DEV03) Open U A05 K A05
Close(d) U B02 /
Tab. A5-184: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-186: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.63 Bay type No. 48: Feeder bay with circuit breaker, double busbar
A21.104.R04
Q0
Q2 (DEV03) Open U A05 K A05
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
A5.2.1.64 Bay type No. 49: Feeder bay with circuit breaker, double busbar, direct
motor control
A21.105.M05
Q0
Q2 (DEV03) Open U A05 K A05
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (X0=0)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (X0=0)
A5.2.1.65 Bay type No. 50: Feeder bay with circuit breaker, double busbar
A21.105.R01
Close(d) U A04 / X0
Q0
Q2 (DEV03) Open U A05 /
Close(d) U A06 / Q8
Close(d) U B02 /
Close(d) U B04 /
Tab. A5-193: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-194: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-195: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.66 Bay type No. 51: Feeder bay with circuit breaker, double busbar
A21.105.R03
Q0
Q2 (DEV03) Open U A05 K A05
Close(d) U B02 /
Close(d) U B04 /
Tab. A5-196: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-198: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.67 Bay type No. 52: Feeder bay with circuit breaker, double busbar
A21.105.R04
Q0
Q2 (DEV03) Open U A05 K A05
Close(d) U B04 /
Tab. A5-199: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
A5.2.1.68 Bay type No. 53: Feeder bay with circuit breaker, double busbar
A21.105.R05
Q0
Q2 (DEV03) Open U A05 K A05
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (X0=0)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (X0=0)
A5.2.1.69 Bay type No. 526: Feeder bay with circuit breaker, double busbar
A21.125.R02
Q01 Q02
X01 (DEV03) Open U A05 /
Close(d) U A06 / Q8
Close(d) U B02 /
Close(d) U B04 /
Close(d) U B06 /
Close(d) U C02 /
Tab. A5-205: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q01 Close(d) /(X01=X) & /(X02=X) & (Q15=0) & (Q25=0) & /(FctBl1=I) & /(FctBl2=I)
Q02 Close(d) /(X01=X) & /(X02=X) & (Q15=0) & (Q25=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-206: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q01 Close(d) /(X01=X) & /(X02=X) & (Q15=0) & (Q25=0) & /(FctBl1=I) & /(FctBl2=I)
Q02 Close(d) /(X01=X) & /(X02=X) & (Q15=0) & (Q25=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-207: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.70 Bay type No. 54: Feeder bay with switch disconnector, double busbar,
direct motor control
A21.204.M04
Q0
Q2 (DEV03) Open U A05 K A05
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
A5.2.1.71 Bay type No. 55: Feeder bay with switch disconnector, double busbar
A21.204.R01
Close(d) U A04 / X0
Q0
Q2 (DEV03) Open U A05 /
Close(d) U A06 /
Close(d) U B02 /
Tab. A5-211: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-212: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-213: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.72 Bay type No. 56: Feeder bay with switch disconnector, double busbar
A21.204.R03
Q0
Q2 (DEV03) Open U A05 K A05
Close(d) U B02 /
Tab. A5-214: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-216: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.73 Bay type No. 57: Feeder bay with switch disconnector, double busbar
A21.204.R04
Q0
Q2 (DEV03) Open U A05 K A05
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
A5.2.1.74 Bay type No. 58: Feeder bay with switch disconnector, double busbar,
direct motor control
A21.205.M05
Q0
Q2 (DEV03) Open U A05 K A05
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (X0=0)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (X0=0)
A5.2.1.75 Bay type No. 59: Feeder bay with switch disconnector, double busbar
A21.205.R01
Close(d) U A04 / X0
Q0
Q2 (DEV03) Open U A05 /
Close(d) U A06 / Q8
Close(d) U B02 /
Close(d) U B04 /
Tab. A5-223: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-224: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-225: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.76 Bay type No. 60: Feeder bay with switch disconnector, double busbar
A21.205.R03
Q0
Q2 (DEV03) Open U A05 K A05
Close(d) U B02 /
Close(d) U B04 /
Tab. A5-226: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-228: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.77 Bay type No. 61: Feeder bay with switch disconnector, double busbar
A21.205.R04
Q0
Q2 (DEV03) Open U A05 K A05
Close(d) U B04 /
Tab. A5-229: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
A5.2.1.78 Bay type No. 62: Feeder bay with switch disconnector, double busbar
A21.205.R05
Q0
Q2 (DEV03) Open U A05 K A05
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (X0=0)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (X0=0)
A5.2.1.79 Bay type No. 63: Feeder bay with switch disconnector / fuse unit,
double busbar, direct motor control
A21.404.M04
Q0
Q2 (DEV03) Open U A05 K A05
F
Close(d) U A06 K A06
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
A5.2.1.80 Bay type No. 64: Feeder bay with switch disconnector / fuse unit,
double busbar
A21.404.R01
Close(d) U A04 / X0
Q0
Q2 (DEV03) Open U A05 /
F
Close(d) U A06 /
Close(d) U B02 /
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-239: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-240: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.81 Bay type No. 65: Feeder bay with switch disconnector / fuse unit,
double busbar
A21.404.R03
Q0
Q2 (DEV03) Open U A05 K A05
F
Close(d) U A06 K A06
Close(d) U B02 /
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-243: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.82 Bay type No. 66: Feeder bay with switch disconnector / fuse unit,
double busbar
A21.404.R04
Q0
Q2 (DEV03) Open U A05 K A05
F
Close(d) U A06 K A06
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
A5.2.1.83 Bay type No. 67: Feeder bay with switch disconnector / fuse unit,
double busbar, direct motor control
A21.405.M05
Q0
Q2 (DEV03) Open U A05 K A05
F
Close(d) U A06 K A06 Q8
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (X0=0)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (X0=0)
A5.2.1.84 Bay type No. 68: Feeder bay with switch disconnector / fuse unit,
double busbar
A21.405.R01
Close(d) U A04 / X0
Q0
Q2 (DEV03) Open U A05 /
F
Close(d) U A06 / Q8
Close(d) U B02 /
Close(d) U B04 /
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-251: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-252: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.85 Bay type No. 69: Feeder bay with switch disconnector / fuse unit,
double busbar
A21.405.R03
Q0
Q2 (DEV03) Open U A05 K A05
F
Close(d) U A06 K A06 Q8
Close(d) U B02 /
Close(d) U B04 /
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-255: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.86 Bay type No. 70: Feeder bay with switch disconnector / fuse unit,
double busbar
A21.405.R04
Q0
Q2 (DEV03) Open U A05 K A05
F
Close(d) U A06 K A06 Q8
Close(d) U B04 /
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
A5.2.1.87 Bay type No. 71: Feeder bay with switch disconnector / fuse unit,
double busbar
A21.405.R05
Q0
Q2 (DEV03) Open U A05 K A05
F
Close(d) U A06 K A06 Q8
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (X0=0)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (X0=0)
A5.2.1.88 Bay type No. 72: Feeder bay with circuit breaker, double busbar
A22.101.R02
Close(d) U B02 /
Close(d) U B04 /
Tab. A5-262: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q01 Close(d) (Q02=0) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Q02 Close(d) (Q01=0) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-263: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
A5.2.1.89 Bay type No. 73: Feeder bay with circuit breaker, double busbar
A22.101.R04
Close(d) U B04 /
Tab. A5-265: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q01 Close(d) (Q02=0) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Q02 Close(d) (Q01=0) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
A5.2.1.90 Bay type No. 74: Feeder bay with circuit breaker, double busbar
A22.101.R05
Switchgear
Control O/C Interlock equation
unit
Q01 Close(d) (Q02=0) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Q02 Close(d) (Q01=0) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
A5.2.1.91 Bay type No. 75: Feeder bay with circuit breaker, double busbar
A22.103.R02
Close(d) U B02 /
Close(d) U B04 /
Close(d) U B06 /
Tab. A5-271: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q01 Close(d) (Q02=0) & /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Q02 Close(d) (Q01=0) & /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-272: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q01 Close(d) /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Q02 Close(d) /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-273: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.92 Bay type No. 76: Feeder bay with circuit breaker, double busbar
A22.103.R03
Close(d) U B02 /
Close(d) U B06 /
Tab. A5-274: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q01 Close(d) (Q02=0) & /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Q02 Close(d) (Q01=0) & /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q01 Close(d) /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Q02 Close(d) /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
A5.2.1.93 Bay type No. 77: Feeder bay with circuit breaker, double busbar
A22.103.R05
Close(d) U B06 /
Tab. A5-277: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q01 Close(d) (Q02=0) & /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Q02 Close(d) (Q01=0) & /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q01=0)
Close(d) (Q02=0)
Tab. A5-278: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q01 Close(d) /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Q02 Close(d) /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q01=0)
Close(d) (Q02=0)
Tab. A5-279: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.94 Bay type No. 78: Feeder bay with circuit breaker, double busbar
A22.103.R06
Switchgear
Control O/C Interlock equation
unit
Q01 Close(d) (Q02=0) & /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Q02 Close(d) (Q01=0) & /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (Q9=0)
Close(d) (Q01=0)
Close(d) (Q02=0)
Tab. A5-281: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q01 Close(d) /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Q02 Close(d) /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (Q9=0)
Close(d) (Q01=0)
Close(d) (Q02=0)
Tab. A5-282: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.95 Bay type No. 79: Feeder bay with switch disconnector, double busbar
A22.201.R02
Close(d) U B02 /
Close(d) U B04 /
Tab. A5-283: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q01 Close(d) (Q02=0) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Q02 Close(d) (Q01=0) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-284: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
A5.2.1.96 Bay type No. 80: Feeder bay with switch disconnector, double busbar
A22.201.R04
Close(d) U B04 /
Tab. A5-286: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q01 Close(d) (Q02=0) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Q02 Close(d) (Q01=0) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
A5.2.1.97 Bay type No. 81: Feeder bay with switch disconnector, double busbar
A22.201.R05
Switchgear
Control O/C Interlock equation
unit
Q01 Close(d) (Q02=0) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Q02 Close(d) (Q01=0) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
A5.2.1.98 Bay type No. 82: Feeder bay with switch disconnector, double busbar
A22.203.R02
Close(d) U B02 /
Close(d) U B04 /
Close(d) U B06 /
Tab. A5-292: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q01 Close(d) (Q02=0) & /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Q02 Close(d) (Q01=0) & /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-293: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q01 Close(d) /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Q02 Close(d) /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-294: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.99 Bay type No. 83: Feeder bay with switch disconnector, double busbar
A22.203.R03
Close(d) U B02 /
Close(d) U B06 /
Tab. A5-295: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q01 Close(d) (Q02=0) & /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Q02 Close(d) (Q01=0) & /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q01 Close(d) /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Q02 Close(d) /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
A5.2.1.100 Bay type No. 84: Feeder bay with switch disconnector, double busbar
A22.203.R05
Close(d) U B06 /
Tab. A5-298: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q01 Close(d) (Q02=0) & /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Q02 Close(d) (Q01=0) & /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q01=0)
Close(d) (Q02=0)
Tab. A5-299: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q01 Close(d) /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Q02 Close(d) /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q01=0)
Close(d) (Q02=0)
Tab. A5-300: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.101 Bay type No. 85: Feeder bay with switch disconnector, double busbar
A22.203.R06
Switchgear
Control O/C Interlock equation
unit
Q01 Close(d) (Q02=0) & /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Q02 Close(d) (Q01=0) & /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (Q9=0)
Close(d) (Q01=0)
Close(d) (Q02=0)
Tab. A5-302: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q01 Close(d) /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Q02 Close(d) /(Q9=X) & /(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (Q9=0)
Close(d) (Q01=0)
Close(d) (Q02=0)
Tab. A5-303: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.102 Bay type No. 86: Feeder bay with circuit breaker, double busbar, direct
motor control
A23.104.M03
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.1.103 Bay type No. 87: Feeder bay with circuit breaker, double busbar
A23.104.R01
Close(d) U A04 /
Q0
Q2 (DEV03) Open U A05 /
Close(d) U A06 /
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.1.104 Bay type No. 88: Feeder bay with circuit breaker, double busbar
A23.104.R03
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.1.105 Bay type No. 89: Feeder bay with circuit breaker, double busbar, direct
motor control
A23.105.M04
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Q1 Close(d) (Q8=0)
Q2 Close(d) (Q8=0)
A5.2.1.106 Bay type No. 90: Feeder bay with circuit breaker, double busbar
A23.105.R01
Close(d) U A04 /
Q0
Q2 (DEV03) Open U A05 /
Q8
Close(d) U A06 /
Close(d) U B02 /
Tab. A5-316: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-317: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-318: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.107 Bay type No. 91: Feeder bay with circuit breaker, double busbar
A23.105.R03
Close(d) U B02 /
Tab. A5-319: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Q1 Close(d) (Q8=0)
Q2 Close(d) (Q8=0)
Tab. A5-321: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.108 Bay type No. 92: Feeder bay with circuit breaker, double busbar
A23.105.R04
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Q1 Close(d) (Q8=0)
Q2 Close(d) (Q8=0)
A5.2.1.109 Bay type No. 93: Feeder bay with circuit breaker, double busbar, direct
motor control
A23.106.M04
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FctBl2=I)
Q9 Open (Q0=0)
Close(d) (Q0=0)
Tab. A5-326: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FctBl2=I)
Q9 Open (Q0=0)
Close(d) (Q0=0)
Tab. A5-327: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.110 Bay type No. 94: Feeder bay with circuit breaker, double busbar
A23.106.R01
Close(d) U A04 /
Q0
Q2 (DEV03) Open U A05 / Q9
Close(d) U A06 /
Close(d) U B02 /
Tab. A5-328: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-329: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-330: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.111 Bay type No. 95: Feeder bay with circuit breaker, double busbar
A23.106.R04
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FctBl2=I)
Q9 Open (Q0=0)
Close(d) (Q0=0)
Tab. A5-332: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FctBl2=I)
Q9 Open (Q0=0)
Close(d) (Q0=0)
Tab. A5-333: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.112 Bay type No. 96: Feeder bay with circuit breaker, double busbar, direct
motor control
A23.107.M05
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (Q9=0)
Q9 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (Q9=0)
Q9 Open (Q0=0)
A5.2.1.113 Bay type No. 97: Feeder bay with circuit breaker, double busbar
A23.107.R01
Close(d) U A04 /
Q0
Q2 (DEV03) Open U A05 / Q9
Close(d) U A06 / Q8
Close(d) U B02 /
Close(d) U B04 /
Tab. A5-337: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-338: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-339: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.114 Bay type No. 98: Feeder bay with circuit breaker, double busbar
A23.107.R04
Close(d) U B04 /
Tab. A5-340: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FctBl2=I)
Q9 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FctBl2=I)
Q9 Open (Q0=0)
A5.2.1.115 Bay type No. 99: Feeder bay with circuit breaker, double busbar
A23.107.R05
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (Q9=0)
Q9 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (Q9=0)
Q9 Open (Q0=0)
A5.2.1.116 Bay type No. 100: Feeder bay with switch disconnector, double busbar,
direct motor control
A23.204.M03
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.1.117 Bay type No. 101: Feeder bay with switch disconnector, double busbar
A23.204.R01
Close(d) U A04 /
Q0
Q2 (DEV03) Open U A05 /
Close(d) U A06 /
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.1.118 Bay type No. 102: Feeder bay with switch disconnector, double busbar
A23.204.R03
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.1.119 Bay type No. 103: Feeder bay with switch disconnector, double busbar,
direct motor control
A23.205.M04
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Q1 Close(d) (Q8=0)
Q2 Close(d) (Q8=0)
A5.2.1.120 Bay type No. 104: Feeder bay with switch disconnector, double busbar
A23.205.R01
Close(d) U A04 /
Q0
Q2 (DEV03) Open U A05 /
Q8
Close(d) U A06 /
Close(d) U B02 /
Tab. A5-358: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-359: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-360: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.121 Bay type No. 105: Feeder bay with switch disconnector, double busbar
A23.205.R03
Close(d) U B02 /
Tab. A5-361: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Q1 Close(d) (Q8=0)
Q2 Close(d) (Q8=0)
Tab. A5-363: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.122 Bay type No. 106: Feeder bay with switch disconnector, double busbar
A23.205.R04
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Q1 Close(d) (Q8=0)
Q2 Close(d) (Q8=0)
A5.2.1.123 Bay type No. 107: Feeder bay with switch disconnector, double busbar,
direct motor control
A23.206.M04
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FctBl2=I)
Q9 Open (Q0=0)
Close(d) (Q0=0)
Tab. A5-368: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FctBl2=I)
Q9 Open (Q0=0)
Close(d) (Q0=0)
Tab. A5-369: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.124 Bay type No. 108: Feeder bay with switch disconnector, double busbar
A23.206.R01
Close(d) U A04 /
Q0
Q2 (DEV03) Open U A05 / Q9
Close(d) U A06 /
Close(d) U B02 /
Tab. A5-370: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-371: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-372: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.125 Bay type No. 109: Feeder bay with switch disconnector, double busbar
A23.206.R04
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FctBl2=I)
Q9 Open (Q0=0)
Close(d) (Q0=0)
Tab. A5-374: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FctBl2=I)
Q9 Open (Q0=0)
Close(d) (Q0=0)
Tab. A5-375: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.126 Bay type No. 110: Feeder bay with switch disconnector, double busbar,
direct motor control
A23.207.M05
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (Q9=0)
Q9 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (Q9=0)
Q9 Open (Q0=0)
A5.2.1.127 Bay type No. 111: Feeder bay with switch disconnector, double busbar
A23.207.R01
Close(d) U A04 /
Q0
Q2 (DEV03) Open U A05 / Q9
Close(d) U A06 / Q8
Close(d) U B02 /
Close(d) U B04 /
Tab. A5-379: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-380: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-381: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.128 Bay type No. 112: Feeder bay with switch disconnector, double busbar
A23.207.R04
Close(d) U B04 /
Tab. A5-382: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FctBl2=I)
Q9 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FctBl2=I)
Q9 Open (Q0=0)
A5.2.1.129 Bay type No. 113: Feeder bay with switch disconnector, double busbar
A23.207.R05
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (Q9=0)
Q9 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(Q9=X) & /(FctBl1=I) & /(FctBl2=I)
Q8 Close(d) (Q9=0)
Q9 Open (Q0=0)
A5.2.1.130 Bay type No. 114: Feeder bay with switch disconnector / fuse unit,
double busbar, direct motor control
A23.404.M03
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.1.131 Bay type No. 115: Feeder bay with switch disconnector / fuse unit,
double busbar
A23.404.R01
Close(d) U A04 /
Q0
Q2 (DEV03) Open U A05 / F
Close(d) U A06 /
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.1.132 Bay type No. 116: Feeder bay with switch disconnector / fuse unit,
double busbar
A23.404.R03
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.1.133 Bay type No. 117: Feeder bay with switch disconnector / fuse unit,
double busbar, direct motor control
A23.405.M04
Q8
Close(d) U A06 K A06
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Q1 Close(d) (Q8=0)
Q2 Close(d) (Q8=0)
A5.2.1.134 Bay type No. 118: Feeder bay with switch disconnector / fuse unit,
double busbar
A23.405.R01
Close(d) U A04 /
Q0
Q2 (DEV03) Open U A05 / F
Q8
Close(d) U A06 /
Close(d) U B02 /
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-401: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-402: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.135 Bay type No. 119: Feeder bay with switch disconnector / fuse unit,
double busbar
A23.405.R03
Q8
Close(d) U A06 K A06
Close(d) U B02 /
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Q1 Close(d) (Q8=0)
Q2 Close(d) (Q8=0)
Tab. A5-405: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.136 Bay type No. 120: Feeder bay with switch disconnector / fuse unit,
double busbar
A23.405.R04
Q8
Close(d) U A06 K A06
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Q1 Close(d) (Q8=0)
Q2 Close(d) (Q8=0)
A5.2.1.137 Bay type No. 222: Feeder bay with circuit breaker, double busbar, direct
motor control
A25.105.M03.1
Close(d) U B02 /
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Q1 Close(d) (Q8=0)
Q2 Close(d) (Q8=0)
Tab. A5-411: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.138 Bay type No. 223: Feeder bay with circuit breaker, double busbar, direct
motor control
A25.105.M03.2
Close(d) U B02 /
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Q1 Close(d) (Q8=0)
Q2 Close(d) (Q8=0)
Tab. A5-414: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.139 Bay type No. 121: Feeder bay with circuit breaker, double busbar, direct
motor control
A25.105.M04.1
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q1=0) & (Q2=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-416: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Q1 Close(d) (Q8=0)
Q2 Close(d) (Q8=0)
Close(d) (Q0=0) & (Q1=0) & (Q2=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-417: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.140 Bay type No. 122: Feeder bay with circuit breaker, double busbar, direct
motor control
A25.105.M04.2
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q1=0) & (Q2=0) & /(FctBl1=I) & (FctBl2=I)
Tab. A5-419: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Q1 Close(d) (Q8=0)
Q2 Close(d) (Q8=0)
Close(d) (Q0=0) & (Q1=0) & (Q2=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-420: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.141 Bay type No. 123: Feeder bay with circuit breaker, double busbar
A25.105.R01.1
Close(d) U A04 /
Q8
Q2 (DEV03) Open U A05 / Q0
Close(d) U A06 /
Close(d) U B02 /
Tab. A5-421: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-422: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-423: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.142 Bay type No. 124: Feeder bay with circuit breaker, double busbar
A25.105.R01.2
Close(d) U A04 /
Q8
Q2 (DEV03) Open U A05 / Q0
Close(d) U A06 /
Close(d) U B02 /
Tab. A5-424: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-425: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-426: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.143 Bay type No. 224: Feeder bay with circuit breaker, double busbar
A25.105.R03.1
Close(d) U B02 /
Tab. A5-427: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Q1 Close(d) (Q8=0)
Q2 Close(d) (Q8=0)
Tab. A5-429: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.144 Bay type No. 225: Feeder bay with circuit breaker, double busbar
A25.105.R03.2
Close(d) U B02 /
Tab. A5-430: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Q1 Close(d) (Q8=0)
Q2 Close(d) (Q8=0)
Tab. A5-432: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.145 Bay type No. 125: Feeder bay with circuit breaker, double busbar
A25.105.R04.1
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q1=0) & (Q2=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-434: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Q1 Close(d) (Q8=0)
Q2 Close(d) (Q8=0)
Close(d) (Q0=0) & (Q1=0) & (Q2=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-435: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.146 Bay type No. 126: Feeder bay with circuit breaker, double busbar
A25.105.R04.2
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q1=0) & (Q2=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-437: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q1=X) & /(Q2=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Q1 Close(d) (Q8=0)
Q2 Close(d) (Q8=0)
