Rooftop Package Air Conditioner: Installation Manual
Rooftop Package Air Conditioner: Installation Manual
Rooftop Package Air Conditioner: Installation Manual
ROOFTOP
PACKAGE AIR CONDITIONER
IM-RTC-0611(3)-ACSON
Part No.: R08019036619C
English
Model: RT150C
855.0 142.0
Original Instruction
652.0
684.0
994.0
652.0
50.0
350.0
CONTROL
BOX
1390.0
165.0
700.0
125.0
150.0
CENTER OF GRAVITY
Model: RT180C
830.0 412.0
652.0
684.0
994.0
652.0
1710.0
CONTROL
BOX
1390.0
700.0
1988.0
125.0
1748.0
CENTER OF GRAVITY
Model: RT240C
1045.0 158.0
456.0
1076.0
994.0
456.0
1981.0
61.0
170 484.0
CONTROL
1690.0
BOX
768.0
200
150.0
CENTER OF GRAVITY
Model: RT300C
1000.0 160.0
677.0
1076.0
1215.0
677.0
2104.0
CONTROL
BOX
1650.0
768.0
245.0
150.0
CENTER OF GRAVITY
English
This manual provides the procedures of installation to ensure a safe and good standard of operation for the air
conditioner unit.
Special adjustment may be necessary to suit local requirements.
Before using your air conditioner, please read this instruction manual carefully and keep it for future reference.
This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for
commercial use by lay persons.
This appliance is not intended for use by persons, including children, with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
SAFETY PRECAUTIONS
! WARNING ! CAUTION
• Installation and maintenance should be performed by Please take note of the following important points
qualified persons who are familiar with local code when installing.
and regulation, and experienced with this type of • Do not install the unit where leakage of flammable
appliance. gas may occur.
• All field wiring must be installed in accordance with If gas leaks and accumulates around the unit, it
the national wiring regulation. may cause fire ignition.
• Ensure that the rated voltage of the unit corresponds • Ensure that drainage piping is connected
to that of the name plate before commencing wiring properly.
work according to the wiring diagram. If the drainage piping is not connected properly,
• The unit must be GROUNDED to prevent possible it may cause water leakage which will dampen
the furniture.
hazard due to insulation failure.
• Do not overcharge the unit.
• All electrical wiring must not touch the refrigerant
This unit is factory pre-charged.
piping, or any moving parts of the fan motors.
Overcharge will cause over-current or damage
• Confirm that the unit has been switched OFF before to the compressor.
installing or servicing the unit. • Ensure that the unit’s panel is closed after service
• Disconnect from the main power supply before or installation.
servicing the air conditioner unit. Unsecured panels will cause the unit to operate
• DO NOT pull out the power cord when the power is noisily.
ON. This may cause serious electrical shocks which • Sharp edges and coil surfaces are potential
may result in fire hazards. locations which may cause injury hazards.
• Keep the indoor and outdoor units, power cable and Avoid from being in contact with these places.
transmission wiring, at least 1m from TVs and radios, • Before turning off the power supply, set the remote
to prevent distorted pictures and static. {Depending controller’s ON/OFF switch to the “OFF” position
on the type and source of the electrical waves, static to prevent the nuisance tripping of the unit. If
may be heard even when more than 1m away}. this is not done, the unit’s fans will start turning
automatically when power resumes, posing a hazard
to service personnel or the user.
• Do not operate any heating apparatus too close to
the air conditioner unit.
• Don’t use joined and twisted wires for incoming
power supply.
• The equipment is not intended for use in a
potentially explosive atmosphere.
NOTICE
Disposal Requirement
Dismantling of the unit, treatment of the refrigerant, oil and other parts must be done in accordance with the
applicable legislation.
Model: RT150/180/240/300C
No Item Description
1 Compressor
2 High Pressure Switch
3 Access Valve
4 Outdoor Heat Exchanger
5 Indoor Heat Exchanger
6 Filter Dryer
7 Thermal Expansion Valve (TXV)
8 Low Pressure Switch
Subcool Circuit
9
(Applicable to RT150 (only)
HEADER
IN HEADER
3
3
5
4
8
2
HEADER
OUT DISTRIBUTOR
1
Thermal Expansion
Valve Sensor Bulb
6 7
English
(A) Location For Installation
– Install the unit in such way that air distributed by the unit cannot be drawn in again (as in the case of short
circuit of discharge air). Allow sufficient space for maintenance around the unit.
– When two or more units are installed in a location, they must be positioned such that one unit will not be
taking the discharge air from another unit.
– Ensure that there is no obstruction of air flow into or out of the unit. Remove obstacles which block air intake
or air discharge.
– The location must be well ventilated, so that the unit can draw and distribute plenty of air.
– The unit is recommended to install in:-
• A place capable of bearing the weight of the unit and isolating noise and vibration.
• A place where has adequate drainage.
• A place where the unit will not be buried in snow.
• A place where air outlet port is not exposed to strong wind.
• A place where the air discharge and operating sound level will not annoy the neighbours.
• The location where it is not accessible by general public.
Note:
Unit shown in diagram is RT300C. Other models will follow the same method in lifting.
! CAUTION
Do not install the unit at altitude over 2000m
B
A 70mm
C
B 2C
Drain piping
A
C 2 X ESP
Electrical
control circuit
service &
compressor
service
Condenser
air inlet
1200
English
Model
Description
RT150C RT180C RT240C RT300C
Refrigerant R22
Refrigerant charge kg 4.6/4.6 6.0/6.0 8.0/8.0 10.6/10.6
CFM 4600 6500 7900 8700
Evaporator air flow
L/S 2171 3068 3728 4106
mmAq 12.5 15 20 25
External static pressure
Pa 123 147 196 245
CFM 9900 13800 12230 21500
Condenser air flow
L/S 4672 6513 5772 10149
Control Mechanical Controller/Sequential Controller
Compressor (Type/Quantity) Scroll/2
Air filter (Type/Quantity) Washable Saranet/2
Air filter dimension (L x W x T) mm 895 x 685 x 4 834 x 760 x 4 1040 x 750 x 4
ELECTRICAL DATA
Model
Description
RT150C RT180C RT240C RT300C
Power supply V/Ph/Hz 380-415/3N~/50
Max continuous current (Comp) A 20.0/20.0 24.2/24.2 31.0/31.0 42.0/35.0
Full load current (FLA, Comp) A 13.7/13.7 16.8/16.8 22.3/22.3 31.0/25.0
Locked rotor current (LRA, Comp) A 100.0/100.0 111.0/111.0 118.0/118.0 174.0/140.0
*Min. circuit amps, MCA A 48.0 57.0 72.5 85.0
*Max. fuse amps, MFA A 63.0 63.0 80.0 100.0
WIRE CONNECTION
• All electrical work must be carried out by qualified electrician and accordance with local supply requirement and associate
regulation.
• Before connecting the wire, consult the electric power company of jurisdiction.
a
b PE
a. Power supply d. Unit
c g b. Main switch/fuse e. Remote control/Thermostat
(field supply)
f f. Connection wiring for
d c. Power supply unit & remote controller
wiring for unit
e g. Earth
Model: RT150/180/240/300C
CONTROL
BOX
Terminal block
Terminal block
Power cable
Control wire
Note:
• While installing the circuit breaker onto the unit, make sure that the screws do not damage the components
(e.g. coil) inside the unit.
Note:
• A main switch or other means for disconnection, having a contact separation in all poles, must be incorporated
in fixed wiring in accordance with local and national legislation.
• The unit is to be wired directly from an electrical distribution board either by a circuit breaker (preferred) or
HRC fuse.
• Fix the power supply wiring to control module. Connect control wiring to control terminal block through the
control box’s hole.
