MP2200 User's Manual
MP2200 User's Manual
MP2200 User's Manual
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system,
or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording,
or otherwise, without the prior written permission of Yaskawa. No patent liability is assumed
with respect to the use of the information contained herein. Moreover, because Yaskawa is con-
stantly striving to improve its high-quality products, the information contained in this manual is
subject to change without notice. Every precaution has been taken in the preparation of this
manual. Nevertheless, Yaskawa assumes no responsibility for errors or omissions. Neither is
any liability assumed for damages resulting from the use of the information contained in this
publication.
Using this Manual
Please read this manual to ensure correct usage of the MP2200 system. Keep this manual in a safe place for
future reference.
Basic Terms
Manual Configuration
Read the chapters of this manual as required by the purpose.
Selecting
Studying Maintenance
Models and Designing Installation Trial
Chapter Specifications and
Peripheral the System and Wiring Operation
and Ratings Inspection
Devices
Chapter 1
Applicable − − − − −
Overview of the MP2200
Chapter 2
Applicable − − − − −
System Configuration
Chapter 3
− − − − Applicable −
System Startup
Chapter 4
Applicable Applicable Applicable Applicable − −
Module Specifications
Chapter 5
− Applicable Applicable Applicable − −
Mounting and Wiring
Chapter 6
− − Applicable − Applicable −
Basic System Operation
Chapter 7
Maintenance and − − − − − Applicable
Inspection
Chapter 8
− − − − Applicable Applicable
Troubleshooting
iii
Visual Aids
The following aids are used to indicate certain types of information for easier reference.
Describes technical terms that are difficult to understand, or appear in the text without an explana-
TERMS
tion being given.
• S-ON = /S-ON
• P-CON = /P-CON
Copyrights
iv
Related Manuals
Refer to the following related manuals as required.
Thoroughly check the specifications, restrictions, and other conditions of the product before attempting to
use it.
v
Safety Information
The following conventions are used to indicate precautions in this manual. Failure to heed precautions pro-
vided in this manual can result in serious or possibly even fatal injury or damage to the products or to related
equipment and systems.
Indicates precautions that, if not heeded, could possibly result in loss of life or serious
WARNING
injury.
Indicates precautions that, if not heeded, could result in relatively serious or minor
CAUTION
injury, damage to the product, or faulty operation.
In some situations, the precautions indicated could have serious consequences if not heeded.
Indicates prohibited actions that must not be performed. For example, this symbol
PROHIBITED
would be used as follows to indicate that fire is prohibited: .
Indicates compulsory actions that must be performed. For example, this symbol would
MANDATORY
be used as follows to indicate that grounding is compulsory: .
vi
Safety Precautions
The following precautions are for checking products on delivery, storage, transportation, installation, wiring,
operation, maintenance, inspection, and disposal. These precautions are important and must be observed.
WARNING
• Before starting operation in combination with the machine, ensure that an emergency stop procedure
has been provided and is working correctly.
There is a risk of injury.
• Do not touch anything inside the MP2200.
There is a risk of electrical shock.
• Always keep the front cover attached when power is being supplied.
There is a risk of electrical shock.
• Observe all procedures and precautions given in this manual for trial operation.
Operating mistakes while the servomotor and machine are connected can cause damage to the machine or even
accidents resulting in injury or death.
• Do not remove the front cover, cables, connector, or options while power is being supplied.
There is a risk of electrical shock.
• Do not allow installation, disassembly, or repairs to be performed by anyone other than specified per-
sonnel.
There is a risk of electrical shock or injury.
• Do not damage, pull on, apply excessive force to, place heavy objects on, or pinch cables.
There is a risk of electrical shock, operational failure or burning of the MP2200.
• Do not attempt to modify the MP2200 in any way.
There is a risk of injury or device damage.
• Do not approach the machine when there is a momentary interruption to the power supply. When
power is restored, the machine may start operation suddenly. Provide suitable safety measures to
protect people when operation restarts.
There is a risk of injury.
vii
Storage and Transportation
CAUTION
• Do not store or install the MP2200 in the following locations.
There is a risk of fire, electrical shock, or device damage.
• Direct sunlight
• Ambient temperature exceeds the storage or operating conditions
• Ambient humidity exceeds the storage or operating conditions
• Rapid changes in temperature or locations subject to condensation
• Corrosive or flammable gas
• Excessive dust, dirt, salt, or metallic powder
• Water, oil, or chemicals
• Vibration or shock
• Do not overload the MP2200 during transportation.
There is a risk of injury or an accident.
Installation
CAUTION
• Never use the MP2200 in locations subject to water, corrosive atmospheres, or flammable gas, or
near burnable objects.
There is a risk of electrical shock or fire.
• Do not step on the MP2200 or place heavy objects on the MP2200.
There is a risk of injury.
• Do not block the air exhaust port or allow foreign objects to enter the MP2200.
There is a risk of element deterioration inside, an accident, or fire.
• Always mount the MP2200 in the specified orientation.
There is a risk of an accident.
• Do not subject the MP2200 to strong shock.
There is a risk of an accident.
viii
Wiring
CAUTION
• Check the wiring to be sure it has been performed correctly.
There is a risk of motor run-away, injury, or an accident.
• Always use a power supply of the specified voltage.
There is a risk of burning.
• In places with poor power supply conditions, take all steps necessary to ensure that the input power
supply is within the specified voltage range.
There is a risk of device damage.
• Install breakers and other safety measure to provide protection against shorts in external wiring.
There is a risk of fire.
• Provide sufficient shielding when using the MP2200 in the following locations.
There is a risk of device damage.
• Noise, such as from static electricity
• Strong electromagnetic or magnetic fields
• Radiation
• Near to power lines
• When connecting the battery, connect the polarity correctly.
There is a risk of battery damage or explosion.
CAUTION
• Consider the following items when selecting the I/O signal lines (external cables) to connect the
MP2200 to external devices.
• Mechanical strength
• Noise interference
• Wiring distance
• Signal voltage, etc.
• Separate the I/O signal lines from the power lines both inside and outside the control box to reduce
the influence of noise from the power lines.
If the I/O signal lines and power lines are not separated properly, malfunctioning may result.
Example
外部配線の分離例of Separated External Cables
Steel separator
鉄板製のセパレータ
ix
Maintenance and Inspection Precautions
CAUTION
• Do not attempt to disassemble the MP2200.
There is a risk of electrical shock or injury.
• Do not change wiring while power is being supplied.
There is a risk of electrical shock or injury.
• When replacing the MP2200, restart operation only after transferring the programs and parameters
from the old Module to the new Module.
There is a risk of device damage.
Disposal Precautions
CAUTION
• Dispose of the MP2200 as general industrial waste.
x
CONTENTS
Using this Manual - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - iii
Safety Information - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - vi
Safety Precautions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - vii
1 Outline of MP2200
1.1 Features - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-2
1.2 Module Appearance - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-3
1.2.1 Basic Unit - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-3
1.2.2 Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-4
2 System Configuration
2.1 System Configuration - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2-2
2.1.1 Basic System Configuration - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2-2
2.1.2 System Configuration Precautions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2-4
3 System Startup
3.1 Outline- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-2
3.1.1 System Startup Flowchart- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-2
3.1.2 System Configuration - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-3
3.1.3 Device Preparation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-4
3.1.4 Connecting and Wiring the System - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-6
3.1.5 Initializing the System - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-8
3.1.6 Starting the MPE720 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-11
xi
3.4.2 Operation- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-53
3.4.3 Program Details - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-55
4 Module Specifications
4.1 General Specifications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-3
4.1.1 Hardware Specifications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4-3
4.1.2 Function List - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4-4
xii
4.9 LIO-04 Module - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-40
4.9.1 Outline of Functions- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-40
4.9.2 LED Indicators and Switch Settings- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-40
4.9.3 Hardware Specifications- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-41
xiii
6 Basic System Operation
6.1 Operating Mode - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 6-2
6.1.1 Online Operating Mode - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -6-2
6.1.2 Offline Stop Mode - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -6-2
xiv
8 Troubleshooting
8.1 Overview of Troubleshooting - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 8-2
8.1.1 Troubleshooting Methods - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 8-2
8.1.2 Basic Troubleshooting Flow - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 8-3
8.1.3 Indicator Errors - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 8-3
Appendices
A List of System Registers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A-2
A.1 System Service Registers- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A-2
A.2 Scan Execution Status and Calendar - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A-5
A.3 Program Software Numbers and Remaining Program Memory Capacity - - - - - - - - - - - - - - - - - A-5
INDEX
Revision History
xv
1
1
Outline of MP2200
This chapter provides an overview and describes the features of the MP2200 Machine Control-
ler.
1-1
1 Outline of MP2200
1.1 Features
The MP2200 is a high-performance, multi-axis Machine Controller for flexible system construction. In addition
to I/O and Communication Modules, it has a wide range of Optional Modules, including various Motion Mod-
ules that support a variety of motor drives. It provides ideal motion control for a range of machines, from stand-
alone machines to FA systems.
(1) Flexibility
• With an option slot configuration that enables expansion to 35 slots, Optional Modules can be selected
freely and the optimum system can be built for your machine.
(4) Compact
• The mounting area has been reduced to half that of the MP920.
1-2
1.2 Module Appearance
1
MP2200 MBU-01 CPU-01 218IF-01 SVB-01 LIO-01
POWER
LIO-01 LIO-02 260IF-01 217IF-01 EXIOIF
YASKAWA
1-3
1 Outline of MP2200
1.2.2 Modules
1.2.2 Modules
The following figures show the external appearance of the Modules.
LED indicators
LED indicators
CPU-01 SVB-01
DIP switch
DIP switch RDY RUN RUN ERR
ALM ERR
Switches (station TX
address setting)
BAT
M/S
SIZE
STOP
SPD
SUP
OFF ON
INIT
CNFG 10
MON
TEST
SW1 1
OFF ON
MECHATROLINK M-I/II
connector
CN1
MECHATROLINK
connector
CN2
CPU-01 SVB-01
Switch Switch
LIO-01 LIO-02
CN1
CH1
CH2
+24V
ON
CN2 DC IN
LIO-04 SVA-01
1-4
1.2 Module Appearance
Switch Switch
1
Ethernet connector Serial connector
(10Base-T) (RS-422/485)
218IF-01 217IF-01
PROFIBUS
DeviceNet connector PROFIBUS connector
260IF-01 261IF-01
EXIOIF
External input connector
EXIOIF
1-5
2
System Configuration
2
This chapter explains the product information required to build MP2200 systems.
2-1
2 System Configuration
2.1.1 Basic System Configuration
24-VDC
power
supply
9 Modules max.
Optional Modules
MECHATROLINK-II Motion Modules
SVB-01 MECHATROLINK
PL2900
PL2910
IO2310
SGDS
SGDH
NS115
I/O Modules
M M
LIO-01 External I/O
Communication Modules
218IF-01 Ethernet
217IF-01 RS485/422
260IF-01 DeviceNet
261IF-01 PROFIBUS
RS-232C
2-2
2.1 System Configuration
EXAMPLE
24-VDC
power
supply
2
External I/O
MECHATROLINK-II
Control panel
RS-232C
PL2900
PL2910
IO2310
SGDS
SGDH
NS115
MPE720
M M
Ethernet
MECHATROLINK- Servodrives
compatible I/O Modules
2-3
2 System Configuration
2.1.2 System Configuration Precautions
Optional Modules
24 VDC
or
100/200
External I/O Modules
VAC
External I/O
LIO-04
LIO-01
LIO-02
Slot 1 External I/O
Slot 9
Communication Modules
RS-232C MMI
218IF-01
260IF-01
261IF-01
217IF-01
Ethernet MPE720
DeviceNet
PROFIBUS
Slot 1 Slot 9
RS-422/485
Motion Modules
M
SVB-01
SVA-01
SERVOPACK
PG
Slot 1 Slot 9
External output
External input
* A distributed I/O function is provided by the SVB-01 Modules through MECHATROLINK communication.
2-4
2.2 List of Modules
Base Units
Base Unit (for DC Basic Unit with 24-VDC (±20%) power sup-
MBU-02 JEPMC-BU2210 −
power supply) ply (9 slots)
CPU Mod-
CPU Module CPU-01 JAPMC-CP2200 1 MP2200 system CPU
ules 2
MECHATROLINK MECHATROLINK-I and
Motion Interface Servo SVB-01 JAPMC-MC2310 1 MECHATROLINK-II-compatible
Modules Module SERVOPACKs (16 axes max.)
Analog Servo Inter-
SVA-01 JAPMC-MC2300 1 Analog servo interface (2 axes)
face Module
16 inputs and 16 outputs (sink mode outputs)
I/O Module LIO-01 JAPMC-IO2300 1
1 pulse input
16 inputs and 16 outputs (source mode out-
I/O Modules
I/O Module LIO-02 JAPMC-IO2301 1 puts)
Optional Modules
1 pulse input
I/O Modules LIO-04 JAPMC-IO2303 1 32 inputs and 32 outputs (sink mode outputs)
Ethernet Communi-
218IF-01 JAPMC-CM2300 1 RS-232C/Ethernet communication
cation Module
General-purpose
RS-232C, RS-422, and RS-485 communica-
Communi- Serial Communica- 217IF-01 JAPMC-CM2310 1
tion
cation Mod- tion Module
ules DeviceNet Commu-
260IF-01 JAPMC-IO2320 1 RS-232C and DeviceNet communication
nication Module
PROFIBUS Com-
261IF-01 JAPMC-IO2330 1 RS-232C and PROFIBUS communication
munication Module
Expansion 1
Connection Inter- System bus expansion (maximum 4-Rack con-
Interface EXIOIF JAPMC-EX2200
face figuration)
Modules
2-5
2 System Configuration
2-6
2.4 Cables and Accessories
2.4.2 Accessories
Name Model Remarks
DIN Rail Mounting Clips JEPMC-OP300 −
Battery ZZK000064 ER3VC + Special Connector (BA000517)
721-863/001-034 MBU-01 Unit Cable side (manufactured by WAGO, black)
Power Supply Connector
721-863/001-000 MBU-02 Unit Cable side (manufactured by WAGO, white)
2-7
2 System Configuration
2.5.1 Software for Programming Devices
2.5 Software
2.5.1 Software for Programming Devices
Name Model Remarks
MPE720 CPMC-MPE720 (Ver. 5.10 or later)* CD-ROM (1 disk)
* Older versions cannot be used. Always use Ver. 5.10 or later.
2-8
3
System Startup
This chapter describes the startup procedure for the MP2200 system and provides sample pro- 3
grams for typical operation and control.
3-1
3 System Startup
3.1.1 System Startup Flowchart
3.1 Outline
This section explains the system startup procedure when the sample program on the MPE720 installation disk is
used. Details on the machine system design have been omitted here.
3-2
3.1 Outline
218IF-01
SVB-01
MP2200
MP2200 MBU-02 CPU-01 218IF-01 SVB-01 LIO-01
24-VDC POWER
power
supply
I/O
Optional Module
Optional Module
Optional Module
Optional Module
Optional Module
PORT
BATTEY CN1
10Base-T
DC CN2
POWER
MECHATROLINK-II
3
SERVOPACK SERVOPACK
YASKAWA SERVOPACK 200V YASKAWA SERVOPACK 200V
SGDS-01A12A SGDS-01A12A
Terminator
SW1 SW1
C C
N N
CHARGE 6
A/B
JEPMC-W6002-01 CHARGE 6
A/B
L1 L1
L2 L2
L1C C L1C C
N N
L2C 3 L2C 3
B1/ B1/
B2 B2
C C
U N U N
1 1
V V
W W
MPE720 C
N
C
N
2 2
C C
N N
4 4
200 VAC
Servomotor Servomotor
* The 24-VDC power supply is not required for a Basic Unit with a 100-VAC power supply input.
INFO Refer to Chapter 5 Mounting and Wiring for information on mounting Modules.
