ModBerry 500
512 MB RAM and 4GB NAND FLASH memory
500
USER
ModBerry
STATUS
Basic information
Designed for the needs of automation, telecommunications, remote supervision, and monitoring
Fully configurable platform - you can setup hardware options of your device
Standard protocol support (e.g. MODBUS, SNMP), possibility to install dedicated user protocols
Web page visualization of current/archived data and remote control directly from the device or cloud service
ModBerry 500 - Industrial Embedded Computer based on the Raspberry Pi Linux system 1/6
www.techbase.eu e-mail: [email protected] tel. +48 58 302 39 90 ver: 1407021042
Applications
Data logger (Log) - archiving and sharing data in a file format, database or with the use of external systems (SCADA or dedicated iModCloud)
ModBerry 500
Access via WWW (Visualize) - data is presented directly from the device or with dedicated cloud computing services (iModCloud)
Access via
External devices
web browser
I/O
ModBerry 500
Input/Output Data server
data e.g. SCADA
Built-in LTE/3G/GPRS/EDGE*
Modem for data LTE/3G/GPRS data transmission and SMS support. iMod has unique hardware-software features providing connection efficiency and economy:
Pre-installed software for constant verification of LTE/3G/GPRS connection and GPRS reconnect function.
Multiplexing server provides 3 independent modem communication channels. Allows sending and receiving of SMS during LTE/3G/GPRS transmission.
You can use telemetry SIM cards with dynamic IP addresses due to the use of DynDNS. VPN or iModCloud technology allows use of cards with
non-public IP.
ModBerry 500 - Industrial Embedded Computer based on the Raspberry Pi Linux system 2/6
www.techbase.eu e-mail: [email protected] tel. +48 58 302 39 90 ver: 1407021042
Configuration Scheme
ModBerry 500
ModBerry 500
Broadcom 700MHz
BASE
-25 ~ 80°C
ModBerry 500 - Industrial Embedded Computer based on the Raspberry Pi Linux system 3/6
www.techbase.eu e-mail: [email protected] tel. +48 58 302 39 90 ver: 1407021042
Dedicated ready-to-use device software
iMod - an innovative software platform allowing for fast start-up and full exploitation of device
COMING SOON
capabilities without the need for writing programs. A fully configurable system reflecting typical C-L-V
use (see clarification above). In order to learn more about the iMod platform, visit the page:
ModBerry 500
www.techbase.eu/imod
READY-TO-USE
iModCloud is ready-to-use set of components that can be adjusted to any remote
monitoring and control system
COMING SOON
REMOTE CONTROL
User interface of the system is accessible from any place of the world through web
browsers of desktops and mobile devices
PLC - software for creation of algorithms in the ladder system with the capability of operation on NPE,
services the MODBUS protocol
GPRS - facilitating management of the 3G/GPRS connection and containing the functionality
of monitoring connection status and DynDNS service
SMS - allows sending and receiving text messages
APACHE - HTTP server pack, enabling device access from web browser
PYTHON/RUBY/JAVA/PHP - packs allowing creating, develomepent and start-up of applications
in many programming languages
PostgreSQL, MSSQL, SQLite - tools for database management
Open VPN - enables creating a connection, allowing communication between devices located
in different networks, providing very high level of security
NXDynamics - a platform for fast and easy (drag and drop system) creation of WWW visualiza-
tions and a web panel for NPE management through an internet browser
SSH - enables remote connection with device while maintainging high level of security
GPS - allows the location of the device, traffic monitoring for the unit and time synchronization
ModBerry R500 - Industrial Embedded Computer based on the Raspberry Pi Linux system 4/6
www.techbase.eu e-mail: [email protected] tel. +48 58 302 39 90 ver: 1407021042
Accessories
POWER FEEDERS
SDK-0302-12VDC-R
AC/DC power feeder, input 100-240V AC, output 12V DC 1000mA, cable endings in tube terminals
DN-20-24
DIN bus power feeder, output 24V DC 24W, input 88..264 V AC or 124..370 V DC
ModBerry 500
ANTENNAS
ANT-GSM-1M
GSM antenna with frequency 824-960MHz/1710-1910MHZ/1920-2170MHz
ADA-0086-L
Screw-in angular antenna, SMA, 900/1800 MHz
1-WIRE SENSORS
1Wire-Therm-Stainless
Digital temperature sensor in steel housing
1Wire-Therm-ABS
Digital temperature sensor closed in ABS plastic housing
M-BUS CONVERTERS
mBus 10
The mBus 10 is a transparent converter from RS-232 to M-Bus interface.
mBus 400
The mBus 400 is a transparent converter from RS-232 to M-Bus interface. You can connect 4 RS-232 signal
lines - RxD, TxD, CTS, RTS.
ZIGBEE SENSORS/MODULES
ZS-10, ZS-20
Multi-channel ZigBee Sensor with Battery Power Supply
ZM-10, ZM-20
ZigBee Relay I/O Module
Pinout
500
DI DIO DO 1-WIRE
DATA
GND
3.3V
GND
1 2 3 4 5 6 7 8 9 10 11 12
COM1 COM2 RS485_1 RS485_2 CAN ADC RESET
BUTTON
HDMI
B (+)
B (+)
HIGH
GND
A (-)
LOW
RxD
RxD
TxD
GND
TxD
A (-)
1 2 3 4
TERMINAL 1
500
POWER USER
LAN1
V- V+ USB (eth0)
SIM CARD AUDIO OUT BUTTON
ModBerry 500 - Industrial Embedded Computer based on the Raspberry Pi Linux system 5/6
www.techbase.eu e-mail: [email protected] tel. +48 58 302 39 90 ver: 1407021042
Technical specification
Processor module Raspberry Pi Compute Module SO-DIMM
CPU Broadcom 700MHz
RAM 512MB
Flash Memory 4096MB (shared with RAM)
ModBerry 500
Operating system Linux Kernel 3.6, supported by Raspberry Pi
Real Time Clock RTC, 240 byte SRAM, Wath Dog Timer
ETHERNET INTERFACE
1x Ethernet 10/100 Mbps (RJ45 connector)
SERIAL PORTS
RS-232 / RS-485 Ports 2x RS-232 (3 pins) / 2x RS-485 (2 pins)
USB PORTS
1x external USB 2.0 (host), 1x internal USB 2.0
INPUTS / OUTPUTS
Digital inputs (DI) 4x DI (0..5V DC)
Digital outputs (DO) 4x DO (0..30V), max. power efficiency: 500 mA
Configurable I/Os 4x DI/DO, max. power efficiency: 500 mA
Analog inputs 4x AI - range 0..10V DC (18bit resolution)
1-Wire 1x 1-Wire
CAN 1x CAN
POWER SUPPLY
9 ~ 24 V DC, 1000 mA
MECHANICAL PARAMETERS
Dimensions 91 x 106 x 61 mm
Weight 300g
Casing ABS or Aluminum, DIN bus instalation