2300E Digital Load Sharing and Speed Control For Engines: Product Manual 26691 (Revision E, 7/2016)
2300E Digital Load Sharing and Speed Control For Engines: Product Manual 26691 (Revision E, 7/2016)
2300E Digital Load Sharing and Speed Control For Engines: Product Manual 26691 (Revision E, 7/2016)
(Revision E, 7/2016)
Original Instructions
This publication may have been revised or updated since this copy was produced.
To verify that you have the latest revision, check manual 26455, Customer
Publication Cross Reference and Revision Status & Distribution Restrictions, on
Revisions the publications page of the Woodward website:
www.woodward.com/publications
Revisions—Changes in this publication since the last revision are indicated by a black line
alongside the text.
Woodward reserves the right to update any portion of this publication at any time. Information provided by Woodward is
believed to be correct and reliable. However, no responsibility is assumed by Woodward unless otherwise expressly
undertaken.
Manual 26691
Copyright © Woodward, Inc. 2012–2016
All Rights Reserved
Manual 26691 2300E Digital Control
Contents
Woodward i
2300E Digital Control Manual 26691
ii Woodward
Manual 26691 2300E Digital Control
Woodward iii
2300E Digital Control Manual 26691
iv Woodward
Manual 26691 2300E Digital Control
Regulatory Compliance
European Compliance for CE Mark
These listings are limited only to those units bearing the CE Marking.
Marine Compliance
Woodward v
2300E Digital Control Manual 26691
Lloyd’s Register LR Type Approval Test Specification No. 1, 2002 for
of Shipping: Shipping: Environmental Categories ENV1, ENV2
and ENV3
The control must be installed in a suitable enclosure. The final combination must
be approved by the local authority having jurisdiction.
vi Woodward
Manual 26691 2300E Digital Control
Chapter 1.
General Information
Description
The 2300E is a digital control that can be programmed with applicable application
software. This control is housed in a sheet metal chassis and consists of a single
printed circuit board. This control is designed to perform the speed and load
control functions for a small engine, steam turbine, or gas turbine. The 2300E
has no application software in it when shipped from Woodward, which allows it to
be configured and modified to meet site-specific requirements. It utilizes the
Woodward GAP 3.X software to create an application specific application
software that can be downloaded to the 2300E.
The 2300E has two serial communication ports, allowing it to easily interface with
a Human Machine Interface (HMI), PLC, or plant DCS. These configuration and
dynamic settings are set, changed, tuned, and saved via a laptop computer and
Woodward’s user-friendly Control Assistant software program. This program
allows users to set and adjust all application-based parameters, plus upload and
download configurations to and from the control. Woodward’s Toolkit software is
also capable of communicating to the 2300E
The following is an example of the typical hardware needed for a 2300E system
controlling a single prime mover and generator:
A 2300E electronic control
An external 18 to 36 Vdc power source
Two speed-sensing devices, typically magnetic pickups (MPUs)
A proportional actuator to position the fuel-metering device
Current and potential transformers for measuring the load carried by the
generator
Woodward 1
2300E Digital Control Manual 26691
The frequency from the magnetic pickup must be within the range of 100 to 25
000 Hz at rated speed. The 2300E speed range needs to be configured using an
external computer during installation.
References
The following publications contain additional product or installation information on
Load Sharing and Speed Controls, and related components. They can be
ordered from any Woodward office.
