ENGLISH Quick Start Guide - ATV32

S1A4171502
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Read and understand this quick start guide before performing any procedure with this drive.
• The user is responsible for compliance with all international and national electrical code requirements with respect to grounding of all
equipment.
• Many parts of this drive, including the printed circuit boards, operate at the line voltage. DO NOT TOUCH. Use only electrically insulated tools.
• DO NOT touch unshielded components or terminal strip screw connections with voltage present.
• DO NOT short across terminals PA/+ and PC/- or across the DC bus capacitors.
• Before servicing the drive:
- Disconnect all power, including external control power that may be present.
- Place a "DO NOT TURN ON" label on all power disconnects.
- Lock all power disconnects in the open position.
- WAIT 15 MINUTES to allow the DC bus capacitors to discharge.
- Measure the voltage of the DC bus between the PA/+ and PC/- terminals to ensure that the voltage is less than 42 Vdc.
- If the DC bus capacitors do not discharge completely, contact your local Schneider Electric representative. Do not repair or operate
the drive
• Install and close all covers before applying power or starting and stopping the drive.
Failure to follow these instructions will result in death or serious injury.

Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider
Electric for any consequences arising out of the use of this product.

Information below is designed to use single drive connected to single asynchronous motor with a motor cable length less than 50 meters (164
ft).
In any other case, consult the ATV32 installation manual (S1A28686) and programming manual (S1A28692) on www.schneider-electric.com.
Check your cables before connecting the drive with motor (length, power, shielded or unshielded). Motor cable length is _______(< 50 meters, 164 ft)

1 Check the delivery of the drive


• Remove ATV32 from the packaging and check that it has not been damaged.

WARNING
DAMAGED DRIVE EQUIPMENT
Do not operate or install any drive or drive accessory that appears damaged.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

• Check that the drive reference printed on the label is the same as that on the delivery note corresponding to the
purchase order. ATV32H037M2
0,37KW - 1/2HP - 220/ 240V
Write the drive Model Reference: _____________ ___________and Serial Number: ____________________________

• For ATV32H0ppM2, H0ppN4, HU1pN4 , ATV32HUppM2, ATV32HU22N4, U30N4, U40N4,


remove the output connector from the packaging and check that it has not been damaged.

8B0917121134
2 Check the line voltage compatibility
• Check that the line voltage is compatible with the supply range of the drive.
Line voltage _______ Volts Drive voltage range _______ Volts
Drive range: ATV32 M2 = 200 ... 240 V single phase - ATV32 N4 = 380 ... 500 V three-phase

3 Mount the drive vertically


For a surrounding air temperature up to 50 °C (122°F), see installation manual (S1A28686) on www.schneider-electric.com for other thermal
conditions.
u 50 mm

(1) (1) Minimum value corresponding to thermal contrainst. On ATV32H0ppM2, H0ppN4,


2 in.

HU1pN4, ATV32HUppM2, ATV32HU22N4, U30N4, U40N4 , a 150 mm (5.9 in)


clearance may help to connect the ground.
u 50 mm
2 in.

u 10 mm
0.39 in.

www.schneider-electric.com 1/4 S1A41715 - 06/2011


4 Connect the drive: Power
• Wire the drive to the ground.
• Check circuit breaker rating or fuse rating.
• Check that the motor voltage is compatible with the drive voltage. Motor voltage ______Volts.
• Wire the drive to the motor.
• Wire the drive to the line supply.

1 ... 1,5 Nm
8.9 ... 13.3 lb.in

ATV32H0ppM2, H0ppN4, HU1pN4


ATV32HUppM2
ATV32HU22N4, U30N4, U40N4

0,6 ... 0,8 N.m


200...240 V
5.3 ... 7.1 lb.in

OR OR OR

380...500 V

ATV32HU55N4, U75N4
ATV32HD11N4, D15N4

1,2 ... 1,5 N.m


10.6 ... 13.3 lb.in

Asynchronous motor

DANGER
HAZARD OF FIRE OR ELECTRIC SHOCK
• To avoid overheating or loss of contact, connections must be carried out according to the cable sizes and tightening torques visible on
the label stuck on the ATV32.
• The use of multi-wire cable without a lug is forbidden for the mains connection.
• For ATV32H0ppM2, H0ppN4, HU1pN4 , ATV32HUppM2, ATV32HU22N4, U30N4, U40N4, the stripping length of the output power and braking
resistor cables must be shorter than 10 mm (0.39 in.)
• Carry-out a pull out test to check that terminal screws are correctly tighten.
Failure to follow these instructions will result in death or serious injury.

5 Connect the drive: Control by external reference (Fr1 = Al1 )


• Wire the speed reference: • Wire the command:
Control command 2-wire: Parameter tCC = 2C

Source A1
+10 v

AI 1

COM

LI1: forward
LI2: reverse SW1 Ext ATV32
Sink
+24

Int
LI2

LI1

0V

0,5 N.m
4.4 lb.in

www.schneider-electric.com 2/4 S1A41715 - 06/2011


6 Apply power to the drive
• Check that used Logic Inputs are not active (LI1, LI2 see drawing 5 ).
• Apply power to the drive.
• At first power up, drive displays bFr, in the menu SIM- [SIMPLY START]

7 Set motor parameters for asynchronous motor (2).


• See on the motor Nameplate to set the following parameters .
Customer
Menu Code Description Factory setting
setting
[Standard mot. freq]:
bFr 50.0
Standard motor frequency (Hz)
[Rated motor power]:
nPr drive rating
Nominal motor power on motor nameplate (KW)
[Rated motor volt.]:
UnS drive rating
Nominal motor voltage on motor nameplate (V)
ConF > FULL >
[Rated motor current.]:
SIM- nCr drive rating
Nominal motor current on motor nameplate (A)
[SIMPLY START]
[Rated motor freq.]:
FrS 50.0
Nominal motor frequency on motor nameplate (Hz)
[Rated motorspeed]:
nSP drive rating
Nominal motor speed on motor nameplate (rpm)
[Mot. therm. current]:
ItH drive rating
Nominal motor current on motor nameplate (A)

(2)for synchronous motor, consult the ATV32 programming manual (S1A28692) on www.schneider-electric.com.

8 Set basic parameters


Customer
Menu Code Description Factory setting
setting
[Acceleration]:
ACC 3.0
Acceleration time (s)
[Deceleration]:
ConF > FULL > dEC 3.0
Deceleration time (s)
SIM-
[Low speed]:
[SIMPLY START] LSP 0.0
Motor frequency at minimum reference (Hz)
[High speed]:
HSP 50.0
Motor frequency at maximum reference (Hz)

9 Start the motor

www.schneider-electric.com 3/4 S1A41715 - 06/2011


10
9 Annex: Menus structure
= ENT ESC rdY

ESC
ESC
ESC

rEF MOn COnF

[SPEED REFERENCE] [MONITORING] [CONFIGURATION]

A dash appears after menu codes to differentiate them from parameter codes. Example: [SIMPLY START]SIM-, tCC parameter.

ESC ESC ESC ESC


COnF FULL SIM- tCC 3C
ENT ENT ENT ENT

Refer to the programming manual (S1A28692) for 2C


bFr
comprehensive menu description.
ENT

ESC 2C
HSP
«LED ConF” and «LED
Value” illuminated

www.schneider-electric.com 4/4 S1A41715 - 06/2011