Technical Guide R-410A ZJ/ZR/ZF Series 15 - 25 TON 60 Hertz: Description
Technical Guide R-410A ZJ/ZR/ZF Series 15 - 25 TON 60 Hertz: Description
Technical Guide R-410A ZJ/ZR/ZF Series 15 - 25 TON 60 Hertz: Description
15 - 25 TON Although the units are primarily designed for curb mounting on
a roof, they can also be mounted at ground level or set on steel
60 Hertz beams above a finished roof.
ZJ/ZR Shown
Table of Contents
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Prior Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Capacity Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Sound Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Component Location
(ZJ shown)
Outdoor Fan #2
Outdoor Fan #1
Outdoor Fan #4
Outdoor Fan #3
Nomenclature
Cabinet Options
Product Identifier
A = Std Cabinet
F = Pkg AC Std Eff B = HFD (Hinged FLTR/Toolless DR)
J = Pkg AC High Eff C = HCD (Hinged & Toolless ACS DR)
R = Pkg AC Reheat D = DBW/HCD (Doublewall Cabinet/HCD)1
E = SSD (SST Drain Pan)
F = SSD,HFD
Nominal Cooling Capacity G = SSD,HCD
H = SSD,DBW/HCD
180 = 15 Ton J = DBW
210 = 17.5 Ton K = DBW/HFD
240 = 20 Ton L = DBW/SSD
300 = 25 Ton M = DBW/SSD/HFD
00 = Cooling Only
Refrigeration
Gas MBH Input
A = Standard Refrigeration
30 = 300 MBH Input B = ECC (E-Coat Cond Coil)
40 = 375 MBH Input1 C = EEC (E-Coat Evap Coil)
40 = 400 MBH Input D = HGBP (Hot Gas Bypass)
F = ECC,EEC
Note: 1. ZF180 G = ECC,EEC,HGBP
J = ECC,HGBP
Blower Option M = EEC,HGBP
B = Standard Static
C = Low Static1 Controls Option
D = High Static
E = VFD/VAV Std Static A = Stand Alone Smart Equipment™
F = VFD/VAV Low Static1 C = BACnet MSTP,Mdbs,N2 COM Card
G = VFD/VAV High Static D = CPC Control, DFS, APS
H = VFD/VAV w/Bypass Std Static F = Fault Detection Diagnostics
J = VFD/VAV w/Bypass Low Static1 G = Novar UCM Ctrl, DFS, APS
K = VFD/VAV w/Bypass High Static H = Hnywll Excel 10 CTRL,DFS,APS
L = VFD/VAV Customer Std Static M = Verasys Single Zone
M = VFD/VAV Customer Low Static1 N = Verasys Change Over Bypass
N = VFD/VAV Customer High Static Q = Verasys Single Zone W/FDD
P = VFD IntelliSpeed Std Static R = Verasys COBP W/FDD
Q = VFD IntelliSpeed Low Static1 T = Verasys VAV W/FDD
R = VFD IntelliSpeed High Static
S = VFD w/Byp IntelliSp Std Static
T = VFD w/Byp IntelliSp Low Static1 Sensors
U = VFD w/Byp IntelliSp Hi Static
V = VFD Cust IntelliSp Std Static A = No Sensors
W = VFD Cust IntelliSp Low Static1 B = PHM (Phase Monitor)
X = VFD Cust IntelliSp Hi Static C = DFS (Dirty Filter Switch)
D = SAD (Supply Air Smoke DET)
Note: 1. Available Only in the ZF300, ZJ300 and ZR300 E = RSD (Return Air Smoke DET)
F = PHM,DFS
Voltage G = PHM,SAD
H = PHM,RSD
2 = 208/230-3-60 J = DFS,SAD
4 = 460-3-60 K = DFS,RSD
5 = 575-3-60 L = SAD,RSD
M = PHM,DFS,SAD
N = PHM,DFS,RSD
Outdoor Air Option
P = PHM,SAD,RSD
A = No Economizer Q = DFS,SAD,RSD
B = Economizer w/Barometric RLF1 R = PHM,DFS,SAD,RSD
C = Economizer w/o Barometric RLF
D = Economizer w/Power EXH1
H = Motorized Damper Service Options
J = Motorized Damper w/Baro RLF1
1 = No Service Options
Note: 1. Available Downflow Only 2 = DSC (Disconnect Switch)
3 = NCO (Non-PWR Conv. Outlet)
4 = PCO (Powered Conv. Outlet)
5 = DSC,NCO
6 = DSC,PCO
7 = SCCR (High SCCR)
8 = SCCR,DSC
9 = SCCR,DSC,NCO
Prior Nomenclature
Note: Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
1. ZF180 Only
Notes:
Product Generation 1. BAS Ready econ requires input from a field installed BAS control. Not available with
Airflow
factory installed BAS controls.
3 = Third Generation 2. Double wall available on ZJ and ZR units only
A = Std. Motor
D = Std. Motor/Motorized Damper
E = Std. Motor/Motorized Damper/Barometric Relief
F = Std. Motor/Low Leak Econ Additional Options
G = Std. Motor/Low Leak Econ/Power Exhaust 1
Standard Cabinet Hinged Filter Door & Tool Free Access Cabinet
H = Std. Motor/Low Leak Econ/Barometric Relief
N = Hi Static
AA = None BA = Hinged Filter Door & Tool Free Access Panels
R = Hi Static/Motorized Damper
AB = Phase Monitor BB = Phase Monitor, Hinged Filter Door & Tool Free
K = Hi Static/Motorized Damper/Barometric Relief
AC = Coil Guard Access Panels
L = Hi Static/Low Leak Econ AD = Dirty Filter Switch BC = Coil Guard, Hinged Filter Door & Tool Free
M = Hi Static/Low Leak Econ/Power Exhaust 1 AE = Phase Monitor & Coil Guard Access Panels
T = Hi Static/Low Leak Econ/Barometric Relief AF = Phase Monitor & Dirty Filter Switch BD = Dirty Filter Switch, Hinged Filter Door &
2 = Low Static 2 AG = Coil Guard & Dirty Filter Switch Tool Free Access Panels
5 = Low Static/Motorized Damper 2 AH = Phase Monitor, Coil Guard & Dirty Filter Switch BE = Phase Monitor & Coil Guard, Hinged Filter
6 = Low Static/Motorized Damper/Barometric Relief 2 RC = Coil Guard & American Flag Door & Tool Free Access Panels
U = Low Static/Low Leak Econ 2 TA = Technicoat Condenser Coil BF = Phase Monitor & Dirty Filter Switch, Hinged
V = Low Static/Low Leak Econ/Power Exhaust 1,2 TJ = Technicoat Evaporator Coil Filter Door & Tool Free Access Panels
W = Low Static/Low Leak Econ/Barometric Relief 2 TS = Technicoat Evaporator & Condenser Coils BG = Coil Guard & Dirty Filter Switch, Hinged Filter
EA = E-Coat Condenser Coil Door & Tool Free Access Panels
Notes: EJ = E-Coat Evaporator Coil BH = Phase Monitor, Coil Guard & Dirty Filter Switch,
1. Downflow Only ES = E-Coat Cond & Evap Coils Hinged Filter Door & Tool Free Access Panels
2. Available only in the ZJ300, ZR300 and ZF300.
Voltage ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60
Installation Options
Options
Features and Benefits for 10, 15 or 25% outdoor air. With bottom duct connections,
the fixed outdoor air intake assembly should be mounted
Standard Features over the opening in the return air panel. With horizontal
ductwork, it should be mounted on the return air duct.
• High Efficiency - High efficiency units reach as high as
• System Protection - Suction line freezestats are supplied
12.2 EER. Gas/electric units have electronic spark ignition
on all units to protect against loss of charge and coil frosting
and power vented combustion with steady state efficiencies
when the economizer operates at low outdoor air
of 80%. These efficiencies exceed all legislated minimum
temperatures while the compressors are running. Every unit
levels and provide low operating costs.
has solid-core liquid line filter-driers and high and low-
• Balanced Heating - pressure switches. Internal compressor protection is
• Gas Heat - All gas heat units are built with two heating standard on all compressors. Phase Monitors are optional
sections for two equal stages of capacity control. Each on all units. This accessory monitors the incoming power to
section includes a durable heat exchanger with the unit and protects the unit from phase loss and reversed
aluminized steel or optional stainless steel tubes, a phase rotation.
redundant gas valve, spark ignition, power venting, an • Advanced Controls - ZJ/ZR/ZF Models have Smart
ignition module for 100% shut-off and all of the safety Equipment™ control boards that standardized a number
controls required to meet the latest ANSI standards. of features previously available only as options or by
The gas supply piping can be routed into the heating utilizing additional controls.
compartment through a hole in the base pan of the unit
or through a knockout in the piping panel on the front of
the unit.
• Electric Heat - All electric heat models (field installed
accessory only) are wired for a single power source and The Smart Equipment™ control board used in this
include a bank of nickel chromium elements mounted at product will effectively operate the cooling system
the discharge of the supply air blower to provide a high down to 0°F when this product is applied in a comfort
velocity and uniform distribution of air across the heating cooling application for people. An economizer is
elements. Every element is fully protected against typically included in this type of application. When
excessive current and temperature by fuses and two applying this product for process cooling applications
thermal limit switches. (computer rooms, switchgear, etc.), please
The power supply wiring can be routed into the control reference applications bulletin AE-011-07 or call the
box through a threaded pipe connection in the base pan applications department for Unitary Products @ 1-
of the unit or through a knockout in the wiring panel on 877-UPG-SERV for guidance. Additional
the front of the unit. accessories may be needed for stable operation at
• Unit Controllers - York's Sunline™ series offer factory temperatures below 30°F.
mounted Smart Equipment™ UCB, with optional
Communication board, a 4-stage board if 4 stages are
required, an Economizer board, and an FDD (Fault
Detection and Diagnostic) board. A MAP Device can be
used to remotely access.
• Convertible Airflow Design - All models (including those
with an economizer) are suitable for either bottom or
horizontal duct connections. Models with factory
installed power exhaust are suitable for bottom duct
connections only. For bottom duct, you remove the sheet
metal panels from the supply and return air openings
through the base of the unit. For horizontal duct, you
replace the supply and return air panels on the rear of the
unit with a side duct flange accessory.
• Factory Mounted Outdoor Air Dampers - All models are
available with these "factory mounted" outdoor air damper
options:
• Dry Bulb economizer with or without power exhaust
• Motorized outdoor air damper
• Barometric Relief Damper
• Units will come with the new state of the art Smart
A fixed outdoor air intake assembly will be shipped in the Equipment™ control system. The new unit control
return air compartment of all units ordered without an incorporates the best of the already proven Simplicity™
economizer or motorized outdoor air damper option. The unitary controls and creates a more robust, intelligent
assembly includes a rain hood with a baffle that can be set control. The goal of this control is to utilize cutting edge
technology making the equipment easier to install, control board will lock out the associated compressor.An
operate, and service. All units are Factory commissioned, alarm message will be displayed on the LCD screen.
configured, and run tested. • Lead-Lag - An integrated Lead-Lag option allows equal
• Versatile - The Smart Equipment™ control can be run time hours on all compressors, thereby extending
configured to use with a standard thermostat (easy to the life of all compressors. This option is selectable on
connect screw terminals), A zone sensor, or can be setup the unit control board.
to communicate with multiple BAS communication • Reliable - From the beginning - All units undergo
protocols to integrate with building automation systems. computer automated testing before they leave the factory.
• Reduce field installed complexity - Each unit will comes Units are tested for refrigerant charge and pressure, unit
equipped with factory installed supply air, return air, and amperage, and 100% functionality. For the long term - All
outdoor air temperature sensors providing key units are painted with a long lasting, powder paint that
temperature readings thus reduce field installed stands up over the life of the unit. The paint used has
complexity. been proven by a 1000 hour salt spray test.
