MZX Fire detection system LIM800

LIM800 Line Isolator Module – Installation


Instruction

Fig. 1: LIM800 Line Isolator Module

Technical specifications Parameter Value


Parameter Value Dimensions (HWD) 87 x 148 x 14 mm
System Compatibility Use only with MX Fire Mounting  One MK backbox sur-
Alarm Controllers Requirements face mount or an
Environment Indoor Application ANC-8 ancillary hous-
only ing

Operating  -25 °C to +70 °C Wire Size Min 1.5 mm2


Temperature Max 2.5 mm2
Storage Temperature -40 °C to +80 °C Maximum Wiring 10 ohm
Operating Humidity Up to 95% non-con- Resistance Monitored
densing Circuit:

Table 1: Technical Specifications Table 1: Technical Specifications (cont.)

Fixing instructions Doc. version 2.0 1/8


LIM800 MZX Fire detection system

Electromagnetic Compatibility How to install MX800 modules into an


The LIM800 complies with the following: ANC-8 ancillary housing
 Product family standard EN50130-4 in 1 Assemble the required ancillary PCBs onto
respect of: the chassis plate as required, fixing as shown
– Conducted Disturbances in Fig. 2.
– Radiated Immunity 2 Assemble the chassis plate into the housing
and secure using fixing screw, see Fig. 2.
– Electrostatic Discharge
3 Connect the chassis plate earth lead to the
– Fast Transients
housing, see Fig. 2.
– Slow High Energy
 EN 61000-6-3 for emissions
1 2

Introduction
The LIM800 Line Isolator Module is designed to
be used on the MX addressable controller loop
circuits. It monitors the line condition and when
detecting a short circuit will isolate the affected
section whilst allowing the rest of the address-
ing circuit to function normally. The purpose of
the LIM800 Line Isolator Module is to ensure 6
that, on a looped addressable system, no short
circuit fault can disable more detection devices
than would be lost on a conventional non-
addressable fire circuit and to meet the require-
ments of BS 5839 : Part 1. 5 4 3

Mounting Fig. 2: ANC-8 - Chassis Plate


Installation of modules into an ANC- 1 – Chassis plate fixing screw
8 ancillary housing 2 – Chassis plate
3 – Cover earth
The housing can accommodate up to eight ancil- 4 – Chassis plate earth
lary PCBs. A stacking kit is available if a second 5 – Transit screw
layer of PCBs is required. 6 – Typical positions of 800 modules (4 per row)

CAUTION
Ensure only nylon stand-offs and
washers are used

2/8 Fixing instructions Doc. version 2.0


MZX Fire detection system LIM800

6
5
4
3

Fig. 3: ANC-8- PCB Fixing Detail


1 – Housing
2 – Plate
3 – Nylon spacer
4 – Ancillary PCB
5 – Plain washer
6 – Nylock nut

Installation to M520 Double Gang


cover
TB6
R-
R+
S-
S+
L-
L+
LED2

Fig. 4: LIM800 Fitted to Cover

How to install the LIM800 to a M520 Avoid smearing sealant over the LED surface.
Double Gang cover Using a fine nozzle is recommended.
1 Assemble the LIM800 to the M520 Double 3
Gang cover, using the four screws and wash- 2
ers provided,
1
2 Fit cover onto MK backbox.
3 If an IP22 rating is required additional sealing
must be applied. Apply Loctite S1595 silicone
Fig. 5: Sealed LED
sealant around the LED, as shown in Fig. 5.
1 – Cover
Note how the sealant fills the small gap
2 – LED
between the LED and its hole in the cover.
3 – Sealant

