RAM Connection Verification Manual

The document describes verification examples for structural steel connections according to AISC and Eurocode standards. It includes 13 examples of various steel beam to column connections, base plate configurations, and brace connections. Dimensions, material properties, and loading conditions are provided for each example problem to compare the results against.

Uploaded by

Benedict Ogbagha
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
685 views47 pages

RAM Connection Verification Manual

The document describes verification examples for structural steel connections according to AISC and Eurocode standards. It includes 13 examples of various steel beam to column connections, base plate configurations, and brace connections. Dimensions, material properties, and loading conditions are provided for each example problem to compare the results against.

Uploaded by

Benedict Ogbagha
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 47

RAM Connection

V8i (SELECTseries 6) Release 10.0

Verification Manual
Last Updated: April 22, 2015
Table of Contents
Chapter 1: AISC Verification Examples ........................................................................................ 3
1.1 Base Plate Bearing on Concrete ................................................................................................................................................... 3
1.2 Welded/Bolted Wide Tee Connection to an HSS Column ................................................................................................ 5
1.3 Double Angle Connection to an HSS Column ......................................................................................................................... 6
1.4 Unstiffened Seated Connection to an HSS Column .............................................................................................................. 8
1.5 Four Bolt Unstiffened Extended End Plate FR Moment Connection (Beam to Column Flange) ...................10
1.6 Four Bolt Unstiffened Extended End Plate FR Moment Connection (Beam to Column Flange) ...................12
1.7 All Bolted Double Angle Connection in a Coped Beam ................................................................................................... 14
1.8 Bolted Flange-Plated FR Moment Connection (Beam to Column Flange) ..............................................................16
1.9 Moment Frame Beam-to-Column Connection .................................................................................................................... 18
1.10 OMF Beam-Column Connection ................................................................................................................................................ 19
1.11 SMF Beam-Column Connection .................................................................................................................................................22
1.12 SCBF Brace-to-Brace Connection ............................................................................................................................................. 24
1.13 SMF Beam-Column Connection .................................................................................................................................................28
Chapter 2: Eurocode Verification Examples ..............................................................................31
2.1 Fin Plates - Beam to Beam ........................................................................................................................................................... 31
2.2 Double Cleats Aangle – Beam to Column Web – Tying Resistance ............................................................................ 32
2.3 Partial Depth End Plate – Beam to Hollow Section Column ......................................................................................... 33
2.4 Column Splice – End Plate with Rectangular Column ..................................................................................................... 34
2.5 Column Splice – End Plate with Circular Column ..............................................................................................................35
2.6 Column splice – Web Angle Cleats, Bearing Splice (No Net Tension) .......................................................................36
2.7 Beam Splice – Web Cover Plate ................................................................................................................................................. 36
2.8 Column Splice – Flange Cover Plate, Nonbearing Splice ................................................................................................ 37
2.9 Bolted End Plate Connection (Unstiffened) ......................................................................................................................... 39
2.10 Bolted End Plate Haunched ........................................................................................................................................................ 40
2.11 Unstiffened Column Base Plate ................................................................................................................................................. 42
2.12 Base Plate ............................................................................................................................................................................................44
2.13 Bracing Connection ........................................................................................................................................................................ 45

RAM Connection 2 Verification Manual


AISC Verification Examples
1
1.1 Base Plate Bearing on Concrete
Reference
American Institute of Steel Construction. 2011. Design Examples V14.1 . Chicago, IL:American Institute of Steel
Construction. p J-16

Problem
From the reference:

An ASTM A992 W12×96 column bears on a 24-in. × 24-in. concrete


pedestal with f′c = 3 ksi. The space between the base plate and the
concrete pedestal has grout with f′c = 4 ksi. Design the ASTM A36 base
plate to support the following loads in axial compression:

PD = 115 kips
PL = 345 kips

Refer to the figure in the reference for additional details.

Calculations
Pu = 1.2(115 kips) + 1.6(345 kips) = 690 kips

Comparison
Table 1: Comparison with AISC Design Example J-7

Parameter RAM Connection Reference Difference

A1 (in2) 484 484 none

A2 (in2) 576 576 none

RAM Connection 3 Verification Manual


AISC Verification Examples
Base Plate Bearing on Concrete

Parameter RAM Connection Reference Difference

m (in) 4.97 4.97 none

n (in) 6.12 6.12 none

ϕPp (kips) 875.161 875 none

Cocnrete brearing 875.16 875 < 1%


strength, LRFD (kips)

Concrete bearing strength, 582.86 583 < 1%


ASD (kips)

Notes:
1. RAM Connection reports the Pp separately, and multiplying by ϕ = 0.65 gives a value of 875.16 kips.

Input Data
The following data is input into the New Joint dialog:
Joint Data tab
• Joint = CB
• Column/Section = W 12x96
• Column/Material = ASTM A992 Gr50 (from AISC database and according to the reference)
Loads tab
• Axial = -690 kips
The following data is input into the Connection Pad:
Base Plate group
• Longitudinal dimension = 22 in.
• Transverse dimension = 22 in.
• Thickness = 2 in.
Support group
• Longitudinal dimension = 24 in.
• Transverse dimension = 24 in.
• Material = C 3-40
Anchor group
• Longitudinal edge distance on the plate = 2 in.
• Transverse edge distance on the plate = 2 in.

RAM Connection 4 Verification Manual


AISC Verification Examples
Welded/Bolted Wide Tee Connection to an HSS Column

Note: Any anchor bolt diameter and material may be used for this comparison, as these values
do not affect the compared results with the reference.

1.2 Welded/Bolted Wide Tee Connection to an HSS Column


Reference
American Institute of Steel Construction. 2011. Design Examples V14.1 . Chicago, IL:American Institute of Steel
Construction. p K-2

Problem
From the reference:

Design a connection between an ASTM A992 W16×50 beam and an ASTM


A500 Grade B HSS8×8×4 column using an ASTM A992 WT5×24.5. Use w-
in.-diameter ASTM A325-N bolts in standard holes with a bolt spacing, s,
of 3 in., vertical edge distance Lev of 14 in. and 3 in. from the weld line to
the bolt line. Design as a flexible connection for the following vertical
shear loads:

PD = 6.20 kips
PL = 18.5 kips

Note: A tee with a flange width wider than 8 in. was


selected to provide sufficient surface for flare bevel
groove welds on both sides of the column, because
the tee will be slightly offset from the column
centerline.

Refer to the figure in the reference for additional details.


Vu = 1.2(6.20) + 1.6(18.5) = 37.0 kips

Comparison
Table 2: Comparison with AISC Design Example K-1

Parameter RAM Connection Reference Difference

Tee Bolt Shear (kips) 17.9 17.9 none

Stem shear yielding 117.3 117 < 1%


strength

RAM Connection 5 Verification Manual


AISC Verification Examples
Double Angle Connection to an HSS Column

Parameter RAM Connection Reference Difference

Stem shear rupture 79.56 79.5 < 1%


strength

Stem block shear rupture 97.21 97.3 < 1%


strength

Weld capacity 84.6 106 Connector does not fit in


support. Additionally,
RAM Connection does not
have the weld type for the
standard tee used in the
example.

Input Data
The following data is input into the New Joint dialog:
Joint Data tab:

Joint = BCF
Beam/Section = W 16x50
Beam/Material = ASTM A992 Gr50
Column/Section = HSS_SQR 8x8x1_4
Column/Material = H500 GrB Rectangular

Loads tab:

V2 (beam) = 37 kips

The following data is input into the Connection Pad:


Tee group:

Tee section = WT 5x24.5 (from AISC database)


Material = A992 Gr50 (from AISC database, according to the reference example)
Rows of Bolts, nr = 4
Vertical edge distance, Lev = 1.25 in
Horizontal edge distance, Leh = 1.99 in

RAM Connection 6 Verification Manual


AISC Verification Examples
Double Angle Connection to an HSS Column

1.3 Double Angle Connection to an HSS Column


Reference
American Institute of Steel Construction. 2011. Design Examples V14.1 . Chicago, IL:American Institute of Steel
Construction. p K-13

Problem
From the reference:

Use AISC Manual Tables 10-1 and 10-2 to design a double-angle


connection for an ASTM A992 W36x231 beam to an ASTM A500 Grade B
HSS14x14x½ column. Use ¾-in.-diameter ASTM A325-N bolts in
standard holes. The angles are ASTM A36 material. Use 70-ksi electrodes.
The bottom flange cope is required for erection. Use the following vertical
shear loads:

PD = 37.5 kips
PL = 113 kips

Refer to the figure in the reference for additional details.

