Sub Module 3.12 DC Gen Motors
Sub Module 3.12 DC Gen Motors
MODULE 3
Sub Module 3.12
CONTENTS
BASIC GENEARATOR AND MOTOR THEORY ------------------- 1
DC GENERATOR --------------------------------------------------------- 7
CONSTRUCTION AND PUPOSE OF COMPONENTS ---------- 7
ELECTROMAGNETIC PROBLEMS ---------------------------------14
FACTORS AFFECTING OUTPUT OF DC GENERATORS ---- 31
DC MOTORS -------------------------------------------------------------- 32
DC MOTOR CONSTRUCTION --------------------------------------- 35
TYPES OF DC MOTOR AND THEIR CHARACTERISTICS ---35
SERIES DC MOTOR ---------------------------------------------------- 36
SHUNT DC MOTOR ----------------------------------------------------- 37
COMPOUND DC MOTOR ---------------------------------------------- 38
TORQUES IN A DC MOTOR: ----------------------------------------- 41
STARTER GENERATOR CONSTRUCTION ----------------------47
Emf = B L V Sin Ө
EMF = B L V
Each end of the loop is connected to a segment of the FIGURE: 3.12.3 PRODUCTION OF DC BY COMMUTATOR ACTION
commutator and the load is connected to the loop by brushes
on opposite sides of the commutator. As the loop rotates, an
alternating voltage is induced in it, but, because of the action of
the commutator, a ‘rippled dc’ is produced as opposed to a
genuine ac waveform. Because Commutator rotates with the
loop, the brushes bear on opposite segments of it during each
half cycle. This results in the left-hand brush always being in
contact with the segment that is positive, with the change-over
taking place at the instant when the voltage induced in the loop
is zero. The current in the external circuit is therefore always in
the same direction and is called a UNI-DIRECTIONAL current.
It is also the first step towards obtaining a true dc output such
as we get from a battery.
FIGURE: 3.12.4
At position C: 900 → 1800 The voltage at the brushes, and therefore the current in the
The conductors initially cut max lines of force and progressively external circuit of a single loop dc generator, falls to zero twice
less and less number of lines and finally at position ‘c’ they no during each complete revolution. As has already been
more cut any magnetic line of force. The induced emf thereby mentioned, this variation of dc is called ‘ripple’ and can be
decreases from max to zero, however its polarity remains same. reduced by the addition of more loops as shown in Fig 3.12.4
Nɸ= max
= zero
for two loops and eight segments for four loops. The loops are
not just loops of wire but are made up like coils and so the
The voltage at the brushes equals the sum of the emf’s induced
in the loops connected in series between the brushes. In Fig
5(a), loops A, B and C are in series between the brushes on the
right and loops D, E and F with the brushes on the left, with the
two branches in parallel with each other. The graph in Fig 5(b)
shows the resultant voltage between the brushes. Only three
loops need to be considered as the arrangement is symmetrical
and both branches (A, B and C and D, E and F) give the same
voltage at the instant shown. As the number of loops is
increased, the ripple in the brush voltage becomes smaller and
the magnitude of the dc output voltage increases
FIGURE: 3.12.7 Connection of Multiple Loops with
Commutator Segments and Resultant Output
DC GENERATOR
The Figure: 3.12.7 shows brush gears with pig tail connection.
brush action on the commutator or slip-ring surface to attain a The Iron Core provides a low reluctance path between the field
serviceable thickness. pole pieces giving increased flux density, ensuring that the
largest emf possible is induced into the output windings. The
The windings are wedged into the slots with insulating material
FIGURE: 3.12.11: A worn and rusted brush in a generator. to prevent them from being thrown out by centrifugal force.
All coil connections are silver soldered to withstand local hot
Under no circumstances should non-film forming brushes be run spot temperatures.
on films created by film-forming brushes, nor should film forming
and non-film-forming brushes be used simultaneously in the
same machine. When changing from film-forming to non-film
forming brushes the existing film must be completely removed
by cleaning the commutator or slip-ring with a rag moistened in
lead free gasoline, or other approved cleaning agent.
THE ARMATURE
LAP WINDING
GENERATOR COOLING
The fundamental requirements of the element through which The commutator and brush gear of a dc machine have two
torque is transmitted to the rotor shaft of the generator may be distinct functions:
summarized as follows:
Collection - the transference of current between the moving
Effective transmission of torque up to a specified armature and the fixed external circuit.
maximum.