Fixing instructions Doc. version 2.0 3/8


LIM800 MZX Fire detection system

Verifying loop wiring


WARNING
Do not megger loop wiring
Cabling with line isolator modules
Cables are to be selected in accordance with connected.
Publication 17A-02-D and the requirements of
the current issue of BS5839. One pair of termi- The Line Isolator Module is not designed to work
nals is used to provide a spur circuit (S+/S-). Two with line voltages above the specified maximum
pairs of connection terminals (R+/R- and L+/L-) 40V dc. This means that continuity testing of the
are provided on the terminal block. These termi- loop wiring with Line Isolator Bases connected
nals are used for connecting the module on to must be done using a voltage between 20-40 V
the addressable circuit. A maximum of one dc. The resistance measurement range on con-
1.5mm2 or one 2.5mm2 cable may be connected ventional voltmeters use low voltage only, there-
at any one terminal. fore, the following method can be employed to
confirm loop integrity.
Wiring notes A power supply capable of providing 30 - 40 V dc
with a 300 to 600 mA current limit is connected
The following notes apply: to one end of the loop (in correct polarity). A volt-
 There are no user-required settings (such as meter is connected to the other end of the loop
switches or headers) on the LIM800. or any base along the loop to verify the wiring up
 All wiring must conform to the current edition to that point.
of IEE Wiring Regulations and BS5839 part 1. If there is no voltage out at any measured point,
 All conductors to be free of earths. this may be due to:
 Fit the PCB to the M520 cover/ANC-8 ancil-  Loop Open Circuit - wiring incomplete to part
lary housing. of the loop.
 Connect loop wiring . For LIM800 typical wir-  Incorrect Polarity - LIM800 Line Isolator Mod-
ing configurations (see Fig. 6). ules will appear as a short circuit if they are
 Verify the correct polarity of wiring before
wired with incorrect polarity.
connecting the LIM800 to the addressable  Loop Short Circuit - If this occurs between
loop circuit. two LIM800 Line Isolator Modules, it will iso-
late that section of the line, which will then
appear as an open circuit.
 If this occurs between the supply and the first
LIM800 Line Isolator Modules, the supply
output will go low due to the internal current
limit.

4/8 Fixing instructions Doc. version 2.0


MZX Fire detection system LIM800

-VE

+VE
1
+VE

L1 L1
L L
-VE
L2 L2

TB6
R R

R-
R+
S-
S+
L-
L+
3 3

LED2
2

Fig. 6: LIM800 Line Isolator Module - Simplified Wiring Diagram


1 – For spur circuit
2 – 801 RIL Remote indicator
3 – MX Controller

Fig. 7: LIM800 Line Isolator Module Facia Plate

Fixing instructions Doc. version 2.0 5/8


LIM800 MZX Fire detection system

L+ R+

S+

S-

L- R-
Fig. 8: LIM800 Operation

Switches are normally closed. Ordering information


If a short circuit is detected on the spur, both
switches open. Name Stock code
number
If a short circuit is detected on the left hand side,
the left hand side switch opens. LIM800 Line Isolator Module 545.800.004
If a short circuit is detected on the right hand
LIM800 Line Isolator Module 545.800.033
side, the right hand side switch opens.
c/w cover:
M520 Double-Gang Cover 517.035.007
Associated equipment
The module fits onto a standard dual-gang MK ANC8 Ancillary Housing assy. 557.180.096.
box, or an ANC8 ancillary housing. A/T/Y
Table 2: Ordering information

6/8 Fixing instructions Doc. version 2.0


MZX Fire detection system LIM800

CPR Information

0832

Tyco Fire & Security GmbH


Victor von Bruns-Strasse 21
8212 Neuhausen am Rheinfall
Switzerland
15
DoP-2015-4100

EN54-17:2005
Short-circuit isolator device for use in fire
detection and alarm systems in buildings
LIM800

Essential Characteristics
EN54-17:2005
Performance under fire conditions: Pass
Operational reliability: Pass
Durability of operational reliability; tempera-
ture resistance: Pass
Durability of operational reliability; vibration
resistance: Pass
Durability of operational reliability; humidity
resistance: Pass
Durability of operational reliability; corrosion
resistance: Pass
Durability of operational reliability; electrical
stability: Pass

Fixing instructions Doc. version 2.0 7/8


LIM800 MZX Fire detection system

© Tyco Fire & Security GmbH, Victor von Bruns-Strasse 21, 8212 Neuhausen
am Rheinfall, Switzerland