3-3
3 System Startup
3.1.3 Device Preparation
JEPMC-W6022
JEPMC-W6002-01
DC
Computer
JEPMC-W5311-03
MPE720
3-4
3.1 Outline
1 12
3
SVON COIN TGON REF CHARGE
VCMP
YASKAWA
JOG
DATA
SVON
READ WRITE
SERVO SERVO
DIGITAL OPERATOR JUSP-OP05A
3-5
3 System Startup
3.1.4 Connecting and Wiring the System
PORT
Optional Module
Optional Module
Optional Module
Optional Module
Optional Module
Optional Module
M- /
BATTEY CN1
10Base-T
DC CN2
POWER
JEPMC-W5311-03
PORT
Optional Module
Optional Module
Optional Module
Optional Module
Optional Module
Optional Module
M- /
BATTEY CN1
10Base-T
DC CN2
POWER
SERVOPACK SERVOPACK
YASKAWA SERVOPACK 200V YASKAWA SERVOPACK 200V
SGDS-02A12A SGDS-02A12A
SW1 SW1
C
N
C
N Terminator
MECHATROLINK-II CHARGE
A/B
6
JEPMC-W6002-01 CHARGE 6
A/B
L1 L1
L2 L2
L1C C L1C C
N N
L2C 3 L2C 3
B1/ B1/
B2 B2
C C
U N U N
1 1
V V
W W
C C
N N
2 2
C C
N N
4 4
3-6
3.1 Outline
PORT
Optional Module
Optional Module
Optional Module
Optional Module
Optional Module
Optional Module
M- /
BATTEY CN1
10Base-T
DC
CN2
POWER
SERVOPACK SERVOPACK
YASKAWA SERVOPACK 200V YASKAWA SERVOPACK 200V
SGDS-02A12A SGDS-02A12A
MECHATROLINK-II
SW1
CHARGE
C
N
6
A/B
SW1
CHARGE
C
N
6
A/B
Terminator 3
L1 L1
L2 L2
L1C C L1C C
N N
L2C 3 L2C 3
B1/ B1/
B2 B2
C C
U N U N
1 1
V V
W W
C C
N N
2 2
C C
N N
4 4
JZSP-CSM01-03 JZSP-CSP01-03
Servomotor Servomotor
3-7
3 System Startup
3.1.5 Initializing the System
4. Turn ON SERVOPACK.
Turn ON the control power supply and main power supply for the SERVOPACK.
The method for initializing the parameter settings (step 2, above) from the SERVOPACK Digital Operator is
shown below.
3-8
3.1 Outline
3-9
3 System Startup
3.1.5 Initializing the System
OFF ON
3. Turn ON the power.
Turn ON the Basic Unit 24-VDC power supply.
STOP
SUP
INIT 5. Reset DIP switch.
CNFG
Turn OFF the INIT and CNFG pins on the DIP switch (SW1) on the
MON
TEST Basic Unit.
SW1
OFF ON
• INIT Switch
IMPORTANT
RAM data will be cleared if the INIT pin on the DIP switch on the CPU Module is turned ON and the
power is turned ON. Flash memory data is read when the INIT switch is turned OFF and the power is
turned ON. Therefore, always save data to the MP2200 flash memory before turning OFF the power when
writing or editing programs.
Refer to 3.1.6 Starting the MPE720 for information on saving data to flash memory.
3-10
3.1 Outline
2. Communication settings
Define communications with the MP2200.
6. Logging on online
Log on online to the MP2200.
3-11
3 System Startup
3.1.6 Starting the MPE720
Double-click
3-12
3.1 Outline
2. Double-click Logical PT number 1 in the Communication Process Window to display the Logical Port
Setting Window.
Double-click
3. For RS-232C connections, select Port Kind - Serial in the Logical Port Setting Window.
3-13
3 System Startup
3.1.6 Starting the MPE720
b) The Serial Port Setting Window will be displayed. Match the settings under Physical Port to the com-
puter’s serial communication port. Leave the other items on the default settings. Once the settings have
been completed and checked, click the OK button.
c) The Logical Port Setting Window will be displayed. Click the OK button again. The screen will return
to the Communication Process Window. Check that Serial has been allocated to the Logical PT number
1.
5. Ethernet Connections
Double-click Logical PT number 2 in the Communication Process Window to display the Logical Port
Setting Window.
Double-click
3-14
3.1 Outline
6. Ethernet Settings
a) Select Port Kind - CP-218 in the Logical Port Setting Window and click the Detail button.
b) The CP-218 Port Setting Window will be displayed. Select OFF for Default and enter the computer IP
address in the IP Address (First) field. Leave the other items on the default settings. Once the settings
have been completed and checked, click the OK button.
c) The Logical Port Setting Window will be displayed. Click the OK button again. The screen will return
to the Communication Process Window. Check that CP-218 has been allocated to the Logical PT num-
ber 2.
3-15
3 System Startup
3.1.6 Starting the MPE720
c) Double-click the Communication Manager icon in the YE_Applications Folder to reopen the Com-
munication Process Window.
Double-click
3-16
3.1 Outline
2. Enter the group folder name in the Make New Folder Window and click the OK button. The group folder
name must be 8 characters or less.
3. The new group folder MP2200 will be created. Double-click the root directory or click the button to
display the MP2200 Group Folder.
3-17
3 System Startup
3.1.6 Starting the MPE720
2. Enter the order folder name in the Make New Folder Window and click the OK button. The order folder
name must be 8 characters or less.
3. The new “YESAMPLE” Order Folder will be created. Double-click the MP2200 Group Folder or click
the button to display the YESAMPLE order folder.
3-18
3.1 Outline
2. Set the Controller Name and Controller Type shown below, and click the OK button.
Controller name: 2200SMPL
Controller type: MP2200
3. A new controller folder 2200SMPL will be created. Double-click the YESAMPLE Order Folder or click
the button to display the 2200SMPL Controller Folder.
3-19
3 System Startup
3.1.6 Starting the MPE720
2. Right-click the 2200SMPL Controller Folder and check that there is a check mark next to Online. Also
check that Online at the bottom right of the screen is listed as Connected, then select Properties.
3. The Controller Configuration Window will be opened. Select the Network Tab. Online should be set to
Yes.
Under Logical Port Number (Device Type), select the same Logical PT that was set for the communica-
tion process.
3-20
3.1 Outline
4. For RS-232C connections, leave all settings other than Logical Port Number (Device Type) on the default
settings.
3
5. For Ethernet connections, make the settings shown below.
3-21
3 System Startup
3.1.6 Starting the MPE720
7. Logging On Online
a) Right-click the 2200SMPL Controller Folder and select Log On.
b) Input the user name USER-A and the password USER-A and click the OK button.
3-22
3.1 Outline
Double-click
2. The window for specifying the destination of the file will be displayed. Specify the destination of the file
and click the Decompress button. 3
3. Right-click the 2200SMPL Controller Folder and select File Transfer - All File Transfer - All Program
File Transfer (Other Media - HD).
3-23
3 System Startup
3.1.6 Starting the MPE720
4. The Execute Window will be displayed. The transfer source path must be changed, so click the Change
button.
Click
5. The Transfer Path Window will be displayed. Make the settings given below and click the OK button.
Drive: Select the drive where the sample program was stored. (The A drive, in this example.)
Transfer path: 2200SMPL
7. The Execute Status Window will be displayed. Wait until the transfer has been completed.
8. A message will appear when the transfer has been completed. Click the OK button.
3-24
3.1 Outline
9. The All File Transfer Disk to Disk Window will be displayed. Select File - Exit.
3-25
3 System Startup
3.1.6 Starting the MPE720
2. The Individual Load Window will be displayed. Select the following transfer items:
• DWG
• Scan Time
• Data Trace
• Motion Main Program
3-26
3.1 Outline
3. Click the Details button to the right of DWG to display the DWG Detail Data Set Window. Select Select
All and click the OK button.
4. Click the Details button to the right of Motion Main Program to display the Motion Main Program Detail
Set Window. Select Select All and click the OK button.
3-27
3 System Startup
3.1.6 Starting the MPE720
7. The Execute Status Window will be displayed. Wait until the transfer has been completed.
8. A message will appear when the transfer has been completed. Click the OK button.
3-28
3.1 Outline
a) Point
b) Double-click
3-29
3 System Startup
3.1.6 Starting the MPE720
a) Select
3-30
3.1 Outline
2. The Save Flash Memory Content Window will be displayed. Select File - Execute.
3-31
3 System Startup
3.1.6 Starting the MPE720
3. A message appears to confirm that the CPU will be stopped. Click the Yes Button.
5. A message will appear when the save has been completed normally. Click the OK button.
6. The Save Flash Memory Content Window will be displayed. Select File - Exit.
3-32
3.1 Outline
3. An Execute Status Window will be displayed. Wait until the transfer has been completed.
4. A message will appear when the transfer has been completed. Click the OK button.
3-33
3 System Startup
3.1.6 Starting the MPE720
2. The Controller Running Status Window will be displayed. Click the RUN button.
3-34
3.1 Outline
3. A confirmation message will be displayed. Click the Yes button. Check that the RUN LED indicator on
the CPU Module is lit.
4. The Controller Running Status Window will be displayed again. Click the Close button.
3-35
3 System Startup
3.2.1 Description
• SERVO ON
SEE
Name H01 • Alarm reset
• Parameter settings
H02.01 Drawing
END
Axis 1
• Jog operation
• Step operation
H02 Drawing
END
SEE
SEE Name H02.01
Name H02
SEE
Name H02.02 H02.02 Drawing
END
Axis 2
END
• Jog operation
• Step operation
High-speed scan
END
This sample program has no power OFF circuit for the SERVOPACK in the event of emergency stops or
IMPORTANT
overtravel. Include a proper emergency stop circuit in actual applications.
3-36
3.2 Sample Program 1: Manual Operation
3.2.2 Operation
(1) Display of Tuning Panel Window
In this sample program, run, stop, and other operations can be checked from a Tuning Panel Window.
Use the following procedure to display the Tuning Panel Window.
1. Log on online and open the 2200SMPL Controller Folder, then the Programs and High Scan Programs
folders in the MPE720 File Manager Window.
2. Right-click the H02 drawing in the High Scan Programs Folder and select Open - Tuning Panel.
3-37
3 System Startup
3.2.2 Operation
3. The Tuning Panel Window for the H02 drawing will be displayed.
The details on the Tuning Panel Window display are shown in the following table.
Display
No. Data Name S Current Value Units Lower Limit Upper Limit REG-No. DWG
Definition
1 ***************Common monitor*************** XXXXX 00000 00000 32767 DW00010 L
2 Axis 1 operation ready ON/OFF OFF IB80000
3 Axis 2 operation ready ON/OFF OFF IB80000
4 Axis 1 current position XXXXXXXXXX 0000000000 −0214783648 2147483647 IL8016
5 Axis 2 current position XXXXXXXXXX 0000000000 −0214783648 2147483647 IL8096
6 ***************Common operation*************** XXXXX 00000 00000 32767 DW00010 L
7 Servo ON PB S ON/OFF OFF MB300000
8 Alarm reset PB S ON/OFF OFF MB300001
9 ************Manual operation and setting************ XXXXX 00000 00000 32767 DW00010 L
10 Axis 1 Forward Jog S ON/OFF OFF DB000010 H02.01
11 Axis 1 Reverse Jog S ON/OFF OFF DB000011 H02.01
12 Axis 2 Forward Jog S ON/OFF OFF DB000010 H02.02
13 Axis 2 Reverse Jog S ON/OFF OFF DB000011 H02.02
14 Axis 1 Forward Step S ON/OFF OFF DB000012 H02.01
15 Axis 1 Reverse Step S ON/OFF OFF DB000013 H02.01
16 Axis 2 Forward Step S ON/OFF OFF DB000012 H02.02
17 Axis 2 Reverse Step S ON/OFF OFF DB000013 H02.02
18 Axis 1 Step Moving Amount S XXXXXXXXXX 0000000000 −0214783648 2147483647 DL00010 H02.01
19 Axis 2 Step Moving Amount S XXXXXXXXXX 0000000000 −0214783648 2147483647 DL00010 H02.02
3-38
3.2 Sample Program 1: Manual Operation
Confirm operation.
The following table gives an outline of the operation when the Tuning Panel window is used.
3-39
3 System Startup
3.2.3 Program Details
3-40
3.2 Sample Program 1: Manual Operation
3-41
3 System Startup
3.2.3 Program Details
MPM running
Linear acceleration/deceleration setting
3-42
3.2 Sample Program 1: Manual Operation
3-43
3 System Startup
3.2.3 Program Details
3-44
3.2 Sample Program 1: Manual Operation
3-45
3 System Startup
3.2.3 Program Details
3-46
3.3 Sample Program 2: Positioning Control
Servomotor
3
X-Y plotter
Text-format
High-speed scan program
• This program is solely for the purpose of describing the MP2200 system startup. Care must be taken
IMPORTANT
because actual applications will differ.
• This program has no power OFF circuit for the SERVOPACK in the event of emergency stops or overtravel.
Include a proper emergency stop circuit in actual applications.
3-47
3 System Startup
3.3.2 Operation
3.3.2 Operation
(1) Tuning Panel
1. Use the Tuning Panel Window for the H04 drawing to check operations, just as described in 3.2.2 Opera-
tion. Right-click the H04 drawing in the High Scan Programs Folder and select Open - Tuning Panel.
2. The Tuning Panel Window for the H04 drawing will be displayed.
The details on the Tuning Panel Window display are shown in the following table.
Display
No. Data Name S Current Value Units Lower Limit Upper Limit REG-No. DWG
Definition
1 ***************Common monitor*************** XXXXX 00000 00000 32767 DL00010 L
2 Axis 1 operation ready ON/OFF ON IB80000
3 Axis 2 operation ready ON/OFF ON IB80800
4 Axis 1 current position XXXXXXXXXX 0000000000 −2147483648 2147483647 IL8016
5 Axis 2 current position XXXXXXXXXX 0000000000 −2147483648 2147483647 IL8096
6 ***************Common operation*************** XXXXX 00000 00000 32767 DW00010 L
7 Servo ON PB S ON/OFF OFF MB300000
8 Alarm reset PB S ON/OFF OFF MB300001
9 *********Positioning operation and settings********* XXXXX 00000 00000 32767 DW00010 L
10 Start positioning S ON/OFF OFF DB000010 H04
11 Hold positioning S ON/OFF OFF DB000011 H04
12 Abort positioning S ON/OFF OFF DB000010 H04
13 Motion program No. setting S XXX 001 001 003 DW00030 H04
14 1st target position (X axis) S XXXXXXXXXX 0000010000 −2147483648 2147483647 DL00010 H04
15 1st target position (Y axis) S XXXXXXXXXX 0000020000 −2147483648 2147483647 DL00012 H04
16 2nd target position (X axis) S XXXXXXXXXX 0000040000 −2147483648 2147483647 DL00014 H04
17 2nd target position (Y axis) S XXXXXXXXXX 0000060000 −2147483648 2147483647 DL00016 H04
18 MPM running ON/OFF OFF MB300020
19 MPM alarm ON/OFF OFF MB300028
3-48
3.3 Sample Program 2: Positioning Control
Positioning starts.
The process for confirming operation will be explained based on the above flowchart.
1. Switching between Servo ON and Servo OFF
Change the current value setting for Servo ON PB from OFF to ON on the Tuning Panel Window. The
Servomotor will turn ON and the Servo will be clamped.
3
2. Setting Motion Program Number
Change the current value setting for Motion Program No. Setting to a value between 1 and 3 on the Tun-
ing Panel Window. This sets the motion program number that will be executed. No programs have been
created for numbers 4 onwards, so an MPM alarm will occur if a number other than 1 to 3 is entered.
3. Entering Target Values for Each Axis
Enter any value for the current value for the items listed below. The values entered here will be the posi-
tioning target values when motion program numbers 2 and 3 are executed.
• 1st target value (X axis)
• 1st target value (Y axis)
• 2nd target value (X axis)
• 2nd target value (Y axis)
4. Starting Positioning
Set the current value for Start Positioning to ON on the Tuning Panel Window. Positioning will start based
on the motion program number set earlier (MPM No.). After positioning has been executed, change the
current value to OFF.
5. Confirming Motion Program Operation
When a motion program is started, the current value for MPM Running on the Tuning Panel Window will
change to ON. And when the Servo axis rotates, the values for the current position on the Tuning Panel
Window change.
If an error occurs during execution of a motion program, the current value for MPM Alarm on the Tuning
IMPORTANT
Panel Window will change to ON. Use the following procedure to clear the alarm.
1. Change the current value for Abort of Positioning to ON and then to OFF.
2. Change the current value for Alarm Reset PB to ON and then to OFF.
3-49
3 System Startup
3.3.3 Program Details
MPM number
MPM***execution
3-50
3.3 Sample Program 2: Positioning Control
3
(3) Motion Programs MPM002 and MPM003
Motion programs MPM002 and MPM003 are text-format programs that are started by the MSEE instruction
(motion program call instruction) in the H04 drawing.
EXAMPLE
In this example, motion programs MPM002 and MPM003 perform 2-axis positioning and interpolation.
MPM002 has timer commands in between each travel command to provide clear delimits for each operation.
MPM003 is MPM002 without the timer commands, so that the travel commands are executed continuously.
YESAMPLE PRG. MPM002 MP text
3-51
3 System Startup
3.4.1 Description
Previous New
method method
Controller Line shaft drive motor
Line shaft
MP2200
Gear
Driver
Clutch
Differential gear
SERVO-
Phase synchronization PACK
mechanism
Servo-
motor
Motor
Moving section
Phase control
SEE SEE Electronic shaft
Name H06 Name H06.01 • Axis 1
• Axis 2
High-speed scan
• This program is solely for the purpose of describing the MP2200 system startup. Care must be taken
IMPORTANT
because actual applications will differ.
• This program has no power OFF circuit for the SERVOPACK in the event of emergency stops or overtravel.