Calculations
Vu = 1.2(37.5) + 1.6(113) = 226 kips

Comparison
Table 3: Comparison with AISC Design Example K-3

Parameter RAM Connection Reference Difference

Bolt Shear, LRFD (kips) 286.4 286 < 1%

Weld Strength, LRFD 278.9 279 < 1%


(kips)

Bolt Shear, ASD (kips) 190.9 191 < 1%

Weld Strength, ASD (kips) 186.0 186 none

Input Data
The following data is input into the New Joint dialog:

RAM Connection 7 Verification Manual


AISC Verification Examples
Unstiffened Seated Connection to an HSS Column

Joint Data tab:

Joint = BCF
Beam/Section = W 36x231
Beam/Material = ASTM A992 Gr50
Column/Section = HSS_SQR 14x14x1_2
Column/Material = H500 GrB Rectangular

Loads tab:

V2 (beam) = 226 kips

The following data is input into the Connection Pad:


Members/Coped group:

Bottom coped depth, dcb = 2 in


Bottom coped length, cb = 3 in

Note: These values are both used for demonstrative purposes, as the example does not provide
cope dimensions.

Angle group:

Angle section = LU 4x3-1_2x3_8 (from AISC database, according to the example)


Rows of bolts, nr = 8

Tee group:

Weld size to support (1/16s in), D2 = 5

1.4 Unstiffened Seated Connection to an HSS Column


Reference
American Institute of Steel Construction. 2011. Design Examples V14.1 . Chicago, IL:American Institute of Steel
Construction. p K-16

Problem
From the reference:

Use AISC Manual Table 10-6 to design an unstiffened seated connection


for an ASTM A992 W21×62 beam to an ASTM A500 Grade B HSS12×12×2
column. The angles are ASTM A36 material. Use 70-ksi electrodes. Use the
following vertical shear loads:

PD = 9.00 kips

RAM Connection 8 Verification Manual


AISC Verification Examples
Unstiffened Seated Connection to an HSS Column

PL = 27.0 kips

Refer to the figure in the reference for additional details.

Calculations
Vu = 1.2(9.00) + 1.6(27.0) = 54 kips

Comparison
Table 4: Comparison with AISC Design Example K-4

Parameter RAM Connection Reference Difference

Weld Strength, LRFD 66.74 66.7 < 1%


(kips)

Weld Strength, ASD (kips) 44.49 44.5 < 1%

Input Data
The following data is input into the New Joint dialog:
Joint Data tab:

Joint = BCF
Beam/Section = W 21x62
Beam/Material = ASTM A992 Gr50
Beam/Beam setback, sb = 0.75 in.
Column/Section = HSS_SQR 12x12x1_2
Column/Material = A500 GrB Rectangular

Loads tab:

V2 (beam) = 54 kips

The following data is input into the Connection Pad:


Members group:

Beam setback, sb = 0.75 in.

Unstiffened Seated / Seat Angle group:

Seat angle section = LU 8x4x5_8


Seat angle length, c = 8 in.
Gage (transverse center-to-center spacing), g = 5.5 in.
Weld size to support (1/16s in), D2 = 5

RAM Connection 9 Verification Manual


AISC Verification Examples
Four Bolt Unstiffened Extended End Plate FR Moment Connection (Beam to Column Flange)

Unstiffened Seated / Top Angle group:

Seat angle section = LU 4x4x1_4


Weld size to support (1/16s in), D1 = 3

1.5 Four Bolt Unstiffened Extended End Plate FR Moment Connection


(Beam to Column Flange)
Reference
American Institute of Steel Construction. 2011. Design Examples V14.1 . Chicago, IL:American Institute of Steel
Construction. p IIB-22

Problem
From the reference:

Design a four-bolt unstiffened extended end-plate FR moment connection


between an ASTM A992 W18×50 beam and an ASTM A992 W14×99
column flange to transfer the following vertical shear forces and strong-
axis moments:

VD = 7 kips and MD = 42 kip·ft


VL = 21 kips and ML = 126 kip·ft

Use ASTM A325-N snug-tight bolts in standard holes and 70-ksi


electrodes. The plate is ASTM A36 material.
a. Use the design procedure from AISC Steel Design Guide 4 Extended
End-Plate Moment Connections. Seismic and Wind Applications (Murray
and Sumner, 2003).

Refer to the figure in the reference for additional details.

Calculations
Vu = 1.2(7) + 1.6(21) = 42 kips
Mu = 1.2(42) + 1.6(126) = 252 kip·ft

RAM Connection 10 Verification Manual


AISC Verification Examples
Four Bolt Unstiffened Extended End Plate FR Moment Connection (Beam to Column Flange)

Comparison
Table 5: Comparison with AISC Design Example II.B-4

Parameter RAM Connection Reference Difference

Additional Calculation of 19.22 19.2 < 1%


H0 (in.)

Additional Calculation of 15.65 15.6 < 1%


H1 (in.)

End plate yield line 2.74 2.74 none


mechanism, s (in.)

Yp (in) 139.9 140 < 1%

End plate shear yielding 145.8 146 < 1%


(kips)

Available strength due to 137.0 137 none


shear rupture (kips)

Input Data
The following data is input into the New Joint dialog:
Joint Data tab:

Joint = BCF
Beam/Section = W 18x50
Beam/Material = ASTM A992 Gr50
Column/Section = W14x99
Column/Material = ASTM A992 Gr50

Loads tab:

V2 (beam) = 42 kips
M33 (beam) = 252 kip·ft

Select the Smart Connections/Smart MEP Extended both ways (DG4/Seismic) connection type.
The following data is input into the Connection Pad:
Moment End Plate group:

Plate thickness, tp = 1 in.


Top flange weld type = fillet
Bottom flange weld type = fillet
Bolts = 1"⌀ A325N

RAM Connection 11 Verification Manual


AISC Verification Examples
Four Bolt Unstiffened Extended End Plate FR Moment Connection (Beam to Column Flange)

Gage (transverse center-to-center spacing), g = 4 in.


Vertical edge distance, Lev = 1.75 in.
Horizontal edge distance, Leh = 1.75 in.
Distance from first interior bolt centerline to the beam flange, pfi = 1.5 in.
distance from the outer bolt centerline to the beam flange, pfo = 1.5 in.

1.6 Four Bolt Unstiffened Extended End Plate FR Moment Connection


(Beam to Column Flange)
Reference
American Institute of Steel Construction. 2011. Design Examples V14.1 . Chicago, IL:American Institute of Steel
Construction. p IIB-22

Problem
From the reference:

Design a four-bolt unstiffened extended end-plate FR moment connection


between an ASTM A992 W18×50 beam and an ASTM A992 W14×99
column flange to transfer the following vertical shear forces and strong-
axis moments:

VD = 7 kips and MD = 42 kip·ft


VL = 21 kips and ML = 126 kip·ft

Use ASTM A325-N snug-tight bolts in standard holes and 70-ksi


electrodes. The plate is ASTM A36 material.
b. Use design procedure 2 (then end-plate and larger diameter bolts)
from AISC Design Guide 16, Flush and Extended Multiple-Row Moment
End-Plate Connections (Murray and Shoemaker, 2002).

Refer to the figure in the reference for additional details.