Close(d) (Q0=0) & (Q1=0) & (Q2=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-438: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.147 Bay type No. 127: Feeder bay with circuit breaker, double busbar
A25.128.R01
Close(d) U A04 /
Q81 Q82
Q2 (DEV03) Open U A05 / Q0
Close(d) U A06 /
Close(d) U B02 /
Close(d) U B04 /
Tab. A5-439: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q1=X) & /(Q2=X) & (Q81=0) & (Q82=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-440: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q1=X) & /(Q2=X) & (Q81=0) & (Q82=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-441: Bay Interlock Equations for Operation with Station Interlocking
A5.2.1.148 Bay type No. 128: Feeder bay with circuit breaker, double busbar
A25.128.R05
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q1=X) & /(Q2=X) & (Q81=0) & (Q82=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q1=0) & (Q2=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q1=0) & (Q2=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-443: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q1=X) & /(Q2=X) & (Q81=0) & (Q82=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q1=0) & (Q2=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q1=0) & (Q2=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-444: Bay Interlock Equations for Operation with Station Interlocking
A5.2.2.1 Bay type No. 133: Bus sectionalizer bay with circuit breaker, single
busbar
L11.100.R01
Close(d) U A04 /
Q0
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.2.2 Bay type No. 553: Bus sectionalizer bay with circuit breaker, single
busbar
L11.100.R01.2
Close(d) U A04 /
Q0
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.2.3 Bay type No. 134: Bus sectionalizer bay with circuit breaker, single
busbar
L11.100.R02
Switchgear
Control O/C Interlock equation
unit
Close(d) (Q0=0)
Tab. A5-452: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Close(d) (Q0=0)
Tab. A5-453: Bay Interlock Equations for Operation with Station Interlocking
A5.2.2.4 Bay type No. 528: Bus sectionalizer bay with circuit breaker, single
busbar
L11.102.R01
Close(d) U A06 /
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.2.5 Bay type No. 542: Bus sectionalizer bay with circuit breaker, single
busbar
L11.102.R01.2
Close(d) U A06 /
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.2.6 Bay type No. 135: Bus sectionalizer bay with circuit breaker, single
busbar
L11.104.R01
Close(d) U A04 / Q0
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.2.7 Bay type No. 136: Bus sectionalizer bay with circuit breaker, single
busbar
L11.104.R02
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.2.8 Bay type No. 137: Bus sectionalizer bay with circuit breaker, single
busbar
L11.104.R03
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
Q8 Close(d) (X01=0)
A5.2.2.9 Bay type No. 547: Bus sectionalizer bay with circuit breaker, single
busbar, direct motor control
L11.112.M04
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(X0=X) & (Q15=0) & (Q16=0) & /(FctBl1=I) & /(FctBl2=I)
X0 Open (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(X0=X) & (Q15=0) & (Q16=0) & /(FctBl1=I) & /(FctBl2=I)
X0 Open (Q0=0)
A5.2.2.10 Bay type No. 564: Bus sectionalizer bay with circuit breaker, single
busbar
L11.112.R01.2
Close(d) U A06 /
Close(d) U B02 /
Tab. A5-472: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(X01=X) & (Q15=0) & (Q16=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-473: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
A5.2.2.11 Bay type No. 138: Bus sectionalizer bay with circuit breaker, single
busbar
L11.116.R01
Close(d) U A04 /
Q0
X02 (DEV03) Open U A05 /
Close(d) U A06 /
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.2.12 Bay type No. 545: Bus sectionalizer bay with circuit breaker, single
busbar
L11.116.R01.2
Close(d) U A04 /
Q0
X02 (DEV03) Open U A05 /
Close(d) U A06 /
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.2.13 Bay type No. 139: Bus sectionalizer bay with circuit breaker, single
busbar
L11.116.R03
Switchgear
Control O/C Interlock equation
unit
Close(d) (Q0=0)
Close(d) (Q0=0)
Tab. A5-482: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Close(d) (Q0=0)
Close(d) (Q0=0)
Tab. A5-483: Bay Interlock Equations for Operation with Station Interlocking
A5.2.2.14 Bay type No. 548: Bus sectionalizer bay with circuit breaker, single
busbar, direct motor control
L11.120.M03
Close(d) U B02 /
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.2.15 Bay type No. 552: Bus sectionalizer bay with circuit breaker, single
busbar, direct motor control
L11.120.M03.2
Close(d) U B02 /
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.2.16 Bay type No. 140: Bus sectionalizer bay with circuit breaker, single
busbar
L11.120.R01
Close(d) U A04 / Q0
Close(d) U B02 /
Tab. A5-490: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.2.17 Bay type No. 141: Bus sectionalizer bay with circuit breaker, single
busbar
L11.120.R03
Close(d) U B02 /
Tab. A5-493: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.2.18 Bay type No. 543: Bus sectionalizer bay with circuit breaker, single
busbar
L11.120.R03
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.2.19 Bay type No. 142: Bus sectionalizer bay with circuit breaker, single
busbar
L11.120.R04
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.2.20 Bay type No. 558: Bus sectionalizer bay with circuit breaker, single
busbar
L11.128.R01
Close(d) U A04 / Q0
Close(d) U B02 /
Close(d) U B04 /
Tab. A5-502: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.2.21 Bay type No. 143: Bus sectionalizer bay with circuit breaker, single
busbar, direct motor control
L13.113.M03
Close(d) U B02 /
Close(d) U B04 /
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q11=X) & /(Q12=X) & (Q81=0) & (Q82=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q11=X) & /(Q12=X) & (Q81=0) & (Q82=0) & /(FctBl1=I) & /(FctBl2=I)
A5.2.2.22 Bay type No. 144: Bus sectionalizer bay with circuit breaker, single
busbar, direct motor control
L13.113.M05
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q11=X) & /(Q12=X) & (Q81=0) & (Q82=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q11=X) & /(Q12=X) & (Q81=0) & (Q82=0) & /(FctBl1=I) & /(FctBl2=I)
A5.2.2.23 Bay type No. 145: Bus sectionalizer bay with circuit breaker, single
busbar
L13.113.R01
Close(d) U A04 / Q0
Close(d) U A06 /
Close(d) U B02 /
Close(d) U B04 /
Tab. A5-511: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q11=X) & /(Q12=X) & (Q81=0) & (Q82=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-512: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q11=X) & /(Q12=X) & (Q81=0) & (Q82=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-513: Bay Interlock Equations for Operation with Station Interlocking
A5.2.2.24 Bay type No. 146: Bus sectionalizer bay with circuit breaker, single
busbar
L13.113.R03
Close(d) U B02 /
Close(d) U B04 /
Tab. A5-514: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q11=X) & /(Q12=X) & (Q81=0) & (Q82=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q11=X) & /(Q12=X) & (Q81=0) & (Q82=0) & /(FctBl1=I) & /(FctBl2=I)
A5.2.2.25 Bay type No. 517: Bus sectionalizer bay with circuit breaker, single
busbar
L13.113.R03.2
Close(d) U A06 /
Close(d) U B04 /
Tab. A5-517: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q11=X) & /(Q12=X) & (Q81=0) & (Q82=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q11=X) & /(Q12=X) & (Q81=0) & (Q82=0) & /(FctBl1=I) & /(FctBl2=I)
A5.2.2.26 Bay type No. 147: Bus sectionalizer bay with circuit breaker, single
busbar
L13.113.R05
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q11=X) & /(Q12=X) & (Q81=0) & (Q82=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q11=X) & /(Q12=X) & (Q81=0) & (Q82=0) & /(FctBl1=I) & /(FctBl2=I)
A5.2.2.27 Bay type No. 148: Bus sectionalizer bay with switch disconnector, single
busbar
L13.200.R01
Q0
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-524: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-525: Bay Interlock Equations for Operation with Station Interlocking
A5.2.2.28 Bay type No. 149: Bus sectionalizer bay with switch disconnector, single
busbar
L13.202.R01
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.2.29 Bay type No. 150: Bus sectionalizer bay with switch disconnector, single
busbar
L13.202.R03
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.2.30 Bay type No. 226: Bus sectionalizer bay with circuit breaker, single
busbar, direct motor control
L15.113.M03
Close(d) U B02 /
Close(d) U B04 /
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q11=X) & /(Q12=X) & (Q15=0) & (Q16=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q11=X) & /(Q12=X) & (Q15=0) & (Q16=0) & /(FctBl1=I) & /(FctBl2=I)
A5.2.2.31 Bay type No. 151: Bus sectionalizer bay with circuit breaker, single
busbar, direct motor control
L15.113.M05
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q11=X) & /(Q12=X) & (Q15=0) & (Q16=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q11=0) & (Q12=I) & /(FctBl1=I) & /(FctBl2=I) & (Q15=I)
Close(d) (Q0=0) & (Q12=0) & (Q11=I) & /(FctBl1=I) & /(FctBl2=I) & (Q16=I)
Tab. A5-536: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q11=X) & /(Q12=X) & (Q15=0) & (Q16=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q11=0) & (Q12=I) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q12=0) & (Q11=I) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-537: Bay Interlock Equations for Operation with Station Interlocking
A5.2.2.32 Bay type No. 152: Bus sectionalizer bay with circuit breaker, single
busbar
L15.113.R01
Close(d) U B02 /
Close(d) U B04 /
Tab. A5-538: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q11=X) & /(Q12=X) & (Q15=0) & (Q16=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-539: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q11=X) & /(Q12=X) & (Q15=0) & (Q16=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-540: Bay Interlock Equations for Operation with Station Interlocking
A5.2.2.33 Bay type No. 227: Bus sectionalizer bay with circuit breaker, single
busbar
L15.113.R03
Close(d) U B02 /
Close(d) U B04 /
Tab. A5-541: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q11=X) & /(Q12=X) & (Q15=0) & (Q16=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q11=X) & /(Q12=X) & (Q15=0) & (Q16=0) & /(FctBl1=I) & /(FctBl2=I)
A5.2.2.34 Bay type No. 153: Bus sectionalizer bay with circuit breaker, single
busbar
L15.113.R05
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q11=X) & /(Q12=X) & (Q15=0) & (Q16=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q11=0) & (Q12=I) & /(FctBl1=I) & /(FctBl2=I) & (Q15=I)
Close(d) (Q0=0) & (Q12=0) & (Q11=I) & /(FctBl1=I) & /(FctBl2=I) & (Q16=I)
Tab. A5-545: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q11=X) & /(Q12=X) & (Q15=0) & (Q16=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q11=0) & (Q12=I) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q12=0) & (Q11=I) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-546: Bay Interlock Equations for Operation with Station Interlocking
A5.2.2.35 Bay type No. 154: Bus sectionalizer bay with circuit breaker, double
busbar, direct motor control
L21.101.M04.1
Q11 Q12
Close(d) U A04 K A04
X0
Q12 (DEV03) Open U A05 K A05 Q0
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q11=X) & /(Q12=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0)
Close(d) (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q11=X) & /(Q12=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0)
Close(d) (Q0=0)
A5.2.2.36 Bay type No. 155: Bus sectionalizer bay with circuit breaker, double
busbar, direct motor control
L21.101.M04.2
Q21 Q22
Close(d) U A04 K A04
X0
Q22 (DEV03) Open U A05 K A05 Q0
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q21=X) & /(Q22=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0)
Close(d) (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q21=X) & /(Q22=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0)
Close(d) (Q0=0)
A5.2.2.37 Bay type No. 156: Bus sectionalizer bay with circuit breaker, double
busbar
L21.101.R01.1
Q11 Q12
Close(d) U A04 /
X0
Q12 (DEV03) Open U A05 / Q0
Close(d) U A06 /
Close(d) U B02 /
Tab. A5-553: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q11=X) & /(Q12=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-554: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q11=X) & /(Q12=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-555: Bay Interlock Equations for Operation with Station Interlocking
A5.2.2.38 Bay type No. 157: Bus sectionalizer bay with circuit breaker, double
busbar
L21.101.R01.2
Q21 Q22
Close(d) U A04 /
X0
Q22 (DEV03) Open U A05 / Q0
Close(d) U A06 /
Close(d) U B02 /
Tab. A5-556: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q21=X) & /(Q22=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-557: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q21=X) & /(Q22=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-558: Bay Interlock Equations for Operation with Station Interlocking
A5.2.2.39 Bay type No. 158: Bus sectionalizer bay with circuit breaker, double
busbar
L21.101.R03.1
Q11 Q12
Close(d) U A04 K A04
X0
Q12 (DEV03) Open U A05 K A05 Q0
Close(d) U B02 /
Tab. A5-559: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q11=X) & /(Q12=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0)
Close(d) (Q0=0)
Tab. A5-560: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q11=X) & /(Q12=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0)
Close(d) (Q0=0)
Tab. A5-561: Bay Interlock Equations for Operation with Station Interlocking
A5.2.2.40 Bay type No. 159: Bus sectionalizer bay with circuit breaker, double
busbar
L21.101.R03.2
Q21 Q22
Close(d) U A04 K A04
X0
Q22 (DEV03) Open U A05 K A05 Q0
Close(d) U B02 /
Tab. A5-562: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q21=X) & /(Q22=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0)
Close(d) (Q0=0)
Tab. A5-563: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q21=X) & /(Q22=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0)
Close(d) (Q0=0)
Tab. A5-564: Bay Interlock Equations for Operation with Station Interlocking
A5.2.2.41 Bay type No. 160: Bus sectionalizer bay with circuit breaker, double
busbar
L21.101.R04.1
Q11 Q12
Close(d) U A04 K A04
X0
Q12 (DEV03) Open U A05 K A05 Q0
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q11=X) & /(Q12=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0)
Close(d) (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q11=X) & /(Q12=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0)
Close(d) (Q0=0)
A5.2.2.42 Bay type No. 161: Bus sectionalizer bay with circuit breaker, double
busbar
L21.101.R04.2
Q21 Q22
Close(d) U A04 K A04
X0
Q22 (DEV03) Open U A05 K A05 Q0
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q21=X) & /(Q22=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0)
Close(d) (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q21=X) & /(Q22=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0)
Close(d) (Q0=0)
A5.2.2.43 Bay type No. 513: Bus sectionalizer bay with circuit breaker, double
busbar
L21.109.R03.1
Q11 Q12
Close(d) U A04 K A04
X0
Q12 (DEV03) Open U A05 K A05 Q0 Q8
Close(d) U B02 /
Close(d) U B04 /
Tab. A5-571: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q11=X) & /(Q12=X) & /(X0=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q11=X) & /(Q12=X) & /(X0=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
A5.2.2.44 Bay type No. 514: Bus sectionalizer bay with circuit breaker, double
busbar
L21.109.R03.2
Q21 Q22
Close(d) U A04 K A04
X0
Q22 (DEV03) Open U A05 K A05 Q0 Q8
Close(d) U B02 /
Close(d) U B04 /
Tab. A5-574: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q21=X) & /(Q22=X) & /(X0=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q21=X) & /(Q22=X) & /(X0=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
A5.2.2.45 Bay type No. 162: Bus sectionalizer bay with circuit breaker, double
busbar
L23.101.R02
Q11 Q21
Close(d) U A04 K A04
Q12 Q22
Q11 (DEV03) Open U A05 / Q01 Q02
Close(d) U A06 /
Close(d) U B02 /
Close(d) U B04 /
Close(d) U B06 /
Tab. A5-577: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.2.46 Bay type No. 163: Bus sectionalizer bay with circuit breaker, double
busbar
L23.101.R06
Q11 Q21
Close(d) U A04 K A04
Q12 Q22
Q11 (DEV03) Open U A05 K A05 Q01 Q02
Switchgear
Control O/C Interlock equation
unit
Close(d) (Q01=0)
Close(d) (Q01=0)
Close(d) (Q02=0)
Close(d) (Q02=0)
Tab. A5-581: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Close(d) (Q01=0)
Close(d) (Q01=0)
Close(d) (Q02=0)
Close(d) (Q02=0)
Tab. A5-582: Bay Interlock Equations for Operation with Station Interlocking
A5.2.2.47 Bay type No. 554: Bus sectionalizer bay with other switchgear unit,
double busbar, direct motor control
L23.901.M01.1
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-584: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-585: Bay Interlock Equations for Operation with Station Interlocking
A5.2.2.48 Bay type No. 555: Bus sectionalizer bay with other switchgear unit,
double busbar, direct motor control
L23.901.M01.2
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-587: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-588: Bay Interlock Equations for Operation with Station Interlocking
A5.2.2.49 Bay type No. 164: Bus sectionalizer bay with other switchgear unit,
double busbar
L23.901.R02
Switchgear
Control O/C Interlock equation
unit
Close(d) (Q11=I)
Close(d) (Q21=I)
Tab. A5-590: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-591: Bay Interlock Equations for Operation with Station Interlocking
A5.2.2.50 Bay type No. 242: Bus sectionalizer bay with other switchgear unit,
double busbar, direct motor control
L23.903.M01.3
Close(d) U A04 /
Close(d) U A06 /
Switchgear
Control O/C Interlock equation
unit
Close(d) (Q12=I)
Tab. A5-593: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-594: Bay Interlock Equations for Operation with Station Interlocking
A5.2.2.51 Bay type No. 243: Bus sectionalizer bay with other switchgear unit,
double busbar, direct motor control
L23.903.M01.4
Q15 Q25
Close(d) U A04 /
Close(d) U A06 /
Switchgear
Control O/C Interlock equation
unit
Close(d) (Q21=I)
Tab. A5-596: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-597: Bay Interlock Equations for Operation with Station Interlocking
A5.2.2.52 Bay type No. 511: Bus sectionalizer bay with other switchgear unit,
double busbar, direct motor control
L23.903.M02
Close(d) U A06 /
Close(d) U B02 /
Switchgear
Control O/C Interlock equation
unit
Close(d) (Q11=I)
Close(d) (Q21=I)
Tab. A5-599: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-600: Bay Interlock Equations for Operation with Station Interlocking
A5.2.2.53 Bay type No. 228: Bus sectionalizer bay with circuit breaker, double
busbar, direct motor control
L25.113.M03.1
Q11 Q12
Close(d) U A04 K A04
Q15 Q16
Q12 (DEV03) Open U A05 K A05
Q0
Close(d) U A06 K A06
Close(d) U B02 /
Close(d) U B04 /
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q11=X) & /(Q12=X) & (Q15=0) & (Q16=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q11=X) & /(Q12=X) & (Q15=0) & (Q16=0) & /(FctBl1=I) & /(FctBl2=I)
A5.2.2.54 Bay type No. 229: Bus sectionalizer bay with circuit breaker, double
busbar, direct motor control
L25.113.M03.2
Q21 Q22
Close(d) U A04 K A04
Q25 Q26
Q22 (DEV03) Open U A05 K A05
Q0
Close(d) U A06 K A06
Close(d) U B02 /
Close(d) U B04 /
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q21=X) & /(Q22=X) & (Q25=0) & (Q26=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q21=X) & /(Q22=X) & (Q25=0) & (Q26=0) & /(FctBl1=I) & /(FctBl2=I)
A5.2.2.55 Bay type No. 165: Bus sectionalizer bay with circuit breaker, double
busbar, direct motor control
L25.113.M05.1
Q11 Q12
Close(d) U A04 K A04
Q15 Q16
Q12 (DEV03) Open U A05 K A05
Q0
Close(d) U A06 K A06
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q11=X) & /(Q12=X) & (Q15=0) & (Q16=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q11=0) & (Q12=I) & /(FctBl1=I) & /(FctBl2=I) & (Q15=I)
Close(d) (Q0=0) & (Q12=0) & (Q11=I) & /(FctBl1=I) & /(FctBl2=I) & (Q16=I)
Tab. A5-608: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q11=X) & /(Q12=X) & (Q15=0) & (Q16=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q11=0) & (Q12=I) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q12=0) & (Q11=I) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-609: Bay Interlock Equations for Operation with Station Interlocking
A5.2.2.56 Bay type No. 166: Bus sectionalizer bay with circuit breaker, double
busbar, direct motor control
L25.113.M05.2
Q21 Q22
Close(d) U A04 K A04
Q25 Q26
Q22 (DEV03) Open U A05 K A05
Q0
Close(d) U A06 K A06
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q21=X) & /(Q22=X) & (Q25=0) & (Q26=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q21=0) & (Q22=I) & /(FctBl1=I) & /(FctBl2=I) & (Q25=I)
Close(d) (Q0=0) & (Q22=0) & (Q21=I) & /(FctBl1=I) & /(FctBl2=I) & (Q26=I)
Tab. A5-611: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q21=X) & /(Q22=X) & (Q25=0) & (Q26=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q21=0) & (Q22=I) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q22=0) & (Q21=I) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-612: Bay Interlock Equations for Operation with Station Interlocking
A5.2.2.57 Bay type No. 167: Bus sectionalizer bay with circuit breaker, double
busbar
L25.113.R01.1
Q11 Q12
Close(d) U A04 /
Q15 Q16
Q12 (DEV03) Open U A05 /
Q0
Close(d) U A06 /
Close(d) U B02 /
Close(d) U B04 /
Tab. A5-613: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q11=X) & /(Q12=X) & (Q15=0) & (Q16=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-614: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q11=X) & /(Q12=X) & (Q15=0) & (Q16=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-615: Bay Interlock Equations for Operation with Station Interlocking
A5.2.2.58 Bay type No. 168: Bus sectionalizer bay with circuit breaker, double
busbar
L25.113.R01.2
Q21 Q22
Close(d) U A04 /
Q25 Q26
Q22 (DEV03) Open U A05 /
Q0
Close(d) U A06 /
Close(d) U B02 /
Close(d) U B04 /
Tab. A5-616: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q21=X) & /(Q22=X) & (Q25=0) & (Q26=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-617: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q21=X) & /(Q22=X) & (Q25=0) & (Q26=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-618: Bay Interlock Equations for Operation with Station Interlocking
A5.2.2.59 Bay type No. 230: Bus sectionalizer bay with circuit breaker, double
busbar
L25.113.R03.1
Q11 Q12
Close(d) U A04 K A04
Q15 Q16
Q12 (DEV03) Open U A05 K A05
Q0
Close(d) U A06 K A06
Close(d) U B02 /
Close(d) U B04 /
Tab. A5-619: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q11=X) & /(Q12=X) & (Q15=0) & (Q16=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q11=X) & /(Q12=X) & (Q15=0) & (Q16=0) & /(FctBl1=I) & /(FctBl2=I)
A5.2.2.60 Bay type No. 231: Bus sectionalizer bay with circuit breaker, double
busbar
L25.113.R03.2
Q21 Q22
Close(d) U A04 K A04
Q25 Q26
Q22 (DEV03) Open U A05 K A05
Q0
Close(d) U A06 K A06
Close(d) U B02 /
Close(d) U B04 /
Tab. A5-622: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q21=X) & /(Q22=X) & (Q25=0) & (Q26=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q21=X) & /(Q22=X) & (Q25=0) & (Q26=0) & /(FctBl1=I) & /(FctBl2=I)
A5.2.2.61 Bay type No. 169: Bus sectionalizer bay with circuit breaker, double
busbar
L25.113.R05.1
Q11 Q12
Close(d) U A04 K A04
Q15 Q16
Q12 (DEV03) Open U A05 K A05
Q0
Close(d) U A06 K A06
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q11=X) & /(Q12=X) & (Q15=0) & (Q16=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q11=0) & (Q12=I) & /(FctBl1=I) & /(FctBl2=I) & (Q15=I)
Close(d) (Q0=0) & (Q12=0) & (Q11=I) & /(FctBl1=I) & /(FctBl2=I) & (Q16=I)
Tab. A5-626: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q11=X) & /(Q12=X) & (Q15=0) & (Q16=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q11=0) & (Q12=I) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q12=0) & (Q11=I) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-627: Bay Interlock Equations for Operation with Station Interlocking
A5.2.2.62 Bay type No. 170: Bus sectionalizer bay with circuit breaker, double
busbar
L25.113.R05.2
Q21 Q22
Close(d) U A04 K A04
Q25 Q26
Q22 (DEV03) Open U A05 K A05
Q0
Close(d) U A06 K A06
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q21=X) & /(Q22=X) & (Q25=0) & (Q26=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q21=0) & (Q22=I) & /(FctBl1=I) & /(FctBl2=I) & (Q25=I)
Close(d) (Q0=0) & (Q22=0) & (Q21=I) & /(FctBl1=I) & /(FctBl2=I) & (Q26=I)
Tab. A5-629: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q21=X) & /(Q22=X) & (Q25=0) & (Q26=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q21=0) & (Q22=I) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q22=0) & (Q21=I) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-630: Bay Interlock Equations for Operation with Station Interlocking
A5.2.3.1 Bay type No. 505: Bus coupler bay with circuit breaker, double busbar
Q21.100.R01
Close(d) U A04 /
Q0
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.3.2 Bay type No. 197: Bus coupler bay with circuit breaker, double busbar,
direct motor control
Q21.101.M04
Q0
Q20 (DEV03) Open U A05 K A05
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q10=X) & /(Q20=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0)
Close(d) (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q10=X) & /(Q20=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0)
Close(d) (Q0=0)
A5.2.3.3 Bay type No. 198: Bus coupler bay with circuit breaker, double busbar
Q21.101.R01
Close(d) U A04 / X0
Q0
Q20 (DEV03) Open U A05 /
Close(d) U A06 /
Close(d) U B02 /
Tab. A5-637: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q10=X) & /(Q20=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-638: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q10=X) & /(Q20=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-639: Bay Interlock Equations for Operation with Station Interlocking
A5.2.3.4 Bay type No. 199: Bus coupler bay with circuit breaker, double busbar
Q21.101.R03
Q0
Q20 (DEV03) Open U A05 K A05
Close(d) U B02 /
Tab. A5-640: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q10=X) & /(Q20=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0)
Close(d) (Q0=0)
Tab. A5-641: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q10=X) & /(Q20=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0)