• Earth wiring must be connected.
• The power supply cord must be equivalent to H07RN-F which is the minimum requirement, and to be used in
protective tube.
English
• Before working in this unit, isolate it from the power supply.
• Electrical wiring to this unit and the remote controller shall be installed in accordance with the appropriate
requirement of the local wiring code.
Observe the notes mentioned below when wiring to the terminal block.
Precautions to be taken for power supply wiring. Round crimp-style
(Use a round crimp-style terminal for connection to the terminal block. terminal
In case it cannot be used due to unavoidable reasons, be sure to observe Stranded wire
the following instruction.)
! CAUTION
• When connecting the connection wires to the terminal block using a single core wire, be sure to perform curling.
Problems with the work may cause heat and fires.
Good Wrong
• Pull the wire and make sure that it does not disconnect. Then fix the wire in place with a wire stop.
! WARNING
• Transmission wire must be routed at least 50mm away from the power cable.
• Transmission wire should be a shielded wire.
(4) Arrangement of terminal blocks and components for controller are shown as below:
(a) Mechanical Control
Model : RT150C
3 Phase Protector
F1316A
F1315A
S
T
4 Terminal Block
5 Relay
L1 L2 L3 N
R S T
N N F2H
R S T
N N F2H 1 2 3 4 5 6
6 Fuse
C1 C2
U V W U V W
7 Transformer
8 Timer
9 Control Module
4 1 4 2 1 4 2 1 4
3
7
7
4 3
2
4
5
1 1
4
4
1
1 1 1
Model : RT150C
3 6 5 9
HEATER2
COMP 4
COMP 3
COMP 2
COMP 1
HEATER1
IN FAN
4WV 4
4WV 3
4WV 2
4WV 1
LIVE
NR
OUT FAN 4
F13.15A
S
TRANSFORMER
T
N N F2H N N F3H
R S T R S T
L1 L2 L3 N
C1 C2
U V W U V W
4 1 4 2 1 4 2 1
6 9 3 6 5 4 9
HEATER2
COMP 3
COMP 2
COMP 1
HEATER1
IN FAN
4WV 4
4WV 3
4WV 2
4WV 1
TB2
HEATER2
COMP 2
COMP 4
COMP 1
HEATER1
4WV 4
4WV 3
IN FAN
4WV 2
4WV 1
LIVE
NR
N N N
LIVE
3
F13.15A
S
OUT FAN 4
TRANSFORMER
OUT FAN 4
T
F13.15A
TRANSFORMER
NEUTRAL
2
N N F3H N N F2H
4
R S T
R S T A1 R S T A1
U V W A2 U V W A2
U V W
1
L1 L2 L3 N
RESET
2 6
95
98
96
R S T
4 L1 L2 L3 N
U V W
1
RESET
2 6
95
98
96
4 1 1 1 1
10
English
Ensure the operating temperature is within the allowable range, as stated in diagram below:
54
! CAUTION
Outdoor DB temperature (°C)
52
The use of the air conditioner outside the
range of working temperature and humidity
can result in serious failure.
19
14 19.4 23
PHASE PROTECTOR
The unit with Scroll Compressor can only rotate in one direction. For this reason, a protective device (phase protector) is fitted
to prevent incorrect wiring of the electrical phases. When the three phases are not connected correctly, the phase protector
operates, and the unit will not start. This device is located in the control box of the outdoor unit.
The following table shows the LED indicator light for phase protector under normal operation and fault conditions.
Normal operation -
Reverse phase Switch off the unit. Check the 3 phase wiring.
T phase missing Switch off the unit. Check the 3 phase wiring.
S phase missing Switch off the unit. Check the 3 phase wiring.
R phase missing Switch off the unit. Check the 3 phase wiring.
S &T phase missing+ Switch off the unit. Check the 3 phase wiring.
+
Overload High discharge temperature. Check the refrigerant system.
! WARNING
• Trouble shooting must be performed by qualified personnel.
11
Remove filter cover for filter service Air Filter Air Filter
TROUBLESHOOTING
For any enquiries on spare parts, please contact your authorized dealer. If any malfunction of the air conditioner unit
is noted, check the following fault conditions and causes for some simple troubleshooting tips.
Problem Causes Action
Unit does not run. Power failure. Press the [ON/OFF] after power restore.
Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker.
Power supply wiring phase incorrect. Modify the wiring phase.
Compressor does not operate in 3 Protection against frequent starting. Wait for 3 minutes for the compressor to
min after unit has started. start.
Air flow is low . Filter is filled with dust and dirt. Clean the filter.
There are some obstacles at the air inlet or Remove obstacles.
outlet of the units.
Compressor operate continuously . Dirty air filter. Clean the air filter.
Temperature setting too low. Reset the temperature.
No cool air delivered. Temperature setting too high. Set the temperature lower .
12
LOT 60334, PERSIARAN BUKIT RAHMAN PUTRA 3, TAMAN PERINDUSTRIAN BUKIT RAHMAN PUTRA,
47000 SUNGAI BULOH, SELANGOR DARUL EHSAN, MALAYSIA.
LOT 60334, PERSIARAN BUKIT RAHMAN PUTRA 3, TAMAN PERINDUSTRIAN BUKIT RAHMAN PUTRA,
47000 SUNGAI BULOH, SELANGOR DARUL EHSAN, MALAYSIA.
ﺍﻧﺘﻈﺮ ﻟﻤﺪﺓ 3ﺩﻗﺎﺋﻖ ﻟﺒﺪﺀ ﺗﺸﺘﻐﻞ ﺍﻟﻀﺎﻏﻄﺔ. ﺍﻟﺤﻤﺎﻳﺔ ﺿﺪ ﺍﻟﺘﺸﻐﻴﻞ ﺍﻟﻤﺘﻜﺮﺭ. ﺍﻟﻀﺎﻏﻄﺔ ﻻ ﺗﺸﺘﻐﻞ ﺧﻼﻝ 3
ﺩﻗﺎﺋﻖ ﺑﻌﺪ ﺑﺪﺀ ﺗﺸﻐﻴﻞ ﺍﻟﻮﺣﺪﺓ.
ﻧﻈﻒ ﺍﻟﻤﺮﺷﺢ.
ﹼ ﺍﻟﻤﺮﺷﺢ ﻣﻤﺘﻠﺊ ﺑﺎﻟﻐﺒﺎﺭ ﻭﺍﻷﻭﺳﺎﺥ. ﺗﺪﻓﻖ ﺍﻟﻬﻮﺍﺀ ﻣﻨﺨﻔﺾ.
ﺍﺯﻝ ﺍﻟﻌﻮﺍﺋﻖ. ﻳﻮﺟﺪ ﻫﻨﺎﻙ ﺑﻌﺾ ﺍﻟﻌﻮﺍﺋﻖ ﻋﻠﻰ ﻓﺘﺤﺔ ﺩﺧﻮﻝ ﺍﻭ
ﺧﺮﻭﺝ ﺍﻟﻬﻮﺍﺀ ﻟﻠﻮﺣﺪﺍﺕ.
ﹼ
ﻧﻈﻒ ﻣﺮﺷﺢ ﺍﻟﻬﻮﺍﺀ. ﻣﺮﺷﺢ ﺍﻟﻬﻮﺍﺀ ﻏﻴﺮ ﻧﻈﻴﻒ. ﺍﻟﻀﺎﻏﻄﺔ ﺗﺸﺘﻐﻞ ﺑﺸﻜﻞ
ﻣﺴﺘﻤﺮ.