Include a proper emergency stop circuit in actual applications.
3-52
3.4 Sample Program 3: Phase Control with an Electronic Shaft
3.4.2 Operation
(1) Tuning Panel
1. Use the Tuning Panel Window for the H06 drawing to check operations, just as described in 3.2.2 Opera-
tion. Right-click the H06 drawing in the High Scan Programs Folder and select Open - Tuning Panel.
2. The Tuning Panel Window for the H06 drawing will be displayed.
The details on the Tuning Panel Window display are shown in the following table.
Display Current
No. Data Name S Units Lower Limit Upper Limit REG-No. DWG
Definition Value
1 ***************Common monitor*************** XXXXX 00000 00000 32767 DW00010 L
2 Axis 1 operation ready ON/OFF ON IB80000
3 Axis 2 operation ready ON/OFF ON IB80800
4 Axis 1 current position XXXXXXXXXX 0000000000 −2147483648 2147483647 IL8016
5 Axis 2 current position XXXXXXXXXX 0000000000 −2147483648 2147483647 IL8096
6 ***************Common operation*************** XXXXX 00000 00000 32767 DW00010 L
7 Servo ON PB S ON/OFF OFF MB300000
8 Alarm reset PB S ON/OFF OFF MB300001
9 *************Phase control (Electronic shaft)************* XXXXX 00000 00000 32767 DW00010 L
10 Electronic shaft start S ON/OFF OFF DB000010 H06.01
11 Speed setting (motor rated speed: 30000 mm/min) S XXXXXX 000000 mm/min −030000 030000 DL00010 H06.02
12 *************Phase control (Electronic cam)************* XXXXX 0000 0000 32767 DW00010 L
13 Electronic cam start S ON/OFF OFF DB000010 H06.02
Main axis speed setting (motor rated speed:
14 S XXXXXX 00000 mm/min 00000 030000 DL00010 H06.01
30000 mm/min)
15 Cam axis: amplitude setting (double amplitude) S XXX.XXX 010.000 mm 000.000 999.999 ML30200
16 Cam axis: main axis moving amount per cycle S XXXXX.XXX 00500.000 mm 00000.000 50000.000 ML30202
3-53
3 System Startup
3.4.2 Operation
Confirm operation.
The process for confirming operation will be explained based on the above procedure.
1. Switching between Servo ON and Servo OFF
Change the current value setting for Servo ON PB from OFF to ON on the Tuning Panel Window. The
Servomotor will turn ON and the Servo will be clamped.
2. Starting the Electronic Shaft
Change the current value for Electronic Shaft Start to ON in the Tuning Panel Window. The mode will
change to Phase Control (Electronic Shaft) Mode. Change the current value to OFF to exit Phase Control
(Electronic Shaft) Mode.
3. Entering Speed Settings
Change the current value for the Speed Setting (Motor Rated Speed) in the Tuning Panel Window to any
value between 0 and 30000. The value set will be the synchronous speed for both axes and the axes will
start rotating.
3-54
3.4 Sample Program 3: Phase Control with an Electronic Shaft
Electronic shaft
operation reference Axis 1 motion command 0 Axis 1 motion command 0 Electronic shaft start
Electronic shaft
operation reference Zero speed Electronic shaft stop
3-55
3 System Startup
3.4.3 Program Details
Zero speed
3-56
3.5 Sample Program 4: Phase Control with an Electronic Cam
Previous New
method method
Controller Line shaft drive motor
Line shaft
MP2200
Gear
Driver
Clutch
Differential
gear SERVO-
Phase synchronization
PACK
Transmis-
3
mechanism sion
Cam Servo-
motor
Motor
Ball
screw
Moving section
Phase control
SEE SEE Electronic shaft
Name H06 Name H0602 • Axis 1
Electronic cam
• Axis 2
High-speed scan
• This program is solely for the purpose of describing the MP2200 system startup. Care must be taken
IMPORTANT
because actual applications will differ.
• This program has no power OFF circuit for the SERVOPACK in the event of emergency stops or overtravel.
Include a proper emergency stop circuit in actual applications.
3-57
3 System Startup
3.5.2 Operation
3.5.2 Operation
(1) Tuning Panel
1. Use the Tuning Panel Window for the H06 drawing to check operations, just as described in 3.4.2 Opera-
tion. Right-click the H06 drawing in the High Scan Programs Folder and select Open - Tuning Panel.
2. The Tuning Panel Window for the H06 drawing will be displayed.
The details on the Tuning Panel Window display are shown in the following table.
Display Current
No. Data Name S Units Lower Limit Upper Limit REG-No. DWG
Definition Value
1 ***************Common monitor*************** XXXXX 00000 00000 32767 DW00010 L
2 Axis 1 operation ready ON/OFF ON IB80000
3 Axis 2 operation ready ON/OFF ON IB80800
4 Axis 1 current position XXXXXXXXXX 0000000000 −2147483648 2147483647 IL8016
5 Axis 2 current position XXXXXXXXXX 0000000000 −2147483648 2147483647 IL8096
6 ***************Common operation*************** XXXXX 00000 00000 32767 DW00010 L
7 Servo ON PB S ON/OFF OFF MB300000
8 Alarm reset PB S ON/OFF OFF MB300001
9 ************Phase control (electronic shaft))************ XXXXX 00000 00000 32767 DW00010 L
10 Electronic shaft start S ON/OFF OFF DB000010 H06.01
11 Speed setting (motor rated speed: 30000 mm/min) S XXXXXX 000000 mm/min −030000 030000 DL00010 H06.02
12 *************Phase control (electronic cam)************* XXXXX 0000 0000 32767 DW00010 L
13 Electronic cam start S ON/OFF OFF DB000010 H06.02
Main axis speed setting (motor rated speed:
14 S XXXXXX 00000 mm/min 00000 030000 DL00010 H06.01
30000 mm/min)
15 Cam axis: amplitude setting (double amplitude) S XXX.XXX 010.000 mm 000.000 999.999 ML30200
16 Cam axis: main axis moving amount per cycle S XXXXX.XXX 00500.000 mm 00000.000 50000.000 ML30202
3-58
3.5 Sample Program 4: Phase Control with an Electronic Cam
Confirm operation.
The process for confirming operation will be explained based on the above procedure.
1. Switching between Servo ON and Servo OFF
Change the current value setting for Servo ON PB from OFF to ON on the Tuning Panel Window. The
Servomotor will turn ON and the Servo will be clamped.
3
2. Entering Cam Data
Enter any value within the setting range for the Tuning Panel Window items listed below. The cam pattern
is generated from these settings. Cam pattern data is not changed, however, if the Electronic Cam Start
(described next) is set to ON.
• Cam axis amplitude setting (double amplitude) . . . . . Setting range: 0 to 999.999
• Cam axis main axis moving amount for one cycle . . . Setting range: 0 to 50000.000
3. Starting Electronic Cam Operation
Change the current value for Electronic Cam Start to ON in the Tuning Panel Window. The second axis
will enter Phase Control (Electronic Cam) Mode. Change the current value to OFF to exit the Phase Con-
trol (Electronic Cam) Mode.
4. Entering Main Axis Speed Settings
Change the current value for the Main Axis Speed Setting in the Tuning Panel Window to any value
between −30000 to 30000. The value set will be the master axis speed and the axis operation will start.
3-59
3 System Startup
3.5.3 Program Details
Operation reference Axis 1 motion command 0 Axis 1 motion command 0 Electronic cam start
########## Slave axis phase generation calculation disabled (Electronic Cam Mode) ########## Axis 2 phase
Operation reference generation disabled
Cam operation
Zero speed reference
3-60
3.5 Sample Program 4: Phase Control with an Electronic Cam
Operation reference
Linear accelerator/decelerator input
Operation reference
Axis 1 speed reference setting
Zero speed
3
########## Slave axis control circuit ##########
########## Electronic cam phase generation ##########
Cam operation reference
Electronic cam phase
Cycle detection
3-61
3 System Startup
3.5.3 Program Details
Forward detection
Electronic cam phase
Reverse detection
Electronic cam phase
3-62
3.5 Sample Program 4: Phase Control with an Electronic Cam
(2) L Drawing
The L parent drawing is in the low-speed scan and controls the overall sample program.
Main Program Low-speed Main Program
########## Low-speed main program ##########
Phase (deg)
3-63
4
Module Specifications
This chapter explains detailed specifications for the Basic Unit and Optional Modules of the
MP2200.
4-1
4 Module Specifications
4-2
4.1 General Specifications
4-3
4 Module Specifications
4.1.2 Function List
4-4
4.2 Base Unit
MP2200 MBU-01
POWER
BATTEY
4
100/200V
AC
MP2200 MBU-02
POWER
BATTEY
DC 0
(2) Indicator
The LED indicator that displays the status of the power supply is detailed in the following table.
Indicator
Indicator Color Significance when Lit
Name
Green The power supply is operating nor-
POWER POWER
mally.
4-5
4 Module Specifications
4.2.3 Hardware Specifications
4-6
4.3 CPU-01 Module
LED indicators
CPU-01
DIP switch RDY RUN
ALM ERR
BAT
STOP
SUP
INIT
CNFG
MON
TEST
SW1
OFF ON
(2) Indicators
The LED indicators that display the operating status and error details for the Base Unit are detailed in the follow-
ing table.
Indicator
Indicators Color Significance when Lit
Name
RDY Green Unit operating normally.
RDY RUN
RUN Green User program running.
ALM ERR ALM Red Lights/blinks for warning.
BAT ERR Red Lights/blinks for failures.
BAT Red Battery alarm occurred.
Note: Refer to (2) Indicator Details in 8.1.3 Indicator Errors for details on the meaning of indicators.
4-7
4 Module Specifications
4.3.2 LED Indicators and Switch Settings
STOP
SUP
INIT
CNFG
MON
SW1
TEST
OFF ON
4-8
4.3 CPU-01 Module
Item Specifications
Name CPU-01 Module
Model JAPMC-CP2200
Abbreviation CPU-01
Flash Memory 12 Mbytes
SDRAM 32 Mbytes
512 Kbytes, M registers, S registers, trace memory, alarm history
SRAM
(battery backup)
Calendar Seconds to year timer (battery backup)
Self-diagnostic Mode (factory test switch)
Watchdog timer
Protective Functions
Software: SH4 internal WDT
Hardware: 0 to 510 ms (register setting)
Reset output for power failure detection signal (POKH) after
Reset Circuit
NMI generation.
RDY (green)
RUN (green) 4
ALM (red)
Indicators
ERR (red)
TX (green)
BAT (red)
STOP
SUP
INIT
Switches
CNFG
MON
TEST
Dimensions (mm) 125 × 95 (H × D)
Mass 90 g
4-9
4 Module Specifications
4.3.4 Functions and Specifications
Operation
Performance 2.0 1.0 to 1.1 1.0 −
Ratio
32 MB (SDRAM)
RAM Size SDRAM 2/4 MB −
512 Kb (SRAM backup)
512 Kb (SRAM backup)
Flash Memory 12 MB (4 MB firmware; 8 MB
8 MB 2/4 MB −
Size user area)
Shared Memo-
ry (Computer None None None −
Interface)
User Memory 8 MB 6 MB Same as MP2300 −
Average: 50 bytes/
Language Memory Load Capacity
4-10
4.3 CPU-01 Module
(cont’d)
Item MP2200 MP2300 MP920 Remarks
MP2200 does not
Trace
Motion
Approx. 70 Same as MP2200 Same as MP2200 −
Language
Being considered for develop-
C language Same as MP2200 Not supported −
ment.
Motion API
(Provided by Approx. 150 Same as MP2200 Not supported −
System)
User Functions
(Created by 500 Same as MP2200 Same as MP2200 −
User)
Subscript
Supported Same as MP2200 Same as MP2200 −
(CP Ladders)
4-11
4 Module Specifications
4.3.4 Functions and Specifications
(cont’d)
Item MP2200 MP2300 MP920 Remarks
Servo tuning must be
Engineering Functions
4-12
4.4 SVB-01 Module
MECHATROLINK
SERVOPACK
Position
User application
references
Position control
Ladder or
motion Speed
references Speed control
programs
Torque Torque control SERVOPACK
references
Phase control
Phase
references
4
4.4.2 LED Indicators and Switch Settings
(1) External Appearance
The following figure shows the external appearance of the SVB-01 Module.
LED indicators
Rotary switches TX
MECHATROLINK
connector M-I/II
CN1
MECHATROLINK
connector
CN2
(2) Indicators
The following table shows the indicators that show the operating status of the SVB-01 Module and error infor-
mation.
Indicator
Indicators Color Significance when Lit
Name
Lights during normal operation of the
RUN Green microprocessor used for control.
RUN ERR
Not lit during error.
TX
Lights/blinks for failures.
ERR Red
Not lit during normal operation.
MECHATROLINK transmission in
TX Green
progress.
4-13
4 Module Specifications
4.4.2 LED Indicators and Switch Settings
M/S
SIZE
SPD
OFF ON
Default
Name Status Operating Mode Details
Setting
ON Reserved OFF
− Not used.
OFF Reserved
ON Slave Mode OFF
M/S Select Master or Slave Mode.
OFF Master Mode
ON 17 bytes OFF
SIZE Select the number of transfer bytes.
OFF 32 bytes
ON 4 Mbps OFF
SPD Select the baud rate.
OFF 10 Mbps
10
Default
Name Status Operating Mode Details
Setting
Local station address when in Slave Sets the 10s digit of the local slave
×10 0 to 9 0
Mode (10s digit) address.
Local station address when in Slave Sets the 1s digit of the local slave
×1 0 to 9 1
Mode (1s digit) address.
4-14
4.4 SVB-01 Module
4-15
4 Module Specifications
4.4.4 Function Lists
Item Details
Number of Communication
MECHATROLINK communication
1 line
Lines
Number of Communication
2 ports
Ports (Connectors)
Terminating Resistance JEPMC-W6022 Terminator must be purchased separately.
MECHATROLINK-II: Total Network length of 50 m, minimum distance between
stations of 0.5 m
Transmission Distance
MECHATROLINK-I: Total Network length of 50 m, minimum distance between
stations of 0.3 m
MECHATROLINK-II MECHATROLINK-I
Master Functions
Communication Interface −
(2:N asynchronous) (1:N asynchronous)
Baud Rate 10 Mbps 4 Mbps −
0.5 ms, 1 ms, 1.5 ms, or
Communication Cycle 2 ms −
2 ms
Number of Link Commu-
17 bytes or 32 bytes 17 bytes −
nication Bytes
Messaging (Slave Func-
Supported Not supported. −
tion)
4-16
4.4 SVB-01 Module
(cont’d)
Item Details
Single transmission (communication cycle = transmission cycle) synchronous com-
Servo Control
munication
Communication Method Transmission/communication error detection (hardware) provided.
Synchronous communication error detection (software) provided.
Automatic recovery function not provided (recovery when alarm cleared).
I/O Registers Input/output using motion registers (synchronized on high-speed scan)
Command Mode Motion Command Mode/MECHATROLINK Transparent Command Mode
Supported Servomotors Standard motors, linear motors, and DD motors
Control Type Position control, speed control, torque control, and phase control
Positioning, External Positioning, Zero Point Return, Interpolation, Interpolation
Motion Commands with Position Detection, Fixed Speed Feed, Fixed Length Feed, Speed Reference*,
Torque Reference*, Phase Control*, etc.
Acceleration/Deceleration One-step asymmetric trapezoidal acceleration/deceleration, exponential accelera-
Method tion/deceleration filter, moving average filter
Position Unit pulse, mm, inch, degree
Speed Unit Reference units/s, 10n reference units/min, percentage of rated speed
Acceleration Unit Reference units/s2, ms (acceleration from 0 until rated speed reached)
Torque Unit Percentage of rated torque 4
Electronic Gear Supported
Finite length position control, infinite length position control, absolute system infi-
Position Control Method nite length position control, and simple absolute system infinite length position con-
trol
Software limit Positive/negative direction for each point
Zero Point Return Method 13 types
Servo Parameter
Parameters can be managed in the MPE720’s SERVOPACK Parameter Window.
Management
Single transmission (communication cycle = transmission cycle) asynchronous com-
Inverter Control
munication
Communication Method Transmission/communication error detection (hardware) provided.
Synchronous communication error detection not provided.
Automatic recovery function provided.
Input/output using motion registers (synchronized on high-speed scan)
I/O Registers
CP-216 communication: Input/Output using I/O registers
Command Mode Motion Command Mode/MECHATROLINK Transparent Command Mode
Speed control only (V/F, vector control and other control methods use inverter set-
Control Type
tings)
Motion Commands Inverter I/O control, etc.
Speed Unit The speed unit depends on the inverter settings.
Inverter Parameter
Parameters can be managed in the MPE720’s Inverter Parameter Window.
Management
Single transmission (communication cycle = transmission cycle) asynchronous com-
I/O Control
munication
Communication Method Transmission/communication error detection (hardware) provided.