Manual Title
25070 Electric Governor Installation Guide
25195 Governing Fundamentals
82510 Magnetic Pickups and Proximity Switches for Electric Governors
82715 Guide for Handling and Protection of Electronic Controls, Printed
Circuit Boards, and Modules
Product
Spec Title
03405 2300E Digital Load Sharing and Speed Control Hardware
82516 EG-3P/3PC Actuator
82575 EGB-1P/2P Governor/Actuator
2 Woodward
Manual 26691 2300E Digital Control
Woodward 3
2300E Digital Control Manual 26691
4 Woodward
Manual 26691 2300E Digital Control
30 1
23 5
ANAL OG I NPUT # 2
( 0- 5 V DC, 4 - 2 0mA, OR 2 .5 V DC)
22 4
2
21 1
20 ANAL OG I NPUT # 1 A
( 2 .5 V DC)
19
B
18 1
C
17 ANAL OG OUT PUT
4 - 2 0mA
16 DET AI L " A"
12 1
11
L OAD SHARE
10 AMMET ERS, ET C
ON SWI T CHBOARD 8
9
2
8
7
3 WARNI NG 2
6
5
2
4
3
9 0- 2 4 0 V AC
4 5 - 6 6 HZ T O V OL T MET ER, ET C
POT ENT I AL 2 ON SWI T CHBOARD
V OL T AGE
1
5
MAI N
BUS
A
4
GENERAT OR B
4
C
6 CI RCUI T
4 BREAKER
Woodward 5
2300E Digital Control Manual 26691
SERI AL I / 0
54 CAN HI GH
( 9 - DF )
53 CAN SHI EL D
10 1
52 CAN L OW 6
2 RX
51 CAN GND 7
RS- 2 3 2 PORT
3 TX
8
4
9
50 CHASSI S GROUND
5 COM
49 I NPUT POWER
( 18 - 3 6 V DC, 0.6 AMP MAX)
48
47 9 DO- 4
46 9 DO- 3
DI SCRET E OUT PUT 1
45 9 DO- 2 RT + 6
2 T+
44 9 DO- 1 R- 7
RS- 4 2 2 PORT 3 R+
43 + 12 / 2 4 V DC T- 8
REL AY DRI V ER POWER
I NPUT 4
42 ( 0.8 AMP MAX) RT - 9
5 GND
41 DI - H
40 DI - G
39 DI - F
38 DI - E
DI SCRET E I NPUT S 7
( APPL Y + 2 4 V T O ACT I V AT E)
37 DI - D
36 DI - C
35 DI - B
34 DI - A
33 COM
J UMPER I F USI NG I NT ERNAL
POWER F OR DI SCRET E I NPUT S
32 2 4 V DC OUT PUT
POWER F OR
DI SCRET E I NPUT S
31
6 Woodward
Manual 26691 2300E Digital Control
6 F OR OPT I ONAL CURRENT T RANSF ORMER CONNECT I ON, SEE DET AI L " A" .
Woodward 7
2300E Digital Control Manual 26691
Chapter 2.
Installation
Introduction
This chapter contains general installation instructions for the 2300E control.
Power requirements, environmental precautions, and location considerations are
included to determine the best location for the control. Additional information
includes unpacking instructions, electrical connections, and an installation check-
out procedure.
The surface of this product can become hot enough or cold enough
to be a hazard. Use protective gear for product handling in these
circumstances. Temperature ratings are included in the specification
section of this manual.
Unpacking
Before handling the control, read all of this chapter and “Electrostatic Discharge
Awareness” at the beginning of this manual. Be careful when unpacking the
electronic control. Check the control for signs of damage such as bent or dented
panels, scratches, and loose or broken parts. If any damage is found,
immediately notify the shipper. Do not take the control out of the ESD bag it ships
in until ESD precautions are in place. Keep yourself discharged while handing
the unit outside the ESD bag, at least until it is grounded.
Power Requirements
The 2300E control requires a voltage source of 18 to 36 Vdc, with a current
capacity of at least 600 mA for operating power. If a battery is used for operating
power, an alternator or other battery charging device is necessary to maintain a
stable supply voltage. The battery charging device should be suppressed from
load dump events or the power bus must have central suppression. The 2300E
does not have sufficient capability to withstand all battery load dump events.
8 Woodward
Manual 26691 2300E Digital Control
Location Considerations
This product is intended for installation in a “closed electrical operating area” or in
an enclosed industrial control cabinet. Consider these requirements when
selecting the mounting location:
Adequate ventilation for cooling
Space for servicing and repair
Protection from direct exposure to water or to a condensation-prone
environment
Protection from high-voltage or high-current devices, or devices which
produce electromagnetic interference (segregate the unit and wiring by at
least 15 cm (6 inches).
Avoidance of vibration
Selection of a location that will provide an operating ambient air temperature
range of –40 to +70 °C (–40 to +158 °F) at the control
The control must NOT be mounted on the engine.