ﺍﻋﺪ ﺿﺒﻂ ﺩﺭﺟﺔ ﺍﻟﺤﺮﺍﺭﺓ. ﺿﺒﻂ ﺩﺭﺟﺔ ﺍﻟﺤﺮﺍﺭﺓ ﻣﻨﺨﻔﺾ ﺟﺪﺍ ﹰ.
ﺍﺿﺒﻂ ﺩﺭﺟﺔ ﺍﻟﺤﺮﺍﺭﺓ ﻋﻠﻰ ﺩﺭﺟﺔ ﺍﻗﻞ. ﺿﺒﻂ ﺩﺭﺟﺔ ﺍﻟﺤﺮﺍﺭﺓ ﻣﺮﺗﻔﻊ ﺟﺪﺍ ﹰ. ﻻ ﻳﺨﺮﺝ ﺍﻟﻬﻮﺍﺀ ﺍﻟﺒﺎﺭﺩ.
ﺍﺫﺍ ﺍﺳﺘﻤﺮﺕ ﺑﻘﺎﺀ ﺍﻟﻌﻄﻞ ،ﻳﺮﺟﻲ ﺍﻻﺗﺼﺎﻝ ﺑﻮﻛﻴﻠﻚ ﺍﻟﻤﺤﻠﻲ ﺍﻟﻤﺮﺧﺺ /ﻓﻨﻲ ﺍﻟﺼﻴﺎﻧﺔ.
١٢
ﺗﺄﻛﺪ ﻣﻦ ﺍﻥ ﺩﺭﺟﺔ ﺣﺮﺍﺭﺓ ﺍﻟﺘﺸﻐﻴﻞ ﻫﻲ ﺿﻤﻦ ﺍﻟﻨﻄﺎﻕ ﺍﻟﻤﺴﻤﻮﺡ ﺑﻪ ،ﻛﻤﺎ ﻫﻮ ﻣﺸﺮﻭﺡ ﻓﻲ ﺍﻟﻤﺨﻄﻂ ﻓﻲ ﺍﻻﺳﻔﻞ:
52
! ﺗﻨﺒﻴﻪ
ﻳﻤﻜﻦ ﺍﻥ ﻳﻨﺘﺞ ﻋﻦ ﺍﺳﺘﻌﻤﺎﻝ ﻣﻜﻴﻒ ﺍﻟﻬﻮﺍﺀ
ﺧﺎﺭﺝ ﻧﻄﺎﻕ ﺩﺭﺟﺔ ﺣﺮﺍﺭﺓ ﺍﻟﺘﺸﻐﻴﻞ ﻭﺍﻟﺮﻃﻮﺑﺔ
ﺇﺧﻔﺎﻕ ﺧﻄﻴﺮ ﺑﺎﻟﺘﺸﻐﻴﻞ.
19
ﻭﺍﻗﻲ ﺍﻟﻄﻮﺭ
ﻳﻤﻜﻦ ﻓﻘﻂ ﺗﺪﻭﻳﺮ ﺍﻟﻮﺣﺪﺓ ﻣﻊ ﺍﻟﻀﺎﻏﻄﺔ ﺍﻟﺤﻠﺰﻭﻧﻴﺔ ﺑﺎﺗﺠﺎﻩ ﻭﺍﺣﺪﺓ .ﻟﻬﺬﺍ ﺍﻟﺴﺒﺐ ،ﺗﻢ ﺗﺜﺒﻴﺖ ﺍﺩﺍﺓ ﺍﻟﺤﻤﺎﻳﺔ )ﻭﺍﻗﻲ ﺍﻟﻄﻮﺭ( ﻟﺘﻔﺎﺩﻱ ﻣﺪ ﺗﻮﺻﻴﻼﺕ ﻏﻴﺮ
ﺻﺤﻴﺤﺔ ﻟﻼﻃﻮﺍﺭ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ .ﻋﻨﺪ ﻋﺪﻡ ﺗﻮﺻﻴﻞ ﺍﻻﻃﻮﺍﺭﺍﻟﺜﻼﺛﺔ ﺑﺸﻜﻞ ﺻﺤﻴﺢ ،ﺗﺸﺘﻐﻞ ﺣﻤﺎﻳﺔ ﺍﻟﻄﻮﺭ ،ﻭﻻﺗﺸﺘﻐﻞ ﺍﻟﻮﺣﺪﺓ .ﺗﻘﻊ ﻫﺬﻩ ﺍﻻﺩﺍﺓ ﻓﻲ ﺻﻨﺪﻭﻕ
ﺍﻟﺘﺤﻜﻢ ﻟﻠﻮﺣﺪﺓ ﺍﻟﺨﺎﺭﺟﻴﺔ.
ﻳﺒﲔ ﺍﻟﺠﺪﻭﻝ ﺍﻟﺘﺎﻟﻲ ﻛﻴﻔﻴﺔ ﺇﺿﺎﺀﺓ ﻣﺆﺷﺮ LEDﻟﻀﺎﺑﻂ ﺗﻌﺎﻗﺐ ﺍﻟﻄﻮﺭ ﺃﺛﻨﺎﺀ ﺍﻟﺘﺸﻐﻴﻞ ﺍﻟﻌﺎﺩﻱ ﻭﻓﻲ ﻇﺮﻭﻑ ﺍﻟﺨﻠﻞ.
TـP SـP RـP PW LED
ﺍﻻﺟﺮﺍﺀﺍﺕ )ﺃﺻﻔﺮ( )ﺃﺻﻔﺮ( )ﺃﺻﻔﺮ( )ﺃﺣﻤﺮ( ﺍﻟﻮﺻﻒ
- ﺗﺸﻐﻴﻞ ﻋﺎﺩﻱ
ﺍﻭﻗﻒ ﺗﺸﻐﻴﻞ ﺍﻟﻮﺣﺪﺓ .ﺍﻓﺤﺺ ﺗﻮﺻﻴﻼﺕ ﺍﺳﻼﻙ ﺍﻟﻄﻮﺭ .3 ﺍﻟﻄﻮﺭ ﺍﻟﻌﻜﺴﻲ
ﺍﻭﻗﻒ ﺗﺸﻐﻴﻞ ﺍﻟﻮﺣﺪﺓ .ﺍﻓﺤﺺ ﺗﻮﺻﻴﻼﺕ ﺍﺳﻼﻙ ﺍﻟﻄﻮﺭ .3 Tﻓﻘﺪﺍﻥ ﺍﻟﻄﻮﺭ
ﺍﻭﻗﻒ ﺗﺸﻐﻴﻞ ﺍﻟﻮﺣﺪﺓ .ﺍﻓﺤﺺ ﺗﻮﺻﻴﻼﺕ ﺍﺳﻼﻙ ﺍﻟﻄﻮﺭ .3 Sﻓﻘﺪﺍﻥ ﺍﻟﻄﻮﺭ
ﺍﻭﻗﻒ ﺗﺸﻐﻴﻞ ﺍﻟﻮﺣﺪﺓ .ﺍﻓﺤﺺ ﺗﻮﺻﻴﻼﺕ ﺍﺳﻼﻙ ﺍﻟﻄﻮﺭ .3 Rﻓﻘﺪﺍﻥ ﺍﻟﻄﻮﺭ
ﺍﻭﻗﻒ ﺗﺸﻐﻴﻞ ﺍﻟﻮﺣﺪﺓ .ﺍﻓﺤﺺ ﺗﻮﺻﻴﻼﺕ ﺍﺳﻼﻙ ﺍﻟﻄﻮﺭ .3 +
T & Sﻓﻘﺪﺍﻥ ﺍﻟﻄﻮﺭ
ﺭﺟﺔ ﺣﺮﺍﺭﺓ ﺍﻟﺘﻔﺮﻳﻎ ﻋﺎﻟﻴﺔ .ﺍﻓﺤﺺ ﺟﻬﺎﺯ ﻣﺎﺩﺓ ﺍﻟﺘﺒﺮﻳﺪ. +
ﺣﻤﻞ ﺯﺍﺋﺪ
ﺍﻭﻗﻒ ﺗﺸﻐﻴﻞ ﺍﻟﻮﺣﺪﺓ .ﺍﻭﺻﻞ ﺍﻟﻤﺘﺤﺴﺲ. ﻓﻘﺪﺍﻥ ﺍﻟﻤﺘﺤﺴﺲ
+
! ﺗﺤﺬﻳﺮ
• ﻭﻳﺠﺐ ﺃﻥ ﻳﺆﺩﻱ ﺍﻟﺨﻠﻞ ﻣﻦ ﻗﺒﻞ ﻣﻮﻇﻔﻴﻦ ﻣﺆﻫﻠﻴﻦ.