Commutation - the periodic reversal of current during transfer
Effective interruption of torque transmission if the torque- between the armature and the external circuit to produce DC
demand of the generator exceeds the permitted These two operations are independent, but faulty collection or
maximum, this condition can arise as a result of seizures incorrect commutation produce similar results, ie. the formation
of the generator rotor, etc. of a destructive spark or arc between the trailing edges of the
brushes and the commutator surface.
Quick and simple removal and replacement of the
torque-transmission element. FAULTY COLLECTION
The requirements quoted above are satisfied almost entirely by Normally the result of poor brush fittings and maintenance
‘weak-link’ devices known as quill drives. The device is causes Sparking between the brush trailing edge and the
basically a ‘necked’ metal shaft with serrations or splines commutator surface which is very destructive.
(These may be either male or female) at one or both ends. The
serrations or splines mate with corresponding formations on the ELECTROMAGNETIC PROBLEMS
driven rotor shaft to transmit the torque delivered by the drive
unit, and the ‘necked’ portion is designed to shear in the event In addition to the problems associated with actual collection, two
of rotor seizure, etc, thus interrupting the drive and protecting problems which are associated with the electromagnetic
the components against further possible danger. functions in the generator also exist. Though having similar
effects, they are created by different things, may be
compensated for by different design features and should
therefore be understood as separate entities.
These are:
Armature Reaction
Reactive Sparking
FIGURE: 3.12.15
RESULTANT MAGNETIC FIELDS DUE TO ARMATURE REACTION
GEOMETRICAL NEUTRAL AXIS: COMPENSATING WINDINGS, both of which counteract the effect of
An imaginary line drawn vertically at a point midway between armature reaction.
the opposite Poles of a field is termed as GNA. In other words,
we can say GNA is an imaginary line drawn at right angles to
the field flux with No Armature Reaction. BRUSH POSITIONING
The brush-positioning method is only satisfactory in smaller
MAGNETIC NEUTRAL AXIS installations in which the generator operates under a fairly
MNA is an imaginary line drawn at right angle to the field flux constant load.
with Armature reaction. It is a line joining the two points at which
no emf is induced in the armature coil. If the load varies to a marked degree, the MNA will shift
proportionally, and the brushes will not be in the correct position
The brushes of a generator must be set in the MNA which at all times. This method is most commonly used in smaller
means that they must contact segments of the commutator that generators (those producing 1000W or less) because it is less
are connected to armature coils having no induced emf. If the expensive. Larger generators require the use of interpoles.
brushes were contacting commutator segments outside the
MNA, they would short-circuit ‘live’ coils and cause arcing and
loss of power (reactive sparking). In an ideal machine, the MNA
will be equal to the GNA, which means there would be no
distortion of the field flux and so no shifting of the MNA away
from the brushes. This would result in no armature reaction or
reactive sparking. However, the ideal machine has never been
invented and armature reaction is something that has to be
accepted and compensated for, and there are three principle
methods with which it is overcome.
1- Brush Positioning
2- Interpole Windings
3- Compensating windings
FIGURE: 3.12.16
The first method is to shift the position of the brushes so that GENERATOR CIRCUIT WITH INTERPOLES
they are in the MNA when the generator is producing its normal
load current. The second method is by using special field poles,
called INTERPOLES, and the third is by the use of
If the brushes remain in the field’s neutral plane then they will
be short circuiting the coils that have voltage induced in them
consequently there will be less arcing between the brushes of
the commutator.
Self-Excited Generators
GENERATOR CHARACTERISTICS
With load applied, causing current to flow in the armature winding, the
voltage at the generator terminals falls slightly, and the machine is
said to have a falling characteristic. (Fig 3.12.20 (b)) i.e. when IL ↑then
VT ↓This fall in terminal voltage is due to:
a- Weakening of the main flux by armature reaction, set up by
the current in the armature winding.
b- Va- Voltage drop (IaRa) in the armature winding and
c- Vb - Voltage drop (IaRb) in the Brushes
FIGURE: 3.12.20
Numerically, Eg = Va + Vb + VT
VT = Eg - (Ia Ra + IbRb)
= Eg – Ia(Ra + Rb)
Residual Magnetism is necessary for generating emf in such When the generator is not running, the residual magnetism
machines. creates a strong enough magnetic field to produce a weak emf
in the armature when rotation starts. As speed of rotation
Self-Excited generators may be series, shunt or compound increases, so does armature emf until full output voltage is
wound. reached.