Calculations
Vu = 1.2(7) + 1.6(21) = 42 kips
Mu = 1.2(42) + 1.6(126) = 252 kip·ft

RAM Connection 12 Verification Manual


AISC Verification Examples
Four Bolt Unstiffened Extended End Plate FR Moment Connection (Beam to Column Flange)

Comparison
Table 6: Comparison with AISC Design Example II.B-4

Parameter RAM Connection Reference Difference

w' (in.) 2.69 2.69 none

a1 (in.) 2.38 2.34 1.7% (rounding of small


numbers)

Fi' (kips) 30.41 30.4 < 1%

Qmax,i (kips) 6.09 6.10 < 1%

a0 (in.) 1.5 1.50 none

F0' 30.41 30.4 < 1%

Qmax,o (kips) 9.67 9.68 < 1%

ϕMn (kip·ft) 272.7 273 < 1%

Input Data
The following data is input into the New Joint dialog:
Joint Data tab:

Joint = BCF
Beam/Section = W 18x50
Beam/Material = ASTM A992 Gr50
Column/Section = W14x99
Column/Material = ASTM A992 Gr50

Loads tab:

V2 (beam) = 42 kips
M33 (beam) = 252 kip·ft

Select the Smart Connections/Smart MEP Extended both ways (DG4/Seismic) connection type.
The following data is input into the Connection Pad:
Moment End Plate group:

Plate thickness, tp = 0.875 in.


Flush extension length = 0.1 in.
Top flange weld type = fillet
Bottom flange weld type = fillet

RAM Connection 13 Verification Manual


AISC Verification Examples
All Bolted Double Angle Connection in a Coped Beam

Bolts = 1"⌀ A325N


Gage (transverse center-to-center spacing), g = 4 in.
Vertical edge distance, Lev = 1.5 in.
Horizontal edge distance, Leh = 1.75 in.
Distance from first interior bolt centerline to the beam flange, pfi = 1.5 in.
Distance from the outer bolt centerline to the beam flange, pfo = 1.5 in.
Number of bolt rows = 1 (for bolt group bottom flange, per the reference)

1.7 All Bolted Double Angle Connection in a Coped Beam


Reference
American Institute of Steel Construction. 2011. Design Examples V14.1 . Chicago, IL:American Institute of Steel
Construction. p IIA-9

Problem
From the reference:

Use AISC Manual Table 10-1 to select an all-bolted double-angle


connection between an ASTM A992 W18×50 beam and an ASTM A992
W21×62 girder web to support the following beam end reactions:

RD = 10 kips
RL = 30 kips

The beam top flange is coped 2 in. deep by 4 in. long, Lev = 1¼ in., Leh =
1¾ in. Use ¾-in.-diameter ASTM 325-N or F1852-N bolts in standard
holes and ASTM A36 angles

Refer to the figure in the reference for additional details.

Calculations
Vu = 1.2(10) + 1.6(30) = 60 kips

Comparison
Table 7: Comparison with AISC Design Example II.A-4

Parameter RAM Connection Reference Difference

Bolt bearing on girder 210.6 210 < 1%


web (kips)

RAM Connection 14 Verification Manual


AISC Verification Examples
All Bolted Double Angle Connection in a Coped Beam

Parameter RAM Connection Reference Difference

Flexural local web 234.6 234 < 1%


buckling (kips)

Shear yielding of beam 170.4 170 < 1%


web (kips)

Shear rupture of beam 138.9 139 < 1%


web (kips)

Input Data
The following data is input into the New Joint dialog:
Joint Data tab:

Joint = BG
Beam/Section = W 18x50
Beam/Material = ASTM A992 Gr50
Column/Section = W21x62
Column/Material = ASTM A992 Gr50

Loads tab:

V2 (beam) = 60 kips

Select the Smart Connections/Smart DA All bolted connection type.


The following data is input into the Connection Pad:
Members group:

Top cope depth, dct = 2 in.


Top copy length, ct = 4 in.

Angle / Beam Side group:

Angle section = LU 4X3-1_2X1_4


Angle position on beam = top
Distance to beam top, dtop = 2 in.
Vertical edge distance, Lev = 1.25 in.
Horizontal edge distance, Leh = 1.75 in.

Angle / Support Side group:

Number of bolt rows, nr = 3


Vertical edge distance, Lev = 1.25 in.
Horizontal edge distance, Leh = 1.0625 in.

RAM Connection 15 Verification Manual


AISC Verification Examples
Bolted Flange-Plated FR Moment Connection (Beam to Column Flange)

1.8 Bolted Flange-Plated FR Moment Connection (Beam to Column


Flange)
Reference
American Institute of Steel Construction. 2011. Design Examples V14.1 . Chicago, IL:American Institute of Steel
Construction. p IIB-22

Problem
From the reference:

Design a bolted flange-plated FR moment connection between an ASTM


A992 W18×50 beam and an ASTM A992 W14× 99 column flange to
transfer the following vertical shear forces and strong-axis moments:

VD = 7.0 kips and MD = 42 kip·ft


VL = 21 kips and ML = 126 kip·ft

Use 7/8-in.-diameter ASTM A325-N or F1852-N bolts in standard holes


and 70-ksi electrodes. The flange plates are ASTM A36 material. Check
the column for stiffening requirements.

Refer to the figure in the reference for additional details.

Calculations
Vu = 1.2(7) + 1.6(21) = 42 kips
Mu = 1.2(42) + 1.6(126) = 252 kip·ft

Comparison
Table 8: Comparison with AISC Design Example II.B-1

Parameter RAM Connection Reference Difference

Flange plate tensile 170.1 170 < 1%


strength (kips)

Flange plate tensile 163.1 164 < 1%


rupture (kips)

Flange plate block shear 320.4 320 < 1%


rupture (kips)

RAM Connection 16 Verification Manual


AISC Verification Examples
Bolted Flange-Plated FR Moment Connection (Beam to Column Flange)

Parameter RAM Connection Reference Difference

Flange local bending of 171.1 171 < 1%


column (kips)

Web local yielding of 185.9 186 < 1%


column (kips)

Input Data
The following data is input into the New Joint dialog:
Joint Data tab:

Joint = BCF
Beam/Section = W 18x50
Beam/Material = ASTM A992 Gr50
Column/Section = W14x99
Column/Material = ASTM A992 Gr50

Loads tab:

V2 (beam) = 42 kips
M33 (beam) = 252 kip·ft

Select the Smart Connections/Smart FP Bolted connection type.


The following data is input into the Connection Pad:
Flange Plate group:

Top plate thickness, tp = 0.75 in.


Bottom plate thickness, tpb = 0.75 in.

Flange Plate / Beam Side group:

Bolts = 7/8"⌀ A325N


Number of bolt rows = 4
Gage (transverse center-to-center spacing), g = 4 in.
Vertical edge distance, Lev = 1.5 in.
Horizontal edge distance, Leh = 1.5 in.
Longitudinal distance to beam edge (top plate), ef = 2 in.
Longitudinal distance to beam edge (bottom plate), efb = 2 in.

Flange Plate / Support Side group:

Weld size to support (1/16s in), D2 = 6

RAM Connection 17 Verification Manual


AISC Verification Examples
Moment Frame Beam-to-Column Connection

1.9 Moment Frame Beam-to-Column Connection


Reference
American Institute of Steel Construction. 2010. Seismic Design Manual . Chicago, IL:American Institute of Steel
Construction.

Problem
Refer to Joint JT-1 in Figure 3-2 of the reference. Design a bolted flange-plated fully restrained moment
connection between Beam BM-1 and Column CL-1. The beam and column are ASTM A992 W-shpaes and ASTM
A36 is used for the connecting material. Use ASTM A325-N bolts and 70-ksi electrodes.
From the reference:

LRFD

Vu = 33.9 kips
Mu = 316 kip·ft

Refer to the figure in the reference for additional details.

Comparison
Table 9: Comparison with AISC Seismic Design Example 3.4.4

Parameter RAM Connection Reference Difference

Available flexural strength 351.9 352 < 1%


of beam (kip·ft)

Available bearing strength 628.8 627 < 1%


of beam flange (kips)

Flange plate block shear 320.4 320 < 1%


rupture (kips)

Flange local bending of 171.1 171 < 1%


column (kips)

Web local yielding of 185.9 186 < 1%


column (kips)

RAM Connection 18 Verification Manual


AISC Verification Examples
OMF Beam-Column Connection

Input Data
The following data is input into the New Joint dialog:
Joint Data tab:

Joint = BCF
Beam/Section = W 18x55
Beam/Material = ASTM A992 Gr50
Column/Section = W 12x87
Column/Material = ASTM A992 Gr50

Loads tab:

V2 (beam) = 33.9 kips


M33 (beam) = 316 kip·ft

Select the Smart Connections/Smart FP Bolted connection type.


