Typical Design Loads Schedule

The document outlines typical design loads for various building elements, including a roof pitched at 40 degrees that has a variable load of 0.75 kN/m2 and permanent loads of 0.8 kN/m2 measured on slope and 1.04 kN/m2 measured on plan. Ceilings have variable loads of 0.25 kN/m2 and permanent loads of 0.3 kN/m2, while first floors have variable loads of 1.5 kN/m2 and permanent loads of 0.45 kN/m2. Cavity walls have loads of 1.8 kN/m2 for 100mm block and 2 kN/m2 for 102.5mm

Uploaded by

Benedict Ogbagha
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
51 views1 page

Typical Design Loads Schedule

The document outlines typical design loads for various building elements, including a roof pitched at 40 degrees that has a variable load of 0.75 kN/m2 and permanent loads of 0.8 kN/m2 measured on slope and 1.04 kN/m2 measured on plan. Ceilings have variable loads of 0.25 kN/m2 and permanent loads of 0.3 kN/m2, while first floors have variable loads of 1.5 kN/m2 and permanent loads of 0.45 kN/m2. Cavity walls have loads of 1.8 kN/m2 for 100mm block and 2 kN/m2 for 102.5mm

Uploaded by

Benedict Ogbagha
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Typical Design Loads

Roof

Pitch         = 40 degrees

Variable = 0.75 kN/m²

Permanent measured on slope

Tiles = 0.60 kN/m²


Battens + felt = 0.05 kN/m²
Rafters = 0.15 kN/m²
Σ 0.80 kN/m²

Permanent measured on plan = 0.80 kN/m2 / COS  40 = 1.04 kN/m²

Ceiling

Variable = 0.25 kN/m²

Permanent,
Ceiling Joists = 0.10 kN/m²
Plasterboard = 0.20 kN/m²
Σ 0.30 kN/m²

Stud Partitions

Partitions = 0.25 kN/m² On Plan

First Floor

Variable = 1.50 kN/m²

Permanent,
Boards = 0.10 kN/m²
Joists = 0.15 kN/m²
Plasterboard = 0.20 kN/m²
Σ 0.45 kN/m²

Cavity Wall

100mm Block Wall = 1.60 kN/m²


Plaster = 0.20 kN/m²
Σ 1.80 kN/m²

102.5mm Brick = 2.00 kN/m²