0% found this document useful (0 votes)
862 views158 pages

Panelview 800 Hmi Terminals: User Manual

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
862 views158 pages

Panelview 800 Hmi Terminals: User Manual

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 158

PanelView 800 HMI Terminals

Catalog Numbers 2711R-T4T, 2711R-T7T, 2711R-T10T

User Manual Original Instructions


PanelView 800 HMI Terminals User Manual

Important User Information


Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize
themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.

Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to
be carried out by suitably trained personnel in accordance with applicable code of practice.

If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use
or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for
actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software
described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is
prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which
may lead to personal injury or death, property damage, or economic loss.

ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.

IMPORTANT Identifies information that is critical for successful application and understanding of the product.

Labels may also be on or inside the equipment to provide specific precautions.

SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.

BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.

ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential
Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory
requirements for safe work practices and for Personal Protective Equipment (PPE).

2 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Table of Contents

Preface
About This Publication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Download Firmware, AOP, EDS, and Other Files . . . . . . . . . . . . . . . . . . . . 9
Summary of Changes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Who Should Use this Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Firmware Upgrades . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Chapter 1
Overview Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
About the Terminals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
How to Connect Browser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
USB Device Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Ethernet Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
PanelView Explorer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Peripheral Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Catalog Number Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Chapter 2
Configure the Terminal Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Configuration Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Configure Using the Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Configure Terminal Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Adjusting Settings on the Terminal. . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Main Configuration Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Goto Current Application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Select a Terminal Language. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Change the Date and Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Reboot the Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
File Manager Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Export an Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Import an Application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Change the Startup Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Copy or Edit Recipes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Copy Alarm History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Change Controller Settings for an Application. . . . . . . . . . . . . . . . . . 26
Terminal Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Change Ethernet Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Change Port Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Enable the FTP Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Adjust the Display Brightness. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Calibrate the Touch Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Changing the Display Orientation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Configure Screen Saver Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Delete Fonts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Change the Error Alert Display Settings . . . . . . . . . . . . . . . . . . . . . . . 38
Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 3
Table of Contents

Configure Print Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39


System Information Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
View System Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Change Daylight Savings Time and Timezone . . . . . . . . . . . . . . . . . . 43
Transferring Applications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

Chapter 3
DesignStation in DesignStation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Connected Components Install the Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Uninstall the Software. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Workbench Software
Launch Mechanism . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Configure Key Repeat Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Creating Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Downloading Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Uploading Applications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Create Recipes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Add Ingredients to a Recipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Delete Ingredients from a Recipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Download Recipes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Configure FTP Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Configure Email Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Configure the Alarm Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Change Application Font . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Add Fonts to the Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Add Screen Savers to the Terminal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Trend and Datalog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Alarm List Filter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Import Tags From a Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Import Tags From a CompactLogix Controller. . . . . . . . . . . . . . . . . . 67
Import Tags From a Micro800 Controller . . . . . . . . . . . . . . . . . . . . . . 69
Assign Tags From a CompactLogix 5370 Controller . . . . . . . . . . . . . . . . . 70
Export and Import a Language List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Export a Language List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Import a Language List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Update Tag Name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Animation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Time Entry Data Type Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
View List of Objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75

Chapter 4
Secure the Terminal Securing Your Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Set Terminal Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Change Terminal Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Clear Terminal Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Secure Design Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Manage User Accounts Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Add Users . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Managing Users . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Assign Design Rights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
4 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021
Table of Contents

Create Access Rights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83


Managing Rights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Assign Rights to a Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Changing Terminal Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Security at Runtime . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Idle Mode Timeout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Resetting the Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Starting the Terminal in Safe Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Protected Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87

Chapter 5
Virtual Network Computing Virtual Network Computing (VNC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Guidelines for Using VNC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Recommended VNC Clients and Settings . . . . . . . . . . . . . . . . . . . . . . . . . 89
Configure VNC Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Set the Password for VNC Connection . . . . . . . . . . . . . . . . . . . . . . . . . 92
Establish VNC Connection to the Terminal . . . . . . . . . . . . . . . . . . . . . . . . 93

Chapter 6
Troubleshoot the System Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
View System Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Alerts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Check for Adequate Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Observe Splash Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Interpret the LED Indicators at Startup. . . . . . . . . . . . . . . . . . . . . . . 103
Returning to the Out-of-box Condition . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Restoring the Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104

Appendix A
Specifications General Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Certifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108

Appendix B
Upgrade Firmware Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Prepare for Firmware Upgrade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Upgrading Firmware Using ControlFLASH . . . . . . . . . . . . . . . . . . . . . . . . 111
Firmware Installation Using Removable Storage Device . . . . . . . . . . . 115
Prepare the Storage Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Install the Firmware from the Storage Device . . . . . . . . . . . . . . . . . 116

Appendix C
Install and Replace Components Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
microSD Memory Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
USB Flash Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Battery Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 5


Table of Contents

Appendix D
Cable Connections and Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Communication Wiring and Safety Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Connecting Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
MicroLogix Controller Cable Charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Micro800 Controller Cable Charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
CompactLogix 5370 Controller Cable Charts . . . . . . . . . . . . . . . . . . . . . . 125
Ethernet Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Ethernet Connector. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Security Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Serial Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
RS-422/RS-485 Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
USB Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
USB Host Port. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128

Appendix E
Using PanelView 800 Terminals Add a CompactLogix 5370 Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
with CompactLogix 5370 Map the Terminal and Controller Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Validate the Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Controllers
Download the Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Upload the Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
CompactLogix 5370 Controller Addressing . . . . . . . . . . . . . . . . . . . . . . . 133
Addressing Formats from PanelView 800 Terminals to
CompactLogix 5370 Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Limitations with CompactLogix 5370 Controller Support . . . . . . . . . . 135

Appendix F
PanelView Explorer Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Configuration Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Configure Using the Browser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Terminal Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Adjusting Settings on the PanelView Explorer Startup Window . 139
Select a Terminal Language. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Adjust the Display Brightness. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Configure the Screen Saver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Replace the Screen Saver Image. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Configure Key Repeat Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Calibrate the Touch Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Reboot the Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
Change the Startup Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
Change the Date and Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
Enable Terminal Security. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
View System Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150

6 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Table of Contents

Managing Applications and Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150


Adding Font Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Import a Font File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Remove a Font File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152

Index

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 7


Table of Contents

Notes:

8 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Preface

About This Publication This manual provides information for configuring the PanelView™ 800
terminal. You can configure the terminal, through a web browser(a) on a
computer connected to the terminal, or through Connected Components
Workbench™ software. This manual also provides information on how to
troubleshoot the PanelView 800 terminal.

Topic Page
Summary of Changes 9
Who Should Use this Manual 9
Firmware Upgrades 10
Additional Resources 10

Download Firmware, AOP, Download firmware, associated files (such as AOP, EDS, and DTM), and access
EDS, and Other Files product release notes from the Product Compatibility and Download Center at
rok.auto/pcdc.

Summary of Changes This publication contains the following new or updated information. This list
includes substantive updates only and is not intended to reflect all changes.

Topic Page
Updated template throughout
Updated information on the supported operating systems 46
Updated section Downloading Applications 53
Added section Import Tags From a Controller 67
Added section Assign Tags From a CompactLogix 5370 Controller 70
Added section Export and Import a Language List 70
Added section Update Tag Names 72
Added section Animation Configuration 73
Added section Time Entry Data Type Support 74
Added section View List of Objects 75
Updated section Manage User Account Settings 80

Who Should Use this Manual Use this manual if you are responsible for configuring, operating, or
troubleshooting the PanelView 800 terminals.

No special knowledge is required to understand this manual or operate the


terminal.

Equipment installers must be familiar with standard panel installation


techniques.

(a) The web browser feature is not supported on PanelView 800 terminals from firmware
revision 3.011 onwards.
Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 9
Firmware Upgrades To receive firmware upgrades and other downloads for your PanelView 800
terminal:
• Contact your local Allen-Bradley distributor or sales representative.
• Go to the Rockwell Automation Product Compatibility and Download
Center at rok.auto/pcdc.

IMPORTANT You must sign in to the Rockwell Automation website before downloading
a firmware revision.

Additional Resources These documents contain additional information concerning related products
from Rockwell Automation.

Resource Description
PanelView 800 HMI Terminals Installation Instructions, publication 2711R-IN001 Provides instructions for installing a PanelView 800 terminal.
Describes how to configure and use EtherNet/IP™ devices to communicate on the EtherNet/IP
EtherNet/IP Network Devices User Manual, ENET-UM006 network.
Ethernet Reference Manual, ENET-RM002 Describes basic Ethernet concepts, infrastructure components, and infrastructure features.
Provides guidance on how to conduct security assessments, implement Rockwell Automation
System Security Design Guidelines Reference Manual, SECURE-RM001 products in a secure system, harden the control system, manage user access, and dispose of
equipment.
Industrial Components Preventive Maintenance, Enclosures, and Contact Ratings Provides a quick reference tool for Allen-Bradley® industrial automation controls and
Specifications, publication IC-TD002 assemblies.
Designed to harmonize with NEMA Standards Publication No. ICS 1.1-1987 and provides general
Safety Guidelines for the Application, Installation, and Maintenance of Solid-state guidelines for the application, installation, and maintenance of solid-state control in the form of
Control, publication SGI-1.1 individual devices or packaged assemblies incorporating solid-state components.
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, rok.auto/certifications. Provides declarations of conformity, certificates, and other certification details.

You can view or download publications at rok.auto/literature.

10 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 1

Overview

Chapter Objectives This chapter gives an overview of the PanelView 800 terminals.
• About the terminals
• How to connect browser(a)
• PanelView Explorer(b)
• How to display help
• Peripheral connection
• Catalog number configuration

About the Terminals PanelView 800 terminals are operator interface devices for monitoring and
controlling devices attached to a controller. HMI applications are created
using Connected Components Workbench software, then downloaded to the
terminal.

PanelView 800 Terminal – 2711R-T4T

12
5

1 2 10 11

9
6 7 6

PanelView terminal 2711R-T4T Description


Item Description Item Description
1 Power status LED(1) 7 10/100 Mb Ethernet port
2 Touch display, function keys 8 RS-232 port
3 24V DC power input 9 RS-422 and RS-485 port

(a) The web browser feature is not supported on PanelView 800 terminals from firmware
revision 3.011 onwards.
(b) The PanelView Explorer feature is not supported on PanelView 800 terminals from firmware
revision 3.011 onwards.
Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 11
Chapter 1 Overview

PanelView terminal 2711R-T4T Description (Continued)


Item Description Item Description
4 USB device port(2) 10 USB host port
5 microSD™ (Secure Digital) card slot 11 Diagnostic status indicator
6 Mounting slots 12 Replaceable real-time clock battery
(1) The Power Status LED is red when in screen saver or dimmer mode and green when in normal (operational) mode.
(2) The USB device port is not intended for Customer use.

PanelView 800 Terminals – 2711R-T7T

1 2 9

11

3 4 5 6 3
12
10

PanelView 800 Terminals 2711R-T7T Description


Item Description Item Description
1 Power status LED(1) 7 Replaceable real-time clock battery
2 Touch display 8 USB host port
3 Mounting slots 9 Diagnostic status indicator
4 RS-422 and RS-485 port 10 microSD (Secure Digital) card slot
5 RS-232 port 11 24V DC power input
6 10/100 Mb Ethernet port 12 USB device port(2)
(1) The Power Status LED is red when in screen saver or dimmer mode and green when in normal (operational) mode.
(2) The USB device port is not intended for Customer use.

12 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 1 Overview

PanelView 800 Terminal – 2711R-T10T

7
10

1 2 8 9

3 4 5 6 3
11

12

IMPORTANT Analog touch screens are intended for single presses at a time. If the
touch screen is pressed in two locations at the same time, the presses are
averaged as a single press in-between the two locations

PanelView 800 Terminal 2711R-T10T Description


Item Description Item Description
1 Power status LED(1) 7 Replaceable real-time clock battery
2 Touch display 8 USB host port
3 Mounting slots 9 Diagnostic status indicator
4 RS-422 and RS-485 port 10 microSD (Secure Digital) card slot
5 RS-232 port 11 24V DC power input
6 10/100 Mb Ethernet port 12 USB device port(2)
(1) The Power Status LED is red when in screen saver or dimmer mode and green when in normal (operational) mode.
(2) The USB device port is not intended for Customer use.

How to Connect Browser The terminals can be connected to a browser using an Ethernet network
connection. You must enter the IP address of the PanelView 800 terminal into
the address field of your browser. You can find the IP address on the terminal
configuration screen under Communications.

IMPORTANT The web browser feature is only supported on PanelView 800 terminals
with firmware revision 2.020 or earlier. It is not supported from
firmware revision 3.011 onwards.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 13


Chapter 1 Overview

USB Device Port

The PanelView 800 terminals have a USB device port to support


communication with the terminal using TCP/IP.

IMPORTANT The USB device port is for maintenance only and is not intended for normal
runtime operation.
The USB device port is not intended for Customer use.

Ethernet Port
The PanelView 800 terminals have an Ethernet port. The Ethernet port
supports both static IP addresses and Dynamic Host Configuration Protocol
(DHCP) assigned IP addresses. If using static IP addressing, then you
manually set the IP address, the subnet mask, and the default gateway. If using
DHCP, then the server automatically assigns an IP address, the subnet mask,
the default gateway, and the DNS and WINS server.

IMPORTANT If a terminal is set for DHCP and is not on a network or is on a network that
does not have a DHCP server (or the server is not available), it will
automatically assign itself an Automatic Private IP address (or auto IP
address). The auto IP address is in the range of 169.254.0.0 through
169.254.255.255.
The terminal makes sure the auto IP address is unique from any other auto
IP address of other devices on the network. The terminal can now
communicate with other devices on the network that have IP addresses in
the 169.254.xxx.xxx range (and a subnet mask of 255.255.0.0).

PanelView Explorer PanelView Explorer is the browser interface for interacting with PanelView
800 terminals. Through this interface you can configure the terminal settings,
transfer files, test, and run applications. See Appendix F for more information
on using PanelView Explorer.

IMPORTANT The PanelView Explorer feature is only supported on PanelView 800


terminals with firmware revision 2.020 or earlier. It is not supported from
firmware revision 3.011 onwards.

Peripheral Connection PanelView 800 terminals have a USB host port. You can power USB
peripherals directly from the PanelView 800 terminal. If the USB peripheral is
not powered directly from the PanelView USB port either:
• install the USB peripheral in the same enclosure as the PanelView
terminal and make sure it is connected to the same ground system.
• connect to the USB peripheral through a galvanically isolated hub.

WARNING: If you connect or disconnect the communications cable with power


applied to this module or any device on the network, an electrical arc can occur.
This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.

14 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 1 Overview

WARNING: If you connect or disconnect the USB cable with power applied to
this module or any device on the USB network, an electrical arc can occur. This
could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.

ATTENTION: Removing the USB flash drive or microSD card, from the
PanelView 800 terminal, while a firmware upgrade is in process, could
corrupt the firmware and make the terminal unusable. Take precautions to
prevent the USB flash drive or microSD card from being accidentally
disconnected. Also, do not power off the terminal while a firmware upgrade is
in progress.
USB hubs can produce unexpected behaviors and as a result are not
recommended.

Catalog Number These are the available PanelView 800 terminals.


Configuration
Cat. No. Operator Input Size Display Type
2711R-T4T Touch screen and function keys 4 in. Color TFT
2711R-T7T Touch screen 7 in. Color TFT
2711R-T10T Touch screen 10 in. Color TFT

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 15


Chapter 1 Overview

Notes:

16 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 2

Configure the Terminal

Chapter Objectives This chapter covers topics that show how to configure your PanelView 800
terminal.
• Configuration interfaces
• Terminal settings
• Managing applications and files
• Creating applications
• Upload and Download applications
• Transferring applications
• Transferring user-defined objects

Configuration Interfaces The terminal can be configured from either the browser interface(a) or the
configuration screens on the terminal. The browser interface requires a
computer browser connected to the terminal's web service through an
Ethernet network connection. The configuration data for a terminal refers to
the collection of all of the system interface parameters.

Access to the Terminal’s Configuration

Running
Internet Explorer or
Firefox browser

Ethernet
connectivity

On Terminal
Configuration

(a) The web browser feature is not supported on PanelView 800 terminals from firmware
revision 3.011 onwards. For more information about the PanelView Explorer feature, see
Appendix F.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 17


Chapter 2 Configure the Terminal

Configure Using the Terminal

The on-terminal interface lets you make changes to the terminal settings. The
menu is displayed on the left side of the terminal screen. Changes can be made
whether an application is running or not running.

Terminal Interface Main Menu

Main
Current Application
File Manager Goto

Config Language Date and Time


English Day Hour
Português 14 10
Terminal Setting
Français
Italiano Month Minute
Deutsch
1 30
Español
简体中文 Year Second
System Information
Reset Terminal 2015 56

Configure Terminal Settings Terminal settings can be configured either through the PanelView Explorer
browser(a) interface or through the on-terminal interface.

Adjusting Settings on the Terminal

From the terminal, you can view and edit the terminal settings. Most settings
take effect immediately.

By clicking the menu items on the screen, you can:


• change the terminal language.
• change the current date and time.
• reboot or reset the terminal.
• import or export an application.
• change the startup application.
• copy or edit recipes of an application.
• copy the alarm history of an application.
• change the controller settings for an application.
• change Ethernet network settings.
• change Virtual Network Computing (VNC) settings.
• change communication port settings.
• change the FTP server settings.

(a) The PanelView Explorer feature is not supported on PanelView 800 terminals from firmware
revision 3.011 onwards. For more information about the PanelView Explorer feature, see
Appendix F.

18 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 2 Configure the Terminal

• adjust the display brightness.


• calibrate the touch screen, if supported.
• change the display orientation.
• configure screen saver settings.
• delete fonts from the terminal.
• change the error alert display settings.
• configure print settings.
• view system information.

Main Configuration Settings You can perform the following actions on the main configuration screen:
• Goto Current Application
• Select a Terminal Language
• Change the Date and Time
• Reboot the Terminal

Main
Current Application
File Manager Goto

Config Language Date and Time


English Day Hour
Português 14 10
Terminal Setting
Français
Italiano Month Minute
Deutsch
1 30
Español
简体中文 Year Second
System Information
Reset Terminal 2015 56

Goto Current Application

The current application field displays the name of the application that is
currently running on the terminal. You can press the Goto button to switch to
that application. If no application is running, the field is empty.

Select a Terminal Language

You can change the terminal display language. The terminal is shipped with
English, Portuguese, French, Italian, German, Spanish, and Chinese fonts
installed. Korean is supported but you must first install the Korean font. See
Add Fonts to the Terminal on page 63 for information on how to install the font
onto the terminal.

IMPORTANT At runtime, diagnostic messages appear in the same language as the


application if the application language is English, Portuguese, French,
Italian, German, Spanish, Chinese, or Korean. For all other languages, the
diagnostic messages appear in the configuration language set on the
terminal.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 19


Chapter 2 Configure the Terminal

Follow these steps to change the terminal language from the terminal.
1. Go to the main configuration screen.
2. To select the language, use the up and down arrow keys.
The change takes effect immediately.

Change the Date and Time

You can adjust the current date and time for terminal operations. The time is
set in 24-hour format. If using PanelView Explorer, you can also set the
terminal to automatically adjust the time for daylight savings time.

Follow these steps to change the terminal date and time from the terminal.
1. Go to the main configuration screen.
2. Click the number next to what you want to change under the 'Date and
Time' section.
A numeric keypad is displayed.
3. Select the numbers that you want and press the Enter key.

14 Main
Current Application
File Manager 7 8 9 Goto

4Config Language
5 6 Date and Time
Terminal Setting
1
English
Português 2 3 Day
14
Hour
10
Français
Italiano
Deutsch
0 - Month Minute
Esc
Español
简体中文
1 30

Year Second
System Information
Reset Terminal 2015 56

Reboot the Terminal

You can restart the terminal without having to disconnect and reapply power.
After a reset, the terminal performs series of startup tests and then either
enters configuration mode or runs the startup application.

Follow these steps to reboot the terminal from the terminal.


1. Go to the main configuration screen.
2. Press Reset Terminal.
3. Press Yes to confirm.

20 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 2 Configure the Terminal

File Manager Settings On the main configuration screen, press File Manager to go to the File
Manager screen.

File Manager
Source: To:

Internal Internal Copy

Delete
PV800_App1
PVcApplication1 Set As Startup

Run

Stop Application
Recipe Copy Alarm History Controller Settings
Startup Application
Reset Main

IMPORTANT The Stop Application button is only available in firmware revision


3.011 onwards.

IMPORTANT The Controller Settings button is only available in firmware revision


4.011 onwards.

You can perform the following actions under File Manager settings:
• Export an Application
• Import an Application
• Change the Startup Application
• Copy or Edit Recipes
• Copy Alarm History
• Change Controller Settings for an Application

Export an Application

During an export, the application file is transferred from internal storage of


the terminal to a USB flash drive or microSD card. The application is saved
with its default name and “.cha” file type.

Follow these steps to export an application from the terminal.


1. Go to the File Manager screen.
2. Select Internal as the Source location of the application.
3. Select the location to copy the application from the To list, either USB or
microSD card.
4. Select the name of the application from the Name list.
5. Press Copy.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 21


Chapter 2 Configure the Terminal

Import an Application

During an import, the application file (.cha) is transferred from a USB flash
drive or microSD card to the internal storage of the terminal. The transfer
operation communicates with the terminal to import the file.

You cannot overwrite an application while the application is running. You


must unload the current application before overwriting the application. You
can import applications while another is running.

Follow these steps to import an application from the terminal.


1. Go to the File Manager screen.
2. Select the source location of the application from the Source list, either
USB or microSD card.
3. Select Internal as the To location to copy the application.
4. Select the name of the application from the Name list.
5. Press Copy.

The application is transferred to the internal storage of the terminal.

If an application with the same name exists in internal storage, you are asked
if you want to replace the existing application.

Change the Startup Application

You can select or change the application that runs on the terminal each time
the terminal starts up. Only applications in the internal storage of the terminal
can be run or set as a Startup Application.

IMPORTANT If the application list is empty, the run, copy, delete, and set as startup
functions will not perform any action.

Follow these steps to select or change the startup application from the
terminal.
1. Go to the File Manager screen.
2. Select Internal from the Source list.
3. Select the name of the startup application from the Name list.
4. Click Set As Startup.

Copy or Edit Recipes


You can copy recipes from a USB device or microSD card to an application on
the terminal, or from the terminal to a USB device or microSD card. You can
also edit the name of a recipe in an application, or delete the recipe from an
application.

IMPORTANT To perform a copy or edit operation on a recipe of an application, that


application must be unloaded or not running.

22 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 2 Configure the Terminal

You cannot perform these actions on a password protected application.

Copy a Recipe

Follow these steps to copy a recipe.


1. Go to the File Manager screen.
2. Select the application that you want to copy the recipe, then press Recipe.

Recipe

Copy Recipe Edit Recipe

Back

3. Press Copy Recipe.

Copy Recipe
Copy From PV800_App1
To: USB Recipe1
Recipe2
Copy
Recipe3

Copy To PV800_App1
From: SD Recipe5
Recipe6
Copy
Recipe7

Back

4. Select the location where you want to copy the recipe from, or copy the
recipe to.
5. Select the recipe from the recipe list.
6. Press Copy.

