FMM-101 Monitor Module: Installation and Maintenance Instructions

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Installation And Maintenance Instructions

I56-3508-001
12 Clintonville Road
Northford, CT 06472-1653
FMM-101 Monitor Module Phone: 203.484.7161
Specifications
Nominal Operating Voltage: 15-32 VDC
Average Operating Current: 375µA maximum (group poll); 350 µA (direct poll); 600 µA Max. (Communicating, IDC Shorted)
EOL resistance: 47K Ohms
Maximum SLC Wiring Resistance: 40 Ohms
Maximum IDC Wiring Resistance: 1,500 Ohms
Maximum IDC Voltage: 11 Volts
Maximum IDC Current: 450µA
Temperature Range: 32°F to 120°F (0°C to 49°C)
Humidity: 10% to 93% Non-condensing
Dimensions: 1.3˝ H x 2.75˝ W x 0.5˝ D
Wire Length: 6˝ minimum

Before Installing Mounting and Wiring


This information is included as a quick reference installation guide. Refer to NOTE: This module is intended to be wired and mounted without rigid con-
the control panel installation manual for detailed system information. If the nections inside a standard electrical box. All wiring must conform to appli-
modules will be installed in an existing operational system, inform the opera- cable local codes, ordinances and regulations.
tor and local authority that the system will be temporarily out of service. Dis-
1. Connect the red (+) and black (–) wires to the positive and negative
connect power to the control panel before installing the modules.
loop power leads of the signaling line circuit (SLC).
NOTICE: This manual should be left with the owner/user of this equipment. 2. Connect the violet (+) and yellow (–) wires to a two-wire, normally
General Description open initiating loop.
The FMM-101 monitor module can be installed in a single gang junction box 3. Install the specified EOL resistor value to terminate the initiating loop.
directly behind the monitored unit. Its small size and light weight allow it to 4. Set the address on the module per job drawings.
be installed without rigid mounting (see Figure 1). The FMM-101 is intended
5. Install the module in the desired mounting location.
for use in intelligent, two-wire systems where the individual address of each
module is selected using rotary switches. It provides a two-wire initiating de- Figure 2. Typical 2-wire style B initiating device circuit
vice circuit for normally open contact fire alarm and security devices. This configuration:
module can be used to replace an MMX-101 module in existing systems. UL LISTED
COMPATIBLE
Compatibility Requirements CONTROL SIGNAL LINE CIRCUIT (SLC)
To ensure proper operation, this module shall be connected to a compatible PANEL
(+) TO
Notifier system control panel (list available from Notifier). NEXT
(–) DEVICE
Figure 1:
BLACK

RED

(–) (+)
67 8 9 6789 )+( )–(
ALL WIRING
5 10 5
4 11 4
3 12 3

SHOWN IS
2 13 2
1 0 15 14 10

SUPERVISED AND
POWER LIMITED
VIOLET

YELLOW

47k EOL
INCLUDED
(ELR-47k)
C0614-02

C1063-00
NO-460-012 1 I56-3508-001
©2007 Notifier