• On-board USB Port - The new control comes with a long • Full Perimeter Base Rails - The permanently attached
list of features including data logging, current and base rails provide a solid foundation for the entire unit and
previous system faults and software update capabilities protect the unit during shipment. The rails offer rigging
using the on board USB port and common flash drive. holes so that an overhead crane can be used to place the
Energy use monitoring capabilities allow custom tailoring units on a roof.
to allow a system to work more efficiently at all times and • Easy Installation - Gas and electric utility knockouts are
occupancy levels. Self test and start-up reports also supplied in the unit underside as well as the side of the
available from the board VIA the USB port. unit. Utility connections can be made quickly and with a
• Embedded LCD Display - The board has a easy to read, minimum amount of field labor. All units are shipped with
built-in LCD display and easy to use navigation joystick 2" throw-away filters installed.
and buttons allowing the user to quickly navigate the • Wide Range of Indoor Airflows - All supply air blowers
menus displaying unit status, options, current function, are equipped with a belt drive that can be adjusted to
supply, return and outdoor temperatures, fault codes and meet the exact requirements of the job. A high static drive
other information. option is available for applications with a higher CFM and/
• Safety Monitoring - The control monitors the outdoor, or static pressure requirement.
supply, and return air temperatures and the high and low • Warranty - All models include a 1-year limited warranty
pressure switch status on the independent refrigerant on the complete unit. Compressors and electric heater
circuits. On units with heating the gas valve and high elements each carry a 5-year warranty. Aluminized steel
temperature limit switches are monitored on gas and tubular heat exchangers carry a 10 year warranty.
electric heating units. The control also monitors the Stainless steel heat exchangers a 15 year warranty.
voltage supplied to the unit and will protect the unit if low
Factory Installed Options
voltage due to a brown out, or other electrical issue
occurs. YORK® offers several equipment options factory installed, for
• Low Ambient - An integrated low-ambient control allows the ZJ/ZR/ZF Series.
units to operate in the cooling mode down to 0°F outdoor • Dry Bulb Economizers - All units offer a variety of
ambient without additional components or intervention. optional factory installed down flow economizers that are
Optionally, the control board can be programmed to shipped, installed and wired with low leak dampers
lockout the compressors when the outdoor air designed to meet ASHRAE 90.1-2010, AMCA 511 Class
temperature is low or when free cooling is available. 1A damper, and the International Energy Conservation
• Anti-Short Cycle Protection - To aid compressor life, an Code (IECC) certification requirements by achieving
anti- short cycle delay is incorporated into the standard leakage rates of 3 cfm/sq. ft. at 1" of static pressure. Each
control. Compressor reliability is further ensured by economizer goes through a rigorous 60,000 cycle test.
programmable minimum run times. For testing, the anti- Dry bulb, single enthalpy, and dual enthalpy (with field
short cycle delay can be temporarily overridden with the installed kit) can be selected. All economizer options are
push of a button. fully integrated into the Smart Equipment™ controls. The
economizer has spring return, fully modulating damper
• Fan Delays - Fan on and fan off delays are fully actuators and is capable of introducing up to 100%
programmable. Furthermore, the heating and cooling fan outdoor air. As the outdoor air intake dampers open, the
delay times are independent of one another. All units are return air dampers close. The changeover from
programmed with default values based upon their mechanical refrigeration to economizer operation is
configuration of cooling and/or heating capacity. regulated by the outdoor air dry bulb temperature or the
• Nuisance Trip Protection and Three Strikes - To outdoor air enthalpy input. The dual enthalpy kit provides
prevent nuisance calls, the control board uses a three a second input used to monitor the return air (field
times, you're out philosophy. The high, low-pressure installed). The installer needs only to assemble the
switch, anti-freeze protection, low voltage or heating high outdoor air hood, attach the enthalpy control the hood and
limit must trip three times within two hours before the unit
mount the hood to the unit (Hood and control are bracket installed in the Blower Access compartment which
provided). may accommodate other vendor’s drives depending on
• Power Exhaust - Our economizer options are available their size. In order to utilize the unit’s mounting bracket,
with power exhaust. Whenever the outdoor air intake the maximum recommended drive dimensions are as
dampers are opened for free cooling, the exhaust fan will follows:
be energized to prevent the conditioned space from being For 5-hp motor applications ........................13” H x 6” W x 7” D
over-pressurized during economizer operation. For 7.5 thru 15-hp motor applications .........13” H x 8” W x 8” D
The exhaust fan, motor and controls are installed and If the drive will not fit in the allotted space, then it will have
wired at the factory. The rain hood must be assembled to be mounted elsewhere; either within the building on a
and installed in the field. perpendicular wall which is not subjected to excessive
The power exhaust option can only be used on bottom temperature, vibration, humidity, dust, corrosive gas,
duct configurations. explosive gas, etc., or within an appropriate enclosure
• Motorized Outdoor Air Intake Damper - Includes a rated for outside installation to safeguard against
slide-in / plug-in damper assembly with a 2- position, moisture, dust and excessive heat.
spring return motor actuator which opens to a pre-set A terminal block located in the control box is provided for
position whenever the supply air blower is operating and field connection of the VFD controls.
will drive fully closed when the blower unit shuts down. • IntelliSpeed™ Supply Fan Control Option (ASHRAE
The rain hood is painted to match the basic unit and must 90.1 compliant, section 6.4.3.10) - Units configured with
be field assembled before installing. the IntelliSpeed™ Supply Fan Option will contain a VFD
• Barometric Relief Damper - This damper option can be for multi-speed supply fan operation. This option allows
used to relieve internal building air pressure on units with the supply fan RPM to vary based on the number of
an economizer without power exhaust. This accessory compressors or heating stages energized. The
includes a rain hood, a bird screen and a fully assembled economizer's minimum position will also be configurable
damper. With bottom duct connections, the damper to vary based on the supply fan VFD frequency output.
should be mounted over the opening in the return air • Hot Gas Bypass - To allow for low cooling load operation,
panel. With horizontal ductwork, the accessory should be a direct-acting pressure-modulating bypass control valve
mounted on the return air duct. installed on the system #1 discharge line is used to divert
high temperature, high pressure refrigerant around the
• E-Coat Condenser Coils - The condenser coils are
TXV in order to maintain a desired minimum evaporator
coated with an epoxy polymer coating to protect against
pressure. HGBP is standard on all units with VAV and
corrosion.
optional with CV units.
• E-Coat Evaporator Coils - The evaporator coils are
• Filter Options - Standard units are shipped with 2" throw-
coated with an epoxy polymer coating to protect against
away filters installed. 2" pleated and 4" pleated filters are
corrosion.
offered as a factory installed option.
• Variable Air Volume (VAV) - A factory-installed variable
• Convenience Outlet - This 110 volt outlet can be
frequency drive (VFD), mounted in the Blower Access
"powered" by the unit with a stepdown transformer or you
compartment, is used to control the speed of the indoor
may order the unit with a "non-powered" convenience
blower motor in order to maintain a constant static
outlet that can be wired in the field.
pressure in the supply duct. A pressure transducer and
VAV control board are mounted inside the control box. • Disconnect Switch - For gas heat units a HACR breaker
The drive comes completely wired and pre-programmed sized to the unit is provided. For cooling only units, a
from the factory. disconnect switch sized to the largest electric heat (field
installed accessory) available for the particular unit is
An optional, factory-installed manual bypass switch
provided. Factory installed option only.
available with factory-installed VFD can be found in the
Blower Motor Access compartment. The switch can be • Double Wall Construction - Optional double wall
used to either route power to the VFD for modulating construction is available to provide smooth inner surfaces
control of the blower motor, to bypass the drive and for easy and effective cleaning to reduce risk of dirt and
operate the motor at full speed, or to power the drive (and bacterial accumulation. Fiberglass insulation is sandwiched
not the motor) for diagnostic purposes. between heavy gauge steel sheets to form a durable, rigid
casing to withstand higher working pressures and impact
Due to space limitations, VAV is not available with any of
forces. The heavy-duty construction provides excellent
the factory-installed BAS options described below, but is
acoustic and thermal insulation and eliminates erosion of
available with ‘BAS-ready’ models. Terminal blocks are
insulation material and contamination of the air stream.
provided in the control box for field wiring of the customer-
installed BAS. • Smoke Detectors - (supply air & return air) The smoke
detectors stop operation if smoke is detected within the air
A ‘VFD-ready’ option provides the provisions for a
compartment.
customer-installed drive. The unit comes with a mounting
• Flue Exhaust Extension Kit - In locations with wind or need for any additional tools. Verasys creates enhanced
weather conditions which may interfere with proper integration of HVACR equipment, zoning, and controls.
exhausting of furnace combustion products, this kit can be Contractors are able to offer a complete bundled solution
installed to prevent the flue exhaust from entering nearby of equipment and controls to serve the light commercial
fresh air intakes. market.
• Wood Skid - Allows unit to be handled with 90" forks.
• CO2 Sensor - Senses CO2 levels and automatically Guide Specifications
overrides the economizer when levels rise above the
present limits. General
• Coil Guard - Customers can purchase a coil guard kit to
Units shall be manufactured by Johnson Controls Unitary
protect the condenser coil from damage. This is not a hail
Products in an ISO 9001 certified facility.
guard kit.
• Phase Monitors - Designed to prevent unit damage. The York's ZJ/ZR/ZF units are convertible single package units. ZJ
phase monitor will shut the unit down in an out-of phase models have four independent refrigerant circuits and ZR/ZF
condition. models have dual independent refrigerant circuits for efficient
• Electric Heaters - wired for single point power supply. part load operation and maximum comfort control. Although the
These nickel chromium heater elements are provided with units are primarily designed for curb mounting on a roof, they
limit and automatic reset capability to prevent operation at can also be slab-mounted at ground level or set on steel beams
excessive temperatures. above a finished roof. Cooling only and cooling with gas heat
models are available with a wide variety of factory-mounted
Control Options options and field-installed accessories to make them suitable
Smart Equipment™ with Communication Option for almost every application. All units are self-contained and
Control - The York® Smart Equipment™ with assembled on full perimeter base rails with holes in the four
Communication Option Control is factory installed. It corners for overhead rigging. Every unit is completely piped,
includes all the features of the Smart Equipment™ control wired, charged and tested at the factory to simplify the field
with an additional gateway to BACnet MS/TP installation and to provide years of dependable operation. All
(programmable to Modbus or N2 protocols). models (including those with an economizer) are suitable for
either bottom or horizontal duct connections. Models with power
FDD (Fault Detection and Diagnostics) - Refrigerant
exhaust are suitable for bottom duct connections only. For
side A factory installed control system option on the
bottom duct, remove the sheet metal panels from the supply
commercial equipment that constantly monitors
and return air openings through the base of the unit. For
refrigerant circuit pressures, refrigerant circuit
horizontal duct, replace the supply and return air panels on the
temperatures, as well as the environmental temperatures
rear of the unit with a side duct flange accessory. All supply air
and humidity via multiple sensor inputs.
blowers are equipped with a belt drive that can be adjusted to
• Provides a building owner, technician or contractor with meet the exact requirements of the job. A high static drive
the operational characteristics of the RTUs entire option is available for applications with a higher CFM and/or
refrigerant circuit to ensure the unit is functioning at its static pressure requirement.
specified performance level.