Synchronous communication error detection not provided.
Automatic recovery function provided.
Input/output using I/O registers and synchronized on the high-speed scan or low-
I/O Registers
speed scan (selectable).
Self-configuration Function Module and slave devices can be automatically allocated.
Synchronization supported (enabled when power is cycled) when high-speed scan
Synchronization between Modules
cycle = communication cycle times n
* Only with MECHATROLINK-II
4-17
4 Module Specifications
4.5.1 Outline of Functions
Servo connector
• Torque reference Torque reference monitor
• Phase control
• Zero point return Pulse inputs: Phases A, B, and C (5-V differential)
Monitor Functions Six general-purpose digital inputs (2 latch inputs)
Six general-purpose digital outputs
System bus connector
CN2
System bus
above.
Same
Interfaces Same as above.
as
Servo parameters
OW CN3
IW
LED indicators
SVA-01
RUN ERR
CH1
Servo connectors
CH2
+24V
ON
DC IN
(2) Indicators
The following table shows the indicators that show the operating status of the SVA-01 Module and error informa-
tion.
Indicators Indicator Name Color Significance When Lit
Lights when control microprocessor is operating normally.
RUN Green
Not lit during error.
RUN ERR
Lights/blinks for failures.
ERR Red
Not lit during normal operation.
4-18
4.5 SVA-01 Module
4-19
4 Module Specifications
4.5.4 Function Lists
Item Details
According to the torque unit selection parame-
Control functions
Torque Reference
Torque Reference (Open Loop) ter.
Speed Limit at Torque Reference Rated speed percentage designation [0.01%]
According to the speed unit selection parame-
Speed Reference
ter.
According to the acceleration unit selection
Acceleration
parameter.
According to the acceleration unit selection
Deceleration
parameter.
Speed Reference (Open Loop)
Moving Average Filter Time Con-
ms
stant Setting
According to the torque unit selection parame-
Torque Limits
ter.
Positive Speed Limit Rated speed percentage designation [0.01%]
Negative Speed Limit Rated speed percentage designation [0.01%]
Position References mm, inch, deg, pulse
According to the speed unit selection parame-
Speed References
ter.
According to the acceleration unit selection
Acceleration
parameter.
According to the acceleration unit selection
Deceleration
parameter.
Moving average or exponential acceleration/
Filter Type
deceleration
Filter Time Constant ms
Position Control Position Compensation mm, inch, deg, pulse
According to the speed unit selection parame-
Speed Compensation
ter.
Position Loop Gain 1/s
Position Loop Integration Time
ms
Constant
Speed Feed Forward Compensation Position derivative percentage designation
Primary Delay Time Constant ms
Torque Limit Rated torque percentage designation [0.01%]
Positive Speed Limit Rated speed percentage designation [0.01%]
Negative Speed Limit Rated speed percentage designation [0.01%]
According to the speed unit selection parame-
Speed References
ter.
According to the speed unit selection parame-
Speed Compensation
ter.
Phase Compensation mm, inch, deg, pulse
Phase Control Phase Control Proportional Gain Same as position loop gain parameter.
Phase Control Integral Time Con- Same as position loop integral time constant
stant parameter.
Torque Limit Rated torque percentage designation [0.01%]
Positive Speed Limit Rated speed percentage designation [0.01%]
Negative Speed Limit Rated speed percentage designation [0.01%]
4-20
4.5 SVA-01 Module
(cont’d)
Item Details
Positioning, external positioning, zero point return, interpolation, interpolation with
Motion Functions
Motion Commands position detection function, JOG operation, STEP operation, speed references, torque
references, phase control, etc.
Acceleration/Deceleration 1-step asymmetrical trapezoidal acceleration/deceleration, exponential acceleration/
Method deceleration filter, moving average filter
Position Units pulse, mm, inch, degree
Speed Units Reference unit/s, 10n reference unit/min, rated speed percentage designation
Acceleration Units Reference unit/s2, ms (acceleration time from 0 to rated speed)
Torque Units Rated torque percentage designation
Electronic Gear Yes
Finite length position control, infinite length position control, absolute infinite length
Position Control Method
position control, simple absolute infinite length position control
Software Limits 1 each in forward and reverse directions
Home Return Types 17
Latch Function Phase-C latch, external signal input latch
Self-configuration Function Automatic allocation by Module is supported.
4-21
4 Module Specifications
4.6.1 Outline of Functions
Interrupt
input
16 points
DI-00
Input Input port
processing (isolated DI)
DI-01
Latch 5-V/12-V
I/O connector
Z input
System bus
input
Pulse input
processing 5-V differential
Coinci- A/B input
dence
output
Coinci-
dence in-
terrupt
DO-00
16 points
Output port
Output (isolated DI)
(sink mode
processing outputs)
Switch
I/O connector
4-22
4.6 LIO-01 Module
7
LD1 LD5
8
9
6
LD2 LD6
0
5
LD3 LD7
1
3
4
LD4 LD8 2
Indicators SW1
4-23
4 Module Specifications
4.6.3 Hardware Specifications
4-24
4.7 LIO-02 Module
Interrupt
input
16 points
DI-00
Input Input port
processing (isolated DI)
DI-01
I/O connector
Latch 5-V/12-V
System bus
input Z input
Pulse input
processing 5-V differential
Coinci- A/B input
dence
output
Coinci-
dence in-
terrupt DO-00
Output
16 points
Output port
(isolated DO)
4
(source mode
processing output)
Switch
I/O connector
4-25
4 Module Specifications
4.7.2 LED Indicators and Switch Settings
7
LD1 LD5
8
9
6
LD2 LD6
0
5
LD3 LD7
1
3
4
LD4 LD8 2
Indicators SW1
4-26
4.7 LIO-02 Module
4-27
4 Module Specifications
4.8.1 Outline of Functions
I/O
Counter Monitor Information from LIO-01 or connector
Parameters (32 words) LIO-02 Module to MP2200
• Operation status
• Incremental pulse 5-V
• Current counter value differential
• Latch data, etc. interface
4-28
4.8 LIO-01 and LIO-02 Module Counter Functions
4-29
4 Module Specifications
4.8.2 Counter Function Details
n2 Count preset*2
0
n6
n1
n7
n4 n5
(−)
MIN MIN
(80000000H) (80000000H)
A or B pulse UP Stop UP DOWN UP Stop DOWN Stop DOWN
Ts
Current count n1 n2 n3 n4 n5 n6 n7
value*1
Ts: Scan setting
4-30
4.8 LIO-01 and LIO-02 Module Counter Functions
(+)
COINDATA
Counter counting register
(−)
COINDAT
4
Coincidence point
detection*1
Coincidence detection
request*2
Coincidence output
signal
T1
Interrupt reception 4
• Coincidence output signal uses DO-00. Therefore, DO-00 will be masked when 1 is set to fixed parameter
IMPORTANT
No. 9 (Coincidence Detection Function Selection). Actual signal outputs are not affected even if the register
allocated to DO-00 is turned ON or OFF from the ladder program.
• Use counter status (IW + 0 Bit5) to monitor coincidence detection signal outputs.
4-31
4 Module Specifications
4.8.2 Counter Function Details
PINT
Counter counting register
Hardware latch
(−)
PI latch detection
request*1
1 µs min.
External signal
or phase Z
PI latch completed
signal
4-32
4.8 LIO-01 and LIO-02 Module Counter Functions
(2) Settings
Use steps 1 to 5 in the following procedure to make the settings.
1. Confirm the machine specifications.
2. Confirm the number of encoder pulses input to the counter and set this value to the counter fixed parame-
ter No. 24 (Number of Pulses Per Encoder Rotation).
3. Decide the reference unit.
The reference unit is the smallest unit for the position data that moves the load. (The smallest reference
unit used by the host device.)
Moving a table in 0.001-mm
increments.
Reference unit: 0.001 mm
EXAMPLE
• When reference unit is 0.01 mm, 0.001 mm, 0.1°, or 0.01 inches:
The workpiece is moved 1 reference unit per pulse reference input.
• When reference unit is 1 µm:
When 50,000 reference pulses are input, the workpiece will be moved by 50,000 × 1 µm = 50 mm.
4-33
4 Module Specifications
4.8.3 Electronic Gear Function
4. Find the load travel distance for each rotation of the load axis using the reference unit.
EXAMPLE
• For a ball screw pitch of 5 mm and a reference unit of 0.001 mm:
5
= 5000 (Reference unit)
0.001
D
P: pitch D: Pulley diameter
Load axis
P 360
1 rotation = 1 rotation = πD
Reference unit 1 rotation =
Reference unit Reference unit
5. Set the Encoder Gear Ratio and the Machine Gear Ratio in the counter fixed parameters No. 20 and No.
21.
• No. 18 setting range: 1 to 231-1 [1 = 1 reference unit]
EXAMPLE
Setting Examples
• Load moving amount per load axis rotation = 12 mm
• Smallest reference unit = 0.001 mm (reference unit: mm, to 3 decimal places)
Counter fixed parameter No. 18 = 12 mm/0.001 mm = 12000
• When the encoder axis has rotated m times and the mechanical configuration allows the load axis to
rotate n times, set the following values:
Counter fixed parameter No. 20 = m rotations
Counter fixed parameter No. 21 = n rotations
Setting range: 1 to 65,535 [rotations]
• For the configuration shown in the diagram:
4 rotations
7 rotations
9 rotations
3 rotations
4-34
4.8 LIO-01 and LIO-02 Module Counter Functions
5 rotations
n
Ball screw pitch P =
6 mm/rotation
In the above machine system, if the requirement is reference unit = output unit = 0.001 mm, the setting of
each parameter will be as follows:
• No. 18 = 6 mm/0.001 mm = 6000
• Gear ratio = n/m = 5/7
• No. 20 = 7
• No. 21 = 5
10
rotations
Rotating load
360°/rotation
In the above machine system, if the requirement is reference unit = output unit = 0.1°, the setting of each
parameter will be as follows:
• No. 18 = 360°/0.1° = 3600
• Gear ratio = n/m = 10/30 = 1/3
• No. 20 = 3
• No. 21 = 1
4-35
4 Module Specifications
4.8.3 Electronic Gear Function
* The reset position is set in the counter fixed parameter No. 22 (Infinite Length Axis Reset Position) (POSMAX).
POSMAX
4-36
4.8 LIO-01 and LIO-02 Module Counter Functions
4-37
4 Module Specifications
4.8.4 Counter Parameters
Coincidence Detection
Setting (COINDAT)
OL+004 −231 to 231−1 1 = 1 reference unit
OL+008
Reserved to
OL+01C
System Monitor OL+0x1E −231 to 231−1 System use
4-38
4.8 LIO-01 and LIO-02 Module Counter Functions
4-39
4 Module Specifications
4.9.1 Outline of Functions
LED indicators
LIO-04
RUN FU
CN1
I/O connectors
CN2
(2) Indicators
The following table shows the status of LIO-04 Module LED indicators.
Indicator Indicator
Status
Name Color
Green Lit: Module normal
RUN FU RUN
Not lit: Module error
Red Lit: One of the output protection fuses is blown.
FU
Not lit: All of the output protection fuses are normal.
Note: The burnout detection circuit will not function when there is no external 24-V power supply.
4-40
4.9 LIO-04 Module
25
No. of ON inputs
20
15
10
0
0 10 20 30 40 50 60 (°C)
Ambient temperature
4-41
4 Module Specifications
4.10.1 Outline of Functions
DIP switch
Serial connector
(RS-232C)
Ethernet connector
(10Base-T)
4-42
4.10 218IF-01 Module
(2) Indicators
The following table shows the status of 218IF-01 Module LED indicators.
Indicator Color Status
Lit during normal operation.
RUN Green
Not lit during errors.
Lit/blinking during malfunctions.
ERR Red
Not lit during normal operation.
RUN ERR Lit during RS-232C data transmission or reception. Not lit
STRX Green
when data not being transmitted or received.
STRX COL
Ethernet collision status.
COL Red
TX RX Lit: Collision, Not lit: No collision
Ethernet transmission status. Lit during transmission.
TX Green
Not lit if data not being transmitted.
Ethernet reception status. Lit during reception.
RX Green
Not lit if data not being received.
Label Name
Sta-
tus
Function
Factory
Setting
4
For engineering communication. Starts up using
default parameters (excluding automatic reception
ON function settings.) Given higher priority than CPU
INIT INIT Initial Startup Module Flash Startup and Self-configuration Star- OFF
TEST tup.
OFF ON Set to OFF for CPU Module Flash Startup and Self-
OFF
configuration Startup.
ON System use
TEST TEST OFF
OFF Normal operation (Always leave turned OFF.)
4-43
4 Module Specifications
4.10.3 Hardware Specifications
4-44
4.11 217IF-01 Module
LED indicators
217IF-01
DIP switch
Serial connector
(RS-232C) 4
Serial connector
(RS-422/485)
(2) Indicators
The following table shows the status of 217IF-01 Module LED indicators.
Indicator Color Status
Lit during normal operation.
RUN Green
Not lit during errors.
Lit/blinking during malfunctions.
ERR Red
Not lit during normal operation.
RUN ERR
Lit during RS-232C (PORT) data transmission and
STRX TRX STRX Green reception. Not lit when data not being transmitted or
received.
Lit during RS-422/485 (RS-422/485) data transmis-
TRX Green sion and reception.
Not lit when data not being transmitted or received.
4-45
4 Module Specifications
4.11.2 LED Indicators and Switch Settings
4-46
4.11 217IF-01 Module
4-47
4 Module Specifications
4.12.1 Outline of Functions
LED indicators
260IF-01
Switches
Serial connector
(RS-232C)
DeviceNet connector
(2) Indicators
The following table shows the status of 260IF-01 Module LED indicators.
Indicator Color Status
Green Normal operation
MS
Red Module error
(two-color LED)
Not lit Module power supply disconnected
Green Normal operation
MS NS No I/O allocations while connection is being
Green blinking
established
NS
Red Error (Bus OFF, duplicated MAC ID)
(two-color LED)
STRX Red blinking Communication error
Communication power supply disconnected,
Not lit
checking for duplicated MAC ID
STRX Green lit/blinking Transmitting or receiving RS-232C data
(mounted on PCB) Not lit No RS-232C data communication
4-48
4.12 260IF-01 Module
TEST TEST
ON System use 4
OFF Normal operation (Always leave turned OFF.)
Node Address
×10 − Sets the node address. (Rotary decimal switch)
10s Digit Setting
Node Address
×1 − Sets the node address. (Rotary decimal switch)
1s Digit Setting
4-49
4 Module Specifications
4.12.3 Hardware Specifications
4-50
4.12 260IF-01 Module
4-51
4 Module Specifications
4.13.1 Outline of Functions
LED indicators
261IF-01
Switches
Serial connector
(RS-232C)
PROFIBUS
PROFIBUS connector
(2) Indicators
The following table shows the status of 261IF-01 Module LED indicators.
Indicator Color Status
Lit during normal operation.
RUN Green
Not lit during errors or during reset.
Lit/blinking during malfunctions.
RUN ERR
ERR Red
Not lit during normal operation. Lit during reset.
STRX TRX Lit during RS-232C data transmission or reception.
STRX Green
Not lit when data not being transmitted or received.
Lit during PROFIBUS data transmission or reception.
TRX Green
Not lit when data not being transmitted or received.
4-52
4.13 261IF-01 Module
4-53
4 Module Specifications
4.13.3 Hardware Specifications
4-54
4.13 261IF-01 Module
* 1. The PROFIBUS ID is 05C1.The GSD file YASK05C1.GSD is provided for master configuration.GSD
file: Defines slave information.
* 2. The PROFIBUS ID can be set between 0 and 125, but the 261IF-01 Module can be set only between 1
and 64.
4-55
4 Module Specifications
4.14.1 Outline of Functions
EXIOIF
External input connector
4-56
4.15 External Appearance
Unit: mm
M4 mounting screws (4)
240
(18) 108
4
(4.5)
(4.5) 231 4.5
MP2200 MBU-01 CPU-01 218IF-01 SVB-01 LIO-01 LIO-01 LIO-02 260IF-01 217IF-01
POWER
M- /
121
130
BATTEY CN1
100/200V DeviceNet
RS422/465
10Base-T
AC CN2
POWER
4.5
Cable Connector
(3P) 721-203/026-000
4-57
4 Module Specifications
4.15.2 Mounting Optional Module Connectors
(2) (2)
LIO-01 LIO-02
(45) (45)
(6) (6)
218IF-01 217IF-01
(45) (62)
(6) (6)
260IF-01 261IF-01
4-58
4.15 External Appearance
(41) (41)
(2) (2)
LIO-04 SVA-01
(36) (41)
EXIOIF SVB-01
4-59
5
Mounting and Wiring
This chapter explains how to handle the MP2200 and the connection methods for each Module.
