ELnet LT Modbus Communication Manual

The document describes MODBUS and BACNET communication protocols that can be used with ELNET PowerMeters. MODBUS allows communication between a PC master and up to 247 PowerMeter slaves using functions like read/write registers. It uses RTU transmission mode with an 8-bit data format. BACNET IP supports reading and writing time/date and analog values from ELNET powermeters. The document also provides a table matching ELNET PowerMeter register numbers with measured values like voltage, current, power, etc.

Uploaded by

raajita
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
403 views44 pages

ELnet LT Modbus Communication Manual

The document describes MODBUS and BACNET communication protocols that can be used with ELNET PowerMeters. MODBUS allows communication between a PC master and up to 247 PowerMeter slaves using functions like read/write registers. It uses RTU transmission mode with an 8-bit data format. BACNET IP supports reading and writing time/date and analog values from ELNET powermeters. The document also provides a table matching ELNET PowerMeter register numbers with measured values like voltage, current, power, etc.

Uploaded by

raajita
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 44

MODBUS & BACNET Communication with ELNET PowerMeters

Last Update 10.12.2011

MODBUS Protocol

The ElNet Energy & Power Multimeter has a serial interface port allowing direct
interface with an external communication network supporting the MODBUS Protocol.

MODBUS is an Industry Standard, widely known and commonly used communications


protocol. Using MODBUS provides communication between a PC and up to 247 Powermeter
slaves on a common line- the PC being the master and the powermeters the slaves. The PC
initiates the transaction (either a query or broadcast) and the Powermeter/s responds.
Powermeters respond to the master PC’s request, but will not iniate any transmission on its
own. The PC sends a single Query transaction and the Powermeter responds in a single response
frame and is capable of only one query and one response at a time

1.1 — MODBUS Framing

1.1.1— RTU Transmission Mode

MODBUS uses the standard Remote Terminal Unit (RTU) transmission mode. RTU mode
sends data in 8-bit binary EVEN parity or 8-bit binary NO parity data format. For the ElNet
Energy & Power Multimeter to successfully communicate, choose one in the
communication Set Up.

Field No. of bits


Start bit 1
Data 8
bits
Parity 1
Stop it 1
Table 1-1 RTU Data Format

1
1.1.2 — The RTU Frame Format

Query and response information is sent in frames. Each frame contains:


Address
Function (See Section 1.1.4 for descriptions of functions),
Data
Check.

Address Function Data Check


8 bits 8 bits N * 8 bits 16 bits
Table 1-2 R T U Message Frame Format

If the receiving device (Powermeter) detects a time laps of five characters, then it will assume
the message is incomplete and will flush the frame. The device then assumes that the next byte
received will be an address. The maximum query and response message length is 256 bytes
includuing check characters.

1.1.3 — Address Field


Each Powermeter is designated in a network system by a user assigned address. The Address
can be any number between 1 and 255. The Powermeter will only respond to it’s own
specifacally assigned address.

1.1.4 — Function Field

The function field contains the code that tells the Powermeter what action to perform.

The ElNet Energy & Power Multimeter uses and responds to four standard Message
Format Functions.
Function 03
Function 04
Function 06
Function 16

2
Function Meaning in MODBUS Action
Function 03 Read holding register Obtain data from Powermeter
(Read register)
Function 04 Read input register Obtain data from Powermeter
(Read register)
Function 06 Preset single register Transmit data to Powermeter
(Write single register)
Function 16 Preset multiple register Transmit data to Powermeter
(Write multiple register)
Table 1-3 Function Codes

1.1.5 — Data Field

The Data field contains the body of the message and contains instructions from the PC master
to the Powermeter slave to perform a particuler action or respond to a query. The reply message
from the Powermeter will be information contained in one or more of it’s registers.

1.1.6 — Check Field

The error check field contains the result of Cyclical Redundancy Check (CRC). The start of the
message is ignored in calculating the CRC.
For more detailed information on CRC, refer to the MODBUS Protocol Reference Guide.

1.2 — Registers for ElNet Multimeter

The ElNet Energy & Power Multimeter is capable of supporting either Function 03 or
Function 04 Message Format(See Table 1-3). In a reply to a query from the PC master for a
reading from a particular field, the response from the Powermeter can be either in Format 03 or
Format 04 but will depend on which Format the qeuery was originally sent.

The difference is significant because by using Function 03 the ELNet will only send the
INTEGER part of the field value requested and the PC master will only display the INTEGER
part of the field value.

3
Function 04 on the other hand, is capable of sending two separate halves of the full FLOAT
requested information (each half contained in a separate register). Then it is the task of the PC
master to merge the two halves into a full FLOAT reply. (For more detailed information See
IEEE Standard 754 Floating-Point).

E.G. 1 If the user’s PC master supports Function 03, then the reply will contain the INTEGER
part of the field only.

The PC master requests the Voltage from Line1, and the actual Voltage in that field is
230.5 Volts.

Function 03 will respond with the INTEGER only i.e. 230V.

E.G. 2 If the user PC master supports Function 04, then the reply will contain the information
stored in the two registers asssigned to that field and will contain the full, accurate reply.

The PC master requests the Voltage from Line1, and the actual Voltage in that field is
230.5 Volts.
Function 04 will respond with a composite reply of both register 1 and 2 giving the full
FLOAT value (in IEEE Format) from that field i.e. 230.5V.

When Writing The Clock Registers (151-157) –


User must write special value (123) in register 99.

Bacnet Protocol

The Elnet powermeters supports Bacnet IP.


The information that can be read\write from the Elnets is:

• Time and Date


• Analog values

4
When using ElNet TXT (System B) – User must add 2000 to item (4000 to Register)
(e.g Current Line 1 - System B = ModBus Register # 4013-14)

MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #


Register (UniArt\
Bacnet)
1-2 Voltage Line 1 R 9 9 9 9 9 9 9 1
3-4 Voltage Line 2 R 9 9 9 9 9 9 9 2
5-6 Voltage Line 3 R 9 9 9 9 9 9 9 3
7-8 Voltage between line 1 and Line 2 R 9 9 9 9 9 9 9 4
9-10 Voltage between line 2 and Line 3 R 9 9 9 9 9 9 9 5
11-12 Voltage between line 3 and Line 1 R 9 9 9 9 9 9 9 6
13-14 Current in Line 1 R 9 9 9 9 9 9 9 7
15-16 Current in Line 2 R 9 9 9 9 9 9 9 8
17-18 Current in Line 3 R 9 9 9 9 9 9 9 9
19-20 Active Power Line 1 (Watt) R 9 9 9 9 9 9 9 10
21-22 Active Power Line 2 (Watt) R 9 9 9 9 9 9 9 11
23-24 Active Power Line 3 (watt) R 9 9 9 9 9 9 9 12
25-26 Combined Active Power Line 1+2 +3 R 9 9 9 9 9 9 9 13
27-28 Apparent Power Line 1 (VA) R 9 9 9 9 9 9 9 14
29-30 Apparent Power Line 2 (VA) R 9 9 9 9 9 9 9 15
31-32 Apparent Power Line 3 (VA) R 9 9 9 9 9 9 9 16
33-34 Combined Apparent Power Line 1+2+3 R 9 9 9 9 9 9 9 17
35-36 Reactive Power Line 1 (VAR) R 9 9 9 9 9 9 9 18
37-38 Reactive Power Line 2 (VAR) R 9 9 9 9 9 9 9 19
39-40 Reactive Power Line 3 (VAR) R 9 9 9 9 9 9 9 20
41-42 Combined Reactive Power Line 1+2+3 R 9 9 9 9 9 9 9 21

5
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
43-44 Power Factor Line 1 (PF) R 9 9 9 9 9 9 9 22
45-46 Power Factor Line 2 (PF) R 9 9 9 9 9 9 9 23
47-48 Power Factor Line 3 (PF) R 9 9 9 9 9 9 9 24
49-50 Combined Power Factor for Line 1+2+3 R 9 9 9 9 9 9 9 25
51-52 Frequency Line 1 (Hrz) R 9 9 9 9 9 9 9 26
53-54 Frequency Line 2 (Hrz) R 9 9 9 9 9 9 9 27
55-56 Frequency Line 3 (Hrz) R 9 9 9 9 9 9 9 28
57-58 Current Neutral Line R 9 9 9 9 9 9 9 29
59-60 Power Factor Line 1 (L & C) R 9 9 30
61-62 Power Factor Line 2 (L & C) R 9 9 31
63-64 Power Factor Line 3 (L & C) R 9 9 32
65-66 Combined Power Factor for Line 1+2+3 (L & C) R 9 9 33
77-78 TOU (Taoz) rate R/W 9 9 9 9 9 9 39
79-80 Active Total Energy (Wh) R 9 9 9 9 9 9 9 40
81-82 Reactive Total Energy (VARh) R 9 9 9 9 9 9 9 41
83-84 Apparent Total Energy (Vah) R 9 9 9 9 9 9 9 42
85-86 Date Time (Win Format) R 9 9 43
87-88 Time from 01 01 2000 in seconds R 9 9 9 9 9 9 9 44
89-90 ADDRESS R 9 9 9 9 9 9 9 45
91-92 BAUD RATE R 9 9 9 9 9 9 9 46
93-94 PARITY R 9 9 9 9 9 9 9 47
95-96 Current Transformer Ratio R/W 9 9 9 9 9 9 9 48
97-98 Timed average Voltage R/W 9 9 9 9 9 9 9 49
99-100 Timed average Current R/W 9 9 9 9 9 9 9 50

