ATV32 Quick Start Guide
ATV32 Quick Start Guide
ATV32 Quick Start Guide
S1A4171502
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Read and understand this quick start guide before performing any procedure with this drive.
• The user is responsible for compliance with all international and national electrical code requirements with respect to grounding of all
equipment.
• Many parts of this drive, including the printed circuit boards, operate at the line voltage. DO NOT TOUCH. Use only electrically insulated tools.
• DO NOT touch unshielded components or terminal strip screw connections with voltage present.
• DO NOT short across terminals PA/+ and PC/- or across the DC bus capacitors.
• Before servicing the drive:
- Disconnect all power, including external control power that may be present.
- Place a "DO NOT TURN ON" label on all power disconnects.
- Lock all power disconnects in the open position.
- WAIT 15 MINUTES to allow the DC bus capacitors to discharge.
- Measure the voltage of the DC bus between the PA/+ and PC/- terminals to ensure that the voltage is less than 42 Vdc.
- If the DC bus capacitors do not discharge completely, contact your local Schneider Electric representative. Do not repair or operate
the drive
• Install and close all covers before applying power or starting and stopping the drive.
Failure to follow these instructions will result in death or serious injury.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider
Electric for any consequences arising out of the use of this product.
Information below is designed to use single drive connected to single asynchronous motor with a motor cable length less than 50 meters (164
ft).
In any other case, consult the ATV32 installation manual (S1A28686) and programming manual (S1A28692) on www.schneider-electric.com.
Check your cables before connecting the drive with motor (length, power, shielded or unshielded). Motor cable length is _______(< 50 meters, 164 ft)
WARNING
DAMAGED DRIVE EQUIPMENT
Do not operate or install any drive or drive accessory that appears damaged.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
• Check that the drive reference printed on the label is the same as that on the delivery note corresponding to the
purchase order. ATV32H037M2
0,37KW - 1/2HP - 220/ 240V
Write the drive Model Reference: _____________ ___________and Serial Number: ____________________________
8B0917121134
2 Check the line voltage compatibility
• Check that the line voltage is compatible with the supply range of the drive.
Line voltage _______ Volts Drive voltage range _______ Volts
Drive range: ATV32 M2 = 200 ... 240 V single phase - ATV32 N4 = 380 ... 500 V three-phase
u 10 mm
0.39 in.
1 ... 1,5 Nm
8.9 ... 13.3 lb.in
OR OR OR
380...500 V
ATV32HU55N4, U75N4
ATV32HD11N4, D15N4
Asynchronous motor
DANGER
HAZARD OF FIRE OR ELECTRIC SHOCK
• To avoid overheating or loss of contact, connections must be carried out according to the cable sizes and tightening torques visible on
the label stuck on the ATV32.
• The use of multi-wire cable without a lug is forbidden for the mains connection.
• For ATV32H0ppM2, H0ppN4, HU1pN4 , ATV32HUppM2, ATV32HU22N4, U30N4, U40N4, the stripping length of the output power and braking
resistor cables must be shorter than 10 mm (0.39 in.)
• Carry-out a pull out test to check that terminal screws are correctly tighten.
Failure to follow these instructions will result in death or serious injury.
Source A1
+10 v
AI 1
COM
LI1: forward
LI2: reverse SW1 Ext ATV32
Sink
+24
Int
LI2
LI1
0V
0,5 N.m
4.4 lb.in
(2)for synchronous motor, consult the ATV32 programming manual (S1A28692) on www.schneider-electric.com.
ESC
ESC
ESC
A dash appears after menu codes to differentiate them from parameter codes. Example: [SIMPLY START]SIM-, tCC parameter.
ESC 2C
HSP
«LED ConF” and «LED
Value” illuminated