5-1
5 Mounting and Wiring
5.1.1 Mounting the MP2200
PORT
Optional Module
Optional Module
M- /
BATTEY CN1
100/200V
10Base-T
AC CN2
POWER
Mounting base
DIN rail
5-2
5.1 Handling the MP2200
When mounting the MP2200 to a DIN rail with a 10-mm gap, insert spacers behind the MP2200 to protect
against vibration.
Spacer
DIN rail
(10-mm gap)
The parts for mounting the MP2200 to DIN rail are supplied separately. Purchase the following product when
IMPORTANT
using DIN rail.
Product name: DIN Rail Mounting Parts
Model No.: JEPMC-OP300
PORT
Optional Module
Optional Module
M- /
BATTEY CN1
100/200V
10Base-T
AC CN2
POWER
Clip
5-3
5 Mounting and Wiring
5.1.1 Mounting the MP2200
a)
b)
M- /
BATTEY CN1
100/200V
10Base-T
AC CN2
POWER
Clip
DIN rail
PORT
Optional Module
Optional Module
M- /
BATTEY CN1
100/200V
10Base-T
AC CN2
End plate
POWER
5-4
5.1 Handling the MP2200
(1) Preparations
1. Create a backup data file.
Use the MPE720 to save the MP2200 program on a computer.
2. Remove the MP2200.
Turn OFF the power supply and disconnect all cables from the MP2200. Then remove the MP2200 from
the panel or rack and place it on a workbench or other area with sufficient space.
5-5
5 Mounting and Wiring
5.1.2 Replacing and Adding Optional Modules
Notch
Round knob
Hold the center of the battery cover as shown in the following diagram. Push the battery cover down and
out, rotating from the round knob to disconnect the Module and mounting base connectors, and then pull
the Optional Module forward.
Fulcrum
Round knob
5-6
5.1 Handling the MP2200
Guide
rail
Guide rails are visible at the top and bottom of the Option Slot, as shown in the above diagram. Line up
the Module with the guide rail and insert the Module straight. The FG bar on the inside bottom of the Unit
Case may be damaged if the Module is not inserted straight.
2. Mount on to the mounting base.
Once the Optional Module has been completely inserted, place your hand on the front face of the Optional
Module and push hard until the Optional Module has been inserted into the mounting base connectors.
The front face of the Optional Module and the hook will be aligned when the Optional Module has been
installed properly.
3. Install the Optional Module panel. 5
Place the hole on the bottom of the panel of the Optional Module onto the hook on the bottom of the
MP2200.
Next, hook the hole at the top of the panel of the Optional Module onto the hook at the top of the MP2200.
5-7
5 Mounting and Wiring
5.2.1 Connecting Power Supply
MP2200
721-863
721-203/026
AC
Noise
AC input
filter
AC
FG
POWER
FG
Note: Use a noise filter on the AC power supply line to the MBU-01.
Recommended noise filter:
Manufacturer Model
TDK ZHG2210-11S
5-8
5.2 Module Connections
6.5 mm
2. First, insert an operation lever or flat-blade screwdriver into the opening and press it down as shown by
the arrows in the following diagrams to open the clamp in the plug. Insert the wire into the opening and
then close the opening by releasing the lever or removing the screwdriver.
Press down.
Press down with
a screwdriver.
Operation lever
or
INFO Always separate the primary and secondary wiring when using a noise filter.
5-9
5 Mounting and Wiring
5.2.1 Connecting Power Supply
Frame ground
FG
Ground to 100 Ω max.
MP2200
721-863
721-203/026
24 VDC 24 V
AC input 24-VDC
power 0V
supply 0V
POWER
FG
FG
Note: Use an insulated 24-VDC power supply. Attach the power supply switch on the AC side. If the switch
is attached on the 24-VDC side, there will be an inrush current of approximately 40 A when the
power is turned ON.
5-10
5.2 Module Connections
CN2
INFO • There are two connectors on the MECHATROLINK-I/MECHATROLINK-II, but the communication line supports only 5
one channel.
• If the SVB-01 Module is connected at the end of a network, connect a JEPMC-W6022 Terminator to the other connec-
tor.
• Both connectors perform the same function, so connections can be made to either.
5-11
5 Mounting and Wiring
5.2.2 SVB-01 Module Connections
(3) Cables
JEPMC-W6003-
JEPMC-W6010-
JEPMC-W6022
5-12
5.2 Module Connections
SVB-01
MP2200
MP2200 MBU-02 CPU-01 218IF-01 SVB-01
POWER
PORT
M- /
BATTEY CN1
Terminator
10Base-T
DC CN2
POWER
MECHATROLINK-
Terminator
SGDS-01A12A SGDS-01A12A
SW1 SW1
C C
N N
CHARGE 6 CHARGE 6
A/B A/B
L1 L1
L2 L2
5
L1C C L1C C
N N
JEPMC-IO2
310
L2C 3 L2C 3
B1/ B1/
VS mini V7
B2 B2
C C
U N U N
1 1
V V
W W
C C
N N
2 2
C C
N N
4 4
I/O
5-13
5 Mounting and Wiring
5.2.2 SVB-01 Module Connections
(b) Connecting the SVB-01 Module in the Middle of the MECHATROLINK Network
The following diagram shows a system configuration example.
SVB-01
MP2200
MP2200 MBU-02 CPU-01 218IF-01 SVB-01
POWER
PORT
M- /
BATTEY CN1
10Base-T
DC CN2
POWER
MECHATROLINK- MECHATROLINK-
Terminator Terminator
SGDS-01A12A SGDS-01A12A
SW1 SW1
C C
N N
CHARGE 6 CHARGE 6
A/B A/B
L1 L1
L2 L2
C C JEPMC-IO2310
L1C L1C
N N
L2C 3 L2C 3
C C
U N U N
1 1
V V
W W
C C
N N
2 2
C C
N N
4 4
I/O
5-14
5.2 Module Connections
(NC) 1 1 (NC)
DATA 2 2 /DATA
DATA 3 3 DATA
SH 4 4 SH
(b) Cable Connections between the SVB-01 and SGD-N and SGDB-AN
SERVOPACKs
Cable model number: JEPMC-W6011-
DATA 3 3 3 3
TERM
SH 4 4 TERM 4 TERM 4
Shield FG FG
Shell 5 5 5 FG
8 8 8
Note: 1. The JEPMC-6010- has a USB connector on one end and loose wires on the other end. Use an MR
connector and wiring material to create a 1:N cable.
2. The terminating resistance for SGD-N ,SGDB-AN must be provided by the user.
3. Prepare the cables according to following MECHATROLINK-I specifications. Connections that do
not meet the specifications will prevent normal communication due to the influence of reflected
waves or other factors.
Total network length: 50 m max.
Maximum number of slave stations: 14 stations max.
Minimum distance between stations: 0.3 m min.
5-15
5 Mounting and Wiring
5.2.2 SVB-01 Module Connections
/DATA 2
130 Ω
DATA 3
SH 4
Shield Shell
(d) Connection Example between the SVB-01, SERVOPACKs, and the IO2310
L1
PORT CN1
IN1 OUT1 IN2 OUT2
Optional Module
Optional Module
M- /
A1 B1 A1 B1 A1 B1 A1 B1
BATTEY CN1
100/200V
10Base-T
AC CN2
POWER
L1
L2 Ln
c
Terminator
5-16
5.2 Module Connections
CH1
PORT
M-I/II
CH2
BATTEY CN1
10Base-T
DC CN2
+24V
POWER
OV
DC IN
24-VDC
power
2 analog outputs/axis
supply
2 analog inputs/axis
1 pulse input/axis
5
SGDH-04EA SGDH-04EA
Two SERVOPACKs
Note: The customer must provide cables for the SGDA and SGDB SERVOPACKs.
5-17
5 Mounting and Wiring
5.2.3 SVA-01 Module Connections
Connector Model
Connector No. of Cable Model Num-
Name Manufac-
Name Pins Module side Cable side bers
turer
• Connector body:
10136-3000VE
Servo interface • Shell:
JEPMC-W2040-
connector 1 CN1 10336-52A0-008
36 10236-52A2JL 3M (For the SGDH/
and connector CN2 ÅiScrew lockingÅj
2
SGDM/SGDS)
10336-52F0-008
ÅiOne-touch
lockingÅj
The CN3 connector is
included with the SVA-
24-V input con- 01 Module, but a cable
CN3 2 • BL3.5/2F-AU Weidmuller
nector is not included. The
user must connect the
cable.
Core
6.5 mm
Sheath
5-18
5.2 Module Connections
5
17
35
18
36
5-19
5 Mounting and Wiring
5.2.3 SVA-01 Module Connections
The following figure shows the pin names and assignments for connectors CN1 and CN2.
Ground Ground
1 SG 19 SG
(analog) (For SEN signal)
General-purpose
AO_0 analog output 0 SEN SEN Signal
2 20
(NREF) (speed reference output) (5V) (Servo) General-purpose
5-V differential phase analog input 1
3 PA 21 AI_1
A pulse input (+) (Torque reference monitor
input)
4 PAL 5-V differential phase 22 − Not connected
A pulse input (−)
5-V differential phase 5-V differential phase
5 PC C pulse input (+) 23 PB
B pulse input (−)
5-V differential phase 5-V differential phase
6 PCL 24 PBL
C pulse input (−) B pulse input (−)
7 SG Ground 25 SG Ground
General-purpose
analog input 0
8 AI_0 26 AI-GND Analog input ground
(Feedback speed General-purpose
monitor input) AO_1 analog output 1 Analog output
9 27 AO-GND
(TREF) (torque reference output) ground
0V 0V
10 0 V (for 24 V) output 28 0 V (for 24 V) output
(For 24 V) (For 24 V)
0V 0V
11 0 V (for 24 V) output 29 0 V (for 24 V) output
(For 24 V)
General-purpose (For 24 V)
General-purpose
DO_2 output DO_2 DO_1 output DO_1
12 30
(PCON) (P action reference output) (ALMRST) (Alarm reset ouput)
General-purpose General-purpose
output DO_4 DO_0
13 DO_4 31 output DO_0
(SV ON)
DO_5 General-purpose (Servo ON output)
14 DO_3 General-purpose 32
output DO_3 (SEN) output DO_5
General-purpose (VS866 24-V SEN signal)
DI_3 input DI_3 DI_4 General-purpose
15 33 input DI_4
(P-OT) (positive overtravel input) (N-OT)
(Negative overtravel input)
16 +24V +24 V output 34 +24V +24 output
General-purpose
General-purpose
DI_0 input DI_0 DI_1
17 35 input DI_1
General-purpose (SVALM) (Servo alarm input) (SRDY)
DI_2 General-purpose (Servo delay input)
input DI_2 DI_5 input DI_5
18 (ZERO/ 36
(ZERO/HOME LS input) (EXT/DEC)
HOME LS) (EXT/DEC signal input)
Either 5 V or 24 V can be selected for the SEN signal. Connect pin 20 or pin 32 according to the application. Pin 20 (5 V)
INFO
is connected in the standard cable.
(f) Cables
The following standard cables are available for use with the SVA-01 Module. These cables are used to con-
nect the SVA-01 Module to SERVOPACKs, overtravel limit switches, and other machine connections.
5-20
5.2 Module Connections
SVA-01 SGDA
CN1/CN2 CN1
SG 1 2 SG
AO_0 (NREF) 2 3 V-REF
PA 3 20 PA
PAL 4 21 /PA
PC 5 24 PC
PCL 6 25 /PC
SG 7 4 SG
AI_0 (VMON) 8
AO_1 (TREF) 9 1 T-REF
0V (for 24V) 10 35 ALM-SG
0V (for 24V) 11
DO_2 (PCON) 12 15 /P-CON
DO_4
DO_3
13
14
11
12
/P-CL
/N-CL 5
DI_3 (P-OT) 15 16 P-OT
+24V 16 13 +24V IN
DI_0 (SVALM ) 17 34 ALM
DI_2 (ZERO/HOME LS) 18
SG 19 6 0 SEN
SEN (5V) 20 5 SEN
AI_1(TREFMON) 21
− 22
PB 23 22 PB
PBL 24 23 /PB
SG 25 10 SG-COM
AI-GND 26 7 /BK
AO-GND 27 19 SG
0V (for 24V) 28 29 BAT0
0V (for 24V) 29 28 BAT
DO_1 (ALMRST) 30 18 /ALM RST
DO_0 (SV ON) 31 14 /S-ON
DO_5 (SEN for VS866) 32
DI_4 (N-OT) 33 17 N-OT
+24V 34
DI_1 (SRDY) 35
DI_5 (EXT/DEC) 36
Hood FG FG Hood
P-OT input
Brake interlock output (+)
N-OT input
Brake interlock output (-)
5-21
5 Mounting and Wiring
5.2.3 SVA-01 Module Connections
5-22
5.2 Module Connections
AI_1
AI_2
NP:SVA GND NP:SERVOPAK
L
OTF BAT
OTR BAT0
EXT /BRK+
ZERO /BRK-
5
• Cable Specifications
Diagram
Name Model Qty Manufacturer Remarks
No.
c Plug on SVA end 10136-3000VE 1 Sumitomo 3M Soldered
d Shell on SVA end 10336-52A0-008 1 Sumitomo 3M
e Plug on Servo end 10150-3000VE 1 Sumitomo 3M Soldered
f Shell on Servo end 10350-52Z0-008 1 Sumitomo 3M
HP-SB/20276SR
g Cable − Taiyo Cable Shield wire
26 x AWG28
Sumitomo Electric
h Heat-shrinking tube F2 (Z) − Or equivalent
Industries. Ltd.
OTF: Brown
OTR: Orange
EXT: Black
ZERO:
BAT: Blue
i Wires UL1061 AWG28 − − BAT0: Purple
*BRK+: Gray
*BRK-: White
AI_1: White
AI_2: Red
GND: Black
5-23
5 Mounting and Wiring
5.2.3 SVA-01 Module Connections
5-24
5.2 Module Connections
5-25
5 Mounting and Wiring
5.2.4 LIO Module Connections
5-26
5.2 Module Connections
Vcc
+24 V
22 kΩ
DI_COM
Input register
680 Ω 0.01 µF
1 kΩ
5
2200 PF
DI_IN 5.6 kΩ/0.5 W
024
Vcc
+24 V
22 kΩ
DI_COM
Input register
1 kΩ
680 Ω 0.01 µF
2200 PF
DI_IN 5.6 kΩ/0.5 W
024
5-27
5 Mounting and Wiring
5.2.4 LIO Module Connections
+24 V
470 Ω
DO_24V
Output
register
DO_OUT
33 kΩ
DO_COM
33 kΩ
024
5-28
5.2 Module Connections
Pulse generator
+5 V
A1 PA Phase A
220 Ω B1 PAL
0V
A2 PB Phase B
220 Ω B2 PBL
A4 GND
+5 V
330 Ω A3 PC
Latch input or B3 PCL5
phase Z pulse
680 Ω B4 PCL12
5
Pulse Input Circuit
5-29
5 Mounting and Wiring
5.2.4 LIO Module Connections
220 Ω PAL
B1
0V
Pulse input
A2 PB Phase B
220 Ω PBL
B2
A4 GND
A24
+5 V
B24
5V
A3 PC
A23 DI_COM0
24 VDC
B23 DI_COM1
B15 DI_14
A16 DI_13
B16 DI_12
DI_11
B17 DI_10
A18 DI_09
B18 DI_08
A19 DI_07
B19 DI_06
A20 DI_05
B20 DI_04
A21 DI_03
B21 DI_02
A22 DI_01
B22 DI_00
B6 DO_24V
24 VDC
A6 DO_24V
A7 DO_15 Fuse
Digital outputs L
B7 DO_14
L
A8 DO_13
L
B8 DO_12
L
A9 DO_11
L
B9 DO_10
L
External output signals
A10 DO_09
L
B10 DO_08
L
A11 DO_07
L
B11 DO_06
L
A12 DO_05
L
B12 DO_04
L
A13 DO_03
L
B13 DO_02
L
A14 DO_01
L
B14 DO_00
L
Fuse A5 DO_COM
B5 DO_COM
Fuse blown
detection circuit
Note: Connect a fuse suitable for the load specifications in the output signal circuit in series with the load. If an
external fuse is not connected, load shorts or overloads could result in fire, destruction of the load device, or
damage to the output element.