6
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
101-102 Timed average Power R/W 9 9 9 9 9 9 9 51
103-104 Timed avaerge Frequqncy R/W 9 9 9 9 9 9 9 52
105-106 THD for Volts Line 1 R 9 9 91 9 91 53
107-108 THD for Volts Line 2 R 9 9 91 9 91 54
109-110 THD for Volts Line 3 R 9 9 91 9 91 55
111-112 THD for Current Line 1 R 9 9 91 9 91 56
113-114 THD for Current Line 2 R 9 9 91 9 91 57
115-116 THD for Current Line 3 R 9 9 91 9 91 58
117-118 Active Rate (1,2,3) R 9 9 9 9 9 59
119-120 Active Energy Line 1 (W-Import) R 9 9 9 9 9 9 9 60
121-122 Active Energy Line 2 (W-Import) R 9 9 9 9 9 9 9 61
123-124 Active Energy Line 3 (W-Import) R 9 9 9 9 9 9 9 62
125-126 Reactive Energy Line 1 (VAR-Import) R 9 9 9 9 9 9 9 63
127-128 Reactive Energy Line 2 (VAR-Import) R 9 9 9 9 9 9 9 64
129-130 Reactive Energy Line 3 (VAR-Import) R 9 9 9 9 9 9 9 65
131-132 Apparant Energy Line 1 (VA-Import) R 9 9 9 9 9 9 9 66
133-134 Apparant Energy Line 2 (VA-Import) R 9 9 9 9 9 9 9 67
135-136 Apparant Energy Line 3 (VA-Import) R 9 9 9 9 9 9 9 68
137-138 Active Energy Line 1 – Rate 1 (Imp) R 9 9 9 9 9 9 69
139-140 Active Energy Line 2 – Rate 1 (Imp) R 9 9 9 9 9 9 70
141-142 Active Energy Line 3 – Rate 1 (Imp) R 9 9 9 9 9 9 71
143-144 Active Energy Line 1 – Rate 2 (Imp) R 9 9 9 9 9 9 72
145-146 Active Energy Line 2 – Rate 2 (Imp) R 9 9 9 9 9 9 73
147-148 Active Energy Line 3 – Rate 2 (Imp) R 9 9 9 9 9 9 74

7
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
149-150 Active Energy Line 1 – Rate 3 (Imp) R 9 9 9 9 9 9 75
151-152 Active Energy Line 2 – Rate 3 (Imp) R 9 9 9 9 9 9 76
153-154 Active Energy Line 3 – Rate 3 (Imp) R 9 9 9 9 9 9 77
155-156 Active Energy Line 1+2+3 – Rate 1 (I) R 9 9 9 9 9 9 78
157-158 Active Energy Line 1+2+3 – Rate 2 (I) R 9 9 9 9 9 9 79
159-160 Active Energy Line 1+2+3 – Rate 3 (I) R 9 9 9 9 9 9 80
161-162 Apparant Energy Line 1 – Rate 1 (I) R 9 9 9 9 9 9 81
163-164 Apparant Energy Line 2 – Rate 1 (I) R 9 9 9 9 9 9 82
165-166 Apparant Energy Line 3 – Rate 1 (I) R 9 9 9 9 9 9 83
167-168 Apparant Energy Line 1 – Rate 2 (I) R 9 9 9 9 9 9 84
169-170 Apparant Energy Line 2 – Rate 2 (I) R 9 9 9 9 9 9 85
171-172 Apparant Energy Line 3 – Rate 2 (I) R 9 9 9 9 9 9 86
173-174 Apparant Energy Line 1 – Rate 3 (I) R 9 9 9 9 9 9 87
175-176 Apparant Energy Line 2 – Rate 3 (I) R 9 9 9 9 9 9 88
177-178 Apparant Energy Line 3 – Rate 3 (I) R 9 9 9 9 9 9 89
179-180 Apparant Energy 1+2+3 – Rate 1 (I) R 9 9 9 9 9 9 90
181-182 Apparant Energy 1+2+3 – Rate 2 (I) R 9 9 9 9 9 9 91
183-184 Apparant Energy 1+2+3 – Rate 3 (I) R 9 9 9 9 9 9 92
185-186 Voltage Transformer Ratio R/W 9 9 9 9 9 9 9 93
187-188 Epeom Revision R 9 9 9 9 9 9 9 94
189-190 Demo Mode R/W* 9 9 9 9 9 9 9 95
191-192 Configuration PassWord R/W 9 9 9 9 9 9 96
193-194 Min. Current To Accumulate Energy R/W 9 9 9 9 9 9 97
195-196 MuliMeter ID R 9 9 9 9 9 9 98

8
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
197-198 User Function Mode (Technical) R/W 9 9 9 9 9 9 9 99

201-202 Demand – KW Max (Watt) R 9 9 101


203-204 Demand – PF (KW) R 9 9 102
205-206 Demand – Date (KW) R 9 9 103
207-208 Demand – KVA (Watt) R 9 9 104
209-210 Demand – PF (KVA) R 9 9 105
211-212 Demand – Date (KVA) R 9 9 106
213-214 Demand – Current (A) L1 R/W* 9 9 9 9 107
215-216 Demand – Current (A) L2 R/W* 9 9 9 9 108
217-218 Demand – Current (A) L3 R/W* 9 9 9 9 109
219-220 Demand – Current (A) L1+L2+L3 R/W* 9 9 9 9 110
221-222 Demand – Current (A) L1 – Date R 9 9 9 9 111
223-224 Demand – Current (A) L2 – Date R 9 9 9 9 112
225-226 Demand – Current (A) L3 – Date R 9 9 9 9 113
227-228 Demand – Current (A) L1+2+3 – Date R 9 9 9 9 114

233-234 Clear All Current Demand W 9 9 9 9 117


235-236 Current Demand – KW Max R 9 9 118
241-242 PFC – Power Factor R/W 9 121
243-244 PFC – On Time R/W 9 122
245-246 PFC – Off Time R/W 9 123
247-248 PFC – Avarege Time (Minute) R/W 9 124
249-250 PFC – Stages R/W 9 125

9
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
251-252 PFC – Mode Of Operation R/W 9 126
253-254 PFC – THD (Volt) R/W 9 127
255-256 PFC – Capacitor #1 (KVAR) R/W 9 128
257-258 PFC – Capacitor #2 (KVAR) R/W 9 129
259-260 PFC – Capacitor #3 (KVAR) R/W 9 130
261-262 PFC – Capacitor #4 (KVAR) R/W 9 131
263-264 PFC – Capacitor #5 (KVAR) R/W 9 132
265-266 PFC – Capacitor #6 (KVAR) R/W 9 133
267-268 PFC – THD (Current) R/W 9 134

271-272 PFC – PF Avarrage Time R/W 9 136


273-274 PFC – Comb. Stayble Time R/W 9 137
275-276 PFC – Hysteresis R/W 9 138
277-278 PFC – % Voltage (VT) For OK R/W 9 139
279-280 PFC – % Current (CT) To Stop R/W 9 140
281-282 PFC – Capacitor #1 Status R 9 141
283-284 PFC – Capacitor #2 Status R 9 142
285-286 PFC – Capacitor #3 Status R 9 143
287-288 PFC – Capacitor #4 Status R 9 144
289-290 PFC – Capacitor #5 Status R 9 145
291-292 PFC – Capacitor #6 Status R 9 146
293-294 Pulse Value (KW-IMP) Relay 1 R/W 9 9 147
295-296 Pulse Value (KW-EXP) Relay 2 R/W 9 9 148
297-298 Pulse Value (KQ-IMP) Relay 3 R/W 9 9 149

10
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
299-300 Pulse Duration (Seconds) R/W 9 9 150
301-302 Clock : Seconds R/W* 9 9 9 9 9 9 9 151
303-304 Clock : Minutes R/W* 9 9 9 9 9 9 9 152
305-306 Clock : Hours R/W* 9 9 9 9 9 9 9 153
307-308 Clock : Week Day (1-7) R/W* 9 9 9 9 9 9 9 154
309-310 Clock : Day R/W* 9 9 9 9 9 9 9 155
311-312 Clock : Month R/W* 9 9 9 9 9 9 9 156
313-314 Clock : Year (20xx) R/W* 9 9 9 9 9 9 9 157
315-316 Run Time (Seconds With Current) R/W* 9 9 9 158
317-318 Day Time (Win Format) R 9 9 159
319-320 Force Cpu To response in MC R/W 9 160
321-322 Type Of Din 1 R/W* 9 161
323-324 Type Of Din 2 R/W* 9 162
325-326 Type Of Din 3 R/W* 9 163
327-328 Type Of Din 4 R/W* 9 164

