WDZ-5211 Line Protection Measurement and Control Device 1 Device Function 2 Protection Function and Principle
WDZ-5211 Line Protection Measurement and Control Device 1 Device Function 2 Protection Function and Principle
Page 1
1 device function
WDZ-5211 line protection measurement and control device is mainly used for the protection and measurement and control of 10KV and below feeders.
WDZ-5200 series line protection device includes WDZ-5215 short line comprehensive protection and monitoring device.
The difference of measurement and control functions is shown in the table below.
WDZ-5211 WDZ-5215
Differential quick break protection √
Ratio differential protection √
CT disconnection alarm √ √
Low voltage blocking over current one-stage protection
√ √
Low voltage blocking overcurrent two-stage protection
√ √
Three-stage overcurrent protection √ √
Post-accelerated protection √ √
Overload protection √ √
Ground protection section √ √
Two-stage grounding protection √ √
PT disconnection alarm √ √
Measurement function √ √
control function √ √
Hardware energy metering function √ √
Operating circuit function √ √
Over-current protection for one stage can be set via low-voltage lockout, when any one of the three line voltages is less than the low-voltage lockout
Value, open the over-current one-stage protection through low voltage blocking.
Page 1 of 20
Page 2
https://translate.googleusercontent.com/translate_f 1/17
11/19/21, 10:12 AM WDZ-5211 line protection measurement and control device 1 device function 2 protection function and principle
2.1.2 Protection action criterion
⎧I > I
⎪ max gl 1
⎨tt > gl 1
⎪
⎩U min < U dybs
t gl1:The setting value of over-current protection action time for one stage (s)
Over-current two-stage protection can be set to be locked by low voltage, when any one of the three line voltages is less than the low voltage, it can be locked
Value, open the over-current two-stage protection through low voltage blocking.
⎧I > I
⎪ max gl 2
>
⎨tt gl 2
⎪
⎩U min < U dybs
In the formula, I gl2 : overcurrent two-stage protection action current setting value (A)
t gl2 : the setting value of the second- stage overcurrent protection action time (s)
Page 2 of 20
Page 3
⎪I max > I gl 3
⎧
⎨
⎩tt > gl 3
⎪
In the formula, I gl3 : overcurrent three-stage protection action current setting value (A)
https://translate.googleusercontent.com/translate_f 2/17
11/19/21, 10:12 AM WDZ-5211 line protection measurement and control device 1 device function 2 protection function and principle
In order to prevent the auxiliary power switch from being switched on to the faulty line, the device provides post-acceleration protection. The post-acceleration signal supports
Signal input and pulse signal input, after the acceleration protection is turned on for 5 seconds.
⎧I >I
max hjs
⎪
>
⎨tt hjs
⎪
⎩Post-accelerated
open
protection
In the formula, I hjs : the setting value of the operating current of the back acceleration protection (A)
t hjs:The setting value of the post acceleration protection action time (s)
Overload protection provides options for definite time, normal inverse time, very inverse time, and abnormal inverse time. Inverse time curve symbol
Page 3 of 20
Page 4
Trip
≥1
Signal
Warn
In the formula, I gfh : overload protection action current setting value (A)
⎧I > I
max gfh
⎪
⎪ > 14.0 Xt
⎨t gfh
⎛ ⎞02.0
⎪ I
⎜ max ⎟ −
⎪ ⎜ ⎟ 1
⎩ ⎝ I gfh ⎠
⎧I > I
max gfh
⎪
⎪
⎨
https://translate.googleusercontent.com/translate_f 3/17
11/19/21, 10:12 AM WDZ-5211 line protection measurement and control device 1 device function 2 protection function and principle
⎧I > I
max gfh
⎪
⎪ > 80 Xt
⎨t 2 gfh
⎪ ⎛ ⎞
⎜I max ⎟ −
⎪ ⎜ ⎟ 1
⎩ ⎝ I gfh ⎠
The zero-sequence current is obtained through a special zero-sequence current transformer, and the two-stage zero-sequence overcurrent protection is used to achieve the purpo
of. The measuring range of the external zero sequence current of the device is 10mA~6A.
