Instruction Manual: Installation Operation Maintenance Voltage Regulator
Instruction Manual: Installation Operation Maintenance Voltage Regulator
Instruction Manual: Installation Operation Maintenance Voltage Regulator
Installation
Operation
Maintenance
Voltage Regulator
K65-12B and K125-10B
Publication
351-01057-00 B (09/19/2014)
Kato Engineering, Inc. | P.O. Box 8447 | Mankato, MN USA 56002-8447 | Tel: 507-625-4011
[email protected] | www.KatoEngineering.com | Fax: 507-345-2798
Table of Contents
Introduction............................................................... 3
Foreword..................................................................................... 3
Safety Instructions....................................................................... 3
General Information................................................... 3
General....................................................................................... .3
Specifications.............................................................................. 4
Installation..................................................................6
Mounting..................................................................................... 6
Connections................................................................................ 7
Operation.................................................................. 13
General..................................................................................... 13
Preliminary Setup...................................................................... 13
System Startup.......................................................................... 13
Adjustments.............................................................................. 15
Field flashing................................................................. 15
Frequency roll-off adjustment........................................ 15
Stability (STB)............................................................... 16
Voltage (VLT ADJ) adjustment.......................................16
Factory voltage adjust range calibration adjustment..... 16
Parallel drop (DRP) compensation................................ 16
Options..................................................................................... 16
Remote voltage adjust................................................... 16
Excitation disable........................................................... 17
VAR/PF control.............................................................. 17
Manual voltage control.................................................. 17
Operational Test....................................................................... 17
Maintenance............................................................. 19
Note: Because of rapid changes in designs
Preventive................................................................................. 19
and processes and the variability of Kato Troubleshooting........................................................................ 19
Engineering’s products, information in this
manual must not be regarded as binding
and is subject to change without notice.
Page 2
Introduction
Foreword
This manual contains instructions for installing, operating and
maintaining Kato Engineering K65-12B and K125-10B voltage
regulators.
Safety Instructions
In order to prevent injury or equipment damage, everyone involved
in installation, operating and maintenance of the equipment described
in this manual must be qualified and informed of the current safety
standards that govern his or her work. The following paragraphs define
warnings, cautions, and notes as they are used in this manual:
Page 3
Specifications
Refer to Table 1 for the electrical specifications. Refer to Table 2 for the
physical specifications:
Specification K65-12B K125-10B
12 Adc @ 65 Vdc maximum 10 Adc @ 125 Vdc maximum
Output power (with a 240 continuous. continuous.
Vac Input): 25 Adc @ 125 Vdc forcing for 10 20 Adc @ 250 Vdc forcing for
seconds. 10 seconds.
100 to 280 Vac, single-phase 50 180 to 280 Vac, single-
to 400 Hz, or 63 to 105 Vac; three- phase or three-phase, 50 to
AC input power:
phase, 50 to 400 Hz, 1092 VA 400 Hz, 1750 VA maximum
maximum continuous burden continuous burden
90 to 140 Vac, 50/60 or 400 Hz; 90 to 140 Vac, 50/60 Hz;
AC sensing voltage:
single- or three-phase. single- or three-phase.
External voltage adjust
10k ohm, 2 W, potentiometer 10k ohm, 2 W, potentiometer
rheostat:
Regulation accuracy: ±0.5% Average responding ±0.5% Average responding
±1% voltage variation for a 40° C ±1% voltage variation for a
Voltage drift:
(104° F) change. 40° C (104° F) change.
Response time: < 4 milliseconds < 4 milliseconds
1 or 2 V/Hz jumper selectable with 1 or 2 V/Hz jumper selectable
Frequency compensation: knee adjustable from 45 Hz to 65 with knee adjustable from 45
Hz. Hz to 65 Hz.
EMI suppression: Internal filter Internal filter
Internal provisions for
Internal provisions for automatic
automatic voltage build-up
Voltage Build-Up: voltage build-up from generator
from generator residual
residual voltages as low as six Vac.
voltages as low as six Vac.
Overexcitation protection
Overexcitation protection starts
starts timing at 180 Vdc ±5%
timing at 90 Vdc ±5% and takes
and takes the output to zero
Overexcitation shutdown: the output to zero in greater than
in greater than 30 seconds.