333-334 K.Factor – Current – Line 1 R 9 9 167


335-336 K.Factor – Current – Line 2 R 9 9 168
337-338 K.Factor – Current – Line 3 R 9 9 169
339-340 K.Factor – Current – Line 1+2+3 R 9 9 170
341-342 Din 1 Energy Total – Rate 1 R 9 171
343-344 Din 2 Energy Total – Rate 1 R 9 172
345-346 Din 3 Energy Total – Rate 1 R 9 173
11
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
347-348 Din 4 Energy Total – Rate 1 R 9 174
349-350 Din 1 Energy Total – Rate 2 R 9 175
351-352 Din 2 Energy Total – Rate 2 R 9 176
353-354 Din 3 Energy Total – Rate 2 R 9 177
355-356 Din 4 Energy Total – Rate 2 R 9 178
357-358 Din 1 Energy Total – Rate 3 R 9 179
359-360 Din 2 Energy Total – Rate 3 R 9 180
361-362 Din 3 Energy Total – Rate 3 R 9 181
363-364 Din 4 Energy Total – Rate 3 R 9 182
365-366 Din 1 Energy Total – Rate 1+2+3 R 9 183
367-368 Din 2 Energy Total – Rate 1+2+3 R 9 184
369-370 Din 3 Energy Total – Rate 1+2+3 R 9 185
371-372 Din 4 Energy Total – Rate 1+2+3 R 9 186

379-380 Temprature Sensor R/W* 9 9 9 9 9 190


381-382 Digital In 1 - Status R 9 9 9 9 9 191
383-384 Digital In 2 - Status R 9 9 9 9 9 192
385-386 Digital In 3 - Status R 9 9 9 193
387-388 Digital In 4 - Status R 9 9 9 194

395-396 Web Authentication (User=admin) R/W 9 9 198


397-398 Fast Trend Cycle Time (Seconds) R/W 9 9 199
399-400 History - Date W 9 9 9 9 9 9 200
401-402 History – Day W 9 9 9 9 9 9 201

12
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
403-404 History – Month W 9 9 9 9 9 9 202
405-406 History - Year W 9 9 9 9 9 9 203
407-408 History-Active Energy Line 1 – Rate 1 R 9 9 9 9 9 9 204
409-410 History-Active Energy Line 2 – Rate 1 R 9 9 9 9 9 9 205
411-412 History-Active Energy Line 3 – Rate 1 R 9 9 9 9 9 9 206
413-414 History-Active Energy Line 1 – Rate 2 R 9 9 9 9 9 9 207
415-416 History-Active Energy Line 2 – Rate 2 R 9 9 9 9 9 9 208
417-418 History-Active Energy Line 3 – Rate 2 R 9 9 9 9 9 9 209
419-420 History-Active Energy Line 1 – Rate 3 R 9 9 9 9 9 9 210
421-422 History-Active Energy Line 2 – Rate 3 R 9 9 9 9 9 9 211
423-424 History-Active Energy Line 3 – Rate 3 R 9 9 9 9 9 9 212
425-426 History-ReActive Energy Ln 1–Rate 1 R 9 9 9 9 9 9 213
427-428 History-ReActive Energy Ln 2–Rate 1 R 9 9 9 9 9 9 214
429-430 History-ReActive Energy Ln 3–Rate 1 R 9 9 9 9 9 9 215
431-432 History-ReActive Energy Ln 1–Rate 2 R 9 9 9 9 9 9 216
433-434 History-ReActive Energy Ln 2–Rate 2 R 9 9 9 9 9 9 217
435-436 History-ReActive Energy Ln 3–Rate 2 R 9 9 9 9 9 9 218
437-438 History-ReActive Energy Ln 1–Rate 3 R 9 9 9 9 9 9 219
439-440 History-ReActive Energy Ln 2–Rate 3 R 9 9 9 9 9 9 220
441-442 History-ReActive Energy Ln 3–Rate 3 R 9 9 9 9 9 9 221
443-444 History-Din 1 Energy – Rate 1 R 9 222
445-446 History-Din 2 Energy – Rate 1 R 9 223
447-448 History-Din 3 Energy – Rate 1 R 9 224
449-450 History-Din 4 Energy – Rate 1 R 9 225

13
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
451-452 History-Din 1 Energy – Rate 2 R 9 226
453-454 History-Din 2 Energy – Rate 2 R 9 227
455-456 History-Din 3 Energy – Rate 2 R 9 228
457-458 History-Din 4 Energy – Rate 2 R 9 229
459-460 History-Din 1 Energy – Rate 3 R 9 230
461-462 History-Din 2 Energy – Rate 3 R 9 231
463-464 History-Din 3 Energy – Rate 3 R 9 232
465-466 History-Din 4 Energy – Rate 3 R 9 233

491-492 History – Reading Date R 9 9 9 9 9 9 246


493-494 Debug Counter 1 R/W 9 9 9 9 247
495-496 Debug Counter 2 R/W 9 9 9 9 248
497-498 Debug Counter 3 R/W 9 9 9 9 249
499-500 Debug Counter 4 R/W 9 9 9 9 250
501-502 Technical Calibration Value 1 R 9 9 9 9 9 9 251
503-504 Technical Calibration Value 2 R 9 9 9 9 9 9 252
505-506 Technical Calibration Value 3 R 9 9 9 9 9 9 253
507-508 Technical Calibration Value 4 R 9 9 9 9 9 9 254
509-510 Float Format (0,1,2) R/W 9 9 9 255
511-512 Compatibility Mode (0,130,170) R/W 9 9 9 256
513-514 Technical Current Calibration R/W 9 9 9 257

519-520 Start Time1 For Period Alarm R/W 9 9 260


521-522 Stop Time1 For Period Alarm R/W 9 9 261

14
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
523-524 High Power (KW) (Period) R/W 9 9 262
525-526 Low Power (KW) (Period) R/W 9 9 263
527-528 Time Table For Period Alarm High R/W 9 9 264
529-530 Time Table For Period Alarm Low R/W 9 9 265
531-532 Start2 Time For Period Alarm R/W 9 9 266
533-534 Stop2 Time For Period Alarm R/W 9 9 267

537-538 ReActive Energy Line 1 –Rate 1 (Imp) R 9 9 9 9 269


539-540 ReActive Energy Line 2 –Rate 1 (Imp) R 9 9 9 9 270
541-542 ReActive Energy Line 3 –Rate 1 (Imp) R 9 9 9 9 271
543-544 ReActive Energy Line 1 –Rate 2 (Imp) R 9 9 9 9 272
545-546 ReActive Energy Line 2 –Rate 2 (Imp) R 9 9 9 9 273
547-548 ReActive Energy Line 3 –Rate 2 (Imp) R 9 9 9 9 274
549-550 ReActive Energy Line 1 –Rate 3 (Imp) R 9 9 9 9 275
551-552 ReActive Energy Line 2 –Rate 3 (Imp) R 9 9 9 9 276
553-554 ReActive Energy Line 3 –Rate 3 (Imp) R 9 9 9 9 277
555-556 ReActive E. Line 1+2+3 –Rate 1 (I) R 9 9 9 9 278
557-558 ReActive E. Line 1+2+3 –Rate 2 (I) R 9 9 9 9 279
559-560 ReActive E. Line 1+2+3 –Rate 3 (I) R 9 9 9 9 280
561-562 Virtual Pulse Value (KW) P-Total R/W 9 9 281
563-564 Virtual Pulse Counter R/W 9 9 282
565-566 Fix Value (Debug) 123.4 R 9 9 283
567-568 Float Order (0=LM),(1=ML) R/W 9 9 284
569-570 ReActive E.Total In Capacitor Mode R 9 285

15
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
571-572 ReActive E.Total In Non Capacitor Mode R 9 286

579-580 Delay (MS) for response time (RS485) R/W 9 290


581-582 Current Line 1 Opposite Error R 9 9 9 9 9 9 291
583-584 Current Line 2 Opposite Error R 9 9 9 9 9 9 292
585-586 Current Line 3 Opposite Error R 9 9 9 9 9 9 293
587-588 Voltage Seq. Error R 9 9 9 9 9 9 294

601-602 1st Harmonics for Volts Line 1 R 9 9 91 91 301


603-604 2nd Harmonics for Volts Line 1 R 9 9 91 91 302
91 91
⇓ ⇓ ⇓ ⇓
1 1
661-662 31st Harmonics for Volts Line 1 R 9 9 9 9 331
663-664 32nd Harmonics for Volts Line 1 R 9 9 91 91 332
665-666 1st Harmonics for Volts Line 2 R 9 9 91 91 333
667-668 2nd Harmonics for Volts Line 2 R 9 9 91 91 334
91 91
⇓ ⇓ ⇓ ⇓
1 1
725-726 31st Harmonics for Volts Line 2 R 9 9 9 9 363
727-728 32nd Harmonics for Volts Line 2 R 9 9 91 91 364
729-730 1st Harmonic for Volts Line 3 R 9 9 91 91 365
731-732 2nd Harmonics for Volts Line 3 R 9 9 91 91 366