Close(d) (Q0=0)
Tab. A5-642: Bay Interlock Equations for Operation with Station Interlocking
A5.2.3.5 Bay type No. 200: Bus coupler bay with circuit breaker, double busbar
Q21.101.R04
Q0
Q20 (DEV03) Open U A05 K A05
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q10=X) & /(Q20=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0)
Close(d) (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q10=X) & /(Q20=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0)
Close(d) (Q0=0)
A5.2.3.6 Bay type No. 556: Bus coupler bay with circuit breaker, double busbar,
direct motor control
Q21.112.M04
Q0
Q25 (DEV03) Open U A05 K A05
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(X0=X) & (Q15=0) & (Q25=0) & /(FctBl1=I) & /(FctBl2=I)
X0 Open (Q0=0)
Close(d) (Q0=0)
Tab. A5-647: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(X0=X) & (Q15=0) & (Q25=0) & /(FctBl1=I) & /(FctBl2=I)
X0 Open (Q0=0)
Close(d) (Q0=0)
Tab. A5-648: Bay Interlock Equations for Operation with Station Interlocking
A5.2.3.7 Bay type No. 565: Bus coupler bay with circuit breaker, double busbar,
direct motor control
Q21.112.M04.2
Q0
Q25 (DEV03) Open U A05 K A05
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(X0=X) & (Q15=0) & (Q25=0) & /(FctBl1=I) & /(FctBl2=I)
X0 Open (Q0=0)
Close(d) (Q0=0)
Tab. A5-650: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(X0=X) & (Q15=0) & (Q25=0) & /(FctBl1=I) & /(FctBl2=I)
X0 Open (Q0=0)
Close(d) (Q0=0)
Tab. A5-651: Bay Interlock Equations for Operation with Station Interlocking
A5.2.3.8 Bay type No. 201: Bus coupler bay with circuit breaker, double busbar
Q21.117.R01
Close(d) U A06 /
Close(d) U B02 /
Close(d) U B04 /
Close(d) U B06 /
Tab. A5-652: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q10=X) & /(Q20=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-653: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q10=X) & /(Q20=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-654: Bay Interlock Equations for Operation with Station Interlocking
A5.2.3.9 Bay type No. 202: Bus coupler bay with circuit breaker, double busbar
Q21.117.R05
Close(d) U B06 /
Tab. A5-655: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q10=X) & /(Q20=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0)
Close(d) (Q0=0)
Tab. A5-656: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q10=X) & /(Q20=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0)
Close(d) (Q0=0)
Tab. A5-657: Bay Interlock Equations for Operation with Station Interlocking
A5.2.3.10 Bay type No. 203: Bus coupler bay with circuit breaker, double busbar
Q21.117.R06
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q10=X) & /(Q20=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0)
Close(d) (Q0=0)
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q10=X) & /(Q20=X) & /(X0=X) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0)
Close(d) (Q0=0)
A5.2.3.11 Bay type No. 245: Bus coupler bay with circuit breaker, double busbar
Q21.132.R01
Close(d) U A06 /
Close(d) U B02 /
Tab. A5-661: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.3.12 Bay type No. 563: Bus coupler bay with circuit breaker, double busbar
Q21.133.R01
Close(d) U A04 /
Q0
X02 (DEV03) Open U A05 /
Close(d) U A06 /
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.3.13 Bay type No. 204: Bus coupler bay with circuit breaker, double busbar,
direct motor control
Q23.101.M03
Switchgear
Control O/C Interlock equation
unit
Close(d) (Q0=0)
Close(d) (Q0=0)
Tab. A5-668: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Close(d) (Q0=0)
Close(d) (Q0=0)
Tab. A5-669: Bay Interlock Equations for Operation with Station Interlocking
A5.2.3.14 Bay type No. 205: Bus coupler bay with circuit breaker, double busbar
Q23.101.R01
Close(d) U A04 /
Q0
Q20 (DEV03) Open U A05 /
Close(d) U A06 /
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.3.15 Bay type No. 206: Bus coupler bay with circuit breaker, double busbar
Q23.101.R03
Switchgear
Control O/C Interlock equation
unit
Close(d) (Q0=0)
Close(d) (Q0=0)
Tab. A5-674: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Close(d) (Q0=0)
Close(d) (Q0=0)
Tab. A5-675: Bay Interlock Equations for Operation with Station Interlocking
A5.2.3.16 Bay type No. 207: Bus coupler bay with circuit breaker, double busbar
Q23.117.R01
Q0
Q20 (DEV03) Open U A05 /
Close(d) U A06 /
Close(d) U B02 /
Close(d) U B04 /
Tab. A5-676: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.3.17 Bay type No. 208: Bus coupler bay with circuit breaker, double busbar
Q23.117.R05
Q0
Q20 (DEV03) Open U A05 K A05
Switchgear
Control O/C Interlock equation
unit
Close(d) (Q0=0)
Close(d) (Q0=0)
Tab. A5-680: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Close(d) (Q0=0)
Close(d) (Q0=0)
Tab. A5-681: Bay Interlock Equations for Operation with Station Interlocking
A5.2.3.18 Bay type No. 236: Bus coupler bay with circuit breaker, double busbar,
direct motor control
Q25.105.M03
Close(d) U B02 /
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q10=X) & /(Q20=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q10=X) & /(Q20=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
A5.2.3.19 Bay type No. 209: Bus coupler bay with circuit breaker, double busbar,
direct motor control
Q25.105.M04
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q10=X) & /(Q20=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q10=0) & (Q20=I) & /(FctBl1=I) & /(FctBl2=I) & (Q8=I)
Tab. A5-686: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q10=X) & /(Q20=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q10=0) & (Q20=I) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-687: Bay Interlock Equations for Operation with Station Interlocking
A5.2.3.20 Bay type No. 210: Bus coupler bay with circuit breaker, double busbar
Q25.105.R01
Close(d) U A04 /
Q8
Q20 (DEV03) Open U A05 / Q0
Close(d) U A06 /
Close(d) U B02 /
Tab. A5-688: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q10=X) & /(Q20=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-689: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q10=X) & /(Q20=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-690: Bay Interlock Equations for Operation with Station Interlocking
A5.2.3.21 Bay type No. 237: Bus coupler bay with circuit breaker, double busbar
Q25.105.R03
Close(d) U B02 /
Tab. A5-691: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q10=X) & /(Q20=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q10=X) & /(Q20=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
A5.2.3.22 Bay type No. 211: Bus coupler bay with circuit breaker, double busbar
Q25.105.R04
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q10=X) & /(Q20=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q10=0) & (Q20=I) & /(FctBl1=I) & /(FctBl2=I) & (Q8=I)
Tab. A5-695: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q10=X) & /(Q20=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q10=0) & (Q20=I) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-696: Bay Interlock Equations for Operation with Station Interlocking
A5.2.3.23 Bay type No. 238: Bus coupler bay with circuit breaker, double busbar,
direct motor control
Q25.109.M03
Close(d) U B02 /
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q10=X) & /(Q20=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q10=X) & /(Q20=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
A5.2.3.24 Bay type No. 212: Bus coupler bay with circuit breaker, double busbar,
direct motor control
Q25.109.M04
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q10=X) & /(Q20=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q20=0) & (Q10=I) & /(FctBl1=I) & /(FctBl2=I) & (Q8=I)
Tab. A5-701: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q10=X) & /(Q20=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q20=0) & (Q10=I) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-702: Bay Interlock Equations for Operation with Station Interlocking
A5.2.3.25 Bay type No. 213: Bus coupler bay with circuit breaker, double busbar
Q25.109.R01
Close(d) U A04 /
Q8
Q20 (DEV03) Open U A05 / Q0
Close(d) U A06 /
Close(d) U B02 /
Tab. A5-703: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q10=X) & /(Q20=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-704: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q10=X) & /(Q20=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-705: Bay Interlock Equations for Operation with Station Interlocking
A5.2.3.26 Bay type No. 239: Bus coupler bay with circuit breaker, double busbar
Q25.109.R03
Close(d) U B02 /
Tab. A5-706: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q10=X) & /(Q20=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q10=X) & /(Q20=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
A5.2.3.27 Bay type No. 214: Bus coupler bay with circuit breaker, double busbar
Q25.109.R04
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q10=X) & /(Q20=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q20=0) & (Q10=I) & /(FctBl1=I) & /(FctBl2=I) & (Q8=I)
Tab. A5-710: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Open (Q8=0)
Close(d) /(Q10=X) & /(Q20=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q20=0) & (Q10=I) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-711: Bay Interlock Equations for Operation with Station Interlocking
A5.2.3.28 Bay type No. 240: Bus coupler bay with circuit breaker, double busbar,
direct motor control
Q25.113.M03
Close(d) U B02 /
Close(d) U B04 /
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q10=X) & /(Q20=X) & (Q15=0) & (Q25=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q10=X) & /(Q20=X) & (Q15=0) & (Q25=0) & /(FctBl1=I) & /(FctBl2=I)
A5.2.3.29 Bay type No. 215: Bus coupler bay with circuit breaker, double busbar,
direct motor control
Q25.113.M05
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q10=X) & /(Q20=X) & (Q15=0) & (Q25=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q10=0) & (Q20=I) & /(FctBl1=I) & /(FctBl2=I) & (Q15=I)
Close(d) (Q0=0) & (Q20=0) & (Q10=I) & /(FctBl1=I) & /(FctBl2=I) & (Q25=I)
Tab. A5-716: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q10=X) & /(Q20=X) & (Q15=0) & (Q25=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q10=0) & (Q20=I) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q20=0) & (Q10=I) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-717: Bay Interlock Equations for Operation with Station Interlocking
A5.2.3.30 Bay type No. 216: Bus coupler bay with circuit breaker, double busbar
Q25.113.R01
Close(d) U A04 /
Q15 Q25
Q20 (DEV03) Open U A05 / Q0
Close(d) U A06 /
Close(d) U B02 /
Close(d) U B04 /
Tab. A5-718: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q10=X) & /(Q20=X) & (Q15=0) & (Q25=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-719: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q10=X) & /(Q20=X) & (Q15=0) & (Q25=0) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-720: Bay Interlock Equations for Operation with Station Interlocking
A5.2.3.31 Bay type No. 241: Bus coupler bay with circuit breaker, double busbar
Q25.113.R03
Close(d) U B02 /
Close(d) U B04 /
Tab. A5-721: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q10=X) & /(Q20=X) & (Q15=0) & (Q25=0) & /(FctBl1=I) & /(FctBl2=I)
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q10=X) & /(Q20=X) & (Q15=0) & (Q25=0) & /(FctBl1=I) & /(FctBl2=I)
A5.2.3.32 Bay type No. 217: Bus coupler bay with circuit breaker, double busbar
Q25.113.R05
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q10=X) & /(Q20=X) & (Q15=0) & (Q25=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q10=0) & (Q20=I) & /(FctBl1=I) & /(FctBl2=I) & (Q15=I)
Close(d) (Q0=0) & (Q20=0) & (Q10=I) & /(FctBl1=I) & /(FctBl2=I) & (Q25=I)
Tab. A5-725: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Close(d) /(Q10=X) & /(Q20=X) & (Q15=0) & (Q25=0) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q10=0) & (Q20=I) & /(FctBl1=I) & /(FctBl2=I)
Close(d) (Q0=0) & (Q20=0) & (Q10=I) & /(FctBl1=I) & /(FctBl2=I)
Tab. A5-726: Bay Interlock Equations for Operation with Station Interlocking
A5.2.4.1 Bay type No. 218: Bus coupler and sectionalizer bay with circuit
breaker, double busbar
K29.101.R02
Close(d) U B02 /
Close(d) U B04 /
Close(d) U B06 /
Close(d) U C02 /
Close(d) U C04 /
Tab. A5-727: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
A5.2.4.2 Bay type No. 219: Bus coupler and sectionalizer bay with circuit
breaker, double busbar
K29.101.R06
Close(d) U C02 /
Close(d) U C04 /
Tab. A5-730: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(Q10=X) & /(Q20=X) & /(FctBl1=I) & /
(FctBl2=I)
Q1 Open (Q0=0)
Q2 Open (Q0=0)
X0 Open (Q0=0) & (Q1=0) & (Q2=0) & (Q10=0) & (Q20=0)
Close(d) (Q0=0) & (Q1=0) & (Q2=0) & (Q10=0) & (Q20=0)
Tab. A5-731: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q0 Close(d) /(Q1=X) & /(Q2=X) & /(X0=X) & /(Q10=X) & /(Q20=X) & /(FctBl1=I) & /
(FctBl2=I)
Q1 Open (Q0=0)
Q2 Open (Q0=0)
X0 Open (Q0=0) & (Q1=0) & (Q2=0) & (Q10=0) & (Q20=0)
Close(d) (Q0=0) & (Q1=0) & (Q2=0) & (Q10=0) & (Q20=0)
Tab. A5-732: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.1 Bay type No. 171: Busbar measurement bay with fuse unit, single
busbar
M11.300.R00
Close(d) U A02 /
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-734: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-735: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.2 Bay type No. 172: Busbar measurement bay with fuse unit, single
busbar
M11.300.R01
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-737: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-738: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.3 Bay type No. 540: Busbar measurement bay with fuse unit, single
busbar
M11.304.R02
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-741: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.4 Bay type No. 173: Busbar measurement bay with other switchgear unit,
single busbar
M11.900.R00
Close(d) U A02 /
X0
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-743: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-744: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.5 Bay type No. 174: Busbar measurement bay with other switchgear unit,
single busbar
M11.900.R01
X0
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-746: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-747: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.6 Bay type No. 175: Busbar measurement bay with fuse unit, single
busbar, direct motor control
M13.312.M02
F
Close(d) U A04 K A04
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-750: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.7 Bay type No. 176: Busbar measurement bay with fuse unit, single
busbar
M13.312.R01
F
Close(d) U A04 /
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-752: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-753: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.8 Bay type No. 177: Busbar measurement bay with fuse unit, single
busbar
M13.312.R02
F
Close(d) U A04 K A04
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-756: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.9 Bay type No. 506: Busbar measurement bay with other switchgear unit,
single busbar
M13.902.R00
Close(d) U A02 /
BB1
Q1
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-758: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-759: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.10 Bay type No. 232: Busbar measurement bay with other switchgear unit,
single busbar, direct motor control
M15.903.M01
Close(d) U A04 /
Q8
Motor relay (SIG_1: Sig nal S01 2 EX T) U B06 /
Switchgear
Control O/C Interlock equation
unit
Q1 Close(d) (Q8=0)
Tab. A5-761: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q1 Close(d) (Q8=0)
Tab. A5-762: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.11 Bay type No. 178: Busbar measurement bay with other switchgear unit,
single busbar, direct motor control
M15.903.M02
Switchgear
Control O/C Interlock equation
unit
Q1 Close(d) (Q8=0)
Q8 Close(d) (Q1=0)
Tab. A5-764: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q1 Close(d) (Q8=0)
Q8 Close(d) (Q1=0)
Tab. A5-765: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.12 Bay type No. 233: Busbar measurement bay with other switchgear unit,
single busbar
M15.903.R01
Close(d) U A04 /
Q8
Switchgear
Control O/C Interlock equation
unit
Q1 Close(d) (Q8=0)
Tab. A5-767: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q1 Close(d) (Q8=0)
Tab. A5-768: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.13 Bay type No. 179: Busbar measurement bay with other switchgear unit,
single busbar
M15.903.R02
Switchgear
Control O/C Interlock equation
unit
Q1 Close(d) (Q8=0)
Q8 Close(d) (Q1=0)
Tab. A5-770: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q1 Close(d) (Q8=0)
Q8 Close(d) (Q1=0)
Tab. A5-771: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.14 Bay type No. 180: Busbar measurement bay with fuse unit, double
busbar
M21.302.R02
F1 F2
X01 (DEV03) Open U A05 /
Close(d) U A06 /
Close(d) U B02 /
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-773: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-774: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.15 Bay type No. 181: Busbar measurement bay with fuse unit, double
busbar
M21.302.R04
F1 F2
X01 (DEV03) Open U A05 K A05
Switchgear
Control O/C Interlock equation
unit
Close(d) (Q1=0)
Close(d) (Q2=0)
Tab. A5-776: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Close(d) (Q1=0)
Close(d) (Q2=0)
Tab. A5-777: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.16 Bay type No. 182: Busbar measurement bay with fuse unit, double
busbar
M21.312.R02
Close(d) U A06 /
Close(d) U B02 /
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-780: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.17 Bay type No. 183: Busbar measurement bay with fuse unit, double
busbar
M21.312.R04
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-783: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.18 Bay type No. 184: Busbar measurement bay with other switchgear unit,
double busbar
M21.902.R02
Close(d) U A06 /
Close(d) U B02 /
Tab. A5-784: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-785: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-786: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.19 Bay type No. 185: Busbar measurement bay with other switchgear unit,
double busbar
M21.902.R04
Switchgear
Control O/C Interlock equation
unit
Close(d) (Q1=0)
Close(d) (Q2=0)
Tab. A5-788: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Close(d) (Q1=0)
Close(d) (Q2=0)
Tab. A5-789: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.20 Bay type No. 186: Busbar measurement bay with other switchgear unit,
double busbar
M21.912.R02
Close(d) U A06 /
Close(d) U B02 /
Tab. A5-790: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-792: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.21 Bay type No. 187: Busbar measurement bay with other switchgear unit,
double busbar
M21.912.R04
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-795: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.22 Bay type No. 188: Busbar measurement bay with fuse unit, double
busbar
M23.302.R02
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-797: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-798: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.23 Bay type No. 189: Busbar measurement bay with fuse unit, double
busbar
M23.312.R02
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-801: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.24 Bay type No. 190: Busbar measurement bay with fuse unit, double
busbar, direct motor control
M23.328.M04
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-804: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.25 Bay type No. 191: Busbar measurement bay with fuse unit, double
busbar
M23.328.R02
Close(d) U A06 /
Close(d) U B02 /
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-806: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-807: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.26 Bay type No. 192: Busbar measurement bay with fuse unit, double
busbar
M23.328.R04
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-810: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.27 Bay type No. 193: Busbar measurement bay with other switchgear unit,
double busbar
M23.902.R02
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-812: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-813: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.28 Bay type No. 559: Busbar measurement bay with other switchgear unit,
double busbar
M23.904.R00
Close(d) U A02 /
BB1
BB2
Q15
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-815: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-816: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.29 Bay type No. 509: Busbar measurement bay with other switchgear unit,
double busbar, direct motor control
M23.906.M01
Close(d) U A04 /
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-818: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-819: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.30 Bay type No. 529: Busbar measurement bay with other switchgear unit,
double busbar, direct motor control
M23.906.M02
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-822: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.31 Bay type No. 560: Busbar measurement bay with other switchgear unit,
double busbar
M23.908.R00
Close(d) U A02 /
BB1
BB2
Q25
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-824: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-825: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.32 Bay type No. 510: Busbar measurement bay with other switchgear unit,
double busbar, direct motor control
M23.910.M01
Close(d) U A04 /
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-827: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-828: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.33 Bay type No. 530: Busbar measurement bay with other switchgear unit,
double busbar, direct motor control
M23.910.M02
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-831: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.34 Bay type No. 194: Busbar measurement bay with other switchgear unit,
double busbar
M23.912.R02
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-834: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.35 Bay type No. 234: Busbar measurement bay with other switchgear unit,
double busbar, direct motor control
M25.903.M02
Close(d) U A06 /
Close(d) U B02 /
Switchgear
Control O/C Interlock equation
unit
Q1 Close(d) (Q81=0)
Q2 Close(d) (Q82=0)
Tab. A5-836: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q1 Close(d) (Q81=0)
Q2 Close(d) (Q82=0)
Tab. A5-837: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.36 Bay type No. 195: Busbar measurement bay with other switchgear unit,
double busbar, direct motor control
M25.903.M04
Switchgear
Control O/C Interlock equation
unit
Q1 Close(d) (Q81=0)
Q2 Close(d) (Q82=0)
Switchgear
Control O/C Interlock equation
unit
Q1 Close(d) (Q81=0)
Q2 Close(d) (Q82=0)
A5.2.5.37 Bay type No. 235: Busbar measurement bay with other switchgear unit,
double busbar
M25.903.R02
Close(d) U A06 /
Close(d) U B02 /
Tab. A5-841: Assignment of Binary Inputs and Output Relays
Switchgear
Control O/C Interlock equation
unit
Q1 Close(d) (Q81=0)
Q2 Close(d) (Q82=0)
Tab. A5-842: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
Q1 Close(d) (Q81=0)
Q2 Close(d) (Q82=0)
Tab. A5-843: Bay Interlock Equations for Operation with Station Interlocking
A5.2.5.38 Bay type No. 196: Busbar measurement bay with other switchgear unit,
double busbar
M25.903.R04
Switchgear
Control O/C Interlock equation
unit
Q1 Close(d) (Q81=0)
Q2 Close(d) (Q82=0)
Switchgear
Control O/C Interlock equation
unit
Q1 Close(d) (Q81=0)
Q2 Close(d) (Q82=0)
A5.2.6.1 Bay type No. 129: Busbar grounding bay with other switchgear unit,
single busbar, direct motor control
E13.901.M01
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-849: Bay Interlock Equations for Operation with Station Interlocking
A5.2.6.2 Bay type No. 130: Busbar grounding bay with other switchgear unit,
single busbar
E13.901.R01
Q15
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-852: Bay Interlock Equations for Operation with Station Interlocking
A5.2.6.3 Bay type No. 131: Busbar grounding bay with other switchgear unit,
double busbar, direct motor control
E23.903.M02
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-855: Bay Interlock Equations for Operation with Station Interlocking
A5.2.6.4 Bay type No. 132: Busbar grounding bay with other switchgear unit,
double busbar
E23.903.R02
Switchgear
Control O/C Interlock equation
unit
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-858: Bay Interlock Equations for Operation with Station Interlocking
A5.2.7.1 Bay type No. 1: Other bay type with other switchgear unit, without
busbar
X99.901.R00
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-860: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-861: Bay Interlock Equations for Operation with Station Interlocking
A5.2.7.2 Bay type No. 980: Other bay type with other switchgear unit, without
busbar
X99.902.R06.2
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-863: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-864: Bay Interlock Equations for Operation with Station Interlocking
A5.2.7.3 Bay type No. 981: Other bay type with other switchgear unit, without
busbar
X99.903.R12.2
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-866: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-867: Bay Interlock Equations for Operation with Station Interlocking
A5.2.7.4 Bay type No. 982: Other bay type with other switchgear unit, without
busbar
X99.904.R06.2
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-869: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-870: Bay Interlock Equations for Operation with Station Interlocking
A5.2.7.5 Bay type No. 983: Other bay type with other switchgear unit, without
busbar
X99.905.R12.2
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-872: Bay Interlock Equations for Operation without Station Interlocking
Switchgear
Control O/C Interlock equation
unit
―
Tab. A5-873: Bay Interlock Equations for Operation with Station Interlocking
A6 Version History
This manual is dedicated for the Easergy MiCOM 30 Series with colored graphic
HMI. The version history of P139 is listed. Please refer to the manuals before
software version -670 for old graphic HMI.