In a series generator, the field coils are connected in series If a generator is not handled correctly, when it is off the aero
with the armature, so that the whole load current flows through plane, there is a risk that the residual magnetism will be lost.
them. Field coils are of a few turns of thick wire. If the load is Subjecting a generator to excessive heat, vibration, dropping it,
disconnected, the circuit is incomplete and no current flows leaving it on metal racks for a long time, may cause this
through the field coils. problem.
In a shunt generator, the field coils are connected in parallel ‘FLASHING’ THE FIELD
with the armature and generator output. The Field coils contain
many turns of fine wire and divert only a little of the armature The residual magnetism may be recreated by connecting a dc
current because of their high resistance. This generator is supply (with the generator disconnected) equivalent to the
excited even with the load disconnected. generator’s rated output across the field for a short duration and
then disconnecting that supply. The rapid collapse of the
A compound generator contains both series and shunt field magnetic field produced by the ‘flashing’ supply will induce a
windings. small quantity of permanent magnetism – the residual
There is enough residual magnetism in the pole pieces to magnetism – in the generator field poles.
enable a self-excited machine to start. As soon as a little
armature current flows, the magnetic field builds up until the full
generator output is reached.
After Saturation (IL ∝ ):IL↑, Ia↑, then (Va + Vf ) ↑, VT↓ in parallel with the armature, as shown in the illustration, the
machines are said to be ‘shunt-wound’.
After saturation IL and Ia increases and then (Va+Vf) increases
In such machines the armature current divides into two
while VT decreases.
branches, one portion of the current passing through the field
winding, the remainder through the external circuit. It is
Any further rise in current beyond this point will not result in a
therefore advantageous to keep the current in the shunt field
rise of generated emf since the flux is already at maximum, but
winding as small as possible, thus avoiding expenditure of
it will, on the other hand, cause an increase of voltage drop in
electrical energy in the machine itself. The necessary flux can
the armature and field windings. Since Vb is negligible therefore
be created by the ampere-turns produced by a small current in
it is ignored.
coils consisting of many turns of fine wire. A shunt field winding
is consequently of high resistance and, since it is iron-cored of
Since the terminal voltage is the difference between generated
high inductance.
emf and this voltage drop, it follows that the terminal voltage will
begin to fall.
Ia = Ish + IL
As Rsh>>RL therefore Ish<< IL
Eg is controlled by Rd , when Rd↓, If ↓, B↓, Eg↓
The voltage of a series generator may be controlled by a series
diverter, i.e. a resistance connected in parallel with the field
winding so as to divert some of the current from it. Decrease of
the diverter resistance reduces the current in the field winding
reducing the flux density and thus causing a fall in the
generated emf. Series wound generators have limited
application, and not used for aircraft main power supplies. They
are used as boosters on dc feeders & as a constant current
generator for welding generator and arc lamps.
Eg = Va + Vse + Vb + VT
= Ia Ra + IaRse + Vb + VT
= Ia (Ra + Rse ) + Vb + VT
When IL = 0 then VT = Eg
FIGURE: 3.12.23
After Saturation: when IL↑, Ia↑, then (Va + Vse ) ↑, VT↓↓ until
BUILD-UP OF TERMINAL VOLTAGE VT = 0 , IL = 0&Eg = 0.
If the process of increasing the load is continued after full
When the armature is rotated the conductors cut the weak working load condition have been reached, the terminal voltage
magnetic flux which is due to residual magnetism in the will fall at an increasing rate until a point is reached when the
magnetic system. A small emf is induced in the armature characteristic graph becomes vertical (see illustration). At this
winding and is applied to the ends of the field winding, causing point the generator shuts down; the collapsing voltage can no
a current to flow through the latter and so increasing the longer sustain the load current, and both voltage and load
magnetic flux. current fall to zero.