⇓ ⇓ ⇓ ⇓
789-790 31st Harmonics for Vots Line 3 R 9 9 91 91 395

16
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
791-792 32nd Harmonics for Volts Line 3 R 9 9 91 91 396
793-794 1st Harmonics for Current Line 1 R 9 9 91 91 397
795-796 2nd Harmonics for Current Line 1 R 9 9 91 91 398
91 91
⇓ ⇓ ⇓ ⇓
1 1
853-854 31st Harmonics for Current Line 1 R 9 9 9 9 427
855-856 32nd Harmonics for Current Line 1 R 9 9 91
91
428
857-858 1st Harmonics for Current Line 2 R 9 9 91 91 429
859-860 2nd Harmonics for Current Line 2 R 9 9 91 91 430
91 91
⇓ ⇓ ⇓ ⇓
1 1
917-918 31st Harmonics for Current line 2 R 9 9 9 9 459
919-920 32nd Harmonicsfor Current Line 2 R 9 9 91 91 460
921-922 1st Harmonics for Current Line 3 R 9 9 91 91 461
923-924 2nd Harmonics for Current Line 3 R 9 9 91 91 462
91 91
⇓ ⇓ ⇓ ⇓
1 1
981-982 31st Harmonics for Current Line 3 R 9 9 9 9 491
983-984 32nd Harmonics for Current Line 3 R 9 9 91 91 492

1001-2 User Alarm #1 R 9 9 501


1003-4 User Alarm #2 R 9 9 502
1005-6 User Alarm #3 R 9 9 503
⇓ ⇓ ⇓ ⇓
1253-4 User Alarm #127 R 9 9 627
17
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
1255-6 User Alarm #128 R 9 9 628

1261-62 Demand – Watt L1 R 9 9 631


1263-64 Demand – Watt L2 R 9 9 632
1265-66 Demand – Watt L3 R 9 9 633
1267-68 Demand – VAR L1 R 9 9 634
1269-70 Demand – VAR L2 R 9 9 635
1271-72 Demand – VAR L3 R 9 9 636
1273-74 Demand – VA L1 R 9 9 637
1275-76 Demand – VA L2 R 9 9 638
1277-78 Demand – VA L3 R 9 9 639
1279-80 Demand – Watt L1+L2+L3 R 9 9 640
1281-82 Demand – VAR L1+L2+L3 R 9 9 641
1283-84 Demand – VA L1+L2+L3 R 9 9 642
1285-86 Demand – Current (A) L1 R 9 9 643
1287-88 Demand – Current (A) L2 R 9 9 644
1289-90 Demand – Current (A) L3 R 9 9 645
1291-92 Demand – Current (A) L1+L2+L3 R 9 9 646

1299-00 Long Wave Write Now !! W 9 650


1301-02 Long Wave Event (Before) - Seconds R/W 9 651
1303-04 Long Wave Event (Total) - Seconds R/W 9 652

18
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
1305-06 Current L1 – High - Write Long Wave Event R/W 9 653
1307-08 Current L1 – Hysteresis (Long Wave Event) R/W 9 654

1315-16 PQ – V.Nominal R/W 9 658


1317-18 PQ – Enable (Active) R/W 9 659
1319-20 Active Energy Line 1 (Export) R 9 9 9 9 660
1321-22 Active Energy Line 2 (Export) R 9 9 9 9 661
1323-24 Active Energy Line 3 (Export) R 9 9 9 9 662
1325-26 Reactive Energy Line 1 (Export) R 9 9 9 9 663
1327-28 Reactive Energy Line 2 (Export) R 9 9 9 9 664
1329-30 Reactive Energy Line 3 (Export) R 9 9 9 9 665
1331-32 Apparant Energy Line 1 (Export) R 9 9 9 9 666
1333-34 Apparant Energy Line 2 (Export) R 9 9 9 9 667
1335-36 Apparant Energy Line 3 (Export) R 9 9 9 9 668
1337-38 Active Energy Line 1 – Rate 1 (Exp) R 9 9 9 9 669
1339-40 Active Energy Line 2 – Rate 1 (Exp) R 9 9 9 9 670
1341-42 Active Energy Line 3 – Rate 1 (Exp) R 9 9 9 9 671
1343-44 Active Energy Line 1 – Rate 2 (Exp) R 9 9 9 9 672
1345-46 Active Energy Line 2 – Rate 2 (Exp) R 9 9 9 9 673
1347-48 Active Energy Line 3 – Rate 2 (Exp) R 9 9 9 9 674
1349-50 Active Energy Line 1 – Rate 3 (Exp) R 9 9 9 9 675
1351-52 Active Energy Line 2 – Rate 3 (Exp) R 9 9 9 9 676
1353-54 Active Energy Line 3 – Rate 3 (Exp) R 9 9 9 9 677
1355-56 Active Energy Line 1+2+3 –Rate 1 (E) R 9 9 9 9 678

19
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
1357-58 Active Energy Line 1+2+3 –Rate 2 (E) R 9 9 9 9 679
1359-60 Active Energy Line 1+2+3 –Rate 3 (E) R 9 9 9 9 680
1361-62 Apparant Energy Line 1 – Rate 1 (E) R 9 9 9 9 681
1363-64 Apparant Energy Line 2 – Rate 1 (E) R 9 9 9 9 682
1365-66 Apparant Energy Line 3 – Rate 1 (E) R 9 9 9 9 683
1367-68 Apparant Energy Line 1 – Rate 2 (E) R 9 9 9 9 684
1369-70 Apparant Energy Line 2 – Rate 2 (E) R 9 9 9 9 685
1371-72 Apparant Energy Line 3 – Rate 2 (E) R 9 9 9 9 686
1373-74 Apparant Energy Line 1 – Rate 3 (E) R 9 9 9 9 687
1375-76 Apparant Energy Line 2 – Rate 3 (E) R 9 9 9 9 688
1377-78 Apparant Energy Line 3 – Rate 3 (E) R 9 9 9 9 689
1379-80 Apparant Energy 1+2+3 – Rate 1 (E) R 9 9 9 9 690
1381-82 Apparant Energy 1+2+3 – Rate 2 (E) R 9 9 9 9 691
1383-84 Apparant Energy 1+2+3 – Rate 3 (E) R 9 9 9 9 692
1385-86 Active Energy (Export) R 9 9 9 9 693
1387-88 Reactive Energy (Export) R 9 9 9 9 694
1389-90 Apparant Energy (Export) R 9 9 9 9 695

1401-2 EN50160 SetUp Value #1 R/W 9 9 701


⇓ ⇓ ⇓ ⇓
1519-20 EN50160 SetUp Value #60 R/W 9 9 760

1521-22 EN50160 Alarm 1(Phase Bit 1,2,3) R 9 9 761

20
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
⇓ ⇓ ⇓ ⇓
1599-00 EN50160 Alarm 40(Phase Bit 1,2,3) R 9 9 800

1601-2 EN50160 Daily Cnt Alrm #1 (L1) R 9 9 801


1603-4 EN50160 Daily Cnt Alrm #1 (L2) R 9 9 802
1605-6 EN50160 Daily Cnt Alrm #1 (L3) R 9 9 803
1607-8 EN50160 Daily Cnt Alrm #2 (L1) R 9 9 804
1609-10 EN50160 Daily Cnt Alrm #2 (L2) R 9 9 805
1611-12 EN50160 Daily Cnt Alrm #2 (L3) R 9 9 806
⇓ ⇓ ⇓ ⇓
1835-6 EN50160 Daily Cnt Alrm #40 (L1) R 9 9 918
1837-8 EN50160 Daily Cnt Alrm #40 (L2) R 9 9 919
1839-40 EN50160 Daily Cnt Alrm #40 (L3) R 9 9 920

2001-2 EN50160 Daily MaxVal Alrm #1 (L1) R 9 9 1001


2003-4 EN50160 Daily MaxVal Alrm #1 (L2) R 9 9 1002
2005-6 EN50160 Daily MaxVal Alrm #1 (L3) R 9 9 1003
2007-8 EN50160 Daily MaxVal Alrm #2 (L1) R 9 9 1004
2009-10 EN50160 Daily MaxVal Alrm #2 (L2) R 9 9 1005
2011-12 EN50160 Daily MaxVal Alrm #2 (L3) R 9 9 1006
⇓ ⇓ ⇓ ⇓
2235-6 EN50160 Daily MaxVal Alrm#40(L1) R 9 9 1118

21
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
2237-8 EN50160 Daily MaxVal Alrm#40(L2) R 9 9 1119
2239-40 EN50160 Daily MaxVal Alrm#40(L3) R 9 9 1120

2401-2 EN50160 Daily Time Alrm #1 (L1) R 9 9 1201


2403-4 EN50160 Daily Time Alrm #1 (L2) R 9 9 1202
2405-6 EN50160 Daily Time Alrm #1 (L3) R 9 9 1203
2407-8 EN50160 Daily Time Alrm #2 (L1) R 9 9 1204
2409-10 EN50160 Daily Time Alrm #2 (L2) R 9 9 1205
2411-12 EN50160 Daily Time Alrm #2 (L3) R 9 9 1206
⇓ ⇓ ⇓ ⇓
2635-6 EN50160 Daily Time Alrm#40(L1) R 9 9 1318
2637-8 EN50160 Daily Time Alrm#40(L2) R 9 9 1319
2639-40 EN50160 Daily Time Alrm#40(L3) R 9 9 1320