Hardware
As an alternative slot 4 can now be equipped with the 5-pole voltage transformer
module T (for the Automatic Synchronism Check function).
Additional to the 40 TE case variant with pin-terminal connection there is now an
84 TE case variant with ring-terminal connection as well as a 40 TE case variant
with a combination of pin- and ring-terminal connection (transformer module: for
ring-terminal connection; other modules: for pin-terminal connection)
The binary (I/O) module X(6xO) is now optionally available with rapid-response
output by 4 thyristors.
Diagram
The updated connection diagrams now include the 5-pole voltage transformer
module T and show the variants with ring-terminal connection:
● P139 -402 (for 40 TE case, with pin-terminal connection)
● P139 -403 (for 84 TE case, with ring-terminal connection)
● P139 -404 (for 40 TE case, transformer module: with ring-terminal
connection; other modules: with pin-terminal connection)
Software
LOC Measurands previously missing are now included in the selection of the
Operation Panel, Overload Panel and Ground Fault Panel:
● (004 134) ME ASI : Cu rren t ID C
● (004 135) MEA SI: Cu rre nt ID C p.u .
● (004 136) MEASI : Cu rr. ID C,li n. p.u.
● (005 100) MEASO: Curre nt A -1
● (005 099) MEASO: Cu rren t A-2
Bug fixing:
● Control actions from the local control panel are now no longer rejected in
the DNP3 protocol.
PC User-defined signal selections for the PC interface can now be made by setting
(003 189) PC : Sele ct . spon tan .si g., and these selected signals are
spontaneously transmitted in addition to the VDEW signals.
The PC interface "Time-out" can now be set with the parameter (003 188) PC:
T ime-out.
OUTP, LED Addition of function assignment to output relays and LED indicators with these
signals:
SFMON : D efect .modu le sl ot 1 (097 000)
to
SFMON : Defect .modu le sl ot20 (097 019)
Now defective modules can be indicated by output relays for instance.
MAIN The following signals were added to the parameter setting selection tables for
the trip command blocking signals:
● (003 173) C O MM1: Comman d block. E XT
● (037 074) C OMM1 : Si g./meas . block EX T
● (040 014) OUTP: Block ou tp.re l . EXT
● (037 070) MAIN: Te st mode EXT
● (036 045) MA IN: Trip cmd. block. EX T
The following signals were added to the selection table for:
● (097 004) S FMON: D efe ct.modu le sl ot 5
● (097 017) SFMON: D efe ct.modu le sl ot1 8
● (097 118) to (097 123) SFMON: De fect.module slot19 … SFMON:
Error K 120 6
The following settings for the 5th VT input were added to the MAIN function
group:
● (010 100) MAI N: V ref ,n om V .T. pri m.
● (031 052) MAI N: V ref ,n om V .T. se c.
● (011 034) MAIN: Me as . val . re l. V r ef
The direct time output signals of the 32 logic equations are now available to the
function assignment of trip command 1 and trip command 2.
In addition to the standard procedure to determine energy output a second
procedure is now available. The selection of the procedure depends on the given
load ratio and is made by setting (010 138) MAI N: O p. mode energy cnt..
The physical communication channel assignment to the "logical" communication
interfaces COMM1 and COMM2 can be set with the parameter (003 169) MAIN:
C hann.assign.C OMM1/2.
Addition of two measured operating values:
● (005 046) MAIN: V oltage Vre f pri m.
● (005 047) MAIN: Vol tage V r ef p.u .
Incorrect termination is now fixed for the close commands issued by the control
function and terminated with the starting of the trip command.
Time switching to setting “Daylight saving time” (003 095) MAIN: Time
swit ching is now stored so that it will remain valid after a warm restart.
The multiple signal (036 251) MA IN: Gen . trip signal is now supported.
Bug fixing:
● Rated current setting is changed from 1 A to 5 A when electro-magnetic
interference occurs. To confirm settings the internal values of (010 003)
MA IN : I nom de vi ce and (010 026) MAIN: I N,nom device are
overwritten by the set values once every software cycle.
● A disabled residual current system protection, which is displayed by the
signal (040 134) MAI N: Sys tem IN disable d is now considered by the
DTOC and IDMT residual current stages.
● During incrementation of the overflow counter for active and reactive
energy output and input a negative value of the integrated count is now
prevented.
MAIN, ARC, ASC, In addition to enabling or disabling of the functions Auto-Reclosing Control,
PSIG Automatic Synchronism Check, Protective Signaling and Residual Current
System protection by using two binary signal inputs it is now possible to use just
one binary signal input for enabling or disabling. If, for example, only the signal
(037 010) AR C : E nable E XT is assigned to one binary signal input, the
function is enabled by the rising edge and disabled by the falling edge of the
input signal.
DTOC Step size for thresholds I>, I>> and I>>> reduced from 0.1 Inom to 0.01 Inom.
ARC New function Automatic Synchronism Check (ASC) is taken into account by the
Auto-Reclosing Control (ARC) function. The signal (037 077) AR C: (R e)close
request is used in this context to have ASC triggered by ARC.
ASC Function Automatic Synchronism Check (ASC) has been added: The voltage and
synchronism conditions are checked before an automatic or manual closing
occurs.
The transformer module T with a fifth VT is required to provide a reference
voltage.
GFDSS A fixed time delayed reset of 80 ms is now implemented for the stage (016 062)
GF DSS: V NG>.
COUNT The unit (min) was added to the parameter (217 007) COUNT: Cycle t. count
t ransm in the data model.
SFMON Because of the addition of a fifth VT these warning signals were added:
● (098 022) SF MO N: F F, V re f trigge red
● (098 023) SFMON: M.ci rc. V, Vre f f lty.
Addition of function assignment to warnings by the delayed and direct time
signals from logic equations 30 to 32.
The following signals that are included in the function selection of warnings are
fully supported now:
● (098 026) SF MO N: Ope n circ. 2 0mA i np.
● (098 024) SFMON: PT100 ope n circu it
● (098 025) S FMON: Ove rload 2 0 mA input
Hardware
No changes.
Diagram
No changes.
Software
SFMON Decreased severity for entries in the monitoring signal memory during short-
time supply voltage dipping.
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
LOC The signals (221 005) LOC: Loc. acc.block.acti ve and (221 004) L OC:
Rem.a cc.block.active are now sent spontaneously as individual signals with
the protocol IEC 60870-5-103.
INP The function assignment of the binary signal inputs U 1001 to U 1006, which are
not present on slot 10, have been removed from the data model.
Hardware
Device is prepared for the supplementary fitting with the new temperature p/c
board (RTD module), which will become available as of version P139
-304-405/406/407-605.
Diagram
No changes.
Software
COMM1 The measurand (005 047) MAI N: V oltage Vre f p.u. has been added to the
selection for the cyclic ILS telegram.
The unnecessary parameter (003 168) COMM1 : A ddress mode is now
hidden.
LOC The measurand (005 046) MA IN: Vol tage V ref prim. has been added to the
function assignment for the Operation Panel, the Overload Panel and the
numerical display.
The measurand (005 047) MA IN: Vol tage Vre f p.u. has been added to the
function assignment for the Operation Panel, the Overload Panel and the bar
chart display.
MEASI, THERM, Functions have been enhanced in preparation for the supplementary fitting with
LIMIT, SFMON the new temperature p/c board (RTD module). For THERM protection this
includes direct temperature monitoring, temperature measurement, coolant
temperature acquisition, and open-circuit monitoring of the individual resistance
thermometers.
MAIN, ARC, ASC, The functionality of equal-priority enabling or disabling a function via any device
PSIG interface is modified now in that way, that the functions are enabled by default.
IDMT The setting ranges for parameters Iref,neg and Iref,N as well as Iref,neg dynamic and
Iref,N dynam have been increased from 0.1 – 4.00 Inom to 0.01 – 4.00 Inom.
ASC Setting to continuous synchronism test procedure after a test close request:
When a test close request is issued the operative time is not terminated by the
starting of the close enable but will continue until it has reached its set time
duration. Synchronism is continuously checked, even after the first close enable,
as long as the operative time is running. The signal (037 083) A SC : C lose
enable (if synchronism conditions are met) and the delta measured values are
continuously updated and periodically transmitted by the device interfaces. The
cycle time to transmit the telegram with the measured values is set at:
● (101 212) AS C: Trans m .cycle, meas .v.
The signal close enable is signaled spontaneously both as “start” and as “end”
and must therefore be included in a general scan.
The signal (037 086) A SC: Cl ose re j ecti on is issued only after the operative
time has elapsed and there is then no synchronism. This signal is also issued
after a test close request if, during the operative time, a close enable is
temporarily signaled.
The number of test close requests and the number of close rejections after test
close requests are not counted, e.g. the counters (009 033) A SC: No. close
requests and (009 034) A SC: No. cl ose re j ection s will only consider
“authentic” close requests.
If during the operative time (after a test close request) there is an authentic
close request issued by the device control function (HMI) or from the interfaces
(or the ARC) the test run is terminated and ASC is restarted. Then, after the first
close enable is reached, the close command is issued and the operative time is
terminated. The signal (037 086) A SC: Cl ose re j ection is issued when the set
operative time has elapsed without synchronism conditions having been met
and the circuit breaker is not switched.
The setting range for the operative time was increased from 0.00 – 60.00 s to
0.0 – 6000.0 s and the step range was reduced from 0.01 s to 0.1 s.
The settable reset times for the signals (0XX 241) ASC: tClos e en able
Volt .PS x, (0XX 240) ASC: tClos e en able syn. PSx have been replaced by
fixed minimum times of 100 ms.
These measured event values have been added to the Automatic Synchronism
Check:
● (004 087) A SC : V ol tage Vre f
● (004 088) AS C: Vol t. s el. me as. loop
The measuring range of the measured event value:
● (004 091) A SC : V ol t. magnit . diff .
has been changed from 0.000 – 3.000 Vnom to −3.000 … 3.000 Vnom.
LIMIT If the temperature measurand T was set to not measured the stages T< and
T<< in the limit value monitoring function would start.
Hardware
A new communication module A, providing the InterMiCOM protective interface
COMM3 (InterMiCOM), is available now as an ordering option.
A new temperature p/c board (RTD module) can now be fitted in slot 3, instead of
the transient ground fault detection module N (TGFD module).
As an alternative to the conventional transformer modules for analog input
signals there is now a new CT/VT-board with NCIT available. Details are available
on request.
Binary signal inputs with a higher switching threshold are now available.
Installation is only recommended if the application specifically requires such
binary signal inputs.
Diagram
The new connection diagrams include the InterMiCOM communication interface
(function group COMM3), the temperature p/c board (RTD module) and the
CT/VT-board with NCIT.
● P139 -405 (for 40 TE case, with pin-terminal connection)
● P139 -406 (for 40 TE case, transformer module: with ring-terminal
connection; other modules: with pin-terminal connection)
● P139 -407 (for 84 TE case, with ring-terminal connection)
Software
COMM1 The fault location (004 029) FT_DA : Faul t re act., prim. (Function Type 80h,
Information Number 49h), will no longer be sent spontaneously, if its value is
Not measured.
With the fault values transmission the scaling factor for the primary value of
channel VNG was corrected by a factor of 1/√3.
Bug fixing:
● DNP3: Multiple telegrams are prevented.
● The protocol per IEC 60850-5-101 incorrectly transmitted negative
operating values.
● IEC 60870-5-101: In the data model there was an incorrect selection for
parameter (003 198) COMM1: Tim e tag l e ngt h. Furthermore 3 Bytes
were used irrespective of the setting.
● IEC 60870-5-103: For the reclose commands of high-speed and time-
delayed reclosing (Function Type 80h, Information Numbers 80h and 81h),
the status changes “On” to “Off” were signaled spontaneously and were
transmitted as part of the response to a general scan.
COMM3 New function group COMM3 (InterMiCOM protection interface) permits end-end
channel-aided schemes to be configured, without the need of discrete carrier
equipment.
INP Further reset commands were added to the function assignment of binary signal
inputs.
MEASO Scaling of the BCD coded output of measurands now allows the setting of an
output values range. This feature is required if signed event measurands are
assigned to the BCD output (like fault location or short-circuit reactance,…).
MAIN Sensitivity for the setting of this parameter was increased to 0.01 s: (017 054)
MAIN : Suppre ss star t. s ig..
The determination of the faulty phase during a ground fault in Petersen coil
compensated power systems is improved to avoid incorrect signaling at the end
of the ground fault.
These measured operating values have been added:
● (005 025) MA IN : Appar. powe r S pri m.
● (005 026) MA IN : Appar. powe r S p. u.
● (005 009) MA IN : Angle Σ VP G vs . IN
The delay time for the Running Time Monitoring of manually operated
switchgear can now be set: (221 079) MAI N: De lay Man.Op. Super v..
Bug fixing:
● All energy counters were reset by a general starting (GS).
● The values set for the primary transformer voltages were reset to their
default values when a warm restart of the device occurred.
● If a device or switchgear designation was omitted in a customized panel
then the device went out of order when such a panel was selected.
MAIN, ARC, ASC, The stored status is no longer reset with a warm restart of the device, when
PSIG specific functions are enabled or disabled through a binary signal input.
FT_DA The determination of measured fault values during short fault times is
improved.
Bug fixing:
● Fault locations of numerical values >655.35% were falsely displayed as
small values.
● When a residual current starting occurs without a phase current starting
all measured fault values dependent on a measurement loop are set to
Not measured.
FT_RC Direction signaling for the short-circuit direction determination function was
added to the selection table for the fault recording trigger (003 085) FT _RC:
Fct . assig. tri gg er.
TGFD The setting range of (016 042) TGFD: IN, p> is extended down to 0.03 Inom.
The pick-up delay of the measuring circuit monitoring signal (093 094) SFMON:
TGF D mon. t rig ge red is now increased from 5 s to 65 s.
P<> The power directional protection now includes overload stages for active and
reactive power.
The starting signals from the power directional protection stages now feature
direction dependency.
The setting range for the parameter (017 172) P <>: Release delay Q> PSx
is now extended to max. 100.00 s.
LIMIT Reference voltage monitoring was added to the Limit Value Monitoring function.
CMD_1 Single commands, created with the bay editor from the PC Access Software
MiCOM S1, can now also be configured to output relays on the output module
X(6O) in slot 10 (with 40 TE cases) or slot 18 (with 84 TE cases).
Hardware
The new Ethernet module for communication per IEC 61850 is now available and
may be fitted to slot 2 as an alternative to communication module A.
Diagram
The updated connection diagrams now include the Ethernet module
communication interface.
● P139 ‑408 (for 40 TE case, with pin-terminal connection)
● P139 ‑409 (for 40 TE case, transformer module: with ring-terminal
connection; other modules: with pin-terminal connection)
● P139 ‑410 (for 84 TE case, with ring-terminal connection)
Software
LOC Addition of the event counter to the selection for the Fault Panel ASC: No. RC
aft. man .clos (004 009).
Addition of the measured value to the selection for the Operation Panel MEASI:
Scaled value ID C,l in (004 180).
COMM1 The selection of register assignments for signals in the MODBUS protocol has
been extended with the signal SCDD: Fau lt P backward (036 019) erweitert.
Time stamping of status signals from external devices has been adapted to the
DNP3 protocol.
Bug fixing:
● A change of a communication parameter will no longer lead to a sporadic
warm restart of the device, when the Courier protocol is used.
COMM3 After a warm restart with COMM3 activated, the entry at SFMON: Har dwa re
error C OM M3 (093 143) will now only occur if there actually is such a
hardware error.
SFMON A number of device bugs previously led to a blocking with the second entry to
the monitoring signal memory (i. e. if the recurring fault was already stored in
the monitoring signal memory – see Chapter “Troubleshooting” in the Technical
Manual). This reaction was modified in such a manner that device blocking will
only occur if a renewed appearance of the same device fault lies within a set
“memory retention time” (021 018) SF MO N: Mon. sig. ret e nt ion. This makes
it possible to tolerate sporadic faults, resulting from control actions, without
having to clear the monitoring signal memory in the interim.