ZJ/ZR models have 4 condenser fan motors and ZF models
• Provides alarms if the unit is not functioning optimally.
have 2 condenser fan motors. All compressors include
• Remotely accessible via the Mobile Access Portal crankcase heat and internal pressure relief. Every refrigerant
(MAP) gateway as well as scrolled on the UCB LCD circuit includes an expansion valve, a liquid line filter-drier, a
screen. discharge line high pressure switch and a suction line with a
freezestat and low pressure/loss of charge switch. The unit
Novar® BAS Control - The Novar® building automation
control circuit includes a 75 VA transformer, a 24-volt circuit
system controller is factory installed. Includes supply air
breaker and a relay board with two compressor lockout circuits,
sensor, return air sensor, dirty filter indicator switch, and
a terminal strip for thermostat wiring, plus an additional set of
air proving switch.
pin connectors to simplify the interface of additional field
CPC BAS Control - The Computer Process Controls controls. All units have long lasting powder paint cabinets with
Model 810-3060 ARTC Advanced Rooftop building 1000 hour salt spray test approval under ASTM-B117
automation system controller is factory installed. Includes procedures. All models are CSA approved. All models include a
supply air sensor, return air sensor, with optional dirty 1-year limited warranty on the complete unit. Compressors and
filter indicator switch and air proving switch. electric heater elements carry an additional 4-year warranty.
Honeywell BAS Control - The Honeywell W7750C Aluminized steel tubular heat exchangers carry an additional 9-
building automation system controller is factory installed. year warranty.
Includes air supply sensor, return air sensor, with optional
dirty filter indicator switch, and air proving switch. Description
Verasys - Verasys provides a simple user experience ZJ units shall be factory-assembled, single packaged, ZJ***N
with configurable self-recognizing controllers without the Electric Cooling/Gas Heat, ZJ***C00 Electric Cooling/Field
Installed Electric Heat Accessory designed for outdoor mounted shall not exceed the motors nameplate horsepower rating, plus
installation. The 15 ton unit shall have a minimum EER rating of the service factor. Units shall be designed not to operate above
12.2. The 17.5 ton unit shall have a minimum EER rating of service factor. Fan wheel shall be double-inlet type with
12.1. The 20 ton unit shall have a minimum EER rating of 11.0. forward-curved blades, dynamically balanced to operate
The 25 ton unit shall have a minimum EER rating of 10.6. smoothly throughout the entire range of operation. Airflow
design shall be constant air volume.
ZR units shall be factory-assembled, single packaged, ZR***N
Electric Cooling/Gas Heat, ZR***C00 Electric Cooling/Field A variable air volume (VAV) option using a variable frequency
Installed Electric Heat Accessory designed for outdoor mounted drive (VFD) is available for applications requiring a constant
installation. The 15 ton unit shall have a minimum EER rating of supply duct static pressure. Units equipped for VAV shall be
11.2. The 20 ton unit shall have a minimum EER rating of 11.0. controlled by a duct pressure transducer with a 0 - 5” WC
The 25 ton unit shall have a minimum EER rating of 10.0. pressure range. The pressure transducer shall provide a 0 - 5
VDC output signal to a VAV control board which, in turn shall
ZF units shall be factory-assembled, single packaged, ZF***N provide a 2 - 10 VDC speed reference signal to the VFD. The
Electric Cooling/Gas Heat, ZF***C00 Electric Cooling/Field VAV control board shall operate using factory-installed Supply
Installed Electric Heat Accessory designed for outdoor mounted Air, Return Air and Outside Air Temperature Sensors. Units
installation. The 15 and 17.5 ton units shall have a minimum equipped with VFD’s shall have factory-installed manual bypass
EER rating of 11.0. The 20 and 25 ton units shall have a as an option.
minimum EER rating of 10.
Outdoor (Condenser) Fan Assembly
They shall have built-in field convertible duct connections for
down discharge supply/return or horizontal discharge supply/ The outdoor fans shall be of the direct-driven propeller type,
return, and be available with factory installed options or field discharge air vertically, have aluminum blades riveted to
installed accessories. The units shall be factory wired, piped, corrosion resistant steel spider brackets and shall be
charged with R-410A refrigerant and factory tested prior to dynamically balanced for smooth operation. The 4 outdoor fan
shipment. All unit wiring shall be both numbered and color motors shall be totally enclosed with permanently lubricated
coded. All units shall be manufactured in a facility certified to bearings, internally protected against overload conditions and
ISO 9001 standards and the cooling performance shall be rated staged independently.
in accordance with DOE and AHRI test procedures. Units shall
be CSA listed, classified to ANSIZ21.47 standards, UL 1995/ Refrigerant Components
CAN/CSA No. 236-M90 conditions.
Compressors:
Unit Cabinet a. Shall be Scroll compressors internally protected with
internal high-pressure relief and over temperature
Unit cabinet shall be constructed of galvanized steel, with
protection.
exterior surfaces coated with a non-chalking, powdered paint
finish, certified at 1000 hours salt spray test per ASTM-B117 b. Shall have internal spring isolation and sound muffling to
standards. Indoor blower section shall be insulated with a minimize vibration and noise, and be externally isolated
minimum 1/2" thick insulation, coated on the airside. Aluminum on a dedicated, independent mounting.
foil faced insulation shall be used in the furnace compartment Coils:
and be fastened with ridged fasteners to prevent insulation from
entering the air stream. Cabinet panels shall be "large" size, a. Evaporator and condenser coils shall have aluminum
easily removable for servicing and maintenance. Full perimeter plate fins mechanically bonded to seamless internally
base rails shall be provided to assure reliable transit of enhanced copper tubes with all joints brazed. Special
equipment, overhead rigging and proper sealing on roof curb Phenolic coating shall be available as a factory option.
applications. Disposable 2" filters shall be furnished and be b. Evaporator and Condenser coils shall be of the direct
accessible through a removable access door, sealed airtight. expansion, draw-thru, design.
Units filter track shall be designed to accommodate either 2" or
Refrigerant Circuit and Refrigerant Safety Components shall
4" filters. Fan performance measuring ports shall be provided
include:
on the outside of the cabinet to allow accurate air
measurements of evaporator fan performance without removing a. Balance-port thermostatic expansion valve with
panels or creating air by-pass of the coils. Condensate pan independent circuit feed system.
shall be internally sloped and conform to ASHRAE 62-89 self- b. Filter drier/strainer to eliminate any moisture or foreign
draining standards. Condensate connection shall be a minimum matter.
of 1" I.D. female and be a ridged mount connection. Unit shall
incorporate a fixed outdoor air damper with an outdoor air c. Accessible service gage connections on both suction
intake opening covered with a bird screen and a rain hood and discharge lines to charge, evacuate, and measure
painted to match the exterior of the unit. refrigerant pressure during any necessary servicing or
troubleshooting, without losing charge.
Indoor (Evaporator) Fan Assembly d. The refrigeration system shall provide at least 15° F of
sub-cooling at design conditions.
Fan shall be a belt drive assembly and include an adjustable-
pitch motor pulley. Job site selected (B.H.P.) brake horsepower e. All models shall have four independent circuits.
f. Hot gas bypass option shall be factory-installed on required, from 13.5 KW to 72 KW capacities. The heating
compressor #1 discharge line to provide cooling in low- section shall have a primary limit control(s) and automatic reset
load applications. HGBP shall be a standard feature on to prevent the heating element system from operating at an
VAV models and an optional feature on CV models. excessive temperature. Units with Electric Heating shall be
wired for a single point power supply with branch circuit fusing
Unit Controls (where required).
a. Unit shall be complete with self-contained low-voltage
Unit Operating Characteristics
control circuit protected by a resettable circuit breaker on
the 24-volt transformer side. Unit shall be capable of starting and running at 125° F outdoor
b. Unit shall incorporate a lockout circuit which provides temperature, exceeding maximum load criteria of AHRI
reset capability at the space thermostat or base unit, Standard 340/360. The compressor, with standard controls,
should any of the following standard safety devices trip shall be capable of operation down to 25° F outdoor
and shut off compressor. temperature. Accessory low ambient kit shall be available for
operation to 0° F. Unit shall be provided with fan time delay to
c. Loss-of-charge/Low-pressure switch. prevent cold air delivery before heat exchanger warms up (Gas
1. High-pressure switch. heat only).
2. Freeze condition sensor, evaporator coil. If any of
these safety devices trip, the LCD screen will display Electrical Requirements
the alarm message. All unit power wiring shall enter unit cabinet at a single factory
d. Unit shall incorporate "AUTO RESET" compressor over provided location and be capable of side or bottom entry, to
temperature, over current protection. minimize roof penetrations and avoid unit field modifications.
Separate side and bottom openings shall be provided for the
e. Unit shall operate with conventional thermostat designs control wiring.
and have a low voltage terminal strip for easy hook-up.
Standard Limited Warranties
f. Unit control board shall have on-board diagnostics and
fault message display. • Compressor 5 Years
g. Standard controls shall include anti-short cycle and low • Heat Exchanger 10 Years
voltage protection, and permit cooling operation down to • Electric Heat Element 5 Years
0 °F. • Other Parts 1 Year
h. Control board shall monitor each refrigerant safety switch
independently. Optional Outdoor Air (Shall be made available by either/or):
one of two pre-selected positions - regardless of the • Burglar Bars - Designed to work with above roof curbs,
outdoor air enthalpy. Dampers return to the fully closed depending on unit model. Fits duct openings of curb
position when the indoor fan motor is de-energized. supply and return air openings.
Dampers shall fully close on power loss. • Side Duct Flange - Supply and return air duct flanges for
side duct applications. Do not use on units with power
Other Factory Installed Options
exhaust.
• Power Exhaust Option - To work in conjunction with • High Static Drive - May include a belt, blower pulley,
economizers. motor pulley or a motor change to enhance blower
• Stainless Steel Heat Exchanger performance.
• Stainless Steel Drain Pan • Wood Skid - Allows unit to be handled with 90" forks.
• E-Coat Epoxy Polymer Coated Condenser And • Economizer/motorized Damper Rain Hood
Evaporator Coil (ZJ/ZR/ZFN/C300 only) - Contains all hood panels and
• Electronic Single Enthalpy Economizer the hardware for assembling.
• Dirty Filter Switch • Anti-Recycle Timer - Assures 5-minute off time between
compressor cycles.
• Double Wall
• Low Ambient Kit - Provides unit cooling operation down
• Phase Monitor
to 0 °F.
• Coil Guard
• Coil Guard Kit - Guard for cooling coil.
• Powered GFI Convenience Outlet
• Non-powered GFI Convenience Outlet • Electric Heat Accessory - (Field Installed Only)
• BAS Controls - Smart Equipment™ with BAS
Hot Gas Reheat
Communication (BACnet MS/TP, Modbus, and Johnson
Controls N2) Option, CPC, HONEYWELL, NOVAR, Setpoints and Related Data
Verasys, FDD
• BAS Ready Economizer (2-10 V.D.C. Actuator With Setpoints and related data includes:
Smart Equipment™ Controller)
• Hot Gas Reheat Alternate Operation Enabled (HGRAlt-
• Hinged Filter Door Access And Tool Free Access En)
Panels
• Hot Gas Reheat Enabled for Operation (HGR-En)
• Hinged Tool Free Blower, Blower Motor, Filter And
• Hot Gas Reheat Alternate Operation Writable
Electrical Access Panels
(HGRAltWrite)
• High Static Drive
• Hot Gas Reheat Humidity Setpoint (HGRHum-Sp)
• Low Static Drive (ZJ/ZR/ZF300 only)
• HGR Unoccupied Humidity Setpoint (HGRUnoccHum-Sp)
• 2" Pleated Filters, MERV 8
• HGR Enabled for Unoccupied Operation (HGRUnocc-En)
• 4" Pleated Filters, MERV 13
• Disconnect Switch Inputs
• Supply Air Smoke Detector
Inputs include:
• Return Air Smoke Detector
• Operational space humidity (OprSH)
Other Pre-engineered Accessories Available
• Roof Curb - 14" high, full perimeter curb with wood nailer Outputs
(shipped knocked-down).
• Outputs include:
• 100% Barometric Relief Damper - Contains a rain hood,
air inlet screen, exhaust damper and mounting hardware. • 24 VAC from AUX-HGR to energize the hot gas reheat
Used to relieve internal air pressure through the unit. solenoid. 24 VAC from C1 or C2 to energize compressor
contactors
• Propane Conversion Kit - Contains new orifices and gas
valve parts to convert from natural to L.P. gas. One per
Operation For ZR Units Only
unit required.