١١
3
7
7
3 4
2
4
5
1 1
4
4
1
1 1 1
( ﺍﻟﺘﺤﻜﻢ ﺍﻟﻤﺘﺴﻠﺴﻞb)
RT150C : ﻃﺮﺍﺯ
3 6 5 9
HEATER2
COMP 4
COMP 3
COMP 2
COMP 1
HEATER1
IN FAN
4WV 4
4WV 3
4WV 2
4WV 1
LIVE
NR
OUT FAN 4
F13.15A
S
TRANSFORMER
T
N N F2H N N F3H
R S T R S T
L1 L2 L3 N
C1 C2
U V W U V W
4 1 4 2 1 4 2 1
COMP 3
COMP 2
COMP 1
HEATER1
IN FAN
4WV 4
4WV 3
4WV 2
4WV 1
TB2
HEATER2
COMP 2
COMP 4
COMP 1
HEATER1
4WV 4
4WV 3
IN FAN
LIVE
4WV 2
4WV 1
N N N
NR
LIVE
3
F13.15A
S
OUT FAN 4
TRANSFORMER
OUT FAN 4
T
F13.15A
TRANSFORMER
T S NR
NEUTRAL
DS4 DS3 DS2 DS1 ROOM
ID4 ID3 ID2 ID1
2
N N F3H N N F2H
4
R S T
R S T A1 R S T A1
U V W A2 U V W A2
U V W
1
L1 L2 L3 N
RESET
2 6
95
98
96
R S T
4 L1 L2 L3 N
U V W
1
RESET
2 6
95
98
96
4 1 1 1 1
١٠
! ﺗﻨﺒﻴﻪ
• ﻋﻨﺪ ﺗﻮﺻﻴﻞ ﺍﺳﻼﻙ ﺍﻟﺘﻮﺻﻴﻞ ﻣﻊ ﻣﺠﻤﻮﻋﺔ ﺍﻻﻃﺮﺍﻑ ﺍﺳﺘﻌﻤﻞ ﺳﻠﻚ ﻗﻠﺐ ﻣﻔﺮﺩ ،ﻭﺗﺄﻛﺪ ﻣﻦ ﻋﻤﻞ ﺍﻟﺴﻠﻚ ﻋﻠﻰ ﺷﻜﻞ ﺿﻔﻴﺮﺓ.
ﺍﻟﻤﺸﺎﻛﻞ ﻓﻲ ﺍﻟﻌﻤﻞ ﻳﻤﻜﻦ ﺍﻥ ﺗﺴﺒﺐ ﺣﺮﺍﺭﺓ ﻭﺣﺮﻳﻖ.
ﺟﻴﺪ ﺧﻄﺄ
• ﺍﺳﺤﺐ ﺍﻟﺴﻠﻚ ﻭﺗﺄﻛﺪ ﻣﻦ ﺍﻧﻪ ﻻ ﻳﻨﻔﺼﻞ .ﺑﻌﺪ ﺫﻟﻚ ﺛ ﹼﺒﺖ ﺍﻟﺴﻠﻚ ﻓﻲ ﺍﻟﻤﻜﺎﻥ ﺑﻤﺜﺒﺖ ﺳﻠﻚ.
! ﺗﺤﺬﻳﺮ
• ﻳﺠﺐ ﺗﻤﺪﻳﺪ ﺳﻠﻚ ﺍﻟﺈﺭﺳﺎﻝ ﻋﻠﻰ ﻣﺴﺎﻓﺔ 50ﻣﻢ ﻋﻠﻰ ﺍﻟﺄﻗﻞ ﺑﻌﻴﺪﺍ ﻣﻦ ﺳﻠﻚ ﺍﻟﻄﺎﻗﺔ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ.
• ﻳﺠﺐ ﺃﻥ ﻳﻜﻮﻥ ﺳﻠﻚ ﺍﻟﺎﺭﺳﺎﻝ ﻣﺤﺠﻮﺑﺎ.
ﻭﺍﻗﻲ ﺍﻟﻄﻮﺭ
F1316A
F1315A
3
S
T
٩
ﻃﺮﺍﺯRT150/180/240/300C :
ﺻﻨﺪﻭﻕ
ﺍﻟﺘﺤﻜﻢ
ﻣﺠﻤﻮﻋﺔ ﺍﻻﻃﺮﺍﻑ
ﻣﺠﻤﻮﻋﺔ ﺍﻻﻃﺮﺍﻑ
ﻣﻼﺣﻈﺔ:
• ﺍﻟﻤﻔﺘﺎﺡ ﺍﻟﺮﺋﻴﺴﻲ ﺍﻭ ﻭﺳﺎﺋﻞ ﺍﻟﻔﺼﻞ ﺍﻻﺧﺮﻯ ﻳﺠﺐ ﺍﻥ ﺗﻤﺘﻠﻚ ﻓﺎﺻﻞ ﺑﻴﻦ ﻧﻘﺎﻁ ﺍﻟﺘﻮﺻﻴﻞ ﻋﻠﻰ ﺟﻤﻴﻊ ﺍﻻﻗﻄﺎﺏ ،ﻭﻳﺠﺐ ﺍﻥ ﺗﺮﻛﺐ ﺍﻻﺳﻼﻙ ﺑﺸﻜﻞ
ﺛﺎﺑﺖ ﺣﺴﺐ ﺍﻟﻘﻮﺍﻧﻴﻦ ﺍﻟﻤﺤﻠﻴﺔ ﻭﺍﻟﻮﻃﻨﻴﺔ.
• ﻳﺠﺐ ﺍﻥ ﻳﺘﻢ ﺗﻮﺻﻴﻞ ﺍﺳﻼﻙ ﺍﻟﻮﺣﺪﺓ ﻣﺒﺎﺷﺮﺓ ﻣﻦ ﻟﻮﺣﺔ ﺗﻮﺯﻳﻊ ﻛﻬﺮﺑﺎﺋﻴﺔ ﺍﻣﺎ ﺑﻮﺍﺳﻄﺔ ﻗﺎﻃﻊ ﺩﺍﺋﺮﺓ ﻛﻬﺮﺑﺎﺋﻴﺔ )ﻳﻔﻀﻞ( ﺍﻭ ﻓﺎﺻﻤﺔ .HRC
• ﺛﺒﹼﺖ ﺍﺳﻼﻙ ﺗﺰﻭﻳﺪ ﺍﻟﻄﺎﻗﺔ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ ﻣﻊ ﻗﺴﻢ ﺍﻟﺘﺤﻜﻢ .ﺍﻭﺻﻞ ﺍﺳﻼﻙ ﺍﻟﺘﺤﻜﻢ ﻣﻊ ﻣﺠﻤﻮﻋﺔ ﺍﻃﺮﺍﻑ ﺍﻟﺘﺤﻜﻢ ﻣﻦ ﺧﻼﻝ ﺛﻘﺐ ﺻﻨﺪﻭﻕ
ﺍﻟﺘﺤﻜﻢ.