Electrical Connections
All inputs and outputs are made through screwless spring-actuated terminal
blocks. Use ESD precautions noted above when installing the wiring to prevent
damage due to ESD.
The spring clamp can be actuated by using a standard 2.5 mm or 3/32 inch flat
bladed screwdriver. The terminal blocks accept wires from 0.08–4 mm²
(27–12 AWG). Two 18 AWG or three 20 AWG wires can be easily installed in
each terminal. Wires for the fixed mounted power terminals should be stripped
5–6 mm (0.22 inch) long.
Do not tin (solder) the wires that terminate at the terminal blocks. The
spring-loaded terminal blocks are designed to flatten stranded wire,
and if those strands are tinned together, the connection loses
surface area and is degraded.
Woodward 9
2300E Digital Control Manual 26691
Relay outputs, contact inputs, and power supply wiring do not normally require
shielding, but can be shielded if desired. Shields should terminate to chassis and
may be direct or share a shield pin except the AI or CAN shields.
The 2300E is designed for shield termination to earth ground at the control. If
intervening terminal blocks are used in routing a signal, the shield should be
continued through the terminal block. If shield grounding is desired at the
terminal block, it should be ac coupled to earth with a capacitor. All other shield
terminations except at the control (in the field) should be ac coupled to earth
through a capacitor. A 1000 pF, 500 V capacitor is typically sufficient, however
1–10 nF, 500–1500 V may be used or needed, and 1000 pF (1 nF) 1000 V is
recommended. The intent is to provide a low impedance path to earth for the
shield at frequencies of 150 kHz and up. Multiple direct connections of a shield to
earth risk high levels of current to flow within the shield (exception, see note
below on cabinet installations).
Shields can be grounded at both ends (2300E and load) if the cable length is
sufficiently short (i.e., within a cabinet, less than about 10 m straight line between
the ground points) to prevent ground loop current in the shield.
The potential transformer secondary line-to-line voltage must produce 90 to 120 Vac or
200 to 240 Vac. The PT and CT input connections are not needed if using a DSLC for
load sharing or load control. Refer to the plant wiring diagram, Figure 1-2.
The load share signals have 4 kV ESD withstand when the control is
not grounded rather than 8 kV or more on other pins. (Load Share
Lines have at least 7 kV withstand when the control is grounded.)
Use shielded cable and connect the load-sharing lines directly to terminals 10(+)
and 11(–). Connect the shield to terminal 12(chassis). When all controls in the
system are of the 2300E, 2301D, or 2301A types, the shields may be connected
continuously between controls. When load sharing with different controls, do not
connect the shields at the point where connections are made to the load-sharing-
line bus or if needed, connect only through a capacitor. The droop contact for
selecting droop or isochronous operation is wired in series with the circuit-
breaker auxiliary contact between terminal 37 and terminal 31 (see CB
Aux/Droop contact).
Woodward 11
2300E Digital Control Manual 26691
When running a single unit on an infinite bus with an external load control device,
terminals 37 and 40 must be connected to terminal 31 to connect the Load
Matching Circuit to the load-sharing lines. The load-sharing lines must be wired
to the external load control device. The circuit-breaker auxiliary contact will then
be connected to this device and not to the 2300E.
When power is applied, the 2300E begins performing internal memory tests to
‘boot-up’ the processor, which takes approximately 2 seconds to complete. The
CPU Status LED between terminals 30 and 31 remains on during this boot-up.
The control will remain in I/O lock and will not control the prime mover until the
boot-up is complete. For systems requiring fast start functions, it will be
necessary to continuously power the 2300E.
DO NOT attempt to start the prime mover while the CPU Status LED
is RED.
DO NOT apply power to the control at this time. Applying power
before a control is completely connected may damage the control.