• High Altitude - Natural Gas - Contains orifices required Normal Occupied Operation Mode
for applications between 2000 and 6000 feet altitude.
If the return humidity is greater than or equal to the Hot Gas
• High Altitude - Propane Gas - Contains orifices required
Reheat Humidity Setpoint, and no demand for cooling, C1
for applications between 2000 and 6000 feet altitude.
output energizes and the AUX-HGR output energizes.
Must be used with propane conversion kit.
If there is a demand for one stage of cooling and the return
humidity is greater than or equal to the Hot Gas Reheat
Humidity Setpoint, C1 output energizes but the AUX-HGR If there is a demand for both first and second cooling stages
output de-energizes. and the return humidity is greater than or equal to the Hot Gas
Reheat Humidity Setpoint, C1 and C2 outputs energize and
Any additional cooling demands energize compressor outputs, AUX-HGR de-energizes.
but do not change the status of the AUX-HGR output.
When the return humidity falls to 3% or more below the
When the return humidity falls to 3% or more below the setpoint, the C1, C2, and AUX-HGR outputs de-energize.
setpoint, the C1 and AUX-HGR outputs de-energize.
NOTE: If HGR Enabled for Unoccupied Operation is enabled,
NOTE: If HGR Enabled for Unoccupied Operation is enabled, during unoccupied mode the control works the same as
during unoccupied mode the control works the same as described above, except it uses the HGR Unoccupied
described above, except it uses the HGR Unoccupied Humidity Setpoint instead.
Humidity Setpoint instead.
Dehumidification Sequence in Normal and Alternate
Alternate Mode Mode
Normal Mode Alternate Mode
If the return humidity is greater than or equal to the Hot Gas Request
Reheat Humidity Setpoint, and no demand for cooling, C1 and HGR C1 C2 HGR C1 C2
AUX-HGR outputs energize, and C2 energizes. Dehumidification On On Off On On Off
One Stage of Cooling (Y1) Off On Off On On On
If there is a demand for one stage of cooling and the return
humidity is greater than or equal to the Hot Gas Reheat Two Stages of Cooling (Y2) Off On On Off On On
Humidity Setpoint, C1 and AUX-HGR outputs energize, and C2
energizes.
Physical Data
Capacity Performance
ZJ180-300 Cooling Capacities
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Airflow Performance
ZJ180-300 Side Duct Application
Standard 10 HP
7400 806 4.14 838 4.58 870 5.00 901 5.39 933 5.76 964 6.12 996 6.45 1028 6.78
7800 833 4.78 865 5.22 897 5.63 928 6.03 959 6.40 991 6.75 1023 7.09 1055 7.41
& Drive
8200 861 5.47 893 5.91 925 6.33 956 6.72 988 7.09 1019 7.45 1051 7.78 1083 8.11
8600 891 6.23 923 6.67 955 7.08 986 7.47 1018 7.85 1049 8.20 1081 8.54 1113 8.86
9000 922 7.05 955 7.48 986 7.90 1018 8.29 1049 8.66 1080 9.02 1112 9.36 1145 9.68
9400 955 7.93 987 8.37 1019 8.78 1050 9.17 1082 9.54 1113 9.90 1145 10.24 1177 10.56
9800 989 8.87 1021 9.31 1053 9.73 1084 10.12 1115 10.49 1147 10.84 1179 11.18 1211 11.51
10200 1024 9.88 1056 10.32 1088 10.74 1119 11.13 1150 11.50 1182 11.86 1214 12.19 1246 12.52
10600 1060 10.96 1092 11.40 1124 11.81 1155 12.20 1186 12.58 1218 12.93 1250 13.27 1282 13.59
11000 1096 12.10 1129 12.54 1160 12.95 1192 13.34 1223 13.72 1255 14.07 1286 14.41 1319 14.73
11400 1134 13.30 1166 13.74 1198 14.16 1230 14.55 1261 14.92 1292 15.27 1324 15.61 1357 15.94
11800 1173 14.57 1205 15.01 1237 15.42 1268 15.82 1299 16.19 1331 16.54 1363 16.88 1395 17.20
12200 1212 15.90 1244 16.34 1276 16.75 1308 17.14 - - - - - - - -
15 HP &
Field
High Static 15 HP & Drive
Supplied
Drive
RPM Selection
Size Max Motor Blower 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn Fully
Model HP
(Tons) BHP Sheave Sheave Open Open Open Open Open Open Closed
180 5 5.75 1VP65 BK110 815 850 885 920 950 985 N/A
ZJ/ZF
(15) 5 5.75 1VP65 BK090 1010 1055 1095 1135 1180 1220 N/A
210 5 5.75 1VP60 BK110 730 765 800 835 870 905 N/A
ZJ/ZF
(17.5) 7.5 8.63 1VP60 BK090 905 950 990 1035 1075 1120 N/A
240 5 5.75 1VP60 BK110 730 765 800 835 870 905 N/A
ZJ/ZF
(20) 7.5 8.63 1VP60 BK090 905 950 990 1035 1075 1120 N/A
7.5 8.63 1VP60 1B5V94 810 850 885 920 960 1000 N/A
300
ZJ/ZF 10 11.50 1VP75X 1B5V110 975 1005 1040 1070 1100 1135 1165
(25)
15 17.25 1VP75X 1B5V94 1140 1180 1215 1255 1290 1330 1365
180 5 5.75 1VP65 BK110 815 850 885 920 950 985 N/A
ZR
(15) 7.5 8.63 1VP65 BK090 1010 1055 1095 1135 1180 1220 N/A
240 7.5 8.63 1VP60 BK110 730 765 800 835 870 905 N/A
ZR
(20) 10 11.50 1VP60 BK090 905 950 990 1035 1075 1120 N/A
7.5 8.63 1VP60 1B5V94 810 850 885 920 960 1000 N/A
300
ZR 10 11.50 1VP75X 1B5V110 975 1005 1040 1070 1100 1135 1165
(25)
15 17.25 1VP75X 1B5V94 1140 1180 1215 1255 1290 1330 1365
Drive Selection
1. 6800 CFM
2. 2.0 iwg
3. Using the supply air blower performance table below, the following data point was located: 1020 RPM & 5.92 BHP.
4. Using the RPM selection table below, Size X and Model Y is found.
5. 5.92 BHP exceeds the maximum continuous BHP rating of the 5.0 HP motor. The 7.5 HP motor is required.
6. 1020 RPM is within the range of the 7.5 HP drives.
7. Using the 7.5 HP motor and drive, 3.5 turns open will achieve 1020 RPM.
1.100
1.050
1.000
Sea Level
0.950
Correction Factor
1000 ft
0.900 2000 ft
3000 ft
0.850
4000 ft
0.800 5000 ft
6000 ft
0.750 7000 ft
8000 ft
0.700
9000 ft
10000 ft
0.650
0.600
40 50 60 70 80 90 100
Air Temperature (ºF)
For units with VFD and gas heat, the speed of the indoor
blower motor continues to be controlled by duct static
pressure via the VAV control board.
If there are VAV boxes present in the duct system,
the boxes must be driven to the full-open position
using a customer-supplied power source to assure
adequate airflow across electric heating elements
or gas heat exchanger tubes.
For units with VFD and electric heat, the speed of the
indoor blower motor continues to be controlled by duct
static pressure via the VAV control board.
If there are VAV boxes present in the duct system,
the boxes must be driven to the full-open position
using a customer-supplied power source to assure
adequate airflow across electric heating elements
or gas heat exchanger tubes.
Sound Performance
ZJ/ZR/ZF Indoor Sound Power Levels
Sound Power, dB (10-12) Watts
Size ESP Blower 1
CFM Sound Rating Octave Band Centerline Frequency (Hz)
(Tons) (IWG)
RPM BHP dB (A) 63 125 250 500 1000 2000 4000 8000
180 (15) 6000 1.0 1,080 4.6 91 88 90 90 87 85 81 81 76
210 (17.5) 7000 1.0 940 5.1 85 84 84 82 81 81 77 74 69
240 (20) 8000 1.0 1,020 6.6 86 85 85 83 82 82 78 75 70
300 (25) 10000 1.3 1,160 12.5 92 91 91 89 88 88 84 81 76
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric/free field. The dBA values
provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacturer has no way
of knowing the details of each system. This constitutes an exception to any specification or guarantee requiring a dBA value of sound data
in any other form than sound power level ratings.
