List of Material: Saudi Arabian Oil Company

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

SAUDIARAMCO.

NOTES:
LIST OF MATERIAL
1. ALL DIMENSIONS ARE IN MILLIMETER UNLESS
OTHERWISE SPECIFIED.
DWG. ISSUE REQ'D.
AMS # DESCRIPTION 2. POLES SHALL BE PRE-DRILLED WITH 20MM DIA HOLES
CODE UNIT QTY.
AT LOCATIONS SPECIFIED IN THIS DRAWING.

1 1000233149 EA WASHER, FLAT, ƒ" DIA. BOLT 3. ALL PRE-DRILLED HOLES SHALL BE PROVIDED WITH
15
CAPS OR PLUGS (DURABLE PLASTIC OR COMPOSITE

OF
2 1000233194 EA 7 WASHER, LOCK SPRING, ƒ" NOM. CS MATERIALS)

CONSENT
4. EARTHING NUT SHALL BE PROVIDED WITH BOLT AND
3 1000386998 EA STUD, POST INSULATOR, SHORT 3/4" DIA
3
WASHER.

4 1000390097 EA 6 BOLT, MACHINE 3/4 " x 14" LONG GALV. STEEL WITH NUT 5. POLE SHALL BE PERMANENTLY MARKED WITH MANU-
FACTURERS NAME YEAR OF MANUFACTURE LEGNTH
5 1000390451 EA 3 BRACKET: FOR POST INSULATOR
AND ULTIMATE LOAD RATING.

TTEN
6 1000829281 EA 1 POLE: STEEL OCTAGONAL, 55 FEET OR LENGTH REQUIRED 6. CONTRACTOR SHALL NOT INSTALL BOTTOM LINE

CAP PLATE IN CASE OF 1-PHASE 2-WIRE + SHIELD WIRE.

WRI
7 1000386822 EA 3 INSULATOR, LINE POST, PORCELAIN, TIE TOP
7. POD POLE TAG MUST BE INSTALLED IN ALL POLES

102
8 CS PC 1 CONDUIT; 1" DIA. PVC DB-120 BEARING THE POLE NUMBER AND INSTALLATION DATE.

THE
8. GALVANIZED STEEL POLE MUST BE COATED WITH
SHEILD WIRE 1000392957 ST 1 ROD: ARMOR 0.176 - 0.182 INCH DIA 60" LONG ACSR
9 ANTI-CORROSION COATING OF COAL TAR EPOXY
OR

THOUT
1000
OPGW AS PER 14-SAMSS-403.
10 1000168148 EA 2 TAG; BRASS TAG
9. INSULATORS SHALL BE RATED ACCORDINGLY FOR
11 1000393964 FT 3 TIE, INSULATOR, SIDE 34.5kV SYSTEM.

WI
2 10. REFER TO SAES-P-107, TABLE 1 FOR CONDUCTOR &
12 1000374602 EA 1 LUG; TERMINATING, 25MM (#4AWG) CABLE

NG
1 2 4 POLE CLEARANCES.

DRAWI
13 1000420040 MT 5 WIRE; 25MM (#4AWG) 1, GREEN, PVC INSU. COPPER

610
11. EITHER COMPOSITE OR PORCELAIN TYPE INSULATORS

14 1 MAY BE USED. REFER TO SAES-P-107 FOR DETAILS.


1000379019 EA ROD GROUNDING (3/4")
3 EA.
12. FOR HORIZONTAL POST COMPOSITE INSULATORS,

S
15 CS EA 1 THERMIT WELD

THI
HORIZONTAL CLAMTOPS WITH BOLTED ALUMINIUM
3 7 11 9
SUSPENSION TRUNNION CLAMPS FOR SINGLE
16 CS EA 1 ELBOW; 1" DIA. 90° RADIUS PVC DB-120
CONDUCTOR SHALL BE USED.

610

FROMNED
OBTAI
5

BE
SEE ENLARGE VIEW

PART,SHALL
6 REFERENCE DRAWINGS

N
I
FULL,OR
HOT-DIP
GALVSNIZED CAP PLATE
STEEL POLE
POLE SHAFT

N
I
10

ON
102

102

REPRODUCTI
NOTE

50MM
GREEN BAND
SEE

M12 EARTHING NUT (WELDED)

HEX. HEAD BOLT WITH WASHER


M12x30LG. (SUPPLIED WITH STEEL POLE)

1000

SAUDIARAMCO.NO
16 13

8 12

GROUND LEVEL
6550

254

OF
PROPERTY
610
NAME PLATE
356

10

SOLE
1400

THE
254

15

ARE
610

12
400

N
HEREI
356

GROUND LEVEL 1500

14

NED
L

NONE
DETAI

SCALE:
15
254

CONTAI
REVISION VALIDATION
ON

THIS REVISION NO. 00 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION


POLE
FOUNDATI

REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:

ON
765200-0915-001
14

NFORMATI
SEE

DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER


(DESIGN AGENCY) REQUIRED (SAUDI ARAMCO)

ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE

RM JAB RM JAB
09/01/15 09/01/15 09/01/15 09/01/15

REV.NO. DATE REVISION DESCRIPTION

I
DETAIL-1 00 09/01/15 NEW STANDARD FOR STEEL POLE

POLE GROUNDING

THE
JOB ORDER/EWO NO.
THIS REVISION IS NOT TO BE USED FOR
765200 CONSTRUCTION UNTIL CERTIFIED AND DATED

SAUDI ARABIAN OIL COMPANY

AND
OCTAGONAL STEEL POLE ENLARGE VIEW DRAWING TYPE

ARMLESS TANGENT POLE (0-2DEG) STD


OCTAGONAL STEEL POLE

NG
13.8KV - 34.5KV OVERHEAD POWERLINE

DRAWI
STANDARD DRAWING

STD. DWG. SAUDI ARABIA

S
PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

THI
990 P AA-036142 002 00
Saudi Aramco 2615 ENG. (05/05)

RESTRICTED VECTOR CADD-01