IMPORTANT Copying out a recipe from a design secured application is not allowed.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 23


Chapter 2 Configure the Terminal

Edit a Recipe

Follow these steps to rename or delete a recipe.


1. Go to the File Manager screen.
2. Select the application that you want to edit the recipe, then press Recipe.

Recipe

Copy Recipe Edit Recipe

Back

3. Press Edit Recipe.

Edit Recipe
Application Name: PV800_App1

Recipe1
Recipe2
Recipe3
Recipe5 Delete

Name: Recipe1

Back

The name of the currently loaded application is displayed, as well as a list


of the recipes for that application.
4. Select the recipe from the recipe list.
5. Press Delete if you wish to delete the recipe, then press OK to confirm.

IMPORTANT Renaming of a recipe in a design secured application is not allowed.


6. Press the blue area next to Name to change the name of the recipe.

IMPORTANT Deletion of a recipe in a design secured application is not allowed.


7. Type in the desired name using the on-screen keypad, then press Enter.

24 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 2 Configure the Terminal

Recipe4 Edit Recipe


Esc F1 F2Name:
Application F3 PV800_App1
F4 F5 F6 F7 F8 F9 F10 F11 F12 Home End

1 2
`Recipe1 3 4 5 6 7 8 9 0 - =
q w
Recipe2 e r t y u i o p [ ] \
Recipe3
Caps a s d f g h j k l ; ’
Recipe4 Delete
Shift z x c v b n m , . /
Ctrl Win Alt ins del
Name: Recipe1

Back

8. The recipe name is changed and the recipe list is automatically resorted
alphanumerically.

Edit Recipe
Application Name: PV800_App1

Recipe2
Recipe3
Recipe4
Recipe5 Delete

Name: Recipe4

Back

Copy Alarm History

You can copy the alarm history of an application on the terminal into a USB or
microSD card.

Follow these steps to copy the alarm history.


1. Go to the File Manager screen.
2. Use the up and down arrow keys to select the application that you want to
copy the alarm history from.
3. Press Copy Alarm History.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 25


Chapter 2 Configure the Terminal

Copy Alarm History

From: PV800_App1

To: USB

Copy

Back

4. Select the location to copy the alarm history from the To list, either USB
or microSD card.
5. Press Copy.

Change Controller Settings for an Application

You can change the network address or node address of the controller in your
application using the terminal. This feature is available in firmware revision
4.011 onwards.

Follow these steps to change the network address or node address of the
controller for your application from the terminal.
1. Go to the File Manager screen.
2. Press Controller Settings.

Controller Settings
Application Name: PV800_App1

Protocol: Ethernet | Allen-Bradley MicroLogix/ENI


PLC-1 : 10.116.37.12

Type: MicroLogix 1400

Address: 10.116.37.12
Back

3. Press the blue area next to Address to change the address.

26 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 2 Configure the Terminal

Type in the desired IP address using the on-screen keypad, then press
Enter.

10.116.37.12 Controller Settings


Application
Esc F1 Name:
F2 F3 PV800_App1
F4 F5 F6 F7 F8 F9 F10 F11 F12 Home End

`
Protocol: 1 2 4 5| Allen-Bradley
3 Ethernet 6 7 MicroLogix/ENI
8 9 0 - =
q w
PLC-1 : 10.116.37.12 e r t y u i o p [ ] \
Caps a s d f g h j k l ; ’
Shift z x c v b n m , . /
Type: MicroLogix 1400
Ctrl Win Alt ins del

Address: 10.116.37.12
Back

IMPORTANT You cannot change the controller setting for an application that
is running.

Terminal Settings On the main configuration screen, press Terminal Settings to go to the
Terminal Settings screen.

Terminal Setting

Communication

Display

Error Alert Display Settings

Print Settings
Main

You can perform the following actions under Terminal Settings:


• Change Ethernet Settings
• Configure VNC Settings (see Configure VNC Settings on page 90)
• Change Port Settings
• Enable the FTP Server
• Adjust the Display Brightness
• Calibrate the Touch Screen
• Changing the Display Orientation
• Configure Screen Saver Settings
• Delete Fonts
• Change the Error Alert Display Settings
• Configure Print Settings

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 27


Chapter 2 Configure the Terminal

Change Ethernet Settings

You can establish an Ethernet connection between the connected PanelView


800 terminal and computer using the Ethernet port on the terminal.
You cannot change the Ethernet settings from PanelView Explorer. If you want to
change this setting, you must do so from the terminal configuration screens.

For the Ethernet port, IP addresses can be set dynamically by the network if
Dynamic Host Configuration Protocol (DHCP) is enabled. If DHCP is disabled,
the IP addresses must be entered manually.

IMPORTANT If a terminal is set for DHCP and is not on a network or is on a network that
does not have a DHCP server (or the server is not available), it will
automatically assign itself an Automatic Private IP address (or auto IP
address). The auto IP address is in the range of
169.254.0.0…169.254.255.255.
The terminal makes sure that the auto IP address is unique from any other
auto IP address of other devices on the network. The terminal can now
communicate with other devices on the network that have IP addresses in
the 169.254.xxx.xxx range (and a subnet mask of 255.255.0.0).

Ethernet Settings
Parameter Description
Read-only field that defines the MAC ID of the PanelView 800 terminal. Each
Ethernet device has a unique MAC ID.
MAC ID The MAC ID is shown in PanelView Explorer, and the Communication terminal
screen from firmware revision 4.011 onwards.
Network Device Name Unique name that identifies the terminal on the network.
Unique address that identifies the terminal on the Ethernet network.
The format of the IP address is xxx.xxx.xxx.xxx, for example, 10.90.95.30 The
IP address range of values for the first set of decimal numbers is 1…255 unless all fields
are set to 000. The range of values for the last three sets of decimal numbers
is 0…255.
Address that must be identical to the server subnet mask. The subnet mask
Subnet Mask is formatted like the IP address.
Default Gateway Optional address that is formatted like the IP address.

If DHCP is enabled for the Ethernet port, the current fields show the IP
addresses assigned by the network. You can assign IP addresses manually by
disabling DHCP and entering addresses in the static fields.

IMPORTANT If the Ethernet port is disabled, you cannot set a static IP address for the
terminal. The terminal prompts an alert (ID: 2058) when you try to do so.

Follow these steps to set a static IP address for the terminal’s Ethernet port
from the terminal.
1. Go to the Terminal Settings screen.

28 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 2 Configure the Terminal

2. Press Communication.

Communication
Protocol: * Disable DHCP
Status: Unavailable
Device Name: PV800T7T Set Static IP Address

Node Address: 0 VNC Settings


IP Mode: DHCP
Port Settings
IP Address: 0.0.0.0
Mask: 0.0.0.0 FTP Settings
Gateway: 0.0.0.0
MAC Address: XX:XX:XX:XX:XX Back

IMPORTANT The MAC address value display is only available in firmware


revision 3.011 onwards.
3. Press Disable DHCP.
The IP Mode now displays the text "Static".
4. Press Set Static IP address screen appears.

Static IP Address

IP Address: 0.0.0.0

Mask: 0.0.0.0

Gateway: 0.0.0.0

Back

5. Press the blue area next to IP address to enter an IP address in the Static
IP address field.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 29


Chapter 2 Configure the Terminal

Type in the desired IP address using the on-screen keypad, then press
Enter.

Static IP Address
169.254.158.177
Esc F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11 F12 Home End

` 1 2 Address:
IP 3 4 5 6 8 9
70.0.0.0 0 - =
q w e r t y u i o p [ ] \
Mask:
Caps a s d f g h j 0.0.0.0
k l ; ’
Shift z x c v b n m , . /
Gateway: 0.0.0.0
Ctrl Win Alt ins del

Back

6. Repeat step 5 to enter the address for the Subnet Mask and Gateway
Address.

Change Port Settings

You can control access to the terminal through Ethernet or Serial


communication by enabling or disabling the respective port.

Follow these steps to enable or disable the communication port on the


terminal.
1. Go to the Terminal Settings screen.
2. Press Communication.

Communication
Protocol: * Disable DHCP
Status: Unavailable
Device Name: PV800T7T Set Static IP Address

Node Address: 0 VNC Settings


IP Mode: DHCP
Port Settings
IP Address: 0.0.0.0
Mask: 0.0.0.0 FTP Settings
Gateway: 0.0.0.0
MAC Address: XX:XX:XX:XX:XX Back

30 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 2 Configure the Terminal

3. Press Port Settings.

Port Settings

Ethernet: Enable

Serial: Enable

Back

4. The Ethernet and Serial ports are enabled by default. Press Enable for the
respective port to disable it, then press OK to confirm.

IMPORTANT From firmware revision 5.011 onwards, the port settings can only be
enabled or disabled when no application is running on the terminal.

IMPORTANT If the Ethernet port is disabled, you cannot set a static IP address for the
terminal. The terminal prompts an alert (ID: 2058) when you try to do so.

IMPORTANT If the Ethernet port is disabled, the IP address, Mask, and Gateway
settings display a “*”.

Communication
Protocol: * Disable DHCP
Status: Unavailable
Device Name: PV800T7T Set Static IP Address

Node Address: 0 VNC Settings


IP Mode:
Port Settings
IP Address: *
Mask: * FTP Settings
Gateway: *
MAC Address: XX:XX:XX:XX:XX Back

Enable the FTP Server

You can connect to a PanelView 800 terminal using an FTP (File Transfer
Protocol) client such as a web browser, PC file explorer, or third-party FTP
software. This gives you read-only access to the Alarm History, Datalog, and
Recipe folders on the terminal. To access the contents of these folders,
permissions must be configured in Connected Components Workbench
software. See Configure FTP Settings on page 57.
The Alarm History folder contains only the alarm history of the current running
application on the terminal.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 31


Chapter 2 Configure the Terminal

After you have established an FTP connection to the terminal, you can copy the
contents of the folders out from the terminal to your PC. The FTP server on the
terminal is disabled by default.

IMPORTANT The terminal supports only one FTP connection. If another connection is
attempted, it is rejected and no notification is given. The behavior varies
from one FTP client to another.

IMPORTANT An FTP connection cannot be established while the terminal is loading


an application. Wait until the application has finished loading before
connecting to the terminal.

IMPORTANT It is recommended to download files from the terminal one at a time.


Also, set the connection inactivity timeout for your FTP client to 60
seconds or longer to avoid unsuccessful file download.

IMPORTANT The FTP server feature is not available for CompactLogix™ 5370
controllers.

Follow these steps to enable the FTP server.


1. Go to the Terminal Settings screen.
2. Press Communication.

Communication
Protocol: * Disable DHCP
Status: Unavailable
Device Name: PV800T7T Set Static IP Address

Node Address: 0 VNC Settings


IP Mode: DHCP
Port Settings
IP Address: 0.0.0.0
Mask: 0.0.0.0 FTP Settings
Gateway: 0.0.0.0
MAC Address: XX:XX:XX:XX:XX Back

3. Press FTP Settings.

FTP Settings

FTP Server: Enable / Disable

Status: Disabled

Back

4. Press Enable/Disable to enable the FTP server.


The Status now displays the text “Enabled”.

32 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 2 Configure the Terminal

Adjust the Display Brightness

You can modify the brightness of the terminal display. You can use the default
intensity of 100% for brightness or adjust the intensity for runtime operations.

Follow these steps to change the display brightness from the terminal.
1. Go to the Terminal Settings screen.
2. Press Display.

Display
Brightness 100

Calibrate Touchscreen

Orientation (Requires Reset) 0 degrees

Screen Saver

Font

Back

3. Use the arrow keys to adjust the brightness up or down.

The change takes effect immediately.

Calibrate the Touch Screen

Over time you may notice that an object on the screen does not respond when
touched, or the activation spot of the object is not correct. This is normal with a
touch screen and can be easily fixed.
You cannot calibrate the touch screen using VNC or with a mouse. If you have
triggered the calibration process, you can press the “ESC” key on the keyboard to
cancel the procedure.

Follow these steps to calibrate the touch screen from the terminal.
1. Go to the Terminal Settings screen.
2. Press Display.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 33


Chapter 2 Configure the Terminal

3. Press Calibrate touch screen.

Display
Brightness 100

Calibrate Touchscreen

Orientation (Requires Reset) 0 degrees

Screen Saver

Font

Back

Follow these steps to complete the calibrate touch screen procedure. This
process must be done by physically touching the screen. Use a plastic stylus
device with a minimum tip radius of 1 mm (0.040 in.) to prevent damage to the
touch screen.
1. With a stylus, tap the center of the target (+) on the terminal screen.

2. Repeat step 1 as the target moves around the screen.

34 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 2 Configure the Terminal

3. Tap OK when the message appears to accept the changes.


If you do not tap the screen within 30 seconds, the calibration data is
discarded and the current settings are retained.

OK ? : 30 sec

Changing the Display Orientation

You can change the display orientation of the terminal between landscape and
portrait mode.
You cannot change the display orientation from PanelView Explorer. If you want to
change this setting, you must do so from the terminal configuration screens.

Follow these steps to change the display orientation from the terminal.
1. Go to the Terminal Settings screen.
2. Press Display.

Display
Brightness 100

Calibrate Touchscreen

Orientation (Requires Reset) 0 degrees

Screen Saver

Font

Back

3. Select the degree of orientation (0 – Landscape, 90 – Reverse portrait, or


270 – Portrait).
4. Press Back to return to the main configuration screen.
5. Press Reset Terminal, then press Yes to confirm.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 35


Chapter 2 Configure the Terminal

Configure Screen Saver Settings

You can enable or disable the screen saver on the PanelView 800 terminal. To
add a screen saver to the terminal, see Add Screen Savers to the Terminal on
page 64. The terminal supports up to 25 screen savers.

The terminal has four screen saver modes: image, dimmer, image and
dimmer, or disable.
• Image – activates after the idle timeout elapses using the selected screen
saver image. The screen saver deactivates when you touch the screen.
• Dimmer – dims the display from full brightness to the brightness level
you set when the idle timeout elapses. While the display is dimmed, you
can still see on-screen activity. When you touch the screen, the display is
restored to full brightness.
• Image and dimmer – activates the screen saver and dims the display
when the idle timeout elapses.
• Disable screen saver and dimmer – keeps the display on.

The screen saver timeout is the amount of idle time that must elapse before the
screen saver, dimmer, or screen saver and dimmer activates. The idle time can
be adjusted between 1…60 minutes.

The brightness intensity of the screen saver or dimmer can be adjusted


between 0…100%.

Follow these steps to configure the screen saver from the terminal.
1. Go to the Terminal Settings screen.
2. Press Display.

Display
Brightness 100

Calibrate Touchscreen

Orientation (Requires Reset) 0 degrees

Screen Saver

Font

Back

36 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 2 Configure the Terminal

3. Press Screen Saver.

Screen Saver
Current Screen Saver: RA_DEFAULT
RA_DEFAULT

Screen Saver 1.bmp

Screen Saver 2.bmp Set

Delete

Mode Image

Brightness 11

Timeout 10 Min Back

4. Use the up and down arrow keys to select the screen saver, then press Set
to use it or Delete to remove it from the terminal.

“RA_DEFAULT” is the default terminal screen saver and cannot be deleted.

You cannot delete the current screen saver. The terminal prompts and error if
you try to do so.
5. Select the Mode.

Mode = Disable, Image, Dimmer, Image and Dimmer.


6. Select the brightness.

Brightness 0…100, increments of 1.


7. Select the idle timeout.

Choices are 1, 2, 5, 10, 15, 20, 30, or 60 min

Delete Fonts

To add fonts to the terminal, see Add Fonts to the Terminal on page 63.

Follow these steps to delete fonts from the terminal.


1. Go to the Terminal Settings screen.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 37


Chapter 2 Configure the Terminal

2. Press Display.

Display
Brightness 100

Calibrate Touchscreen

Orientation (Requires Reset) 0 degrees

Screen Saver

Font

Back

3. Press Font.

Font

calibri.ttf

gara.ttf

segoeui.ttf

Delete

Back

4. Select the font, then press Delete.

IMPORTANT The Korean language font “Gulim” is treated as a system font. After
downloading it to the terminal and restarting the terminal, you can
switch the terminal language to Korean by selecting it from the main
configuration screen. See Select a Terminal Language on page 19. The
“Gulim” font will not appear in the Font screen and cannot be deleted
unless you restore or return the terminal to out-of-box condition.

Change the Error Alert Display Settings


You can set the error alert display behavior from the terminal. You can choose
to enable or disable an error alert independent of the application setting or you
can use the application setting for displaying an error alert.

Follow these steps to change the error alert display settings from the terminal.

IMPORTANT Make sure that the application is not running before you make any
changes.
We recommend that you enable error alerts to allow diagnostics and
communications error messages to display.

38 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 2 Configure the Terminal

1. Go to the Terminal Settings screen.


2. Press Error Alert Display Settings.

Error Alert Display Settings


Current Error Alert Display Settings: Enable Error Alert

Error Alert Display Settings:

Enable Error Alert

Disable Error Alert

Use Application Setting Set

Error Alert Display will be enabled.

Note: The Display Alert Setting will take effect after stop and restart the
application.
Back

3. Use the up and down arrow keys to select an option.


4. Press Set.

Configure Print Settings

You can choose to print either the current screen or the alarm history of the
application that is running on your PanelView 800 terminal. The print
command is sent from the terminal either through Ethernet to a print server
(for example, a PC), or through USB to a printer connected to the terminal.
Only printers that use the PCL 5 protocol are supported. The actual print size
depends on the size of the terminal, paper size, orientation, and stretch option.

Follow these steps to configure the print settings.


1. Go to the Terminal Settings screen.
2. Press Print Settings.

Print Settings

Printing Port: USB

Paper Settings

Ethernet Print Settings

Back

3. Select the Printing Port to use (USB or Ethernet).

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 39


Chapter 2 Configure the Terminal

Configure the paper settings


1. Press Paper Settings.

Paper Settings

Orientation: Portrait

Print quality: Standard

Paper size: A4

Color output: Color

Stretch: Original
Back

2. Configure the following settings:


• Orientation = Portrait, Landscape
• Print quality = Standard (300 dpi), Draft (150 dpi)
• Paper size = Legal, Letter, A4, B5
• Color output = Color, Monochrome
• Stretch = Original, Stretch to paper
If the “Stretch to paper” option is chosen, the image is stretched
proportionately to fit the selected paper size.
3. Press Back to go back to Print Settings.

Configure the Ethernet print settings

Before configuring the Ethernet print settings, make sure that the print server
is available on the PC. To do so, the printer driver must be installed on the PC
and the printer must be shared on the network.

It is not necessary to configure the Ethernet print settings if you are not
printing through a print server.
1. Press Ethernet Print Settings.

Ethernet Print Settings

Network Share Path:

Username:

Password:

Domain:

Edit Credentials

Back

40 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 2 Configure the Terminal

2. Press Enter Credentials.


Network Share Path:
User Name:
Password: Ethernet Print Settings
Domain:

Esc F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11 F12 Home End


Network Share Path:

` 1 2 4 5
3 Domain: 6 7 8 9 0 - =
q w e r t y u i o p [ ] \
Username:
Caps a s d f g h j k l ; ’
Shift z x cPassword:
v b n m , . /
Ctrl Win Alt ins del
Edit Credentials

Back

3. Enter the login credentials for your print server. Then press the Enter
key.

IMPORTANT If your account does not have a password, leave the Password
field blank.
If your PC is not part of a domain or workgroup, enter the name
of your PC in the Domain field.

An example is shown below.

Ethernet Print Settings

Network Share Path: \\My_PC\Printer_1

Username: Administrator

Password: ******

Domain: My_PC

Edit Credentials

Back

Add a print button to your application

After configuring the print settings on your terminal, you have to add a print
button to your application.
1. In Connected Components Workbench software, double-click a screen
for your application where you want to place the Print button.
2. Drag-and-drop a Print button from the Toolbox window to your
application screen.
3. Right-click the Print button and select Properties.
4. In the Properties window, configure the Print Type setting.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 41


Chapter 2 Configure the Terminal

Print Type = Print Current Screen, Print Alarm History.

IMPORTANT The portrait and color options are not supported when printing the
alarm history. The print settings switches automatically to the
landscape and monochrome options.

System Information Settings On the main configuration screen, press System Information to go to the
system information screen.

System Information
Firmware Version: 5.011
Boot Code Version: 4.011
Logic Board Version: 4
Terminal On Time: 102,330
Display On Time: 102,330
Battery Status: Good

Memory Usage (bytes)


Internal Used: 1,392,640
Internal Free: 164,741,120
Advanced
Application Used: 31,600,640
Application Free: 193,994,752 Main

You can perform the following actions under System Information:


• View System Information
• Change Daylight Savings Time and Timezone

View System Information


You can view system information about your terminal including information
about the firmware, boot code, logic board, battery status (if applicable),
terminal on time, and memory used.

Follow these steps to view system information from the terminal.


1. Press System Information.

The system information screen displays firmware revision, boot code


version, logic board version, terminal on time, display on time, and
battery status.

42 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 2 Configure the Terminal

Change Daylight Savings Time and Timezone

Follow these steps to change the daylight savings time and timezone from the
terminal.
1. Press System Information.
2. Press Advanced.

Advanced
Automatically adjust for daylight savings time:

Disable

Current TimeZone:
(GMT-08:00) Pacific Time (US & Canada)

Select TimeZone
(GMT-11:00) Midway Island, Samoa
(GMT-10:00) Hawaii
English
(GMT-09:00) Alaska
(GMT-08:00) Tijuana, Baja California
(GMT-08:00) Pacific Time (US & Canada)
(GMT-07:00) Mountain Time (US & Canada)
(GMT-07:00) Chihuahua, La Paz, Mazatian
(GMT-07:00) Arizona Set Back
(GMT-06:00) Central Time (US & Canada)

3. Use the arrow keys to enable or disable daylight savings time.


4. Use the arrows keys to select the timezone you want, then press Set.

Transferring Applications Applications that are created for one PanelView 800 terminal can be used on
other PanelView 800 terminals. For example, you might create an application
for one terminal and then distribute the application to other terminals for
production. An application created for PanelView 800 terminals cannot be
used on older PanelView Component terminals.

Transferring an application is a two-step process.


• Export the application from the internal storage of the terminal to a USB
flash drive or microSD card.
• Import the application from a USB flash drive, or microSD card to the
internal storage of another terminal.

If the target terminal is a different type and size than the source terminal,
some aspects of the application are converted and the remaining properties
require updates. If trying to run an application, you are warned that the
application was not created for the terminal, but you are given an option to
continue or cancel unless the differences make it impossible to run the
application (for example, an Ethernet application on a terminal without an
Ethernet network connection).