The significance of the time stamp was modified to accommodate this new
feature. The time stamp now represents the last appearance of the fault.
OUTP, LED Addition of the signal (034 018) ASC: Cl ose requ est to the selection of freely
configurable LED indicators and output relays.
MEASI Open-circuit monitoring of the 20 mA input and the “PT 100” input has been
improved.
MAIN Parameters from the MAIN function, which could previously only be set in the
branch "General Functions" of the menu tree, have been transferred to the
parameter subsets.
● MAI N: N eut r.pt. t re at. PSx
● MA IN : Hld ti me dyn.par.P Sx
● MAIN : B l.tim.st.IN, ne g PSx
● MAI N: Ge n. star t. m ode P Sx
● MAI N: Op . r ush re st r. PSx
● MA IN : R ush I( 2fn) /I( f n) PSx
● MAI N: I >l ift rus h res trP Sx
● MAI N: Suppr.start.si g. P Sx
● MAIN: t GS PSx
With this improvement it is now possible to consider operational changes by
selecting the appropriate parameter subset.
The parameter (010 048) MAIN: Neu tr. pt. treat. PSx used only in
conjunction with the ASC is now visible if the ASC function has been configured.
Furthermore the selections at various neutral point treatments that occur by this
parameter have now been reduced to a selection relevant to the application.
The primary source for synchronizing the date and time can now be selected.
Available are COMM1, COMM2/PC, IRIG-B or a binary input for minute signal
pulses. A backup source may additionally be selected.
● (103 210) MAIN: P rim.Sour ce Ti me Syn c
● (103 211) MA IN: Backu pSource Time Sync
For bay control function signals detected via binary signal inputs and
conditioned with debouncing it is now possible to select whether the time tag for
the signal is to be issued after debouncing (or when the first pulse edge is
detected). The setting (221 083) MA IN: Ti me TagAfter Debounce is provided
for this purpose.
Bug fixing:
● The enabling or disabling of the ground protection via a binary signal input
was incorrectly inverted.
ASC Selecting the CB assignment to an external device has been adapted to the
maximum possible number of external devices.
Bug fixing:
● The enabling or disabling of the ASC function via a binary signal input was
incorrectly inverted.
GFDSS The setting parameters for the function GFDSS are now included in the
parameter subsets and can be changed, according to operating conditions, by
selecting the appropriate parameter subset. It is also possible to individually
enable this function in each parameter subset.
Processing of the function GFDSS now occurs with a higher priority in order to
obtain reduced reaction times with less fluctuation. This is a response to the
increased application of ground fault direction signaling as a tripping condition.
Bug fixing:
● The cause for faulty or unstable directional decisions with the operate
delay tVNG> set below 60 ms has been removed.
● The operate delays LS and BS are now accurate, even with set values
> 65 s.
TGFD The setting parameters for the function TGFD are now included in the parameter
subsets and can be changed, according to operating conditions, by selecting the
appropriate parameter subset. It is also possible to individually enable this
function in each parameter subset.
P<> The setting range for the following parameters was extended from max.
0.5 Snom to now max. 1.5 Snom:
● (017 120) P<>: P > PSx
● (017 140) P <>: P >> PSx
● (017 160) P <>: Q> P Sx
● (017 180) P <>: Q>> P Sx
Bug fixing:
● When setting a high operate value as well as a high disengaging ratio for
the P< or Q< stages an internal overflow was possible that led to a lower
disengaging ratio than that which had been set.
● When the stage P< (P<<, Q< or Q<<) was triggered the signal
P<>: Fault P< (P<<, Q< or Q<<) was issued even though the operate
delay for the stage was blocked.
CBM Function group circuit breaker monitoring (CBM) has been added.
LIMIT Parameter cells and signals related to Vref are only visible when the device has
been fitted with a fifth VT to measure Vref .
Hardware
No changes.
Diagram
No changes.
Software
IEC With regard to IEC 61850-8-1 the data type for the quality of measured values
and signals has been changed from 14 bit to 13 bit.
Hardware
Further variants with binary signal inputs with a higher operate threshold are
now available. This makes the following selections available:
● >18 V (standard variant) (Without order extension No.)
● >90 V (60...70% of VA,nom = 125 ... 150 V) (Order ext. No. 461)
● >155 V (60...70% of VA,nom = 220 ... 250 V) (Order ext. No. 462)
● >73 V (67% of VA,nom = 110 V) (Order ext. No. 463)
● >146 V (67% of VA,nom = 220 V) (Order ext. No. 464)
Standard variant recommended if higher pickup threshold is not specifically
required by application.
Diagram
No changes.
Software
COMM1, COMM2 With the IEC 60870-5-103 protocol, the selection of measured operating values
has been extended for the cyclic ILS telegram.
IEC General expansion of the Logical Nodes according to the IEC 61850 data model.
For access by the support software S1 via Ethernet the function “Setting by
Tunneling” has been implemented.
GOOSE For the exchange of binary information in an Ethernet network section the
IEC 61850 communication procedure (IEC-GOOSE) has been implemented.
SFMON Change of the English signal designation for this signal: (098 072) SFMON: CB
faulty EX T
MAIN The following per unit measured operating values have been added:
● (009 016) MA IN: C urr en t Ipos p.u.
● (009 015) MAI N: Cu rre nt In eg p.u.
● (009 018) MAI N: V oltage V pos p.u.
● (009 017) MA IN: Vol tage Vne g p. u.
● (004 070) MA IN: Fre que ncy f p.u .
● (005 072) MAI N: A ngl e V PG/IN p.u .
● (005 073) MA IN: L oad an gl e phi A p.u
● (005 074) MAIN: Load angl e ph i B p.u
● (005 075) MAIN: Load angl e ph i C p.u
● (005 076) MAIN: A ngle phi N p.u.
The parameter (010 049) MAIN: R otar y fie l d was renamed to (010 049)
MAIN: Phase se que nce. In addition the parameter selection for clockwise
and anticlockwise was also changed to A-B-C and A-C-B.
Change of the English signal designation for the following parameters:
● (103 210) MAIN: Pri m.Source Time Sync
● (103 211) MA IN : BackupSource Ti meSyn c
FT_RC The signal (002 002) FT_RC : Re cord.trig acti ve has been implemented,
which shows that a fault-recording trigger is present.
FT_DA When a fault location is outside the measuring range it could happen that the
fault location was measured as too small by the fault measurand (004 027)
FT _DA: Fault l ocat. percen t.
DTOC A fourth overcurrent stage (residual current stage) IN>>>> with an extended
setting range has been integrated.
Because of its extended setting range this stage always uses the residual
current calculated from the three phase currents.
SCDD A voltage memory has been added to the short-circuit direction determination
function. In general SCDD will operate as previously with the non-faulted
voltages. Now the device offers a voltage memory from which the SCDD
function can obtain necessary voltage information for direction determination
when 3-pole faults with a large 3-phase voltage drop have occurred.
MP The motor protection function has been extended by these per unit measured
operating values:
● (005 071) MP: Th erm. re pl . MP p. u.
● (005 086) MP: St-u ps st. pe r m.p.u.
THERM The parameters THERM: Bl. f . C TA f aul t P Sx have been replaced by the
parameters with an extended setting range THERM: Fun ct. f.CTA fail. PSx.
In order to obtain improved visibility control of the parameters for the relative
and absolute replica the previous parameter (022 063)
THERM: Op erat in g m ode has been replaced by:
● (022 064) THERM: Re lati ve re pl ica
● (022 065) THE R M: A bsol ute re pl ica
It should be remembered that an explicit selection – relative or absolute
replica – for the thermal overload protection must be carried out. If no such
explicit selection – relative or absolute replica – is carried out the thermal
overload protection will be blocked and the warning signal (039 110) THERM:
Set ting error,bl ock. is issued.
These parameters are now available to set the over temperature and the
warning temperature in the absolute replica:
● THERM: O/T f.Ire f pe rs . PSx
● THER M: War nin g te mp. P Sx
The following signals have been added to the thermal overload protection:
● (039 024) THERM: Re clos ur e blocke d
● (040 035) THERM: Not re ady
V<> The over-/undervoltage function may now be optionally operated with an enable
threshold based on the minimum current monitor for the undervoltage stages
(V<, V<<, Vpos<, Vpos<<).
The undervoltage stages are blocked if during active monitoring the set
threshold of at least one phase is not exceeded by the phase currents. There
are two new setting parameters to activate the operating mode for minimum
current monitoring and to set the enable threshold:
● V<>: Op. mod e V < mon . PSx (001 162)
● V<>: I e nab le V< PSx (001 155)
CBF The complete revision of the circuit breaker failure protection function now
includes a current breaking-off criterion.
The previous signal (036 017) CBF: CB fai l ur e has been replaced by the
following signals:
● (038 215) C BF: Tr ip s ignal t1
● (038 219) CBF : Tri p s ignal t2
(Note: The signal (036 017) CB F: CB fai l ure becomes available again as of
version ‑613.)
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
INP The request routine for binary signal inputs has been enhanced to suppress
external interference.
Hardware
As an ordering option for the 40 TE and 84 TE model versions there is now a
variant available with a detachable HMI. The detachable HMI is always supplied
with a case width of 40 TE. The freely configurable LED indicators H4 to H16 on
the detachable HMI are provided as multi-color LEDs.
The ordering option Ethernet module with 100 Mbit/s glass fiber and ST
connector has replaced the ordering option Ethernet module with 10 Mbit/s glass
fiber and ST connector.
Diagram
The updated connection diagrams now include the interfaces to connect the
detachable HMI.
● P139 -411 (for 40 TE case, with pin-terminal connection)
● P139 -412 (for 40 TE case, transformer module: ring-terminal connection;
other modules: pin-terminal connection)
● P139 -413 (for 84 TE case, with ring-terminal connection)
Software
DVICE, LOC Because of the ordering option “detachable HMI” these additional Device
Identification parameters are now available:
● (002 131) D VI CE: SW ve rsi on DH MI
● (002 132) DV IC E: SW vers ion D HMI DM
● (221 099) LOC : Local H MI e xis ts
LOC Additional item in the selection table for the operation panel: (217 100)
C O UN T: Count 1.
COMM1 When the protocols per IEC 60870-5-101 or IEC 60870-5-103 are used, the
message (221 100) COMM1: Buf fe r ove rru n is issued when an internal buffer
overrun of the spontaneous control function signals has occurred.
GOOSE VLAN priority for GOOSE is set via (106 007) GO OSE: VL AN Priority.
The dataset reference for GOOSE is displayed via the measured value (106 008)
GOOSE: Dat aSe t R ef e ren ce.
LED The operating mode for the LED indicators has been extended by the operating
mode LED flashing.
Configuration, operating mode and physical state of the permanently configured
LED indicators H1 and H17 are now displayed via configuration parameters and
physical state signals.
The freely configurable LED indicators H4 to H16 may now be assigned two
signals, each with a different color (red or green). If both assigned signals are
active the resulting LED color will be “amber”.
MAIN The parameter (221 098) MAIN: Ti me tag has replaced the previous
parameter (221 083) MAI N: TimeTagA fte rDe boun ce. In addition there is a
third operating mode available for selection.
COUNT The settable debouncing time for count value acquisition is no longer required.
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
With this version resetting options have been extended such that now there is a
corresponding external signal available for each manual reset function; now the
respective counter or memory can be reset by an appropriately assigned binary
signal.
Similar to this all manual reset parameters have been renamed by adding the
phrase “USER” to the descriptive text (it may be abbreviated so that the max
number of characters allowed is not exceeded).
Example:
● MAI N: General r e se t was renamed to MA IN: General reset USER.
LOC A selection of memories to be reset may now be assigned (with the new
parameter LOC: A ssi gnme nt r e se t key) to the CLEAR key situated on the
local control panel. Now each time the CLEAR key is pressed not only the LED
indicators and the display are reset but the selected memory is also reset
immediately.
Additionally two menu jump lists are now available that can have functions
assigned by setting these new parameters:
● LOC : Fct. menu j mp lis t 1 and
● LOC: Fct . men u jm p li st 2
SCDD For earth fault direction evaluation it is now settable, whether the measured or
the calculated displacement voltage is used for the direct evaluation.
ARC In case of a starting shorter than the set trip time during an ARC cycle the
reclaim time resettled with the beginning of the starting is set again instead of
interruption of the ARC cycle as before.
Selective determination of phase- and earth faults implemented. Only selective
starting signals with activated ARC trip time will be considered for ARC trip.
All parameters containing the phrase “Ineg>” in the descriptive text have been
renamed and now use the term “Iref,neg”. Similarly the terms “kIref>” and
“kINref>” were renamed to “IrefP>” and “IrefN>”.
SFMON The parameter (093 075) SFMON: Inval . SW ve rs. C OMM1 was renamed to
SFMON : I nv al. SW COMM1/I EC (093 075).
MEASI In case a hardware fault on the temperature p/c board (RTD module) is detected
then the parameter MEASI: RTD H W Fai lu re (006 102) is set. When a
hardware fault is detected on the analog I/O module Y the parameter MEA SI:
I /O HW F ailure (006 103) is set.
DEVxx The state signals are now stored in the operating data memory:
● (218 000) DEV 01: Open cmd. r ece i ve d (…etc for DEV02,…)
● (218 001) DE V01: Clos e cmd. re ce ive d (…etc for DEV02,…)
Supporting of 3 position disconnector / earthing switch.
CBF The signal (036 017) CBF: CB f ailure was not supported in previous version.
IEC IEC : D e ad band v alue (104 051) was divided into several individual settings:
● (104 229) I EC: Update Me as ure m en ts
● (104 230) IEC : De ad band IP
● (104 231) I EC: De ad band IN
● (104 232) IE C: De ad band VP P
● (104 233) I EC : D e ad band V PG
● (104 234) I EC: D ead ban d f
● (104 235) IEC : De ad band P
● (104 236) IE C: D ead ban d phi
● (104 237) IEC: De ad band Z
● (104 238) I EC: D ead ban d min /max
● (104 239) IEC: Dead ban d A SC
● (104 240) IEC: Dead ban d te mp.
● (104 241) I EC: De ad band 20mA
Bug fixing:
● Correction in the modeling of: DtpPhsPTOC3, DtpEftPTOC3, DtpEftPTOC4,
ItpPhsPTOC2, DtpEftPTOC2 and RREC1: ModOper
GOOSE The number of addressable external devices was increased from 16 to 32.
The parameter GOOSE: Dat ase t C fg.Revi si on (106 005) was renamed to
GOOSE : D ataSet C fg.Re vis ion (106 009) and all parameters
GOOSE: Ext .De vxx int erm. pos (xx=1 to 16) are now available as GO OS E:
Ex t.D ev yy int erm .pos (yy=01 to 32).
MAIN Two group reset parameters implemented, each of which will reset several
memories "simultaneously” with configurable assignment of eligible memories.
The group reset is now issued by a manual reset from the local control panel,
and may also be created by linking it to a binary signal input or a function key.
The parameter (006 096) MAI N: Meas . P ,Q,C OS allows for setting the sign of
the following measured operating data values for active and reactive power:
● (004 050) MAI N: A ctive powe r P prim.
● (004 052) MAIN : Reac. powe r Q pri m.
● (004 051) MAIN : Active power P p. u.
● (004 052) MA IN: Reac. pow er Q p.u .
The following logic state signals are issued depending on the respective control
point position:
● (221 101) MAI N: Cmd. fr. comm.inte rf
● (221 102) MA IN : C omm an d from HMI
● (221 103) MAI N: Cmd. f r. e lectr.ctrl
COMM1/IEC, COMM2/PC, IRIG-B or a minute pulse input may now be selected as
the primary source to synchronize the date and time (MA IN: Prim.Sou rce
TimeSyn c (103 210)).
COMM1/IEC, COMM2/PC, IRIG-B or a minute pulse input continue to be available
as the backup source (MAIN: BackupSource TimeSync (103 211)).
THERM The descriptive text in English for the following parameter has been changed:
THERM: Rset t her m.repl.USER to THERM: Res e t replica U SER
(022 061)
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
TGFD New version of the software module for Transient Ground Direction
Determination.
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
LOC The parameter L OC: A ssi gn men t read ke y (080 110) was renamed to LO C :
Fct . rea d k ey
MAIN The following measured operating data for delayed/stored phase current values
have been added:
● MAIN : I A pri m, de mand (006 226)
● MAIN : IB prim,de mand (006 227)
● MA IN: I C p rim,de mand (006 228)
● M AI N: IA prim ,dem an d s tor. (006 223)
● MAI N: IB pr im ,dem and stor. (006 224)
● MAIN : I C prim,deman d s tor . (006 225)
● MA IN : I A p .u.,de mand (006 235)
● MAI N: IB p.u .,de mand (006 236)
● MAI N: IC p.u .,de mand (006 237)
● MAI N: IA p.u ., de mand stor. (006 232)
● MA IN : I B p.u.,deman d s tor. (006 233)
● MAI N: IC p.u .,de mand s tor. (006 234)
The label of the parameter MAIN: Me as. P ,Q,CO S, that has been introduced
with version ‑613 and that allows for changing the sign of the displayed values
of the active and reactive power, has been changed to: MAIN: Meas.
d irecti on P,Q.
The descriptive text in English for the following parameters has been changed:
● MAI N: IP ,maxprim,de mand.st (005 034)
● MA IN : I P,maxp.u.,de mand.st (005 035)
● MAIN : IP,max prim. ,deman d (005 036)
● MAIN : IP,max p.u.,deman d (005 037)
● MA IN : P h. e rr. V CG, 2 NC IT (010 194)
INP The setting INP : Fil ter (010 220) is now available for conformity with standard
IEC 60255-22-7, class A.
MP Now the device features an “hours run” counter and this includes a comparison
to the corresponding set upper limit.
The descriptive text in English for the following parameter has been changed:
MP: Rse t therm.repl.U SER to MP: Res e t replica USER (022 073).
CBF The signal CBF: CB failure (036 017) is now available again.
The parameter designation for (022 160) CBF: I> was changed to (022 160)
CBF: I<.
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
Hardware
Three optional new binary I/O modules are now available:
● Bi6Bo6H: Control board with 6 binary signal inputs and 6 output relays with
heavy duty contacts
● Bo4H: Binary output relay board with 4 heavy duty contacts
● Bi6Bo3: Control board with 6 binary signal inputs and 3 output relays
Diagram
The updated connection diagrams now include the interfaces with the new binary
I/O modules.
● P139-414 (for 40TE case, with pin-terminal connection)
● P139-415 (for 40TE case, transformer module: with ring-terminal
connection; other modules: with pin-terminal connection)
● P139-416 (for 84TE case, with ring-terminal connection)
Software
LOC New address for the hold-time of the measured value display added. (031 072)
LOC : Hold-t . meas.v.dis pl
Values range from 1 to 60 seconds.
Default setting blocked, therefore the behavior is backward-compatible (new
functionality disabled).
Functionality: With the Bay Panel display the next or the previous configured
measured value may be selected by pressing the keys “cursor down” or “cursor
up”. The new feature is that the next value will appear after the set time period
has elapsed. When set to blocked the selected value will always be displayed.
Bug fixing:
● The Password Display mode was not supported during a startup.
THERM The new measured operating value “Thermal current” has been implemented as
a part of function group THERM.
Statustherm,repl
I therm,prim = 100 · I ref · I nom,CT,prim
V<> The stages Vref>, Vref>> and Vref<, Vref<< have been added to the time-voltage
protection function:
New parameters:
● V<>: V ref> P Sx
o (007 064, 007 071, 007 075, 007 079)
● V<>: Vre f>> P Sx
o (007 065, 007 068, 007 072, 007 076)
● V<>: t Vr e f> PSx
o (007 066, 007 069, 007 073, 007 077)
● V<>: t Vre f>> P Sx
o (007 067, 007 070, 007 074, 007 078)
● V<>: V ref< P Sx
o (007 086, 007 097, 007 101, 007 105)
● V<>: Vre f<< PSx
o (007 087, 007 098, 007 102, 007 106)
● V<>: tVr ef< PSx
o (007 088, 007 099, 007 103, 007 107)
● V<>: t Vref<< PSx
o (007 096, 007 100, 007 104, 007 108)
MAIN Measured operating values are now also calculated during a general starting
condition and no longer set to “not measured”.
New addresses with a 32 bit measured value display have been added for the 4
energy measured values:
● (008 065) MAIN: Act.en ergy outp.prim
o 0 ... 6,553,500.00 MWh
● (008 066) MAIN: Act.en ergy in p. pri m
o 0 ... 6,553,500.00 MWh
● (008 067) MA IN: Re act.e n. ou tp. prim
o 0 ... 6,553,500.00 Mvar h
● (008 068) MA IN: R eact. e n. inp. pr im
o 0 ... 6,553,500.00 Mvar h
The 4 addresses with the 16 bit display and overrun counter have been
removed.
IEC, GOOSE Phase 2 of the IEC 61850 communications protocol has been implemented.
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
Hardware
The following three new binary I/O modules are now available as ordering
options:
● Bi6Bo6H: Binary module with 6 binary signal inputs and 6 high-power
contacts
● Bo4H: Binary module with 4 high-power contacts
● Bi6Bo3: Binary module with 6 binary signal inputs and 3 output relays
Diagram
The updated connection diagrams include the wiring configuration for the new
binary I/O modules.
● P139 ‑414 (for case 40TE, pin-terminal connection)
● P139 ‑415 (for case 40TE, CT/VT ring-, all other modules pin-terminal
connection)
● P139 ‑416 (for case 84TE, ring-terminal connection)
Software
Bug fixing:
● All parameters of function group FKEY (which is not supported by this
device) were removed. (Since the HMI of the P139 does not have any
function keys, these parameters were invalid.)
LOC New parameter for the hold-time of the measured values display.
● (031 072) L OC: Hol d-t. meas .v.dis pl
Range: 1 to 60 seconds.