2801-2 EN Yesterday Cnt Alrm #1 (L1) R 9 9 1401


2803-4 EN Yesterday Cnt Alrm #1 (L2) R 9 9 1402
2805-6 EN Yesterday Cnt Alrm #1 (L3) R 9 9 1403
2807-8 EN Yesterday Cnt Alrm #2 (L1) R 9 9 1404
2809-10 EN Yesterday Cnt Alrm #2 (L2) R 9 9 1405
2811-12 EN Yesterday Cnt Alrm #2 (L3) R 9 9 1406
⇓ ⇓ ⇓ ⇓
3035-6 EN Yesterday Cnt Alrm#40(L1) R 9 9 1518
3037-8 EN Yesterday Cnt Alrm#40(L2) R 9 9 1519
22
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
3039-40 EN Yesterday Cnt Alrm#40(L3) R 9 9 1520

3201-2 EN Yesterday MaxVal Alrm #1 (L1) R 9 9 1601


3203-4 EN Yesterday MaxVal Alrm #1 (L2) R 9 9 1602
3205-6 EN Yesterday MaxVal Alrm #1 (L3) R 9 9 1603
3207-8 EN Yesterday MaxVal Alrm #2 (L1) R 9 9 1604
3209-10 EN Yesterday MaxVal Alrm #2 (L2) R 9 9 1605
3211-12 EN Yesterday MaxVal Alrm #2 (L3) R 9 9 1606
⇓ ⇓ ⇓ ⇓
3435-6 EN Yesterday MaxVal Alrm#40(L1) R 9 9 1718
3437-8 EN Yesterday MaxVal Alrm#40(L2) R 9 9 1719
3439-40 EN Yesterday MaxVal Alrm#40(L3) R 9 9 1720

3601-2 EN Yesterday Time Alrm #1 (L1) R 9 9 1801


3603-4 EN Yesterday Time Alrm #1 (L2) R 9 9 1802
3605-6 EN Yesterday Time Alrm #1 (L3) R 9 9 1803
3607-8 EN Yesterday Time Alrm #2 (L1) R 9 9 1804
3609-10 EN Yesterday Time Alrm #2 (L2) R 9 9 1805
3611-12 EN Yesterday Time Alrm #2 (L3) R 9 9 1806
⇓ ⇓ ⇓ ⇓
3835-6 EN Yesterday Time Alrm#40(L1) R 9 9 1918
3837-8 EN Yesterday Time Alrm#40(L2) R 9 9 1919
3839-40 EN Yesterday Time Alrm#40(L3) R 9 9 1920
23
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)

3841-42 Summer Clock DTE #1 (Sec) R/W 9 9 9 1921


3843-44 Summer Clock DTE #2 (Sec) R/W 9 9 9 1922
⇓ ⇓ ⇓ ⇓
3879-80 Summer Clock DTE #20 (Sec) R/W 9 9 9 1940
3881-82 Summer Clock #1 – Minute To Add R/W 9 9 9 1941
3883-84 Summer Clock #2 – Minute To Add R/W 9 9 9 1942
⇓ ⇓ ⇓ ⇓
3919-20 Summer Clock #20 – Minute To Add R/W 9 9 9 1960
3921-22 Summer Clock DTE #1 (Hour) R/W 9 9 9 1961
3923-24 Summer Clock DTE #2 (Hour) R/W 9 9 9 1962
⇓ ⇓ ⇓ ⇓
3959-60 Summer Clock DTE #20 (Hour) R/W 9 9 9 1980

4001-2 Active Energy (L123)- Month 1 -KWh R 9 9 9 9 9 2001


4003-4 Active Energy (L123)- Month 2-KWh R 9 9 9 9 9 2002
⇓ ⇓ ⇓ ⇓
4071-72 Active Energy(L123)- Month 36-KWh R 9 9 9 9 9 2036
4073-74 Month # 1 (1-12) (For Register 2001) R 9 9 9 9 2037
4075-76 Month # 2 (1-12) (For Register 2002) R 9 9 9 9 2038
⇓ ⇓ ⇓ ⇓

24
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
4143-44 Month #36 (1-12) (For Register 2036) R 9 9 9 9 2072
4145-46 Year # 1 (2001-99) (Register 2001) R 9 9 9 9 2073
4147-48 Year # 2 (2001-99) (Register 2002) R 9 9 9 9 2074
⇓ ⇓ ⇓ ⇓
4215-16 Year #36 (2001-99) (Register 2036) R 9 9 9 9 2108

4241-42 U.Alarm – High Current Value R/W 9 2121


4243-44 U.Alarm – High Voltage Value R/W 9 2122
4245-46 U.Alarm – Low Voltage Value R/W 9 2123
4247-48 U.Alarm – Low PF Value R/W 9 2124
4249-50 U.Alarm – High V.THD Value R/W 9 2125
4251-52 U.Alarm – High I.THD Value R/W 9 2126

4261-62 U.Alarm – High Current DelayOn R/W 9 2131


4263-64 U.Alarm – High Voltage DelayOn R/W 9 2132
4265-66 U.Alarm – Low Voltage DelayOn R/W 9 2133
4267-68 U.Alarm – Low PF DelayOn R/W 9 2134
4269-70 U.Alarm – High V.THD DelayOn R/W 9 2135
4271-72 U.Alarm – High I.THD DelayOn R/W 9 2136

4281-82 Demand – THD Current (A) L1 R/W* 9 9 2141


4283-84 Demand – THD Current (A) L2 R/W* 9 9 2142
4285-86 Demand – THD Current (A) L3 R/W* 9 9 2143
4287-88 Demand – THD Current (A) L1 | L2 | l3 R/W* 9 9 2144
25
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
4289-90 Demand – THD Current (A) L1 - Date R 9 9 2145
4291-92 Demand – THD Current (A) L2 - Date R 9 9 2146
4293-94 Demand – THD Current (A) L3 - Date R 9 9 2147
4295-96 Demand – THD Current (A) L123 - Date R 9 9 2148
4297-98 Demand – THD Voltage (A) L1 R/W* 9 9 2149
4299-300 Demand – THD Voltage (A) L2 R/W* 9 9 2150
4301-02 Demand – THD Voltage (A) L3 R/W* 9 9 2151
4303-04 Demand – THD Voltage (A) L1 | L2 | l3 R/W* 9 9 2152
4305-06 Demand – THD Voltage (A) L1 - Date R 9 9 2153
4307-08 Demand – THD Voltage (A) L2 - Date R 9 9 2154
4309-10 Demand – THD Voltage (A) L3 - Date R 9 9 2155
4311-12 Demand – THD Voltage (A) L123 - Date R 9 9 2156
4313-14 Clear All THD Demand W 9 9 9 9 2157

4413-14 Alarm- High Voltage L1 R/W 9 9 2207


4415-16 Alarm- High Voltage L2 R/W 9 9 2208
4417-18 Alarm- High Voltage L3 R/W 9 9 2209
4419-20 Alarm- High Voltage L1-2 R/W 9 9 2210
4421-22 Alarm- High Voltage L2-3 R/W 9 9 2211
4423-24 Alarm- High Voltage L3-1 R/W 9 9 2212
4427-28 Alarm- High Current L1 R/W 9 9 2214
4429-30 Alarm- High Current L2 R/W 9 9 2215
4431-32 Alarm- High Current L3 R/W 9 9 2216
4433-34 Alarm- High Current L0 R/W 9 9 2217

26
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
4437-38 Alarm- High PF L1 R/W 9 9 2219
4439-40 Alarm- High PF L2 R/W 9 9 2220
4441-42 Alarm- High PF L3 R/W 9 9 2221
4443-44 Alarm- High PF (L1-2-3) R/W 9 9 2222
4453-54 Alarm- High Voltage THD L1 R/W 9 9 2227
4455-56 Alarm- High Voltage THD L2 R/W 9 9 2228
4457-58 Alarm- High Voltage THD L3 R/W 9 9 2229
4469-70 Alarm- High Current THD L1 R/W 9 9 2235
4471-72 Alarm- High Current THD L2 R/W 9 9 2236
4473-74 Alarm- High Current THD L3 R/W 9 9 2237
4475-76 Alarm- High Current THD L0 R/W 9 9 2238
4479-80 Alarm- High Current TDD L1 R/W 9 9 2240
4481-82 Alarm- High Current TDD L2 R/W 9 9 2241
4483-84 Alarm- High Current TDD L3 R/W 9 9 2242
4485-86 Alarm- High Current TDD L0 R/W 9 9 2243
4489-90 Alarm- High Current KF L1 R/W 9 9 2245
4491-92 Alarm- High Current KF L2 R/W 9 9 2246
4493-94 Alarm- High Current KF L3 R/W 9 9 2247
4495-96 Alarm- High Current KF L0 R/W 9 9 2248

4613-14 Alarm- Low Voltage L1 R/W 9 9 2307


4615-16 Alarm- Low Voltage L2 R/W 9 9 2308
4617-18 Alarm- Low Voltage L3 R/W 9 9 2309
4619-20 Alarm- Low Voltage L1-2 R/W 9 9 2310