PanelView 800 applications are saved with a “.cha” file type.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 43


Chapter 2 Configure the Terminal

Notes:

44 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 3

DesignStation in Connected Components


Workbench Software

DesignStation PanelView 800 DesignStation is a component within the Connected


Components Workbench software that allows you to create applications for
PanelView 800 terminals. You can create applications in Connected
Components Workbench software without being connected to a terminal but
you can only run the application on a physical terminal. Applications created
with Connected Components Workbench software can be downloaded to the
terminal through Ethernet, or transferred using a USB flash drive or microSD
card.

Figure 1 - Connected Components Workbench Software

We strongly recommend that you validate the transferred application using


the terminal software before running the application. Non-validated
applications, when started on the terminal, display a reminder popup message
that the application is not validated. Applications that are designed for the
CompactLogix 5370 controllers must be validated before running on the
terminal.

You can download the latest version of Connected Components Workbench


software at rok.auto/ccw.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 45


Chapter 3 DesignStation in Connected Components Workbench Software

Install the Software To use the Connected Components Workbench software effectively your
computer should meet the following hardware requirements:
Minimum System Requirements
Component Requirement
Processor Intel Pentium 4 2.8 GHz or equivalent
RAM Memory 2 GB
Hard disk space 10 GB free
Optical Drive DVD-ROM
Pointing Device Any Microsoft Windows® compatible pointing device

Recommended System Requirements


Component Requirement
Processor Intel Core i5 2.4 GHz or equivalent
RAM Memory 8 GB or more
Hard disk space 10 GB free or more
Optical Drive DVD-ROM
Pointing Device Any Microsoft Windows compatible pointing device

DesignStation in Connected Components Workbench software version 13 and


later is supported on the following operating systems:
• Windows® Server 2012 (64-bit) - requires .NET Framework 3.5 SP1 to be
installed
• Windows Server 2012 R2 - requires .NET Framework 3.5 SP1 to be
installed
• Windows Server 2016 - requires .NET Framework 3.5 SP1 to be installed
• Windows Server 2019 - requires .NET Framework 3.5 SP1 to be installed
• Windows 10 IoT Enterprise 2016 LTSB 64-bit- requires .NET Framework
3.5 SP1 to be installed
• Windows 10 IoT Enterprise 2019 LTSC - requires .NET Framework 3.5
SP1 to be installed
• Windows 10 (32-bit and 64-bit) (tested to Version 2004) - requires .NET
Framework 3.5 SP1 to be installed

Your computer information can be found by right-clicking My Computer and


then selecting Properties.

Follow these steps to install Connected Components Workbench software.


Connected Components Workbench software version 11 is used in the
following examples.
1. Run the executable file.

46 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 3 DesignStation in Connected Components Workbench Software

2. In the Setup window, choose


“Install now” to go with the
default installation, or
“Customize” to select the
individual components to
install.

3. If you chose “Customize”, select


the components that you want to
install, then click Install.

Certain components are pre-


selected for you and cannot be
unchecked.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 47


Chapter 3 DesignStation in Connected Components Workbench Software

4. Review the license agreement


and click Accept all to proceed
with the installation.

5. The next screen provides a visual


indication of the installation
progress.

48 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 3 DesignStation in Connected Components Workbench Software

6. When the installation is


successfully completed, a final
confirmation screen is shown.
Click Close to end the
installation process.

Uninstall the Software Uninstalling Connected Components Workbench software removes all
registry settings, files, directories, and Windows Start menu items that were
originally installed with this software.

Follow these steps to uninstall Connected Components Workbench software.


1. Run the same executable file
used to install Connected
Components Workbench
software.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 49


Chapter 3 DesignStation in Connected Components Workbench Software

2. Click Next, then select the


components that you want to
uninstall.

Note to uninstall Connected


Components Workbench
software, you must first unselect
the checkboxes for the following
components:
• Drives - Unified Device
Configuration
• Graphic Terminals -
DesignStation
• Guardmaster® 440C Safety Relay
• 450L Safety Light Curtain
• Controller - Micro800

3. After you have unselected the


checkboxes of the components
that are listed above, you can
then unselect the checkbox for
Connected Components
Workbench software. Click
Install to proceed with the
uninstallation.

50 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 3 DesignStation in Connected Components Workbench Software

4. The next screen provides a visual


indication of the uninstallation
progress.

5. When the uninstallation is


successfully completed, a final
confirmation screen is shown.
Click Close to end the
uninstallation process.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 51


Chapter 3 DesignStation in Connected Components Workbench Software

Launch Mechanism Launch Connected Components Workbench software from the entry in your
Windows Start Menu, or by double-clicking the Connected Components
Workbench software shortcut on your desktop.

Figure 2 - Windows Start Menu

Configure Key Repeat Settings

You can configure key repeat settings for the terminal keys or attached
keyboard of the connected terminal.

You cannot change the key repeat settings from the on-terminal configuration
screens. If you want to change this setting, you must connect to the terminal
through a web browser.(1)
(1) The web browser feature is not supported on PanelView 800 terminals from firmware revision 3.011 onwards.

The repeat rate is the speed at which a character repeats per second when you
hold down a key. The repeat delay is the amount of time, in milliseconds, that
elapses before a character begins to repeat when you hold down a key.

From firmware revision 3.011 onwards, the key repeat settings can be
configured in Connected Components Workbench software. This feature also
requires Connected Components Workbench software version 9 or later to be
installed.

Follow these steps to change the repeat settings for keys using Connected
Components Workbench software.
1. Go to the Settings tab for your PanelView 800 terminal.

52 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 3 DesignStation in Connected Components Workbench Software

2. Click Advanced in the settings list.


3. Select the Set Terminal On First Load checkbox.

4. Under Input Devices, select the checkbox for the setting you want to
configure.
5. Use the up or down arrows to adjust the value, or input the value directly
into the text box.
6. Save the project.

Creating Applications Applications for PanelView 800 terminals can be created using the Connected
Components Workbench software version 8 or later. You can create
applications without being connected to a terminal but you can only run the
application on a physical terminal.

Downloading Applications Applications created with Connected Components Workbench software can be
downloaded to the terminal through the following methods:
• Only for firmware revision 2.020 or earlier
- PanelView Explorer using Ethernet
• For firmware revision 3.011 or later
- CIP™ Ethernet
- CIP Bridge connection through CompactLogix™ 5370 controller
- CIP Bridge connection through Micro800™ controller

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 53


Chapter 3 DesignStation in Connected Components Workbench Software

IMPORTANT If the terminal is password protected using Connected Components


Workbench software version 10 or later, you cannot download an
application to the terminal using Connected Components Workbench
software version 9 or earlier. An error message stating the system is
busy will be shown in the output window under the Graphic Terminal
message list.
• If the terminal is password protected, you must enter the password before you can
download an application.

Follow these steps to download the application to the terminal.


1. From the Project Organizer, right-click the PanelView 800 terminal, then
click Download.
Alternatively, click the Download icon in the Settings tab of the terminal.

The Connection Browser dialog box appears.

2. Select the terminal that you want to download the application to, then
click OK.

In Connected Components Workbench software version 12 or later, after you


have successfully downloaded an application to your terminal, a dialog prompt
appears to ask to start the application. This feature also requires firmware
revision 5.012 or later.

Uploading Applications You can upload an application from the terminal into the Connected
Components Workbench software. This allows you to edit the application,
then download the changes to the terminal. If you have a current project
opened in Connected Components Workbench software, that project will be
backed up, then the application from the terminal overwrites the current
project.
• The current project will be backed up with the string “__bak” appended to the end of
the filename. The status message can be viewed in the Output window under the
Graphics Terminal message list.
• If the terminal is password protected, you must enter the password before you can
upload an application.

Follow these steps to upload an application from the terminal.


1. From the Project Organizer, right-click the PanelView 800 terminal, then
click Upload.
Alternatively, click the Upload icon in the Settings tab of the terminal.

54 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 3 DesignStation in Connected Components Workbench Software

The Connection Browser dialog box appears.

2. Select the terminal that you want to upload the application from, then
click OK.
3. Select an application from the list.
4. Click OK.

Create Recipes Recipes are created using Connected Components Workbench software and
each PanelView 800 terminal application supports up to 50 recipes. Each
recipe contains a list of ingredients (up to 50), each with its own tag, and one
data set. A data set pairs values with each ingredient.

Follow these steps to create a recipe in Connected Components Workbench


software.
1. In the Project Organizer, double-click Recipe to open the Recipe tab.

2. Click Create Recipe to add a recipe to the recipe list.


A recipe is added to the list. The default name is RECIPE_01.
3. You can change the Recipe Name and Recipe Filename by clicking the
Recipe Details button next to the Recipe.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 55


Chapter 3 DesignStation in Connected Components Workbench Software

IMPORTANT From firmware revision 4.011 onwards, recipe names and recipe
filenames are restricted to only English characters (alphanumeric and
certain special characters). If you use non-English characters, you will
not be able to save the recipe. This does not affect the usability of the
recipe, it can still be downloaded to the terminal.
This limitation is due to the new feature that allows you to edit the
recipe name in the terminal, which supports only English characters on
the terminal keyboard.
If non-English characters are used, the field is outlined in red and the
OK button is grayed out.

4. You can optionally assign a Status Tag to monitor the status of the recipe
downloads and uploads.

You can now add ingredients to the recipe.

Add Ingredients to a Recipe A recipe can hold up to 50 ingredients. Each ingredient is created as a separate
row in the recipe table. When you create a recipe, a row is automatically added
for the first ingredient. Each recipe must have at least one ingredient.

Follow these steps to add ingredients to a recipe.


1. Select a recipe in the Recipe List.

2. Click the Add Ingredient button for each ingredient you want to add to
the recipe.
3. For each ingredient:
a. change the name of the ingredient if necessary.
b. select the tag to store the value of the ingredient.
c. select a numeric or string data type for the ingredient.
d. enter a minimum and maximum value for the ingredient if the data
type is numeric.
e. enter a value for each ingredient.

56 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 3 DesignStation in Connected Components Workbench Software

Delete Ingredients from a Recipe

Follow these steps to delete ingredients from a Recipe.


1. Click the space on the left of the ingredient to select the entire row.

2. Click Delete Ingredient.


3. Click Yes to confirm.

Download Recipes Recipes are downloaded together with the application into the PanelView 800
terminal. See Downloading Applications on page 53 for information on how to
download applications to the terminal.

Configure FTP Settings You can connect to a PanelView 800 terminal using an FTP (File Transfer
Protocol) client such as a web browser, PC file explorer, or third-party FTP
software. This gives you read-only access to the Alarm History, Datalog, and
Recipe folders on the terminal. The FTP server on the terminal is disabled by
default. To enable the FTP server, see Enable the FTP Server on page 31.

Follow these steps to grant access to the contents of the folders.


1. In Connected Components Workbench software, click the Settings tab
for your terminal.

2. Click the FTP item in the menu list.


3. Under FTP Accessibility Settings, select the checkbox for the folders that
you want to grant access to. If the checkbox is not selected, the contents
of that folder will not be shown. None of the checkboxes are selected by
default.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 57


Chapter 3 DesignStation in Connected Components Workbench Software

To connect to the terminal, enter the IP address of the terminal in the FTP
client. For this example, the PC file explorer is used.

Recommended FTP Clients and Settings

These are the recommended FTP clients you can use to connect to
PanelView 800 terminals.
Recommended FTP Clients and Settings
Recommended
Device OS Version FTP Client Settings
FileZilla Default
Cyberduck Change Transfer Files option to “Open single connection”.
PC Windows 7 Internet Explorer 11 Default
Firefox (with FireFTP plug-in) Default
Windows File Explorer Default
Windows 8.1 FileZilla Free Default
Tablet Android 6.0 AndFTP Default
iOS 9.1 FTP Sprite Default
Windows 8.1 FTPme Default
Smartphone Android 5.1/6 AndFTP Default
iOS 9 FTP Sprite Default

IMPORTANT Only the user name “anonymous” is supported. If you try to connect to
the terminal with a different user name, you may receive the following
error:
“Critical error: Could not connect to server.”

Configure Email Settings You can configure the PanelView 800 terminal to automatically send an email
when an alarm is triggered, and also manually by using an email button in the
application. The email can be sent to one or more recipients and you can also
choose to send attachments such as a screen capture of the current screen or
the datalog file of the application.

IMPORTANT The Email feature is not available for CompactLogix 5370 controllers.

58 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 3 DesignStation in Connected Components Workbench Software

Configure the Email settings

Follow these steps to configure the email settings.


1. In the Connected Components Workbench software, click on the
Settings tab for your PanelView 800 terminal.
2. Click the Email item in the menu list.

3. Under the Email Server configuration, enter the following:


• Server Address = The address of the email server.
• SMTP Port = The port number of the email server (1...65535, default is
465).
If an invalid value is entered for the port number, it will not be saved. The
port number reverts to the previous saved value when the project is closed
and open again.
• TLS 1.2 Enabled = Select this checkbox if encryption is enabled on the
email server.
• STARTTLS = Select this checkbox to enable STARTTLS if the email
security protocol of the email server is of STARTTLS type.
4. Under the Email Sender Account configuration, enter the following:
• Email Account = The account name of the email service (for example,
[email protected])
• Password = The login password for the email account.
• Email Address = The “From” or “Sender” email address associated with
the account when sending an email.
5. Under the Recipients Settings configuration, enter the email addresses
of the recipients in the “To”, “Cc”, and “Bcc” fields as required.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 59


Chapter 3 DesignStation in Connected Components Workbench Software

Add an Email button to your application

After configuring the email settings on your terminal, you have to add an email
button to your application.
1. In Connected Components Workbench software, double-click an
application screen to open it.
2. Drag-and-drop an Email object from the Toolbox onto the screen.

3. Right-click the Email object and select


Properties.
Configure the properties as required.
• Attachment = Select “None”, “screen
capture”, or “Datalog” from the drop-down
list.
Only one type of attachment can be sent with
the email. The screen capture option sends
the current application screen.
• Enter the email address of the recipients in
the “To”, “Cc”, and “Bcc” fields as required.
• You can configure the subject and body of the
email with text strings, and Date, Time,
Number, and String variables.
Email configuration can also be done during
runtime through system tags.

Use system tags to configure Email settings

The following system tags can be used to configure


the email account during runtime:
• $SysEmailAccount = The account name of the email service (for example,
[email protected])
• $SysEmailAddress = The “From” or “Sender” email address associated
with the account when sending an email.
• $SysEmailPassword = The login password for the email account.
• $SysEmailServerAddress = The address of the email server.
• $SysEmailSMTPPort = The port number of the email server (1...65535,
default is 465).
If an invalid value is entered for the port number, it will not be saved. The
port number reverts to the previous saved value when the project is closed
and open again.
• $SysEmailSTARTTLS = 1 – Enable email STARTTLS encryption, 0 –
Disable email STARTTLS encryption.
• $SystEmailTLS = 1 – Enable email TLS encryption, 0 – Disable email TLS
encryption.

To change the runtime email configuration of the Email button, memory tags,
external tags, or system tags can be used for the runtime format of the email
Subject, Body, and To/Cc/Bcc email addresses.

60 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 3 DesignStation in Connected Components Workbench Software

To change the runtime email configuration of alarm triggered emails, only


system tags can be used for changing the To/Cc/Bcc email addresses.

Email server configuration examples

The following table shows examples of email server configuration.


Email Server Configuration
Email Service Server Address SMTP Port TLSL StartTLS
Gmail smtp.gmail.com 465 Enabled Grayed Out
Yahoo smtp.mail.yahoo.com 465 Enabled Grayed out
Hotmail smtp-mail.outlook.com 587 Grayed Out Enabled
Outlook smtp-mail.outlook.com 587 Grayed Out Enabled

Configure the Alarm Settings You can enable the terminal to automatically send an email when an alarm is
triggered by configuring the alarm settings. For more information on
configuring the email settings, see Configure Email Settings on page 58.
1. In Connected Components Workbench software, double-click Alarms in
your application to open the Alarms tab.

2. If the number of fields shown is different from the example above, click
the link “Advanced >>” to show additional alarm fields.
3. Configure the following settings:
• Trigger = Select the tag to be used as the trigger for the alarm.
• Message = This field is displayed on the terminal when the alarm is
triggered and is sent as the body of the email. You can configure the
message with Date, Time, Number, and String variables.
• Print = Select this checkbox to print the current alarm information when
the alarm is triggered.
• Send Email = Select this checkbox to enable the terminal to send an email
when the alarm is triggered.
• Subject = This field is sent as the subject of the email. You can configure
the subject with Date, Time, Number, and String variables.

Change Application Font You can change the font used in your PanelView 800 application, either for the
entire application or for each individual object. You can also import fonts into
your application. The font types supported are “.ttf”, “.ttc”, and “.ac3”.

IMPORTANT The Korean language font “Gulim” is treated as a system font. After
downloading it to the terminal and restarting the terminal, you can switch
the terminal language to Korean by selecting it from the main
configuration screen. See Select a Terminal Language on page 19. The
“Gulim” font will not appear in the Font screen and cannot be deleted
unless you restore or return the terminal to out-of-box condition.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 61


Chapter 3 DesignStation in Connected Components Workbench Software

If your application uses a font that is not in the terminal, the font will be download
to the terminal together with your application.

Follow these steps to change the application font.


1. In Connected Components Workbench software, double-click Screens in
your application to open the Screen Settings tab.
2. Select the font to use from the
Font drop-down list. To import a
font, select Import Font.

3. Browse your computer for the


font, then select it and click
Open.
The font is now imported into
your application.
4. To change the font for an
individual object, select the font
from the object properties. Here
are some examples.

62 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 3 DesignStation in Connected Components Workbench Software

Add Fonts to the Terminal To add fonts to a PanelView 800 terminal, you must first import them into
Connected Components Workbench software. The font types supported are
“.ttf”, “.ttc”, and “.ac3”.

IMPORTANT The Korean language font “Gulim” is treated as a system font. After
downloading it to the terminal After downloading it to the terminal and
restarting the terminal, you can switch the terminal language to Korean
by selecting it from the main configuration screen. See Select a
Terminal Language on page 19. The “Gulim” font will not appear in the
Font screen and cannot be deleted unless you restore or return the
terminal to out-of-box condition.
If your application uses a font that is not in the terminal, the font will be download
to the terminal together with your application.

Follow these steps to download a font to the terminal.


1. In Connected Components Workbench software, click Device ->
Download -> Download Font.

2. If the font you want to download to the terminal is not shown in the
Download Font window, click Import.

3. Browse your computer for the font, then select it and click Open.
The font is now imported into Connected Components Workbench
software.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 63


Chapter 3 DesignStation in Connected Components Workbench Software

4. Select the font in the Font window, then click Download.


The Connected Components Workbench software connects to the
terminal and downloads the font.

To delete a font from the terminal, see Delete Fonts on page 37.

Add Screen Savers to the The PanelView 800 terminal comes with a default screen saver "RA_Default".
Terminal You can change the screen saver by downloading them to the terminal. The
terminal supports up to 25 screen savers and the screen saver has the following
requirements:
• Maximum resolution of 128 x 128 pixels.
• In bitmap (.bmp) file format.

Follow these steps to download a screen saver to the terminal.


1. In Connected Components Workbench software, click Device ->
Download -> Download Screen Saver.

2. Browse your computer for the screen saver, then select it and click Open.
The Connected Components Workbench software connects to the
terminal and downloads the screen saver.

To select and configure a screen saver to use, or delete a screen saver from the
terminal, see Configure Screen Saver Settings on page 36.

64 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 3 DesignStation in Connected Components Workbench Software

Trend and Datalog Trends are used to monitor the values of tags over a specific time interval. Only
live trends are supported. There is no support to view historical trends. There
can be up to 7 trends with a maximum of 20 pens per trend. The values of the
tags can be recorded into a datalog file.

Follow these steps to add a Trend object to your PanelView 800 application.
1. In Connected Components Workbench software, double-click an
application screen to open it.
2. Drag-and-drop a Trend object from the Toolbox onto the screen.

3. Double-click the Trend object.


The Pens window appears.

4. Modify the fields as required.


5. Click Add if more pens are required.
6. Click OK when finished.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 65


Chapter 3 DesignStation in Connected Components Workbench Software

7. Right-click the Trend object and


select Properties.
Configure the properties as
required.
• Sample Interval
• Sample Interval Unit
• Update While Off Screen: False =
The trend updates only when the
screen with the Trend is shown on
the terminal.
True = The trend always updates.
• Log File Location: Select the location
where the datalog file is saved.
• Log Trigger Tag: The datalog starts
recording when the value of the tag
is TRUE.

Alarm List Filter The Alarm List object displays the list of alarms that occurs on the terminal.
You can filter the list to display all the alarms that have occurred, or only the
active alarms.

Follow these steps to add an Alarm List object to your PanelView 800
application.
1. In Connected Components Workbench software, double-click an
application screen to open it.
2. Drag-and-drop an Alarm List object
from the Toolbox onto the screen.

66 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 3 DesignStation in Connected Components Workbench Software

3. Right-click the Alarm List object and


select Properties.
Configure the properties as
required.
• Display Active Alarm: By default, all
alarms are displayed. When the
value of the tag is “1”, only the active
alarms are displayed.

Import Tags From a You can import tags from a CompactLogix controller or Micro800 controller
Controller into your PanelView 800 application.

IMPORTANT If the data type of a controller tag is not supported by PanelView 800,
the tag is not shown in the Tag Selector dialog. However, if the tag
contains sub tags that have supported data types, then the main tag
and sub tags will be shown in the Tag Selector dialog.

Import Tags From a CompactLogix Controller


Follow these steps to import CompactLogix controller tags into your
PanelView 800 application.
1. In the Tag Editor tab, click the Import.
2. In the submenu, select CompactLogix.
The open file dialog appears.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 67


Chapter 3 DesignStation in Connected Components Workbench Software

3. Select Studio 5000 Logix Designer® application project file (.l5x), then
click Open.
The Tag Selector dialog appears.

IMPORTANT An error message appears if one of the following conditions is


true:
• The file does not have the extension “.l5x”.
• The file is damaged.
• The file is from a non-supported version of Logix Designer
application.
• The file is a non-supported Logix Designer application project
type.

If the tags you want to import exists in your application, a warning message
appears. Click Yes to import all selected tags and overwrite existing tags, or No
to only import tags that do not exist in your application.

The Import tag result is show in the Output pane.

IMPORTANT After importing a tag with the String data type, you must change
“TagName.Data/0” to “TagName.Data/N” where N is the length of the
string.
If no default value was set for the controller string tag, the tag is named
“TagName.Data/0” by default after it has been imported to your
PanelView 800 application.

For more information on the differences in supported data types between


PanelView 800 terminals and CompactLogix 5370 controllers, see
CompactLogix 5370 Controller Addressing on page 133.

68 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 3 DesignStation in Connected Components Workbench Software

Import Tags From a Micro800 Controller

Follow these steps to import Micro800 controller tags into your PanelView 800
application.
1. In the Tag Editor tab, click the Import.
2. In the submenu, select Micro800.
The Tag Selector dialog appears.

IMPORTANT An error message appears if there is no Micro800 controller in


your project
3. Select the tags you want to import, then click Import.