The default value is blocked, so that the behavior is backward-compatible (i.e.
the new functionality is deactivated).
Functionality: On the Bay Panel, one can select the previous or next configured
measured value by pressing the “Up” or “Down” key, respectively. This works
exactly like before. The new feature is that always after the set time the display
automatically steps forward to the next value. If the parameter is set to blocked,
the selected measured value is always displayed.
Bug fixing:
● The Password Display mode was not supported during a startup.
MAIN Measured operating values are now also calculated during a general starting
condition and no longer set to “not measured”.
New addresses with a 32 bit measured value display have been added for the 4
energy measured values:
● (008 065) MAI N: A ct.en ergy outp.pr im
o 0 ... 6,553,500.00 MWh
● (008 066) MAI N: A ct.en ergy in p. pri m
o 0 ... 6,553,500.00 MWh
● (008 067) MAI N: Re act.e n. ou tp. pri m
o 0 ... 6,553,500.00 Mvar h
● (008 068) MA IN : Re act. en . in p. pr im
o 0 ... 6,553,500.00 Mvar h
The 4 addresses with the 16 bit display and overrun counter have been
removed.
V<> The setting range for Vneg> and Vneg>> has been extended. New setting range:
0.02 to 1.5 Vnom/√3 (previously: 0.2 to 1.5 Vnom/√3). This affects the following
parameters:
● V<>: Vn eg > PSx
● V<>: V ne g>> PSx
DEV01 ... DEV10 User-defined names can now be used as device identifiers. In the parameter
D EVx x: D esi gnat. e xt. de v., the new option Device Name User is available.
Then the text for the device's name, entered by the user at each of the
D EVxx : D EV -Name Use r parameters, will be used as the device’s
designation. (The maximum length is 4 characters, as with the fixed identifiers.
Any longer text entered is truncated to 4 characters internally.) The following
parameters are new:
(218 101) DEV 01: D EV -Nam e U se r
to
(218 110) DEV 10: D EV -Nam e U se r
Hardware
No changes.
Diagram
No changes.
Software
Bug fixing:
● For those parameters which allow for setting options dependent on the
fitted modules, slot 18 was visible for 40 TE cases, too, although this
particular slot does not exist for this case size.
Hardware
No changes.
Diagram
No changes.
Software
Hardware
As a further ordering option the Chinese character set is now available for the
HMI.
Diagram
No changes.
Software
DEV01 ... DEV10 User-defined names can now be used as device identifiers. In the parameter
DE Vx x : De sign at. ext. dev., the new option Device Name User is available.
Then the text for the device's name, entered by the user at each of the
DEVxx : D EV-N ame U ser parameters, will be used as the device’s
designation. (The maximum length is 4 characters, as with the fixed identifiers.
Any longer text entered is truncated to 4 characters internally.) The following
parameters are new:
(218 101) DE V0 1: DEV -Name Use r
to
(218 110) D EV1 0: DEV -Name Us e r
MAIN The phase sequence for the current, given by the active parameter subset with
the setting at MAI N: P has e reve rsal I PSx (010 200, 010 201, 010 202, 010
203), may be reversed by triggering a binary signal input configured at MAIN:
Phase reversal I EXT (007 248).
To enable the function a phase sequence for normal operation must be set in
the parameter. (Setting selection: A-B swapped, B-C swapped, C-A swapped.)
The default setting is No swap, which disables the function.
Note: This feature is primarily designed for motor protection applications with
“left/right” motor rotation control by phase reversal with parallel circuit breakers
(one CB with phase reversal). Here the voltage is measured on the busbar side
and the current down-stream between CB and motor. Dependent on the
operating mode the current can therefore be measured in phase reversal to the
voltage.
The values range for the 3 power measured values has been expanded:
● (005 025) MA IN: Appar. powe r S pri m.
o -3,199.9 – 3,200 MVA
● (004 050) MAIN: Active power P pri m.
o -3,199.9 – 3,200 MW
● (004 052) MA IN: Reac. powe r Q pri m.
o -3,199.9 – 3,200 Mvar
DTOC The “IN Measured” or “IN Calculated” setting, which was previously available
only globally for all three residual current stages IN>, IN>> and IN>>> together,
can now be set individually for each residual current stage.
Parameters:
● DTOC: E val. IN>> PSx
o (007 239, 007 240, 007 241, 007 242)
● DTOC : E val . IN>>> PSx
o (007 243, 007 244, 007 245, 007 246)
The setting parameter previously valid for all three residual current stages,
D TOC: Ev al. I N>, >>, >>> PSx (072 128, 073 128, 074 128, 075 128), has
been renamed to DTOC: Eval . IN> P Sx (072 128, 073 128, 074 128, 075
128) and will now only operate with the first residual current stage.
DTOC, IDMT1, IDMT2 The inrush stabilization has been extended by DTOC: IN> PSx and IDMT 1:
Ire f,N PSx, I DMT2 : I re f, N PSx.
DTOC, IDMT When a phase starting is present then a subsequent triggering of the inrush
stabilization is not taken into account anymore.
Note: When a change from a single-pole fault to a two-phase fault or from a two-
phase fault to a three-phase fault occurred it was possible that, because of
transients during the change, the inrush stabilization was momentarily triggered
which would reset the starting and the timer.
IDMT1 For all IP, Ineg and IN types of characteristics the enable threshold for the IDMT1
protection starting can now be set with the factor KI (values range: 1 to 10)
dependent on Iref. This factor KI will result in a linear shifting of the enable
threshold along the X-axis of the respective characteristic. The factor will not
result in a shifting of the characteristic itself.
Parameters:
● I DMT1: Factor KI,P PSx
o (007 250, 007 251, 007 252, 007 253)
● ID MT1: Fact or KI,ne g PSx
o (007 254, 007 255, 008 002, 008 005)
● ID MT 1: Fact or KI,N P Sx
o (001 173, 001 174, 001 175, 001 176)
ASC Function ASC now provides a choice as to whether the CB operating time (tCB),
as configured at Function Parameters/Global/MAIN, is to be taken into account
for the precisely synchronized reclosure (AR) or not.
Parameters:
● MAIN: t CB,cl ose
o (000 032); value range: 0.06s … 1s
● ASC : A R with tCB P Sx
o (000 038, 000 039, 000 050, 000 051)
FT_RC An additional analog recording channel for the frequency has been
implemented.
Parameter:
● FT_RC : Re c. analog ch ann. 10 (035 169)
Default is Without, optional setting is fnom.
CBM The correction acquisition time can now be set separately to be triggered by the
open command and by the position signal issued by the CB auxiliary contacts.
Differing inherent delay times from the two command chains can now be
configured independently of each other so as to achieve optimum time
adjustment.
Parameter:
● CBM: Corr. acqu .time trip
o (007 249); values range: 0 to 0.2 s
The previous common selection parameter CBM: Corr. acquis. time
(022 018) values range: (-0.2 s to 0.2 s), has been renamed to CBM:
C orr.a cqu.t. C B si g. and is now only a correction acquisition time value
affecting the position signal issued by the CB auxiliary contacts.
SFMON The S FMO N: TGFD mon. tri gge re d signal is now no longer permanently
listed in the alarm signal list.
Depending on the application this signal can now be configured using
parameterSFMON : Fct. as s ign. war nin g (021 030).
V<> The minimum value for the parameters below was changed from 0.2 to 0.02:
● V<>: Vneg> P Sx
o (076 023, 077 023, 078 023, 079 023)
● V<>: Vneg>> P Sx
o (076 024, 077 024, 078 024, 079 024)
Change of label text for the reference voltage (separate input) from “Vnom” to
“Vref,nom”.
MP In case of parameter switching (e.g. via LIMIT) the number of permitted motor
startups (3/2 – 2/1) is now correctly detected. The thermal replica, however, is
lost in this case.
I2> The settable lower limit for I2> is now 0.02·Inom (2%).
Hardware
No changes.
Diagram
No changes.
Software
MP When switching between parameter subsets (e.g. via LIMIT) the number of
permitted motor startups (3/2 – 2/1) is now determined accurately. However,
the thermal replica is lost in this case.
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
MAIN In the case of direct motor control by motor relay K200 monitoring has been
modified.
With previous P139 software versions, the direction control contacts would open
in the following case: The K200 contacts have not opened until the end of the
command to the motor when the set monitoring time-delay had expired
(monitoring via binary signal input –U 706, signal SIG_1: Signal S0 12 EXT as
the standard setting). This reaction by the P139 (the previously permanent
feature) would result in interrupting the motor control command circuit and
thereby preventing an undefined switch position. However, this would involve
the danger of contact burn.
By setting the new selection parameter (221 111) MA IN: Cmd.en d f .K20 0
fa il . it is now possible to select whether the previous reaction (setting = Yes) or
a new behavior (setting = No) is effected.
In this new implementation option, the P139 issues respective fault signals when
the monitoring time delay has expired and the direction control contacts will
remain closed. (Note: This new feature bears the danger of an undefined switch
position!)
For this new implementation option, the following new logic state signals have
been added:
● (221 108) MAI N: K200 f ail. cmd. en d - This signal is issued if the K200
contacts have not opened after the set monitoring time-delay has elapsed.
● (221 109) MAI N: K200 f ail. cmd.start - This signal is issued if the K200
contacts have not closed after the set monitoring time-delay has elapsed.
● (221 110) MAI N: DE V op.ti me e xcee de d - This fault signal is issued
(as a group signal) when no positive position signal (status signal) has
been received from the external device after a command has been issued
and the set running time-delay has elapsed.
For further processing each of these new fault signals may be configured to
selection parameters from the function groups LED (assignment to LED
indicators), OUTP (assignment to output relays), LOGIC (processing by the
programmable logic function), COMMx / IEC / GOOSE (signaling via the control
system) or they may be mapped to the signal panel as an alarm signal.
Acknowledging from the local control panel HMI is done by pressing the CLEAR
(C) key.
The four 16 bit energy measured values, that existed for earlier software
versions and were then replaced by 32 bit energy measured values, have been
re-introduced, so that as of now, both the 16 bit and 32 bit values are available.
● (005 061) MAIN : Act.en ergy outp.prim
● (005 062) MA IN : Ac t.e ne r gy i np. prim
● (005 063) MA IN : Re act.e n. outp. prim
● (005 064) MA IN : React. e n. i np. prim
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
MAIN The four 16 bit energy measured values, that existed for earlier software
versions and were then replaced by 32 bit energy measured values, have been
re-introduced, so that as of now, both the 16 bit and 32 bit values are available.
● (005 061) MA IN: Act.e ne rgy outp.prim
● (005 062) MA IN: A ct. en er gy i np. prim
● (005 063) MAI N: Re act.e n. outp. prim
● (005 064) MA IN: React. e n. i np. prim
LOC The descriptive text in English for the following parameters has been changed:
● (218 192) L OC : Bu sbar2 Name by Us e r
● (218 193) L OC: Bu sbar3 Name by Us er
The previous English descriptive texts – LOC: Bus bar#-NameUser, # = 2,3 –
differed from those used for LOC: Bus bar 1 Name by User which made
harmonization necessary.
Bug fixing:
● The display Local/Remote in fields with the three position switches was
sometimes incorrect.
● In case of a cold restart incorrect symbols could appear for a short time on
the display.
Hardware
No changes.
Diagram
No changes.
Software
Hardware
New Schneider Electric design for the local control panel (HMI).
Diagram
No changes.
Software
COMM1 The data point (003 178) COMM1: -1 03 prot. variant may now be used to
select between the ‑103 protocol variants Private and Compatible. The protocol
variant Compatible corresponds to the VDEW implementation.
Note: As before this setting is hidden unless an IEC 60870-5 protocol is enabled.
The data point (003 214) COMM1: MOD BUS prot. variant may now be used
to select between the MODBUS protocol variants Private and Compatible. The
protocol variant Compatible corresponds to the MODBUS implementation in the
MiCOM Px20 and Px40 protection devices. The protocol variant Private
corresponds to the first implementation of the MODBUS protocol.
Note: As before this setting is hidden unless the MODBUS protocol is enabled.
Bug fixing:
● Measured energy values were not transmitted by the MODBUS protocol.
COMM1, COMM2 The menu points (003 161) C OMM1: Name of manufacturer and (103 161)
CO MM2: Name of manuf actu rer can no longer be set by using a selection
list but, for reasons of compatibility, they may now be defined as free text. The
default is SE but, in individual cases, it may become necessary to enter texts
differing from the default.
Notes:
● These parameters can only be set using the operating program and it is
not possible to set them locally using the integrated local control panel
(HMI). The maximum text length is 8 characters and designations
exceeding this will be truncated.
● The parameter CO MM1: Name of man uf acturer is hidden unless an
IEC 60870-5 protocol is enabled.
MCMON Setting menu point (017 023) MCMON: Ope rate delay = Blocked is now
supported.
Enhanced accuracy with monitoring of Vmin<.
Bug fixing:
● Monitoring of Vmin< was stopped by (040 000) MAI N: Gen eral s tar t ing.
I2> The threshold for the input current was decreased from 0.1·Inom to 0.01·Inom.
Hardware
New Schneider Electric design for the local control panel (HMI).
Diagram
No changes.
Software
PC The following parameter has been removed: PC: Name of manufact urer
(003 183).
Note: Compatibility even with older versions of the operating program continues
to be guaranteed.
COMM1 The data point (003 178) COMM1: -103 prot. va riant may now be used to
select between the ‑103 protocol variants Private and Compatible. The protocol
variant Compatible corresponds to the VDEW implementation.
Note: As before this setting is hidden unless an IEC 60870-5 protocol is enabled.
The data point (003 214) COMM1: MODBUS prot. variant may now be used
to select between the MODBUS protocol variants Private and Compatible. The
protocol variant Compatible corresponds to the MODBUS implementation in the
MiCOM Px20 and Px40 protection devices. The protocol variant Private
corresponds to the first implementation of the MODBUS protocol.
Note: As before this setting is hidden unless the MODBUS protocol is enabled.
Bug fixing:
● Measured energy values were not transmitted by the MODBUS protocol.
COMM1, COMM2 The menu points (003 161) COMM1: Name of m anufacturer and (103 161)
COMM2: N am e of m anu factur er can no longer be set by using a selection
list but, for reasons of compatibility, they may now be defined as free text. The
default is SE but, in individual cases, it may become necessary to enter texts
differing from the default.
Notes:
● These parameters can only be set using the operating program and it is
not possible to set them locally using the integrated local control panel
(HMI). The maximum text length is 8 characters and designations
exceeding this will be truncated.
● The parameter COMM1: Name of manu fact ure r is hidden unless an
IEC 60870-5 protocol is enabled.
MCMON Setting menu point (017 023) MCMON: Operate delay = Blocked is now
supported.
Enhanced accuracy with monitoring of Vmin<.
Bug fixing:
● Monitoring of Vmin< was stopped by (040 000) MAI N: Gen eral s tart ing.
● The value set for menu point (014 012) MCMON: Oper. delay F F,
Vref was ignored (e.g. the “Fuse Failure” monitoring function of the
reference voltage was triggered without delay).
Hardware
No changes.
Diagram
No changes.
Software
Hardware
Slot 3 of the P139 can now also be fitted with the binary module X(24I) or with
the analog module Y(4I). (See the Supporting Document for details.)
The P139 is now by default available with the serial graphical display and with
multi-colored LEDs.
(The variant with detachable graphical display (DHMI) is available as an
alternative option.)
Diagram
The diagrams document the new fitting variants, which are described above.
● P139 -417: case 40 TE, pin-terminal connection
● P139 -418: case 40 TE, CT/VT ring-, I/O pin-terminal connection
● P139 -419: case 84 TE, ring-terminal connection
Software
This software version is available in the following language variants:
● German + English (order option -801),
● French + English (order option -802),
● Spanish + English (order option -803),
● Polish + English (order option -804),
● Russian + English (order option -805).
MAIN In the case of direct motor control by motor relay K200 monitoring has been
modified.
With previous P139 software versions, the direction control contacts would open
in the following case: The K200 contacts have not opened until the end of the
command to the motor when the set monitoring time-delay had expired
(monitoring via binary signal input –U 706, signal SIG_1: Signal S0 12 EXT as
the standard setting). This reaction by the P139 (the previously permanent
feature) would result in interrupting the motor control command circuit and
thereby preventing an undefined switch position. However, this would involve
the danger of contact burn.
By setting the new selection parameter (221 111) M AIN: Cmd.end f .K 20 0
fa il. it is now possible to select whether the previous reaction (setting = Yes) or
a new behavior (setting = No) is effected.
In this new implementation option, the P139 issues respective fault signals when
the monitoring time delay has expired and the direction control contacts will
remain closed. (Note: This new feature bears the danger of an undefined switch
position!)
For this new implementation option, the following new logic state signals have
been added:
● (221 108) MA IN: K200 fail . cmd. e nd - This signal is issued if the K200
contacts have not opened after the set monitoring time-delay has elapsed.
● (221 109) MA IN: K200 fail . cmd. start - This signal is issued if the K200
contacts have not closed after the set monitoring time-delay has elapsed.
● (221 110) MA IN: DEV op.time exce e de d - This fault signal is issued
(as a group signal) when no positive position signal (status signal) has
been received from the external device after a command has been issued
and the set running time-delay has elapsed.
For further processing each of these new fault signals may be configured to
selection parameters from the function groups LED (assignment to LED
indicators), OUTP (assignment to output relays), LOGIC (processing by the
programmable logic function), COMMx / IEC / GOOSE (signaling via the control
system) or they may be mapped to the signal panel as an alarm signal.
Acknowledging from the local control panel HMI is done by pressing the CLEAR
(C) key.
Bug fixing:
● The minimum value was corrected for the following power measurement
parameters:
o (005 025) MA IN: A ppar. pow er S pri m.
o (004 050) MA IN: Active powe r P pri m.
o (004 052) MA IN: Re ac. pow er Q prim.
DTOC, IDMT In case of a short-time triggering of the inrush stabilization the DTOC/IDMT
timers are no longer reset.
MAIN, DEVxx The following new configuration parameters allow for defining monitoring timers
for the switchgear units:
(210 007) DEV0 1: StartC mdTi me s u pe rv.
(210 057) DEV 0 2: StartC mdTime superv.
(210 107) DE V0 3: St artC mdTi me s u pe rv.
(settable in the range 0.1 s … 10.0 s, default: blocked)
After sending an Open / Close command, the corresponding timer starts. If the
switchgear unit has not reached its intermediate position after this time has
elapsed then the command is deactivated.
In case of a switchgear unit for which it is (almost) impossible to detect the
intermediate position it is recommended to switch off this monitoring by setting
the parameter to blocked.
If the monitoring is active then an exceeded timer is flagged by the new logic
state signal (221 112) MAIN: Startcmdtim e exc eed..
Hardware
The P139 is now fitted with an improved power supply module.
Note that the voltage range has changed for DC input:
● For the DC / AC variant, the range is
o now 60 … 250 VDC / 100 ... 230 VAC
o (previously 48 … 250 VDC / 100 ... 230 VAC).
● For the DC-only variant, the range is
o now 24 … 60 VDC
o (previously 24 VDC).
Diagram
No changes (compared to P139 -310 -634).
Software
No changes (compared to P139 -310 -634).
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
GOOSE The GOOSE Time Allowed to Live (TAL) supervision is enhanced with respect to
simultaneous state changes of multiple GOOSE messages.
Hardware
A new communication module (“REB” = “Redundant Ethernet Board”) is now
available as an ordering option.
This module can be used for redundant communication via IEC 61850 and may
be fitted to slot 2, as an alternative to the other communication modules. The
following communication protocols are supported:
● SHP (Self-Healing Protocol).
● RSTP (Rapid Spanning Tree Protocol).
● DHP (Dual-Homing Protocol).
A detailed description of the module and the appropriate network connections is
available as a separate document (“Redundant Ethernet Board, Application
Guide”).
Diagram
No changes.
Software
No changes (compared to P139 -311 -634).
Hardware
No changes (compared to P139 -312 -634).
Diagram
No changes (compared to P139 -312 -634).
Software
IEC The Originator Category information is now extensively supported for control
commands.
Bug fixing:
● During the process of connection with clients that use the “IntegrityPeriod”
option, sporadically the MMS communication of the Ethernet
communication module would crash without an internal monitoring
response to re-establish the functionality. (GOOSE messaging and other
communication tasks were not affected.)
● Upon receiving a “Cancel” command while a switchgear device is selected,
a positive acknowledgement response (“Ack OK”) is sent. Previously, a
“Negative ack” was sent.
● If clients did connect to the device immediately after completion of
Ethernet communication module startup, this could lead to the temporary
erroneous reporting of default values for the external device status
(DEVxx) and of the single-pole signals (SIG_1).
● If a close command could not be performed because of a rejection from
the sync-check function, the command termination message is now sent
with the correct “Block by Synchrocheck” (11) acknowledgement code
number. Previously, code (16) “Timeout” was sent instead.
● Reports of events could get lost if too many state changes occurred in a
short period of time, especially during secondary injection testing.
● Events that occured after a communication link had been interrupted and
before this interruption had been detected by the server, were not sent as
“Buffered reports” after the connection was re-established.
GOOSE The GOOSE Time Allowed to Live (TAL) supervision is enhanced with respect to
simultaneous state changes of multiple GOOSE messages.
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
Hardware
The P139 is now fitted with an improved processor module.
Diagram
No changes.
Software
New MiCOM P30 platform software.
Many parameter labels have been modified so that they harmonize with other
MiCOM P30 devices.
MAIN DTOC and IDMT with settable inrush stabilization per parameter subset:
Stabilization selectable per stage (Phase; E/F and I2 stages): MAI N:
Funct.Rush restr.P Sx (017 093, 017 064, 017 082, 017 083).
Settable maximum timer, for which inrush stabilization should be effective:
Blocked (w/o timer) or settable from 0.01 to 10s. (019 001, 019 002, 019 003,
019 004) MAIN : t li ft rus h rs tr.P Sx.