Electrical Data
ZJ180 - 300
ZJ180-300 - Standard Drive Without Powered Convenience Outlet
Compressors
OD Fan Supply Pwr
Electric Heat Max Fuse2/
Size (each)
Motors Blower Conv
(Field Installed Accessory Only) MCA1 Breaker3
Volt (each) Motor Outlet
(Tons) (Amps) Size
RLA LRA MCC FLA FLA FLA Model kW Stages Amps (Amps)
NONE - - - 77.7 90
E18 13.5 1 37.5 77.7 90
208-3-60 13.1 83.1 20.5 2.1 13.5 0 E36 27 2 74.9 110.6 125
E54 40.6 2 112.7 157.7 175
E72 54.1 2 150.2 167 200
NONE - - - 77.1 90
E18 18 1 43.3 77.1 90
230-3-60 13.1 83.1 20.5 2.1 13 0 E36 36 2 86.6 124.5 125
E54 54 2 129.9 146.2 175
180 E72 72 2 173.2 189.5 225
(15) NONE - - - 37.6 40
E18 18 1 21.7 37.6 40
460-3-60 6.1 41 9.5 1.26 6.5 0 E36 36 2 43.3 62.3 70
E54 54 2 65 73.1 80
E72 72 2 86.6 94.7 110
NONE - - - 26.7 30
E18 18 1 17.3 28.2 30
575-3-60 4.4 33 6.8 0.66 5.2 0 E36 36 2 34.6 49.8 50
E54 54 2 52 58.5 70
E72 72 2 69.3 75.8 90
NONE - - - 83.5 90
E18 13.5 1 37.5 83.5 90
208-3-60 14.5 98 22.6 2.1 13.5 0 E36 27 2 74.9 110.6 125
E54 40.6 2 112.7 157.7 175
E72 54.1 2 150.2 167 200
NONE - - - 83 90
E18 18 1 43.3 83 90
230-3-60 14.5 98 22.6 2.1 13 0 E36 36 2 86.6 124.5 125
E54 54 2 129.9 146.2 175
210 E72 72 2 173.2 189.5 225
(17.5) NONE - - - 38.4 40
E18 18 1 21.7 38.4 40
460-3-60 6.3 55 9.9 1.26 6.5 0 E36 36 2 43.3 62.3 70
E54 54 2 65 73.1 80
E72 72 2 86.6 94.7 110
NONE - - - 33.3 35
E18 18 1 17.3 33.3 35
575-3-60 6 41 9.4 0.66 5.2 0 E36 36 2 34.6 49.8 50
E54 54 2 52 58.5 70
E72 72 2 69.3 75.8 90
Compressors
OD Fan Supply Pwr
Electric Heat Max Fuse2/
Size (each)
Motors Blower Conv
(Field Installed Accessory Only) MCA1 Breaker3
Volt (each) Motor Outlet
(Tons) (Amps) Size
RLA LRA MCC FLA FLA FLA Model kW Stages Amps (Amps)
NONE - - - 88.6 100
E18 13.5 1 37.5 88.6 100
208-3-60 15.6 110 24.4 2.2 13.5 0 E36 27 2 74.9 110.6 125
E54 40.6 2 112.7 157.7 175
E72 54.1 2 150.2 167 200
NONE - - - 88.1 100
E18 18 1 43.3 88.1 100
230-3-60 15.6 110 24.4 2.2 13 0 E36 36 2 86.6 124.5 125
E54 54 2 129.9 146.2 175
240 E72 72 2 173.2 189.5 225
(20) NONE - - - 44.1 50
E18 18 1 21.7 44.1 50
460-3-60 7.8 52 12.1 1.1 6.5 0 E36 36 2 43.3 62.3 70
E54 54 2 65 73.1 80
E72 72 2 86.6 94.7 110
NONE - - - 33.5 35
E18 18 1 17.3 33.5 35
575-3-60 5.8 38.9 9.1 0.9 5.2 0 E36 36 2 34.6 49.8 50
E54 54 2 52 58.5 70
E72 72 2 69.3 75.8 90
NONE - - - 130.9 150
E18 13.5 1 37.5 130.9 150
208-3-60 22.4 149 35 2.2 26 0 E36 27 2 74.9 130.9 150
E54 40.6 2 112.7 173.4 175
E72 54.1 2 150.2 182.7 200
NONE - - - 129.7 150
E18 18 1 43.3 129.7 150
230-3-60 22.4 149 35 2.2 25 0 E36 36 2 86.6 139.5 150
E54 54 2 129.9 161.2 175
300 E72 72 2 173.2 204.5 225
(25) NONE - - - 62.4 70
E18 18 1 21.7 62.4 70
460-3-60 10.6 75 16.5 1.1 12.5 0 E36 36 2 43.3 69.8 70
E54 54 2 65 80.6 90
E72 72 2 86.6 102.2 110
NONE - - - 46.9 50
E18 18 1 17.3 46.9 50
575-3-60 7.7 54 12 0.9 10 0 E36 36 2 34.6 55.8 60
E54 54 2 52 64.5 70
E72 72 2 69.3 81.8 90
Compressors
OD Fan Supply Pwr
Electric Heat Max Fuse2/
Size (each)
Motors Blower Conv
(Field Installed Accessory Only) MCA1 Breaker3
Volt (each) Motor Outlet
(Tons) (Amps) Size
RLA LRA MCC FLA FLA FLA Model kW Stages Amps (Amps)
NONE - - - 87.7 100
E18 13.5 1 37.5 87.7 100
208-3-60 13.1 83.1 20.5 2.1 13.5 10 E36 27 2 74.9 123.1 125
E54 40.6 2 112.7 170.2 175
E72 54.1 2 150.2 179.5 200
NONE - - - 87.1 100
E18 18 1 43.3 87.1 100
230-3-60 13.1 83.1 20.5 2.1 13 10 E36 36 2 86.6 137 150
E54 54 2 129.9 158.7 175
180 E72 72 2 173.2 202 225
(15) NONE - - - 42.6 45
E18 18 1 21.7 42.6 45
460-3-60 6.1 41 9.5 1.26 6.5 5 E36 36 2 43.3 68.5 70
E54 54 2 65 79.3 90
E72 72 2 86.6 101 110
NONE - - - 30.7 35
E18 18 1 17.3 33.2 35
575-3-60 4.4 33 6.8 0.66 5.2 4 E36 36 2 34.6 54.8 60
E54 54 2 52 63.5 70
E72 72 2 69.3 80.8 90
NONE - - - 93.5 100
E18 13.5 1 37.5 93.5 100
208-3-60 14.5 98 22.6 2.1 13.5 10 E36 27 2 74.9 123.1 125
E54 40.6 2 112.7 170.2 175
E72 54.1 2 150.2 179.5 200
NONE - - - 93 100
E18 18 1 43.3 93 100
230-3-60 14.5 98 22.6 2.1 13 10 E36 36 2 86.6 137 150
E54 54 2 129.9 158.7 175
210 E72 72 2 173.2 202 225
(17.5) NONE - - - 43.4 45
E18 18 1 21.7 43.4 45
460-3-60 6.3 55 9.9 1.26 6.5 5 E36 36 2 43.3 68.5 70
E54 54 2 65 79.3 90
E72 72 2 86.6 101 110
NONE - - - 37.3 40
E18 18 1 17.3 37.3 40
575-3-60 6 41 9.4 0.66 5.2 4 E36 36 2 34.6 54.8 60
E54 54 2 52 63.5 70
E72 72 2 69.3 80.8 90
NONE - - - 98.6 110
E18 13.5 1 37.5 98.6 110
208-3-60 15.6 110 24.4 2.2 13.5 10 E36 27 2 74.9 123.1 125
E54 40.6 2 112.7 170.2 175
E72 54.1 2 150.2 179.5 200
NONE - - - 98.1 110
E18 18 1 43.3 98.1 110
230-3-60 15.6 110 24.4 2.2 13 10 E36 36 2 86.6 137 150
E54 54 2 129.9 158.7 175
240 E72 72 2 173.2 202 225
(20) NONE - - - 49.1 50
E18 18 1 21.7 49.1 50
460-3-60 7.8 52 12.1 1.1 6.5 5 E36 36 2 43.3 68.5 70
E54 54 2 65 79.3 90
E72 72 2 86.6 101 110
NONE - - - 37.5 40
E18 18 1 17.3 37.5 40
575-3-60 5.8 38.9 9.1 0.9 5.2 4 E36 36 2 34.6 54.8 60
E54 54 2 52 63.5 70
E72 72 2 69.3 80.8 90
Compressors
OD Fan Supply Pwr
Electric Heat Max Fuse2/
Size (each)
Motors Blower Conv
(Field Installed Accessory Only) MCA1 Breaker3
Volt (each) Motor Outlet
(Tons) (Amps) Size
RLA LRA MCC FLA FLA FLA Model kW Stages Amps (Amps)
NONE - - - 140.9 150
E18 13.5 1 37.5 140.9 150
208-3-60 22.4 149 35 2.2 26 10 E36 27 2 74.9 140.9 150
E54 40.6 2 112.7 185.9 200
E72 54.1 2 150.2 195.2 200
NONE - - - 139.7 150
E18 18 1 43.3 139.7 150
230-3-60 22.4 149 35 2.2 25 10 E36 36 2 86.6 152 175
E54 54 2 129.9 173.7 175
300 E72 72 2 173.2 217 225
(25) NONE - - - 67.4 70
E18 18 1 21.7 67.4 70
460-3-60 10.6 75 16.5 1.1 12.5 5 E36 36 2 43.3 76 80
E54 54 2 65 86.8 90
E72 72 2 86.6 108.5 110
NONE - - - 50.9 60
E18 18 1 17.3 50.9 60
575-3-60 7.7 54 12 0.9 10 4 E36 36 2 34.6 60.8 70
E54 54 2 52 69.5 70
E72 72 2 69.3 86.8 90
Compressors
OD Fan Supply Pwr
Electric Heat Max Fuse2/
Size (each)
Motors Blower Conv
(Field Installed Accessory Only) MCA1 Breaker3
Volt (each) Motor Outlet
(Tons) (Amps) Size
RLA LRA MCC FLA FLA FLA Model kW Stages Amps (Amps)
NONE - - - 77.7 90
E18 13.5 1 37.5 77.7 90
208-3-60 13.1 83.1 20.5 2.1 13.5 0 E36 27 2 74.9 110.6 125
E54 40.6 2 112.7 157.7 175
E72 54.1 2 150.2 167 200
NONE - - - 77.1 90
E18 18 1 43.3 77.1 90
230-3-60 13.1 83.1 20.5 2.1 13 0 E36 36 2 86.6 124.5 125
E54 54 2 129.9 146.2 175
180 E72 72 2 173.2 189.5 225
(15) NONE - - - 37.6 40
E18 18 1 21.7 37.6 40
460-3-60 6.1 41 9.5 1.26 6.5 0 E36 36 2 43.3 62.3 70
E54 54 2 65 73.1 80
E72 72 2 86.6 94.7 110
NONE - - - 26.7 30
E18 18 1 17.3 28.2 30
575-3-60 4.4 33 6.8 0.66 5.2 0 E36 36 2 34.6 49.8 50
E54 54 2 52 58.5 70
E72 72 2 69.3 75.8 90
NONE - - - 91.4 110
E18 13.5 1 37.5 91.4 110
208-3-60 14.5 98 22.6 2.1 20 0 E36 27 2 74.9 118.7 125
E54 40.6 2 112.7 165.9 175
E72 54.1 2 150.2 175.2 200
NONE - - - 90.7 110
E18 18 1 43.3 90.7 110
230-3-60 14.5 98 22.6 2.1 19.4 0 E36 36 2 86.6 132.5 150
E54 54 2 129.9 154.2 175
210 E72 72 2 173.2 197.5 225
(17.5) NONE - - - 42.4 50
E18 18 1 21.7 42.4 50
460-3-60 6.3 55 9.9 1.26 9.7 0 E36 36 2 43.3 66.3 70
E54 54 2 65 77.1 90
E72 72 2 86.6 98.7 110
NONE - - - 36.4 40
E18 18 1 17.3 36.4 40
575-3-60 6 41 9.4 0.66 7.8 0 E36 36 2 34.6 53.1 60
E54 54 2 52 61.7 70
E72 72 2 69.3 79 90
NONE - - - 96.2 110
E18 13.5 1 37.5 96.2 110
208-3-60 15.6 110 24.4 2.2 20 0 E36 27 2 74.9 118.7 125
E54 40.6 2 112.7 165.9 175
E72 54.1 2 150.2 175.2 200
NONE - - - 95.5 110
E18 18 1 43.3 95.5 110
230-3-60 15.6 110 24.4 2.2 19.4 0 E36 36 2 86.6 132.5 150
E54 54 2 129.9 154.2 175
240 E72 72 2 173.2 197.5 225
(20) NONE - - - 47.7 50
E18 18 1 21.7 47.7 50
460-3-60 7.8 52 12.1 1.1 9.7 0 E36 36 2 43.3 66.3 70
E54 54 2 65 77.1 90
E72 72 2 86.6 98.7 110
NONE - - - 36.6 40
E18 18 1 17.3 36.6 40