The following data is input into the Connection Pad:
Flange Plate group:

Top plate thickness, tp = 1 in.


Bottom plate thickness, tpb = 1 in.

Flange Plate / Beam Side group:

Bolts = 7/8"⌀ A325N (from AISC database, according to the example)


Number of bolt rows, nr = 5
Gage (transverse center-to-center spacing), g = 4 in.
Longitudinal distance to top plate edge, Lev = 2 in.
Transverse distance to top plate edge, Leh = 1.5 in.
Longitudinal distance to bottom plate edge, Levb = 2 in.
Transverse distance to bottom plate edge, Lehb = 1.5 in.
Longitudinal distance to beam edge (top plate), ef = 2 in.
Longitudinal distance to beam edge (bottom plate), efb = 2 in.

Flange Plate / Support Side group:

Weld size to support (1/16s in), D2 = 9

RAM Connection 19 Verification Manual


AISC Verification Examples
OMF Beam-Column Connection

1.10 OMF Beam-Column Connection


Reference
American Institute of Steel Construction. 2010. Seismic Design Manual. Chicago, IL:American Institute of Steel
Construction.

Problem
Refer to Joint JT-1 in Figure 4-2 of the reference. Design a fully restrained (FR) moment connection for the
configuration shown in Figure 4-3 of the reference. The beam and column are ASTM A992 W-shapes and the
plate material is ASTM A36. Use 70-ksi electrodes and ASTM A325 bolts.
To avoid the field welding requirements associated with the prescriptive connection described in AISC Seismic
Provisions Section E1.6b(c), an eight-bolt stiffened end-plate connection is used.
The required shear strengths for the column based on a second-order analysis are given in Example 4.2.2. The
other shear forces acting at the beam end simultaneously with Emh are:

VD = 4.86 kips
VS = 6.49 kips

Refer to the figure in the reference for additional details.

Calculations
VEV = 0.2SDSD = 0.2×(0.528)×(4.86 kips) = 0.513 kips

Comparison
Table 10: Comparison with AISC Seismic Design Example 4.2.4

Parameter RAM Connection Reference Difference

Necessary parameters for 2.65 2.65 none


end plate thickness, s (in.)

Yp 231.8 232 < 1%

Necessary parameters for 2.56 2.56 none


column flange flexural
strength, s (in.)

Necessary parameters for 2.01 2.02 < 1%


column flange flexural
strength (psi)

Yc 239.0 239 none

RAM Connection 20 Verification Manual


AISC Verification Examples
OMF Beam-Column Connection

Parameter RAM Connection Reference Difference

Available strength of 2,911 2,910 < 1%


stiffened column flange
(kips)

Beam web weld strength 170.1 14.2 kip/in (170.4 kip/ft) < 1%
to reach yield stress
(kip/ft)

Available strength per 36.45 (72.9 kips over 2 36.5 < 1%


stiffener (kips) stiffeners)

Input Data
The following data is input into the New Joint dialog:
Joint Data tab:

Joint = BCF
Beam/Section = W 18x40
Beam/Material = ASTM A992 Gr50
Column/Section = W 12x35
Column/Material = ASTM A992 Gr50
Seismic load resisting system = OMF (set

Loads tab:

V2 (beam) = 15.9 kips


Beam / Axial = 69 kip (stiffener required strength)

Set the Seismic Parameters option in the Connection Design Configuration dialog.
Select the Smart Connections/Smart MEP Extended both ways (DG4/Seismic) connection type.
The following data is input into the Connection Pad:
Members group:

Thickness for beam stiffener = 0.4375 in.

Connector group:

Four/eight bolts in tension = 8 tension bolts


Plate thickness, tp = 0.625 in.

Connector / Beam Side group:

Top flange weld type = fillet


Top beam flange weld = E70XX
Weld size to top beam flange (1/16s in), D1 = 7
Bottom flange weld type = fillet

RAM Connection 21 Verification Manual


AISC Verification Examples
SMF Beam-Column Connection

Bottom beam flange weld = E70XX


Weld size to bottom beam flange (1/16s in), D3 = 7
Weld size to beam web (1/16s in), D2 = 4

Connector / Support Side group:

Bolts = 3/4"⌀ A325N


Gage (transverse center-to-center spacing), g = 4 in.
Vertical spacing between bolt rows, s = 3 in.
Vertical edge distance, Lev = 1.25 in.
Horizontal edge distance, Leh = 1.5 in.
Distance from first interior bolt centerline to the beam flange, pfi = 2 in.
Distance from the outer bolt centerline to the beam flange = 2 in.

Stiffeners / Transverse Stiffeners group:

Position = both
Full depth = Check (set the option)
Transverse stiffeners width, bs = 3 in.
Transverse stiffener thickness, ts = 0.50 in.
Material = A36
Welding electrode to support = E70XX
Weld size to support (1/16s in), D = 4

1.11 SMF Beam-Column Connection


Reference
American Institute of Steel Construction. 2010. Seismic Design Manual. Chicago, IL:American Institute of Steel
Construction.

Problem
The SMF beam-column connection design presented in this example has been chosen to demonstrate the
application of the design provisions for prequalified RBS connections in accordance with ANSI/AISC 358. This
example demonstrates that the RBS geometry developed below is satisfactory. Some of the results from this
example are used in Example 4.3.3. The geometry of an RBS connection is not unique and alternative
configurations of the RBS geometry are possible.
Refer to Joint JT-1 in Figure 4-8 of the reference. Design the connection between Beam BM-1 and Column CL-1
using the reduced beam section (RBS) shown in Figure 4-9 of the reference. All beams and columns are ASTM
A992 W-shapes. Plate material is ASTM A572 Grade 50. The gravity loads on the beam are:

wD = 0.84 kip/ft
wL = 0.60 kip/ft

RAM Connection 22 Verification Manual


AISC Verification Examples
SMF Beam-Column Connection

Refer to the figure in the reference for additional details.

Calculations
VD = 30 ft × 0.94 kip/ft = 25.2 kips
VL = 30 ft × 0.60 kip/ft = 18 kips

Comparison
Table 11: Comparison with AISC Seismic Design Example 4.3.4

Parameter RAM Connection Reference Difference

Mpr (kip·in) 8,655 8,670 < 1%

Vp (kips) 72.1 72.1 none

Mf (kip·in) 9,700 9,720 < 1%

Plastic moment of hte 11,000 11,000 none


beam based on the
expected yield stress
(kip·in)

Shear strength of the 480 480 none


panel zone (kips)

Input Data
The following data is input into the New Joint dialog:
Joint Data tab:

Joint = BCF
Beam/Section = W 24x76
Beam/Material = ASTM A992 Gr50
Column/Section = W 114x176
Column/Material = ASTM A992 Gr50
Seismic load resisting system = OMF (set

The following data can be added after the Seismic Parameters option is set in the Connection
Design Configuration dialog:

Seismic load resisting system = SMF


Beam/ Length, L = 30 ft.
Beam / Seismic Design / RBS Connection = Yes
Beam / Seismic Design / Horizontal distance to start of RBS cut, a = 5.5 in.
Beam / Seismic Design / Length of RBS cut, b = 18 in.

RAM Connection 23 Verification Manual


AISC Verification Examples
SCBF Brace-to-Brace Connection

Beam / Seismic Design / RBS cut maximum depth, c = 2 in.


Beam / Seismic Design / Shear due to gravity loads between plastic hinges, Vg = 17.25 kips

Loads tab:

V2 (beam) DL = 25.2 kips


V2 (beam) LL = 18 kips

Note: Two load case types: DL and LL are added using the Load Conditions dialog.

Select the Smart Connections/Smart DW connection type.