The following example is using the default logic for the discrete inputs. Positive
Voltage is supplied to the discrete input terminal when an input switch or relay
contact closes. This will cause the input state for that discrete input to be
“TRUE”. The input terminal will be open circuited when the input switch or relay
contact opens. This will cause the input state for that discrete input to be
“FALSE” . When the input switch or relay contact is closed, the voltage supplying
the discrete inputs should be present from the appropriate discrete input
(terminal 34, 35, 36, 37, 38, 39, 40, or 41) to terminal 33 (common). Terminal 33
is the common return path for all of the discrete input channels. A lower voltage
indicates that the switch contacts have too high a resistance when closed and
should be replaced. These terminals must be isolated from ground.
12 Woodward
Manual 26691 2300E Digital Control
In systems that provide an external low voltage source to power the 2300E
control, the discrete inputs may be powered by this external low voltage. The
voltage source used must be capable of supplying 100 mA at a voltage level of
18 to 36 Vdc. Connect the external low voltage source negative to terminal 33(–).
Connect the external low voltage source positive to the appropriate input switch
or relay contact and connect the mated switch or relay contact to the
corresponding discrete input terminal on the 2300E control.
In systems where the external low voltage dc power is not appropriate, the
discrete inputs may be powered by the internal 24 Vdc Discrete Input Power
source at terminal 31 and 32. This source is capable of supplying 100 mA at a
voltage level of 24 Vdc. Connect the internal 24 Vdc voltage source positive from
terminal 31 to the appropriate input switch or relay contact, and connect the
mated switch or relay contact to the corresponding discrete input terminal on the
2300E control. Assure that a connection exists between terminal 32 and terminal
33 when using the internal Discrete Input Power. Do not power other devices
with the internal discrete input power source, and assure that the switch or relay
contacts used are isolated from any other circuit or system. The internally
provided contact wetting voltage may not be used for anything other than DI
Contact wetting; it is dedicated to this function.
Discrete inputs with cable lengths where the end points are
physically greater than 30 meters apart and which are used for
critical functions, such as emergency stop, should not be floated in
either an on or off state. These inputs should be switched to either
+24 Vdc or ground, never floated or tied to reference with a resistor.
The type of the analog inputs can also be chosen from one of the following
options:
4–20 (mA)
0–5 (V)
±2.5 (V)
Woodward 13
2300E Digital Control Manual 26691
This input is limited to a frequency range of 100–24 950 Hz and a voltage range
of 1.7–35 Vac. (The MPU voltage at the 2301E must be above 2.7 Vac in case of
a signal above 13 000 Hz.)
With proper MPU, gear size and MPU-to-gear clearance, speed measurement
should be capable down to 100 Hz. Check the speed sensor for visible damage.
Standard MPU clearance is recommended to be between 0.25 and 1.0 mm
(0.010 and 0.040 inch) at the closest point. Make sure that the gear has less than
0.5 mm (0.020 inch) diametric run out. See manual 82510, Magnetic Pickups and
Proximity Switches for Electronic Governors.
Power wiring for using the PWM output function is required to be local and
dedicated, only located on the engine skid or relatively close to the control and
PWM load. The power connected to control 48(+) and 49(–) terminals must also
be used for the relay driver external Vdc source connected at terminals 42(+) and
43(–). In addition, the PWM load device power must also be from the same
source as the power connected to control terminals 48(+) and 49(–-).
Verify that the output’s shielded wire has continuity its entire distance to the output
device and is insulated from all other conducting surfaces. This current driver
based output is designed to drive into impedances of up to 250 Ω. This output is
not isolated from the other control inputs and outputs, thus an isolation device may
be required with this output if the device being interfaced to is not isolated.
14 Woodward
Manual 26691 2300E Digital Control
Communication Ports
The control’s two serial communication ports are used to configure and service
the unit. These ports are on a common return and are isolated ports.
The RS-232 serial communication service port communicates using either the
2300E Toolkit Service Tool or the Control Assistant software. Refer to Figure 2-2
for plant wiring information.
RS-232
See Figure 2-2 for cable connection.
RXD TXD
TXD RXD
2301E
50
Woodward 15
2300E Digital Control Manual 26691
RS-422
See Figure 2-3 for termination and cable connection example.
2301E
Termination
For RS-422, termination should be located at the receiver when one or more
transmitters are connected to a single receiver. When a single transmitter is
connected to one or more receiver, termination should be at the receiver farthest
from the transmitter. Figure 2-4 is an example.