30 seconds. The output can be 125
The output can be 250 Vdc
Vdc for greater than 10 seconds.
for greater than 10 seconds.
Page 4
Specification K65-12B and K125-10B
Conforms to:
Radiated Emissions............... EN50081-2
Radiated Immunity:
Electric field..................... EN61000-4-3 (10 V/m
Conducted....................... EN61000-4-6 (10 VRMS)
Conducted Emissions............ EN50081-2 (EN55011, Class A)
CE conformity ESD Immunity ����������������������� EN50082-2 (4 kV contact, 8 KV air)
EFT Immunity........................ EN50082-2 (2 kV coupling clamp)
Magnetic Immunity................ EN50082-2 (30ARMS, 50 Hz)
Safety.................................... EN61010-1
(When enclosed within a suitable steel enclosure attached the
generator)
Page 5
Installation
Mounting
The regulator may be mounted in any position. Refer to Figure 1 for
overall dimensions. The regulator may be mounted directly on the
generator set using UNF 1/4-20 or equivalent hardware. Select the
proper hardware to withstand any expected shipping/transportation and
operating conditions.
Page 7
NOTES:
1 IF 1A. SEC CCCT IS USED, CONNECT TO TERMINAL 5 INSTEAD OF 5a. (VAR/PFC & EL CANNOT BE USED WITH 1A. CCCT).
2 IF EXTERNAL VAR IS NOT USED, JUMPER 4 TO 7.
3 FOR 2 x V/HZ, REMOVE CONNECTION TO TERMINAL 8. (1 x V/HZ CONNECTION IS SHOWN).
4 IF EL, VAR/PF, DSLC AND/OR BE3-25A ARE NOT USED, JUMPER 2 TO 3.
VAR NOTE:
10 K IS VOLTAGE RESISTANCE INCREASES TO INCREASE VOLTAGE.
STANDARD CW ADJUST
2 3
VR
4 7 6a 8 9
CH
GND 28 30 26 F1 F2 2 3 22 24 20 6 5a 5
* IF POWER IS REMOVED ** 1
FROM BE3-25A AFTER 4
SYNCHRONIZING, THE
CIRCUIT BETWEEN VR1 &
VR2 MUST BE CLOSED.
BE3- 25A DSLC
VR1 30
*
** IF POWER SOURCE IS VR4 VR3 VR2 31
POLARITY
UNGROUNDED, JUMPER MUST
JUMPER
BE TIED FROM 28 TO 24. * IF POWER
IN "A"
POSITION FROM BE
SYNCHR
CIRCUIT BE
EL
PMG POWER IS SHOWN. F2 C 2 EXCITATION VR2 MUS
E1 E3
1 PHASE POWER MAY BE LIMITER
F1 L 1
FROM PMG, GENERATOR, OR EL-200
OTHER SOURCE. 3 PHASE PMG
POWER, WHEN AVAILABLE, IS ** IF POWE
USED WITH K65-12B ONLY. UNGROUNDE
VAR/PFC BE TIED FRO
C A 2 SCP-250
(11) PM1 PM1 E1 E3
1 PHASE POWER
120 V : K65-12B 1 J K
3 PHASE PMG POWER
240 V : K125-10B
(12) PM2 PM2 or PM4
(REGULATOR 52/B PMG PO
IS 120 VOLT
(13) PM3 SENSING ONLY)
1 PHASE
ALTERNATE LABELING FOR SOME APPLICATIONS 52/b (AUX CONTACT FROM PM
X1 X2 X1 X2
IN CIRCUIT BREAKER) OTHER SOUR
DISABLES SCP-250
F1 (+) WHEN GENERATOR POWER, W
IS NOT OPERATING USED WIT
H1 H2 H1 H2 IN PARALLEL WITH
F2 (-) UTILITY
FROM GENERATOR
ØA ØA (11) PM1
3 PHASE PMG POWER
TO LOAD
ØB ØB
CCCT (12) PM2
5A. SEC 1
ØC ØC
(13) PM3
SHOWN CONNECTED ALTER
FOR A-B-C PHASE
ROTATION. FOR A-C-B
ROTATION, REVERSE
CCCT SECONDARY.