27
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
4621-22 Alarm- Low Voltage L2-3 R/W 9 9 2311
4623-24 Alarm- Low Voltage L3-1 R/W 9 9 2312
4627-28 Alarm- Low Current L1 R/W 9 9 2314
4629-30 Alarm- Low Current L2 R/W 9 9 2315
4631-32 Alarm- Low Current L3 R/W 9 9 2316
4633-34 Alarm- Low Current L0 R/W 9 9 2317
4637-38 Alarm- Low PF L1 R/W 9 9 2319
4639-40 Alarm- Low PF L2 R/W 9 9 2320
4641-42 Alarm- Low PF L3 R/W 9 9 2321
4643-44 Alarm- Low PF (L1-2-3) R/W 9 9 2322
4653-54 Alarm- Low Voltage THD L1 R/W 9 9 2327
4655-56 Alarm- Low Voltage THD L2 R/W 9 9 2328
4657-58 Alarm- Low Voltage THD L3 R/W 9 9 2329
4669-70 Alarm- Low Current THD L1 R/W 9 9 2335
4671-72 Alarm- Low Current THD L2 R/W 9 9 2336
4673-74 Alarm- Low Current THD L3 R/W 9 9 2337
4675-76 Alarm- Low Current THD L0 R/W 9 9 2338
4679-80 Alarm- Low Current TDD L1 R/W 9 9 2340
4681-82 Alarm- Low Current TDD L2 R/W 9 9 2341
4683-84 Alarm- Low Current TDD L3 R/W 9 9 2342
4685-86 Alarm- Low Current TDD L0 R/W 9 9 2343
4689-90 Alarm- Low Current KF L1 R/W 9 9 2345
4691-92 Alarm- Low Current KF L2 R/W 9 9 2346
4693-94 Alarm- Low Current KF L3 R/W 9 9 2347

28
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
4695-96 Alarm- Low Current KF L0 R/W 9 9 2348

4813-14 Alarm- Relay High Voltage L1 R/W 9 9 2407


4815-16 Alarm- Relay High Voltage L2 R/W 9 9 2408
4817-18 Alarm- Relay High Voltage L3 R/W 9 9 2409
4819-20 Alarm- Relay High Voltage L1-2 R/W 9 9 2410
4821-22 Alarm- Relay High Voltage L2-3 R/W 9 9 2411
4823-24 Alarm- Relay High Voltage L3-1 R/W 9 9 2412
4827-28 Alarm- Relay High Current L1 R/W 9 9 2414
4829-30 Alarm- Relay High Current L2 R/W 9 9 2415
4831-32 Alarm- Relay High Current L3 R/W 9 9 2416
4833-34 Alarm- Relay High Current L0 R/W 9 9 2417
4837-38 Alarm- Relay High PF L1 R/W 9 9 2419
4839-40 Alarm- Relay High PF L2 R/W 9 9 2420
4841-42 Alarm- Relay High PF L3 R/W 9 9 2421
4843-44 Alarm- Relay High PF (L1-2-3) R/W 9 9 2422
4853-54 Alarm- Relay High Voltage THD L1 R/W 9 9 2427
4855-56 Alarm- Relay High Voltage THD L2 R/W 9 9 2428
4857-58 Alarm- Relay High Voltage THD L3 R/W 9 9 2429
4869-70 Alarm- Relay High Current THD L1 R/W 9 9 2435
4871-72 Alarm- Relay High Current THD L2 R/W 9 9 2436
4873-74 Alarm- Relay High Current THD L3 R/W 9 9 2437
4875-76 Alarm- Relay High Current THD L0 R/W 9 9 2438
4879-80 Alarm- Relay High Current TDD L1 R/W 9 9 2440

29
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
4881-82 Alarm- Relay High Current TDD L2 R/W 9 9 2441
4883-84 Alarm- Relay High Current TDD L3 R/W 9 9 2442
4885-86 Alarm- Relay High Current TDD L0 R/W 9 9 2443
4889-90 Alarm- Relay High Current KF L1 R/W 9 9 2445
4891-92 Alarm- Relay High Current KF L2 R/W 9 9 2446
4893-94 Alarm- Relay High Current KF L3 R/W 9 9 2447
4895-96 Alarm- Relay High Current KF L0 R/W 9 9 2448

5013-14 Alarm- Relay Low Voltage L1 R/W 9 9 2507


5015-16 Alarm- Relay Low Voltage L2 R/W 9 9 2508
5017-18 Alarm- Relay Low Voltage L3 R/W 9 9 2509
5019-20 Alarm- Relay Low Voltage L1-2 R/W 9 9 2510
5021-22 Alarm- Relay Low Voltage L2-3 R/W 9 9 2511
5023-24 Alarm- Relay Low Voltage L3-1 R/W 9 9 2512
5027-28 Alarm- Relay Low Current L1 R/W 9 9 2514
5029-30 Alarm- Relay Low Current L2 R/W 9 9 2515
5031-32 Alarm- Relay Low Current L3 R/W 9 9 2516
5033-34 Alarm- Relay Low Current L0 R/W 9 9 2517
5037-38 Alarm- Relay Low PF L1 R/W 9 9 2519
5039-40 Alarm- Relay Low PF L2 R/W 9 9 2520
5041-42 Alarm- Relay Low PF L3 R/W 9 9 2521
5043-44 Alarm- Relay Low PF (L1-2-3) R/W 9 9 2522
5053-54 Alarm- Relay Low Voltage THD L1 R/W 9 9 2527
5055-56 Alarm- Relay Low Voltage THD L2 R/W 9 9 2528

30
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
5057-58 Alarm- Relay Low Voltage THD L3 R/W 9 9 2529
5069-70 Alarm- Relay Low Current THD L1 R/W 9 9 2535
5071-72 Alarm- Relay Low Current THD L2 R/W 9 9 2536
5073-74 Alarm- Relay Low Current THD L3 R/W 9 9 2537
5075-76 Alarm- Relay Low Current THD L0 R/W 9 9 2538
5079-80 Alarm- Relay Low Current TDD L1 R/W 9 9 2540
5081-82 Alarm- Relay Low Current TDD L2 R/W 9 9 2541
5083-84 Alarm- Relay Low Current TDD L3 R/W 9 9 2542
5085-86 Alarm- Relay Low Current TDD L0 R/W 9 9 2543
5089-90 Alarm- Relay Low Current KF L1 R/W 9 9 2545
5091-92 Alarm- Relay Low Current KF L2 R/W 9 9 2546
5093-94 Alarm- Relay Low Current KF L3 R/W 9 9 2547
5095-96 Alarm- Relay Low Current KF L0 R/W 9 9 2548

5213-14 Alarm- T.Tbl Voltage L1 R/W 9 9 2607


5215-16 Alarm- T.Tbl Voltage L2 R/W 9 9 2608
5217-18 Alarm- T.Tbl Voltage L3 R/W 9 9 2609
5219-20 Alarm- T.Tbl Voltage L1-2 R/W 9 9 2610
5221-22 Alarm- T.Tbl Voltage L2-3 R/W 9 9 2611
5223-24 Alarm- T.Tbl Voltage L3-1 R/W 9 9 2612
5227-28 Alarm- T.Tbl Current L1 R/W 9 9 2614
5229-30 Alarm- T.Tbl Current L2 R/W 9 9 2615
5231-32 Alarm- T.Tbl Current L3 R/W 9 9 2616
5233-34 Alarm- T.Tbl Current L0 R/W 9 9 2617

31
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
5237-38 Alarm- T.Tbl PF L1 R/W 9 9 2619
5239-40 Alarm- T.Tbl PF L2 R/W 9 9 2620
5241-42 Alarm- T.Tbl PF L3 R/W 9 9 2621
5243-44 Alarm- T.Tbl PF (L1-2-3) R/W 9 9 2622
5253-54 Alarm- T.Tbl Voltage THD L1 R/W 9 9 2627
5255-56 Alarm- T.Tbl Voltage THD L2 R/W 9 9 2628
5257-58 Alarm- T.Tbl Voltage THD L3 R/W 9 9 2629
5269-70 Alarm- T.Tbl Current THD L1 R/W 9 9 2635
5271-72 Alarm- T.Tbl Current THD L2 R/W 9 9 2636
5273-74 Alarm- T.Tbl Current THD L3 R/W 9 9 2637
5275-76 Alarm- T.Tbl Current THD L0 R/W 9 9 2638
5279-80 Alarm- T.Tbl Current TDD L1 R/W 9 9 2640
5281-82 Alarm- T.Tbl Current TDD L2 R/W 9 9 2641
5283-84 Alarm- T.Tbl Current TDD L3 R/W 9 9 2642
5285-86 Alarm- T.Tbl Current TDD L0 R/W 9 9 2643
5289-90 Alarm- T.Tbl Current KF L1 R/W 9 9 2645
5291-92 Alarm- T.Tbl Current KF L2 R/W 9 9 2646
5293-94 Alarm- T.Tbl Current KF L3 R/W 9 9 2647
5295-96 Alarm- T.Tbl Current KF L0 R/W 9 9 2648