• • • •
Page 4 of 20
Page 5
If there is a CT disconnection, the self-produced zero sequence is instantly blocked to prevent the self-produced zero sequence malfunction caused by the CT disconnection. To prev
The unbalanced current caused by the inconsistent sensor characteristics causes the grounding protection to malfunction, and the maximum phase current I max is used as the braking a
I 0 /I 0dz
0 1.05 I max /I e
Zero-sequence over-current logic, suitable for zero-sequence current external connection occasions:
With phase current braking logic, suitable for zero-sequence current self-produced occasions:
⎧I > I
⎨ 0 01 dz
⎩tt >
https://translate.googleusercontent.com/translate_f 4/17
11/19/21, 10:12 AM WDZ-5211 line protection measurement and control device 1 device function 2 protection function and principle
0 01 dz
Page 5 of 20
Page 6
In the formula, I 01dz : Zero-sequence protection one-stage action current setting value (A)
t 01dz:The setting value of a period of action time of zero sequence protection (s)
Zero-sequence over-current logic, suitable for zero-sequence current external connection occasions:
Trip
t 02dz
Signal
t 02dz Warn
With phase current braking logic, suitable for zero-sequence current self-produced occasions:
&
Trip
t 02dz
≥1
Signal
&
&
t 02dz Warn
CT disconnection
⎧I > I
0 02 dz
⎨
⎩tt0 > 02 dz
In the formula, I 02dz : the setting value of the second-stage operating current of the zero sequence protection (A)
t 02dz : the setting value of the second-stage action time of zero sequence protection (s)
Page 6 of 20
Page 7
https://translate.googleusercontent.com/translate_f 5/17
11/19/21, 10:12 AM WDZ-5211 line protection measurement and control device 1 device function 2 protection function and principle
If any of the following conditions is met, the CT disconnection judgment is not performed:
(1) The maximum phase current before starting is less than 0.2Ie, the CT disconnection judgment is not performed;
(2) The maximum phase current after starting is greater than 1.2Ie;
Only after the self-produced zero-sequence components act, it enters the instantaneous CT disconnection discrimination program.
If the current meets the following conditions at the same time, it is considered that the CT is disconnected:
(2) The other two-phase or one-phase current is equal to the current before starting;
The time-delay CT disconnection discrimination logic is: three-phase current, one-phase or two-phase current is less than 0.125 times the rated current, and others
If the two-phase or one-phase current is greater than 0.2 times the rated current, and if this condition is met for more than 2 seconds, a CT disconnection alarm will be issued
2.10 PT disconnection
PT disconnection is divided into three-phase PT disconnection and single-phase or two-phase PT disconnection. The main feature of a three-phase PT disconnection is that the
The main feature of single-phase or two-phase PT disconnection is the large unbalanced voltage, which is judged by the negative sequence voltage.
⎧I > 2.0 I
⎨ max e
⎩U max < 30 V
{U 13 V
2 >
Page 7 of 20
Page 8
https://translate.googleusercontent.com/translate_f 6/17
11/19/21, 10:12 AM WDZ-5211 line protection measurement and control device 1 device function 2 protection function and principle
15 Overload action curve Very inverse time limit/extraordinary
time limit
Note: ①②The fixed value range of the first-stage current of zero-sequence action and the second-stage current of zero-sequence action: when the zero-sequence current is ext
0.010-6.000A; 0.20In-20.00In in the case of zero-sequence current self-production. The access method of zero sequence current is selected in "Installation
Settings menu -> fixed value settings -> system settings -> engineering parameters -> zero sequence current access mode" to configure.
The device provides the function of the soft pressing plate, and the virtual remote signal displacement information of the soft pressing plate will be generated in the process of
Three-phase voltage, three-phase current, active power, reactive power, power factor, frequency.
Page 8 of 20
Page 9
3.2 Open in
3.3 out
Provide remote tripping and closing operations of the circuit breaker switch.
Provide hardware forward active power, forward reactive power, reverse active power, reverse reactive power measurement functions, and provide forward active power,
At the same time, the active and reactive power calculated by the device can be used to accumulate active and reactive energy.