The following data is input into the Connection Pad:
General Information group:

Design criteria / Frame stability considered in analysis = checked (set the option)

Stiffeners / Transverse Stiffeners group:

Position = both
Full depth = checked (set the option)
Transverse stiffeners width, bs = 5.5 in.
Corner clip length, cc = 1 in.
Corner clip width, cc = 1 in.
Transverse stiffener thickness, ts = 0.75 in.
Material = A572 Gr 50
Welding electrode to support = E70XX
Weld size to support (1/16s in), D = 8

Stiffeners / Column Web Panel Zone Stiffeners group:

Stiffener type = doubler plate


Position = one side
Stiffener thickness, ts = 0.50 in.
Material = A572 Gr 50
Weld type to column flange = fillet
Welding electrode to support = E70XX
Weld size to support (1/16s in), D = 3

Note: RAM Connection cannot use different dimensions for transverse stiffeners on both sides.

RAM Connection 24 Verification Manual


AISC Verification Examples
SCBF Brace-to-Brace Connection

1.12 SCBF Brace-to-Brace Connection


Reference
American Institute of Steel Construction. 2010. Seismic Design Manual. Chicago, IL:American Institute of Steel
Construction.

Problem
An alternative design for Example 5.3.8 at Joint JT/1 of Figure 5-11 in the reference is presented here in this
example. Example 5.3.8 used separate gusset plates for each brace, while this example uses continuous “chevron
type” gusset plates for the top and bottom braces as shown in Figure 5-29 in the reference. This is a common
arrangement for this situation, and the example provides and admissible internal force distribution that differs
from the distribution used for the four separate gusset plates. All braces are ASTM A500 Grade B round HSS and
the beam is an ASTM A992 W27x114. For the connection, ASTM A36 plate material and 70-ksi electrodes are
used.
Refer to the figure in the reference for additional details.

Comparison
Table 12: Comparison with AISC Seismic Design Example 5.3.9

Parameter RAM Connection Reference Difference

Brace H1 (kips)1 -159.8 -160 < 1%


Interface
Forces V1 (kips)1 -159.8 -160 < 1%

H2 (kips)1 217.1 217 < 1%

V2 (kips)1 217.1 217 < 1%

H1 (kips)2 388.9 389 < 1%

V1 (kips)2 388.9 389 < 1%

H2 (kips)2 -314 -314 none

V2 (kips)2 -314 -314 none

Upper Gusset Nu (kips) 57.28 57 < 1%

Vu (kips) -376.9 -377 < 1%

Mu (kip·ft) -5,145 -5,160 < 1%

Gusset capacity (kips) 869.4 869 < 1%

RAM Connection 25 Verification Manual


AISC Verification Examples
SCBF Brace-to-Brace Connection

Parameter RAM Connection Reference Difference

Lower Gusset Nu (kips) 74.95 75 < 1%

Vu (kips) 702.9 703 < 1%

Mu (kip·ft) 9,594 9,630 < 1%

Gusset capacity (kips) 1,377 1,380 < 1%

Notes:
1. Refer to Figure 5-30a in the reference.
2. Refer to Figure 5-30b in the reference.

Input Data
The following data is input into the New Joint dialog:
Joint Data tab:

Joint = CVR
Actual members / Upper gusset = yes
Actual members / Lower gusset = yes
Beam/Section = W 27x114
Beam/Material = ASTM A992 Gr50
Upper right brace / Section = HSS_SQR 6x6x5_16
Upper right brace / Material = A500 GrB Rectangular
Upper left brace / Section = HSS_SQR 6x6x5_16
Upper left brace / Material = A500 GrB Rectangular
Lower right brace / Section = HSS_RND 6.875x0.500
Lower right brace / Material = A500 GrB Rounded
Lower left brace / Section = HSS_RND 6.875x0.500
Lower left brace / Material = A500 GrB Rounded

The following data can be added after the Seismic Parameters option is set in the Connection
Design Configuration dialog:

Braced frame system = SCBF

Loads tab:

Braces / Upper right brace = 307 kips


Braces / Upper left brace = -226 kips
Braces / Lower left brace = 550 kips
Braces / Lower right brace = -444 kips

Select the Gusset Connections/CVR connection type.

RAM Connection 26 Verification Manual


AISC Verification Examples
SCBF Brace-to-Brace Connection

The following data is input into the Connection Pad:


General Information group:

Design criteria / Dimensions calculation = Manual

Members group:

Upper right brace / Additional geometric data / Minimum distance to other members, Le = 8 in.
Upper right brace / Additional geometric data / Left distance, Le1 = 1 in.
Upper right brace / Additional geometric data / Right distance, Le2 = 1 in.
Upper right brace / Additional geometric data / Length on beam, LH = 23 in.
Upper left brace / Additional geometric data / Minimum distance to other members, Le = 8 in.
Upper left brace / Additional geometric data / Left distance, Le1 = 1 in.
Upper left brace / Additional geometric data / Right distance, Le2 = 1 in.
Upper left brace / Additional geometric data / Length on beam, LH = 23 in.
Lower right brace / Additional geometric data / Minimum distance to other members, Le = 10 in.
Lower right brace / Additional geometric data / Left distance, Le1 = 1 in.
Lower right brace / Additional geometric data / Right distance, Le2 = 1 in.
Lower right brace / Additional geometric data / Length on beam, LH = 25.5 in.
Lower left brace / Additional geometric data / Minimum distance to other members, Le = 10 in.
Lower left brace / Additional geometric data / Left distance, Le1 = 1 in.
Lower left brace / Additional geometric data / Right distance, Le2 = 1 in.
Lower left brace / Additional geometric data / Length on beam, LH = 25.5 in.

Interfaces group:

Upper gusset / General / Thickness, tp = 0.875 in.


Upper gusset / General / Material = A36
Upper gusset / Directly welded / Weld size to beam (1/16s in), D = 5
Upper right brace / Gusset-to-Brace connection / Length on toe, Lt = 15 in.
Upper right brace / Gusset-to-Brace connection / Length on heal, Lh = 15 in.
Upper right brace / Gusset-to-Brace connection / Weld size (1/16s in), D = 4
Upper left brace / Gusset-to-Brace connection / Length on toe, Lt = 15 in.
Upper left brace / Gusset-to-Brace connection / Length on heal, Lh = 15 in.
Upper left brace / Gusset-to-Brace connection / Weld size (1/16s in), D = 4
Lower gusset / General / Thickness, tp = 1.25 in.
Lower gusset / General / Material = A36
Lower gusset / Directly welded / Weld size to beam (1/16s in), D = 8
Lower right brace / Gusset-to-Brace connection / Length on toe, Lt = 25 in.
Lower right brace / Gusset-to-Brace connection / Length on heal, Lh = 25 in.
Lower right brace / Gusset-to-Brace connection / Weld size (1/16s in), D = 4
Lower left brace / Gusset-to-Brace connection / Length on toe, Lt = 25 in.
Lower left brace / Gusset-to-Brace connection / Length on heal, Lh = 25 in.
Lower left brace / Gusset-to-Brace connection / Weld size (1/16s in), D = 4

RAM Connection 27 Verification Manual


AISC Verification Examples
SMF Beam-Column Connection

1.13 SMF Beam-Column Connection


Reference
International Code Council. 2006. 2006 IBC Structural/Seismic Design Manual, Volume 3: Building Design
Examples for Steel and Concrete. Country Club Hills, IL:International Code Council

Problem
The RBS connection is a pre-qualified connection type per AISC 358. This design example follows the procedure
outlined in AISC 358 with reference to AISC 341 and AISC 360.
The basis for the prequalification of the RBS connection is widely attributed to initial RBS connection tests
conducted at the University of Texas Ferguson Laboratory (Engelhardt etal., 1996). Extensive additional testing
of RBS joint combinations performed as part of projects confirmed the viability of the connection using myriad
beam and column sizes. Further information on the research supporting the validity of pre/qualification
parameters may be found in FEMA-355D State of the Art Report on Connection Performance and AISC 358.
The following calculations comprise a design methodology that is inherently iterative and requires some
experience to gain proficiency. After considering code drift limits and evaluating several combinations for strong
column-weak beam and panel zone strength criteria, the combination of a W27x84 beam and W14x176 column
was selected for use in the factored load combinations (Part 5), and this combination of beam and column sizes
in the computer analysis results in overall frame drifts within the code limits (Part 4). The W14x176 column was
chosen to elucidate details associated with doubler plates and possibly reduce the cost of the frame. When given
the option, steel fabricators have elected W14x176 columns are to be full-height, one length. Full=height
columns without splices were found to be the least-cost option. Column splices in SMFs must comply with AISC
341. The reduced beam section (RBS) connection developed in this example is shown in Figure 3-8 and 3-13