5401-2 Alarm- T.Tbl #1 R/W 9 9 2701


⇓ ⇓ ⇓ ⇓
5431-32 Alarm- T.Tbl #16 R/W 9 9 2716
32
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)

5601-2 TOU- Uruguay (Dbl) Low - From R/W 9 9 2801


5603-4 TOU- Uruguay (Dbl) Low - To R/W 9 9 2802
5605-6 TOU- Uruguay (Dbl) Low - From R/W 9 9 2803
5607-8 TOU- Uruguay (Dbl) Low - To R/W 9 9 2804
5609-10 TOU- Uruguay (Dbl) Med - From R/W 9 9 2805
5611-12 TOU- Uruguay (Dbl) Med - To R/W 9 9 2806
5613-14 TOU- Uruguay (Dbl) Med - From R/W 9 9 2807
5615-16 TOU- Uruguay (Dbl) Med - To R/W 9 9 2808
5617-18 TOU- Uruguay (Dbl) High - From R/W 9 9 2809
5619-20 TOU- Uruguay (Dbl) High - To R/W 9 9 2810
5621-22 TOU- Uruguay (Dbl) High - From R/W 9 9 2811
5623-24 TOU- Uruguay (Dbl) High - To R/W 9 9 2812
5625-26 TOU- Uruguay (Trpl) Low - From R/W 9 9 2813
5627-28 TOU- Uruguay (Trpl) Low - To R/W 9 9 2814
5629-30 TOU- Uruguay (Trpl) Low - From R/W 9 9 2815
5631-32 TOU- Uruguay (Trpl) Low - To R/W 9 9 2816
5633-34 TOU- Uruguay (Trpl) Med - From R/W 9 9 2817
5635-36 TOU- Uruguay (Trpl) Med - To R/W 9 9 2818
5637-38 TOU- Uruguay (Trpl) Med - From R/W 9 9 2819
5639-40 TOU- Uruguay (Trpl) Med - To R/W 9 9 2820
5641-42 TOU- Uruguay (Trpl) High - From R/W 9 9 2821
5643-44 TOU- Uruguay (Trpl) High - To R/W 9 9 2822
5645-46 TOU- Uruguay (Trpl) High - From R/W 9 9 2823

33
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
5647-48 TOU- Uruguay (Trpl) High - To R/W 9 9 2824

6001-2 Relay # 1 Force Start Time R/W 9 9 3001


6003-4 Relay # 1 Force Stop Time R/W 9 9 3002
6005-6 Relay # 1 Force Start Time R/W 9 9 3003
6007-8 Relay # 1 Force Stop Time R/W 9 9 3004
6009-10 Relay # 1 Force Start Time R/W 9 9 3005
6011-12 Relay # 1 Force Stop Time R/W 9 9 3006

6017-18 Relay # 2 Force Start Time R/W 9 9 3009


6019-20 Relay # 2 Force Stop Time R/W 9 9 3010
6021-22 Relay # 2 Force Start Time R/W 9 9 3011
6023-24 Relay # 2 Force Stop Time R/W 9 9 3012
6025-26 Relay # 2 Force Start Time R/W 9 9 3013
6027-28 Relay # 2 Force Stop Time R/W 9 9 3014

6033-34 Relay # 3 Force Start Time R/W 9 9 3017


6035-36 Relay # 3 Force Stop Time R/W 9 9 3018
6037-38 Relay # 3 Force Start Time R/W 9 9 3019
6039-40 Relay # 3 Force Stop Time R/W 9 9 3020
6041-42 Relay # 3 Force Start Time R/W 9 9 3021
6043-44 Relay # 3 Force Stop Time R/W 9 9 3022

6049-50 Flg To Clear SST At MidNight R/W 9 9 3025

34
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)

6061-62 Digital Out #1 (Status) R 9 9 3031


6063-64 Digital Out #2 (Status) R 9 9 3032
6065-66 Digital Out #3 (Status) R 9 9 3033
6067-68 Digital Out #4 (Status) R 9 9 3034

6101-2 TOU – January Type R/W* 9 9 9 9 9 3101


6103-4 TOU – February Type R/W* 9 9 9 9 9 3102
⇓ ⇓ ⇓ ⇓
6123-24 TOU – December Type R/W* 9 9 9 9 9 3112

6125-26 TOU – Hour Details R/W* 9 9 9 9 9 3113


⇓ ⇓ ⇓ ⇓
6655-56 TOU – Hour Details R/W* 9 9 9 9 9 3328

6799-0 Active Total Energy (KWh) R 9 9 9 9 3400


6801-2 Reactive Total Energy (KVARh) R 9 9 9 9 3401
6803-4 Apparent Total Energy (KVah) R 9 9 9 9 3402
6805-6 Active Energy Line 1 (KWh-Import) R 9 9 9 9 3403
6807-8 Active Energy Line 2 (KWh-Import) R 9 9 9 9 3404
6809-10 Active Energy Line 3 (KWh-Import) R 9 9 9 9 3405
6811-12 Reactive Energy Line 1 (KVARh-Import) R 9 9 9 9 3406
6813-14 Reactive Energy Line 2 (KVARh-Import) R 9 9 9 9 3407

35
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
6815-16 Reactive Energy Line 3 (KVARh-Import) R 9 9 9 9 3408
6817-18 Apparant Energy Line 1 (KVAh-Import) R 9 9 9 9 3409
6819-20 Apparant Energy Line 2 (KVAh-Import) R 9 9 9 9 3410
6821-22 Apparant Energy Line 3 (KVAh-Import) R 9 9 9 9 3411
6823-24 Active Energy Line 1 – Rate 1 – KWh (Imp) R 9 9 9 3412
6825-26 Active Energy Line 2 – Rate 1 – KWh (Imp) R 9 9 9 3413
6827-28 Active Energy Line 3 – Rate 1 – KWh (Imp) R 9 9 9 3414
6829-30 Active Energy Line 1 – Rate 2 – KWh (Imp) R 9 9 9 3415
6831-32 Active Energy Line 2 – Rate 2 – KWh (Imp) R 9 9 9 3416
6833-34 Active Energy Line 3 – Rate 2 – KWh (Imp) R 9 9 9 3417
6835-36 Active Energy Line 1 – Rate 3 – KWh (Imp) R 9 9 9 3418
6837-38 Active Energy Line 2 – Rate 3 – KWh (Imp) R 9 9 9 3419
6839-40 Active Energy Line 3 – Rate 3 – KWh (Imp) R 9 9 9 3420
6841-42 Active Energy Line 1+2+3 – Rate 1 – KWh (I) R 9 9 9 3421
6843-44 Active Energy Line 1+2+3 – Rate 2 – KWh (I) R 9 9 9 3422
6845-46 Active Energy Line 1+2+3 – Rate 3 – KWh (I) R 9 9 9 3423
6847-48 ReActive Energy Line 1 –Rate 1 – KVARh (Imp) R 9 9 9 3424
6849-50 ReActive Energy Line 2 –Rate 1 – KVARh (Imp) R 9 9 9 3425
6851-52 ReActive Energy Line 3 –Rate 1 – KVARh (Imp) R 9 9 9 3426
6853-54 ReActive Energy Line 1 –Rate 2 – KVARh (Imp) R 9 9 9 3427
6855-56 ReActive Energy Line 2 –Rate 2 – KVARh (Imp) R 9 9 9 3428
6857-58 ReActive Energy Line 3 –Rate 2 – KVARh (Imp) R 9 9 9 3429
6859-60 ReActive Energy Line 1 –Rate 3 – KVARh (Imp) R 9 9 9 3430
6861-62 ReActive Energy Line 2 –Rate 3 – KVARh (Imp) R 9 9 9 3431

36
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
6863-64 ReActive Energy Line 3 –Rate 3 – KVARh (Imp) R 9 9 9 3432
6865-66 ReActive E. Line 1+2+3 –Rate 1 – KVARh (I) R 9 9 9 3433
6867-68 ReActive E. Line 1+2+3 –Rate 2 – KVARh (I) R 9 9 9 3434
6869-70 ReActive E. Line 1+2+3 –Rate 3 – KVARh (I) R 9 9 9 3435

6879-80 Active Total Energy (Wh) -Meter B R 9 3440


6881-82 Reactive Total Energy (VARh) -Meter B R 9 3441
6883-84 Apparent Total Energy (Vah) -Meter B R 9 3442
6919-20 Active Energy Line 1 (W-Import) -Meter B R 9 3460
6921-22 Active Energy Line 2 (W-Import) -Meter B R 9 3461
6923-24 Active Energy Line 3 (W-Import) -Meter B R 9 3462
6925-26 Reactive Energy Line 1 (VAR-Import) -Meter B R 9 3463
6927-28 Reactive Energy Line 2 (VAR-Import) -Meter B R 9 3464
6929-30 Reactive Energy Line 3 (VAR-Import) -Meter B R 9 3465
6931-32 Apparant Energy Line 1 (VA-Import) -Meter B R 9 3466
6933-34 Apparant Energy Line 2 (VA-Import) -Meter B R 9 3467
6935-36 Apparant Energy Line 3 (VA-Import) -Meter B R 9 3468
6937-38 Active Energy Line 1 – Rate 1 (Imp) -Meter B R 9 3469
6939-40 Active Energy Line 2 – Rate 1 (Imp) -Meter B R 9 3470
6941-42 Active Energy Line 3 – Rate 1 (Imp) -Meter B R 9 3471
6943-44 Active Energy Line 1 – Rate 2 (Imp) -Meter B R 9 3472
6945-46 Active Energy Line 2 – Rate 2 (Imp) -Meter B R 9 3473
6947-48 Active Energy Line 3 – Rate 2 (Imp) -Meter B R 9 3474
6949-50 Active Energy Line 1 – Rate 3 (Imp) -Meter B R 9 3475