The previously available parameters (003 039) MA IN : Warm rest art und
(000 085) MAI N: Col d re start have been relabeled MA IN: Soft Warm
resta rt and MAIN : Sof t Cold re start, respectively. They still trigger a restart
of the device, but now the hardware tests are not carried out anymore during
the startup phase. (This way the restart needs less time.)
For a restart including hardware tests, the following new parameters can now be
used:
● (010 166) MAI N: W arm re start
● (009 254) MA IN : C ol d res tart
A setting for the release time of the enable for the manual close command is
now available:
● (003 088) MAIN : Re l.t . e nab. man. cmd
The manual trip command is enabled by:
● (003 105) MA IN : En .man .cl os.cmd.U SER
The enabling is signaled by the following new signal:
● (039 113) MAIN : Man. cl. cmd. en abl .
There is a pole-selective monitoring of the CB status signals available now (in
addition to the previously existing 3p monitoring).
New input signals:
● (031 029) MAI N: CB clos e d A EXT
● (031 030) MAI N: CB cl ose d B EXT
● (031 031) MAI N: CB clos e d C EXT
New logic state signals:
● (031 032) MA IN : C B open A
● (031 033) MAIN : CB ope n B
● (031 034) MAIN : CB ope n C
● (031 035) MAI N: CB close d A
● (031 036) MA IN : C B clos ed B
● (031 037) MA IN : C B cl ose d C
Note: The plausibility check operates with pole-selective monitoring only.
There is a phase-selective current flow monitoring available now, identical to but
independent of that in function group CBF.
● (010 223) MA IN : C urr en t flow A
● (010 224) MAI N: Curre nt fl ow B
● (010 225) MA IN : Cu rren t flow C
The setting for the neutral-point treatment of the system, MA IN: Neut r.pt .
tre at . PSx, is only used with the ASC, so that it is now visible only if the
function group ASC is configured. Moreover, the set of select options has been
restricted to those which are relevant for the application.
DVICE Instead of one parameter for the software version (previously: (002 120)
DVI CE: Sof t ware ve rsion) the version numbers ‑6XX and ‑7XX are now
separately stored in two new parameters:
● (010 167) DVIC E: Sof tware ve rsi on 6X X
● (010 168) D VI CE: Sof tware ve rsi on 7XX
PC, DVICE It is now possible to upload new firmware into the device via the TCP/IP protocol.
For this purpose there are several new network settings that are not identical to
the ones already existing within function group IEC:
● (111 004) PC : IP addre ss
o (111 005) PC: IP addre ss 1
o (111 006) PC: IP addre ss 2
o (111 006) P C : IP addre ss 3
● (111 008) PC: Subne t m ask
o (111 009) PC: Subn et mask 1
o (111 010) PC : Su bne t mas k 2
o (111 011) PC: Subne t mas k 3
● (111 016) PC: IP addre ss mode
● (111 017) PC : IP E nabl e confi g.
For testing purposes, information parameters store the updated network
settings for this firmware uploading network.
● (111 000) DV IC E: IP addre ss
● (111 001) DV IC E: Su bne t mask
● (111 003) DVICE : MA C addre s s
IEC The number of clients for a report has been increased: An unbuffered report
(urcbA … urcbP) can be allocated to max. 8 clients (previously: 1), and a
buffered report (brcbA … brcbH) can be allocated to max. 4 clients (previously:
1).
FT_DA The following measured fault data values have been introduced:
● (010 198) FT_DA : Fau lt type
● (010 217) FT_D A: Fl t.volt. PG/P P prim
● (010 199) F T_DA : F aul t curre nt P pr im
● (010 216) FT_D A: Fau lt curr. N pri m.
The parameters for the load data have been removed:
● (004 037) FT_DA : Load impe d. post-f lt.
● (004 038) F T_D A : L oad angl e pos t-f lt .
● (004 039) FT_DA : Res id.curr . pos t-fl t
The fault location may now be determined, based solely on a ground starting
condition (without a general starting). For this the P139 determines all three
phase-to-ground loop impedances and then provides the fault location based on
the reactance of the measurement loop with the lowest impedance value.
ASC There are separate parameters now for the manual close command and the
auto-reclose control.
The previously available parameters for the close enable conditions have been
relabeled such that the letters “AR” (for auto-reclose control) are now part of
the label, and there is a corresponding set of new “MC” (for manual close
command) parameters.
MP With the new parameter MP: Re tain re pl i ca P Sx (009 046, 009 250,
009 251, 009 252) it can now be configured whether the thermal replica is
retained in the non-volatile section of the device’s memory so that it will still be
available after an interruption of the supply voltage.
THERM With the new parameter TH ERM: Re tain re pl ica PSx (009 019, 009 030,
009 032, 009 039) it can now be configured whether the thermal replica is
retained in the non-volatile section of the device’s memory so that it will still be
available after an interruption of the supply voltage.
V<> Stages V>>>, V<<<, Vref>>> and Vref<<< have been added, including a separate
timer for each of these new stages.
For all three phase stages the 3p logic OR and AND results are signaled.
CBF It is now possible to also use the residual current (measured or calculated) as an
additional criterion for “circuit breaker open”.
The following setting parameters are new:
● (022 184) CBF : Evaluati on IN
● (022 180) C BF: IN<
The signal (038 235) C BF: Curre nt fl ow N = Yes flags that the residual
current IE is greater than the setting CBF: IN<.
ILOCK The new parameter (250 102) IL OCK: F uncti on group IL OCK allows for
cancelling (or configuring) the function group ILOCK. (Previously, this function
group was always enabled.)
LOG_2 There is a new function group LOG_2 (Programmable Logic 2). It is identical to
the previously available function group LOGIC, but it offers only four logical
equations. These, however, have long-term timers, settable from 0 to 60000 s
(= 16 hours, 40 minutes).
Hardware
No changes.
Diagram
No changes.
Software
COUNT The 4 counters have been equipped with individual debounce timers and limit
monitoring.
Settable limit thresholds and related alarm signals for counter values have been
implemented:
● Setting parameters:
COUNT: Limi t cou nter 1 (217 221) … COUNT: Limit counter 4
(217 224)
● Alarm signals:
C OU NT: W ar nin g cou nt 1 (217 191) … COUNT: Warning count 4
(217 194)
DVICE A “Select before operate (SBO)” operating mode interface has been
implemented as further alternative for local control via HMI (LOC), in addition to
the previously existing “Direct Mode”. Two new options are available with
different graphic visualization.
Setting parameter: LOC: Ope ration m ode (011 240)
Setting options: LOC Direct, LOC SBO option 1, LOC SBO option 2
MAIN A signal for the indication of chatter suppression start has been implemented:
MAIN: Ch att.suppr. s tarte d (221 121)
DTOC Under voltage controlled Phase Over-Current protection has been implemented.
Each of the three phase over-current stages can be applied now with a settable
V< (I>) release stage.
Setting parameters:
● D TOC : V< ( I>) P Sx (011 244)
● DTOC: V< (I >>) PSx (011 248)
● DTOC: V< (I >>>) PSx (011 252)
The default value of each of these parameters is blocked, which turns off the
voltage control.
MP The parameter MP : Pre -c los e time lef t shows the remaining time until the
next start-up procedure will be released. This parameter is supported by the
DNP 3.0 protocol, too.
Control (DEVxx, There is a new alarm signal for “switchgear operating time exceeded”: MAIN:
MAIN) DE V op.ti me exce eded
This signal is issued if the switching command is not successfully reset within
the set operation time by switchgear position indication or an external run-back
signal.
There is a new setting parameter, MAI N: ext.cmd. term. w /o PI (221 115), to
configure whether an “external termination” of the switching command is also
done based on position indication, or if only an external termination signal is
accepted.
DEVxx In addition to the direct motor control principle based on fixed logic (K200),
three configurable setting parameters have been implemented:
● (202 004) C MD _1: CMD_DC1 confi g. — with impulse characteristic
CMD _1: C MD_D C1 con fig. is for direct control of command starting
sequence only; additional original high precision contacts are used for
command reset and for disconnecting the power circuit of the motor drive.
● (202 009) C MD _1: CMD_DC2 conf ig. — without check back signal
● (202 014) C MD _1: CMD_D C3 config. — with check back signal
An operating counter and a settable limit threshold with related alarm signal has
been implemented for each DEVxx:
● (210 043) DEV01: Ope ration cou n ter … (211 243) D EV 1 0:
Operati on counte r
● (218 211) D EV01: Oper. count.li mi t … (218 220) D EV 10:
Oper .count .limi t
● (219 081) DE V01: War ni ng op.count. … (219 090) D EV 1 0: Warning
op.count.
There are two new setting parameters available for each device, which can be
used for blocking any open / close operation of the switchgear unit. These
parameters are not affected by interlocking conditions.
● (218 120) DEV0 1: Block cmd open … (218 129) DE V1 0: Block cmd
op en
● (218 160) DE V01: Block cmd clos e … (218 169) D EV 10: Block cmd
close
TPD1 … TPD4 Four virtual devices have been implemented, for the configuration of Three
Position Switchgear devices (TPD) using one common motor drive for
Disconnector and Earthing Switch. There is a fixed logic to prevent wrong
operation commands and to handle different switchgear positions during
clockwise or anti-clockwise operation.
An operating counter, settable limit thresholds and related alarm signals have
been implemented for the TPDx.
SIG_1 The number of SIG_1 input signals has been extended to 64. However, this
requires that two hardware modules of type X(24I) are fitted.
ILOCK With the ILOCK function assignments there are now also voltage and current
thresholds of the function group LIMIT selectable.
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
Remark: This software version replaces (and corrects) software version ‑650.
The bugs fixed with this version did not appear in any software version other
than ‑650.
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
GSSE The function group GSSE has been removed from the data model, because its
functionality has been replaced by the extended GOOSE input option.
COMM1 Signal and Command Blocking integrated in the General Interrogation for
protocols IEC 60870-5-101 and -103.
TGFD Minimum value for the VNG> release threshold extended down to 0.05 Vnom/
√3.
LOGIC The number of logic outputs (equations) has been extended to 128.
BTC The Bay Type Configurator (BTC) tool has been enhanced with new features for
the creation of customized bay types:
● Integration of new Binary I/O module options available on slot 9/10 for
40TE (or slot 18/20 for 84TE): X(4H), X(6O), X(3I 6O).
● Integration of new module option 2nd X(24I) available on slot 3.
● Extension to 64 binary signals in Function Group SIG_1.
● New command type for direct control using the High Break Contacts of
module X(4H).
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
Hardware
The Redundancy Ethernet Board (REB) can now be ordered with an additional
redundancy protocol: PRP (Parallel Redundancy Protocol) is available now as an
alternative to RSTP, SHP or DHP.
Diagram
No changes.
Software
DTOC, IDMTx New setting parameters allow to select for each overcurrent stage of the phase
and the residual currents whether the starting decision shall be based on the
fundamental or on the r.m.s. value.
Remark: For the negative-sequence stages, the starting decision is always
based on the fundamental.
The following settings are new:
● (060 002) DTOC: Me as. valu e I/I E> PSx
● (060 006) D TOC: Me as.val . I/IE>> P Sx
● (060 010) DTOC: Me as. val. I/I E>>> PSx
● (060 014) DTOC: Meas .v. I/I E>>>> PSx
● (060 018) I D MT1: Me as. valu e I/I E PSx
● (060 022) I D MT2: Me as. valu e I/I E PSx
Hardware
Optionally, a binary module of type X(6I/8O) can now be fitted in slot 8 (40 TE
case) or slot 16 (84 TE case), respectively.
Diagram
The updated diagrams now include the additional binary module.
● P139 -423 (for 40 TE case, with pin-terminal connection)
● P139 -424 (for 40 TE case, transformer module: with ring-terminal
connection; other modules: with pin-terminal connection)
● P139 -425 (for 84 TE case, with ring-terminal connection)
Software
DTOC, IDMT1, IDMT2 I0 elimination has now been introduced for the overcurrent protection.
DTOC: The following addresses are new:
● DTO C: I 0 El imi n. I> P Sx (013 150, 013 151, 013 152, 013 153)
● DTOC : I0 Elimin. I >> P Sx (013 154, 013 155, 013 156, 013 157)
● DTOC: I 0 Eli mi n. I>>> P Sx (013 158, 013 159, 013 160, 013 161)
with the settings:
o without
o with I0 calculated
o with I0 measured
IDMTx: The following addresses are new:
● I DMT1 : I 0 Elimi n. I> PSx (013 166, 013 167, 013 168, 013 169)
● I DM T2: I 0 El imin . I> PSx (013 170, 013 171, 013 172, 013 173)
with the settings:
o without
o with I0 calculated
o with I0 measured
A new setting Calc with I0 elim. has been introduced for the following addresses:
● D TOC: Ev al. I N> PSx (072 128, 073 128, 074 128, 075 128)
● DTOC: Eval. I N>> P Sx (007 239, 007 240, 007 241, 007 242)
● DTOC: Eval. I N>>> P Sx (007 243, 007 244, 007 245, 007 246)
● I DMT1: Ev alu ati on IN P Sx (072 075, 073 075, 074 075, 075 075)
● I DM T2: E val uation I N PSx (071 040, 071 041, 071 042, 071 043)
For an explanation of these addresses and settings, see the “Settings” chapter.
THERM The thermal overload protection can now also be applied to the earth current.
The following settings are new:
● T HERM: Select cur re nt P Sx (013 139, 013 140, 013 141, 013 142)
o Max. phase current
o IN calculated
o IN measured
f<> A 5th frequency stage (f5) has now been introduced for over-/underfrequency
protection.
Hardware
No changes.
Diagram
No changes.
Software
DTOC The new setting Start with direction detection (016 105) DTOC: Start w .
D ir ect. PS1 determines the starting condition for directional OC stages:
● With setting Yes starting takes place only, if the current exceeds the start
threshold AND the measured direction is equal to the set direction of the
OC stages.
● With setting No starting takes place, if the current exceeds the start
threshold.
Additional 4th DTOC stages for phase and negative sequence currents have
been implemented.
IDMT1 A time setting (013 143) ID MT1: Tim e Correcti on PS1 has been
implemented to provide compensation of the function starting time and thus
harmonizing operation time with other installed devices. A negative setting will
reduce the tripping time, a positive setting will prolong the tripping time
accordingly.
This feature is only needed in applications with potentially very short tripping
times (i.e. extremely inverse characteristics, small time dial factors, high I/Iref
ratio).
GFDSS A further operating mode could be selected which provides parallel operation of
wattmetric and neutral admittance methods.
Accordingly both methods provide separate signals, which are OR combined to
form the existing ground fault signals, e.g.
(009 037) GF D SS: Grd. fau lt pow./adm.
= (016 103) GFDS S: Grd. fau lt power
OR (016 138) GFD SS: Grd. f aul t adm.
TIMER Implementation of a new function group that provides 4 time switches, all freely
settable to be active for one period on any or several days of the week.
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
ASC The ASC functionality has been enhanced, so that it is now possible to have the
voltage measured at T90 used instead of the “normal” line voltage transformers
(T5 / T6 / T7).
Hardware
No changes.
Diagram
No changes.
Software
PC Bug fixing:
● File transfer (to use customized bay types or data models) was not
available with previous version -656 together with Easergy Studio.
MAIN A new group signal has been implemented which indicates that inrush blocking
picked up in at least one phase:
● (019 213) MAIN Inrush blk. trigg.
Additionally 8 user configurable group signals have been implemented:
● (019 192) MAIN Group signal 01 to
(019 199) MAIN Group signal 08
For each of them up to 32 internal signals can be freely combined using Boolean
operators NOT, AND, OR. These state signals are continuously updated, but with
no latching nor settable pick up/ release delay timers.
The configuration lists of general trip commands have been updated to
incorporate the new group signals.
ARC Separate HSR and TDR trip times for GFDSS power and Admittance trip
conditions have been implemented. The already existing settings are now solely
assigned to wattmetric trip condition.
● (015 078) ARC: HSR trip t. pow. PS1
● (021 059) ARC: HSR trip t. adm. PS1
● (015 078) ARC: TDR trip t. pow. PS1
● (021 069) ARC: TDR trip t. adm. PS1
GFDSS Function enhancement to allow ground fault detection by power and Admittance
methods, both operating independently in parallel.
For that purpose Admittance method has been accomplished with its dedicated
settings, where previously settings had been shared with power method. These
are:
● (020 176) GFDSS: Oper. mode admit PS1
● (016 111) GFDSS: G(N)> / B(N)> LS PS1
● (020 184) GFDSS: Op. delay LS adm PS1
● (020 188) GFDSS: Rel delay LS adm PS1
● (020 192) GFDSS: Op. delay BS adm PS1
● (020 200) GFDSS: Rel delay BS adm PS1
Both methods have been accomplished by a settable hold timer which prevents
inadvertent reset of starting for short gaps in ground fault current (intermittent
ground faults):
● (020 172) GFDSS: Hold time pow. PS1
● (020 222) GFDSS: Hold time adm. PS1
For versatility in application, both methods have been accomplished by
dedicated blocking input signals:
● (020 227) GFDSS: GF (pow.) block. EXT
● (020 226) GFDSS: Admittance block EXT
P<> The new setting (021 074) P<> Start w. Direct. PS1 determines the starting
condition for all power stages:
● With setting "Yes" starting takes place only, if the power start threshold
operates AND the measured direction is equal to the set direction of the
stage.
● With setting "No" starting takes place, if the power start threshold
operates.
CBF Function of external triggering has been made more robust: If only single-pole
trigger (038 205 CBF Start 3p EXT) is configured, then this input must be active
as long as the CBF timer is running. Otherwise CBF resets as soon as the trigger
input signal resets.
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
IEC IEC 61850 RFLO has been enhanced with following elements:
● (024 207) FT_DA : Fau lt cu rre nt A p.u .
● (024 208) F T_D A : F au lt curre nt B p.u .
● (024 209) F T_D A: F aul t cu rren t C p.u.
● (024 218) F T_D A: C ur re nt IN m eas prim
● (024 217) FT_D A: Curre nt I N meas p. u.
● (024 225) FT_D A: Fault cu rren t A pri m
● (024 226) FT_D A: F aul t curre nt B pri m
● (024 227) FT_D A: Fau lt curr e nt C pr im
GFDSS There is a new setting parameter, (024 221) GF DSS: Block ing with GS, to
configure whether the general starting can block GFDSS function or not.
Hardware
No changes.
Diagram
No changes.
Software
V<> Update of V<> readiness condition: V<> remains ready as long as not all
available protection stages are blocked because of related measurement circuit
failures.
Bug fixing:
● (004 061) MA IN : m.c. b. trip V EXT didn't trigger the (042 004) V<>:
not ready.
Hardware
The P139 is now fitted with the new rejuvenated processor board hardware and
related new real-time operating system and enhanced platform firmware for the
modular MiCOM P30 devices.
The following summarizes the key features provided on basis of this new product
platform solution:
● Sustainability of MiCOM P30 Platform
o Single-Chip-Processor platform with high processing bandwidth
o State of the Art real-time operating system (QNX)
o Integrated support of all modern communication interfaces
● Improved Product Performance
o Faster and more deterministic operating times of main protection
functions like distance, especially with complex fault scenarios
o More uniform processing times of supplementary P&C functions
o Higher accuracy of time stamping of binary signals (external and
internal)
Continuity of Proven Platform Features
o Identical device hardware: case variants/modules/connectors
o Maintaining proven protection/control/communication algorithms
● Solid basis for future developments
o Ready to IEC 61850 Ed2, PRP/HSR, Cyber Security, Web server
The following summarizes the basic platform basis:
● Platform Hardware System
o 32 Bit-Processor with 333 MHz
o QNX as real-time operating system, independent from CPU HW
o Modern memory management system
o Faster code execution as running completely from RAM
o Backward compatible internal interfaces (bus, comms, serial HMI)
o Extended I/O flexibility with > 70 binary inputs and > 40 binary output
contacts
● Platform Software System
o Modern platform software with flexible file transfer concept (e.g. up-/
download without device reboot)
o Adaptation of proven application firmware for protection/control
o SW converted to common code solution, widely independent from
hardware
o Re-use of existing (automatic) type tests
o Minimal risk of unfavorable change in performance/behavior
o Contemporary file management concept for improved engineering
o Extension to 128 LOGIC equations and GOOSE inputs
The P139 is now fitted with Ethernet module (SEB LC/RJ45 or REB LC/RJ45). These
modules are used for IEC 61850 Edition 1 and Edition 2 and are fitted to slot 2, as
an alternative to other communication modules.
Note: Previous Ethernet modules can’t be used with firmware versions -660 or
later.
HSR/PRP communication protocols are supported.
Note: SEB = Single Ethernet Board
REB = Redundant Ethernet Board
HSR = High availability Seamless Redundancy protocol
PRP = Parallel Redundancy Protocol
Diagram
The updated terminal connection diagrams include communication interfaces for
single (SEB) and redundant (REB) network configuration:
● P139 -426 (for 40 TE case, pin-terminal connection)
● P139 -427 (for 40 TE case, hybrid terminal connection)
● P139 -428 (for 84 TE case, ring-terminal connection)
Note: hybrid terminal connection:
transformer module: with ring-terminal connection;
other modules: with pin-terminal connection.
Software
IEC The protocol of the redundant connection is configurable with I EC : ETH COMM
Mode .
When Ethernet module (REB or SEB) is used, second Ethernet information is
provided.
V<> New settings permit the selection for each neutral displacement overvoltage
stage whether the fundamental or the r.m.s. value of the voltage shall be
measured for starting:
● (018 219) V <>: Meas . Value V NG> P S1
● (018 253) V <>: Meas . Val ue V NG>>PS1
Note: Most new features of version -657 are not available with -660, but will get
available again with version -661.
Affected are:
● MAIN: User settable group signals
● GFDSS: Operation of wattmetric and admittance method in parallel.
● CBF: Enhancement of CBF external triggering
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
Hardware
New ETH board variant additionally includes RSTP communication protocol.