Comparison
Parameter RAM Connection Reference Difference

Plastic section modulus at 169.3 168.95 < 1% (small difference


the RBS (in.3) may be due to error in
reference, which uses c =
2.25 in rather than the
cited value)

Maximum probable 10,707 10,686 < 1%


moment at the RBS
(kip·in)

Expected plastic moment 13,420 13,420 none


of the beam (kip·in)

Mf (kip·in) 12,424 12,403 < 1%

RAM Connection 28 Verification Manual


AISC Verification Examples
SMF Beam-Column Connection

Parameter RAM Connection Reference Difference

Required shear strength 101 101 none


(kips)

Minimum required 1.67 1.66 < 1%


thickness of column flange
(in)

Panel zone shear strength 469.3 469 < 1%


(kips)

Input Data
The following data is input into the New Joint dialog:
Joint Data tab:

Joint = BCF
Beam / Section = W27x84
Beam / Material = ASTM A992 Gr 50
Column / Section = W14x176
Column / Material = ASTM A992 Gr 50

The following data can be added after the Seismic Parameters option is set in the Connection
Design Configuration dialog:

Seismic load resisting system = SMF


Beam / Length, L = 28 ft
Beam / Seismic Design / RBS Connection = Yes
Beam / Seismic Design / Horizontal distance to start of RBS cut, a = 6 in.
Beam / Seismic Design / Length of RBS cut, b = 22 in.
Beam / Seismic Design / RBS cut maximum depth, c = 2.24 in.
Beam / Seismic Design / Shear due to gravity loads between plastic hinges, Vg = 26.33 kips

Loads tab:

DL / V2 = 16.4 kips
DL / M33 = 86.83 kip·ft
LL / V2 = 13.3 kips
LL / M33 = 77 kip·ft
EQ / V2 = 19 kips
EQ M 33 = 256.9 kip·ft

Note: Three load case types: DL, LL, and EQ are added using the Load Conditions dialog. The
Generate Load Combinations dialog is then used to create a load combination per AISC 341-05
LRFD amplified seismic factored combos.

Select the Smart Connections/Smart DW connection type.

RAM Connection 29 Verification Manual


AISC Verification Examples
SMF Beam-Column Connection

The following data is input into the Connection Pad:


General Information group:

Design criteria / Frame stability considered in analysis = checked (set the option)

RAM Connection 30 Verification Manual


Eurocode Verification Examples
2
The following verification examples were designed per EN 1993: Eurocode 3: Design of steel structures.

2.1 Fin Plates - Beam to Beam


Reference
Steel Construction Institute. 2011. Joints in Steel Construction – Simple Joints to Eurocode 3 (Publication P358).
Ascot:The Steel Construction Institute. pp 126-140. Co-published by The British Constructional Steelwork
Association Limited.

Problem
From the reference:

Check the following beam to beam connection for the design forces
shown. Yellow pages are used for the initial selection of the connection
detail. A fin plate with a single vertical line of bolts would be adequate for
both connections in this example, but a double vertical line was used for
the 533 x 229 x 92 UKB in order to demonstrate the design checks
required for this configuration.

Refer to the figure in the reference for additional details.

Comparison
Table 13: Comparison with SCI P358 Fin Plate Example 1

Parameter RAM Connection Reference Difference

Fin plate bolt group shear: VRd 584.07 577 None (The difference is due to
(kN) rounding)

Fin plate bolt group bearing : VRd 572.48 574 None (The difference is due to
(kN) rounding)

RAM Connection 31 Verification Manual


Eurocode Verification Examples
Double Cleats Aangle – Beam to Column Web – Tying Resistance

Parameter RAM Connection Reference Difference

Beam web bolt group bearing: VRd 562.63 565 none


(kN)

Fin plate shear at net section (kN) 537.99 538 None

Fin plate shear at gross section (kN) 450.06 450 None

Fin plate block tearing: VVd (kN) 494.38 494 None (The difference is due to
rounding)

Fin plate lateral torsional buckling 742.5 743 None


on fin plates : VRd (kN)

Beam web in shear gross area: VRd 793.64 794 None (The difference is due to
(kN) rounding)

Beam web shear net section: VRd 836.6 837 None (The difference is due to
(kN) rounding)

Beam block tearing: VRd (kN) 480.51 481 None (The difference is due to
rounding)

Moment resistance of the beam at 164.33 164 None


the notch in the presence of shear:
Mc,Rd (kN·m)

2.2 Double Cleats Aangle – Beam to Column Web – Tying Resistance


Reference
Steel Construction Institute. 2011. Joints in Steel Construction – Simple Joints to Eurocode 3 (Publication P358).
Ascot:The Steel Construction Institute. pp 141-146. Co-published by The British Constructional Steelwork
Association Limited.

Problem
From the reference:

Check the following beam to column connection for the tying force
shown.

Note: Fin plate example, but we use to test “Double cleats angle” similar capacities.

Refer to the figure in the reference for additional details.

RAM Connection 32 Verification Manual


Eurocode Verification Examples
Partial Depth End Plate – Beam to Hollow Section Column

Comparison
Table 14: Comparison with SCI P358 Fin Plate Example 2

Parameter RAM Connection Reference Difference

Angle - beam side block tearing due 1,321 661 None (In reference the capacity is
to tension: FRd (kN) for one fin plate)

Angle – beam side bolt shear: FRd 855.27 428 None (In reference the capacity is
(kN) for one fin plate)

Angle – beam side bolt bearing due 1,129.48 560 None (In reference the capacity is
to tension: FRd (kN) for one fin plate)

Beam side block tearing due to 597.37 597 None (The difference is due to
tension: FRd (kN) rounding)

Beam side bolt bearing due to 429.20 432 None (The difference is due to
tension: FRd (kN) rounding)

2.3 Partial Depth End Plate – Beam to Hollow Section Column


Reference
Steel Construction Institute. 2011. Joints in Steel Construction – Simple Joints to Eurocode 3 (Publication P358).
Ascot:The Steel Construction Institute. pp 50-58. Co-published by The British Constructional Steelwork
Association Limited.

Problem
From the reference:

Check the following beam to hollow section column connection for the
design forces shown using property class 8.8 bolts in Flowdrill threaded
holes in the column.
Note:
The connections should be checked independently for (i) shear forces and
(ii) tying forces and not for both forces acting at the same time.

Refer to the figure in the reference for additional details.

RAM Connection 33 Verification Manual


Eurocode Verification Examples
Column Splice – End Plate with Rectangular Column

Comparison
Table 15: Comparison with SCI P358 End Plates Example 3

Parameter RAM Connection Reference Difference

Shear resistance of beam web at the 620.59 621 None (The difference is due to
connection: Vpl,Rd (kN) rounding)

End plate bolt group shear: VVd 903.17 902 None (The difference is due to
(kN) rounding)

End plate shear at gross section: 1,290.17 1,290 None (The difference is due to
VVd (kN) rounding)

End plate shear at net section: VVd 1,539.07 1,539 None (The difference is due to
(kN) rounding)

End plate block tearing: VVd (kN) 1,194.99 1,195 None (The difference is due to
rounding)

Web or wall local shear with one 1,332.24 1,332 None


beam: VVd (kN)

Web or wall local net shear with 1,196.43 1,233 None (Reference error; using d0 as
one beam: VVd (kN) bolt diameter and not hole
diameter)

Structural integrity (Plate side) 449.55 451 None (The difference is due to
Tension: FFd (kN) rounding)

Structural integrity (Beam side) 1,618.75 1,619 None (The difference is due to
Web in tension: FFd (kN) rounding)

Structural integrity (support side) 860.45 862 None (The difference is due to
Wall tying capacity: FFd (kN) rounding)

2.4 Column Splice – End Plate with Rectangular Column


Reference
Steel Construction Institute. 2011. Joints in Steel Construction – Simple Joints to Eurocode 3 (Publication P358).
Ascot:The Steel Construction Institute. pp 215-218.. Co-published by The British Constructional Steelwork
Association Limited.