37
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
6951-52 Active Energy Line 2 – Rate 3 (Imp) -Meter B R 9 3476
6953-54 Active Energy Line 3 – Rate 3 (Imp) -Meter B R 9 3477

7001-2 33 Harmonics for Volts Line 1 R 9 9 3501


7003-4 34 Harmonics for Volts Line 1 R 9 9 3502

⇓ ⇓ ⇓ ⇓
7061-62 63 Harmonics for Volts Line 1 R 9 9 3531
7063-64 64 Harmonics for Volts Line 1 R 9 9 3532
7065-66 33 Harmonics for Volts Line 2 R 9 9 3533
7067-68 34 Harmonics for Volts Line 2 R 9 9 3534

⇓ ⇓ ⇓ ⇓
7125-26 63 Harmonics for Volts Line 2 R 9 9 3563
7127-28 64 Harmonics for Volts Line 2 R 9 9 3564
7129-30 33 Harmonic for Volts Line 3 R 9 9 3565
7131-32 34 Harmonics for Volts Line 3 R 9 9 3566

⇓ ⇓ ⇓ ⇓
7189-90 63 Harmonics for Vots Line 3 R 9 9 3595
7191-92 64 Harmonics for Volts Line 3 R 9 9 3596
7193-94 33 Harmonics for Current Line 1 R 9 9 3597
7195-96 34 Harmonics for Current Line 1 R 9 9 3598

⇓ ⇓ ⇓ ⇓
7253-54 63 Harmonics for Current Line 1 R 9 9 3627
38
MODBUS Field Description Type GR GRC TXT LT MC LTE LTC ITEM #
Register (UniArt\
Bacnet)
7255-56 64 Harmonics for Current Line 1 R 9 9 3628
7257-58 33 Harmonics for Current Line 2 R 9 9 3629
7259-60 34 Harmonics for Current Line 2 R 9 9 3630

⇓ ⇓ ⇓ ⇓
7317-18 63 Harmonics for Current line 2 R 9 9 3659
7319-20 64 Harmonicsfor Current Line 2 R 9 9 3660
7321-22 33 Harmonics for Current Line 3 R 9 9 3661
7323-24 34 Harmonics for Current Line 3 R 9 9 3662

⇓ ⇓ ⇓ ⇓
7381-82 63 Harmonics for Current Line 3 R 9 9 3691
7383-84 64 Harmonics for Current Line 3 R 9 9 3692

Table 1-4 Registers Table

39
1.3 — UniArt Alarms for ElNet Multimeter
The ElNet Energy & Power Multimeter is capable of working with UNIART software. When working with UNIART software user can get
specific alarms from the unit as described in Table 1-5.
Alarm # Description Phase GR LT MC PICO
1 Low Voltage (Line To N) 1 9
2 High Voltage (Line To N) 1 9
3 Low Voltage (Line To N) 2 9
4 High Voltage (Line To N) 2 9
5 Low Voltage (Line To N) 3 9
6 High Voltage (Line To N) 3 9
7 Low Voltage (Line To Line) 1-2 9
8 High Voltage (Line To Line) 1-2 9
9 Low Voltage (Line To Line) 2-3 9
10 High Voltage (Line To Line) 2-3 9
11 Low Voltage (Line To Line) 3-1 9
12 High Voltage (Line To Line) 3-1 9
13 Low Current 1 9
14 High Current 1 9
15 Low Current 2 9
16 High Current 2 9
17 Low Current 3 9
18 High Current 3 9
19 Low Current L0 (N) 9
20 High Current L0 (N) 9
21 Low Power Factor 1 9
22 High Power Factor 1 9
23 Low Power Factor 2 9
40
Alarm # Description Phase GR LT MC PICO
24 High Power Factor 2 9
25 Low Power Factor 3 9
26 High Power Factor 3 9
27 Low Power Factor 1+2+3 9
28 High Power Factor 1+2+3 9

39 High Power Period (Item 262) 1+2+3 9


40 Low Power Period (Item 263) 1+2+3 9
41 Low Voltage THD 1 9
42 High Voltage THD 1 9
43 Low Voltage THD 2 9
43 High Voltage THD 2 9
45 Low Voltage THD 3 9
46 High Voltage THD 3 9
47 Low Current THD 1 9
48 High Current THD 1 9
49 Low Current THD 2 9
50 High Current THD 2 9
51 Low Current THD 3 9
52 High Current THD 3 9
53 Low Current THD L0 (N) 9
54 High Current THD L0 (N) 9
55 Low Current TDD 1 9
56 High Current TDD 1 9
57 Low Current TDD 2 9

41
Alarm # Description Phase GR LT MC PICO
58 High Current TDD 2 9
59 Low Current TDD 3 9
60 High Current TDD 3 9
61 Low Current TDD L0 (N) 9
62 High Current TDD L0 (N) 9
63 Low Current K.Factor 1 9
64 High Current K.Factor 1 9
65 Low Current K.Factor 2 9
66 High Current K.Factor 2 9
67 Low Current K.Factor 3 9
68 High Current K.Factor 3 9
69 Low Current K.Factor L0 (N) 9
70 High Current K.Factor L0 (N) 9

81 U.Alarm – High Current 1 9


82 U.Alarm – High Current 2 9
83 U.Alarm – High Current 3 9
84 U.Alarm – High Voltage 1 9
85 U.Alarm – High Voltage 2 9
86 U.Alarm – High Voltage 3 9
87 U.Alarm – Low Voltage 1 9
88 U.Alarm – Low Voltage 2 9
89 U.Alarm – Low Voltage 3 9
90 U.Alarm – Low PF 1+2+3 9
91 U.Alarm – High V.THD 1+2+3 9

42
Alarm # Description Phase GR LT MC PICO
92 U.Alarm – High I.THD 1+2+3 9
Table 1-5 Alarm Table

43
What’s New?
24.10.2006 : Add Registers 151-157 (Time & Date)
23.01.2007 : Add PFC Registers 121-146
14.02.2007 : Add Month Energy 2001-2012
27.02.2007 : Add Export Energy 660-692
20.03.2007 : Add Reactive Energy 269-280
21.03.2007 : Add Month Energy 2001-2108
03.05.2007 : Add Registers 30-33
24.05.2007 : Add Summer Clock Registers 1921-1980
19.06.2007 : Add Current Phase Order - Registers 291-294 (LT-0.58, Txt–0.47, Gr-1.09)
09.07.2007 : Add Demo Mode - Registers 95
07.08.2007 : Add Rate Registers (59)
21.08.2007 : Add Eprom Revision (94)
07.11.2007 : Add Note About ElNet Txt Registers (System B)
09.11.2007 : Add Clock Calibration (159)
18.05.2008 : Add Alarms Parameters (2201-2700)
06.07.2008 : Add Taoz Type (Par 39)
20.08.2008 : Add Virtual Pulse & Swap Float Mode (281-284)
05.09.2008 : Add Float Format (Item 255) + Exp Total (Item 693-695)
19.09.2008 : Add Digital In (Gr) (Item 191-194)
29.10.2008 : Add Export Energy 660-692 (LT)
03.12.2008 : Add Eng Units To Some Registers
05.03.2009 : Add Period Alarm (Items 260-263)
17.03.2009 : Adjust Items 107-114
20.03.2009 : Add TOU Uruguay (Items 2801-2824)
31.03.2009 : Add Force Relay (Items 3001-3022)
01.06.2009 : Add D.Out Status (Items 3031-3034)
19.06.2009 : Add Current Demand To LT & PFC
24.06.2009 : Add Current Demand Reset (Item 117)
18.09.2009 : Add LTE Registers
23.09.2009 : Add Demand Register (Item 631-646)
16.10.2009 : Add Web Authentication (Item 198)
25.10.2009 : Add LT Reactive (Item 269-280)
05.11.2009 : Add LTE - THD Values
01.03.2010 : Add LT –Demand THD Values (2141-2157)
08.03.2010 : Add GR –KFactor (167-170)
31.05.2010 : Add MC
06.06.2010 : Add Temp Sensor (190)
22.07.2010 : Add Modbus Response Delay (290)
01.09.2010 : Add TOU Registers (3101-3328)
06.06.2010 : Add Energy in KW (3400-3435)
15.06.2010 : Add Energy in KW (3400-3411) in LTE
08.09.2011 : Add Total Q For C & L Mode (285 & 286)
12.09.2011 : Add Meter B (3440 & 3477)
10.11.2011 : Add Fast Trend Cycle (GR) (199)
23.11.2011 : Add Long Wave Events (PQ) (650-654)
10.12.2011 : Update Alarm Table