Diagram
No changes.
Software
IEC The RSTP protocol is supported and configurable with (104 080) IE C: E TH
COMM Mode.
IEC 60870-5-104 protocol has been added. It can be enabled and selected via
(104 078) IEC : IEC 60 870-5-10 4e nable and (104 084) I EC: IE C pr ot .
varian.
To reduce network administration, VLAN and port assignment are supported.
The second communication port is now also supported in Edition 1 mode.
VINP VINP functional group includes 64 virtual inputs and is intended to process
binary information from the Ethernet module running with protocol IEC
60870-5-104.
This function group is only visible if (104 078) IEC: IE C60 870-5-1 04enable is
set to Yes.
MAIN Two further trip commands have been implemented with the same setting
options and functionality as trip command 2. These can be e.g. used for
transformer back-up protection schemes.
8 user configurable group signals have been implemented:
● (019 192) MAIN : Group si gnal 01
to
● ( 019 199) MAI N: Group s ignal 08.
For each of them up to 32 internal signals can be freely combined using Boolean
operators NOT, AND, OR. These state signals are continuously updated, but with
no latching nor settable pick up/ release delay timers.
ARC Separate HSR and TDR trip times for GFDSS wattmetric and admittance trip
conditions have been implemented. The already existing settings are now solely
assigned to wattmetric trip condition.
● (015 078) AR C: H SR tri p t. pow. P S1
● (015 079) AR C: TDR tri p t . pow. P S1
● (021 059) A RC : HSR trip t . adm. P S1
● (021 069) ARC : TDR tri p t. adm. PS1
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
CS Bug fixing:
● The display of the recovery password is now limited to 120 h. Previously it
was permanently displayed, but only valid for 120 h.
● COMM1(2) login with unknown user returned message (80 96)hex
“temporarily locked” instead of (80 93)hex "CS Login failed"
Hardware
No changes.
Diagram
No changes.
Software
DVICE Mounting of transformer module with pin terminal connectors is now also
accepted on 84TE case variant.
IEC The updating of cyclic measurements is now managed independently from other
communication traffic between main and Ethernet module.
Edition 1 handling of buffered reports when no EntryID is given is aligned with
the implementation in edition 2: if no EntryID is written, then all buffered reports
are sent.
The memory buffer for buffered reports is increased: for both edition 1 and 2 at
least the last 100 buffered reports are stored.
Bug fixing:
● New single Ethernet board (SEB released with -660) is now operational in
IEC 61850 edition 1 mode.
● SNTP now considers the subnet mask properly (previously if the third octet
value was not set to 0, then 255 was used instead of the set value).
V<> Update of V<> readiness condition: V<> remains ready as long as not all
available protection stages are blocked because of related measurement circuit
failures.
Bug fixing:
● (004 061) MA IN : m. c.b. t ri p V EXT didn't trigger the signal (042 004)
V <>: Not ready.
f<> Frequency protection gets blocked as long as (040 000) MAIN: General
st ar t ing is present.
Bug fixing:
● In operating mode "f with df/dt" the first stage f1 operated always 100 ms
time delayed.
Hardware
No changes.
Diagram
Optionally, the binary module of type X(6I/6O) can also be fitted in slot 8 (40 TE
case) or slot 16 (84 TE case) and X(24I) can be fitted in slot 7 (40 TE case).
Software
CS The 'Viewer' rights now also grant execution of resetting LED indicators and
measured event data through pressing C (Clear) key or executing (021 010)
MAIN : R eset in dicat. U SER.
LOC Selection lists of signals and counters for configuration on operation and fault
panels have been updated.
PC It is now possible to download the T104 engineering file (as packed zip file) via
the front PC port of Easergy MiCOM devices.
MAIN It can now be selected, whether COMM1 or IEC communication interface is used
for switchgear control (104 242) MA IN: Fct.ass ignm. control.
Operating mode setting for 2-CT operation (011 226) MAIN: DTOC/IDM T
2phase has been enhanced to allow further applications by adding evaluation
of IB as measured or calculated current.
FT_RC The buffer total size has been doubled to 1638 periods for all faults including
pre-fault time for next recording. The maximum duration (length) of a
disturbance recording is increased from 750 to 1500 periods, accordingly.
DTOC Two more phase and neutral OC stages have been added, including directional
operation and triggering of auto-reclosing.
Functionality of 4th neutral OC stage has been harmonized with other stages by
adding a setting to select evaluated signal: (025 254) DTOC: Eval. IN>>>>
PS1.
Also threshold setting range has been aligned up to 40 I(N)nom. Yet, if
evaluation of IN is set to measured, a warning will be issued if the actual setting
is higher than the CT T4 input dynamic range (which is 16 IN,nom).
Visibility control settings have been implemented to shrink the number of visible
stages to application needs, e.g. (026 045) D TOC: Stage Ix> = With /
Without, where default is in line with visibility in previous versions.
f<> Frequency measurement remains blocked for 100 ms upon reset of (004 061)
Pf< MAIN : M.c.b. V t rip EXT.
QV Bug fixing:
● Minimum setting for sector angle is changed to 0°.
CBF Disabling CBF when the function is triggered now resets (038 211) CB F:
Start up 3 p in the same way as CB position change does.
Hardware
No changes.
Diagram
No changes.
Software
CS Bug fixing:
"Execute/don't execute" are now ignored for login, logout and change password
via PC interface.
ARC It is able to switch to a different ARC dead time setting by switching PSS
parameter subset during ARC Cycle running.
Hardware
Enhanced local control panel with colored graphic display (320x240 pixels) for up
to 40 lines is now available for P139. The enhanced local control panel provides
additional keys, such as control keys, 4 context sensitive softkeys and home key.
On the colored graphic display single line diagrams can be configured with two
symbol resolutions with 20x20 large symbols or alternatively 40x40 small
symbols. All objects added to the single line diagrams can be configured to
change the color when two assigned binary signals are changing the status.
A USB-Type B interface is provided to enable device configuration, servicing and
firmware downloading using the existing tools.
Diagram
The updated connection diagrams now include the new enhanced local control
panel.
● P139 -432 (for 40 TE case, with pin-terminal connection)
● P139 -433 (for 40 TE case, with CT/VT ring-, I/O pin-terminal connection)
● P139 -434 (for 84 TE case, with ring-terminal connection)
Software
F_KEY The enhanced local control panel is fitted with 6 freely configurable function
keys. The function group F_KEY “Configurable Function Keys” has been added.
LED The operating mode, function assignment and state of newly added configurable
LED indicators (H 18 – H 23) are provided.
Hardware
Parallel communication modules (serial communication module combined with
Ethernet module) are supported.
Diagram
The updated terminal connection diagrams include the parallel communication
modules (serial communication module combined with Ethernet module) and the
third control board for the control of up to 9 switchgear units.
● P139 -435 (for 40 TE case, with pin-terminal connection)
● P139 -436 (for 40 TE case, with CT/VT ring-, I/O pin-terminal connection)
● P139 -437 (for 84 TE case, with ring-terminal connection)
Software
CS 1xx number to indicate CS patch level is send by the ehternet board and can be
read in the data model.
Bug fixing:
"Execute/don't execute" are now ignored for login, logout and change password
via PC interface.
IEC The RSTP configuration settings can now be set via Easergy Studio.
TLS protocol for IEC 61850 Ed.1 tunnelling is available.
The Ethernet communication mode "Dual-IP" can now be selected via (104 080)
IE C: ETH C OMM Mode.
Bug fixing:
(104 064) IE C: SigGGIO1 se l ecti on was updated on each reboot.
ARC disabled by binary signal could not be actived by IEC 61850.
FT_DA mapping to RFLO1 node wasn’t properly implemented.
GOOSE GOOSE : Input xx status is part of the data model DA selection table and can
be used directly in any LOGIC equation.
Bug fixing:
The IEC 61850 Ed.1 modelling for GosGGIO2 is now supported correctly.
OP_RC New setting (100 004) OP_RC: Op.mode re cording is added and all signals
can be selected.
Storage capacity of operating data recording has been enlarged from 1000 to
3000.
V<> Extended parameter maximum value for all timer stages of V<> function to
600 s.
MCMON The enabling criterion of difference between maximum and minimum phase
current is now settable via (027 137) MC MON: I> enable Idiff>.
DEVxx The third control board is now available. Number of function groups DEVxx is
enhanced from 10 to 15.
Hardware
P139 supports new colored HMI also with the legacy HMI.
Diagram
No changes.
Software
Hardware
No changes.
Diagram
No changes.
Software
IEC 61850 Ed. 2 New control mode (ctlModel) "Select Before Operate with normal security" is
included in Ed. 2.
The pulse configuration for each XSWI and XCBR has been added.
The pulse duration of short and long commands has been extended from 1...254
s to 0.1...254.0 s, steps 0.1 s.
● (221 231) MA IN : Cmd. dur. s hort cmd.
(221 230) MAI N: Cmd. dur.l ong cmd.
MAIN Group signals are added into trip command logic and ARC start logic settings.
● (019 192) MAIN : Group si gn al 01 to
(019 199) MAIN : Group si gn al 08
● (021 001) MA IN : Fct.as si g.t ri p cmd.1
(021 002) MA IN : Fct.as si g.t ri p cmd.2
(021 046) MA IN: Fct.as si g.t ri p cmd.3
(021 047) MA IN: Fc t.ass ig.t rip cmd.4
(015 203) AR C: Fct.as si g.s tart ARC
Enhancements of the ( 017 09 3) MAIN: F un ct.Rus h re st r. PS1 blocking
setting. In addition to the starting signals, the trip signals can be selected.
DTOC New overcurrent residual stages IN>7, IN>8 and IN>9 have been integrated.
● New setting parameters associated to the new stages:
(028 028) DTOC : Stage Ix>7 With/Without
(028 029) DTOC : Stage Ix>8 With/Without
(028 030) DTOC : Stage Ix>9 With/Without
(028 055) DTOC : E val. I N>7 PS1 Calculated/Measured/Calc with I0
elim.
(028 059) DTOC : E val. I N>8 PS1 Calculated/Measured/Calc with I0
elim.
(028 063) DTOC : E val. I N>9 PS1 Calculated/Measured/Calc with I0
elim.
(028 067) DTOC : I N>7 P S1 0.002...40.000 Inom
(028 079) DTOC : IN>7 dynamic P S1 0.002...40.000 Inom
(028 071) D TO C : I N>8 PS1 0.002...40.000 Inom
(028 083) D TO C : I N>8 dyn amic P S1 0.002...40.000 Inom
(028 076) D TOC : IN>9 P S1 0.002...40.000 Inom
(028 089) D TOC : IN>9 dyn amic P S1 0.002...40.000 Inom
(028 094) D TOC : t IN>7 P S1 0.00...100.00 s
(028 128) D TOC : t IN>8 P S1 0.00...100.00 s
(028 132) D TOC : t IN>9 P S1 0.00...100.00 s
(028 031) D TOC : Dire ct ion tIN>7 P S1 Forward/Backward/Non-
directional
(028 035) D TOC : Di re ct ion tIN>8 PS1 Forward/Backward/Non-
directional
(028 039) D TOC : Di re ct ion tIN>9 PS1 Forward/Backward/Non-
directional
● New blocking, starting, time elaspsed and trip signals associated to the
new stages:
(028 107) D TOC : Blocki ng tIN>7 EXT
(028 108) D TOC : Blocki ng tIN>8 EXT
(028 109) D TOC : Blocki ng tIN>9 EXT
(028 098) D TOC : Starti ng IN >7
(028 099) D TOC : Startin g IN >8
(028 100) D TOC : Startin g IN >9
(028 101) D TOC : t IN>7 e laps ed
(028 102) DTOC : t IN>8 e l apse d
(028 103) DTOC : t IN>9 e laps ed
(028 104) DTOC : Trip s ign al tIN>7
(028 105) DTOC : Trip s ign al tIN>8
(028 106) DTOC : Trip s ign al tIN>9
● New signals associated to each DTOC phase stages allow the user to know
if the state of each stage is active.
(028 186) DTOC: I>1 acti ve
(028 187) DTOC: I>2 acti ve
(028 188) DTOC: I>3 acti ve
(028 189) DTOC: I>4 acti ve
(028 190) DTOC: I>5 acti ve
(028 191) DTOC: I>6 acti ve
● New signals associated to each DTOC negative-sequence stages allow the
user to know if the state of each stage is active.
(028 201) DTOC: In eg>1 acti ve
(028 202) DTOC: Ine g>2 active
(028 203) DTOC: I ne g>3 acti ve
(028 204) DTOC: I ne g>4 acti ve
● New signals associated to each DTOC residual stages allow the user to
know if the state of each stage is active.
(028 192) D TO C: IN>1 acti ve
(028 193) D TO C: IN>2 acti ve
(028 194) D TO C: IN>3 acti ve
(028 195) D TO C: IN>4 acti ve
(028 196) D TO C: IN>5 acti ve
(028 197) D TO C: IN>6 acti ve
(028 198) D TO C: IN>7 acti ve
(028 199) D TO C: IN>8 acti ve
(028 200) D TO C: IN>9 acti ve
● New blocking, starting, time elaspsed trip and general signals associated
to IDMT4.
(027 195) ID MT4: Block. tIr e f ,N>
(027 194) I D MT4: Block. tIr e f ,ne g
(027 193) IDMT4: Block. tIr ef ,P>
(027 186) ID MT4: Startin g Ire f ,N>
(027 196) ID MT4: Startin g Ire f ,ne g
(027 185) ID MT4: Startin g Ire f ,P >
(027 188) ID MT4: tIre f ,N> e lapse d
(027 198) ID MT4: tIre f ,n eg> e lapse d
(027 187) ID MT4: tIre f ,P > el aps ed
(027 197) ID MT4: Tri p s ig. tIre f,ne g
(027 189) I D MT4: Tri p s ignal tIr ef
(027 190) I D MT4: Tri p s ignal tIr ef ,N
(027 192) I D MT4: E nabl e d
(027 184) I D MT4: H old ti me N run
(027 202) I DMT4: Hold time ne g ru n
(027 183) I DMT4: H ol d ti me P ru n
(027 201) IDMT4: Me mory N cle ar
(027 200) ID MT4: Me mory ne g clear
(027 199) ID MT4: Memory P cle ar
IDMTx New signals associated to each IDMT phase, negative sequence and residual
stages allow the user to know if the state of each stage is active.
● (028 205) I DMT1: I ref, P active
(028 206) I DMT1: Ire f ,N active
(028 207) IDMT1: Iref , ne g act ive
(028 208) IDMT2: Ire f,P acti ve
(028 209) ID MT2: Iref ,N acti ve
(028 210) ID MT2: Ire f, n eg act ive
(028 211) I D MT3: Ire f ,P acti ve
(028 212) I D MT3: I ref, N acti ve
(028 213) I DMT3: Ire f , ne g act ive
(028 214) IDMT4: Ire f,P acti ve
(028 215) IDMT4: I ref, N acti ve
(028 216) IDMT4: Iref , ne g act ive
IDMT2 Direction determination is available for IDMT2 phase and residual stages.
IDMT1 ● (028 221) I D MT2: Start w. D ir ect. P S1 No/Yes
(028 144) IDMT2: Mode ti mer start P S1 With starting/With direction
(028 043) ID MT2: Di rect. tIre f,N>2 PS1 Forward/Backward/Non-
directional
(028 140) I D MT2: Di rect. tIre f,P >2 P S1 Forward/Backward/Non-
directional
The new setting (028 217) IDMT1: Star t w. Direct . PS1 has been added for
IDMT1 direction determination. Direction determination settings of phase and
residual stages are transferred from SCDD to IDMT1 function group.
● (017 067) I D MT1: D irect.tI ref, N>1 PS1
(017 066) ID MT1: Dire ct.tIref ,P>1 PS1
SCDD1 The setting range of (017 077) SCD D1 : V NG> PS1 has been extended from
0.015...0.600 to 0.0040...0.6000 Vnom(/√3).
The residual current enabling criterion of SCDD1 is now settable via (028 136)
S CDD 1 : I N> P S1 0.005...0.100 Inom.
In case of VNG is set to measured, SCDD1 IN/VNG direction measurement is
blocked when (002 183) M AIN: M. c.b. tri p VNG EXT is active.
SCDD2 New SCDD2 has been introduced which can be used to select different setting
values. Only one SCDD must be activated. If both SCDD1 and SCDD2 are
activated, SCDD1 is available and (098 110) SFMON: In valid SCD D x warning
occurs.
FT_RC It is possible to remove general starting and trip signals from the fixed logic by
the new setting (028 148) FT_RC: Tri g. al ways with GS (No/Yes) and add
both to the configurable list (003 085) FT_R C: Fct. as sig. t rigge r.
New selection list (028 239) FT_R C: Re c. bi nar y s ignals is available to have
the possibility to reduce the signals in the disturbance record. The restriction is
maximum of 99 signals could be selected. If no selection is done, all signals are
shown.
Pulse trigger time (028 241) F T_RC: P ul se ti me and pulse trigger seletion list
(028 240) FT _R C: Fct.as g. puls e tr ig. are added.
GFDSS Two new GFDSS stages IN>2 and IN>3 have been integrated.
● New GFDSS setting parameters:
(028 026) GFDSS: I N>2 PS1 0.003...1.0 IN,nom
(028 110) GFDSS: I N>3 PS1 0.003...1.0 IN,nom
(028 114) GFDSS: t IN >2 P S1 0.00...100.00 s
(028 118) GFDSS: t IN >3 P S1 0.00...100.00 s
● New GFDSS starting, blocking and time elapsed signals:
(028 122) GFDSS: Startin g I N>1
(028 123) GFDSS: Startin g I N>2
(028 124) GFDSS: Startin g I N>3
(028 247) GFDSS: B locki ng tIN>1 EXT
(028 248) GFDSS: B locki ng tIN>2 EXT
(028 249) GFDSS: B locki ng tIN>3 EXT
(028 125) GFDSS: t IN >1 elaps ed
(028 126) GFDSS: t IN >2 elaps ed
(028 127) GFDSS: t IN >3 elaps ed
● The new blocking signals have been added to the selection list of (021
021) M AI N: Fct.assi gn . block. 1 and (021 022) MAIN: Fct.assign.
b lock .2.
Hysteresis of GFDSS IN>1, IN>2, IN>3 has been changed to 5% or 0.001
IN,nom, whichever is bigger.
In case of VNG is set to measured, GFDSS in mode “steady-state power” or
“admittance” is blocked when (002 183) MA IN: M.c.b. trip VNG EXT is
active.
In case of VNG is set to calculated, GFDSS in mode “steady-state power” or
“admittance” is blocked when (038 023) MCMON: Me as. circ. V fault y is
active.
f<> The number of decimal places of df/dt setting has been changed from 1 to 2.
● (018 108) f<>: df 1/dt PS1 0.10...10.00 Hz/s, steps 0.01 Hz/s
The setting range of f<> timer has been extended from 0...10.00 s to 0...60.00
s.
● (018 104) f<>: tf1 PS1
(018 128) f<>: tf2 P S1
(018 152) f<>: tf3 P S1
(018 176) f<>: tf 4 PS1
(019 155) f<>: tf 5 PS1
V<> It is possible to choose independently for the second and third stages if VNG is
calculated or measured via new settings (028 231) V<>: Evaluation VNG>>
PS 1 and (028 235) V <>: Eval uation V NG>>> PS1.
CBM The current-time integral of ruptured and accumulated squared current are
available.
● New setting parameters:
(022 146) C BM: Set Σ I **2*t A
(022 147) C BM: Se t Σ I**2*t B
(022 148) C BM: Se t Σ I**2*t C
● New measurements:
(009 064) CBM: I**2*t A
(009 069) CBM: I**2*t B
(009 070) CBM: I**2*t C
(009 094) CBM: ΣI* *2*t A
(009 095) C BM: ΣI **2*t B
(009 096) C BM: ΣI **2*t C
Time measured values for time between close command and current flow are
available. The timer is started with the “or” configured signals in (028 245)
C BM: Fct.assig.CB Timer and is stopped separately in each phase current
flow (010 223) MAIN : C urre nt f l ow A, (010 224) MAI N: Cu rre nt flow B and
(010 225) MAI N: Cu rre nt fl ow C.
The measured time is displayed with:
● (028 242) C BM: tCB cl osi ng A
(028 243) C BM: tCB cl osi ng B
(028 244) C BM: tCB cl osi ng C
Following measurements are available in IEC 61850 Ed. 2.
● (009 047) C BM: Itri p A
(009 048) C BM: Itrip B
(009 049) C BM: Itrip C
(009 077) C BM: ΣItri p**2 A
(009 078) CBM: ΣItri p**2 B
(009 079) C BM: ΣI tri p**2 C
(009 087) CBM: ΣI*t A
(009 088) CBM: ΣI*t B
(009 089) C BM: Σ I*t C
(009 064) C BM: I **2*t A
(009 069) CBM: I **2*t B
(009 070) CBM: I **2*t C
(009 094) CBM: ΣI**2*t A
(009 095) CBM: ΣI**2*t B
(009 096) CBM: ΣI**2*t C
TIMER Four timers for the length measurement of logic signals are available.
● New setting parameters:
(028 047) TI MER : F ct . ass ignm . T1
(028 049) TI MER : F ct . ass ignm . T2
(028 051) TI MER : F ct . ass ignm . T3
(028 053) TI MER : F ct . ass ignm . T4
● New measurements:
(028 048) TIMER: Time val ue T1
(028 050) TIMER : Ti me val ue T2
(028 052) TIME R: Time valu e T3
(028 054) TI ME R: Time valu e T4
Timer values measurement are available in IEC 103 and IEC 61850 protocols.
Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE
Phone: +33 (0) 1 41 29 70 00
Fax: +33 (0) 1 41 29 71 00
www.schneider-electric.com
Publishing: Schneider Electric
Publication: P139/EN M/R-h8-A Volume 2 12/2020