If the tags you want to import exists in your application, a warning message
appears. Click Yes to import all selected tags and overwrite existing tags, or No
to only import tags that do not exist in your application.

The Import tag result is show in the Output pane.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 69


Chapter 3 DesignStation in Connected Components Workbench Software

Assign Tags From a You can assign tags from a CompactLogix 5370 controller to your PanelView
CompactLogix 5370 800 terminal tags.
Controller IMPORTANT If the data type of a controller tag is not supported by PanelView 800,
the tag is not shown in the Tag Selector dialog.

Follow these steps to set up the CompactLogix 5370 controller tags and assign
them to your PanelView 800 terminal tags.
1. Under Communication settings in the Settings tab, click the ellipses (...)
button for Offline File Path.
2. Select a Logix Designer application project file (.l5x), then click Open.

IMPORTANT An error message appears if one of the following conditions is


true:
• A valid file path is not provided.
• The file does not exist.
• The file does not reside in the local computer.
• The file does not have the extension “.l5x”.
• The file is damaged.
• The file is from a non-supported version of Logix Designer
application.
• The file is a non-supported Logix Designer application project
type.
3. Select the controller tag you want to assign, then click Select.

Export and Import a In Connected Components Workbench software version 11 or later, you can
Language List export and import a language list for your PanelView 800 terminal. This makes
it easier to translate text strings and update them in your application.

70 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 3 DesignStation in Connected Components Workbench Software

Export a Language List

Follow these steps to export a language list from your PanelView 800 terminal.
1. Under Languages in the Settings tab, click Export Language List.
2. Create a new file or select an existing file to save the language list.

IMPORTANT An error message appears if one of the following conditions is


true:
• The file does not reside in the local computer.
• The file does not have the extension “.xlsx”.
• The file is being used by another application.
• The file is set to “Read-only” access.

If you selected an existing file, a warning message appears. Click Yes to


overwrite the existing file or No to cancel the action.

The Export Language List results are shown in the Output pane.

The exported language list is stored in a new worksheet with the name
“Language List”. Each data column contains the text information for one
language.

Import a Language List

Only language text information is imported. Location information and Text ID


are not imported. If the Text ID is not in the current Language List, then the
language text information will not be imported.

IMPORTANT Note the following:


• The import action will be canceled if the selected file is not in the correct
format, the name of the worksheet is not "Language List", or no
language information exists.
• If there is duplicate language information in another column, it will be
ignored.
• If the column contains non-supported language data, it will be ignored.
• If the language count exceeds the limit (10), the excess column data will
be ignored.
• If the language text string length exceeds the limit (255 characters), the
text string will be truncated.

Follow these steps to import a language list into your PanelView 800 terminal.
1. Under Languages in the Settings tab, click Import Language List.
2. Select the file to import the language list from.

IMPORTANT An error message appears if one of the following conditions is


true:
• The file does not reside in the local computer.
• The file does not have the extension “.xlsx”.
• The file is being used by another application.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 71


Chapter 3 DesignStation in Connected Components Workbench Software

The Import Language List results are shown in the Output pane.

IMPORTANT Only language text information is imported. Location information and


Text ID are not imported. If the Text ID is not in the current Language
List, then the language text information will not be imported.
Take note of the following:
• The import action will be canceled if the selected file is not in the correct
format, the name of the worksheet is not “Language List”, or no
language information exists.
• If there is duplicate language information in another column, it will be
ignored.
• If the column contains non-supported language data, it will be ignored.
• If the language count exceeds the limit (10), the excess column data will
be ignored.
• If the language text string length exceeds the limit (255 characters), the
text string will be truncated.
You can import text information for a language that has not been set on
the terminal. Make sure that the column header contains a Language ID
and it will be imported to Languages on the terminal.

Update Tag Name In Connected Components Workbench software version 12 or later, you can
configure the PanelView 800 application to rename a tag automatically when
assigning a CompactLogix 5370 or Micro800 controller tag as the tag address.

The tag name will be updated to match the controller tag name.

Follow these steps to enable the tag name to be updated automatically:


1. From the Tools menu, select Options....
2. Select Graphic Terminals -> Preferences from the list of options.

3. Select the checkbox.


4. Click OK.

72 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 3 DesignStation in Connected Components Workbench Software

Animation Connected Components Workbench software version 13 or later adds a new


property Animation Option to Multistate Indicator objects with the following
options:
• Animation With State
• Animation With Tag

If Animation With State is selected, the following tags are not configurable:
• Height Tag
• Horizontal Position Tag
• Vertical Position Tag
• Visibility Tag
• Width Tag

Double-click the Multistate Indicator to display the States Dialog box.


From the States screen, scroll to the right to configure the last five properties,
if necessary.

If Animation With Tag is selected, the following tags are configurable:


• Height Tag
• Horizontal Position Tag
• Vertical Position Tag
• Visibility Tag
• Width Tag

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 73


Chapter 3 DesignStation in Connected Components Workbench Software

To use Animation With Tag, Connected Components Workbench software version


13 or later adds parameters to memory tags to enhance object animation. See
help file for more information on memory tags.

Memory Tags Parameters


Parameter Value
Tag Name Name of Memory tag.
Data Type 16-bit integer
Retained Value Retains most recent value when application is shutdown
Initial Value Defines the coordinates of the starting position.
Description Enters a description for the Memory tag
Data Entry - Min -32768
Data Entry - Max -32767
Auto Change Select to enable automatic update of value based on the rate of change configured.
Rate Defines the rate if change for automatic updates, in milliseconds. Min value is 1000 ms.
Trigger type for the Memory tag:
• Always
Option
• Trigger Start
• Trigger Start and Stop
Trigger Tag Assign a tag to trigger this Memory tag

Time Entry Data Type Connected Components Workbench software version 13 or later adds support
Support for the Time data type for Micro800 controllers.

74 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 3 DesignStation in Connected Components Workbench Software

From the Object Properties, click Format, set the attribute Time Datatype
Entry to True. When changing the time in the application, the value is
displayed in the onscreen keyboard.

View List of Objects In Connected Components Workbench software version 13 or later, you can
view a list of all the objects in your application screens in the Object Explorer
window. Use the Object Explorer to help you manage and identify the objects
in your application.

To access the Object Explorer window, select it from the View menu. You can
dock it within the workspace or as a tab.

The Object Explorer shows a list of the objects that are used under each
application screen. Selecting the object in the Object Explorer window selects
it in the application screen.

Options Description

Lock Locks the selected object. The object cannot be selected in the application screen.

Unlock Unlocks the selected object.

Unlock all Unlocks all objects

Vibrate Vibrates the selected object in the application screen.


Click the eye icon next to the object to Show/Hide the object in the application screen. If an object is
Visibility hidden, the eye icon is grayed and struck out, it means that one or more objects in that screen are
hidden. Click the eye icon to Show/Hide all the objects in that screen.
Search Object Enter the name of the object to search for it in the list.
Filter on screen Filters the objects in the application screen that match the name entered in the Search Object field.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 75


Chapter 3 DesignStation in Connected Components Workbench Software

Notes:

76 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 4

Secure the Terminal

Securing Your Terminal In Connected Components Workbench software version 10 or later, you can
configure password protection for PanelView 800 terminals with firmware
revision 4.011 or later. Consider adding password protection to prevent
unauthorized end users from accessing the configuration and programming
in your PanelView 800 terminals. Users will be required to enter a password
before performing actions on the terminal.

Set Terminal Password You can create a password for the terminal. Once your terminal is password
protected, users must enter the password before they can:
• change the password
• clear the password
• connect to the terminal to download or upload applications

Follow these steps to set a password for the terminal.


1. From the terminal toolbar, click Secure, then click Set Password.

2. Enter the new password in the Password and Confirm Password fields.

Use the following guidelines when creating a password:


• passwords must be 8...32 characters in length
• valid characters are uppercase and lowercase letters, numbers, symbols
found on the keyboard and spaces

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 77


Chapter 4 Secure the Terminal

3. Click OK.

IMPORTANT If you forget the terminal password there is no way to recover it. You
can perform the restore terminal operation, or return the terminal to the
out-of-box configuration. Doing so will clear the password and also
remove all applications, logs, recipes, user-installed font files, objects
and graphics. See Returning to the Out-of-box Condition on page 103
and Restoring the Terminal on page 104 for more information.
Alternatively, you can update the terminal firmware to the same or later
firmware revision. Doing so will clear the password and other settings,
but your applications, recipes, and fonts will be retained. See Upgrade
Firmware on page 109 for more information.

IMPORTANT If the terminal is password protected using Connected Components


Workbench software version 10 or later, you cannot download an
application to the terminal using Connected Components Workbench
software version 9 or earlier. An error message stating the system is
busy will be shown in the output window under the Graphic Terminal
message list.

Change Terminal Password You must know the current password of the terminal to set a new one.

Follow these steps to change the password of the terminal.


1. From the terminal toolbar, click Secure, then click Change Password.

2. Enter the current password in the Old Password field.


3. Enter the new password in the New Password and Confirm Password
fields.

Use the following guidelines when creating a password:


• passwords must be 8...32 characters in length
• valid characters are uppercase and lowercase letters, numbers, symbols
found on the keyboard and spaces

78 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 4 Secure the Terminal

4. Click OK.

IMPORTANT If you forget the terminal password there is no way to recover it. You
can perform the restore terminal operation, or return the terminal to the
out-of-box configuration. Doing so will clear the password and also
remove all applications, logs, recipes, user-installed font files, objects
and graphics. See Returning to the Out-of-box Condition on page 103
and Restoring the Terminal on page 104 for more information.
Alternatively, you can update the terminal firmware to the same or later
firmware revision. Doing so will clear the password and other settings,
but your applications, recipes, and fonts will be retained. See Upgrade
Firmware on page 109 for more information.

Clear Terminal Password You must know the current password of the terminal to clear it.

Follow these steps to clear the password from the terminal.


1. From the terminal toolbar, click Secure, then click Clear Password.

2. Enter the current password in the Password field.

3. Click OK.

Secure Design Environment The secure design environment lets you restrict user access to screens in an
application and protect the application from unauthorized updates. By
default, all users have unrestricted access to the application. This means any
user can access and make changes to the application. They can also access any
application screens on the terminal at runtime.

Use the secure design environment to:


• Limit users who have access to the system by setting up user accounts
and passwords. The default users (All Users*) do not require a password.
• Create access rights for screens in the application.
• Assign these access rights to users on a need basis. Only users with a
need to access a screen should hold access rights to the screen.
• Protect the application from updates by restricting user access to design
mode. Only users with design rights are allowed to access and update an
application. Initially, all users have design rights to an application.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 79


Chapter 4 Secure the Terminal

• Create security buttons that are used at runtime by operators to login or


logout, change passwords, reset passwords, or disable security.
• Change the idle timeout that automatically logs the user out from a
secured screen to the Startup screen after idle timeout period elapses.

IMPORTANT At least one user must have the design right if you want to allow
updates to the application. If no user is assigned this right, no one will
be able to edit the application. Initially, all users have design rights to an
application. This means anyone can edit the application without logging
in.

Read the rest of this chapter to learn how to make use of the secure design
environment.

Manage User Accounts Follow these steps to access the User Accounts screen.
Settings 1. In the main screen of Connected Components Workbench software,
click the Settings tab for your PanelView 800 terminal.
2. Click User Accounts in the options list.
User Accounts Screen

< screenshot>

80 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 4 Secure the Terminal

Setting Description
Adjust or disable the idle timeout by selecting the value from the drop-down list. If disabled, the application will not transition from a
secured screen to the startup screen.
The default idle timeout is 15 minutes. If the terminal receives no user input within that 15 minute period, it goes into Idle mode. User
Idle Time Out Length input includes key presses, touch screen presses, external mouse, or keyboard input.
If the terminal goes into idle mode, the application transitions from a secured screen to the startup screen. The screen does not
change if the current screen is unsecured. The current user is logged out and the user must log in again.
Masks a password with a character when it is entered so that it is not visible. To disable this feature, set the option to False. Disabling
Mask Password Entry this feature is not recommended.
Prevents the use of an empty string as a password. If you set the option to True and you have an application that is using an empty
password, when you are prompted for screen access, you will be asked to change the password and the action cannot be canceled.
If you allow empty passwords, you will be asked for confirmation when you enter an empty password. If you don’t allow empty
Disable Empty Password passwords, a warning is displayed in the Validation result. You can choose to ignore and download the application to your terminal,
but you will be asked to change the password and the action cannot be canceled.
This feature is only available in Connected Components Workbench software version 12 or later. It also requires firmware revision
5.012 or later.
By default, user names and passwords are entered using an alphanumeric keypad at runtime. To use a numeric keypad, set the
Password and User Name Type option to Numeric Keypad.
Using a numeric keypad requires numeric user names and passwords.
Protects the application by preventing unauthorized access to edit/modify/update an application by users without the proper rights.
Design Environment Secured Create user accounts and assign rights for them to perform these actions. Design rights allow users to update the application, and
access rights allow users to view certain screens on the terminal at runtime.

Add Users You can add up to 16 user accounts to access the application at runtime. Each
account has a user name and password. The account can be an individual user
or a group of users, such as maintenance or operators, who share the same
user name and password.

Follow these steps to add user accounts to the application.


1. Select the Design Environment Secured checkbox.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 81


Chapter 4 Secure the Terminal

2. Click Add User to create a new account.


The Security - Add User dialog appears.

Setting Description
Enter a name for the user account. User names can be 15 alphanumeric
characters with spaces and must be unique. They are not case-sensitive. For
User Name example, Operator, operator, and OPERATOR are considered the same user
name.
Enter a password for the user account. Passwords can be 15 alphanumeric
characters with spaces and are case-sensitive. For example, Operator10 and
Password operator 10 are two different passwords. Multiple users can share the same
password.
Confirm Password Repeat the password for the user account to confirm the entry.
You can specify whether the password can be modified at runtime with a Reset
Password Modifiable Password or Change Password button. Anyone can modify the password if the
user name and password are known.

3. Enter the fields in the dialog box, then click Add to close the dialog and
add the new account to the list.

Managing Users

To delete users, click a row to select it and click the Delete Selected User(s)
button. To select multiple rows, hold down the CTRL or SHIFT key and click
the desired rows. If you delete all users, then you are left with All Users* which
gives any user unrestricted access to the application.

82 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 4 Secure the Terminal

To reset a password for any user, click the Password - Reset cell and the
Security - Reset Password dialog appears. You can enter a new password
without knowing the old password.

To rename a user, click the User cell to select it, and click again on the user
name, then type a new user name.

Assign Design Rights Design rights allows a user account to edit the application. To assign design
rights to a user account, select the checkbox under the DESIGN column for
that account.

When design rights are assigned, the next time the application is opened in
Connected Components Workbench software, a Security - Authentication
dialog appears to prompt the user to enter a user name and password.

Create Access Rights You can create up to 16 rights for an application. Rights are used to determine
the application screens that users can access at runtime.

Users can only access screens that have an access right if they have the same
right assigned to them.

You can create a right for each screen in the application and assign these rights
to users based on the screens you want them to access at runtime, or you can

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 83


Chapter 4 Secure the Terminal

create rights by job function. For example, you can assign maintenance rights
to users that need to access the maintenance screens at runtime.

IMPORTANT We recommend that you do NOT assign any rights to the Startup screen.

After creating an access right, you need to assign the right to users by clicking
the appropriate checkbox, and assign the right to one or more screens.

Follow these steps to add rights to the application and assign them to users.
1. Click the Add Right button and enter a name for the right.

2. Select the checkbox to assign the right to a user account.

Managing Rights

To delete a right, click the column header to select it and click the Delete
Right(s) button. Any assignments of that right to users are also deleted.

84 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 4 Secure the Terminal

To rename a right, click the column header ellipses button and type a new
name.

Assign Rights to a Screen You can secure any screen in an application. To secure a screen, you assign an
access right to the screen. Any user or group who holds this access right can
access the screen at runtime by entering a user name and password. All other
users are denied access to the screen.

Each screen is limited to one access right.

Follow these steps to assign a right to a screen of your application.


1. In the Properties panel of the screen, locate the Access Rights setting
under the Screen category.

2. Click the drop-down arrow and select the right you want to assign from
the list.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 85


Chapter 4 Secure the Terminal

IMPORTANT You cannot secure a screen unless rights are defined and assigned to
users on the User Accounts screen in the Settings tab.

Changing Terminal Settings

To prevent unauthorized changing of terminal settings at runtime, such as


network configuration or the startup application, assign an access right to
screens that contain the Goto Config button.

Security at Runtime The user is prompted to enter a user name and password when logging into
the terminal, either by using the login button or when accessing a secured
screen.

If the login is successful, the user has access to the application. The application
writes the access right and user name of the logged in user to the current
access right and current user name tags.

If the user name and password are invalid, the operation is aborted and an
error message is generated.

When the user presses the logout button, the application clears the current
access right tag and current user name tag.

After logging in, the user can move between secured and unsecured screens
for which the user account has access rights. The user is not prompted to
reenter the password.

If the user moves to a secured screen that he is not authorized to access, he is


prompted to enter a user name and password. If the correct user name and
password are entered, the user is granted access. Otherwise, access is denied
and a warning message is displayed.

Idle Mode Timeout

If the application does not receive user input within the specified idle timeout,
the terminal goes into Idle mode. User input includes key presses, touch screen
presses, external mouse, or keyboard input.

If the active screen is unsecured, the screen remains active.

If the active screen is a secured screen:


• the current user is logged off.
• the current access right tag is cleared.
• the application changes to the startup screen.

86 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 4 Secure the Terminal

Resetting the Terminal

After a terminal is reset, the application:


• displays the startup screen whether the last displayed screen was secured
or unsecured.
• enables security if it was previously disabled.
• retains changed passwords.
• The current user tag and current user rights tag is cleared when the
terminal resets.

Starting the Terminal in Safe Mode

If the terminal is started in safe mode, security is disabled. When the terminal
is restarted, security is enabled for the application.

Protected Mode Protected mode is a feature that enhances the security of a PanelView 800
terminal, and is available from firmware revision 3.011 onwards.

Protected mode restricts certain operations from being performed on the


terminal while it is running. This reduces the risk that the terminal may be
accessed by unauthorized persons, and disrupt the normal operations of the
terminal and other associated devices or processes.

When the terminal is in Protected mode, the following operations are blocked:
• ControlFLASH™ – Users cannot update the firmware of the terminal.
• Remote configuration change – Users cannot change the network
configuration of the terminal remotely.
• Remote reset – Users cannot reset the terminal remotely.
• Enable/disable ports – Users cannot enable or disable the
communication ports.

Protected mode is automatically disabled when an application is unloaded


successfully. When Protected mode is disabled, the operations listed above can
be then performed as normal.

IMPORTANT When a ControlFLASH operation is in progress, issuing a reset command


will not reset the terminal until after the firmware update has
completed.

The terminal automatically enters and exits Protected mode when certain
operations are performed, users do not need to configure any settings.

Terminal Operations and Protected Mode State


Operation Terminal in Protected Mode
During the boot-up process. Yes
After the boot-up process and the terminal displays a No
terminal configuration screen.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 87


Chapter 4 Secure the Terminal

Terminal Operations and Protected Mode State


Operation Terminal in Protected Mode
After the boot-up process and the terminal loads a startup Yes
application.
An application is loaded. Yes
An application is unloaded successfully and the terminal No
displays a terminal configuration screen.

To exit Protected mode, the running application has to be stopped and


unloaded successfully. To unload an application, go to the File Manager
configuration screen on the terminal and press the Stop Application button.

File Manager
Source: To:

Internal Internal Copy

Delete
PV800_App1

PVcApplication1 Set As Startup

Run

Stop Application
Recipe Copy Alarm History Controller Settings
Startup Application
Reset Main

IMPORTANT The Stop Application button is only available in firmware revision 3.011
onwards.

88 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 5

Virtual Network Computing

Virtual Network Computing Virtual Network Computing (VNC) allows you to remotely connect to a
(VNC) PanelView 800 terminal, either over the local network or the Internet. With
VNC you can interact with the terminal without having to be physically at the
terminal location. It transmits keyboard and mouse actions from your
computer to the terminal.

Guidelines for Using VNC


• We recommend that you enable only the view-only access to the
terminal. Enabling control access increases the security risk if the
password is compromised.
• Only one active VNC connection is supported and the terminal will reject
additional connection requests.
• For better performance when using VNC, we recommend that you use a
100 Mbps connection. Using a 10 Mbps connection may result in lower
performance, such as a slower refresh rate.
• If you are using a VNC Viewer application that supports configurable
refresh rate, set the minimum refresh rate to 500 milliseconds.
• Terminate the VNC connection before performing a firmware update as
it may interfere with the process.
• You cannot calibrate the touch screen using VNC. If you have triggered
the calibration process, you can press the “ESC” key on the keyboard to
cancel the procedure.
• The mouse action “Press and hold” is not supported over VNC.

Recommended VNC Clients There are many VNC viewer applications you can use to connect with the
and Settings terminal. These are the recommended VNC clients for use with PanelView 800
terminals.
Recommended VNC Clients and Settings
Client Name Remote Connection Type Recommended Settings
Change Preferred Encoding from “Tight” to “Hextile” for
Tight VNC PC/Laptop – Windows 7 smoother screen switching.
Mobile and Tablet – IOS None
Mobile and Tablet – Android None
Real VNC • Change Color Level from “pal8” to “Full” for a clearer
display.
PC/Laptop – Windows 7
• Change Security Notification Timeout from “2500” to
“0” in the client options.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 89


Chapter 5 Virtual Network Computing

Recommended VNC Clients and Settings (Continued)


Client Name Remote Connection Type Recommended Settings
• Disable the “32-bit color” option in the configuration
settings for a clearer display.
Mobile and Tablet – IOS
• Disable “Zoom to Screen height” option for a better
Mocha VNC screen view.
Mobile and Tablet – Android Enable the “8-bit color” option in the configuration
Mobile – Windows Mobile settings for a clearer display.
Ultra VNC PC/Laptop – Windows 7 None

Configure VNC Settings Follow these steps to configure the VNC settings for your terminal.
1. Go to the main configuration screen.