Figure 2: Regulator connections (three phase)
Page 8
SHOWN
NOTES:
1 IF 1A. SEC CCCT IS USED, CONNECT TO TERMINAL 5 INSTEAD OF 5a. (VAR/PFC & EL CANNOT BE USED WITH 1A. CCCT).
2 IF EXTERNAL VAR IS NOT USED, JUMPER 4 TO 7.
3 FOR 2 x V/HZ, REMOVE CONNECTION TO TERMINAL 8. (1 x V/HZ CONNECTION IS SHOWN).
4 IF EL, VAR/PF, DSLC AND/OR BE3-25A ARE NOT USED, JUMPER 2 TO 3.
VAR NOTE:
10 K IS VOLTAGE RESISTANCE INCREASES TO INCREASE VOLTAGE.
STANDARD CW ADJUST
2 3
VR
4 7 6a 8 9
CH
GND 28 30 26 F1 F2 2 3 22 24 20 6 5a 5
* IF POWER IS REMOVED ** 1
FROM BE3-25A AFTER 4
SYNCHRONIZING, THE
CIRCUIT BETWEEN VR1 &
VR2 MUST BE CLOSED.
BE3- 25A DSLC
VR1 30
*
** IF POWER SOURCE IS VR4 VR3 VR2 31
POLARITY
UNGROUNDED, JUMPER MUST
JUMPER
BE TIED FROM 28 TO 20.
IN "A"
POSITION
EL
PMG POWER IS SHOWN. F2 C 2 EXCITATION
E1 E3
1 PHASE POWER MAY BE LIMITER
F1 L 1
FROM PMG, GENERATOR, OR EL-200
OTHER SOURCE. 3 PHASE PMG
POWER, WHEN AVAILABLE, IS
USED WITH K65-12B ONLY.
VAR/PFC
C A 2 SCP-250
(11) PM1 PM1 E1 E3
1 PHASE POWER
120 V : K65-12B 1 J K
3 PHASE PMG POWER
240 V : K125-10B
(12) PM2 PM2 or PM4
(REGULATOR 52/B
IS 120 VOLT
(13) PM3 SENSING ONLY)
ALTERNATE LABELING FOR SOME APPLICATIONS 52/b (AUX CONTACT
X1 X2
IN CIRCUIT BREAKER)
DISABLES SCP-250
F1 (+) WHEN GENERATOR
IS NOT OPERATING
H1 H2 IN PARALLEL WITH
F2 (-) UTILITY
FROM GENERATOR
ØA ØA TO LOAD
ØB ØB
CCCT
5A. SEC 1
ØC ØC
SHOWN CONNECTED
FOR A-B-C PHASE
ROTATION. FOR A-C-B
ROTATION, REVERSE
CCCT SECONDARY.
Figure 3: Regulator connections (single phase)
Page 9
NOTES:
1 IF 1A. SEC CCCT IS USED, CONNECT TO TERMINAL 5 INSTEAD OF 5a. (VAR/PFC & EL CANNOT BE USED WITH 1A. CCCT).
2 IF EXTERNAL VAR IS NOT USED, JUMPER 4 TO 7.
3 FOR 2 x V/HZ, REMOVE CONNECTION TO TERMINAL 8. (1 x V/HZ CONNECTION IS SHOWN).
VAR NOTE:
10 K IS VOLTAGE RESISTANCE INCREASES TO INCREASE VOLTAGE.
STANDARD CW ADJUST
2 3
VR
4 7 6a 8 9
CH
GND 28 30 26 F1 F2 2 3 22 24 20 6 5a 5
** 1
** IF POWER SOURCE IS
UNGROUNDED, JUMPER MUST
BE TIED FROM 28 TO 24.
120 V : K65-12B
3 PHASE PMG POWER
240 V : K125-10B
(12) PM2 PM2 or PM4
(REGULATOR
IS 120 VOLT
(13) PM3 SENSING ONLY)
ALTERNATE LABELING FOR SOME APPLICATIONS
PT'S IF X1 X2 X1 X2
NEEDED
F1 (+)
H1 H2 H1 H2
F2 (-)
FROM GENERATOR
ØA ØA
TO LOAD
ØB ØB
CCCT
5A. SEC 1
ØC ØC
SHOWN CONNECTED
FOR A-B-C PHASE
ROTATION. FOR A-C-B
ROTATION, REVERSE
CCCT SECONDARY.