The preferred method for common wiring is to include a separate wire in the
cable that connects the circuit grounds at each port together with a dedicated
wire inside the cable shield.
16 Woodward
Manual 26691 2300E Digital Control
If the total cabling is > 30 m (typical), the preferred shield connection is to
connect the shield to earth ground (chassis) at one point (most critical port),
using a capacitor to terminate the shield at the remaining ports. If the total
cabling is < 30 m, connect the shield directly to the earth ground at each port.
The alternate, less robust, way to connect shield and common is to connect all
circuit grounds/commons at each port to the shield instead of a separate wire,
and then connect the shield to earth ground at one point (most critical port), using
a capacitor to terminate the shield at the remaining ports.
If there are non-isolated nodes on the party line, connect the shield to earth
ground at a non-isolated node, not at an isolated node. Figures 2-5 and 2-6
illustrate these cabling approaches.
Figure 2-5. Preferred Multipoint Wiring Using Shielded Twisted-pair Cable with a
Separate Signal Ground Wire
Woodward 17
2300E Digital Control Manual 26691
Figure 2-6. Alternate Multipoint Wiring Using Shielded Twisted-pair Cable without
a Separate Signal Ground Wire
The CAN Port is electrically isolated from all other circuits in the 2300E, requiring
a common to be wired between this port and other ports on the CAN network.
CAN common needs to be sent with the signal wires, but can be separately
shielded. Isolation used on this port is SELV rated with respect to product safety
requirements.
The CAN shield pin is AC coupled to chassis at the 2301E control. The shield
must be directly connected to protective earth ground at one and only one point
in the CAN network.
The CAN Port supports SAE J1939 and CiA CANopen network protocols.
18 Woodward
Manual 26691 2300E Digital Control
When using DeviceNet cables outside a vibration damped enclosure, use the
“Thick” or “Trunk” cable. The “Thin” or “Drop” cables have very small wire sizes
that fatigue easily. Below are two DeviceNet CAN cables that are compatible with
isolated CAN use off engine.
Below are CAN cables that are compatible with isolated CAN use rated at high
temp.
“J1939” cable is a good example of CAN cable for use with un-isolated CAN
ports and for on-engine use. This cable does not include the extra wire used to
carry the common reference Raychem makes a compatible cable as do many
other manufacturers.
The basic cable requirements are listed below. When selecting other cables, be
sure they meet these requirements.
Woodward 19
2300E Digital Control Manual 26691
Figure 2-7 illustrates what the DeviceNet cables will look like including shielding.
There is a foil tape around each conductor pair as well as a braided shield
around the entire group of conductors. J1939 cables will not include the DC
power pair and related extra shielding.
Network Construction
There are several different ways to physically connect devices on a CAN
network. Woodward recommends that multi-drop networks be constructed using
either a “daisy chain” configuration (also called zero length drop line) or a
“backbone” with very short drop lines for best performance. In a daisy chain
configuration, wires are run from one device to the next device without drop lines.
In a backbone with stubs configuration, a main trunk line is run between the two
devices that are physically farthest apart and have the physically longest cable.
Stub lines are run from the intermediate devices to the trunk line. Stubs should
be kept as short as possible and may never exceed 6 m (20 ft). As shown in
Figure 2-8, it is acceptable to mix both methods on the same network.
A daisy chain (zero drop length) connection is not feasible at the 2300E connection
due to the sealed connector design. The next best alternative is to use a very short
drop line from the trunk into the 2300E. Special ‘T’ connectors (Tap in the diagram
above) are available from multiple manufacturers to ease the wiring harness
manufacture. Also available from the same manufacturers, are termination
resistors that plug directly into the ‘T’ connectors for the network ends.
Due to the port isolation on this port, a common wire is needed between all units
on the network. The preferred method for isolated ports is to include a separate
wire within the CAN cable. This keeps the communications and ground reference
at the same potential at all times. The DeviceNet cables listed in this manual
have the common wire feature.