Operating loop functions include jump circle, close circle, jump position monitoring, close position monitoring, jump position signal output, close position signal output,
Control circuit disconnection output, protection trip output, remote control trip output, remote control close output, manual trip input, manual close
Trip input, DCS trip input, protection trip input, 2-way position combined trip or protection combined trip output, etc.
The device provides 1 channel of 4-20mA output, optional 2 channels of 4-20mA output, and the corresponding measurement can be arbitrarily set
https://translate.googleusercontent.com/translate_f 7/17
11/19/21, 10:12 AM WDZ-5211 line protection measurement and control device 1 device function 2 protection function and principle
4 Backplane terminal and wiring schematic diagram
U a , U b , and U c are bus voltages, which are input together as protection and measurement voltages in the device, line voltage is connected, and rated voltage
I A , I B , and I C are measurement currents, which need to be input from the dedicated measurement CT. The measuring current is divided into rated 5A and 1A.
I a , I b , and I c are three-phase protection currents. The protection current is divided into rated 5A and 1A.
3I 0 is the zero-sequence current, which is connected from a dedicated zero-sequence current transformer. The effective measuring range of the secondary value of zero sequen
6A. If there is no special zero-sequence current transformer, the device can also produce zero-sequence by itself
Viewed from the front of the device, the leftmost terminal on the back panel is slot 1, the rightmost is slot 5, and the middle is slot 2, slot 3,
Slot 4. From the back of the device, slot 1 is on the far right, and slot 5 on the far left.
The terminal number is 3 digits, such as "ABC", the first digit A is the slot number, and the second three digits BC are the top-down terminals
The serial number. For example, the first terminal of slot 3 is numbered 301.
Page 9 of 20
Page 10
https://translate.googleusercontent.com/translate_f 8/17
11/19/21, 10:12 AM WDZ-5211 line protection measurement and control device 1 device function 2 protection function and principle
Page 10 of 20
Page 11
Terminals 301~303 are position status output. 302~301 are the status output of the jump position; 303~301 are the status of the closed position
Output.
Terminal 308 is a protective trip outlet (BTJ), which can be connected to terminal 318 via a pressure plate or directly.
Terminal 309 is the remote control positive power input terminal, only when it is connected to the positive power, the device will remote jump and remote close function
Invest.
Terminal 310 is the remote control closing outlet (YHJ), which can be connected to terminal 317 via a pressure plate or directly.
Terminal 311 is a remote control trip outlet (YTJ), which can be connected to terminal 319 via a pressure plate or directly.
The terminal 314 is connected to the external closing mechanism, namely the circuit breaker closing coil.
Terminal 315 is connected to an external trip mechanism, that is, the circuit breaker trip coil.
Terminals 321~322 are output 4, the default is the protection joint jump outlet, and it can also be selected as the position joint jump through the jumper.
Terminals 323~324 are output 5, the default is the protection joint jump outlet, and it can also be selected as the position joint jump through the jumper.
Terminals 331~332 are the action alarm signal output, when the protection action or protection alarm, this signal is output.
Terminals 401~402 are fieldbus 1 input, 401 is positive polarity, and 402 is negative polarity. Can choose CAN,
Terminals 404~405 are fieldbus 2 inputs, 404 is positive polarity, and 405 is negative polarity. Can choose CAN,
Page 11 of 20
Page 12
https://translate.googleusercontent.com/translate_f 9/17
11/19/21, 10:12 AM WDZ-5211 line protection measurement and control device 1 device function 2 protection function and principle
Terminals 406~407 are GPS time synchronization input ports, connected to 485 differential level.
Terminals 410~411 are active energy pulse output, 24V passive empty contact output. 410 is positive, 411 is negative
end.
Terminals 412~413 are reactive energy pulse output, 24V passive empty contact output. 412 is positive, 413 is negative
end.
Terminals 414~416 are 2 channels of 4~20mA output. 414~4165 is the first output, 414 is the positive end, 416
It is the negative terminal; 415~416 are the second output, 415 is the positive terminal, and 416 is the negative terminal.
The device grounding stud must be reliably connected to the site grounding grid.
Terminal 501 is the power ground of the device. After this terminal is connected to the device grounding stud, it is reliably connected to the field grounding grid.