5-30
5.2 Module Connections
(c) Cables
Name Model Length
JEPMC-W2061-A5 0.5 m 5
Cable for LIO Modules JEPMC-W2061-01 1m
JEPMC-W2061-03 3m
5-31
5 Mounting and Wiring
5.2.4 LIO Module Connections
5-32
5.2 Module Connections
Vcc
+24 V
22 kΩ
DI_COM
Input register
1 kΩ 5
680 Ω 0.01 µF
2200 PF
DI_IN 5.6 kΩ/0.5 W
024
Vcc
+24 V
22 kΩ
DI_COM
Input register
1 kΩ
680 Ω 0.01 µF
2200 PF
DI_IN 5.6 kΩ/0.5 W
024
5-33
5 Mounting and Wiring
5.2.4 LIO Module Connections
+24 V
33 kΩ
DO_24V
33 kΩ
470 Ω
Output
register
DO_OUT
DO_COM
024
5-34
5.2 Module Connections
Pulse generator
+5 V
A1 PA Phase A
220 Ω B1 PAL
0V
A2 PB Phase B
220 Ω B2 PBL
A4 GND
+5 V
330 Ω A3 PC
Latch input or B3 PCL5
phase-Z pulse
680 Ω B4 PCL12
5
Pulse Input Circuit
5-35
5 Mounting and Wiring
5.2.4 LIO Module Connections
220 Ω PAL
B1
0V
Pulse input
A2 PB Phase B
220 Ω PBL
B2
A4 GND
A24
+5 V
B24
5V
A3 PC
A23 DI_COM0
24 VDC
B23 DI_COM1
B15 DI_14
A16 DI_13
B16 DI_12
A17 DI_11
A18 DI_09
B18 DI_08
A19 DI_07
B19 DI_06
A20 DI_05
B20 DI_04
A21 DI_03
B21 DI_02
A22 DI_01
Fuse blown
detection circuit B22 DI_00
A7 DO_15 Fuse
L
B7 DO_14
L
A8 DO_13
L
B8 DO_12
L
A9 DO_11
L
External output signals
B9 DO_10
L
A10 DO_09
L
B10 DO_08
L
A11 DO_07
L
B11 DO_06
L
A12 DO_05
L
B12 DO_04
L
A13 DO_03
L
B13 DO_02
L
A14 DO_01
L
B14 DO_00
L
A5 DO_COM
B5 DO_COM
Note: Connect a fuse suitable for the load specifications in the output signal circuit in series with the load. If
an external fuse is not connected, load shorts or overloads could result in fire, destruction of the load
device, or damage to the output element.
5-36
5.2 Module Connections
Connector Model
Connector No. of
Name Manu- Cable Models
Name Pins Module side Cable side
facturer
CN1 50 • Connector body: 3M 5
10150-3000VE
• Shell:
External I/O 10350-52A0-008
10250-52A3JL JEPMC-W6060-
connector 1 (Screw locking)
10350-52F0-008
(One-touch
locking)
CN2 50 • Connector body: 3M
10150-3000VE
• Shell:
External I/O 10350-52A0-008
10250-52A3JL JEPMC-W6060-
connector 2 (Screw locking)
10350-52F0-008
(One-touch
locking)
5-37
5 Mounting and Wiring
5.2.5 LIO-04 Module Connections
• Cable Appearance
NP: JEPMC-W6060-05
50 cores,
loose wires
L 150
Body FG
5-38
5.2 Module Connections
50
25
49
24
27
2
26
1 COM-1 26 −
2 DI-00 27 DI-01
3 DI-02 28 DI-03
4 DI-04 29 DI-05
5 DI-06 30 DI-07
6 COM-2
7
31 −
32 DI-09
5
DI-08
8 DI-10 33 DI-11
9 34 DI-13
DI-12
10 DI-14 35 DI-15
11 − 36 −
12 DO-00 37 DO-01
13 38 DO-03
DI-02
14 − 39 0V-1
15 +24V-1 40 −
16 DO-04 41 DO-05
17 42 DO-07
DO-06
18 − 43 0V-1
19 44 DO-09
DO-08
20 DO-10 45 DO-11
21 − 46 0V-2
22 +24V-2 47 −
23 DO-12 48 DO-13
24 DO-14 49 DO-15
25 − 50 0V-2
5-39
5 Mounting and Wiring
5.2.5 LIO-04 Module Connections
The following figure shows the pin names and assignments for connector CN1.
5-40
5.2 Module Connections
50
25
49
24
27
2
26
1 COM-3 26 −
2 DI-16 27 DI-17
3 DI-18 28 DI-19
4 DI-20 29 DI-21
5 DI-22 30 DI-23
6 COM-4 31 −
7 DI-24 32 DI-25
8 DI-26 33 DI-27
9 DI-28 34 DI-29 5
10 DI-30 35 DI-31
11 − 36 −
12 DO-16 37 DO-17
13 38 DO-19
DI-18
14 − 39 0V-3
15 +24V-3 40 −
16 DO-20 41 DO-21
17 42 DO-23
DO-22
18 − 43 0V-3
19 44 DO-25
DO-24
20 DO-26 45 DO-27
21 − 46 0V-4
22 +24V-4 47 −
23 DO-28 48 DO-29
24 DO-30 49 DO-31
25 − 50 0V-4
5-41
5 Mounting and Wiring
5.2.5 LIO-04 Module Connections
The following figure shows the pin names and assignments for connector CN2.
5-42
5.2 Module Connections
* For details on the number of simultaneously ON points, refer to 4.9.3 Hardware Specifications.
5
Vcc
+24V
22 kΩ
DI_COM
Input register
22 KΩ
750 Ω
1000 PF
DI_IN 5.6 kΩ/0.5 W
024
024
5-43
5 Mounting and Wiring
5.2.5 LIO-04 Module Connections
+24V
470 Ω
DO_24V
Output
register
DO_OUT
33 kΩ
DO_COM
33 kΩ
024
5-44
5.2 Module Connections
24 VDC
Connector CN1
+ −
Pin No.
− + Common 1
1
Input 0 2
Input 1 27
.
.
. Input 6 5
Input 7 30
+5 V
24 VDC
+ -
Common 2
Internal circuits
- + 6 Photocoupler
Input 8 5.6 kΩ
7
Input 9 32 Fuse
12 Output 0
.
. 37 Output 1
L
5
L
. Input 14 10
13 Output 2
Input 15 35 L
38 Output 3
L
39
Photocoupler 24 VDC
15 + -
16 Output 4
L
41 Output 5
L
17 Output 6
L
42 Output 7
L
43
Fuse blown
detection circuit
19 Output 8
L
44 Output 9
L
20 Output 10
L
45 Output 11
L
46
24 VDC
22 + -
23 Output 12
L
48 Output 13
L
24 Output 14
L
49 Output 15
L
50
5-45
5 Mounting and Wiring
5.2.5 LIO-04 Module Connections
24 VDC
Connector CN2
+ − Pin No.
− + Common 3 1
Input 16 2
Input 17 27
.
.
. Input 22 5
Input 23 30
+5V
24 VDC
+ −
− + Common 4 6 Photocoupler
Internal circuits
Input 24 5.6 kΩ
7
Input 25 32 Fuse
12 Output 16
. L
. 37 Output 17
L
. Input 30 10
13 Output 18
Input 31 35 L
38 Output 19
L
39
Photocoupler 24 VDC
15 + −
16 Output 20
L
41 Output 21
L
17 Output 22
L
42 Output 23
L
43
Fuse blown
detection circuit
19 Output 24
L
44 Output 25
L
20 Output 26
L
45 Output 27
L
46
24 VDC
22 + −
23 Output 28
L
48 Output 29
L
24 Output 30
L
49 Output 31
L
50
5-46
5.2 Module Connections
PORT
10Base-T
RS-232C Ethernet
(3) Cables 5
Name Model Length
JEPMC-W5311-03 2.5 m
RS-232C Cable
JEPMC-W5311-15 15 m
5-47
5 Mounting and Wiring
5.2.6 218IF-01 Module Connections
PORT
Optional Module
Optional Module
M- /
BATTEY CN1
100/200V
10Base-T
AC CN2
POWER
5-48
5.2 Module Connections
The following tables show the PORT connector connections based on the device to be connected.
Table 5.2 For 25-pin D-sub Remote Stations
MP2200 Cable Connection and Signal Remote Station
(PORT Connector) Direction (25-pin D-sub)
Signal Signal
Pin No. Pin No.
Name Name
FG 1 1 FG
SD (TXD) 2 2 SD (TXD)
RD (RXD) 3 3 RD (RXD)
RS (RTS) 4 4 RS (RTS)
CS (CTS) 5 5 CS (CTS)
− 6 6 DSR (DR)
SG (GND) 7 7 SG (GND)
− 8 8 CD
ER (DTR) 9 20 DTR (ER)
Table 5.3 For 9-pin D-sub Remote Station Meeting Yaskawa Specifications
Remote Station
MP2200 Cable Connection and Signal
(9-pin D-sub)
(PORT Connector) Direction
(Yaskawa Specifications)
Signal Signal
Pin No. Pin No.
Name Name
FG 1 1 FG
SD (TXD) 2 2 SD (TXD) 5
RD (RXD) 3 3 RD (RXD)
RS (RTS) 4 4 RS (RTS)
CS (CTS) 5 5 CS (CTS)
− 6 6 DR (DSR)
SG (GND) 7 7 SG (GNDÅ)
− 8 8 CD
ER (DTR) 9 9 ER (DTR)
ÅD
5-49
5 Mounting and Wiring
5.2.6 218IF-01 Module Connections
PORT
Optional Module
Optional Module
M- /
BATTEY CN1
100/200V
10Base-T
AC CN2
POWER
10Base-T
Other station Other station
100 m 100 m
100 m
100 m 100 m
• Connection Example 2
218IF-01
MP2200
MP2200 MBU-01 CPU-01 218IF-01 SVB-01
POWER
PORT
Optional Module
Optional Module
M- /
BATTEY CN1
100/200V
10Base-T
AC CN2
POWER
5-50
5.2 Module Connections
PORT RS422/485
RS-232C RS-422/485
(3) Cables
5
Name Model Length
JEPMC-W5311-03 2.5 m
RS-232C Cable
JEPMC-W5311-15 15 m
5-51
5 Mounting and Wiring
5.2.7 217IF-01 Module Connections
Note: A terminator has been included, as shown in the following diagram. If you need to add a terminator,
connect RXR to RX (−), and TXR to TX (−). Leave RXR and TXR open if not adding a terminator.
Terminator
7 RXR
3, 10 RX (+)
4, 6 RX (−)
11 TXR
1, 8 TX (+)
2, 9 TX (−)
• Always keep the communication cable separate from the drive, control, power supply, and other transmis-
IMPORTANT
sion systems.
• The maximum length of RS-422/485 cable is 300 m. Keep all cables as short as possible.
• The 217IF-01 Module RS-422/485 interface is not an isolated system. Noise from connected terminals may
cause malfunctions. If malfunctions occur, use a shielded cable, modem, or other measure to reduce noise.
• For RS-422 connections, add a terminator to the reception terminal if required.
• For RS-485 connections, add a terminator to the nodes at both ends of the transmission line.
5-52
5.2 Module Connections
PORT PORT
Optional Module
Optional Module
BATTEY
100/200V
RS422/465
10Base-T
AC
To controller or
POWER
other terminal
TX + 1
TX − 2
5
TXR 11
RX + 3
RX − 4
RXR 7
GND 14
Connector
shell
TX + 1 3 RX+
TX − 2 4 RX−
TXR 11 7 RXR
RX + 3 1 TX+
RX − 4 2 TX−
RXR 7 11 TXR
GND 14 14 GND
Connector Connector
shell shell
FG
5-53
5 Mounting and Wiring
5.2.7 217IF-01 Module Connections
• RS-485 Wiring
217IF-01
MP2200
MP2200 MBU-01 CPU-01 218IF-01 217IF-01
POWER
PORT PORT
Optional Module
Optional Module
BATTEY
100/200V
RS422/465
10Base-T
AC
RS-485
130 Ω terminator
POWER
RS-422/485
TX+ 1
TX− 2
TXR 11 Shield
RX+ 3
4 130 Ω terminator
RX-
RXR 7
Connector shell
GND 14
TX RX TX RX TX RX FG
GND GND GND
2 1 9 8 4 3 6 10
TX TX TX TX RX RX RX RX
Connector − + − + − + - + Connector
shell shell
Note: The terminator is enabled by connecting terminals 2-11 and 4-7 for RS-422/485 ports.
5-54
5.2 Module Connections
PORT DeviceNet
RS-232C DeviceNet
(3) Cables
Name Model Length 5
JEPMC-W5311-03 2.5 m
RS-232C Cable
JEPMC-W5311-15 15 m
5-55
5 Mounting and Wiring
5.2.8 260IF-01 Module Connections
5-56
5.2 Module Connections
a) Multi-drop Connections
260IF-01
MP2200
MP2200 MBU-01 CPU-01 218IF-01 260IF-01 Internal power supply for I/O
POWER
PS
PORT PORT
PS
BATTEY
100/200V DeviceNet
10Base-T
AC
POWER
I/O I/O I/O
130 Ω terminator
121 Ω terminator
Trunk line cable 5
Drop line cable Power supply tap for
External power supply line for I/O communications (with
Internal power supply line for I/O reverse-current prevention
for multiple power supplies)
Communication power supply line
PS Communication power supply
FG
PORT PORT
Optional Module
Optional Module
BATTEY
10Base-T
AC
External power supply line for I/O
POWER Internal power supply line for I/O
Communication power supply line
130 Ω terminator
130 Ω terminator
5-57
5 Mounting and Wiring
5.2.9 261IF-01 Module Connections
• Slave Mode
The following diagram shows the system configuration for slave mode.
260IF-01
MP2200
MP2200 MBU-01 CPU-01 218IF-01 260IF-01 Internal power supply for I/O
POWER
PS Slave Mode
260IF-01
MP2300
External power
supply for I/O
PORT PORT
Optional Module
Optional Module PS
BATTEY
100/200V DeviceNet
10Base-T
AC
POWER
I/O I/O
PORT PROFIBUS
RS-232C PROFIBUS
(3) Cables
Name Model Length
JEPMC-W5311-03 2.5 m
RS-232C Cable
JEPMC-W5311-15 15 m
5-58
5.2 Module Connections
5-59
5 Mounting and Wiring
5.2.9 261IF-01 Module Connections
261IF-01
PORT
Optional Module
Optional Module
BATTEY
100/200V
PROFIBUS
10Base-T
AC
POWER
5-60
5.2 Module Connections
CN1 CN2
IN OUT
These connectors are use to expand the number of mounting bases to a maximum of four racks.
They are connected using the following cables.
• JEPMC-W2091-
The following diagram shows how to connect the external I/O connectors.
EXIOIF
CN1
IN
Rack 1
CN2
OUT
5
EXIOIF
CN1
IN
Rack 2
CN2
OUT
EXIOIF
CN1
IN
Rack 3
CN2
OUT
EXIOIF
CN1
IN
Rack 4
CN2
OUT
Note: Attached the enclosed dust caps to the unused connectors (1) in the above figure.
5-61
5 Mounting and Wiring
5.2.10 EXIOIF Module Connections
(2) Cables
Name Model Length
JEPMC-W2091-A5 0.5 m
Connection Cables
JEPMC-W2091-01 1.0 m
(with both connectors)
JEPMC-W2091-2A5 2.5 m
Note: 1. The total cable length when adding expansion racks is 6.0 m. Connect the shield to the connector shell.
2. Connection method: 1:1
3. Cable Specifications: Shielded cable, equivalent to UL20276, 0.08 mm2 (AWG28), two ferrite cores
attached
5-62
6
Basic System Operation
6-1
6 Basic System Operation
6.1.1 Online Operating Mode
* The above case applies when a user program error occurs or when there is a hardware fault in the
MP2200. For details on the error content and the action to be taken, see Chapter 8 Troubleshooting.
6-2
6.2 Startup Sequence and Basic Operation
STOP
SUP
INIT
CNFG
MON
SW1
TEST
OFF ON
Pin
Switch Sta- Default
Num- Operating Mode Details
Name tus Setting
ber
ON User program stopped Stops user program execution.
6 STOP OFF
OFF User program running Enabled only when the power is turned ON.
ON System use
5 SUP OFF Always leave set to OFF.
OFF Normal operation
ON Memory clear Set to ON to clear the memory.
4 INIT OFF If this switch is set to OFF, the program stored
OFF Normal operation in flash memory will be executed.
ON Configuration Mode Set to ON to execute self-configuration for
3 CNFG OFF
OFF Normal operation connected devices.
2 MON
ON System use
OFF Always leave set to OFF.
6
OFF Normal operation
ON System use
1 TEST OFF Always leave set to OFF.
OFF Normal operation
6-3
6 Basic System Operation
6.2.2 Indicator Patterns
drops.
The ALM indicator lights
Operation error
z z z { { when a calculation or I/O
I/O error
error is detected.
Note: The symbols under Indicator Name have the following meanings.
z: Not lit, {: Lit, : Blinking, −: Undefined.
6-4
6.2 Startup Sequence and Basic Operation
Startup self-diagnosis
Copied from
FLASH to RAM
Configuration Mode
Self-configuration
executing
OFF
DWG.A execution
(ladder program)
Input Input
DWG.I execution
Output Output
High Priority
6-5
6 Basic System Operation
6.2.3 Startup Sequence
(3) Self-configuration
1. Self-configuration eliminates the need to make settings for Module definitions, making it possible to per-
form startup work easily and quickly for the MP2200 system. Optional Modules are recognized and defi-
nition files are generated automatically. For details, refer to 6.5 Self-configuration.