Page 10
NOTES:
1 IF 1A. SEC CCCT IS USED, CONNECT TO TERMINAL 5 INSTEAD OF 5a. (VAR/PFC & EL CANNOT BE USED WITH 1A. CCCT).
2 IF EXTERNAL VAR IS NOT USED, JUMPER 4 TO 7.
3 FOR 2 x V/HZ, REMOVE CONNECTION TO TERMINAL 8. (1 x V/HZ CONNECTION IS SHOWN).
VAR NOTE:
10 K IS VOLTAGE RESISTANCE INCREASES TO INCREASE VOLTAGE.
STANDARD CW ADJUST
2 3
VR
4 7 6a 8 9
CH
GND 28 30 26 F1 F2 2 3 22 24 20 6 5a 5
** 1
** IF POWER SOURCE IS
UNGROUNDED, JUMPER MUST
BE TIED FROM 28 TO 20.
120 V : K65-12B
3 PHASE PMG POWER
240 V : K125-10B
(12) PM2 PM2 or PM4
(REGULATOR
IS 120 VOLT
(13) PM3 SENSING ONLY)
ALTERNATE LABELING FOR SOME APPLICATIONS
X1 X2
F1 (+)
H1 H2
F2 (-)
FROM GENERATOR
ØA ØA TO LOAD
ØB ØB
CCCT
5A. SEC 1
ØC ØC
SHOWN CONNECTED
FOR A-B-C PHASE
ROTATION. FOR A-C-B
ROTATION, REVERSE
CCCT SECONDARY.
Figure 5: Regulator connections (simple single phase)
Page 11
Figure 6: Cross-current compensation
Page 12
Operation
General
Table 5 provides system start-up procedures for the K65-12B and
K125-10B voltage regulators. Symptoms of problems occurring
during start-up that arise from incorrect regulator adjustment and
certain generator system problems that resemble faulty regulation are
included together with possible solutions. Simplifying the system by
eliminating components, such as remote adjust potentiometers and
other non-essential items can be helpful in the troubleshooting process.
Adjustments, options, and an operational test are included in the
paragraphs after the table.
Preliminary Setup
To prevent damage to the regulator, ensure that the regulator has been
installed and connected in accordance with the installation procedures
before proceeding with the system start-up.
System Startup
Refer to Table 5 for starting up the system
Page 13
Procedure Symptom Remedy
1. Perform the preliminary
N/A N/A
set-up.
Page 14
Adjustments
For location of the adjustments referenced in the following paragraphs,
refer to Figure 1.
Field Flashing (only for units with no PMG) Caution: Do not flash the field with the
generator in motion. The regulator may be
When the regulator is operated with the generator for the first time, the
damaged.
polarity of the residual magnetism may not be correct or of sufficient
magnitude. If the generator residual voltage is less than 6 Vac for the
K65-12B or 12 Vac for the K125-10B at terminals 26 and 28, shut down
the prime mover and proceed with the following steps:
(1) With the prime mover at rest, apply a DC source (ungrounded), of
not more than 24 Vdc, to terminals F1 (positive) and F2 (negative) in
series with a limiting resistor. Use 1 ohm of resistance for each volt
from the DC power source with a power rating of least one 1 watt per
ohm.
Example: If using a 24 Vdc source, use a 24-ohm, 24-watt resistor.
(2) Allow the field to be flashed for approximately 10 seconds before
removing the DC source.
(3) If voltage build-up does not occur after performing steps (1) and (2),
verify the polarity of the DC source used in steps (1) and (2) and re-
perform.
Page 15
Stability (STB) adjustment
Use an oscilloscope or other voltage-recording device if an optimal
stability setting is desired. Adjust the stability setting with the generator
at no load. Good response can be obtained with the following procedure.
(1) Rotation of the STB control in the clockwise (CW) direction will
slow response time.
(2) Rotation of the STB control in the counter-clockwise (CCW)
direction will speed response time. If rotated too far CCW, the
generator voltage may oscillate (hunt).