Main
Current Application
File Manager Goto

Config Language Date and Time


English Day Hour
Português 14 10
Terminal Setting
Français
Italiano Month Minute
Deutsch
1 30
Español
简体中文 Year Second
System Information
Reset Terminal 2015 56

2. Press Terminal Setting.

Terminal Setting

Communication

Display

Error Alert Display Settings

Print Settings
Main

90 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 5 Virtual Network Computing

3. Press Communication.

Communication
Protocol: * Disable DHCP
Status: Unavailable
Device Name: PV800T7T Set Static IP Address

Node Address: 0 VNC Settings


IP Mode: DHCP
Port Settings
IP Address: 0.0.0.0
Mask: 0.0.0.0 FTP Settings
Gateway: 0.0.0.0
MAC Address: XX:XX:XX:XX:XX Back

4. Press VNC Settings.

VNC Settings
Status:
Server: Enable / Disable
Server: Disabled

Access: View-Only / Control Access: View-Only

View-Only: Control:

Reset Password Reset Password

Back

VNC Settings
Setting Description Default
Server Enables or disables VNC connection to the terminal. Disabled
Switch between view-only and control access for the VNC
connection to the terminal.
Access(1) View-Only – No interaction allowed. Only the current screen on View-Only
the terminal is displayed.
Control – Interaction allowed.
Resets the current password a user must enter when
establishing a VNC connection to the terminal for view-only
View-Only Password access. No password(2)
The password is a maximum of seven alphanumeric
characters (A...Z, a...z, 0...9).
Resets the current password a user must enter when
establishing a VNC connection to the terminal for control
access.
Control Password The password is a maximum of seven alphanumeric No password(2)
characters (A...Z, a...z, 0...9) and special characters ('_', '$', '-',
and '!'). A minimum of one special character is required for
the control access password.
(1) We recommend that you enable only the view-only access to the terminal. Enabling control access increases the security risk if the
password is compromised.
(2) Once a password is set, you can only change it. You cannot clear a password unless you perform a restore operation or return the
terminal to the out-of-box condition. See Returning to the Out-of-box Condition on page 103 and Restoring the Terminal on
page 104 for instructions.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 91


Chapter 5 Virtual Network Computing

IMPORTANT Changing any VNC setting will terminate the current VNC connection to
the terminal. For example, if you are connected to the terminal in
control access and change the access to view-only, the VNC connection
will terminate and the next time you connect to the terminal you will be
in view-only access.

IMPORTANT When you update the terminal firmware, the VNC password and settings
will be cleared and reset to their default configuration.

Set the Password for VNC Connection


The default VNC settings (no password) prevents you from establishing a VNC
connection to the terminal. You must set a view-only or control access
password before you can connect to the terminal with the respective access
rights.

Follow these steps to set a password for VNC connection to the terminal.
1. Press Enable/Disable to enable the VNC server.
2. Press Reset Password for either View-Only or Control access.

VNC Settings
Status:
Server: Enable / Disable
Server: Enabled

Access: View-Only / Control Access: View-Only

View-Only: Control:

Reset Password Reset Password

Back

3. Type in the desired password using the on-screen keypad, then press
Enter.
New Password:

Confirm Password:
VNC Settings
Esc F1 F2 F3 F4 F5 F6 F7 F8 Status:
F9 F10 F11 F12 Home End
Server: Enable / Disable
Server: Enabled
` 1 2 3 4 5 6 7 8 9 0 - =
Access: View-Only / Control Access: View-Only
q w e r t y u i o p [ ] \
Caps a s d f g h j k l ; ’
View-Only: Control:
Shift z x c v b n m , . /
Reset Password Reset Password
Ctrl Win Alt ins del

Back

92 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 5 Virtual Network Computing

IMPORTANT If you forget the VNC password there is no way to recover it. You can
perform the restore terminal operation, or return the terminal to the
out-of-box configuration. Doing so will clear the password and also
remove all applications, logs, recipes, user-installed font files, objects
and graphics. See Returning to the Out-of-box Condition on page 103
and Restoring the Terminal on page 104 for more information.
Alternatively you can update the terminal firmware to clear the VNC
settings and reset to their default configuration.

Establish VNC Connection to Follow these steps to establish a VNC connection to the terminal. The
the Terminal TightVNC Viewer is used for the following examples. Your VNC viewer
application may have some differences.
1. Launch the VNC Viewer application.
2. Enter the IP address of your terminal and click Connect.

3. Depending on the type of access enabled on the terminal (view-only or


control), enter the corresponding password for that access type and click
OK.

A window opens on your desktop showing the current screen on the


terminal.
4. To terminate the VNC connection to the terminal, simply close the VNC.
Viewer application.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 93


Chapter 5 Virtual Network Computing

Notes:

94 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 6

Troubleshoot the System

Chapter Objectives This chapter provides information on how to isolate and correct common
operating problems with system components.
• View system information
• Alerts
• Troubleshooting

View System Information You can view current system information for the connected terminal. You
should provide this information when contacting technical support.
• Operating system version
• Firmware revision
• Hardware version number
• Status of the battery
• Total power on time
• Memory used in KBytes

Follow these steps to view the system information on your terminal.


1. Go to the PanelView Explorer Startup window.
2. Click the Terminal Settings link.
3. Click the System Information tab.
4. View the information.
5. Click Apply.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 95


Chapter 6 Troubleshoot the System

Alerts The terminal displays alerts at times during operation. The alert consists of an
ID number and a description. Follow the corrective action to resolve the alert.
PanelView 800 Terminal Alerts
Category ID Description Corrective Action
Check that the communication network cable is connected.
If new ladder logic is downloading to the controller, you could see
this message. After the download, communication should run
normally.
Verify you have good communication to the controller. If a remote
Data Access Error for Alias /*S:0 Param2*/, Controller /*S:0 device not responding alert was present, then all external tags being
Param3*/, Address is /*S:0 Param4*/, Communication Flag is / actively scanned will generate this alert.
Communication 2 *S:0 Param1*/ Is the address configured in the controller? If so, make sure all
The terminal is having trouble reading the external tag at this addresses of external tags to this controller are configured at the
controller and address. controller. If one address is outside of the range, a block of
addresses might show this condition. If the address is configured as
write-only at the controller, this address cannot be read. Set this
external tag as write-only and remove panel devices from your
application that want to display data from this external tag.
Contact technical support providing this data. ID1-/*S:0 Param1*/,
Communication 3 Communication Server Error ID2-/*S:0 Param2*/, P1-/*S:0 Param3*/
Reboot the terminal.
Contact technical support providing this data. ID1-/*S:0 Param1*/,
Communication 4 Communication Server Error ID2-/*S:0 Param2*/, P1-/*S:0 Param3*/, P2-/*S:0 Param4*/
Reboot the terminal.
Contact technical support providing this data. ID1-/*S:0 Param1*/,
ID2-/*S:0 Param2*/, P1-/*S:0 Param3*/, P2-/*S:0 Param4*/, P3-/
Communication 5 Communication Server Error *S:0 Param5*/
Reboot the terminal.
Contact technical support providing this data. ID1-/*S:0 Param1*/,
ID2-/*S:0 Param2*/, P1-/*S:0 Param3*/, P2-/*S:0 Param4*/, P3-/
Communication 6 Communication Server Error *S:0 Param5*/, P4-/*S:0 Param6*/
Reboot the terminal.
Contact technical support providing this data. ID1-/*S:0 Param1*/,
ID2-/*S:0 Param2*/, P1-/*S:0 Param3*/, P2-/*S:0 Param4*/, P3-/
Communication 7 Communication Server Error *S:0 Param5*/, P4-/*S:0 Param6*/, P5-/*S:0 Param7*/
Reboot the terminal.
Contact technical support providing this data. ID1-/*S:0 Param1*/,
ID2-/*S:0 Param2*/, P1-/*S:0 Param3*/, P2-/*S:0 Param4*/, P3-/
Communication 8 Communication Server Error *S:0 Param5*/, P4-/*S:0 Param6*/, P5-/*S:0 Param7*/, P6-/*S:0
Param8*/
Reboot the terminal.
Contact technical support providing this data. ID1-/*S:0 Param1*/,
Communication 9 Communication Server Error ID2-/*S:0 Param2*/
Reboot the terminal.
Verify you have good communication to the controller.
Verify that the communication network cable is connected.
If new ladder logic is downloading to the controller, you could see
Write Error for Alias /*S:0 Param2*/, Controller /*S:0 Param3*/, this message. After the download, communication should run
Address is /*S:0 Param4*/, Communication Flag is /*S:0 normally.
Communication 10 Param1*/ If a remote device not responding alert is present, then all external
The terminal is having trouble writing the external tag at this tags being written to will generate this alert.
controller and address. Is the address configured in the controller? If the address is
configured as read-only at the controller, this address cannot be
written to. Set this external tag as read and remove panel devices
from your application that can write data to this external tag.
Verify you have good communication to the controller.
Verify that the communication network cable is connected.
If new ladder logic is downloading to the controller, you could see
Read Error for Alias /*S:0 Param2*/, Controller /*S:0 Param3*/, this message. After the download, communication should run
Address is /*S:0 Param4*/, Communication Flag is /*S:0 normally.
Communication 11 Param1*/ If a remote device not responding alert was present, then all external
The terminal is having trouble reading the external tag at this tags being read from will generate this alert.
controller and address. Is the address configured in the controller? If the address is
configured as write-only at the controller, this address cannot be
read from. Set this external tag as write and remove panel devices
from your application that can read data from this external tag.

96 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 6 Troubleshoot the System

PanelView 800 Terminal Alerts (Continued)


Category ID Description Corrective Action
Verify all network connections are correct.
Verify that the communication network cable is connected.
If new ladder logic is downloading to the controller, you could see
this message. After the download, communication should run
normally.
Communication 27 Remote Device /*S:0 Param1*/ is Not Responding Verify that the network address of the controller matches the
terminal controller address configured in the Communication tab.
In the Communication tab, verify that the protocol specifications are
correct, such as communication rate, data bits, stop bits. These are
all protocol specific.
Communication 28 Invalid Data Address /*S:0 Param1*/ This is not syntactically a valid address.
This can occur when a write-only address for a controller has been
set for read/write in the external tag of the terminal. Param1 to
Bad address in block /*S:0 Param1*/ to /*S:0 Param2*/ on device
Communication 30 Param2 specifies the address block having the issue. Somewhere
/*S:0 Param3*/ within the range is where the write-only address is defined in a
PanelView external tag. Set the external tag to write.
This message is for informational purposes. No corrective action
Recipe 1001 Recipe upload started. needed.
Make sure that the recipe table is modified before the save operation
Recipe 1002 Recipe save failed. Cause: Recipe in Table has not been modified. is done.
This message is for informational purposes. No corrective action
Recipe 1003 Recipe save had errors. needed.
This message is for informational purposes. No corrective action
Recipe 1004 Recipe save completed successfully. needed.
This message is for informational purposes. No corrective action
Recipe 1005 Recipe download failed. Cause: Operation canceled. needed.
This message is for informational purposes. No corrective action
Recipe 1006 Recipe download started. needed.
This message is for informational purposes. No corrective action
Recipe 1007 Recipe download completed with errors. needed.
This message is for informational purposes. No corrective action
Recipe 1008 Recipe download completed successfully. needed.
Check for:
Communication errors.
Bad data point specification.
The ingredient value written is outside the Low EU and High EU limits
Recipe 1009 Recipe Download failed. Cause: Unable to write to /*S:0 Param1*/. of the numeric data point assigned. (These are optional OPC defined
properties representing data point minimum and maximum values).
The ingredient value could not be converted to the type of the data
point assigned.
This message is for informational purposes. No corrective action
Recipe 1010 Recipe upload completed with errors. needed.
This message is for informational purposes. No corrective action
Recipe 1011 Recipe upload completed successfully. needed.
This message is for informational purposes. No corrective action
Recipe 1012 Recipe restore failed. Cause: Operation canceled. needed.
Check for:
Communication errors
Bad status data point specification
The status data point for Recipe /*S:0 Param1*/ operation could The status value written is outside the Low EU and High EU limits of
Recipe 1013 not be written to. Data Point= /*S:0 Param2*/ the numeric data point assigned. (These are optional OPC defined
properties representing data point minimum and maximum values).
The status value could not be converted to the type of the data point
assigned
Recipe download failed. Cause: The value /*S:0 Param1*/ is less
Recipe 1014 than the minimum value /*S:0 Param2*/ allowed for ingredient / Correct the dataset value.
*S:0 Param3*/
Recipe 1015 Recipe /*S:0 Param1*/ failed. Cause: No Selector on display. Add a recipe selector device to the screen.
Recipe /*S:0 Param1*/ failed. Cause: No DataSet Selector on
Recipe 1016 Add a dataset selector device to the screen.
display.
Recipe 1017 Recipe /*S:0 Param1*/ failed. Cause: No Table on display. Add a Recipe Table Panel device to the Screen.
Recipe /*S:0 Param1*/ operation was not started because the Wait for a recipe operation to complete before starting the next
Recipe 1018 system is currently busy performing another Recipe operation. recipe operation.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 97


Chapter 6 Troubleshoot the System

PanelView 800 Terminal Alerts (Continued)


Category ID Description Corrective Action
Recipe /*S:0 Param1*/ failed. Cause: No recipe selected in
Recipe 1019 Select recipe and try again.
Selector.
Recipe /*S:0 Param1*/ failed. Cause: Data type of data point / Change the type of the ingredient to match the type of the data point,
Recipe 1020 *S:0 Param2*/ is incompatible with ingredient type of ingredient / or select a different data point which matches the type of the
*S:0 Param3*/. ingredient.
Recipe /*S:0 Param1*/ failed. Cause: Unable to read from /*S:0
Recipe 1021 Check the communication settings, and data point specification.
Param2*/
Recipe 1022 Recipe /*S:0 Param1*/ failed. Cause: Unable to read from Tag. Check the communication settings, and data point specification.
Recipe download failed. Cause: The value /*S:0 Param1*/ is
Recipe 1023 greater than the maximum value /*S:0 Param2*/ allowed for Correct the dataset value.
ingredient /*S:0 Param3*/
Recipe /*S:0 Param1*/ failed. Cause: Table does not contain a
Recipe 1024 Restore the recipe in the table before doing a save operation.
recipe.
Recipe /*S:0 Param1*/ of recipe /*S:0 Param2*/failed. Cause: · Try to reload the application to see if the recipe is still there, or
Recipe 1025 Recipe file not accessible. restore from a .cha file from your computer or SD card.
This message is for informational purposes. No corrective action
Recipe 1026 Recipe Upload Failed. needed.
This message is for informational purposes. No corrective action
Recipe 1027 Recipe operation in progress. needed.
This message is for informational purposes. No corrective action
Alert 2000 Loading. needed.
This message is for informational purposes. No corrective action
Alert 2001 Unloading. needed.
This message is for informational purposes. No corrective action
Alert 2002 Terminal is starting up... needed.
Alert 2003 Application is currently being edited, user input is disabled. Put the application into Test or Run mode to enable user input.
This message is for informational purposes. No corrective action
Alert 2004 Copying file... needed.
This message is for informational purposes. No corrective action
Alert 2005 Deleting file... needed.
This message is for informational purposes. No corrective action
Alert 2006 Operation failed. needed.
This message is for informational purposes. No corrective action
Alert 2007 Operation succeeded. needed.
Edit, validate, and then save the application with this version and try
Alert 2008 Cannot run application. Application version incompatible. again.
Terminal does not support the communication connection
Cannot run application. Communication connection not
Alert 2009 configured in this application. Edit the application and configure
supported. communication for the supported connection type.
If you do not want to run the invalid application, cancel the operation,
This application is not validated. Are you sure you want to run a
Alert 2010 then edit and validate the application. Correct all validation errors,
non-validated application? save the application, and try again.
Alert 2011 Cannot run a modified application. Save the application and try again.
Edit the application and save prior to performing this operation,
Alert 2012 Application has been modified. Continue without saving? otherwise changes to the application may be lost.
Currently loaded application has been modified. All changes will Edit the application and save prior to performing this operation,
Alert 2013 be lost by running this application. Continue? otherwise changes to the application may be lost.
Application was designed for a different terminal type and may
Alert 2014 not appear or operate as intended. Continue? Edit the application on the terminal type that it is intended for.
Alert 2015 Application will be unloaded and deleted. Continue? Click Yes to continue with operation.
Alert 2016 Confirm deletion? Click Yes to delete the file.
Alert 2017 Confirm restart? Press Yes to restart the terminal.
If you do not want to overwrite the file, cancel the operation and
Alert 2018 File already exists. Overwrite? rename the file before performing this operation.
Cannot copy over loaded application. Unload application and
Alert 2019 Click OK to unload and overwrite the application.
continue with overwrite?
Alert 2020 Cannot copy over loaded application. Unload application and try again.
Alert 2021 Insufficient space to complete file copy. Remove files to free space from the destination and try again.
Alert 2022 Source and destination cannot be the same. Verify the source and destination are not the same and retry.

98 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 6 Troubleshoot the System

PanelView 800 Terminal Alerts (Continued)


Category ID Description Corrective Action
Reconnect the designer or press OK to proceed to the configuration
Alert 2023 Application has been left in edit or test mode. screens.
Alert 2024 File not found. Verify the location of the file and try again.
Create the recipe through the designer or rename this recipe to the
Recipe 2025 Copy failed. Only existing recipe files can be updated. existing recipe name and try again.
The imported recipe must have the same number of ingredients and
Recipe 2026 Copy failed. Invalid recipe file. data sets as the existing recipe it is replacing.
Alarm 2027 Alarm logs can only be copied from a loaded application. Load the application into Edit, Test, or Run mode and retry.
Files can only be copied to a secured application while editing the The application has been secured with design rights. Load the
Alert 2028 application. application into Edit mode and retry.
Files can only be copied from a secured application while editing The application has been secured with design rights. Load the
Alert 2029 the application. application into Edit mode and retry.
Alert 2030 Cannot delete a loaded application. Unload application and try again.
Files can only be deleted from a secured application while editing The application has been secured with design rights. Load the
Alert 2031 the application. application into Edit mode and retry.
Press Yes to reboot the terminal and return to the out of box
Alert 2032 Return to out of box condition? condition.
Alert 2033 Source file does not exist. Make sure the source file exists and retry.
Alert 2034 Destination folder does not exist. Make sure the destination location exists and retry.
Remove files to free space by pressing the Delete File button on the
Alert 2035 Insufficient disk space. Free disk space and try again. File Transfer tab.
Press Yes to continue running the invalid application, or No to
This application is not validated. Are you sure you want to run a proceed to the configuration screens. Then, edit and validate the
Alert 2036 non-validated application? application. Correct all validation errors, save the application, and try
again.
Press Yes to continue setting the invalid application as a startup
This application is invalid. Continue setting as startup application, or No to proceed to the configuration screens. Then, edit
Aler 2037 application? and validate the application. Correct all validation errors, save the
application, and try again.
Cannot change password because password has been marked as Edit the application and go to the Security tab. Check the Modifiable?
Alert 2038 unmodifiable. box associated with the username and password.
Cannot change password because no user is logged onto the
Alert 2039 Log on as one of the users defined in the application and retry.
terminal.
Alert 2040 Old password does not match the password for the current user. Enter the current user’s password for the Old Password.
Alert 2041 Cannot reset password, this is an unknown user. Log on as one of the users defined in the application and retry.
Cannot change password, new and confirm passwords don't Verify the new password matches the confirmed password and
Alert 2042 match. retry.
The username/password is either incorrect or the user does not
Alert 2043 Access Denied have the access right for the associated screen.
Alert 2044 Cannot run application while in Safe mode. Reboot the terminal to exit Safe mode and retry.
Alert 2045 Cannot run applications from external storage. Copy or save to internal storage and try again.
The change password and reset password devices are only enabled
Alert 2046 Passwords cannot be modified while in test mode. while in Run mode.
Alert 2047 File is read-only. Continue? Choosing to continue will overwrite the read-only file.
Edit the application and save prior to performing this operation,
Alert 2048 Application has been modified. Continue? otherwise changes to the application may be lost.
Alert 2049 Allow firmware update? Press Yes to continue with the firmware update.
Enter a value within the allowable range. If you do not know the
Alert 2050 The value is not within the minimum and maximum range. range Edit the application to determine the allowable range for the
device.
Alert 2051 Allow Autorun? Press No to disallow Autorun.
Press No to disallow Autorun. Edit the application and save prior to
Alert 2052 Application has been modified. Allow Autorun? performing this operation, otherwise changes to the application may
be lost.
Screen navigation devices are disabled if the screen has been
Alert 2053 Screen switching controlled by external source. changed to via controller.
Terminal reboot is disabled on the emulator. Select Flash>Save and
Alert 2054 Cannot reset the terminal in Safe mode. then select File>Reset>Hard to reboot the emulator.
Alert 2055 Image exceeds maximum resolution of 800x800. Open file in image editor and reduce the resolution.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 99


Chapter 6 Troubleshoot the System

PanelView 800 Terminal Alerts (Continued)


Category ID Description Corrective Action
Alert 2056 Cannot copy recipe to a loaded application. Unload application and try again.
Terminal is running low on application memory
Alert 2057 Reset the terminal or this may lead to fatal error.
(<Available_Virtual_Memory>bytes).
Verify the range of the numeric display that uses the external tag as
its write tag is within the range of a tag (validation should provide a
warning if the range of the tag is greater than the range of a numeric
Failed setting property: /*S:0 Param1*/::/*S:0 Param2*/, value = entry). Make sure that the values of the state based objects that write
Alert 2058 /*S:0 Param3*/ to an external tag are within the range of the tag. Make sure that the
value that written to an external tag matches the tag type (for
example, do not write a non-numeric string into a numeric tag).
Make sure the Ethernet port is enabled.
Verify the range of the numeric display that uses the external tag as
its write tag is within the range of a tag (validation should provide a
warning if the range of the tag is greater than the range of a numeric
Failed setting property (/*S:0 Param1*/): /*S:0 Param2*/::/*S:0
Alert 2059 entry). Make sure that the values of the state based objects that write
Param3*/, value = /*S:0 Param4*/ to an external tag are within the range of the tag. Make sure that the
value that written to an external tag matches the tag type (for
example, do not write a non-numeric string into a numeric tag).
Alert 2060 Terminal is running low on RAM (<Available_RAM>bytes). Reset the terminal or this may lead to fatal error.
This is a out of memory critical message. Dismissing this dialog
causes the terminal to reset.
Alert 2061 Out of memory: Terminal cannot continue to run and will be reset. After the terminal resets, try to edit an application and reduce its size
by removing some objects, for example, user controls, screens, tags,
or alarms.
Alert 2062 Cannot copy recipe to a loaded application. Unload application and try again.
Alert 2064 Cannot enter Safe Mode while terminal security is enabled. Disable terminal security and try again.
Alert 2065 Table has changed. Do you want to continue? Press Yes to continue with the changed Recipe table.
Make sure a microSD card or USB device is connected to the terminal
Alert 2066 Logging Error
to store the datalog.
Alert 2067 Invalid filename Make sure filename is valid.
Alert 2068 Only one Trend with data logging is allow Make sure the application only has one Trend with data logging.
Alert 2069 Landscape Orientation. Confirm Restart? Select No to restart later.
Alert 2070 Portrait Orientation. Confirm Restart? Select No to restart later.
Press Yes to continue, or No to cancel. Then change the orientation
Application was designed for a different Orientation and may not
Alert 2071 of the application in Connected Components Workbench software to
appear or operate as intended. Continue? match the terminal and try again.
Application was designed for a different Platform type and Press Yes to continue, or No to cancel. Then change the catalog of
Alert 2072 Orientation, and may not appear or operate as intended. the application in Connected Components Workbench software to
Continue? match the terminal and try again.
Non-validated application is not supported for CompactLogix Validate the application and correct any validation errors, save the
Alert 2073 controller. Validate before loading application, then try again.
This message is for informational purposes. No corrective action
Alert 2074 Terminal encountered an exception and will reboot needed.
Alert 2075 Application will be unloaded. Confirm (Y/N)? Press Yes to unload the application.
Press Yes to continue setting the application as a startup application,
This application does not have at least one Goto Config button. Set
Alert 2076 or No to cancel. Edit the application and make sure there is at least
as Startup Application? one Goto Config button.
Alert 2077 Controller Settings cannot be changed for running application. Stop the application and try again.
Controller address cannot conflict with PanelView 800 terminal Make sure the controller address is different from the PanelView 800
Alert 2078 Station Address. terminal station address.
CompactLogix controller based application must contain valid
Alert 2079 Make sure a valid path exists and try again.
path.
Invalid View-Only password. Password should not contain any Make sure the View-Only password does not contain any special
Alert 2080 special character. characters.
Alert 2081 Old password does not match with terminal. Make sure the correct password is entered in the Old Password field.
Alert 2082 VNC Server error. Restart the terminal and try again.
Controller address cannot be larger than PanelView 800 terminal Make sure the address of the controller is smaller than the maximum
Alert 2083 Max Node('31'). node of PanelView 800 terminal(’31’).
Alert 2084 Password cannot be empty. Enter valid password.
Alert 2085 Enable Ethernet port. Confirm Restart? Press Yes to restart the terminal.
Alert 2086 Disable Ethernet port. Confirm Restart? Press Yes to restart the terminal.