2. The RUN indicator blinks during execution of self-configuration.
6-6
6.3 User Program
• MP900/MP2000 Series Machine Controller User’s Manual: Ladder Programs (Manual No.: SIEZ-C887-
1.2)
• MP900/MP2000 Series Machine Controller User’s Manual: Motion Programs (Manual No.: SIEZ-C887-
1.3)
• MP900/MP2000 Series Machine Controller New Ladder Editor User’s Manual: Programming Instruc-
tions (Manual No.: SIEZ-C887-13.1)
• MP900/MP2000 Series Machine Controller New Ladder Editor User’s Manual: Operation (Manual No.:
SIEZ-C887-13.2)
6-7
6 Basic System Operation
6.3.2 Execution Control of Drawings
The following table gives details of the number of drawings for each type of drawing.
Number of Drawings
Drawing
DWG.A DWG.I DWG.H DWG.L
Parent Drawing 1 (A) 1 (I) 1 (H) 1 (L)
Operation Error
1 (A00) 1 (I00) 1 (H00) 1 (L00)
Drawing
Child Drawing Maximum total of Maximum total of Maximum total of Maximum total of
Grandchild Drawing 62 drawings 62 drawings 198 drawings 498 drawings
DWG.A
Startup drawing
Each high-speed scan Each low-speed scan Operation error Interrupt signal
One high-
speed scan
DWG.H Unused time Unused time Unused time Unused time Unused time Unused time
One low-speed
scan
DWG.L
Unused time
Background*
: Executing
6-8
6.3 User Program
DWG.X01.02 FUNC-001
DWG.X01.99 FUNC-006
DWG.Xnn FUNC-032
FUNC-064
DWG.X 00
6-9
6 Basic System Operation
6.3.2 Execution Control of Drawings
FUNC-001
FUNC-001
DEND
DWG.A01.02
SEE A01.02 DEND
FUNC-001
DEND DEND
Note: 1. A parent drawing is automatically called by the system. The user can execute any child or grand-
child drawing by programming an instruction that calls the drawing (the SEE instruction) in a par-
ent or child drawing.
2. Functions can be called from any drawing. A function can also be called from a function.
3. If an operation error occurs, the operation error drawing corresponding to the drawing will be
called.
6-10
6.3 User Program
There are two methods of designating a motion program: Direct designation of the program number, and indirect
designation of the register number in which the program number is stored.
MPM001
ABS;
Motion program call instruction
MOV[X] _ [Y] _
MVS[X] _ [Y] _ F
MSEE MPM001 DA00000
IOW MB0001
MOV[X] _ [Y] _
MPM number
. 6
.
MPM003
ABS;
IOW MB0001
Setting device
Register number MOV[X] _ [Y] _
Using the
MPM number contents of .
MW00200
.
∗ MW00200 = 3
6-11
6 Basic System Operation
6.3.3 Motion Programs
(1) Groups
With the MP2200, the axes can be grouped by operation so that multiple machines can be independently con-
trolled by one Machine Controller. This enables programming to be done for each axis group. The axes to be
included in a group are defined in the group definitions. Refer to MP900/MP2000 Series Programming Device
Software MPE720 User’s Manual (Manual No. SIJPC88070005) for information on group definitions.
(a) Operation as One Group
MP2200
SGDS
SGDS
SGDS
SGDS
SGDS
xxx SERVOPACK
X1 Y1 Z1 A1 B1 Motor
(Characters are axis names.)
MP2200
SGDS
SGDS
SGDS
SGDS
SGDS
xxx SERVOPACK
X1 Y1 Z1 A1 B1 Motor
(Characters are axis names.)
6-12
6.3 User Program
MPM002
MSEE
MPM002
DEND
END
MPM003 Subprogram
MSEE
MPM003 MPS101
MSEE
MPS101
6
END
RET
DEND
In each high-speed scanning cycle, the ladder instructions for DWG.H are executed in the following hierarchical
order: Parent drawing - child drawing - grandchild drawing.
Motion programs are called in the scanning cycle, but as with ladder programs, all programs cannot necessarily
be executed in one scan. Motion programs are executed and controlled by special system motion management
functions.
The following points apply to calling motion programs. Call motion programs with care.
INFO
• More than one motion program with the same number cannot be called using the MSEE instruction.
• Subprograms (MPS) cannot be called using the ladder program MSEE instruction. They can be called only
from within motion programs (MPM and MPS).
• The same subprogram cannot be called from two different locations at the same time.
6-13
6 Basic System Operation
6.3.3 Motion Programs
IMPORTANT The program will be executed if the program start request signal has been turned ON when the power is turned
ON. Take appropriate precautions; the equipment may start moving depending on the application.
6-14
6.3 User Program
Note: When alarms occur, the details are reflected in the system registers.
(b) Bit D in the Motion Program Control Signals (System Work Number Setting) = OFF
The system work number that is used is automatically decided by the system. For this reason, the work num-
ber that is being used can be confirmed by referring to the Executing Program Number in SW03200 to
SW03215.
For example, if the motion program to be monitored is MPM001, and SW03202 is 001, then the work num-
ber being used is 3 and so the execution information of motion program MPM001 can be monitored with
Work 3 Program Information in SW03380 to SW03437.
6-15
6 Basic System Operation
6.3.3 Motion Programs
The registers for motion program execution information are shown below.
SW05120
Reserved by the system. 64
6-16
6.3 User Program
+5 Alarm code*
Parallel 1 information 3W
+8
Parallel 2 information 3W
+11
Parallel 3 information 3W
+14
Parallel 4 information 3W
+17
Parallel 5 information 3W
+20
Parallel 6 information 3W
+23
Parallel 7 information 3W
* Refer to 10.1 Motion Errors in MP2200/MP2300 Machine Controller Motion Module User’s Manual (Manual
No. SIJPC88070016) for information on motion program alarms.
6-17
6 Basic System Operation
6.3.3 Motion Programs
IB00005 OB8000F
1 0013 Alarm reset
The contents of this ladder program are shown in the following table.
Step No. Program Content
Sets motion setting parameter OB80000 (Servo ON) using external input signal IB00100, and turns ON the
1
servo.
The signals connected to the MP2200 external input signals are stored as the motion program control sig-
nals.
IW0000 (external input signal) Å® DW00001 (second word of MSEE register)
2 to 10 • Program start
• Program pause
• Program stop
• Alarm reset
Calls motion program MPM001.
MSEE MPM001 DA00000
11, 12 c d
cMotion program number
dMSEE work register address
Sets the operating mode and alarm clear (OB0000F) in the setting parameters using the alarm reset signal
13, 14
(IB00005), and clears the alarm.
When the external input signals (IB00000 to IB00005) connected to the MP2200 are input to DW00001 (second
word of MSEE work registers) as motion program control signals using the ladder program shown above, motion
program operations such as run, stop, and pause can be performed by the system motion management functions.
EXAMPLE
The following table shows an example of external input signals required to create the minimum ladder program
for running motion programs on the MP2200.
External
Signal External Signal Name Bit No. Motion Program Control Signal
Address
IB00000 Program start 0 Program start request
IB00001 Program pause 1 Program pause request
IB00002 Program stop 2 Program stop request
IB00005 Alarm reset 5 Alarm reset request
6-18
6.3 User Program
6.3.4 Functions
Functions are executed by being called from a parent, child, or grandchild drawing using the FSTART instruc-
tion. Unlike child and grandchild drawings, functions can be called from any drawing. The same function can
also be called simultaneously from drawings of different types and different hierarchies. Moreover, a function
that was previously created can also be called from another function.
The following advantages can be obtained by using functions:
• User programs can be easily divided into parts.
• User programs can be easily prepared and maintained.
Functions are divided into standard system functions, which are provided by the system, and user functions,
which are defined by the user.
(1) Standard System Functions
The functions given in the following table, which include transfer functions, are provided by the system as stan-
dard functions. The user cannot change the standard system functions.
Type Name Symbol Details
Counters COUNTER Up/down counter
System functions
6-19
6 Basic System Operation
6.4.1 Data Types
6.4 Registers
This section explains the types of register used by MP2200 user programs (mainly ladder programs) and how
these registers are used.
INFO Registers
• Registers are memory locations for storing data, and each register consists of 16 bits.
• The data in a register can be a position, speed, or other numeric value, or it can be an ON/OFF signal, i.e., bit
information.
• There are three types of numeric values that can be stored.
• 16-bit integers (−32768 to 32767)
• 32-bit integers (double-length integers)
• Real numbers (floating-point numbers)
F E D C B A 9 8 7 6 5 4 3 2 1 0
[ ML00100 ]
[ MW00100 ]
[ MF00100 ]
[ MW00101 ]
[ ML00102 ]
[ MW00102 ]
[ MF00102 ]
[ MW00103 ]
[ MB00103A ]
6-20
6.4 Registers
Pointer Designation
Register area
Memory
address
nn
[ MB001003 ]
[ MW00100 ]
[ MW00100 ] [ ML00100 ]
[ MW00101 ]
[ MW00101 ] [ MF00100 ]
[ MW00102 ]
[ MW00102 ]
[ MW00103 ]
[ MW00103 ]
EXAMPLE
• Examples of Use by Data Type
1. Bits
Bits are used for relay circuit ON/OFF status.
IB00010 MB000101
IB00001
IFON
6
2. Words
Words are used for numeric operations and logic operations.
3. Double-length Integers
Double-length integers are used for numeric operations and logic operations.
6-21
6 Basic System Operation
6.4.1 Data Types
4. Real Numbers
Real numbers are used for floating-point number operations.
1.23456 DF00100
(1.23456)
Note: Numbers in parentheses are the data stored in the registers (current value displays).
5. Addresses
Addresses are used only for pointer designations.
MF00200 to MF00228 Used as a Parameter Table
Error input
MF00200
PID MA00200 ⇒ MF00022
MW00200
LAG MA00200 ⇒ MW00022
6-22
6.4 Registers
6-23
6 Basic System Operation
6.4.2 Types of Registers
6-24
6.4 Registers
H03 drawing
System registers
Program
(SB,SW,SL,SFnnnnn)
d Data registers
Registers unique to each (MB,MW,ML,MFnnnnn)
drawing
Constant data 16,384 words max.
(#B,#W,#L,#Fnnnnn)
Individual data 16,384 words max.
(DB,DW,DL,DFnnnnn)
c: Registers common to all drawings can be called from any drawing or function.
d: Registers unique to a drawing can be called only from within that drawing.
e: Registers unique to a function can be called only from within that function.
f: Registers common to all drawings and registers unique to each drawing can be called from
functions using external function registers.
6-25
6 Basic System Operation
6.4.3 Register Designation Methods
Direct Designation
Symbol Designation
6-26
6.4 Registers
2 MB0000002
Equivalent
MB000000i
00030 J MW00031
Equivalent
MW00001j
6-27
6 Basic System Operation
6.4.4 Subscripts i and j
EXAMPLE
Programming Example Using a Subscript
The following program sets the sum of 100 registers from MW00100 to MW00199 in MW00200 using subscript j.
00000 ⇒ MW00200
6-28
6.5 Self-configuration
6.5 Self-configuration
6.5.1 Overview of Self-configuration
Self-configuration eliminates the need to make settings for Module definitions, making it possible to perform
startup work easily and quickly for the MP2200 system. Optional Modules are recognized and definition files are
generated automatically.
Input registers and output registers are automatically allocated to I/O. Allocation is performed in ascending order
from the Module with the lowest option slot number.
In networks, such as MECHATROLINK and DeviceNet, information about the station configuration is collected
and definition files are generated automatically.
Self-configuration can be executed by either turning the power ON with the CNFG and INIT switches ON, or it
can be executed from the MPE720. The procedure for executing self-configuration using the CNFG and INIT
switches is given below.
The allocated I/O register numbers will change when self-configuration is executed.
• Executing Self-configuration for the Whole Configuration
CNFG switch = ON
INIT switch = ON
Self-configuration will be executed for all Modules. All definition files will be created (or recreated). The
contents of ladder drawings, functions, and registers will all be cleared.
• Executing Self-configuration for Additions and Changes
CNFG switch = ON
INIT switch = OFF
Self-configuration is executed for Optional Modules and network devices that have been added or
changed.
Make sure that Modules with existing definition files are connected when self-configuration is executed.
Only definition data for Modules that have been added or changed will be overwritten. 6
CNFG switch ON
Turn ON the power.
INIT switch ON
The RUN indicator blinks during
No execution of self-configuration. The ERR
CNFG ON
indicator lights if an error occurs during
INIT ON
self-configuration.
Yes
Self-configuration processing
6-29
6 Basic System Operation
6.5.2 SVB-01 Modules
6-30
6.5 Self-configuration
Starts self-configuration.
Connected
Searches for connected device found.
devices using
MECHATROLINK-II 32-
byte mode.
No connected devices.
Connected
Searches for connected device found.
devices using
MECHATROLINK-II 17-
byte mode.
No connected devices.
No connected
devices. Searches for connected
devices using
MECHATROLINK-I. 6
Connected device found.
Self-configuration completed.
Note: 1. Detects slaves using each format communication in the following order: SERVOPACK, I/O,
inverter.
2. Stations with a communication error or no response due to a duplicated station number or discon-
nected cable are recognized as having no connected devices.
6-31
6 Basic System Operation
6.5.2 SVB-01 Modules
• Slaves
Item Details Default Value
Fixed value; display only.
Baud rate 4 Mbps
4 Mbps
Communication Fixed value; display only.
2 ms
cycle 2 ms
Message reliability
Setting not required. 0
level
Number of slave Fixed value; display only.
15
stations 15
6-32
6.5 Self-configuration
* If the communication cycle is 0.5 ms, the maximum number of retry stations is 5.
• Slaves
Item Details Default Value
Fixed value; display only.
Baud rate 10 Mbps
10 Mbps
Fixed value; display only.
6
No. send bytes 16 bytes
16 bytes
Communication
Setting not required. 1 ms
cycle
SigmaWin Setting not required. None
No. of retry
stations Setting not required. 1
(messages)
Number of slave Fixed value; display only.
30
stations 30
6-33
6 Basic System Operation
6.5.2 SVB-01 Modules
* If the communication cycle is 0.5 ms, the maximum number of retry stations is 3.
• Slaves
Item Details Default Value
Fixed value; display only.
Baud rate 10 Mbps
10 Mbps
Fixed value; display only.
No. send bytes 31 bytes
31 bytes
Communication
Setting not required. 1 ms
cycle
SigmaWin Setting not required. None
No. of retry sta-
tions Setting not required. 1
(messages)
Number of slave Fixed value; display only.
30
stations 30
6-34
6.5 Self-configuration
INFO MECHATROLINK Transmission Definitions for SVB Built into the MP2300 CPU
The MECHATROLINK transmission definitions are set automatically according to the detected communication method
and number of slaves.
* The communication cycle and number of retry stations when using MECHATROLINK-II (32 byte mode)
will change as shown in the following table, depending on the highest station number in the detected slave
stations.
6-35
6 Basic System Operation
6.5.2 SVB-01 Modules
6-36
6.5 Self-configuration
6-37
6 Basic System Operation
6.5.2 SVB-01 Modules
6-38
6.5 Self-configuration
6-39
6 Basic System Operation
6.5.4 LIO-01 Modules
Note: The above allocations are simply an example. The leading register number will change for manual allocations.
6-40
6.5 Self-configuration
Note: The above allocations are simply an example. The leading register number will change for manual alloca-
tions.
6-41
6 Basic System Operation
6.5.6 LIO-04 Modules
Note: The above allocations are simply an example. The leading register number will change for manual alloca-
tions.
6-42
6.5 Self-configuration
INFO An engineering communication connection with the MPE720 is possible using self-configuration. To perform MEMOBUS
message communication, the MSG-SND (MSG-RCV) function is required.
INFO An engineering communication connection with the MPE720 is possible using self-configuration. Also, depending on the
settings of connected devices, MEMOBUS message communication may be possible using the automatic reception func-
tion.
6-43
6 Basic System Operation
6.5.8 217IF-01 Modules
INFO Also, depending on the settings of connected devices, MEMOBUS message communication may be possible using the
automatic reception function when self-configuration is executed.
6-44
6.5 Self-configuration
INFO An engineering communication connection with the MPE720 is possible using self-configuration. Also, depending on the
settings of connected devices, MEMOBUS message communication may be possible using the automatic reception func-
tion.
6
6-45
6 Basic System Operation
6.5.9 260IF-01 Modules
INFO An engineering communication connection with the MPE720 is possible using self-configuration. Also, depending on the
settings of connected devices, MEMOBUS message communication may be possible using the automatic reception func-
tion.