• ﻳﺠﺐ ﺗﻮﺻﻴﻞ ﺳﻠﻚ ﺍﻟﺘﺄﺭﻳﺾ.
• ﻳﺠﺐ ﺍﻥ ﻳﺘﻄﺎﺑﻖ ﺳﻠﻚ ﺗﺰﻭﻳﺪ ﺍﻟﻄﺎﻗﺔ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ ﻣﻊ ﺷﺮﻭﻁ H07RN-Fﻭﺍﻟﺘﻲ ﻫﻲ ﺍﻟﺤﺪ ﺍﻻﺩﻧﻰ ﻟﻠﻤﺘﻄﻠﺒﺎﺕ ،ﻭﻳﺠﺐ ﺍﻥ ﺗﺴﺘﻌﻤﻞ ﺩﺍﺧﻞ ﺍﻧﺒﻮﺏ
ﻭﺍﻗﻲ.
٨
ﻃﺮﺍﺯ
ﻋﺮﺑﻲ
ﻭﺻﻒ
RT300C RT240C RT180C RT150C
R22 ﻣﺎﺩﺓ ﺍﻟﺘﺒﺮﻳﺪ
10.6/10.6 8.0/8.0 6.0/6.0 4.6/4.6 ﻛﺠﻢ ﺷﺤﻦ ﻣﺎﺩﺓ ﺍﻟﺘﺒﺪﻳﺪ
8700 7900 6500 4600 CFM
ﺗﺪﻓﻖ ﻫﻮﺍﺀ ﺍﻟﻤﺒﺨﺮ
4106 3728 3068 2171 L/S
25 20 15 12.5 mmAq
ﺍﻟﻀﻐﻂ ﺍﻟﺴﺎﻛﻦ ﺍﻟﺨﺎﺭﺟﻲ
245 196 147 123 Pa
21500 12230 13800 9900 CFM
ﺗﺪﻓﻖ ﻫﻮﺍﺀ ﺍﻟﻤﻜﺜﻒ
10149 5772 6513 4672 L/S
ﺗﺤﻜﻢ ﻣﻴﻜﺎﻧﻴﻜﻲ /ﺟﻬﺎﺯ ﺍﻟﺴﻴﻄﺮﺓ ﺍﻟﻤﺘﺴﻠﺴﻞ ﺍﻟﺘﺤﻜﻢ
ﻟﻮﻟﺒﻲ2/ ﺍﻟﻀﺎﻏﻄﺔ )ﺍﻟﻨﻮﻉ/ﺍﻟﻜﻤﻴﺔ(
ﺍﻟﺒﻴﺎﻧﺎﺕ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ
ﻃﺮﺍﺯ
ﻭﺻﻒ
RT300C RT240C RT180C RT150C
380-415/3N~/50 V/Ph/Hz ﺗﺰﻭﻳﺪ ﺍﻟﻄﺎﻗﺔ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ
42.0/35.0 31.0/31.0 24.2/24.2 20.0/20.0 A ﺍﻟﺤﺪ ﺍﻻﻗﺼﻰ ﻟﻠﺘﻴﺎﺭ ﺍﻟﻤﺴﺘﻤﺮ )(Comp
31.0/25.0 22.3/22.3 16.8/16.8 13.7/13.7 A ﺗﻴﺎﺭ ﺣﻤﻞ ﻛﺎﻣﻞ )(FLA, Comp
174.0/140.0 118.0/118.0 111.0/111.0 100.0/100.0 A ﺍﻟﺘﻴﺎﺭ ﺍﻟﺪﻭﺍﺭ ﺍﻟﻤﻘﻔﻞ )(LRA, Comp
85.0 72.5 57.0 48.0 A *ﺍﻟﺤﺪ ﺍﻷﺩﻧﻰ ﻟﺘﻴﺎﺭ ﺍﻟﺪﺍﺋﺮﺓMCA ،
100.0 80.0 63.0 63.0 A *ﺍﻟﺤﺪ ﺍﻷﻗﺼﻰ ﻟﺘﻴﺎﺭ ﺍﻟﻨﻤﺼﻬﺮMFA ،
ﺗﻮﺻﻴﻞ ﺍﻻﺳﻼﻙ
• ﺟﺐ ﺍﻟﻘﻴﺎﻡ ﺑﺠﻤﻴﻊ ﺍﻋﻤﺎﻝ ﺍﻻﺳﻼﻙ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ ﻣﻦ ﻗﺒﻞ ﻓﻨﻲ ﻛﻬﺮﺑﺎﺋﻲ ﻣﺨﺘﺺ ﻭﻣﺆﻫﻞ ﻭﺣﺴﺐ ﻣﺘﻄﻠﺒﺎﺕ ﺍﻟﺘﺰﻭﻳﺪ ﺍﻟﻤﺤﻠﻴﺔ ﻭﺍﻟﻘﻮﺍﻧﲔ
ﺍﻟﻤﺘﻌﻠﻘﺔ ﺑﺬﻟﻚ.
• ﻗﺒﻞ ﺗﻮﺻﻴﻞ ﺍﻻﺳﻼﻙ ،ﺍﺳﺘﺸﺮ ﺷﺮﻛﺔ ﺍﻟﻄﺎﻗﺔ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ ﻭﺍﺣﺼﻞ ﻋﻠﻰ ﺍﻟﺘﺼﺎﺭﻳﺢ ﺍﻟﻘﺎﻧﻮﻧﻴﺔ ﺍﻟﻤﺘﻌﻠﻘﺔ ﺑﺎﻟﺘﺮﻛﻴﺐ.
٧
B
≤ 70ﻣﻢ A
C
2C ≤ B
ﺍﻧﺒﻮﺏ ﺍﻟﺘﺼﺮﻳﻒ
A
ESP X 2 ≤ C
ﺍﻟﻤﻜﺜﻒ 1200
ﻭﺍﻟﻤﺤﺮﻛﺎﺕ ،ﻭﻣﺮﺷﺢ ﺍﻟﻬﻮﺍﺀ
3000
ﺍﻟﻤﻜﺜﻒ
ﻣﺪﺧﻞ ﺍﻟﻬﻮﺍﺀ
ﺍﻟﻤﻜﺜﻒ
ﺧﺪﻣﺔ ﺩﺍﺋﺮﺓ
ﺍﻟﺘﺤﻜﻢ
ﺍﻟﻜﻬﺮﺑﺎﺋﻲ ﻭ
ﺧﺪﻣﺔ ﺍﻟﻀﺎﻏﻄﺔ
ﻣﺪﺧﻞ ﺍﻟﻬﻮﺍﺀ
ﺍﻟﻤﻜﺜﻒ
ﺧﺪﻣﺔ ﻣﻠﻒ ﺍﻟﻤﺒﺨﺮ،
1200
٦
ﻣﻼﺣﻈﺔ:
ﺍﻟﻮﺣﺪﺓ ﺍﻟﻤﻌﺮﻭﺿﺔ ﻓﻲ ﺍﻟﻤﺨﻄﻂ ﻫﻲ ﻟﻠﻤﻮﺩﻳﻞ . RT300Cﺍﻟﻤﻮﺩﻳﻼﺕ ﺍﻻﺧﺮﻯ ﺗﺘﺒﻊ ﻧﻔﺲ ﺍﻟﻄﺮﻳﻘﺔ ﺑﺎﻟﺮﻓﻊ.