100 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 6 Troubleshoot the System

PanelView 800 Terminal Alerts (Continued)


Category ID Description Corrective Action
Alert 2087 Enable Serial port. Confirm Restart? Press Yes to restart the terminal.
Alert 2088 Disable Serial port. Confirm Restart? Press Yes to restart the terminal.
Alert 2089 Cannot disable both communication port. Make sure at least one communication port is enabled.
Alert 2090 Invalid Control password. Password must contain at least one special character.
Alert 2091 VNC Server is Disabled. Enable VNC Server to change/reset password.
Alert 2092 Ethernet port is disabled. Go to Port Settings on the terminal to enable the Ethernet port.
Alert 2093 Serial port is disabled. Go to Port Settings on the terminal to enable the Serial port.
Alert 2094 Existing VNC client connection will be terminated. Confirm (Y/N)? Press Yes to terminate the VNC connection, or No to cancel.
Alert 2095 Cannot edit recipe for running application. Unload the application and try again.
Alert 2096 Recipe with the same name already exists Make sure the recipe name is unique.
Recipe Name cannot contain more than 31 characters. Choose
Alert 2097 Make sure the recipe name does not exceed 31 characters.
another name.
The Name cannot be blank and must contain only alphanumeric Make sure the name contains only alphanumeric characters plus
Alert 2098 characters plus [ $'@!()_- ]. [ $'@!()_- ].
Deletion of a recipe in a design secured application is not allowed.
Alert 2099 Make sure the application is not design secured.
See Copy or Edit Recipes on page 22.
Renaming of a recipe in a design secured application is not
Alert 2100 Make sure the application is not design secured.
allowed. See Copy or Edit Recipes on page 22.
Alert 3001 Available memory is too low to run the application. Try to release some memory or this may lead to fatal error.
Language switch ignored. Application was not configured with Either add the specified language and associated strings or remove
Multilanguage 8193 new language. An attempt was made to switch to a language that the unconfigured language selection.
is not configured for this application.

Troubleshooting If your terminal does not startup correctly, check for adequate power, observe
the splash screen state message and status code, indicator states, or an
application that is not running during power-up.

Determine what changed since the last time the terminal ran normally and
decide if the change can be reversed.

Check for Adequate Power

A terminal that does not receive adequate power could cause unpredictable
behavior. Verify the power requirements in the Specifications table.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 101


Chapter 6 Troubleshoot the System

Observe Splash Screen

Various actions and status conditions of the terminal are reported on the
splash screen, including version information about the hardware and
firmware.

State Message Status or Error


Code

Boot Loader ©2014 Rockwell Automation, Inc. Progress Bar


Version
All Rights Reserved.

AUTOTEST E6

BL 2.010 HW 03 COMM 2.010


OS 2.010 APP 2.010 FONT 2.010

Hardware
Firmware
Version
revision

These tables describe the state messages and the status or error codes that
appear on the splash screen.
Power on Self Test (POST) Failures
Message State Code
POST Failed RAM Fatal 6C
POST Stuck Key Fatal 31
POST Stuck Touch Fatal 3A

Firmware Installation and Loading


Message State Code
Load Firmware Image into RAM Update 1E
Write Firmware Image into Flash Update A5
Complete and Successful Firmware Installation Update OK
Firmware Image Validation (CRC/Format) Failure Fatal 1E
Firmware Image Compatibility Failure Fatal 1F
Firmware Write to Flash error Fatal A5
Firmware Read-After-Write Verify Fatal D2
Invalid or missing Firmware Image Fatal 0A

Other Commonly Observed Status Codes


Message State Code
Boot Loader connects to PC via USB Device AutoTest 0A
Boot Loader loads Firmware Image into RAM AutoTest E6
Boot Loader jumps to Operating System AutoTest FF
Operating System startup Boot G0
Operating System Initialize Init I1…J0
Application Registration and Initialize Init N1…N3
Application Load and Execute Load N4…N6

POST errors are fatal and most likely due to failed hardware. A fatal error
during firmware installation and loading is most likely recoverable by
installing the appropriate firmware.
102 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021
Chapter 6 Troubleshoot the System

Interpret the LED Indicators at Startup

The PanelView 800 terminals have indicators to isolate operating problems.


They can be seen through the battery cover on the back of the unit.
• Comm indicator for communication
• Fault indicator for hardware faults

At startup, the Fault indicator is off, except for a few brief flashes, and the
Comm indicator is on. If the indicators remain off, check the power cable.
After a successful startup, both indicators are off and controlled by the
application running on the terminal.

The table shows indicator states if the terminal stops during startup.
Fault Indicator States During Startup
Fault (Red) Comm (Green) Description Recommended Action
Indicator State Indicator State
Potentially recoverable errors
Blinking Off Last firmware download failed. Reload the firmware.
EBC boot loader firmware failed or Reload the firmware.
Blinking Blinking is missing.
Windows CE OS firmware failed or is Reload the firmware.
Blinking On missing.
Nonrecoverable or fatal errors
On Off Fatal hardware error. Replace the terminal.

Returning to the Out-of-box You may want to return a terminal to the out-of-box condition to refresh the
Condition terminal or to recover from severe application misbehavior. There is a special
maintenance action that permits you to perform a complete reset and return
to the out-of-box condition for the terminal.

Returning a terminal to an out-of-box condition does not affect the terminal


firmware revision or the installed font image.

Follow these steps to return your terminal to the out-of-box condition.


1. Connect an external USB keyboard to the terminal and hold the Ctrl and
Shift keys simultaneously, while starting up the terminal.

A dialog box appears with the prompt:


Return to Out of Box Condition?

IMPORTANT Keyboards initialize at different times. If the terminal boots normally to


the configuration screen or the selected startup application, the
keyboard press was not recognized.
Restart the terminal and wait until the boot screen displays the INIT
code N1, then press and hold the Ctrl and Shift keys until the dialog box
appears.
2. Press Yes or F1 to return to the out-of-box condition, or press No or F2 to
cancel.

If you choose to return to the out-of-box condition, the terminal resets.


On the subsequent boot, the file system is formatted and removes the
contents including applications, logs, recipes, user-installed fonts,

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 103


Chapter 6 Troubleshoot the System

objects, and graphics. Most terminal configuration parameters are


returned to their default values.

IMPORTANT Returning to the out-of-box condition does not change the current
firmware on your terminal. If you upgraded the firmware on your
terminal, the upgraded firmware revision remains unaffected. See
Firmware Installation Using Removable Storage Device on page 115 for
details on what is included in a firmware upgrade.

IMPORTANT If you have forgotten your terminal or VNC password, you can use this
procedure to restore your terminal. Remember, it will remove all
applications, logs, recipes, user-installed font files, objects, and
graphics.

Restoring the Terminal This function enables you to clear all the contents of the terminal and reset
certain settings to their default value using the Restore button. This function is
similar to returning the terminal to the out-of-box configuration.

IMPORTANT If you have forgotten your terminal or VNC password, you can use this
procedure to restore your terminal. Remember, it will remove all
applications, logs, recipes, user-installed font files, objects, and
graphics.
Settings Cleared or Reset to Default When Using Restore or Out-of-Box Condition
Setting Restore Out-of-Box Condition
Applications Y Y
Terminal Startup Application Y Y
User-Installed Font Files Y Y
Screensaver Y Y
VNC Settings Y Y
Port Settings Y Y
FTP Settings Y Y
Print Settings Y Y
Network Credentials Y Y
Terminal Password Y Y
DHCP Option N Y
IP address N Y
Subnet Mask N Y
Display Brightness N Y
Display Timeout N Y
Terminal Name N Y

Follow these steps to restore the terminal.

104 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Chapter 6 Troubleshoot the System

1. While the terminal is not powered, use a small pointed object to press
and hold the Restore button located underneath the battery cover.

Restore button

2. Power up the terminal.


3. Wait until the fault indicator lights up solid red, or the text “GO” is
displayed on the screen before releasing the Restore button.
©2016 Rockwell Automation, Inc.
All Rights Reserved.

BOOT GO

4. Wait for a few minutes until the process is completed.


5. When the restore process is completed, the terminal will boot into the
main configuration screen.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 105


Chapter 6 Troubleshoot the System

Notes:

106 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Appendix A

Specifications

General Specifications
Attribute 2711R-T4T 2711R-T7T 2771R-T10T
Display type Color transmissive TFT active matrix LCD, wide screen format
Display size 4 in. 7 in. 10 in.
Display area 95 x 53.9 mm (3.74 x 2.12 in.) 153.6 x 86.6 mm (6.05 x 3.41 in.) 211.2 x 158.4 mm (8.31 x 6.24 in.)
Resolution (pixels) 480 x 272 800 x 480 800 x 600
Backlight lifespan, min 40,000 hours
Operator input Analog touch and function keys Analog touch
USB port and
Memory card microSD (Secure Digital) card – Industrial grade microSD cards recommended. Supports SDSC and Class 6 & Class 10 SDHC microSD cards,
FAT32/16 formats, up to 32 GB maximum size.
Programming port Ethernet port
Battery lifespan, min 5 years @ 25 °C (77 °F)
Real-time clock Yes
Input voltage range 18…32V DC (24V DC nom)
Power consumption, max 9 W (0.39 A @ 24V DC) 11 W (0.40 A @ 24V DC) 14 W (0.48 A @ 24V DC)
Weight, approx. 0.333 kg (0.73 lb) 0.651 kg (1.44 lb) 1.64 kg (3.62 lb)
116 x 138 x 43 mm 144 x 197 x 54 mm 225 x 287 x 55 mm
Dimensions (HxWxD), approx. (4.56 x 5.43 x 1.69 in.) (5.67 x 7.75 x 2.11 in.) (8.86 x 11.3 x 2.16 in.)
Input Power Terminal Block
Stranded or solid, Cu 90 °C (194 °F)
Wire size Single-Wire Gauge: 0.33…2.08 mm2 (22...14 AWG)
Dual-wire Gauge: 0.33…1.31 mm2 (22…16 AWG)
Wire type Copper
3 – on power ports
Wiring category(1) 2 – on communication ports
Enclosure type ratings Meets NEMA/UL Type 4X (indoor) 12, 13, and IP65
North American temp code T4A
(1) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental
Attribute Value
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
Temperature, operating IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0…50 °C (32…122 °F)
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
Temperature, nonoperating IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-25…+70 °C (-13…+158 °F)
Temperature, surrounding air, max 50 °C (122 °F)
Heat dissipation
2711R-T4T 23 BTU/hr
2711R-T7T 34 BTU/hr
2711R-T10T 61 BTU/hr

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 107


Appendix A Specifications

Environmental (Continued)
Attribute Value
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
Relative humidity 5…95% noncondensing
IEC 60068-2-6 (Test Fc, Operating):|
Vibration 2 g @ 10…500 Hz
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
Shock, operating 15 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
Shock, nonoperating 30 g
Emissions IEC 61000-6-4
IEC 61000-4-2:
ESD Immunity 4 kV contact discharges
8 kV air discharges
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
Radiated RF Immunity 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
IEC 61000-4-4:
EFT/B Immunity ±2 kV @ 5 kHz on power ports
±1 kV @ 5 kHz on communication ports
IEC 61000-4-5:
Surge Transient Immunity ±500V line-line(DM) and ±500V line-earth(CM) on DC power ports
±1 kV line-earth(CM) on communication ports
IEC 61000-4-6:
Conducted RF Immunity 10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications
Certifications (when product is
Value
marked) (1)
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E322657.
c-UL-us UL Listed for Class I, Division 2 Group A, B, C, D Hazardous Locations, certified for U.S. and Canada. See UL File E334470.
European Union 2004/108/EC EMC Directive, compliant with:
CE EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
Australian Radiocommunications Act, compliant with:
RCM AS/NZS CISPR 11; Industrial Emissions
Korean Registration of Broadcasting and Communications Equipment, compliant with:
KC Article 58-2 of Radio Waves Act, Clause 3
(1) See the Product Certification link at rok.auto/certifications for Declarations of Conformity, Certificates, and other certification details.

108 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Appendix B

Upgrade Firmware

Chapter Objectives This chapter provides topics on how to upgrade firmware in the terminal.
• Prepare for firmware upgrade
• Upgrade firmware using ControlFLASH
• Upgrade firmware using a removable storage device

The firmware upgrade runs an executable script on a removable storage device


such as a USB flash drive or a microSD card that copies a firmware image into
the flash memory of the terminal.

Prepare for Firmware Follow these steps before starting a firmware upgrade.
Upgrade
IMPORTANT The PanelView Explorer feature is only supported on PanelView 800
terminals with firmware revision 2.020 or earlier. It is not supported
from firmware revision 3.011 onwards.

IMPORTANT From firmware revision 3.011 onwards, the terminal must not be in
Protected Mode when performing a firmware upgrade. For more
information, see Protected Mode on page 87.

IMPORTANT When you perform a firmware upgrade, your terminal password, VNC
settings, port settings, FTP server setting, and print settings will all be
cleared and reset to their default configuration.

IMPORTANT Terminate the VNC connection before performing a firmware update as


it may interfere with the process.
1. Backup applications and library objects from the terminal.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 109


Appendix B Upgrade Firmware

2. Click Stop to unload the currently loaded application.


The stop sign is shown when an application is loaded and in Test/Run
mode.
Click to stop and unload application

To stop an application from the terminal, go to the File Manager


configuration screen and press the Stop Application button.

File Manager
Source: To:

Internal Internal Copy

Delete

Set As Startup

Run

Stop Application
Recipe Copy Alarm History Controller Settings
Startup Application
Reset Main

IMPORTANT The Stop Application button is only available in firmware revision


3.011 onwards.

If you have not saved changes to the application, you are prompted to do
so. Once the application is unloaded, the terminal displays the
Configuration screen.
3. Close the web browser connected to the terminal.

110 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Appendix B Upgrade Firmware

4. Verify the existing firmware revision of the terminal by looking in the


System Information screen, and compare to the firmware revision of the
file to make sure you are performing the desired upgrade.

System Information
Firmware Version: 4.013.000
Boot Code Version: 4.011.000
Logic Board Version: 4
Terminal On Time: 102,330
Display On Time: 102,330
Battery Status: Good

Memory Usage (bytes)


Internal Used: 1,392,640
Internal Free: 164,741,120
Advanced
Application Used: 31,600,640
Application Free: 193,994,752 Main

See View System Information on page 42 for instructions on how to view


the current firmware revision.

Upgrading Firmware Using The ControlFLASH software is included with the Connected Components
ControlFLASH Workbench software and can be installed or updated when you install
Connected Components Workbench software on your computer. You can also
launch ControlFLASH software within Connected Components Workbench
software version 11 and later.

ATTENTION: Changing the firmware will likely change the behavior of the
terminal. Be aware of the firmware revision for the terminal versus the new
firmware that is on the computer, and be informed of the expected behavior
after the new firmware is installed on the terminal.

For ControlFLASH 13.00 or higher, you can save the downloaded firmware, which
is in DMK format, in one of the default monitored folders before launching
ControlFLASH.
The default monitored folders are typically at:
C:\Progam Files (x86)\ControlFLASH
C:\Users\(username)\Downloads\RA
If you save the firmware file to a different folder, you must add that folder to the
list of monitored folders during the upgrade process. See the details in step 3
for more information.
Follow these steps to upgrade the firmware using ControlFLASH.
1. Verify that the terminal is connected to your computer either through
Ethernet or USB.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 111


Appendix B Upgrade Firmware

2. In Connected Components Workbench software, click Tools ->


ControlFLASH
Alternatively, launch ControlFLASH.

3. Click Next.

4. Select the catalog number for the terminal that you are updating and
click Next.

If you are using ControlFLASH version 13.00 or higher and the catalog
number is not listed, you may need to add a monitored folder for
firmware kits. Follow these steps to do add a monitored folder:
a. Click Browse.
The Firmware Kit Locations dialog box appears.
b. Click Add.
c. Select the folder that contains the firmware DMK file, and then
click OK.
d. Click OK to close the Firmware Kit Locations window.

112 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Appendix B Upgrade Firmware

5. Select the terminal in the connection browser window and click OK.

6. Select the firmware revision to flash and click Next.

7. Verify your selections and click Finish.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 113


Appendix B Upgrade Firmware

8. Click Yes to start the updating process.

A screen showing the progress appears.

9. When the update process is complete, the terminal will automatically


restart.
10. After the terminal has restarted, a screen showing the update status
appears. Click OK to continue.

11. Open the system information screen on the terminal to verify that the
new firmware revision is correct.

System Information
Firmware Version: 5.011
Boot Code Version: 4.011
Logic Board Version: 4
Terminal On Time: 102,330
Display On Time: 102,330
Battery Status: Good

Memory Usage (bytes)


Internal Used: 1,392,640
Internal Free: 164,741,120
Advanced
Application Used: 31,600,640
Application Free: 193,994,752 Main

See View System Information on page 42 for instructions on how to view


the current firmware revision.

114 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Appendix B Upgrade Firmware

Firmware Installation Using The terminal can install firmware from a removable storage device; either a
Removable Storage Device USB flash drive or a microSD card. The firmware consists of an Autorun
executable and firmware image that is downloaded from the PanelView 800
technical support website.

https://www.rockwellautomation.com/en-us/products/hardware/allen-
bradley/human-machine-interface/graphic-terminals/2711r-PanelView-
800.html.

The firmware installation starts when the storage device is inserted either
while the terminal is running, or when the terminal is powered on. During the
firmware installation, you can upgrade or downgrade the firmware. The
firmware image consists of the following components:
• Windows CE Operating System
• Application
• Communication
• Asian font (Simsun – Simplified Chinese)

The terminal has a firmware partition that accommodates one user-


installable Asian font. A Simsun Chinese font is factory-installed.

The currently installed Asian font firmware image is visible in the list of
Configuration Languages on the Main Screen.

ATTENTION: Removing the USB flash drive or microSD card, from the
PanelView 800 terminal, while a firmware upgrade is in process, could
corrupt the firmware and make the terminal unusable. Take precautions to
prevent the USB flash drive or microSD card from being accidentally
disconnected. Also, do not power off the terminal while a firmware upgrade is
in progress, or during the subsequent boot-up process that follows the
firmware upgrade.
ATTENTION: USB hubs can produce unexpected behaviors and as a result
are not recommended.
The firmware revision consists of a major revision number, a minor revision
three-digit number, and a build revision three-digit number, separated by a
period (for example, 01.234.567 where 01 is the major, 234 is the minor, and
567 is the build). The build revision number is for internal use only. The
firmware revision for the terminal is displayed on the System Information
screen.

After upgrading your firmware, you should clear your browser cache.
To clear cache in the Firefox browser, select Tools > Clear Private Data. Verify
the Cache checkbox is checked and click the Clear Private data button.
To clear cache in the Internet Explorer browser, select Tools > Internet
Options. On the General tab, click the Delete button under Temporary Internet
Files to delete all temporary Internet files, including offline content.

ATTENTION: Changing the firmware will likely change the behavior of the
terminal. Be aware of the firmware revision for the terminal versus the new
firmware that is on the computer, and be informed of the expected behavior
after the new firmware is installed on the terminal.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 115


Appendix B Upgrade Firmware

Prepare the Storage Device

Follow these steps to prepare the storage device to transfer firmware files.
1. Insert the storage device into a USB host port or microSD card slot on
your computer.
2. Open a web browser and access the PanelView 800 technical support
website at https://www.rockwellautomation.com/en-us/products/
hardware/allen-bradley/human-machine-interface/graphic-terminals/
2711r-PanelView-800.html.
3. Locate the new firmware file.
4. Observe the firmware revision information that is in the name of the
firmware file and confirm that this is the new, desired firmware.
5. Download the firmware file to a folder on your computer, then open the
file and unpack the contents of the firmware file to a microSD card or
USB flash drive root directory.

Install the Firmware from the Storage Device

Follow these steps to transfer firmware files from a storage device.


1. Open the system information screen on the terminal to verify that the
new firmware revision is correct.

System Information
Firmware Version: 3.011.000
Boot Code Version: 2.020.000
Logic Board Version: 4
Terminal On Time: 102,330
Display On Time: 102,330
Battery Status: Good

Memory Usage (bytes)


Internal Used: 1,392,640
Internal Free: 164,741,120
Advanced
Application Used: 31,600,640
Application Free: 193,994,752 Main

See View System Information on page 42 for instructions on how to view


the current firmware revision.
2. Insert the storage device into the USB host port or microSD card slot on
your terminal.
3. When prompted to run the Autorun, press Yes or the F1 key.

The splash screen appears and the progress bar indicates a firmware
installation is in process.

IMPORTANT Do not remove the microSD card or USB flash drive until upgrade - OK is
displayed.

When the firmware installation is complete and successful, the progress


bar stops with the success code OK.
4. The terminal will automatically restart to complete the process.

116 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Appendix B Upgrade Firmware

5. Open the system information screen to see the firmware revision that is
expected after the installation.

System Information
Firmware Version: 3.011.000
Boot Code Version: 2.020.000
Logic Board Version: 4
Terminal On Time: 102,330
Display On Time: 102,330
Battery Status: Good

Memory Usage (bytes)


Internal Used: 1,392,640
Internal Free: 164,741,120
Advanced
Application Used: 31,600,640
Application Free: 193,994,752 Main

See View System Information on page 42 for instructions on how to view


the current firmware revision.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 117


Appendix B Upgrade Firmware

Notes:

118 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Appendix C

Install and Replace Components

Chapter Objectives This chapter shows how to install, replace, or upgrade various components of
the PanelView 800 terminals.
• microSD memory card
• USB flash drive
• Battery replacement

microSD Memory Card The microSD memory card can be inserted in the following locations on the
PanelView 800 terminals.