In this way a progressive increase in induced emf and in field Effect of Load Current on Voltage Build Up
current occurs until the induced emf and the voltage at the
terminals reach the steady open-circuit maximum. With reduced excitation (If ↓) the external characteristic of a
shunt generator falls much more rapidly than it does when the
Characteristic generator is normally excited. The voltage-collapse or
shutdown point is therefore reached with a much smaller load
current. Consider now the case of a shunt generator starting up
Before Saturation: When IL↑, Ia↑, Va↑, AR↑, B↓ slightly, on load.
Eg↓, If ↓, B↓, VT↓ slightly. Hence (IL ∝ )
The degree of excitation at the outset is extremely small,
probably less than 5 percent normal excitation, being solely due
With increasing load current the terminal voltage tends to fall
to residual magnetism.
owing to voltage drop in the armature winding and, in the
absence of interpoles or compensating windings, to weakening
The voltage collapse point will occur with only a small current in
of the main flux by armature reaction. This reduction of voltage
the load circuit, so the voltage will build up only sufficiently to
reduces the field current, thus weakening the main flux and
support the load current to this figure and will then collapse.
producing a further fall in terminal voltage. Provided the field
The generator thus fails to excite. (It is therefore essential that
system is normally excited (ie. there is a considerable degree of
shunt generators are allowed to build up to their correct voltage
magnetic saturation in the magnetic paths) the decrease in
before connecting the load circuit.)
terminal voltage will be relatively small and constant over the
whole working load range of the generator.
The terminal voltage at a given speed can be controlled by This is a combination of shunt and series windings. Each pole
varying the field current. This is achieved by inserting a variable piece carries shunt and series windings which may assist or
resistance in series with the field winding. By increasing the oppose each other.
resistance of the field circuit, the field current is reduced,
causing a reduction of flux, hence of generated emf and Cumulative Compound ɸT = ɸsh + ɸse
terminal voltage.
In such machines the series field, consisting of a few turns
assists the main shunt field wound on the same pole. If the
number of series turns is arranged so that terminal pd at no load
and at full load is the same, the generator is said to be level
compounded. If the number of series turns is increased so that
the voltage increases with load, the machine is said to be over
compounded.
The shunt field winding is connected only across the armature,
excluding the series field impact.
Eg = Vsh + Va
Vsh = Eg – Ia Ra or
Ish=Eg – Ia Ra…… (1)
Uses of Shunt Wound Generators Rsh
The voltage equation for the generator is
Shunt generators are extensively employed for general supply Eg = VT + Vse + Va + Vb
purposes on aircraft, largely because of their simple voltage = VT + ILRse + Ia Ra + Vb
control and effective performance when operating in parallel, neglecting the small drop across the brushes, we get
together with their outstanding suitability for battery charging. Eg = VT + Ia Ra + ILRse
When used for such purposes a form of automatic voltage Eg – IaRa = VT + ILRse
control is essential, as neither speed or load is likely to be Vsh = VT + ILRse or
constant. They are also suitable for unattended operation on Ish= VT + ILRse…………..(2)
steady loads, provided that the prime mover is fitted with a Rsh
speed governor.
FIGURE: 3.12.25
Voltage Regulation
The right hand is held with the thumb, first finger and second
finger mutually perpendicular to each other (at right angles), as
shown in the diagram.
Figure: 3.12.26
The Thumb represents the direction of Motion of the The AC generator would produce a negative emf the
conductor. commutator in the DC generator reverses the polarity of the coil
with respect to the external circuit, so that the negative half of
The First finger represents the direction of the Field. the AC signal is reversed and made positive. The result is a
(north to south) bumpy direct emf which rises and falls but never changes
direction. This type of pulsating emf can be smoothed out by
The Second finger represents the direction of the using more than one coil rotating about the same axis, or by
induced or generated Current (the direction of the other electrical techniques, to give a good imitation of the direct
induced current will be the direction of conventional current delivered by a battery.
current; from positive to negative).
DC MOTORS
INTRODUCTION
The force on a current carrying conductor in a magnetic field is: To change the direction of rotation of a motor having an electro-
magnetic field we need to reverse the direction of current in the
This is expressed as: armature OR the direction of the current in the field.
Force = ( → x →)
= L BSin Ө Changing the supply connections to the motor will not have any
effect; the current being reversed in direction in both the
Where, B is the Flux Density of the major field, is the current armature and the field, the motor continues to run in the same
through the Conductor (producing the minor field), Lis the length direction.
of the Conductor and Ө is between B and plane of the
conductor L. Permanent magnetic motors are however, reversible by simply
changing over the supply connections.