! ﺗﻨﺒﻴﻪ
ﻻ ﹼ
ﺗﺮﻛﺐ ﺍﻟﻮﺣﺪﺓ ﻋﻠﻰ ﺍﺭﺗﻔﺎﻉ ﺃﻛﺜﺮ ﻣﻦ 2000ﻡ
٥
ﻃﺮﺍﺯRT150/180/240/300C :
ﺍﻟﺮﻗﻢ ﺷﺮﺡ ﺍﻟﺒﻨﺪ
1ﺍﻟﻀﺎﻏﻄﺔ
2ﻣﻔﺘﺎﺡ ﺍﻟﻀﻐﻂ ﺍﻟﻌﺎﻟﻲ
3ﺻﻤﺎﻡ ﺍﻟﻮﺻﻮﻝ
4ﺍﻟﻤﺒﺎﺩﻝ ﺍﻟﺤﺮﺍﺭﻱ ﺍﻟﺨﺎﺭﺟﻲ
5ﺍﻟﻤﺒﺎﺩﻝ ﺍﻟﺤﺮﺍﺭﻱ ﺍﻟﺪﺍﺧﻠﻲ
6ﻣﺠﻔﻒ ﺍﻟﻤﺮﺷﺢ
7ﺻﻤﺎﻡ ﺗﻮﺳﻴﻊ ﺍﻟﺤﺮﺍﺭﻱ )(TXV
8ﻣﻔﺘﺎﺡ ﺍﻟﻀﻐﻂ ﺍﻟﻤﻨﺨﻔﺾ
Subcoolﺍﻟﺪﺍﺋﺮﺓ
) 9ﻻ ﺗﻨﻄﺒﻖ ﺇﻻ ﻋﻠﻰ ﻃﺮﺍﺯﺍﺕ ) RT150ﻓﻘﻂ((
3
5
4
8
2
3
6 7
٤
ﻳﺰﻭﺩﻙ ﻫﺬﺍ ﺍﻟﻜﺘﻴﺐ ﺑﻄﺮﻕ ﺍﻟﺘﺮﻛﻴﺐ ﻟﻀﻤﺎﻥ ﺍﻟﺘﺸﻐﻴﻞ ﺍﻟﻌﺎﺩﻱ ﺍﻟﺠﻴﺪ ﻭﺍﻟﻤﺄﻣﻮﻥ ﻟﻮﺣﺪﺓ ﻣﻜﻴﻔﺔ ﺍﻟﻬﻮﺍﺀ.
ﻗﺪ ﻳﻜﻮﻥ ﻣﻦ ﺍﻟﻀﺮﻭﺭﻱ ﺍﺟﺮﺍﺀ ﺿﺒﻂ ﺧﺎﺹ ﻟﻜﻲ ﻳﻼﺋﻢ ﻣﺘﻄﻠﺒﺎﺗﻚ.
ﻗﺒﻞ ﺍﺳﺘﻌﻤﺎﻝ ﻣﻜﻴﻔﺔ ﺍﻟﻬﻮﺍﺀ ،ﻳﺮﺟﻰ ﻗﺮﺍﺀﺓ ﻛﺘﻴﺐ ﺍﻟﺘﻌﻠﻴﻤﺎﺕ ﻫﺬﺍ ﺑﻌﻨﺎﻳﺔ ﻭﺍﻻﺣﺘﻔﺎﻅ ﺑﻪ ﻟﻠﻤﺮﺍﺟﻌﺔ ﻓﻲ ﺍﻟﻤﺴﺘﻘﺒﻞ.
ﻫﺬﺍ ﺍﻟﺠﻬﺎﺯ ﻣﻌﺪ ﻟﻼﺳﺘﻌﻤﺎﻝ ﻣﻦ ﻗﺒﻞ ﻣﺴﺘﻌﻤﻠﻴﻦ ﺫﻭﻱ ﺧﺒﺮﺓ ﻭﻣﺪﺭﺑﻴﻦ ﻓﻲ ﺍﻟﻤﺘﺎﺟﺮ ،ﻓﻲ ﺍﻟﻤﺼﺎﻧﻊ ﻭﺍﻟﻤﺰﺍﺭﻉ ﺍﻟﺼﻐﻴﺮﺓ ،ﺍﻭ ﻟﻼﺳﺘﻌﻤﺎﻝ ﺍﻟﺘﺠﺎﺭﻱ
ﻣﻦ ﻗﺒﻞ ﺃﺷﺨﺎﺹ ﻣﻌﻨﻴﻴﻦ.
ﻫﺬﺍ ﺍﻟﺠﻬﺎﺯ ﻏﻴﺮ ﻣﺼﻤﻢ ﻟﻼﺳﺘﻌﻤﺎﻝ ﻣﻦ ﻗﺒﻞ ﺍﻻﺷﺨﺎﺹ ،ﺑﻤﺎ ﻓﻲ ﺫﻟﻚ ﺍﻻﻃﻔﺎﻝ ،ﺍﻟﺬﻳﻦ ﻟﺪﻳﻬﻢ ﻧﻘﺺ ﺍﻭ ﺍﻋﺎﻗﺔ ﻓﻲ ﻗﺪﺭﺍﺗﻬﻢ ﺍﻟﺠﺴﺪﻳﺔ
ﺍﻭ ﺍﻟﺤﺴﻴﺔ ﺍﻭ ﺍﻟﻌﻘﻠﻴﺔ ﺍﻭ ﻧﻘﺺ ﻓﻲ ﺍﻟﺨﺒﺮﺓ ﻭﺍﻟﻤﻌﺮﻓﺔ ﺑﺘﺸﻐﻴﻞ ﺍﻟﺠﻬﺎﺯ ،ﺇﻻ ﺍﺫﺍ ﺗﻢ ﺍﻻﺷﺮﺍﻑ ﻋﻠﻴﻬﻢ ﺍﻭ ﺍﻋﻄﺎﺋﻬﻢ ﺍﻟﺘﻌﻠﻴﻤﺎﺕ ﺍﻟﻤﺘﻌﻠﻘﺔ
ﺑﺎﺳﺘﻌﻤﺎﻝ ﺍﻟﺠﻬﺎﺯ ﻣﻦ ﻗﺒﻞ ﺷﺨﺺ ﻣﺴﺆﻭﻝ ﻋﻦ ﺳﻼﻣﺘﻬﻢ.
ﻳﺠﺐ ﺍﻻﺷﺮﺍﻑ ﻋﻠﻰ ﺍﻻﻃﻔﺎﻝ ﻟﻀﻤﺎﻥ ﻋﺪﻡ ﻋﺒﺜﻬﻢ ﺑﺎﻟﺠﻬﺎﺯ.
ﺍﺣﺘﻴﺎﻃﺎﺕ ﺍﻷﻣﺎﻥ
! ﺗﻨﺒﻴﻪ ! ﺗﺤﺬﻳﺮ
ﻳﺮﺟﻰ ﻣﻼﺣﻈﺔ ﺍﻟﻨﻘﺎﻁ ﺍﻟﻤﻬﻤﺔ ﺍﻟﺘﺎﻟﻴﺔ ﻋﻨﺪ ﺍﻟﻨﺼﺐ. ﻳﺠﺐ ﺍﺟﺮﺍﺀ ﻋﻤﻠﻴﺔ ﺍﻟﺘﺮﻛﻴﺐ ﻭﺍﻟﺼﻴﺎﻧﺔ ﻣﻦ ﻗﺒﻞ ﺍﻟﻔﻨﻴﻴﻦ ﺍﻟﻤﺨﺘﺼﻴﻴﻦ •
• ﻻﺗﻨﺼﺐ ﺍﻟﻮﺣﺪﺓ ﻓﻲ ﻣﻜﺎﻥ ﻣﻌﺮﺽ ﻟﻐﺎﺯ ﺳﺮﻳﻊ ﺍﻻﻟﺘﻬﺎﺏ. ﺍﻟﺬﻳﻦ ﻟﺪﻳﻬﻢ ﺣﺴﻦ ﺍﻻﻃﻼﻉ ﻋﻠﻰ ﺍﻟﺸﻔﺮﺓ ﻭﺍﻟﺘﻨﻈﻴﻢ ﺍﻟﻤﺤﻠﻲ،
ﺍﺫﺍ ﺗﺴﺮﹼﺏ ﺍﻟﻐﺎﺯ ﻭﺗﺠﻤﹼ ﻊ ﺣﻮﻝ ﺍﻟﻮﺣﺪﺓ ،ﻓﺎﻧﻪ ﻳﻤﻜﻦ ﺍﻥ ﻳﺴﺒﺐ ﻭﺍﻟﺨﺒﺮﺓ ﻣﻊ ﻫﺬﺍ ﺍﻟﻨﻮﻉ ﻣﻦ ﺍﻻﺟﻬﺰﺓ.