(3) Rotate the front panel STB control CCW until the system just begins
to oscillate and then rotate CW just past the point where oscillation
occurred.
Voltage (VLT ADJ) adjustment
(1) Installation of a jumper across terminals 4 and 7 allows the internal
VLT ADJ adjustment to vary the generator nominal voltage over the
operating range.
(2) Remove the jumper between terminals 4 and 7 and connect a 10k
ohm external voltage adjust potentiometer across terminals 6 and
7 to allow operation of the external voltage adjust potentiometer.
The internal voltage adjustment should be set fully CW for proper
operation of the external adjustment.
Caution: The factory calibration (FAC CAL) Factory voltage adjust range calibration adjustment
adjustment is intended for use by factory
With the voltage regulator operating on a generator, adjust the calibration
technicians only. The factory voltage adjust
range calibration adjustment can be used if
potentiometer fully ccw and the voltage adjust potentiometer fully CW.
the factory calibration has been disturbed. Adjust the calibration potentiometer CW until the generator voltage is
144 ±1 Vac. Adjust the voltage adjust CCW and verify the generator
voltage is less than 90 Vac. The unit is calibrated and the calibration
potentiometer can be sealed.
Parallel droop (DRP) compensation
Variable parallel droop compensation levels can be obtained by adjusting
the droop potentiometer. CW rotation increases the amount of droop for
a given condition.
Options
The K65-12B and the K125-10B may be equipped with the following
options to enhance operational characteristics. Characteristics of these
options are defined in the following paragraphs:
Page 16
Excitation disable
This option provides for disabling of the excitation system by removal
of power from the voltage regulator. A switch removing voltage from
terminals 26, 28 and/or 30 will remove power.
Var/PF control
This option allows the K65-12B and the K125-10B to either regulate the
volt-amps reactive (var) or power factor while the generator is connected
to an infinite or utility bus. The var/PF option (Model Number SCP250G-
50 for 50-Hz operation or SCP250G-60 for 60-Hz operation) supplies a
DC signal into the K65-12B & K125-10B terminals 2 and 3 to regulate
to the SCP250 var or power factor setting.
Operational Test
To operationally test any K65-12B or the K125-10B, perform the
following steps:
a. Connect the voltage regulator as shown by Figure 7, and apply 120
Vac.
b. Adjust the VLT ADJ control fully counterclockwise (CCW).
Result: Observe that the lamp is OFF.
c. Adjust the front panel VLT ADJ control clockwise (CW).
Result: Observe that the lamp is now ON.
d. Adjust the front panel VLT ADJ control until the lamp just goes out.
Regulator operation is satisfactory if the above results are obtained.
Stability, however, must be tested with the regulator operating while
connected to the generator.
Page 17
Figure 7: Operational test setup
Page 18
Maintenance
Preventive Maintenance
Inspect the voltage regulator periodically to ensure that it is clean
and free from accumulations of dust and moisture. Be sure that all
connections are clean and tight.
Troubleshooting
In case of failure or defective operation of the unit, Table 6 is provided
to aid in the determination of the cause and the possible solution.
Simplifying the system by eliminating components, such as remote
adjust potentiometers and other non-essential items can be helpful in the
troubleshooting process.
Page 19
Verify single or three phase sensing is
a. Single or three phase applied to 20, 22 and/or 24 and verify
jumper incorrect connection from terminal 6a to 9 is
correct.
b. Internal or external voltage Adjust VLT ADJ control and/or external
adjustments are improperly voltage adjust rheostat. Verify proper
set connection from 4 to 7.
Verify the generator is rotating at
c. The regulator is operating
the proper frequency. Verify proper
Voltage does not build up on the underfrequency curve
adjustment of the underfrequency pot.
to rated value.
d. Faulty regulator Replace regulator.
e. Terminals 2 and 3 are not a. Jumper terminals 2 and 3.
jumpered and there is no
device connected to these b. Connect var/PF controller or other
terminals device to terminals 2 and 3.
Kato Engineering, Inc. | P.O. Box 8447 | Mankato, MN USA 56002-8447 | Tel: 507-625-4011
[email protected] | www.KatoEngineering.com | Fax: 507-345-2798