20 Woodward
Manual 26691 2300E Digital Control
Node
Node
Multiple Node
Node Daisy Chain
Node Drop Line Node Drop Line
Terminating Tap Multi-Port Tap
Resistor
Node
Node Node
Node
Drop Line
Node
Node Node
{
{
VIS-199
Zero Length Drop Line Short Drop Lines (6 m / 20 ft)
2012-10-25
Non-isolated nodes may not have a signal common available for connection. If a
signal common is not available, use the alternate wiring scheme of connecting
the CAN ground wire from the isolated nodes to the B- terminal at a non-isolated
node. B– is typically the signal reference for CAN if isolation is not provided. The
CAN common wire should not be grounded. The only exception to this rule is if
one of the devices on the link is not isolated, then connecting CAN common to
B– on that device may create a connection to the B- power supply ground,
assuming the power supply has a connection to ground. Otherwise, no other
connections to ground or physical earth should be provided.
Termination
It is necessary to terminate the network to prevent interference caused by signal
reflections. Depending on network length, many CAN networks will not operate
without proper termination.
In order to allow the possibility of removing and inserting a unit onto a running
network, the CAN termination network is not included inside the 2300E control.
An external CAN termination network must be provided.
As a rule, no matter how many units are on a network, there should never be
more than two network terminations installed. Termination resistors must be
installed only for the two units that are at the physical ends of the network.
Terminating more than two units can overload the network and stop all
communications.
Woodward 21
2300E Digital Control Manual 26691
Termination is a simple 121 Ohm, ¼ watt, 1% metal film resistor placed between
CAN high and CAN low terminals at the two end units, a differential termination.
Do not connect the termination resistor to anything besides the CAN high and
CAN low wires.
Shielding
Shielded CAN cable is required between the 2300E and any other devices.
Unshielded or improperly shielded cables are likely to cause communication
problems and unreliable control operation. Improper shield termination to ground
can also cause communication problems and unreliable control operation.
The standard for CAN networks is that each device will have an ac-coupled
shield connection (ac-coupled: connected through a capacitor). Additionally a
single direct network shield ground location may be provided in some situations.
Typically the direct shield grounding location does not have to be at a unit
connector; it can be any convenient place in the system, and is recommended to
be used.
The 2300E has been constructed so that the CAN port shield connection is ac
coupled to chassis ground, chassis ground must be tied directly to earth ground.
The CAN port may also have the CAN cable’s shield tied directly to ground, but
care must be taken in how this is accomplished. It is expected and recommended
that each network have one direct connection to chassis ground. The chassis
grounding point should be chosen nearest the most critical device on the network.
Wiring length restrictions depend on the baud rate used. Table 2-3 is appropriate
for CANopen, at the 4 supported baud rates. The “Trunk” is the length between
the two units that are at the physical ends of the network. The “Cumulative Drop”
is the added length of all drop wires from the trunk to the devices. This only
applies to “backbone” type networks since Daisy chain networks do not have
drops. The “Maximum Drop” is the maximum allowed for any 1 drop. Any network
configured for 1000 kbps should use the daisy chain topology to reduce the
possibility of reflections.
SAE J1939 protocol is restricted to 250 kbps and the SAE J1939 standard limits
wiring distances to 40 meters, when un-isolated controls are connected on the
link.
The limits below are the maximum allowed by the CAN standard. To maintain a
high level of reliability in practice, shorter lengths are highly recommended.
22 Woodward
Manual 26691 2300E Digital Control
Visual Inspection
1. Check the linkage between the actuator and the prime mover for looseness
or binding. Refer to the appropriate actuator manual and to manual 25070,
Electric Governor Installation Guide, for additional information on the linkage.
The actuator lever should be near but not at the minimum position
when the fuel or steam rack is at the minimum position. If the
actuator lever gets to its minimum position before completely
shutting off fuel or steam, the control may not be able to shut down
the prime mover, causing damage to equipment or injury or death.
2. Check for correct wiring in accordance with the plant wiring diagram, Figure 1-2.
3. Check for broken terminals and loose terminal screws.
4. Check the speed sensor for visible damage. Check the clearance of the
magnetic pickup between the gear and the sensor, and adjust if necessary.