ﺫﻟﻚ ﺍﺷﻌﺎﻝ ﺍﻟﻨﺎﺭ. ﻳﺠﺐ ﻧﺼﺐ ﺷﺒﻜﺔ ﺍﺳﻼﻙ ﻣﺠﺎﻝ ﺍﻟﻘﻮﺓ ﻭﻓﻘﺎ ﹰ ﺍﻟﻰ ﺗﻨﻈﻴﻢ ﺷﺒﻜﺔ •
• ﺗﺄﻛﺪ ﻣﻦ ﺗﻮﺻﻴﻞ ﺃﻧﺎﺑﻴﺐ ﺍﻟﺘﺼﺮﻳﻒ ﺑﺼﻮﺭﺓ ﺻﺤﻴﺤﺔ. ﺍﺳﻼﻙ ﺍﻟﻮﻃﻦ.
ﺍﺫﺍ ﻟﻢ ﻳﺘﻢ ﺗﻮﺻﻴﻞ ﺍﻧﺎﺑﻴﺐ ﺍﻟﺘﺼﺮﻳﻒ ﺑﺼﻮﺭﺓ ﺻﺤﻴﺤﺔ ،ﺳﻮﻑ ﺗﺄﻛﺪ ﻣﻦ ﺍﻥ ﻣﻌﺪﻝ ﺍﻟﻔﻮﻟﻄﻴﺔ ﻟﻠﻮﺣﺪﺓ ﻳﺘﻄﺎﺑﻖ ﻣﻊ ﺍﻟﻠﻮﺣﺔ ﺍﻟﻤﺤﺪﺩﺓ •
ﻳﺘﺴﺮﺏ ﺍﻟﻤﺎﺀ ﺍﻟﺬﻱ ﻳﺆﺩﻱ ﺍﻟﻰ ﺗﺮﻃﺐ ﺍﻷﺛﺎﺙ. ﻗﺒﻞ ﺃﻥ ﺗﺒﺪﺃ ﺑﺎﻋﻤﺎﻝ ﺷﺒﻜﺔ ﺍﻻﺳﻼﻙ ﻭﻓﻘﺎ ﹰ ﺍﻟﻰ ﻣﺨﻄﻂ ﺍﻟﺘﻤﺪﻳﺪﺍﺕ
• ﻻﺗﻔﺮﻁ ﻓﻲ ﺷﺤﻦ ﺍﻟﻮﺣﺪﺓ. ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ.
ﺗﻢ ﺷﺤﻦ ﺍﻟﻮﺣﺪﺓ ﻣﺴﺒﻘﺎ ﹰ ﻓﻲ ﺍﻟﻤﺼﻨﻊ. ﻳﺠﺐ ﺗﺄﺭﻳﺾ ﺍﻟﻮﺣﺪﺓ ﻟﻤﻨﻊ ﺍﻟﻤﺨﺎﻃﺮ ﺍﻟﻤﺤﺘﻤﻠﺔ ﺑﺴﺒﺐ ﻧﻘﺺ •
ﻳﺆﺩﻱ ﺍﻟﺸﺤﻦ ﺍﻟﺰﺍﺋﺪ ﺍﻟﻰ ﺗﺠﺎﻭﺯ ﺍﻟﺘﻴﺎﺭ ﺍﻭ ﺗﻠﻒ ﺍﻟﻀﺎﻏﻄﺔ. ﺍﻟﻌﺎﺯﻝ.
• ﺗﺄﻛﺪ ﻣﻦ ﻏﻠﻖ ﻟﻮﺣﺔ ﺍﻟﻮﺣﺪﺓ ﺑﻌﺪ ﺍﺟﺮﺍﺀ ﺍﻟﺼﻴﺎﻧﺔ ﺍﻭ ﺍﻟﻨﺼﺐ. ﻳﺠﺐ ﺍﻥ ﻻ ﺗﻼﻣﺲ ﺍﻻﺳﻼﻙ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ ﺍﻧﺎﺑﻴﺐ ﺍﻟﻤﺒﺮﺩ ﺍﻭ ﺍﻳﺔ ﺍﺟﺰﺍﺀ •
ﻳﺆﺩﻱ ﻋﺪﻡ ﻏﻠﻖ ﺍﻟﻠﻮﺣﺎﺕ ﺑﺄﺣﻜﺎﻡ ﺑﺎﻟﻮﺣﺪﺓ ﺍﻟﻰ ﺍﻟﺘﺸﻐﻴﻞ ﻣﺘﺤﺮﻛﺔ ﻣﻦ ﻣﺤﺮﻛﺎﺕ ﺍﻟﻤﺮﻭﺣﺔ.
ﺍﻟﻤﺼﺤﻮﺏ ﻟﻀﻮﺿﺎﺀ. ﺗﺄﻛﺪ ﻣﻦ ﺗﺤﻮﻳﻞ ﺍﻟﻮﺣﺪﺓ ﻋﻠﻰ ﻣﻮﺿﻊ ﺍﻻﻳﻘﺎﻑ OFFﻗﺒﻞ ﺍﺟﺮﺍﺀ ﻋﻤﻠﻴﺔ •
• ﺣﺎﻓﺎﺕ ﺣﺎﺩﺓ ﻭ ﺍﺳﻄﺢ ﻣﻠﺘﻔﺔ ﻓﻲ ﻣﻮﺍﻗﻊ ﻛﺎﻣﻨﺔ ﻭﺍﻟﺘﻲ ﺗﺴﺒﺐ ﺍﻟﻨﺼﺐ ﺍﻭ ﺍﻟﺼﻴﺎﻧﺔ ﻟﻠﻮﺣﺪﺓ.
ﻣﺨﺎﻃﺮ ﺍﻟﺠﺮﻭﺡ .ﺗﺠﻨﺐ ﻣﻦ ﺍﻻﺣﺘﻜﺎﻙ ﺑﻬﺬﻩ ﺍﻷﻣﺎﻛﻦ. ﺍﻓﺼﻞ ﻣﻜﻴﻒ ﺍﻟﻬﻮﺍﺀ ﻣﻦ ﻣﺼﺪﺭ ﺗﺰﻭﻳﺪ ﺍﻟﻄﺎﻗﺔ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ ﺍﻟﺮﺋﻴﺴﻲ •
• ﻗﺒﻞ ﻓﺼﻞ ﻣﺼﺪﺭ ﺗﺰﻭﻳﺪ ﺍﻟﻄﺎﻗﺔ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ ،ﺍﺿﺒﻂ ﻣﻔﺘﺎﺡ ﻗﺒﻞ ﺍﺟﺮﺍﺀ ﻋﻤﻠﻴﺔ ﺻﻴﺎﻧﺔ ﻭﺣﺪﺓ ﻣﻜﻴﻒ ﺍﻟﻬﻮﺍﺀ.