Since the direction of current through the conductor according
to the construction of a motor is always perpendicular to the
direction of field. i.e. Ө = 900, thereby
F = B L Newton
by insulation (Fig 1), the result of the loop rotating is such that protection are dealt with in a later section. The brake assembly
as one half of the commutator leaves a brush, the other half consists of a coil, a brake armature and a brake lining mounted
comes into contact with it. So now, at (C) in Fig 2, when we on the disc on one end of the motor armature. The operation of
apply Fleming’s Rule, side ‘Q’ will move in a downward direction the brake system is dealt with in a later section.
and side ‘P’ upward, keeping the rotation of the loop in an The voltage equation of a dc motor can be written as:
anticlockwise direction. At position (D), the loop passes through V = Eb + Ia Ra + Vb
the vertical and the current reverses direction again until we get by neglecting the brush drop
to (E) where the loop is back to where it was at the start (A) and V = Eb + Ia Ra
the process goes on. A single loop dc motor would not be able Ia = V - Eb
to turn heavy loads, so to obtain a large mechanical output with Ra
smooth running, some improvements have to be made. A The voltage equation changes little bit depending upon the type
laminated iron core carrying a number of armature coils is used of the dc motor.
together with a corresponding number of commutator segments.
The magnetic field is produced by an electromagnet and its field TYPES OF DC MOTOR AND THEIR CHARACTERISTICS
coils, with the spacing between the armature and the pole
pieces kept as small as possible. There are three basic types of dc motors, namely series, shunt
and compound and they differ largely in the way in which their
DC MOTOR CONSTRUCTION field and armature coils are connected.
SERIES DC MOTOR starting torque is required under heavy load conditions, a series
motor would be the best application.
COMPOUND DC MOTOR
MOTOR CONTROL resistance of 12. The motor takes a current of 6A under ‘no
load’. What is the back emf?
The movement of a conductor in a magnetic field induces in it
an emf, which we know from Lenz’s Law, will OPPOSE the As the back emf is produced by the armature, the first thing to
motion producing it. That is to say, the induced voltage will be calculated is the armature current.
oppose the supply voltage. This is called BACK EMF.
Armature Current (a) = Total Current – Field Current (f)
Back emf will never be as great as the supply input and the
difference between them is always such that current can flow in 24
the conductor and produce motion. The value of this current is f 2A
dependent upon the value of the voltage across the conductor. 12
This voltage, often referred to as the EFFECTIVE VOLTAGE is
equal to the difference between the applied voltage and the a 6 2 4A
back emf. Therefore:
Back emf (Eb) = Supply Voltage – Armature Voltage
EFFECTIVE VOLTAGE = APPLIED EMF – BACK EMF
Example
E b V ( a R a )
24 (4 0.25)
Eb 23V
When the motor is ‘on load’, the current it draws is 52A. What
effect does this have on the back emf (Eb)?
FIGURE: 3.12.37
Consider the diagram in Fig 1. A 24V supply is fed to a shunt
motor with an armature resistance of 0.25 and a field
The field current (f) will remain the same (Ohm’s Law applied to The max power a motor can deliver to a load safely is called
a parallel circuit), so: OUTPUT Rating of a motor. Generally, it is expressed in Horse
Power.
f 2A
The Power available at the shaft i.e. net output of a motor is the
product of Speed and Torque.
a 52 2 50 A
POUT = Tshaft
Eb 24 (50 0.25) 11.5V Where is the angular speed in radian per second.
It is noticeable how the back emf falls as the load is increased FOR a DC motor for Fixed value of Power the Torque is
on the motor. When the motor is ‘loaded’ it will tend to slow inversely proportional to the speed whereas if Power is varied
down, and as generated emf is directly proportional to the rate then Torque is directly proportional to the speed. Which means
of change of flux linkage (Faraday’s Law), the value of the back that, for the same output power, we cannot run an increased
emf will be reduced. This will increase the Effective Voltage, load on the same previous speed and thereby we have to
and therefore the Armature Current and the motor speed will be increase the Power.