6-46
6.5 Self-configuration
INFO An engineering communication connection with the MPE720 is possible using self-configuration. Also, depending on the
settings of connected devices, MEMOBUS message communication may be possible using the automatic reception func-
tion.
6-47
6 Basic System Operation
6.6.1 Saving User-defined Files or Data
IMPORTANT • If a scan setting is close to the maximum execution time, refreshing the displays on the MPE720 will be
extremely slow and communication timeouts will occur. If the maximum execution time exceeds the scan
setting, a watchdog time out error will occur and the MP2200 system will stop.
• Set the high-speed and low-speed scans to integral multiples of the MECHATROLINK communication
cycle of the SVB-01 Module. If you change the MECHATROLINK communication cycle, be sure to check
the scan time settings.
• High-speed and Low-speed Scan Setting Example for the SVB-01 Module
INFO
• Set the high-speed and low-speed scans to integral multiples of the MECHATROLINK communication
cycle.
• If you change the MECHATROLINK communication cycle, be sure to check the scan time settings.
• Setting Example (The calculations are the same for low-speed scans.)
• For communication cycle = 1 ms (possible only when MECHATROLINK-II is used)
and max. execution time is ≤ 0.8 ms
High-speed scan setting ≥ (1.25 × 0.8) = 1 ms
High-speed scan setting = 1 ms, 2 ms, 3 ms, etc. (an integral multiple of 1 ms or higher)
• For communication cycle = 1 ms (possible only when MECHATROLINK-II is used)
and max. execution time is ≤ 1.4 ms
High-speed scan setting ≥ (1.25 × 1.4) = 1.75 ms
High-speed scan setting = 2 ms, 3 ms, etc. (an integral multiple of 2 ms or higher)
• For communication cycle = 2 ms (when MECHATROLINK-I or MECHATROLINK-II is used)
and max. execution time is ≤ 0.8 ms
High-speed scan setting ≥ (1.25 × 0.8) = 1 ms
High-speed scan setting = 1 ms, 2 ms, 4 ms, etc. (1 ms and 2 ms or an integral multiple of 2 ms or
higher)
• For communication cycle = 2 ms (when MECHATROLINK-I or MECHATROLINK-II is used)
and max. execution time is ≤ 1.4 ms
High-speed scan setting ≥ (1.25 × 1.4) = 1.75 ms
High-speed scan setting = 2 ms, 4 ms, etc. (an integral multiple of 2 ms)
• Never change the scan time settings when the Servo is ON, particularly when an axis is moving (i.e., when
the motor is running). Doing so may cause errors in motor rotation operations, such as high-speed rota-
tion.
• Always save any data that has been set or changed to flash memory.
6-48
6.6 Setting and Changing User-defined Files or Data
6-49
7
Maintenance and Inspection
This chapter explains daily and regular inspection items to ensure that the MP2200 can always
be used in its best condition.
7-1
7 Maintenance and Inspection
7.1.1 Daily Inspections
7-2
7.1 Inspection Items
PROHIBITED
• Do not replace the built-in fuse.
If the customer replaces the built-in fuse, the MP2200 may malfunction or break down.
Contact your Yaskawa representative.
0 to 55 °C
temperature Check the tempera-
Ambient humidity ture and humidity 30% to 95 % If the MP2200 is used inside a
with a thermometer
panel, treat the temperature inside
and hygrometer,
the panel as the ambient tempera-
respectively. There must be no corro-
Atmosphere ture.
Check for corrosive sive gases.
gases.
Retighten screws.
play Module. secured properly.
7-3
7 Maintenance and Inspection
7.2.1 Battery Life
LiTHIUM
IMPORTANT Be sure to replace the battery with the power supply to the MBU-01/MBU-02 Unit turned ON.
Replacing the battery with the power supply to the MBU-01/MBU-02 Unit turned OFF will result in the pro-
grams and data stored in the CPU Module memory being lost.
7-4
8
Troubleshooting
This chapter describes the errors that can occur when using the MP2200 system, their probable
causes and the appropriate countermeasures.
8-1
8 Troubleshooting
8.1.1 Troubleshooting Methods
8-2
8.1 Overview of Troubleshooting
8-3
8 Troubleshooting
8.1.3 Indicator Errors
8-4
8.2 System Errors
8-5
8 Troubleshooting
8.2.2 Processing Flow When a System Error Occurs
START
NO
NO
YES
YES
User program
error
YES
* Refer to (2) Indicator Details in 8.1.3 Indicator Errors for details on the meaning of indicators.
8-6
8.2 System Errors
↑ g Check Whether an Operation Error Oc- Check the error count of all drawings at SW00080 to SW00088. Operation
| curred errors are occurring if the count is going up.
|
|
|
|
1. Check Error Details
Check error codes for drawings where the error count is going up.
DWG.A: SW00111 DWG.H: SW00143
When ALM Indicator Lit
8-7
8 Troubleshooting
8.2.4 System Register Configuration
Register
Name Description
Number
Reserved by SW00030 to
−
the system. SW00039
0: Failure
SB000400 READY
1: Normal
SB000401 RUN 0: Stopped, 1: Running
SB000402 ALARM 0: Normal, 1: Alarm
SB000403 ERROR 0: Normal, 1: Error
Reserved by the sys-
SB000404 −
tem.
Reserved by the sys-
SB000405 −
tem.
SB000406 FLASH 1: Flash operation
SB000407 WEN 0: Write-disabled, 1: Write-enabled
CPU Status SW00040 Reserved by the sys-
SB000408 −
tem.
Reserved by the sys-
SB000409 −
tem.
SB00040A
SB00040B Reserved by the sys-
−
SB00040C tem.
SB00040D
Operation Stop
SB00040E 0: RUN, 1: STOP
Request
Run Switch Status at 0: STOP
SB00040F
Power ON 1: RUN
1: WDGE, undefined command
SB000410 Serious failure
See SW00050 for more details.
Reserved by the sys-
SB000411 −
tem.
Reserved by the sys-
SB000412 −
tem.
SB000413 Exception Error −
SB000414
SB000415 Reserved by the sys-
−
CPU Error SB000416 tem.
SW00041
Status SB000417
User Operation
SB000418 1: User operation error
Error
SB000419 I/O error 1: I/O error
Reserved by the sys-
SB00041A −
tem.
Reserved by the sys-
SB00041B −
tem.
SB00041C to Reserved by the sys-
−
SB00041F tem.
8-8
8.2 System Errors
(cont’d)
Register
Name Description
Number
Reserved by the sys-
SB000470 −
tem.
SB000471 Reserved by the sys-
−
SB000472 tem.
Reserved by the sys-
SB000473 −
Reserved by tem.
SW00047
the system. Reserved by the sys-
SB000474 −
tem.
Reserved by the sys-
SB000475 −
tem.
SB000476 to Reserved by the sys-
−
SB00047F tem.
SB000480 TEST
SB000481 MON
SB000482 CNFG
DIP switch status
SB000483 INIT
0: ON, 1: OFF
SB000484 SUP
Hardware
SW00048 SB000485 STOP
Status
Configuration SB000486 Å|
SB000487 Battery alarm −
SB000488 to Reserved by the sys-
−
SB00048E tem.
Reserved by the sys-
SB00048F −
tem.
Reserved by SW000490 to Reserved by the sys-
SW00049 −
the system. SW00049F tem.
8-9
8 Troubleshooting
8.2.4 System Register Configuration
Register
Name Description
Number
0001H Watchdog timeout error
0041H ROM diagnosis error
0042H RAM diagnosis error
0043H CPU diagnosis error
0044H FPU diagnosis error
00E0H Address error (read)
SW00050 0100H Address error (write)
32-bit Error Code
0120H FPU error
0180H Illegal general command error
01A0H Illegal slot command error
01E0H User break after command execution
0800H General FPU inhibited error
0820H Slot FPU inhibited error
SW00051 For system error analysis
32-bit Addresses SW00052
For system error analysis
Generating Error SW00053
0000H: System
Ladder Program Error 0003H: DWG.H
SW00054 0001H: DWG.A
Task 0005H: DWG.L
0002H: DWG.I
0000H: System
0005H: DWG.L
0001H: DWG.A
Ladder Program Type SW00055 0008H: Function
0002H: DWG.I
0003H: DWG.H
Ladder program parent drawing: FFFFH
Ladder program function: 0100H
Ladder Program Error Ladder program child drawing: 00H (H: Child drawing No.)
SW00056
Drawing No.
Ladder program grandchild drawing: yyH (Hyy: Grandchild
drawing No.)
Type of drawing that calls the ladder program function in which an
error occurred.
Ladder Program
Function Calling DWG SW00057 0001H: DWG.A
0008H: Ladder program function
Type 0002H: DWG.I
0010H: Reserved by the system.
0003H: DWG.H
0011H: Reserved by the system.
0005H: DWG.L
Number of drawing that calls the ladder program function in which an
error occurred.
Ladder Program
SW00058 Parent Drawings: FFFFH
Function Calling DWG
Functions: 0100H
No.
Child drawing: 00H (H: Child drawing No.)
Grandchild drawing: yyH (Hyy: Grandchild drawing No.)
Ladder Program STEP number of drawing that calls the ladder program function in
Function Calling DWG SW00059 which an error occurred.
No. 0 when there is an error in the drawing.
8-10
8.2 System Errors
(cont’d)
Register
Name Description
Number
SW00060 Reserved by the system.
SW00061 Reserved by the system.
SW00062 Name of task generating error
SW00063 Name of task generating error
SW00064 Name of task generating error
SW00065 Name of task generating error
SW00066 Reserved by the system.
SW00067 Reserved by the system.
SW00068 Year generated
Error Data
SW00069 Month generated
SW00070 Day of week generated
SW00071 Day of month generated
SW00072 Hour generated
SW00073 Minutes generated
SW00074 Seconds generated
SW00075 Milliseconds generated (Not used.)
SW00076 to
Reserved by the system.
SW00079
8-11
8 Troubleshooting
8.2.4 System Register Configuration
8-12
8.2 System Errors
8-13
8 Troubleshooting
8.2.4 System Register Configuration
Register
Name Remarks
Number
Reserved by the system. SW00090
Reserved by the system. SW00091
−
Reserved by the system. SW00092
Reserved by the system. SW00093
SW00094 to
Reserved by the system. −
SW00097
Existence Of Data Trace Bit 0 to 3 = Group 1 to 4
SW00098
Definition Definition exists = 1, No definition = 0
Bit 0 to 3 = Group 1 to 4
Data Trace Execution Status SW00099
Trace stopped = 1, Trace executing = 0
8-14
8.2 System Errors
Register
Name Remarks
Number
Current Alarm SW00190 Cleared when power is turned ON.
Number of Alarm History Records SW00191 The number of alarms in the alarm history.
1: Clear alarms
Clear Alarm SW00192
2: Clear current alarm and alarm history
8-15
8 Troubleshooting
8.2.4 System Register Configuration
8-16
8.2 System Errors
F 2 1 0 (Bit No.)
Not
SW00225 ST#15 xxxxxxxxxxxxxxxx ST#2 ST#1
used.
F E D
Not
SW00226 ST#30 ST#29 xxxxxxxxxxxxxxxx ST#17 ST#16
used.
8-17
8 Troubleshooting
8.2.4 System Register Configuration
F 2 1 0 (Bit No.)
SW00225 ST#15 xxxxxxxxxxxxxxxx ST#2 ST#1 ST#0
F E D
SW00226 ST#31 xxxxxxxxxxxxxxxx ST#17 ST#16
8-18
8.2 System Errors
F 2 1 0 (Bit No.)
SW00225 ST#15 xxxxxxxxxxxxxxxx ST#2 ST#1 ST#0
F E D
SW00226 ST#31 xxxxxxxxxxxxxxxx ST#17 ST#16
8-19
8 Troubleshooting
8.2.4 System Register Configuration
8-20
8.2 System Errors
8-21
8 Troubleshooting
8.2.4 System Register Configuration
8-22
8.2 System Errors
8-23
8 Troubleshooting
8.2.4 System Register Configuration
8-24
8.2 System Errors
(cont’d)
Name Register Number Remarks
Rack 3, Slot 2 Information SW00960 to SW00967 Same as above.
Rack 3, Slot 3 Information SW00968 to SW00975 Same as above.
Rack 3, Slot 4 Information SW00976 to SW00983 Same as above.
Rack 3, Slot 5 Information SW00984 to SW00991 Same as above.
Rack 3, Slot 6 Information SW00992 to SW00999 Same as above.
Rack 3, Slot 7 Information SW01000 to SW01007 Same as above.
Rack 3, Slot 8 Information SW01008 to SW01015 Same as above.
Rack 3, Slot 9 Information SW01016 to SW01023 Same as above.
SW01024 Module ID
SW01025 Hardware version (BCD)
SW01026 Software version (BCD)
SW01027 Number of subslots
Rack 4, Slot 1 Information
SW01028 Subslot 1 Function Module ID
SW01029 Subslot 1 Function Module Status
SW01030 Subslot 2 Function Module ID
SW01031 Subslot 2 Function Module Status
Rack 4, Slot 2 Information SW01032 to SW01039 Same as above.
Rack 4, Slot 3 Information SW01040 to SW01047 Same as above.
Rack 4, Slot 4 Information SW01048 to SW01055 Same as above.
Rack 4, Slot 5 Information SW01056 to SW01063 Same as above.
Rack 4, Slot 6 Information SW01064 to SW01071 Same as above.
Rack 4, Slot 7 Information SW01072 to SW01079 Same as above.
Rack 4, Slot 8 Information SW01080 to SW01087 Same as above.
Rack 4, Slot 9 Information SW01088 to SW01095 Same as above.
8-25
Appendices
A
A-1
Appendices
A.1 System Service Registers
Register
Name Remarks
Number
Reserved by the system. SB000000 Not used
ON for only the first scan after high-speed scan
High-speed scan SB000001
is started.
ON for only the first scan after low-speed scan
Low-speed scan SB000003
is started.
Always ON SB000004 Always ON. (= 1)
SB000005 to
Reserved by the system. Not used
SB00000F
A-2
A List of System Registers
1.0 s 1.0 s
1.0-s Flicker Relay SB000012
2.0 s 2.0 s
2.0-s Flicker Relay SB000013
0.5 s 0.5 s
0.5-s Sampling Relay SB000014
1 scan
1.0 s 1.0 s
1.0-s Sampling Relay SB000015
1 scan
2.0 s 2.0 s
2.0-s Sampling Relay SB000016
1 scan
60.0 s 60.0 s
60.0-s Sampling Relay SB000017
1 scan
1.0 s
1.0 s After Start of Scan Relay SB000018
2.0 s
2.0 s After Start of Scan Relay SB000019
5.0 s
5.0 s After Start of Scan Relay SB00001A
A-3
Appendices
A.1 System Service Registers
0.5 s 0.5 s
0.5-s Flicker Relay SB000031
1.0 s 1.0 s
1.0-s Flicker Relay SB000032
2.0 s 2.0 s
2.0-s Flicker Relay SB000033
0.5 s 0.5 s
0.5-s Sampling Relay SB000034
1 scan
1.0 s 1.0 s
1.0-s Sampling Relay SB000035
1 scan
2.0 s 2.0 s
2.0-s Sampling Relay SB000036
1 scan
60.0 s 60.0 s
60.0-s Sampling Relay SB000037
1 scan
1.0 s
1.0 s After Start of Scan Relay SB000038
2.0 s
2.0 s After Start of Scan Relay SB000039
5.0 s
5.0 s After Start of Scan Relay SB00003A
A-4
A List of System Registers
Register
Name Remarks
Number
High-speed Scan Set Value SW00004 High-speed Scan Set Value (0.1 ms)
High-speed Scan Current Value SW00005 High-speed Scan Current Value (0.1 ms)
High-speed Scan Maximum Value SW00006 High-speed Scan Maximum Value (0.1 ms)
SW00007 to
Reserved by the system. Not used
Register
Name Remarks
Number
System Program Software Number SW00020 S ( is stored as BCD)
SW00021 to
System Number Not used
SW00025
Remaining Program Memory Capacity SW00026 In bytes
Total Module Memory Capacity SW00028 In bytes
A-5
Index
Index-1
Index
Index-2
Index
Index-3
Revision History
The revision dates and numbers of the revised manuals are given on the bottom of the back cover.
MANUAL NO. SIEP C880700 14A
C Printed in Japan September 2004 04-09
Revision
Printing date Number Section Number Revised Contents
YASKAWA
In the event that the end user of this product is to be the military and said product is to be
employed in any weapons systems or the manufacture thereof, the export will fall under
the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade
Regulations. Therefore, be sure to follow all procedures and submit all relevant
documentation according to any and all rules, regulations and laws that may apply.
Specifications are subject to change without notice
MANUAL NO. SIEP C880700 14A
for ongoing product modifications and improvements. Printed in Japan September 2004 04-9
© 2004 YASKAWA ELECTRIC CORPORATION. All rights reserved. 04-8⑥