575-3-60 5.8 38.9 9.1 0.9 7.8 0 E36 36 2 34.6 53.1 60
E54 54 2 52 61.7 70
E72 72 2 69.3 79 90
Compressors
OD Fan Supply Pwr
Electric Heat Max Fuse2/
Size (each)
Motors Blower Conv
(Field Installed Accessory Only) MCA1 Breaker3
Volt (each) Motor Outlet
(Tons) (Amps) Size
RLA LRA MCC FLA FLA FLA Model kW Stages Amps (Amps)
NONE - - - 144.9 175
E18 13.5 1 37.5 144.9 175
208-3-60 22.4 149 35 2.2 37.2 0 E36 27 2 74.9 144.9 175
E54 40.6 2 112.7 187.4 200
E72 54.1 2 150.2 196.7 225
NONE - - - 141.7 175
E18 18 1 43.3 141.7 175
230-3-60 22.4 149 35 2.2 34.6 0 E36 36 2 86.6 151.5 175
E54 54 2 129.9 173.2 200
300 E72 72 2 173.2 216.5 250
(25) NONE - - - 68.4 80
E18 18 1 21.7 68.4 80
460-3-60 10.6 75 16.5 1.1 17.3 0 E36 36 2 43.3 75.8 80
E54 54 2 65 86.6 100
E72 72 2 86.6 108.2 125
NONE - - - 52.5 60
E18 18 1 17.3 52.5 60
575-3-60 7.7 54 12 0.9 14.5 0 E36 36 2 34.6 61.4 70
E54 54 2 52 70.1 80
E72 72 2 69.3 87.4 100
Compressors
OD Fan Supply Pwr
Electric Heat Max Fuse2/
Size (each)
Motors Blower Conv
(Field Installed Accessory Only) MCA1 Breaker3
Volt (each) Motor Outlet
(Tons) (Amps) Size
RLA LRA MCC FLA FLA FLA Model kW Stages Amps (Amps)
NONE - - - 87.7 100
E18 13.5 1 37.5 87.7 100
208-3-60 13.1 83.1 20.5 2.1 13.5 10 E36 27 2 74.9 123.1 125
E54 40.6 2 112.7 170.2 175
E72 54.1 2 150.2 179.5 200
NONE - - - 87.1 100
E18 18 1 43.3 87.1 100
230-3-60 13.1 83.1 20.5 2.1 13 10 E36 36 2 86.6 137 150
E54 54 2 129.9 158.7 175
180 E72 72 2 173.2 202 225
(15) NONE - - - 42.6 45
E18 18 1 21.7 42.6 45
460-3-60 6.1 41 9.5 1.26 6.5 5 E36 36 2 43.3 68.5 70
E54 54 2 65 79.3 90
E72 72 2 86.6 101 110
NONE - - - 30.7 35
E18 18 1 17.3 33.2 35
575-3-60 4.4 33 6.8 0.66 5.2 4 E36 36 2 34.6 54.8 60
E54 54 2 52 63.5 70
E72 72 2 69.3 80.8 90
NONE - - - 101.4 110
E18 13.5 1 37.5 101.4 110
208-3-60 14.5 98 22.6 2.1 20 10 E36 27 2 74.9 131.2 150
E54 40.6 2 112.7 178.4 200
E72 54.1 2 150.2 187.7 200
NONE - - - 100.7 110
E18 18 1 43.3 100.7 110
230-3-60 14.5 98 22.6 2.1 19.4 10 E36 36 2 86.6 145 150
E54 54 2 129.9 166.7 175
210 E72 72 2 173.2 210 225
(17.5) NONE - - - 47.4 50
E18 18 1 21.7 47.4 50
460-3-60 6.3 55 9.9 1.26 9.7 5 E36 36 2 43.3 72.5 80
E54 54 2 65 83.3 90
E72 72 2 86.6 105 110
NONE - - - 40.4 45
E18 18 1 17.3 40.4 45
575-3-60 6 41 9.4 0.66 7.8 4 E36 36 2 34.6 58.1 60
E54 54 2 52 66.7 70
E72 72 2 69.3 84 90
NONE - - - 106.2 125
E18 13.5 1 37.5 106.2 125
208-3-60 15.6 110 24.4 2.2 20 10 E36 27 2 74.9 131.2 150
E54 40.6 2 112.7 178.4 200
E72 54.1 2 150.2 187.7 200
NONE - - - 105.5 110
E18 18 1 43.3 105.5 110
230-3-60 15.6 110 24.4 2.2 19.4 10 E36 36 2 86.6 145 150
E54 54 2 129.9 166.7 175
240 E72 72 2 173.2 210 225
(20) NONE - - - 52.7 60
E18 18 1 21.7 52.7 60
460-3-60 7.8 52 12.1 1.1 9.7 5 E36 36 2 43.3 72.5 80
E54 54 2 65 83.3 90
E72 72 2 86.6 105 110
NONE - - - 40.6 45
E18 18 1 17.3 40.6 45
575-3-60 5.8 38.9 9.1 0.9 7.8 4 E36 36 2 34.6 58.1 60
E54 54 2 52 66.7 70
E72 72 2 69.3 84 90
Compressors
OD Fan Supply Pwr
Electric Heat Max Fuse2/
Size (each)
Motors Blower Conv
(Field Installed Accessory Only) MCA1 Breaker3
Volt (each) Motor Outlet
(Tons) (Amps) Size
RLA LRA MCC FLA FLA FLA Model kW Stages Amps (Amps)
NONE - - - 154.9 175
E18 13.5 1 37.5 154.9 175
208-3-60 22.4 149 35 2.2 37.2 10 E36 27 2 74.9 154.9 175
E54 40.6 2 112.7 199.9 200
E72 54.1 2 150.2 209.2 225
NONE - - - 151.7 175
E18 18 1 43.3 151.7 175
230-3-60 22.4 149 35 2.2 34.6 10 E36 36 2 86.6 164 175
E54 54 2 129.9 185.7 200
300 E72 72 2 173.2 229 250
(25) NONE - - - 73.4 90
E18 18 1 21.7 73.4 90
460-3-60 10.6 75 16.5 1.1 17.3 5 E36 36 2 43.3 82 90
E54 54 2 65 92.8 100
E72 72 2 86.6 114.5 125
NONE - - - 56.5 70
E18 18 1 17.3 56.5 70
575-3-60 7.7 54 12 0.9 14.5 4 E36 36 2 34.6 66.4 70
E54 54 2 52 75.1 80
E72 72 2 69.3 92.4 100
Compressors
OD Fan Supply Pwr
Electric Heat Max Fuse2/
Size (each)
Motors Blower Conv
(Field Installed Accessory Only) MCA1 Breaker3
Volt (each) Motor Outlet
(Tons) (Amps) Size
RLA LRA MCC FLA FLA FLA Model kW Stages Amps (Amps)
NONE - - - 124 125
E18 13.5 1 37.5 124 125
208-3-60 22.4 149 35 2.2 20 0 E36 27 2 74.9 124 125
E54 40.6 2 112.7 165.9 175
E72 54.1 2 150.2 175.2 200
NONE - - - 123.4 125
E18 18 1 43.3 123.4 125
230-3-60 22.4 149 35 2.2 19.4 0 E36 36 2 86.6 132.5 150
E54 54 2 129.9 154.2 175
300 E72 72 2 173.2 197.5 225
(25) NONE - - - 59.2 60
E18 18 1 21.7 59.2 60
460-3-60 10.6 75 16.5 1.1 9.7 0 E36 36 2 43.3 66.3 70
E54 54 2 65 77.1 90
E72 72 2 86.6 98.7 110
NONE - - - 44.2 50
E18 18 1 17.3 44.2 50
575-3-60 7.7 54 12 0.9 7.8 0 E36 36 2 34.6 53.1 60
E54 54 2 52 61.7 70
E72 72 2 69.3 79 90
Compressors
OD Fan Supply Pwr
Electric Heat Max Fuse2/
Size (each)
Motors Blower Conv
(Field Installed Accessory Only) MCA1 Breaker3
Volt (each) Motor Outlet
(Tons) (Amps) Size
RLA LRA MCC FLA FLA FLA Model kW Stages Amps (Amps)
NONE - - - 134 150
E18 13.5 1 37.5 134 150
208-3-60 22.4 149 35 2.2 20 10 E36 27 2 74.9 134 150
E54 40.6 2 112.7 178.4 200
E72 54.1 2 150.2 187.7 200
NONE - - - 133.4 150
E18 18 1 43.3 133.4 150
230-3-60 22.4 149 35 2.2 19.4 10 E36 36 2 86.6 145 150
E54 54 2 129.9 166.7 175
300 E72 72 2 173.2 210 225
(25) NONE - - - 64.2 70
E18 18 1 21.7 64.2 70
460-3-60 10.6 75 16.5 1.1 9.7 5 E36 36 2 43.3 72.5 80
E54 54 2 65 83.3 90
E72 72 2 86.6 105 110
NONE - - - 48.2 50
E18 18 1 17.3 48.2 50
575-3-60 7.7 54 12 0.9 7.8 4 E36 36 2 34.6 58.1 60
E54 54 2 52 66.7 70
E72 72 2 69.3 84 90
ZR180 - 300
ZR180-300 - Standard Drive Without Powered Convenience Outlet
Compressors
OD Fan Supply Pwr
Electric Heat Max Fuse2/
Size (each)
Motors Blower Conv
(Field Installed Accessory Only) MCA1 Breaker3
Volt (each) Motor Outlet
(Tons) (Amps) Size
RLA LRA MCC FLA FLA FLA Model kW Stages Amps (Amps)
NONE - - - 78.2 100
E18 13.5 1 37.5 78.2 100
208-3-60 25 164 39 2.1 13.5 0 E36 27 2 74.9 110.6 125
E54 40.6 2 112.7 157.7 175
E72 54.1 2 150.2 167 200
NONE - - - 77.7 100
E18 18 1 43.3 77.7 100
230-3-60 25 164 39 2.1 13 0 E36 36 2 86.6 124.5 125
E54 54 2 129.9 146.2 175
180 E72 72 2 173.2 189.5 225
(15) NONE - - - 39 50
E18 18 1 21.7 39 50
460-3-60 12.2 100 19 1.26 6.5 0 E36 36 2 43.3 62.3 70
E54 54 2 65 73.1 80
E72 72 2 86.6 94.7 110
NONE - - - 28.1 35
E18 18 1 17.3 28.2 35
575-3-60 9 78 14 0.66 5.2 0 E36 36 2 34.6 49.8 50
E54 54 2 52 58.5 70
E72 72 2 69.3 75.8 90
NONE - - - 96.5 125
E18 13.5 1 37.5 96.5 125
208-3-60 30.1 225 47 2.2 20 0 E36 27 2 74.9 118.7 125
E54 40.6 2 112.7 165.9 175
E72 54.1 2 150.2 175.2 200
NONE - - - 95.9 125
E18 18 1 43.3 95.9 125
230-3-60 30.1 225 47 2.2 19.4 0 E36 36 2 86.6 132.5 150
E54 54 2 129.9 154.2 175
240 E72 72 2 173.2 197.5 225
(20) NONE - - - 51.7 60
E18 18 1 21.7 51.7 60
460-3-60 16.7 114 26 1.1 9.7 0 E36 36 2 43.3 66.3 70
E54 54 2 65 77.1 90
E72 72 2 86.6 98.7 110
NONE - - - 38.9 50
E18 18 1 17.3 38.9 50
575-3-60 12.2 80 19 0.9 7.8 0 E36 36 2 34.6 53.1 60
E54 54 2 52 61.7 70
E72 72 2 69.3 79 90
NONE - - - 143 175
E18 13.5 1 37.5 143 175
208-3-60 48.1 245 75 2.2 26 0 E36 27 2 74.9 143 175
E54 40.6 2 112.7 173.4 175
E72 54.1 2 150.2 182.7 200
NONE - - - 142 175
E18 18 1 43.3 142 175
230-3-60 48.1 245 75 2.2 25 0 E36 36 2 86.6 142 175
E54 54 2 129.9 161.2 175
300 E72 72 2 173.2 204.5 225
(25) NONE - - - 58.8 70
E18 18 1 21.7 58.8 70
460-3-60 18.6 125 29 1.1 12.5 0 E36 36 2 43.3 69.8 70
E54 54 2 65 80.6 90
E72 72 2 86.6 102.2 110
NONE - - - 46.7 60
E18 18 1 17.3 46.7 60
575-3-60 14.7 100 23 0.9 10 0 E36 36 2 34.6 55.8 60
E54 54 2 52 64.5 70
E72 72 2 69.3 81.8 90
Compressors
OD Fan Supply Pwr
Electric Heat Max Fuse2/
Size (each)
Motors Blower Conv
(Field Installed Accessory Only) MCA1 Breaker3
Volt (each) Motor Outlet
(Tons) (Amps) Size