restored. The back emf therefore determines the armature
current and makes the dc motor a SELF-REGULATING MOTOR SPEED CONTROL
machine. Back emf Eb determines the current in the armature, making the
motor a self-regulating machine in which speed and armature
current are automatically adjusted to the load. At small values
TORQUES IN A DC MOTOR: of load, the shaft torque exceeds the load torque causing the
armature to accelerate and produce a larger back emf. The
Basically, Torque is developed in the Armature of a DC motor increased back emf reduces the armature current, and therefore
and is then shifted to the Load through the Shaft of the motor. the shaft torque, until a state of balance is achieved and the
While transmitting the Power through the shaft, there is a power speed is stabilized. When the load torque is increased (with
loss due to the friction, windage and the Iron losses. The torque increasing load), it exceeds the shaft torque causing a fall in
required to overcome these losses is called a LOST Torque. armature speed. This results in a reduced back emf and a
increased armature current. This increase in armature current
Armature Torque = Shaft Torque + Lost Torque increases the shaft torque, restoring torque balance, and
FIELD CONTROL: B↓ ↑
REVERSIBLE DC MOTORS
Motors used for the operation of landing gear, flaps and other
types of apparatus must be designed to work in either direction
and are therefore called REVERSIBLE MOTORS.
Reversible dc motors are commonly controlled by single-pole FIGURE: 3.12.42BRUSH AND HOLDER ASSEMBLY FOR SMALL
double-throw switches, as with the split field type, but can also MOTORS
be controlled indirectly by the use of relays. The use of relays is
The brushes in a reversible motor are usually held in box-type If the driving motor is connected directly to the operating
holders in line with the centre of the motor shaft as shown in Fig mechanism, a great amount of strain will be imposed upon the
7. With this arrangement the brushes are perpendicular to a motor when it is forced to stop because of the momentum of the
plane tangential to the commutator at the point of brush contact armature and other moving parts. In installations requiring an
and the brushes will wear evenly regardless of the direction of instantaneous stop, a clutch and brake mechanism is employed
motor rotation. On small motors the field and brush housing is to prevent damage when the machine is stopped.
sometimes made in one piece.
CLUTCH AND BRAKE ASSEMBLY
The brush holders are inserted through openings at the end of
the housing and are insulated from the housing by plastic Clutches of several types have been designed for the purpose
bushes. Each brush assembly consists of the brush, a helical of disengaging the motor from the load when the power is cut
spring, a flexible connector inside the spring and a metal off. All such clutches are engaged by magnetic attraction when
contact. When a brush is installed in the motor, it is held in the power is switched on and disengaged by spring action. Two
place by a screw plug. clutch faces are located within the clutch coil. One of the faces
is mounted solidly on the armature shaft and the other is
On some light-duty dc motors, the field coil is replaced by a connected through a diaphragm spring to the drive mechanism.
permanent magnet. To reverse the rotation of this type of When the clutch coil is energized, the two faces are magnetized
motor, the polarity of the applied voltage needs only to be with opposite polarities, hence they are drawn together firmly.
reversed. This reverses the magnetic field of the armature, so The friction thus produced causes the driven mechanism to turn
the motor will reverse its direction of rotation. with the motor. When the power is cut off, the diaphragm spring
separates the faces, thus disengaging the motor.
BRAKES AND CLUTCHES
LIMIT SWITCHES AND PROTECTIVE DEVICES
Many motor-driven devices used in aircraft must be designed so
that the operated mechanism will stop at a precise point. For Because of the limited distance of travel permitted in the driven
example, when landing gear is being retracted or extended, it mechanism, reversible actuating motors are usually limited in
must stop instantly when the operation is complete. their amount of rotation in each direction. It is essential,
therefore, that the motor circuits be provided with switches
which will cut off the power when the driven mechanism has The diagram is a schematic diagram of a reversible motor circuit
reached the limit of its travel. Switches of this type are called with a thermal protective device and a coil for operating the
limit switches and are actuated by cams or levers linked or clutch and brake. A circuit of the type shown would be used for
geared to the driven mechanism. The adjustment of these operating cowl flaps, oil cooler shutter, air valves, and a variety
switches is critical because severe damage may result if the of other devices. Both the limit switches shown are normally
motor continues to run after the limit of operation is reached. closed.
Stripped gears and broken shafts are often the result of
improperly adjusted limit switches. If the driven mechanism is
strong enough to withstand the torque imposed by the motor,
the fuse or circuit breaker in the motor circuit will usually cut off
the current to the motor.
Fig 3.12.44