Terminals 503 ~ 504 are the device power input, and the device power can be AC or DC 220V or DC 110V. 503
Is the negative input terminal of the device power supply, and 504 is the positive input terminal of the device power supply.
Terminals 506~530 are 24 channels of high-current DC 110V or 220V input. 506 is the open input common negative terminal, 507~
530 is 24 input channels. 509 is defined as the back acceleration contact by default.
Terminals 531~532 are device lockout outputs, normally closed contacts. The 24V power failure of the device or the abnormal operation of the internal CPU
4.2.2 Do not configure the basic configuration terminal of the operation panel
Page 12 of 20
Page 13
https://translate.googleusercontent.com/translate_f 10/17
11/19/21, 10:12 AM WDZ-5211 line protection measurement and control device 1 device function 2 protection function and principle
Same as the operation board configuration, the lower mold inserts the board terminal description.
Terminals 301~304 are protection combined jump output. 301~302 are one of the secondary contact outputs; 303~304 are among them
Page 13 of 20
Page 14
Terminals 305~308 are 2 exits. 305~306 are one of the secondary contact outputs; 307~308 are the other
Terminals 331~332 are the action alarm signal output, when the protection action or protection alarm, this signal is output.
Description of the interface board terminals under the same operation board configuration.
510 is defined as the remote position, and 511 and 512 are defined as the circuit breaker tripping and closing access (510, 511, 512 default
If it is undefined, it needs to be set in the factory settings). The rest is the same as the description of the power supply board terminals under the operation board configuration.
1LHa
https://translate.googleusercontent.com/translate_f 11/17
11/19/21, 10:12 AM WDZ-5211 line protection measurement and control device 1 device function 2 protection function and principle
Save
113 114
1LHb
Protect
Electricity
115 116
Electricity
1LHc
flow
UA mother
117 118 Electricity
101
String
Pressure
LH0 flow
UB String
105
2LHa Back to
107 108
2LHb
Measurement
road
109 110
quantity
2LHc
Electricity
111 112
flow
Page 14 of 20
Page 15
4.3.2 Wiring schematic diagram of binary input, central signal, network, analog output, electric energy pulse output circuit
-KM +KM
Small bus
531
3 1 Device lockout
1Q air switch
4 2 532
Pack 325
Device failure
L/DC+ middle
Set 326
504
Electricity
Central
L/DC- 327
503 source Protection action
letter
328
Open into 1
507 No
329
Open in 2 Protection alarm
508
330
Post-acceleration
509
331
remote Action warning signal
Note 1 distance
510 332
Jump
511
NET1-A
In position 401
512
Fieldbus 1
letter NET1-B
Open into 7
513 402
Open into 13
519 GPS- GPS time synchronization
407
Open into 14
520
set Signal ground
Open 15 408
521
Open into 16
522
Note
Active pulse output+ Electricity
410
Open into 17
523
Spend
Open into 18 Active pulse output-
524 411 pulse
Open into 19
525 Reactive pulse output+ rush
412
Open into 20 lose
526
413 Reactive pulse output-
Open into 21 out
527 Note 3
Note 1: If the operation panel is configured, the remote, close, and jump signals do not need to be connected.
Note 2: The electrical energy pulse output is 24V empty contact output, passive.
Note 3: R is an external resistance, which should be less than 500 ohms, 250 ohms are recommended.