RAM Connection 34 Verification Manual


Eurocode Verification Examples
Column Splice – End Plate with Circular Column

Problem
From the reference:

Check the following connection for the design forces shown:

Refer to the figure in the reference for additional details.

Comparison
Table 16: Comparison with SCI P358 Column Splices Example 4

Parameter RAM Connection Reference Difference

Plate and bolt tension: FFd (kN) 842.89 867 None (The difference is due to
rounding)

Bolt tension: FFd (kN) 1,219.97 1,218 None (The difference is due to
rounding)

2.5 Column Splice – End Plate with Circular Column


Reference
Steel Construction Institute. 2011. Joints in Steel Construction – Simple Joints to Eurocode 3 (Publication P358).
Ascot:The Steel Construction Institute. pp 219-223. Co-published by The British Constructional Steelwork
Association Limited.

Problem
From the reference:

Check the following connection for the design forces shown:

Refer to the figure in the reference for additional details.

Comparison
Table 17: Comparison with SCI P358 Column Splices Example 5

Parameter RAM Connection Reference Difference

Plate tension: FEd (kN) 1,031.14 1,030 None (The difference is due to
rounding)

RAM Connection 35 Verification Manual


Eurocode Verification Examples
Column splice – Web Angle Cleats, Bearing Splice (No Net Tension)

Parameter RAM Connection Reference Difference

Plate and bolt tension: FEd (kN) 1,063.34 1,061 None (The difference is due to
rounding)

Bolt tension: FEd (kN) 1,626.62 1,624 None (The difference is due to
rounding)

2.6 Column splice – Web Angle Cleats, Bearing Splice (No Net Tension)
Reference
Steel Construction Institute. 2011. Joints in Steel Construction – Simple Joints to Eurocode 3 (Publication P358).
Ascot:The Steel Construction Institute. pp 198-201. Co-published by The British Constructional Steelwork
Association Limited.

Problem
From the reference:

A bearing splice for connecting two different size universal column


sections using external cover plates and with a division plate between.

Refer to the figure in the reference for additional details.

Note: Example does not need checks on shear, because can be resisted by friction across the bearing surfaces.

Comparison
Table 18: Comparison with SCI P358 Column Splices Example 1

Parameter RAM Connection Reference Difference

Geometric considerations: 127.05 127 None


Angle minimum length
(mm)

Geometric considerations: 25.7 25.7 None


Bearing plate thickness
(mm)

RAM Connection 36 Verification Manual


Eurocode Verification Examples
Column Splice – Flange Cover Plate, Nonbearing Splice

2.7 Beam Splice – Web Cover Plate


Reference
Steel Construction Institute. 2013. Joints in Steel Construction – Moment-Resisting Joints to Eurocode 3
(Publication P398). Ascot:The Steel Construction Institute. pp 129-140. Co-published by The British
Constructional Steelwork Association Limited.

Problem
From the reference:

Design a bolted cover plate beam splice that connects two 457 x 191 x 67
UKB S275 sections. The splice carries a vertical shear, an axial force and
bending moment and is to be non-slip at serviceability (Category B
connection). The splice is located near to a restraint therefore it will not
carry moments due to strut action.

Refer to the figure in the reference for additional details.

Comparison
Table 19: Comparison with SCI P398 Example D.1 Beam Splice

Parameter RAM Connection Reference Difference

Web plate shear at gross section: 850.11 850 None


VVd (kN)

Web plate shear at net section: VVd 1,179.26 1,180 None


(kN)

Beam shear at net section: (kN) 760.19 764 None (Reference error; using “r”
wrong value)

Web plate bending: MMd (kN·m) 105.97 106 None

Web plate compression: NNd (kN) 1,870 1,870 None

RAM Connection 37 Verification Manual


Eurocode Verification Examples
Column Splice – Flange Cover Plate, Nonbearing Splice

2.8 Column Splice – Flange Cover Plate, Nonbearing Splice


Reference
Steel Construction Institute. 2011. Joints in Steel Construction – Simple Joints to Eurocode 3 (Publication P358).
Ascot:The Steel Construction Institute. pp 206-214. Co-published by The British Constructional Steelwork
Association Limited.

Problem
From the reference:

A non-bearing splice for universal columns, with all forces transferred by


the cover plates, and including a structural integrity check.

Refer to the figure in the reference for additional details.

Comparison
Table 20: Comparison with SCI P358

Parameter RAM Connection Reference Difference

Plate resistance Compression: NNd 816.82 817 None


(kN)

Plate bolt group shear: FFd (kN) 828.85 840 None (The difference is due to
rounding)

Bending cover plates (kN·m) 260.23 260 None

Bolt resistance to bending (kN·m) 270.62 274 None (The difference is due to
rounding)

Bending cover plates mino axis 68.75 69 None


(kN·m)

Bolt resistance to bending: FFd 103.61 105 None (The difference is due to
(kN) rounding)

Plate shear: VVd (kN) 857.37 779 None (Reference error, using wrong
γM0 factor)

Bolt shear: FFd (kN) 103.61 105 None (The difference is due to
rounding)

Structural integrity front plate – 797.04 797 None


Tension at net section (kN)

RAM Connection 38 Verification Manual


Eurocode Verification Examples
Bolted End Plate Connection (Unstiffened)

2.9 Bolted End Plate Connection (Unstiffened)


Reference
Steel Construction Institute. 2013. Joints in Steel Construction – Moment-Resisting Joints to Eurocode 3
(Publication P398). Ascot:The Steel Construction Institute. pp 83-105. Co-published by The British
Constructional Steelwork Association Limited.

Problem
From the reference:

Determine the resistances for the extended end plate connection shown
below. It may be assumed that the design moments in the two beams are
equal and opposite.

Refer to the figure in the reference for additional details.

Comparison
Table 21: Comparison with SCI P398 Example C.1

Parameter RAM Connection Reference Difference

Row 1, alone, column flange 398.36 398 None


bending: FFd (kN)

Row 1, alone, column web in 712.69 790 Example reference using wrong beff
transverse tension: FFd (kN)

Row 1, alone, end plate bending: 377.26 377 None


FFd (kN)

Row 2, alone, column flange 398.36 398 None


bending: FFd (kN)

Row 2, alone, column web in 712.69 790 None


transverse tension: FFd (kN)

Row 2, alone, end plate bending: 406.66 406 None


FFd (kN)

Row 2, alone, Beam web in tension: 672.76 675 None


FFd (kN)

RAM Connection 39 Verification Manual


Eurocode Verification Examples
Bolted End Plate Haunched

Parameter RAM Connection Reference Difference

Row 2, with row 1, column web in 321.03 320 None


tension: FFd (kN)

Row 3, alone, column flange 398.36 398 None


bending: FFd (kN)

Row 3, alone, column web in 712.69 790 Example reference using wrong beff
transverse tension: FFd (kN)

Row 3, alone, end plate bending: 406.66 406 None


FFd (kN)

Row 3, alone, Beam web in tension: 672.76 675 None


FFd (kN)

Row 3, with row 2, Effective 292.53 291 None


resistance: FFd (kN)

Compression zone, Column web in 839.86 841 None


transverse compression: FFd (kN)

Compression zone, beam flange and 1,254.11 1,254 None


web compression: FFd (kN)

Moment resistance of joint: MMd 415.77 416 None


(kN·m)

Vertical shear resistance of bolt 498.83 500 None


group: FFd (kN)

2.10 Bolted End Plate Haunched


Reference
Núñez, E. and Malik, A. 2009. Example: Portal frame - eaves moment connection. www.access-steel.com

Problem
From the reference:

This example presents a method for calculating the moment resistance


and the shear resistance of an eaves moment connection, as well as the
design of welds. For the calculation of the moment resistance a simplified
conservative method is used, which makes possible to avoid the

RAM Connection 40 Verification Manual


Eurocode Verification Examples
Bolted End Plate Haunched

calculation of bolt row groups. The connection is a Category A: Bearing


type bolted connection using non-preloaded bolts.

Refer to the figure in the reference for additional details.