RLA LRA MCC FLA FLA FLA Model kW Stages Amps (Amps)
NONE - - - 88.2 110
E18 13.5 1 37.5 88.2 110
208-3-60 25 164 39 2.1 13.5 10 E36 27 2 74.9 123.1 125
E54 40.6 2 112.7 170.2 175
E72 54.1 2 150.2 179.5 200
NONE - - - 87.7 110
E18 18 1 43.3 87.7 110
230-3-60 25 164 39 2.1 13 10 E36 36 2 86.6 137 150
E54 54 2 129.9 158.7 175
180 E72 72 2 173.2 202 225
(15) NONE - - - 44 50
E18 18 1 21.7 44 50
460-3-60 12.2 100 19 1.26 6.5 5 E36 36 2 43.3 68.5 70
E54 54 2 65 79.3 90
E72 72 2 86.6 101 110
NONE - - - 32.1 40
E18 18 1 17.3 33.2 40
575-3-60 9 78 14 0.66 5.2 4 E36 36 2 34.6 54.8 60
E54 54 2 52 63.5 70
E72 72 2 69.3 80.8 90
NONE - - - 106.5 125
E18 13.5 1 37.5 106.5 125
208-3-60 30.1 225 47 2.2 20 10 E36 27 2 74.9 131.2 150
E54 40.6 2 112.7 178.4 200
E72 54.1 2 150.2 187.7 200
NONE - - - 105.9 125
E18 18 1 43.3 105.9 125
230-3-60 30.1 225 47 2.2 19.4 10 E36 36 2 86.6 145 150
E54 54 2 129.9 166.7 175
240 E72 72 2 173.2 210 225
(20) NONE - - - 56.7 70
E18 18 1 21.7 56.7 70
460-3-60 16.7 114 26 1.1 9.7 5 E36 36 2 43.3 72.5 80
E54 54 2 65 83.3 90
E72 72 2 86.6 105 110
NONE - - - 42.9 50
E18 18 1 17.3 42.9 50
575-3-60 12.2 80 19 0.9 7.8 4 E36 36 2 34.6 58.1 60
E54 54 2 52 66.7 70
E72 72 2 69.3 84 90
NONE - - - 153 200
E18 13.5 1 37.5 153 200
208-3-60 48.1 245 75 2.2 26 10 E36 27 2 74.9 153 200
E54 40.6 2 112.7 185.9 200
E72 54.1 2 150.2 195.2 200
NONE - - - 152 200
E18 18 1 43.3 152 200
230-3-60 48.1 245 75 2.2 25 10 E36 36 2 86.6 152 200
E54 54 2 129.9 173.7 200
300 E72 72 2 173.2 217 225
(25) NONE - - - 63.8 80
E18 18 1 21.7 63.8 80
460-3-60 18.6 125 29 1.1 12.5 5 E36 36 2 43.3 76 80
E54 54 2 65 86.8 90
E72 72 2 86.6 108.5 110
NONE - - - 50.7 60
E18 18 1 17.3 50.7 60
575-3-60 14.7 100 23 0.9 10 4 E36 36 2 34.6 60.8 70
E54 54 2 52 69.5 70
E72 72 2 69.3 86.8 90
Compressors
OD Fan Supply Pwr
Electric Heat Max Fuse2/
Size (each)
Motors Blower Conv
(Field Installed Accessory Only) MCA1 Breaker3
Volt (each) Motor Outlet
(Tons) (Amps) Size
RLA LRA MCC FLA FLA FLA Model kW Stages Amps (Amps)
NONE - - - 84.7 100
E18 13.5 1 37.5 84.7 100
208-3-60 25 164 39 2.1 20 0 E36 27 2 74.9 118.7 125
E54 40.6 2 112.7 165.9 175
E72 54.1 2 150.2 175.2 200
NONE - - - 84.1 100
E18 18 1 43.3 84.1 100
230-3-60 25 164 39 2.1 19.4 0 E36 36 2 86.6 132.5 150
E54 54 2 129.9 154.2 175
180 E72 72 2 173.2 197.5 225
(15) NONE - - - 42.2 50
E18 18 1 21.7 42.2 50
460-3-60 12.2 100 19 1.26 9.7 0 E36 36 2 43.3 66.3 70
E54 54 2 65 77.1 90
E72 72 2 86.6 98.7 110
NONE - - - 30.7 35
E18 18 1 17.3 31.4 35
575-3-60 9 78 14 0.66 7.8 0 E36 36 2 34.6 53.1 60
E54 54 2 52 61.7 70
E72 72 2 69.3 79 90
NONE - - - 102.5 125
E18 13.5 1 37.5 102.5 125
208-3-60 30.1 225 47 2.2 26 0 E36 27 2 74.9 126.2 150
E54 40.6 2 112.7 173.4 175
E72 54.1 2 150.2 182.7 200
NONE - - - 101.5 125
E18 18 1 43.3 101.5 125
230-3-60 30.1 225 47 2.2 25 0 E36 36 2 86.6 139.5 150
E54 54 2 129.9 161.2 175
240 E72 72 2 173.2 204.5 225
(20) NONE - - - 54.5 70
E18 18 1 21.7 54.5 70
460-3-60 16.7 114 26 1.1 12.5 0 E36 36 2 43.3 69.8 70
E54 54 2 65 80.6 90
E72 72 2 86.6 102.2 110
NONE - - - 41.1 50
E18 18 1 17.3 41.1 50
575-3-60 12.2 80 19 0.9 10 0 E36 36 2 34.6 55.8 60
E54 54 2 52 64.5 70
E72 72 2 69.3 81.8 90
NONE - - - 154.2 200
E18 13.5 1 37.5 154.2 200
208-3-60 48.1 245 75 2.2 37.2 0 E36 27 2 74.9 154.2 200
E54 40.6 2 112.7 187.4 200
E72 54.1 2 150.2 196.7 225
NONE - - - 151.6 175
E18 18 1 43.3 151.6 175
230-3-60 48.1 245 75 2.2 34.6 0 E36 36 2 86.6 151.6 175
E54 54 2 129.9 173.2 200
300 E72 72 2 173.2 216.5 250
(25) NONE - - - 63.6 80
E18 18 1 21.7 63.6 80
460-3-60 18.6 125 29 1.1 17.3 0 E36 36 2 43.3 75.8 80
E54 54 2 65 86.6 100
E72 72 2 86.6 108.2 125
NONE - - - 51.2 60
E18 18 1 17.3 51.2 60
575-3-60 14.7 100 23 0.9 14.5 0 E36 36 2 34.6 61.4 70
E54 54 2 52 70.1 80
E72 72 2 69.3 87.4 100
Compressors
OD Fan Supply Pwr
Electric Heat Max Fuse2/
Size (each)
Motors Blower Conv
(Field Installed Accessory Only) MCA1 Breaker3
Volt (each) Motor Outlet
(Tons) (Amps) Size
RLA LRA MCC FLA FLA FLA Model kW Stages Amps (Amps)
NONE - - - 94.7 110
E18 13.5 1 37.5 94.7 110
208-3-60 25 164 39 2.1 20 10 E36 27 2 74.9 131.2 150
E54 40.6 2 112.7 178.4 200
E72 54.1 2 150.2 187.7 200
NONE - - - 94.1 110
E18 18 1 43.3 94.1 110
230-3-60 25 164 39 2.1 19.4 10 E36 36 2 86.6 145 150
E54 54 2 129.9 166.7 175
180 E72 72 2 173.2 210 225
(15) NONE - - - 47.2 50
E18 18 1 21.7 47.2 50
460-3-60 12.2 100 19 1.26 9.7 5 E36 36 2 43.3 72.5 80
E54 54 2 65 83.3 90
E72 72 2 86.6 105 110
NONE - - - 34.7 40
E18 18 1 17.3 36.4 40
575-3-60 9 78 14 0.66 7.8 4 E36 36 2 34.6 58.1 60
E54 54 2 52 66.7 70
E72 72 2 69.3 84 90
NONE - - - 112.5 125
E18 13.5 1 37.5 112.5 125
208-3-60 30.1 225 47 2.2 26 10 E36 27 2 74.9 138.7 150
E54 40.6 2 112.7 185.9 200
E72 54.1 2 150.2 195.2 200
NONE - - - 111.5 125
E18 18 1 43.3 111.5 125
230-3-60 30.1 225 47 2.2 25 10 E36 36 2 86.6 152 175
E54 54 2 129.9 173.7 175
240 E72 72 2 173.2 217 225
(20) NONE - - - 59.5 70
E18 18 1 21.7 59.5 70
460-3-60 16.7 114 26 1.1 12.5 5 E36 36 2 43.3 76 80
E54 54 2 65 86.8 90
E72 72 2 86.6 108.5 110
NONE - - - 45.1 50
E18 18 1 17.3 45.1 50
575-3-60 12.2 80 19 0.9 10 4 E36 36 2 34.6 60.8 70
E54 54 2 52 69.5 70
E72 72 2 69.3 86.8 90
NONE - - - 164.2 200
E18 13.5 1 37.5 164.2 200
208-3-60 48.1 245 75 2.2 37.2 10 E36 27 2 74.9 164.2 200
E54 40.6 2 112.7 199.9 200
E72 54.1 2 150.2 209.2 225
NONE - - - 161.6 200
E18 18 1 43.3 161.6 200
230-3-60 48.1 245 75 2.2 34.6 10 E36 36 2 86.6 164 200
E54 54 2 129.9 185.7 200
300 E72 72 2 173.2 229 250
(25) NONE - - - 68.6 80
E18 18 1 21.7 68.6 80
460-3-60 18.6 125 29 1.1 17.3 5 E36 36 2 43.3 82 90
E54 54 2 65 92.8 100
E72 72 2 86.6 114.5 125
NONE - - - 55.2 60
E18 18 1 17.3 55.2 60
575-3-60 14.7 100 23 0.9 14.5 4 E36 36 2 34.6 66.4 70
E54 54 2 52 75.1 80
E72 72 2 69.3 92.4 100
Compressors
OD Fan Supply Pwr
Electric Heat Max Fuse2/
Size (each)
Motors Blower Conv
(Field Installed Accessory Only) MCA1 Breaker3
Volt (each) Motor Outlet
(Tons) (Amps) Size
RLA LRA MCC FLA FLA FLA Model kW Stages Amps (Amps)
NONE - - - 137 175
E18 13.5 1 37.5 137 175
208-3-60 48.1 245 75 2.2 20 0 E36 27 2 74.9 137 175
E54 40.6 2 112.7 165.9 175
E72 54.1 2 150.2 175.2 200
NONE - - - 136.4 175
E18 18 1 43.3 136.4 175
230-3-60 48.1 245 75 2.2 19.4 0 E36 36 2 86.6 136.4 175
E54 54 2 129.9 154.2 175
300 E72 72 2 173.2 197.5 225
(25) NONE - - - 56 70
E18 18 1 21.7 56 70
460-3-60 18.6 125 29 1.1 9.7 0 E36 36 2 43.3 66.3 70
E54 54 2 65 77.1 90
E72 72 2 86.6 98.7 110
NONE - - - 44.5 50
E18 18 1 17.3 44.5 50
575-3-60 14.7 100 23 0.9 7.8 0 E36 36 2 34.6 53.1 60
E54 54 2 52 61.7 70
E72 72 2 69.3 79 90
Compressors
OD Fan Supply Pwr
Electric Heat Max Fuse2/
Size (each)
Motors Blower Conv
(Field Installed Accessory Only) MCA1 Breaker3
Volt (each) Motor Outlet
(Tons) (Amps) Size
RLA LRA MCC FLA FLA FLA Model kW Stages Amps (Amps)
NONE - - - 147 175
E18 13.5 1 37.5 147 175
208-3-60 48.1 245 75 2.2 20 10 E36 27 2 74.9 147 175
E54 40.6 2 112.7 178.4 200
E72 54.1 2 150.2 187.7 200
NONE - - - 146.4 175
E18 18 1 43.3 146.4 175
230-3-60 48.1 245 75 2.2 19.4 10 E36 36 2 86.6 146.4 175
E54 54 2 129.9 166.7 175
300 E72 72 2 173.2 210 225
(25) NONE - - - 61 70
E18 18 1 21.7 61 70
460-3-60 18.6 125 29 1.1 9.7 5 E36 36 2 43.3 72.5 80
E54 54 2 65 83.3 90
E72 72 2 86.6 105 110
NONE - - - 48.5 60
E18 18 1 17.3 48.5 60
575-3-60 14.7 100 23 0.9 7.8 4 E36 36 2 34.6 58.1 60
E54 54 2 52 66.7 70
E72 72 2 69.3 84 90
ZF180 - 300
ZF180-300 - Standard Drive Without Powered Convenience Outlet
OD Fan Supply Pwr
Compressors
Motors Blower Conv
Electric Heat Max Fuse2/
Size (each)
(each) Motor Outlet
(Field Installed Accessory Only) MCA1 Breaker3
Volt
(Tons) (Amps) Size