https://translate.googleusercontent.com/translate_f 12/17
11/19/21, 10:12 AM WDZ-5211 line protection measurement and control device 1 device function 2 protection function and principle
Page 15 of 20
Page 16
302
Closed output
303
321
Out of 4
322
323
Out of 5
324
301
304
combine
305
306 Out 2
307 brake
308
311 Teleconnection
312 mouth
314
Page 16 of 20
https://translate.googleusercontent.com/translate_f 13/17
11/19/21, 10:12 AM WDZ-5211 line protection measurement and control device 1 device function 2 protection function and principle
Page 17
5 Device selection
WDZ-5211
Network Configuration
1: CAN network
2: ProfiBus network
DC power supply
1: DC power supply 110V
2: DC power supply 220V
(1) The device network communication interface can be equipped with CAN and ProfiBus, both of which are dual-network configuration; if you need to choose an RS485 interface,
Please specify;
(3) The device can be equipped with an operating circuit, and the anti-jumping function can be canceled; the combined trip relay defaults to the protection combined trip, if the comb
The relay needs to be connected to the position, please give special instructions; the operating circuit tripping and closing current defaults to 0.3~4A self-adaptive, such as
If the tripping and closing current is 0.05~0.3A or 4~10A, please specify. The operation circuit can also be omitted;
(4) The operating circuit power supply and the input power supply of the device are divided into DC 110V and DC 220V; the device power supply does not distinguish between 110V
(5) The secondary rated current of the device is divided into 1A and 5A. This current is the protection current and the measurement current, and the protection current and the measu
(6) The device is configured with 1 4~20mA output by default, if 4~20mA output is not needed or 2 4~20mA outputs are needed,
Please specify;
(7) The precise working range of the device's zero-sequence CT is 10mA~6A. If the zero-sequence current is not in this range, please specify;
(8) The secondary rated voltage of the device is 100V, 50Hz, and the line voltage is connected;
(9) The device can expand the input and output resources, please specify.
6 Setting instructions
Page 17 of 20
Page 18
(1) Calculated based on the three-phase short-circuit current evading the end of the cable, namely
)3(
Operating current
I gl=1 IKrel fK .
https://translate.googleusercontent.com/translate_f 14/17
11/19/21, 10:12 AM WDZ-5211 line protection measurement and control device 1 device function 2 protection function and principle
In the formula, K rel : reliability coefficient, taking 1.2~1.25
)3(
I : . The
fk secondary value of the three-phase short-circuit current at the end of the cable (A)
)3(
I :. The
ik secondary value of the three-phase short-circuit current at the beginning of the cable (A)
)2(
K sen
: Sensitivity at the beginning of the cable when two phases are short-circuited
If the cable length is long and it is not easy to meet the sensitivity requirements, consider adopting voltage blocking quick-break protection.
(2) Current components are calculated based on the short-circuit at the end of the cable with sufficient sensitivity, while voltage components are calculated based on the three-phase s
)2( )2(
Operating current
I gl=1 I fK. / sen
K
= * ZL
Operating voltage perU
unit value
K rel ( X S + X L )
dybs
In the formula,
I : . The
fk
)2(secondary value of two-phase short-circuit current at the end of the cable (A)
I gl IKrel / n TA
2 = st . all
I gl IKrel / n TA
2 = op max.
Page 18 of 20
Page 19
I op.max : the setting value of the maximum quick-break current of the next-level equipment (A)
If the sensitivity is sufficient, try to use a larger operating current
t gl 2 = 0 + Δ t = Δ t
t gl 2 = max.
t gl + Δt
https://translate.googleusercontent.com/translate_f 15/17
11/19/21, 10:12 AM WDZ-5211 line protection measurement and control device 1 device function 2 protection function and principle
(1) Calculated according to the self-starting current that dodges the motor
(2) Calculated by avoiding the magnetizing inrush current of the transformer on the line
Generally, t hjs =0
The neutral point is set as follows through the low resistance grounding system:
(1) Calculate based on the single-phase grounding current flowing through the protection installation when avoiding the single-phase grounding outside the area:
)1(
I 0=dz IKrel K
In the formula, K rel : Reliability coefficient, take 2~2.5 when protection action is signal, take 2.5~3 when protection action is trip
)1(
I K: Single-phase grounding current supplied by the protected equipment to the short-circuit point when single-phase grounding (A)
Page 19 of 20
Page 20
(2) Coordination calculation with the next level of single-phase grounding protection:
I 0.op.max : the maximum operating current of the next-level single-phase grounding protection (A)
The zero sequence action current takes the larger value of a) and b).
Coordination calculation with the longest action time of the next level single-phase grounding protection
t 0 dz = tmax..0op + Δt .
In the formula, t 0.op.max : the longest action time of the next level of single-phase grounding protection (s)
https://translate.googleusercontent.com/translate_f 16/17
11/19/21, 10:12 AM WDZ-5211 line protection measurement and control device 1 device function 2 protection function and principle
Page 20 of 20