Comparison
Table 22: Comparison with Example: Portal frame - eaves moment connection

Parameter RAM Reference Difference


Connection

Without Row 1, alone, column flange 324.71 298 Example uses calculations for leff
suppleme bending: FFd (kN) and beff that are not reference in the
ntary web standard
plates
Row 1, alone, column web in 481.12 355 Example uses calculations for leff
transverse tension: FFd (kN) and beff that are not reference in the
standard

Row 1, alone, end plate bending: 325 298 Example uses calculations for leff
FFd (kN) and beff that are not reference in the
standard

Row 2, alone, column flange 351.62 294 Example uses calculations for leff
bending: FFd (kN) and beff that are not reference in the
standard

Row 2, alone, column web in 600.14 337 Example uses calculations for leff
transverse tension: FFd (kN) and beff that are not reference in the
standard

Row 2, alone, end plate bending: 406.66 406 None


FFd (kN)

Row 2, alone, Beam web in tension: 795.80 807 None


FFd (kN)

Row 3, alone, column flange 351.62 291 Example uses calculations for leff
bending: FFd (kN) and beff that are not reference in the
standard

Row 3, alone, column web in 600.14 323 Example uses calculations for leff
transverse tension: FFd (kN) and beff that are not reference in the
standard

Row 3, alone, end plate bending: 398.36 403 None


FFd (kN)

Row 3, alone, Beam web in tension: 722.57 723 None


FFd (kN)

RAM Connection 41 Verification Manual


Eurocode Verification Examples
Unstiffened Column Base Plate

Parameter RAM Reference Difference


Connection

Row 4, alone, column flange 351.62 291 Example uses calculations for leff
bending: FFd (kN) and beff that are not reference in the
standard

Row 4, alone, column web in 600.14 323 Example uses calculations for leff
transverse tension: FFd (kN) and beff that are not reference in the
standard

Row 4, alone, end plate bending: 398.36 403 None


FFd (kN)

Row 4, alone, Beam web in tension: 722.57 723 None


FFd (kN)

Row 5, alone, column flange 351.62 321 None


bending: FFd (kN)

Row 5, alone, column web in 600.14 465 Example uses calculations for leff
transverse tension: FFd (kN) and beff that are not reference in the
standard

Row 5, alone, end plate bending: 398.36 403 None


FFd (kN)

Row 5, alone, Beam web in tension: 722.57 723 None


FFd (kN)

Compression zone, Column web in 1,799.91 1,966 Example uses calculations for leff
transverse compression: FFd (kN) and beff that are not reference in the
standard

Compression zone, haunch flange 1,230.96 1,231 None


and web compression: FFd (kN)

Compression zone, column web 1,113.27 1,113.3 None


panel in shear: VVd (kN)

With Compression zone, column web 1,914.80 1,726 Example uses calculations for leff
suppleme panel in shear: VVd (kN) and beff that are not reference in the
ntary web standard
plates
Moment resistance of joint: MMd 922.18 912 None
(kN·m)

RAM Connection 42 Verification Manual


Eurocode Verification Examples
Unstiffened Column Base Plate

2.11 Unstiffened Column Base Plate


Reference
Steel Construction Institute. 2013. Joints in Steel Construction – Moment-Resisting Joints to Eurocode 3
(Publication P398). Ascot:The Steel Construction Institute. pp 143-150. Co-published by The British
Constructional Steelwork Association Limited.

Problem
From the reference:

Verify the resistance of the unstiffened column base plate shown below.

Refer to the figure in the reference for additional details.

Comparison
Table 23: Comparison with SCI P398 Example E.1

Parameter RAM Connection Reference Difference

NLf (kN) 183.23 182 None

NRf (kN) 2,183.23 2,182 None

zt (mm) 225 225 None

zc (mm) 147.9 148 None

beff (mm) 531.01 531 None

leff (mm) 242.31 243 None

Compression resistance of the 2,187.33 2,193 None


foundation: FFd (kN)

Resistance of the column flange and 2,286 2,282 None


web in compression: FFd (kN)

leff (kN) 791.05 754 Difference due to the use of mx


exact value

leff (kN) 695.53 677 Difference due to the use of mx


exact value

leff (kN) 300 300 None

RAM Connection 43 Verification Manual


Eurocode Verification Examples
Base Plate

Parameter RAM Connection Reference Difference

leff (mm) 691.1 668 Difference due to the use of mx


exact value

leff (mm) 593.33 576 Difference due to the use of mx


exact value

leff (mm) 397.78 392 Difference due to the use of mx


exact value

Resistance of base plate in bending: 47.81 47.80 None


MMd (kN*m)

Column – Weld shear: FFd (kN) 490.48 1,216 Wrong effective weld length used in
reference

2.12 Base Plate


Reference
Steel Construction Institute. 2011. Joints in Steel Construction – Simple Joints to Eurocode 3 (Publication P358).
Ascot:The Steel Construction Institute. pp 240-242. Co-published by The British Constructional Steelwork
Association Limited.

Problem
From the reference:

Check the RHS column base for the design forces shown.

Refer to the figure in the reference for additional details.

Comparison
Table 24: Comparison with SCI P358 Column Bases Example 3

Parameter RAM Reference Difference


Connection

Concrete base – concrete 2,040.00 120,000 mm2 x 17.05 N/mm2 None


bearing of the gross area: FFd = 2,046
(kN)

RAM Connection 44 Verification Manual


Eurocode Verification Examples
Bracing Connection

Parameter RAM Reference Difference


Connection

Intermediate result: Aeff 52,952.54 52,900 None


(mm2)

Intermediate result: c (mm) 42.74 43 None

Concrete base – Concrete 900.19 901.94 None


bearing of the effective area:
FFd (kN)

2.13 Bracing Connection


Reference
Steel Construction Institute. 2009. Steel Building Design: Worked examples for students - In accordance with
Eurocodes and the UK National Annexes (Publication P387). Ascot:The Steel Construction Institute. pp 71-81.

Problem
From the reference:

Design summary:
a. The wind loading at each floor is transferred to two vertically braced
end bays on grid lines ‘A’ and ‘J’ by the floors acting as diaphragms.
b. The bracing system must carry the equivalent horizontal forces (EHF)
in addition to the wind loads.
c. Locally, the bracing must carry additional loads due to imperfections
at splices (cl 5.3.3(4)) and restraint forces (cl 5.3.2(5)). These
imperfections are considered in turn in conjunction with external
lateral loads but not at the same time as the EHF.
d. The braced bays, acting as vertical pin-jointed frames, transfer the
horizontal wind load to the ground.
e. The beams and columns that make up the bracing system have
already been designed for gravity loads1). Therefore, only the diagonal
members have to be designed and only the forces in these members
have to be calculated.
f. All the diagonal members are of the same section, thus, only the most
heavily loaded member has to be designed.

Refer to the figure in the reference for additional details.

RAM Connection 45 Verification Manual


Eurocode Verification Examples
Bracing Connection

Comparison
Table 25: Comparison with SCI P387 Example No. 09 - Bracing and bracing connections

Parameter RAM Connection Reference Difference

Interface (Gusset-Bottom right 1,084.42 135 × 8 bolts = None


brace) directly bolted bolt shear: 1,080
FFd (kN)

Interface (Gusset-Bottom right 1,211.08 1,208 None


brace) brace bolt bearing: FFd (kN)

Interface (Gusset-Bottom right 1,362.71 1,487 Reference error in Anv calculations


brace) brace block tearing: FFd
(kN)

Interface (Gusset-Bottom right 876.74 876 None


brace) brace cross-sectional
resistance: NNd (kN)

RAM Connection 46 Verification Manual


Index
A column, double angle 6, 7 special concentrically braced
column, unstiffened seated frame
AISC 3
8, 9 brace-to-brace 24–26
all bolted
column, wide tee 5, 6 special moment frame
double angle 14, 15
beam column 28, 29
beam-to-column 22, 23
B M
moment connection
base plates
bearing 3, 4
bolted flange-plated 16, 17 U
unstiffened extended end unstiffened seated connection
bolted flange-plated FR 16, 17
plate 10–13 8–13
moment frame
C beam-to-column 18, 19
W
coped beam 14, 15
wide tee 5, 6
O
E ordinary moment frame
Eurocode 31 beam-to-column 19–21

H S
HSS seismic detailing 18–26

RAM Connection 47 Verification Manual