RLA LRA MCC
FLA FLA FLA Model kW Stages Amps (Amps)
C1 C2 C1 C2 C1 C2
NONE - - - 78 100
E18 13.5 1 37.5 78 100
208-3-60 25 25 164 164 39 39 4.1 13.5 0 E36 27 2 74.9 110.6 125
E54 40.6 2 112.7 157.7 175
E72 54.1 2 150.2 167 200
NONE - - - 77.1 100
E18 18 1 43.3 77.1 100
230-3-60 25 25 164 164 39 39 3.9 13 0 E36 36 2 86.6 124.5 125
E54 54 2 129.9 146.2 175
180 E72 72 2 173.2 189.5 225
(15) NONE - - - 39.6 50
E18 18 1 21.7 39.6 50
460-3-60 12.8 12.8 100 100 20 20 2.15 6.5 0 E36 36 2 43.3 62.3 70
E54 54 2 65 73.1 80
E72 72 2 86.6 94.7 110
NONE - - - 30 35
E18 18 1 17.3 30 35
575-3-60 9.6 9.6 78 78 15 15 1.6 5.2 0 E36 36 2 34.6 49.8 50
E54 54 2 52 58.5 70
E72 72 2 69.3 75.8 90
NONE - - - 83.8 110
E18 13.5 1 37.5 83.8 110
208-3-60 27.6 27.6 203 203 43 43 4.1 13.5 0 E36 27 2 74.9 110.6 125
E54 40.6 2 112.7 157.7 175
E72 54.1 2 150.2 167 200
NONE - - - 82.9 110
E18 18 1 43.3 82.9 110
230-3-60 27.6 27.6 203 203 43 43 3.9 13 0 E36 36 2 86.6 124.5 125
E54 54 2 129.9 146.2 175
210 E72 72 2 173.2 189.5 225
(17.5) NONE - - - 43 50
E18 18 1 21.7 43 50
460-3-60 14.3 14.3 98 98 22 22 2.15 6.5 0 E36 36 2 43.3 62.3 70
E54 54 2 65 73.1 80
E72 72 2 86.6 94.7 110
NONE - - - 37.4 50
E18 18 1 17.3 37.4 50
575-3-60 12.9 12.9 84 84 18 18 1.6 5.2 0 E36 36 2 34.6 49.8 50
E54 54 2 52 58.5 70
E72 72 2 69.3 75.8 90
NONE - - - 102.3 125
E18 13.5 1 37.5 102.3 125
208-3-60 35.8 35.8 239 239 52 52 4.1 13.5 0 E36 27 2 74.9 110.6 125
E54 40.6 2 112.7 157.7 175
E72 54.1 2 150.2 167 200
NONE - - - 101.4 125
E18 18 1 43.3 101.4 125
230-3-60 35.8 35.8 239 239 52 52 3.9 13 0 E36 36 2 86.6 124.5 125
E54 54 2 129.9 146.2 175
240 E72 72 2 173.2 189.5 225
(20) NONE - - - 51.1 60
E18 18 1 21.7 51.1 60
460-3-60 17.9 17.9 125 125 28 28 2.15 6.5 0 E36 36 2 43.3 62.3 70
E54 54 2 65 73.1 80
E72 72 2 86.6 94.7 110
NONE - - - 37.2 50
E18 18 1 17.3 37.2 50
575-3-60 12.8 12.8 80 80 20 20 1.6 5.2 0 E36 36 2 34.6 49.8 50
E54 54 2 52 58.5 70
E72 72 2 69.3 75.8 90
THERMOSTAT CONTROL
TERMINALS TERMINAL
BLOCK
W1
W1
W2 W2
1
Y1 Y1
G
Y2
Y2
Y3 OCC
Y4 X
G R Smoke
SD-24 Detector
R C
C
C 24V 24 VAC
EXPANSION Class 2
BOARD
SD-24 Jumper Located on Harness 2
3 TERMINAL (If No Smoke Detector) (If Smoke Detector Is Used)
RC BLOCK
SD-R
4
R
5 Y4
X
TERMINALS ON
A LIMITED
NUMBER OF
THERMOSTATS 1 Second stage heating not required on single stage heating units.
2 Jumper is required if there is no Smoke Detector circuit.
3 Jumper is required for any combination of R, RC, or RH.
4 OCC is an output from the thermostat to indicate the Occupied condition.
5 X is an input to the thermostat to display Error Status conditions.
CONTROL
THERMOSTAT TERMINAL
TERMINALS BLOCK
W1
W1
W2
W2
1 Y1
Y1 G
Y2 Y2
OCC
G
X
R R
3
C SD-24 Smoke
Detector
C
RC C
4
TERMINALS ON A SD-R
LIMITED NUMBER 24V Output
OF THERMOSTATS
R
TB4-3
823/R 24V
S4 Return or Space Humidity
RAH
- 1) 824/BK COM
Sensor (0-10VDC)
P4
+ 2) 825/W OUT
DCT - 3)
PRS + 4)
CONTROL
THERMOSTAT TERMINAL
TERMINALS BLOCK
W1
W1
W2
W2
1 Y1
Y1 G
Y2 Y2
OCC
G
X
R R
3
C SD-24
C
Smoke
RC Detector
4
OCC C
5
X 24V 24 VAC
Class 2
R
1 Second stageŚĞĂƟŶŐŶot required on single stage heĂƟŶg units.
2 Jumper is required if there is no Smoke Detector circuit.
3 Jumper is required for any coŵďŝŶĂƟŽŶ of R, RC, or RH.
4 OCC is an output from the thermostat to indicate the Occupied ĐŽŶĚŝƟon.
5 X is an input to the thermostat to display Error Status condiƟons.
B C
B
C D
E
A A
D F
Y
X
FRONT
LEFT
B C
B
C D
A A E
FRONT
FRONT
D F
Size Weight (lbs.) Center of Gravity 4 Point Load Location (lbs.) 6 Point Load Location (lbs.)
Model
(Tons) Shipping Operating X Y A B C D A B C D E F
180 (15) ZJ 2614 2609 85.25 44 467 781 852 510 287 392 568 620 428 313
210 (17.5) ZJ 2670 2665 85.25 44 477 797 870 520 293 401 580 633 437 320
240 (20) ZJ 2702 2697 85.05 44 485 805 878 529 298 406 585 638 443 326
300 (25) ZJ 2788 2783 85.25 44 498 833 908 544 306 419 606 661 457 334
180 (15) ZR 2365 2360 85.25 44 422 706 770 461 260 355 514 561 387 284
240 (20) ZR 2665 2660 85.05 44 478 794 866 522 294 401 477 630 437 321
300 (25) ZR 2765 2760 85.25 44 494 826 901 539 304 415 601 656 453 332
180 (15) ZF 1875 1870 65.26 45 438 477 498 458 288 304 322 337 318 301
210 (17.5) ZF 2011 2006 70.98 45 470 511 534 491 309 327 346 361 341 323
240 (20) ZF 2538 2533 70 44 589 622 679 643 389 404 419 457 440 425
300 (25) ZF 2602 2597 70 44.5 611 645 689 652 403 418 434 464 447 431
Unit Dimensions
ZJ/ZR Unit Dimensions Front View
ECONOMIZER / MOTORIZED DAMPER
FIXED OUTDOOR INTAKE AIR AND
POWER EXHAUST RAIN HOODS
(See detail Y)
BLOWER MOTOR
ACCESS (Location BLOWER ACCESS
BLOWER of Optional VFD Bypass) (Location of
COMPARTMENT Optional VFD)
ACCESS COMPRESSOR ACCESS
180-19/32
(Auxiliary)
COMBUSTION
21.00
AIR INLET HOOD
(C) GAS
SUPPLY 9-3/4 CONDENSER
ENTRY COILS
7-1/8
136-1/4 (A) CONTROL WIRING
6-3/8 92 ENTRY
5
DISCONNECT
46-5/8 SWITCH
CONTROL BOX 11-1/2 LOCATION
5-7/8
ACCESS
(B) POWER
35 WIRING
ENTRY
BOTTOM SUPPLY
AND RETURN
35-1/4 AIR OPENINGS
RETURN (See Note)
33 AIR
SUPPLY
2-3/4 AIR 3-3/4
21-1/2
UNIT BASE RAILS
Shown separately to illustrate
Bottom Duct openings. Power (D)
and Gas Piping Connection GAS SUPPLY
location. (B) POWER WIRING
ENTRY
11-1/8 ENTRY
NOTE:
For curb mounted units, refer to the curb hanger 8-1/8 (A) CONTROL WIRING
dimensions of the curb for proper size of the 12-1/2
supply and return air duct connections. 46-5/8 ENTRY
9-1/4
9-3/4
Utilities Entry
Opening Size
Hole Used For
Diameter
1-1/8” KO Front
A Control Wiring
3/4” NPS (Fem.) Bottom
3-5/8” KO Front
B Power Wiring
3” NPS (Fem.) Bottom
C 2-3/8” KO Gas Piping (Front)1
D 1-11/16” Hole Gas Piping (Bottom)1,2
1. One-inch Gas Piping NPT Required.
2. Opening in the bottom to the unit can be located by the slice in the
insulation.
NOTE: All entry holes should be field sealed to prevent rain water
entry into the building.
DOT PLUG
(For pressure 48-5/8" (15 Ton)
Drop Reading) 52-5/8" (17.5 & 20 Ton)
ELECTRIC
GAS HEAT
ACCESS
VENT A IR CONDENSER
OUTLET COILS
HOODS 21"
n) 5"
To 7-1/8"
COMBUSTION 15 5 )
AIR INLET 4 " ( 17. Ton
1/ ( 5
HOOD 2 5- 1/4" ru 2
1 6 th- 6-3/8"
13
9-3/4" 92"
(C) 5-7/8" (A)
GAS SUPPLY
CONTROL WIRING
ENTRY
46-5/8" ENTRY
CONTROL BOX
11-1/2" (B)
ACCESS 35"
POWER WIRING
BOTTOM SUPPLY ENTRY
AND RETURN
AIR OPENINGS
FRONT To
n)
(See Note) RETURN A IR
5
VIEW " (1 7.5 n)
/4 (1 To RETURN
-1 /4" 5 AIR 3-3/4"
24 5-1 ru 2 SUPPL Y A IR
3 th 33"
SUPPLY
AIR OUTDOOR A IR
2-3/4" 21-1/2"
11-1/8"
OUTDOOR A IR
(Ec o n o m i zer )
UNIT BASE WITH RAILS
(B)
Shown separately to illustrate (D)
POWER WIRING
Bottom Duct openings, Power GAS SUPPLY
ENTRY
and Gas Piping Connection ENTRY
locations (A)
8-1/8" CONTROL WIRING
ENTRY
NOTE:
46-5/8"
For curb mounted units, refer to the curb hanger 9-1/4"
dimensions of the curb for the proper size of the
12-1/2" 9-3/4"
supply and return air duct connections.
Dot Plug
(for Pressure Evaporator
Drop Reading) Section
40-3/8”
Supply
Air
Outdoor
Air
Return
Air
18-5/8” 40-1/2”
Supply Air
27-3/4”
Access Filter
5-1/8”
Access
28-5/8” 1” NPT Female
Dimensions listed are for side duct flange Return Air ZF 180 Outdoor Air Cond. Drain
opening; see Field Accessories for Side Access and
Duct Flange Kit.
Compartment Connector
39-5/8” Access
ZJ/ZR 180-300
ZF 210-300
Fixed
Outdoor Air
Intake Hood
(Located on
36-5/8” Return Air
1” Condensate
Compartment)
16-1/8”
Drain (Must be
Trapped)
5”
28-3/16” 92”
Detail “Y”
Unit with Rain Hoods
25-1/4"
14-1/4”
115-1/4”
NOTE: Ducts can be installed into the curb from the roof. All
electrical and gas line connections can be made inside
the curb.
Roof Jack
Installation
Roof Curb
Installation
Slab On
Ground
Installation