2711R-T4T 2711R-T7T 2711R-T10T

microSD memory card slot

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 119


Appendix C Install and Replace Components

USB Flash Drive The USB flash drive can be inserted in these locations on the terminals.

2711R-T4T

2711R-T7T

USB host port

2711R-T10T

Battery Replacement The PanelView 800 terminals contain a lithium battery that is intended to be
replaced during the life of the product. The battery provides battery backup for
the real-time clock. It is not used for application backup or retention.

WARNING: Verify that power has been removed from the terminal prior to
replacing the battery. Work in a static free environment and wear a properly
grounded electrostatic discharge (ESD) wristband.

Be careful when touching any of the exposed electronic components to prevent


damage from ESD.

WARNING: To avoid the danger of explosion, only replace the battery with
2711P-RY2032 or a manufacturer’s equivalent such as the Matsushita or Duracell
DL2032.

For safety information on the handling of lithium batteries, see the Guidelines for
Handling Lithium Batteries, publication AG-5.4.

Do not dispose of battery in a fire or incinerator. Dispose of used batteries in


accordance with local regulations.

120 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Appendix C Install and Replace Components

WARNING: When you connect or disconnect the battery an electrical arc can
occur. This could cause an explosion in hazardous location installations. Be sure
that the area is nonhazardous before proceeding.

For Safety information on the handling of lithium batteries, including handling


and disposal of leaking batteries, see Guidelines for Handling Lithium Batteries,
publication AG-5.4.
Do not dispose of battery in a fire or incinerator. Dispose of used batteries in
accordance with local regulations.

ATTENTION: Battery contains Perchlorate Material – Special handling may


apply.
See https://dtsc.ca.gov/perchlorate/.

This perchlorate warning only applies to primary Lithium Manganese Dioxide


(LiMnO2) cells or batteries, and products containing these cells or batteries,
sold or distributed in California, USA.

The battery is on the back of the terminals. No special tools are required to
remove the battery cover, but a flat-tip screwdriver may be required to remove
the battery.

Battery cover

This equipment is sensitive to electrostatic discharge (ESD). Follow ESD


prevention guidelines when handling this equipment.

Battery

Battery cover

This equipment is sensitive to electrostatic discharge (ESD). Follow ESD


prevention guidelines when handling this equipment.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 121


Appendix C Install and Replace Components

Notes:

122 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Appendix D

Cable Connections and Communication

Chapter Objectives This chapter provides network and device connections for the terminals.
• Wiring and safety guidelines
• Connecting devices
• MicroLogix™ controller cable charts
• Micro800 controller cable charts
• CompactLogix 5370 controller cable charts
• Ethernet connection
• Serial connections
• USB Ports

Wiring and Safety Guidelines Use publication NFPA 70E Electrical Safety Requirements for Employee
Workplaces, IEC 60364 Electrical Installations in Buildings, or other applicable
wiring safety requirements for the country of installation when wiring the
devices. In addition to the NFPA guidelines:
• connect the device and other similar electronic equipment to its own
branch circuit.
• protect the input power by a fuse or circuit breaker rated at no more than
15 A.
• route incoming power to the device by a separate path from the
communication lines.
• cross power and communication lines at right angles if they must cross.

Communication lines can be installed in the same conduit as low-level


DC I/O lines (less that 10V).
• shield and ground cables appropriately to avoid electromagnetic
interference (EMI).

Grounding minimizes noise from EMI and is a safety measure in


electrical installation.

For more information on grounding recommendations, see the National


Electrical Code published by the National Fire Protection Association.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 123


Appendix D Cable Connections and Communication

Connecting Devices Use these cables for connecting devices to PanelView 800 terminals.
Cables for PanelView 800 Terminals
Cat. No. Description
2711P-CBL-EX04 Ethernet crossover CAT5 cable 4.3 m (14 ft)
1747-CP3 Serial 9-pin D-shell to 9-pin D-shell null modem cable
1761-CBL-PM02 Serial 9-pin D-shell to 8-pin mini DIN cable, 2 m (6.56 ft)
2711C-CBL-AB03 RS-485 5-pin to RJ45 cable
1763-NC01 Series A 8-pin Mini DIN to 6-pin RS-485 terminal block

MicroLogix Controller Cable The chart provides a summary of terminal connections to controllers and
Charts network interface modules.

PanelView 800 Terminal Connections to MicroLogix Controllers


MicroLogix MicroLogix MicroLogix
(8-pin Mini DIN) 1000,
Protocol PanelView 800 Port (9-pin D-shell) 1500LRP 1100/1400 RS-485 (1763- MicroLogix
1100, 1400, 1200LSP, 1100/1400 Ethernet
(Ch 1) NC01)
1500LSP (Ch 0)
DF1 RS-232 1761-CBL-PM02 1747-CP3 — —
Use AIC+ module (1761-NET-
RS-232 1761-CBL-PM02 1747-CP3 —
AIC) connect to port 3
DH-485
Belden 3106 A or #9842 or
RS-485(1) — — equivalent —
Use AIC+ module (1761-NET-
Modbus RS-232 1761-CBL-PM02 1747-CP3 —
AIC) connect to port 3
Ethernet (MicroLogix/ENI) Ethernet — — — CAT 5 Ethernet
(1) RS-485 is isolated. We recommend that you connect only one device. Multi-node communication is supported when appropriate hardware, such as 1747-AIC or AIC+ is added to the wiring.

Micro800 Controller Cable The chart provides a summary of terminal connections to controllers and
Charts network interface modules.

PanelView 800 Terminal Connections to Micro800 Controllers


Protocol PanelView 800 Port Micro820® Micro830® Micro850®/Micro870®
RS-232 –(1) 1761-CBL-PM02 1761-CBL-PM02
Modbus RS-485(2) –(2) –(2) –(2)
Ethernet 2711P-CBL-EX04 (CAT5 Ethernet) — 2711P-CBL-EX04 (CAT5 Ethernet)
Ethernet (AB CIP) Ethernet 2711P-CBL-EX04 (CAT5 Ethernet) — 2711P-CBL-EX04 (CAT5 Ethernet)
Serial (AB CIP) RS-232 –(2) 1761-CBL-PM02 1761-CBL-PM02
(1) Terminal block, wiring required.
(2) RS-485 is isolated. We recommend that you connect only one device.

124 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Appendix D Cable Connections and Communication

CompactLogix 5370 Support for communication with CompactLogix™ 5370 L1 controllers has been
Controller Cable Charts added from firmware revision 3.011 onwards. Support for communication
with CompactLogix 5370 L2 and L3 controllers have been added from firmware
revision 4.012 onwards. This feature also requires Connected Components
Workbench software version 9 or later to be installed.

The chart provides a summary of terminal connections to controllers and


network interface modules.
PanelView 800 Terminal Connections to CompactLogix 5370 Controllers
Protocol (CIP) PanelView 800 Port CompactLogix 5370
Ethernet 2711P-CBL-EX04 2711P-CBL-EX04
(CompactLogix) (CAT5 Ethernet) (CAT5 Ethernet)

For more information on adding CompactLogix 5370 controllers to your


applications, see the DesignStation help in Connected Components
Workbench software on the following topics.
• Configuring communication settings for CompactLogix 5370 controllers.
• Mapping tags from CompactLogix 5370 controllers to PanelView 800
terminals.
• Validating an application that includes a CompactLogix 5370 controller.

Ethernet Connection The PanelView 800 terminals have an Ethernet port that supports:
• communication to a controller.
• connection to a computer for accessing the PanelView Explorer Startup
window and downloading applications from Connected Components
Workbench software to the terminal.

Ethernet Connector

The base-configured unit of the terminals has an RJ45, 10/100 Base-T


connector for Ethernet network communication.
2711R-T4T 2711R-T7T 2711R-T10T

Ethernet port

Ethernet Connector Pinout


Pin Pin Pin Name
1 TD+
Looking into RJ45 2 TD-
Connector
1 8 3 RD+
4 NC
5 NC
6 RD-
7 NC
8 NC
Shield Connection Chassis Gnd

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 125


Appendix D Cable Connections and Communication

Either a standard Ethernet cable or crossover cables such as 2711P-CBL-EX04


can be used when connecting directly to a logic controller or switch.

Cables

The PanelView 800 terminals require category 5 twisted-pair cables. The


maximum cable length between the terminal’s Ethernet port and a 10/100
Base-T port on an Ethernet hub (without repeaters or fiber) is 100 m (328 ft). In
industrial applications, keep the cable length to a minimum.

For additional information, see the Ethernet Design Considerations reference


manual, publication ENET-RM002.

Security Considerations
IGMP (Internet Group Management Protocol) is used for IPv4 multicast. A
multicast is communication between a single sender and multiple receivers on
a network. IGMP is used to exchange membership status data between IPv4
routers that support multicasting and members of multicast groups. A router
is an intermediary device on a communication network that expedites
message delivery by finding the most efficient route for a message packet
within a network, or by routing packets from one subnetwork to another. A
subnetwork is a separate part of an organization’s network identified through
IP addressing.

PanelView 800 terminals provide level 2 (full) support for IPv4 multicasting
(IGMP version 2) as described in RFC 1112 and RFC 2236.

SNMP (Simple Network Management Protocol) is used for internal network


management and is not supported.

Ports 137 and 138 are normally open to support the NetBIOS protocol used by
Windows CE.NET similar to other Microsoft® and IBM network operating
systems.

Serial Connections The terminals have a multi-purpose serial RS-232 port that supports:
• DH-485 communication through a serial connection.
• DF1 full-duplex communication with controllers using direct
connections or modem connections.
• third-party point-to-point communication.

The serial port on the terminal is a 9-pin, male, RS-232 connector. An example
with the 1761-CBL-PM02 cable is shown here:

126 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Appendix D Cable Connections and Communication

The maximum cable length for serial communication is 15.24 m (50 ft) at
19.2 Kbps

RS-422/RS-485 Port
The RS-422/RS-485 port is an isolated port that supports point-to-point
communication.
RS-422/RS-485 Connector Pinout
Pin Signal
1 T
2 T–
3 R
4 R–
5 S (Shield)

The RS422/485 port has integrated 120 ohm termination between the R and R-
signal pair. This value is compatible with RS422 and RS-485 electrical
specifications. Additional termination on the PanelView 800 terminal end of
communication cables is not required.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 127


Appendix D Cable Connections and Communication

USB Ports The terminals have a USB device and USB host port.

ATTENTION: The USB device port is not intended for Customer use.

WARNING: The USB host port is intended for temporary local programming
purposes only and not intended for permanent connection. The USB host port
cable is not to exceed 3.0 m (9.84 ft).

USB Host Port

You can power USB peripherals directly from the PanelView 800 terminal. If
the USB peripheral is not powered directly from the PanelView USB port
either:
• install the USB peripheral in the same enclosure as the PanelView
terminal and make sure it is connected to the same ground system.
• connect to the USB peripheral through a galvanically isolated hub.

You can use the USB host port to connect a USB Flash drive to transfer
application files, fonts, and images.

WARNING: If you connect or disconnect the communications cable with power


applied to this module or any device on the network, an electrical arc can occur.
This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.

WARNING: If you connect or disconnect the USB cable with power applied to
this module or any device on the USB network, an electrical arc can occur. This
could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.

ATTENTION: Removing the USB flash drive or microSD card, from the
PanelView 800 terminal, while a firmware upgrade is in process, could
corrupt the firmware and make the terminal unusable. Take precautions to
prevent the USB flash drive or microSD card from being accidentally
disconnected. Also, do not power off the terminal while a firmware upgrade is
in progress.
USB hubs can produce unexpected behaviors and as a result are not
recommended.

128 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Appendix E

Using PanelView 800 Terminals with


CompactLogix 5370 Controllers

This chapter provides an example of how to use a CompactLogix 5370


controller in your PanelView 800 application. It includes information on how
to address the different data types between PanelView 800 terminals and
CompactLogix 5370 controllers. Examples of how to map them to tags are also
provided.

To use a CompactLogix 5370 controller in your PanelView 800 application,


there are four simple steps to do as follows:
1. Add the CompactLogix 5370 controller to the application.
2. Map the PanelView 800 terminal tags with the CompactLogix 5370
controller tags.
3. Validate the application in DesignStation in Connected Components
Workbench software.
4. Download the application to a PanelView 800 terminal.

Add a CompactLogix 5370 To add a CompactLogix 5370 controller to your application, do the following:
Controller 1. Click on the Settings tab for your PanelView 800 terminal in Connected
Components Workbench software.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 129


Appendix E Using PanelView 800 Terminals with CompactLogix 5370 Controllers

2. Click the Communication item in the menu list.


3. Click the Protocol drop-down list and select "Ethernet | Allen-Bradley
CompactLogix".
4. Under Controller Settings, enter the IP address of the controller into the
Address field.

IMPORTANT When you enter the IP address for a CompactLogix 5370 controller, you
must append path information “1,0” to the end.
For example, if the IP address of the controller is 192.168.0.1, you should
enter 192.168.0.1,1,0 into the Address field.

Map the Terminal and Here is an example of the terminal screen which we will use to map the
Controller Tags PanelView 800 terminal tags to the CompactLogix 5370 controller tags.

Here is an example of the tags used in the terminal screen shown above.

PanelView 800 HMI Controller Tag Address


Tags (Keep the same Tag Name and Addressing format as used in
CompactLogix 5370 controllers.)

To add tags, do the following:


1. Double-click Tags in the Project Organizer to open the Tag Editor tab.
2. Click the Add button to create a new tag entry.

130 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Appendix E Using PanelView 800 Terminals with CompactLogix 5370 Controllers

3. Modify the values of the tag to match the values shown in the example
above.
4. Repeat step 1 to step 3 for the rest of the tags shown in the example above.

For more information on how to address a CompactLogix 5370 controller tag


in PanelView 800, see Addressing Formats from PanelView 800 Terminals to
CompactLogix 5370 Controllers on page 134.

Validate the Application Before you can download the application to the terminal, you must validate it.

To validate the application, do the following:


1. Click the Validate icon on the Settings tab of the terminal.
2. Make sure that there are no validation errors in the application.
If the validation passes, the Validity will be set to True.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 131


Appendix E Using PanelView 800 Terminals with CompactLogix 5370 Controllers

If the validation fails, you will not be able to run the application on the
terminal

IMPORTANT PanelView 800 applications that are configured to communicate with a


CompactLogix 5370 controller must meet the following restrictions:
The following limits apply from firmware revision 5.011 onwards
• Maximum number of CompactLogix 5370 controllers: 1
• Maximum number of Screens: 50
• Maximum number of External Tags: 400
• Maximum number of Alarms: 400
The following limits apply from firmware revision 3.011 to 4.0xx
• Maximum number of CompactLogix 5370 controllers: 1
• Maximum number of Screens: 25
• Maximum number of External Tags: 200
• Maximum number of Alarms: 150
If any one of the above restrictions are not met, the validation will
always fail. You will not be able to download and run the application on
a PanelView 800 terminal.

Download the Application To download the application to the terminal, do the following:
1. Click the Download icon in the Settings tab of the terminal.

The Connection Browser dialog box appears.

2. Select the terminal that you want to download the application to, then
click OK.

Upload the Application To upload the application to the terminal, do the following.
1. Click the Upload icon in the Settings tab of the terminal.

132 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Appendix E Using PanelView 800 Terminals with CompactLogix 5370 Controllers

The Connection Browser dialog box appears.

2. Select the terminal that you want to upload the application from, then
click OK.

CompactLogix 5370 The atomic data types supported in CompactLogix 5370 controllers by
Controller Addressing PanelView 800 terminals are shown in the table below.

Supported Data Types


CompactLogix 5370 Data Types PanelView 800 Data Types
SINT 8-bit integer
INT 16-bit integer
DINT 32-bit integer
REAL Real (Range: -9999999...9999999)
BOOL Boolean
STRING STRING
– 8-bit unsigned integer
– 16-bit unsigned integer
– 32-bit unsigned integer

Although some of the predefined types are structures, they are ultimately
based on these atomic data types. Thus, all non-structure (atomic) members of
a structure are accessible.

For example, a TIMER cannot be assigned as a PanelView 800 tag but an


atomic member of the TIMER can be assigned to the tag (for example,
TIMER.EN, TIMER.ACC, and so forth).

If a structure member is a structure itself, both structures would have to be


expanded to access an atomic member of the substructure. This is more
common with user-defined and module-defined types and is not found in any
of the predefined types.

In summary, predefined, module-defined, and user-defined data types of the


CompactLogix 5370 controller can be accessed from PanelView 800 terminals
from their respective members, which are based on the above atomic data
types

The LINT data type is not supported in CompactLogix 5370 controllers.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 133


Appendix E Using PanelView 800 Terminals with CompactLogix 5370 Controllers

Addressing Formats from PanelView 800 Terminals to CompactLogix


5370 Controllers
When mapping a PanelView 800 terminal tag to a CompactLogix 5370
controller tag, make sure you copy the exact name and format of the controller
tag into the address field of the terminal tag in the Tag Editor.
Element Level Addressing
PanelView 800 CompactLogix 5370 Controller Tag Address Controller Tag Address
Data Type Data Type (Global) Example (Local, MainProgram) Example
Boolean BOOL Tag1 Program: MainProgram.Tag1
32-bit integer DINT Tag2 Program: MainProgram.Tag2
16-bit integer INT Tag3 Program: MainProgram.Tag3
8-bit integer SINT Tag4 Program: MainProgram.Tag4
Real REAL Tag5 Program: MainProgram.Tag5
String STRING *(1) *(2)
(1) Tag6.Data/N – N is the length of String.
(2) Program: MainProgram.Tag6.Data/N
Note the following:
• Tag address of Tag6.Len can be read/written for the length of String.
• Tag address of Tag6.Data[characterNo] is to read/write individual character of string by ASCII. For example, Tag6.Data[1] refers to the element 1.

Accessing a Member of a Structure (predefined, module-defined, user-defined data types)


PanelView 800 CompactLogix 5370 Controller Tag Address Controller Tag Address
Data Type Data Type (Global) Example (Local, MainProgram) Example
Boolean BOOL STRUCTURE.Tag1 Program:MainProgram.STRUCTURE.Tag1
32-bit integer DINT STRUCTURE.Tag2 Program:MainProgram.STRUCTURE.Tag2
16-bit integer INT STRUCTURE.Tag3 Program:MainProgram.STRUCTURE.Tag3
8-bit integer SINT STRUCTURE.Tag4 Program:MainProgram.STRUCTURE.Tag4
Real REAL STRUCTURE.Tag5 Program:MainProgram.STRUCTURE.Tag5
String STRING *(1) *(2)
(1) STRUCTURE.Tag6.Data/N – N is the length of String.
(2) Program:MainProgram.STRUCTURE.Tag6.Data/N

Boolean Addressing
PanelView 800 CompactLogix 5370 Controller Tag Address Controller Tag Address
Data Type Data Type (Global) Example (Local, MainProgram) Example
Boolean DINT Tag2.bitNo Program:MainProgram.Tag2.bitNo
Boolean INT Tag3.bitNo Program:MainProgram.Tag3.bitNo
Boolean SINT Tag4.bitNo Program:MainProgram.Tag4.bitNo
bitNo can be any value – 0...31 for DINT, 0...15 for INT and 0...7 for SINT data type tags in CompactLogix 5370 controller.

Array Addressing of an Element

CompactLogix 5370 Data Type Controller Tag Address Controller Tag Address
PanelView 800 Data Type Array Dimensions
(Global) Example (Local, MainProgram) Example
Boolean BOOL Tag1[x] Program:MainProgram.Tag1[x] 1
32-bit integer DINT Tag2[x,y,z] Program:MainProgram.Tag2[x,y,z] 1,2,3
16-bit integer INT Tag3[x,y,z] Program:MainProgram.Tag3[x,y,z] 1,2,3
8-bit integer SINT Tag4[x,y,z] Program:MainProgram.Tag4[x,y,z] 1,2,3
Real REAL Tag5[x,y,z] Program:MainProgram.Tag5[x,y,z] 1,2,3
String STRING *(1) *(2) 1,2,3

(1) Tag6[x,y,z].Data/N – N is the length of String.


(2) Program:MainProgram.Tag6[x,y,z].Data/N

134 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Appendix E Using PanelView 800 Terminals with CompactLogix 5370 Controllers

Boolean Access from an Array Element

PanelView 800 Data Type CompactLogix 5370 Data Type Controller Tag Address Controller Tag Address
(Global) Example (Local, MainProgram) Example
Boolean DINT Tag2[x,y,z].bitNo Program:MainProgram.Tag2[x,y,z].bitNo
Boolean INT Tag3[x,y,z].bitNo Program:MainProgram.Tag3[x,y,z].bitNo
Boolean SINT Tag4[x,y,z].bitNo Program:MainProgram.Tag4[x,y,z].bitNo
bitNo can be any value – 0...31 for DINT, 0...15 for INT, and 0...7 for SINT data type tags in CompactLogix 5370 controller.

Limitations with There are some limitations when using a CompactLogix 5370 controller in your
CompactLogix 5370 PanelView 800 application, as described below:
Controller Support • PanelView 800 terminals use Connected Components Workbench
software for configuration and screen design, while CompactLogix 5370
controllers use Studio 5000® software.
PanelView 800 terminals do not support the online Tag browsing feature
with CompactLogix 5370 controllers.
• Programming and configuration of CompactLogix 5370 controllers are
not supported in Connected Components Workbench software.
• Only a single CompactLogix 5370 controller is supported.
• PanelView 800 applications can only have a maximum of 25 screens, 200
tags, and 150 alarms.
From firmware revision 5.011 onwards, PanelView 800 applications can
have a maximum of 50 screens, 400 tags, and 400 alarms.
• CompactLogix 5370 L1 controller is supported only in PanelView 800
terminals with firmware revision 3.011 or later. CompactLogix 5370 L2
and L3 controllers are supported only in PanelView 800 terminals with
firmware revision 4.012 or later. Connected Components Workbench
software version 9 or later is also required.
• FTP and Email features are not supported.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 135


Appendix E Using PanelView 800 Terminals with CompactLogix 5370 Controllers

Notes:

136 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Appendix F

PanelView Explorer

IMPORTANT The PanelView Explorer feature is only supported on PanelView 800


terminals with firmware revision 2.020 or earlier. It is not supported
from firmware revision 3.011 onwards.

Chapter Objectives This chapter covers topics that show how to configure your PanelView 800
terminal.
• Configuration interfaces
• Terminal settings
• Managing applications and files
• Creating applications
• Upload and Download applications
• Transferring applications
• Transferring user-defined objects

Configuration Interfaces The terminal can be configured from either the browser interface or the
configuration screens on the terminal. The browser interface requires a
computer browser connected to the terminal's web service through an
Ethernet network connection. The configuration data for a terminal refers to
the collection of all of the system interface parameters.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 137


Appendix F PanelView Explorer

Access to the Terminal’s Configuration


Running
Internet Explorer or
Firefox browser

Ethernet
connectivity

On Terminal
Configuration

Configure Using the Browser


PanelView Explorer is the browser interface that lets you access and make
changes to the terminal settings. This interface is the web server content
hosted by the terminal and it represents a visualization of the terminal's
properties and files. The recommended browsers to use are:
• Internet Explorer 7 or 8
• Firefox 3.0

If you use a browser other than a recommended browser, you may encounter
messages similar to the following examples.