ﺍﻟﺘﺸﻐﻴﻞ /ﺍﻻﻳﻘﺎﻑ ON/OFFﺍﻟﻤﻮﺟﻮﺩ ﻋﻠﻰ ﻭﺣﺪﺓ ﺍﻟﺘﺤﻜﻢ ﻻ ﺗﺴﺤﺐ ﺳﻠﻚ ﺍﻟﻄﺎﻗﺔ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ ﻋﻨﺪﻣﺎ ﺗﻜﻮﻥ ﺍﻟﻄﺎﻗﺔ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ •
ﻋﻦ ﺑﻌﺪ ﻋﻠﻰ ﻭﺿﻊ ﺍﻻﻳﻘﺎﻑ ” “OFFﻭﺫﻟﻚ ﻟﻤﻨﻊ ﺣﺼﻮﻝ ﺍﺯﻋﺎﺝ ﻣﻮﺻﻮﻟﺔ .ﻳﻤﻜﻦ ﺍﻥ ﻳﺴﺒﺐ ﺫﻟﻚ ﺿﺮﺑﺎﺕ ﻛﻬﺮﺑﺎﺋﻴﺔ ﻗﻮﻳﺔ ﻭﻳﻤﻜﻦ ﺍﻥ
ﻭﺿﺮﺭ ﻣﻦ ﺍﻟﻤﻜﻴﻒ .ﻓﻲ ﺣﺎﻟﺔ ﻋﺪﻡ ﻋﻤﻞ ﺫﻟﻚ ،ﺳﻮﻑ ﺗﺸﺘﻐﻞ ﻣﺮﺍﻭﺡ ﺗﺴﺒﺐ ﻣﺨﺎﻃﺮﺍﻟﺤﺮﻳﻖ.
ﺍﻟﻤﻜﻴﻒ ﺍﻭﺗﻮﻣﺎﺗﻴﻜﻴﺎ ﻋﻨﺪ ﺍﺳﺘﻌﺎﺩﺓ ﺍﻟﻄﺎﻗﺔ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ ﻭﻳﻤﻜﻦ ﺍﻥ ﺿﻊ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ ﻭﺍﻟﻮﺣﺪﺓ ﺍﻟﺨﺎﺭﺟﻴﺔ ،ﻭﻛﺒﻞ ﺍﻟﻄﺎﻗﺔ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ •
ﻳﺘﻌﺮﹼﺽ ﺍﻻﺷﺨﺎﺹ ﺍﻟﻔﻨﻴﻴﻦ ﺍﻭﺍﻟﻤﺴﺘﻌﻤﻞ ﻟﻠﺨﻄﺮ. ﻭﺍﺳﻼﻙ ﺍﻻﺭﺳﺎﻝ ،ﻋﻠﻰ ﻣﺴﺎﻓﺔ 1ﻣﺘﺮ ﻋﻠﻰ ﺍﻻﻗﻞ ﺑﻌﻴﺪﺍ ﻋﻦ ﺍﺟﻬﺰﺓ
ﺗﺸﻐﻞ ﺍﻱ ﺟﻬﺎﺯ ﺗﺪﻓﺌﺔ ﺑﻘﺮﺏ ﻣﻜﻴﻒ ﺍﻟﻬﻮﺍﺀ. ﹼ • ﻻ ﺍﻟﺘﻠﻔﺰﻳﻮﻧﺎﺕ ﻭﺍﻟﺮﺍﺩﻳﻮ ،ﻭﺫﻟﻚ ﻟﻤﻨﻊ ﺗﺸﻮﻩ ﺍﻟﺼﻮﺭﺓ ﻭﺍﻟﺘﺸﻮﻳﺶ ﺍﻻﺫﺍﻋﻲ.
• ﻻ ﺗﺴﺘﺨﺪﻡ ﺃﺳﻼﻙ ﻣﻀﻤﻮﻣﺔ ﺃﻭ ﻣﻠﺘﻮﻳﺔ ﻟﺘﻮﻟﻴﺪ ﺍﻟﻄﺎﻗﺔ }ﺍﻋﺘﻤﺎﺩﺍ ﻋﻠﻰ ﻧﻮﻉ ﻭﻣﺼﺪﺭ ﺍﻻﻣﻮﺍﺝ ﺍﻟﻜﻬﺮﺑﺎﺋﻴﺔ ،ﻳﻤﻜﻦ ﺍﻥ ﻳﺘﻢ ﺳﻤﺎﻉ
ﻟﻠﺠﻬﺎﺯ. ﺗﺸﻮﻳﺶ ﺍﺫﺍﻋﻲ ﻭﺣﺘﻰ ﺍﺫﺍ ﻛﺎﻧﺖ ﺍﻟﻤﺴﺎﻓﺔ ﺍﻛﺜﺮ ﻣﻦ 1ﻣﺘﺮ { .
• ﻻ ﻳﺠﺐ ﺍﺳﺘﺨﺪﺍﻡ ﺍﻵﻟﺔ ﻓﻲ ﻣﻜﺎﻥ ﻗﺎﺑﻞ ﻟﻠﺘﻔﺠﻴﺮ.
ﻻﺣﻈﺔ ﹼ
ﻣﺘﻄﻠﺐ ﺍﻟﺘﺨﻠﺺ ﻣﻦ ﺍﻟﺠﻬﺎﺯ
ﹰ
ﻳﺠﺐ ﺃﻥ ﻳﺘﻢ ﺗﻔﻜﻴﻚ ﺍﻟﻮﺣﺪﺓ ،ﻣﻌﺎﻟﺠﺔ ﺍﻟﻤﺒﺮﺩ ،ﻭﺍﻟﺰﻳﺖ ﻭﺍﻷﺟﺰﺍﺀ ﺍﻷﺧﺮﻯ ﻭﻓﻘﺎ ﻟﻠﺘﺸﺮﻳﻌﺎﺕ ﺍﻟﻤﻄﺒﻘﺔ.
٣
ﻃﺮﺍﺯRT240C :
1045.0 158.0
456.0
1076.0
994.0
456.0
1981.0
61.0
170 484.0
CONTROL
BOX
1690.0
768.0
200
150.0
ﻣﺮﻛﺰ ﺍﻟﺠﺎﺫﺑﻴﺔ
ﻃﺮﺍﺯRT300C :
1000.0 160.0
677.0
1076.0
1215.0
677.0
2104.0
CONTROL
BOX
1650.0
768.0
245.0
150.0
ﻣﺮﻛﺰ ﺍﻟﺠﺎﺫﺑﻴﺔ
٢
ﻃﺮﺍﺯRT150C :
ﻋﺮﺑﻲ
855.0 142.0
ﺗﺮﺟﻤﺔ ﺍﻟﺘﻌﻠﻴﻤﺎﺕ ﺍﻻﺻﻠﻴﺔ
652.0
684.0
994.0
652.0
50.0
350.0
CONTROL
BOX
1390.0
165.0
700.0
125.0
150.0
ﻣﺮﻛﺰ ﺍﻟﺠﺎﺫﺑﻴﺔ
ﻃﺮﺍﺯRT180C :
830.0 412.0
652.0
684.0
994.0
652.0
1710.0
CONTROL
BOX
1390.0
700.0
1988.0
125.0
1748.0
ﻣﺮﻛﺰ ﺍﻟﺠﺎﺫﺑﻴﺔ
١
IM-RTC-0611(3)-ACSON
ﺭﻗﻢ ﺍﻟﺠﺰﺀ R08019036619C :.