138 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Appendix F PanelView Explorer

PanelView Explorer Startup Window


8 1 2 3

PanelView Explorer Startup Window


Item Function Description
Use this link to view and change terminal display and communication settings, view system information, and
1 Terminal Settings enable terminal security while connected to the terminal.
Transfers files between the storage media of the terminal and your computer, such as screen saver bitmaps and
2 File Transfer applications. You can also delete applications from terminal storage and export the alarm history log.
3 Sign off Logs you off the Startup window, leaving your browser open.
4 Terminal Type and Status Shows the connection status to your terminal and the type of terminal.
5 Languages Shows the current and available languages for PanelView Explorer.
6 Test, Run Use these buttons to test and run the selected application.
Shows a list of applications stored on the terminal, USB flash drive, or microSD card. The list also shows if the file
7 Available Applications has been validated for correct operation.
Click the Stop button (the stop sign shown when an app is loaded and in Test/Run mode) to unload the currently
8 Stop loaded application. If you have not saved changes to the application, you are prompted to do so. Once the
application is unloaded, the terminal displays the Configuration screen.

Terminal Settings Terminal settings can be configured either through the PanelView Explorer
browser interface or through the on-terminal interface.

Adjusting Settings on the PanelView Explorer Startup Window

From the PanelView Explorer Startup window, you can view and edit settings
for the connected PanelView 800 terminal. The settings take effect
immediately.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 139


Appendix F PanelView Explorer

By clicking the Terminal Settings link on the PanelView Explorer Startup


window, you can access tabs to:
• change the terminal language.
• adjust the display brightness.
• configure screen saver settings.
• configure key repeat settings.
• calibrate the touch screen, if supported.
• reboot or reset the terminal.
• change the startup application.
• change the current date and time.
• configure terminal security, such as passwords.
• view system information.
• managing applications and files.

Select a Terminal Language

You can change the terminal display language. The terminal is shipped with
the English, Portuguese, French, Italian, German, Spanish, and Chinese fonts
installed. Korean is supported but you must first install the Korean font. See
Adding Font Files on page 151 for information on how to install the font onto
the terminal.

IMPORTANT At runtime, diagnostic messages appear in the same language as the


application if the application language is English, Portuguese, French,
Italian, German, Spanish, Chinese, or Korean. For all other languages, the
diagnostic messages appear in the configuration language set on the
terminal.

140 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Appendix F PanelView Explorer

Follow these steps to change the terminal language using PanelView Explorer.
1. Go to the PanelView Explorer Startup window.
2. Click the Terminal Settings link.
3. Click the System Information tab.
4. Select a language from the Terminal Language drop-down list.

5. Click Apply or click Cancel to restore the current setting.

Adjust the Display Brightness

You can modify the brightness of the terminal display. You can use the default
intensity of 100% for brightness or adjust the intensity for runtime operations.

Follow these steps to change the display brightness using PanelView Explorer.
1. Go to the PanelView Explorer Startup window.
2. Click the Terminal Settings link.
3. Click the Display/Input tab.
4. Drag the slider to adjust the brightness level between 1…100%.
5. Click Apply, or click Cancel to restore the current terminal settings.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 141


Appendix F PanelView Explorer

Configure the Screen Saver

You can enable or disable the screen saver on the connected PanelView 800
terminal.

The terminal has four screen saver modes: screen saver, dimmer, screen saver
and dimmer, or disable.
• Screen saver – activates after the idle timeout elapses using a default
screen saver image. The screen saver deactivates when you press a key.
• Dimmer – dims the display from full brightness to the brightness level
you set when the idle timeout elapses. While the display is dimmed, you
can still see on-screen activity. When you press a key, the display is
restored to full brightness.
• Screen saver and dimmer – activates the screen saver and dims the
display when the idle timeout elapses.
• Disable screen saver and dimmer – keeps the display on.

The screen saver timeout is the amount of idle time that must elapse before the
screen saver, dimmer, or screen saver and dimmer activates. The idle time can
be adjusted between 1…60 minutes.

The brightness intensity of the screen saver or dimmer can be adjusted


between 0…100%.

Follow these steps to configure the screen saver using PanelView Explorer.
1. Go to the PanelView Explorer Startup window.
2. Click the Terminal Settings link.
3. Click the Display/Input tab.
4. Select a screen saver mode from the list.

5. Select a time from the drop-down list to adjust the screen saver timeout.
6. Drag the slider to adjust the screen saver brightness.
7. Click Apply, or click Cancel to restore the current screen saver settings.

To disable the screen saver or dimmers, select Disable Screen Saver and
Dimmer from the screen saver mode list.

142 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Appendix F PanelView Explorer

Replace the Screen Saver Image

The default screen saver image is a floating Allen-Bradley logo in a bitmap


format. The name of the default screen saver is 'Screen Saver' with a .bmp file
type. You can replace the default screen saver with your own bitmap image, but
the file must have the same name as the default screen saver.
You cannot replace the screen saver image from the on-terminal
configuration screens. If you want to change this setting, you must connect to
the terminal through a web browser.

Follow these steps to replace the screen saver image using PanelView Explorer.
1. Create a small bitmap image no larger than 128 x 128 pixels.
2. Save your bitmap file to your computer, a USB drive or/and microSD
card. Rename your file as 'Screen Saver' and make sure the file type is
.bmp.
3. Click the File Transfer link in the PanelView Explorer Startup window,
then click New Transfer.
4. Select either My Computer or USB/microSD storage as file source
depending on where you saved your file, then click Next.
5. Select Screen Saver Image as the file type, then click Next.

6. Locate where you saved your bitmap file on your computer or external
storage device.
7. Select Internal Storage as file destination, then click Transfer. The
bitmap file is successfully transferred to the terminal.

The new screen saver takes affect the next time the screen saver is activated.
Your bitmap file should be small in size. A large bitmap will impact
performance of terminal operations.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 143


Appendix F PanelView Explorer

Configure Key Repeat Settings

You can configure key repeat settings for the terminal keys or attached
keyboard of the connected terminal.
You cannot change the key repeat settings from the on-terminal configuration
screens. If you want to change this setting, you must connect to the terminal
through a web browser.

The repeat rate is the speed at which a character repeats per second when you
hold down a key. The repeat delay is the amount of time, in milliseconds, that
elapses before a character begins to repeat when you hold down a key.

Follow these steps to change the repeat settings for keys using PanelView
Explorer.
1. Go to the PanelView Explorer Startup window.
2. Click the Terminal Settings link.
3. Click the Display/Input tab.
4. Check Enable key repeat to enable repeat settings for keys.

5. Drag the slider under Key Repeat Rate to adjust the speed at which a
character repeats when a key is held down.
6. Drag the slider under Key Repeat Delay to set the amount of time that
elapses before a character begins to repeat when the key is held down.
7. Click Apply or click Cancel to restore the current settings.

To disable key repeat settings, uncheck Enable key repeat.

Calibrate the Touch Screen

Over time you may notice that the objects and images on the display screen
don’t seem to fit the display area as well as they once did. This is normal with a
touch screen and can be easily fixed.

144 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Appendix F PanelView Explorer

Use a plastic stylus device with a minimum tip radius of 1 mm (0.040 in.) to
prevent damage to the touch screen.
You cannot calibrate the touch screen using VNC. If you have triggered the
calibration process, you can press the "ESC" key on the keyboard to cancel the
procedure.

Follow these steps to calibrate the touch screen using PanelView Explorer.
8. Go to the PanelView Explorer Startup window.
9. Click the Terminal Settings link.
10. Click the Display/Input tab.
11. Click Calibrate Touch Screen.

Follow these steps to complete the calibrate touch screen procedure.


1. With a stylus, tap the center of the target (+) on the terminal screen.

2. Repeat step 1 as the target moves around the screen.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 145


Appendix F PanelView Explorer

3. Tap OK when the message appears to accept the changes.


If you do not tap the screen within 30 seconds, the calibration data is
discarded and the current settings are retained.

OK ? : 30 sec

Reboot the Terminal

You can restart the terminal without having to disconnect and reapply power.
After a reset, the terminal performs a series of startup tests and then either
enters configuration mode or runs the startup application.

Follow these steps to reboot the terminal from PanelView Explorer.


1. Go to the PanelView Explorer Startup window.
2. Click the Terminal Settings link.
3. Click the Display/Input tab.
4. Click Reboot Terminal.

146 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Appendix F PanelView Explorer

Change the Startup Application

You can select or change the application that runs on the terminal each time
the terminal starts up. Only applications in the internal storage of the terminal
can be run or set as a Startup Application.

IMPORTANT If the application list is empty, the run, copy, delete, and set as startup
functions will not perform any action.

Follow these steps to select or change the startup application using PanelView
Explorer.
1. Go to the PanelView Explorer Startup window.
2. Click the Terminal Settings link.
3. Click the System Information tab.
4. Select the name of the startup application from the Startup Application
drop-down list.

5. Click Apply.

Change the Date and Time

You can adjust the current date and time for terminal operations. The time is
set in 24-hour format. If using PanelView Explorer, you can also set the
terminal to automatically adjust the time for daylight savings time.

Follow these steps to change the terminal date and time using PanelView
Explorer.
1. Go to the PanelView Explorer Startup window.
2. Click the Terminal Settings link.
3. Click the System Information tab.
4. Update the Current date fields.
5. Update the Current time fields.
6. Check Automatically adjust for daylight savings time if you want the
terminal to adjust for daylight savings time.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 147


Appendix F PanelView Explorer

7. Click Apply or click Cancel to restore the current terminal settings.

Enable Terminal Security

Use terminal security to restrict user access to the PanelView Explorer Startup
window. For example, you can require users to enter a user name and
password before accessing the PanelView Startup window.
You cannot enable terminal security from the on-terminal configuration
screens. If you want to change this setting, you must connect to the
terminal through a web browser.

IMPORTANT The PanelView Explorer feature is only supported on PanelView 800


terminals with firmware revision 2.020 or earlier. It is not supported
from firmware revision 3.011 onwards.

Initially, the terminal and the PanelView Explorer Startup window are
unsecured. To enable security, provide a password. The default user name is
Admin. The new password takes effect the next time the terminal is restarted.

As long as security is enabled, any user that tries to access the PanelView
Explorer Startup window must first log in with a valid user name and
password.

The terminal also secures itself when idle. If terminal input is not received
within the idle timeout period, the user is logged out. The user must log in
again to access the terminal. The default terminal idle timeout is 30 minutes.

IMPORTANT Store your password in a safe place. If you forget the password, you will not
be able to connect to the PanelView Explorer Startup window.

Follow these steps to secure the PanelView Explorer Startup window.


1. Go to the PanelView Explorer Startup window.
2. Click the Terminal Settings link.
3. Click the Terminal Security tab.

148 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Appendix F PanelView Explorer

4. Check Terminal Security Enabled.

5. Optionally, enter a new Terminal User Name.


6. Click the Reset Terminal User Password button.
7. In the Reset Password dialog, enter a new password, confirm the
password, then click OK.

Terminal user names are limited to 15 characters.

8. Select a new idle timeout from the Terminal Idle Timeout list, if needed,
or click Cancel to restore the current idle timeout.

The new password and idle timeout value take effect when the terminal is
restarted.

To disable security, uncheck the Terminal Security Enabled checkbox. The next
time the terminal is restarted, it will be unsecured.
The terminal user name and password is stored in a file that is separate from
the application. You can transfer this file to other terminals without having to
manually reenter the information. Use the File Transfer link on the PanelView
Explorer Startup window and transfer the Terminal User file from internal
storage to your computer, USB, or SD storage.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 149


Appendix F PanelView Explorer

View System Information

You can view system information about your terminal including information
about the firmware, boot code, logic board, battery status (if applicable),
terminal on time, and memory used.

Follow these steps to view system information using PanelView Explorer.


1. Go to the PanelView Explorer Startup window.
2. Click the Terminal Settings link.
3. Click the System Information tab.

Managing Applications You can manage the applications and files of the terminal from PanelView
and Files Explorer or directly from the terminal. The File Transfer link in the PanelView
Explorer Startup window and the File Manager screen on the terminal can be
used for transferring files to and from terminal storage media. File names and
tag names should start with an alpha character. Avoid starting names with
numeric or special characters.

You can do the following actions:


• export or import applications, images, the terminal security file, recipes,
and fonts.
• import screen saver bitmap files
• export the alarm log from the currently running application.
• delete applications, images, screen saver files, font files, terminal user
file and recipes from terminal storage.

IMPORTANT Some actions may not be performed in PanelView Explorer but may be
done on the terminal, and vice versa. For example, you cannot transfer
applications using PanelView Explorer but you can do so from the
terminal.

IMPORTANT The PanelView Explorer feature is only supported on PanelView 800


terminals with firmware revision 2.020 or earlier. It is not supported
from firmware revision 3.011 onwards.

A file transfer operation requires you to choose a source location, file type, and
destination location.

150 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Appendix F PanelView Explorer

• Source location – the location of the file you want to transfer. You can
transfer a file from Internal Storage of the terminal, USB Storage,
microSD Storage, or My Computer.
• Source File Type – the type of file you want to transfer. The types of files
you can transfer include PanelView 800 applications, screen saver
images, fonts, recipes, and the terminal security file.
• Destination location - The location where you want to transfer the
selected file. You can transfer a file to Internal Storage of the terminal,
USB Storage, microSD Storage, or My Computer.

IMPORTANT If transferring a file from or to USB or microSD storage, verify that the USB
flash drive or microSD card is inserted in the terminal before starting the
file transfer.

IMPORTANT The USB flash drive or microSD card must be formatted in the FAT/FAT32
file system for the terminal to read the contents of the external storage.

IMPORTANT When transferring an application, if the target terminal is a different type


and size then the source terminal, the application will be converted when
in Test Run or Run mode. The application may require updates before
running properly.

Adding Font Files These fonts reside on the terminal in the firmware image.
• Arial
• Courier New
• Tahoma
• Asian font (Simsun – Simplified Chinese)

The Arial, Courier, Tahoma, and Simsun fonts cannot be altered. Additional
Windows CE licensed fonts can be added to the terminal. Windows CE
licensed fonts can be downloaded from the PanelView 800 technical support
website at https://www.rockwellautomation.com/en-us/products/hardware/
allen-bradley/human-machine-interface/graphic-terminals/2711r-PanelView-
800.html. No other fonts are licensed for use on the terminal.

Import a Font File You can import a Microsoft Windows CE font to your terminal. Other font files
are not supported.

During the import, the font file is transferred from a USB Flash Drive or
microSD card to the internal storage of the terminal. The transfer operation
communicates with the terminal to transfer the file.

You can use the imported font in any application on the terminal.

Fonts cannot be exported for copyright reasons.

IMPORTANT The PanelView Explorer feature is only supported on PanelView 800


terminals with firmware revision 2.020 or earlier. It is not supported
from firmware revision 3.011 onwards.
Font files cannot be imported from PanelView Explorer when using
firmware revision 3.011 or later.

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 151


Appendix F PanelView Explorer

Follow these steps to add a font to the terminal.


1. Open the PanelView Explorer Startup window.
2. Click File Transfer.
3. Click New Transfer.
4. Select the source location of the Font file, typically My Computer, and
click Next.
5. Select Font as the file type and click Next.
6. Click Browse … to locate and select the Font file, then click Open.
7. Select Internal Storage as the destination for the font file and click
Transfer.
8. Observe the informational message for Transferring File.
9. The terminal should be rebooted to load the added font.

Remove a Font File A font that was added to the terminal and is no longer used can be removed.

IMPORTANT The PanelView Explorer feature is only supported on PanelView 800


terminals with firmware revision 2.020 or earlier. It is not supported
from firmware revision 3.011 onwards.
Font files cannot be imported from PanelView Explorer when using
firmware revision 3.011 or later.
Follow these steps to remove a font from the terminal.
1. Open the PanelView Explorer Startup window.
2. Click File Transfer.
3. Click Delete File.
4. Select the source location of the Font file, typically Internal Storage, and
click Next.
5. Select Font as the file type and click Next.

Observe the list of all Font files that have been added to the Terminal.
6. Select the Font file that you want to delete and click Delete.
7. Observe the Confirmation message for the selected Font file and click
OK.
8. Observe the informational message Deleting File.
9. Observe the deleted font file no longer appears in the list of all Font files.
10. Reboot the terminal to remove the file from the terminal.
Font files, especially East Asian Fonts, are large and consume significant
space on Internal Storage. Remove all unused fonts from the terminal.

152 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Index

A D
About PanelView Component DesignStation 45 date and time 20, 147
about the terminals 11 PanelView explorer window 147
access rights 79 terminal 20
assigning 85 DesignStation in Connected Components
creating 83 Workbench software 45, 77, 129
adding fonts 151 display
adjust display brightness 33 change language 19
alerts 96 change orientation 35
applications download
change controller settings 26 applications 53, 132
copy alarm history 25 Connected Components Workbench software
download 53, 132 45
export 21 fonts 63
import 22 recipes 56, 57
startup 22, 147 screen savers 64
transfer 43
unload 22, 88, 110
upload 54, 132 E
applications and files 150 Ethernet 14
cables 126
change settings 28, 30
B connector 125
battery replacement 120 port settings 30
security considerations 126
brightness settings 28
adjust 33 export applications 21
PanelView Explorer window 141

C F
firmware
cables
install from storage device 116
charts 124, 125 prepare for upgrade 109
connections 123 prepare storage device 116
Ethernet 125 upgrade 10, 109
calibrate touch screen 33, 144 using removable storage device 115
PanelView explorer window 145 fonts
terminal 33 adding 151
catalog number configuration 15 delete 37
change startup application 22, 147 download 63
PanelView explorer window 147 import 151
terminal 22 remove 152
CompactLogix 5370 controller FTP server
addressing data types 133 configure settings 57
cable charts 125 enable 31
limitations 135
mapping tags 130
validation restrictions 132 H
configuration interfaces 17, 137 how to
PanelView explorer startup window 139 connect a browser 13
terminal interface main menu 18
configuration mode 17, 137
connect a browser 13 I
Ethernet 14 IGMP Protocol 126
connect devices
import applications 22
124
Connected Components Workbench software import font 151
download 45 install
installation requirements 46 battery 120
launch mechanism 52 SD memory card 119
uninstallation 49 USB flash drive 120

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 153


Index

install and replace components 119 recipes


intended audience 9 copy 23
Internet Group Management Protocol (IGMP) 126 create 55
IP address of terminal 13 delete 24
download 56, 57
Ethernet port 14, 28 edit 24
USB port 28 ingredients 56
replace screen saver image 143
K
key repeat setting 52, 144 S
screen saver 36, 142
L configure 36
PanelView explorer window 142
language replace image 143
change 19 screen savers
Launching Connected Components Workbench download 64
software 52 SD memory card 119
secure design environment 79
access rights 83
M design rights 83
managing features 79
applications 150 security
files 150 change password 78
Micro800 cable charts 124 clear password 79
MicroLogix cable charts 124 idle mode 86
protected mode 87
restting the terminal 87
runtime 86
O safe mode 87
out of box condition 103 set password 77
overview 11 serial connections 126
port settings 30
RS422 and RS485 127
P Simple Network Management Protocol (SNMP)
PanelView explorer window 139 126
brightness 141 SNMP Protocol 126
calibrate touch screen 145 specifications 107
change startup application 147 system information 42, 95, 150
date and time 147 PanelView explorer window 150
key repeat setting 52, 144 terminal 42
reboot terminal 146
screen saver 142
system information 150 T
terminal security 148
password terminal
change 78 adjust brightness 33
clear 79 calibrate touch screen 33
set 77 change display language 19
peripheral connection 14 change display orientation 35
change password 78
print change startup application 22
Ethernet settings 40 clear password 79
paper settings 40 configure screen saver 36
settings 39 date and time 20
protected mode enable security 148
states 87 FTP server 31
language 19, 140
power-on self-test (POST) 102
R print settings 39
reboot terminal 20, 146 restart 20, 146
restore 104
PanelView explorer window 146 return to out-of-box condition 103
set password 77
system information 42
terminal interface main menu 18

154 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


Index

terminal settings 18, 139


calibrate touch screen 33, 144
change startup application 22, 147
date and time 20, 147
Ethernet 28
key repeat 52, 144
on PanelView explorer startup window 139
on terminal 18
Port 30
reboot terminal 20, 146
screen saver 36, 142
system information 42, 150
terminal language 19, 140
touch screen
calibrate 33
transfer
applications 43
troubleshooting 101
alerts 96
check for power 101
out-of-box condition 103
restore the terminal 104
status indicators 103

U
Uninstall Connected Components Workbench
software 49
upload
applications 54, 132
USB
flash drive 120
host port 128
ports 14
user accounts
managing 80
screen 80

V
Virtual Network Computing (VNC)
connecting 93
guidelines 89
settings 91
VNC clients 89

W
wiring and safety guidelines 123

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 155


Index

Notes:

156 Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021


PanelView 800 HMI Terminals User Manual

Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021 157


Rockwell Automation Support
Use these resources to access support information.

Technical Support Center Find help with how-to videos, FAQs, chat, user forums, and product notification updates. rok.auto/support
Knowledgebase Access Knowledgebase articles. rok.auto/knowledgebase
Local Technical Support Phone Numbers Locate the telephone number for your country. rok.auto/phonesupport
Literature Library Find installation instructions, manuals, brochures, and technical data publications. rok.auto/literature
Product Compatibility and Download Center Download firmware, associated files (such as AOP, EDS, and DTM), and access product release rok.auto/pcdc
(PCDC) notes.

Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our
content, complete the form at rok.auto/docfeedback.

Waste Electrical and Electronic Equipment (WEEE)

At the end of life, this equipment should be collected separately from any unsorted municipal waste.

Rockwell Automation maintains current product environmental information on its website at rok.auto/pec.

Allen-Bradley, CompactLogix, Connected Components Workbench, ControlFLASH, expanding human possibility, FactoryTalk, Guardmaster, MicroLogix, Micro800, Micro820, Micro830, Micro850, Micro870,
PanelView, Rockwell Automation, Studio 5000, Studio 5000 Logix Designer, and TechConnect are trademarks of Rockwell Automation, Inc.
CIP and EtherNet/IP are trademarks of ODVA, Inc.
microSD is a trademark of SD-3C.
Microsoft, Microsoft Windows, and Windows are trademarks of Microsoft Corporation.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenkÖy, İstanbul, Tel: +90 (216) 5698400 EEE YÖnetmeliğine Uygundur

Connect with us.

Publication 2711R-UM001H-EN-E - April 2021


Supersedes Publication 2711R-UM001G-EN-E - March 2018 Copyright © 2021 Rockwell Automation, Inc. All rights reserved.

You might also like