Clearance should be between 0.25 and 1.0 mm (0.010 and 0.040 inch) at the
closest point. Make sure the gear has less than 0.5 mm (0.020 inch)
diametric run-out. See manual 82510, Magnetic Pickups and Proximity
Switches for Electric Governors.
Woodward 23
2300E Digital Control Manual 26691
Chapter 3.
GAP Software and Communication
Procedures
Introduction
GAP Software
Woodward’s GAP 3.x is a Windows based software program that allows controls
engineers to create block format application programs for the 2300E. Once the
control logic is entered using the program’s graphical programming environment,
the GAP software compiler function generates code that runs in the control.
The block format allows a controls engineer to re-use a library of known control
blocks, string them together with other known control blocks, and develop a
software program to match customer needs. Through years of use, GAP has
proven to be an extremely successful software package that can be field
modified, even after installation or based on changing customer needs.
An additional advantage incorporated into GAP is the unique rate group structure
on which it operates. Variable execution time blocks have been avoided. This
means that under an unanticipated set of conditions (system upset), the processor
will not become overburdened, and will have time to complete its assigned tasks.
Only with predictable execution times can a multitasking operating system have a
guaranteed update rate. Software tasks may be programmed to run every 5
milliseconds, 10 ms, 20 ms, etc., and all tasks will run simultaneously.
24 Woodward
Manual 26691 2300E Digital Control
The 2300E has the following specifications:
CPU: MPC5553
Clock Speed: 70 Mhz
Flash Memory - 1.5 Mbytes
o Application software file size
o Boot software file size
o Service Interface Definition (SID) software file size
RAM Memory – 68 Kbytes
o Rate Group Allocations
o Variables
EE Memory – 16.0 Kbytes
o Saved Tunables / Variables
o Event Managers
GAP uses a Rate Group structure of the following times: 5 mSec, 10 mSec, 20
mSec, 40 mSec, 80 mSec, and 160 mSec. When adding a Rate Group to the
application, the software will allocate approximately 1.6 Kbytes of overhead for
these Rate Groups. Therefore adding all six Rate Groups will subtract 9.6 Kbytes
of the available RAM of 45 Kbytes, leaving about 35 Kbytes. A suggestion when
programming the 2300E would be to not use all of the Rate Groups available. In
the Standard 2301E application, only two rate groups were used 5 mSec and 80
mSec. The application size is 200 Kbytes, the Total Load on the microprocessor is
10% and the RAM Available is at 7.3 Kbytes. The key is to manage the application
so that the microprocessor is never loaded above 90% and the available RAM
should be monitored carefully as it falls below 2 Kbytes. Be mindful when adding
communications, as that functionality will consume additional RAM as well. Certain
blocks in GAP can also use up more RAM, for instance a Curves Block, the Data
Log Block or the Event Manager block. The Status_2301E block has this
information available: RAM_AVAIL, FLASH_AVAIL, and EE_AVAIL.
If an application file is loaded that exceeds the RAM size limitation or causes an
internal system fault, and causes the control to shut down, there is a backdoor boot
up process. Shorting TP6 to TP8 and re-powering the control causes the control to
automatically go into the boot mode. This boot mode allows you to download a
corrected application.
Woodward 25
2300E Digital Control Manual 26691
The 2300E default baud rate is 115200, which can be entered in the SOS
Servlink OPC Server window or it will automatically detect the correct baud rate.
26 Woodward
Manual 26691 2300E Digital Control
Chapter 4.
Product Support and Service Options
OEM or Packager Support: Many Woodward controls and control devices are
installed into the equipment system and programmed by an Original Equipment
Manufacturer (OEM) or Equipment Packager at their factory. In some cases, the
programming is password-protected by the OEM or packager, and they are the best
source for product service and support. Warranty service for Woodward products
shipped with an equipment system should also be handled through the OEM or
Packager. Please review your equipment system documentation for details.
Woodward 27
2300E Digital Control Manual 26691
Replacement/Exchange: Replacement/Exchange is a premium program
designed for the user who is in need of immediate service. It allows you to
request and receive a like-new replacement unit in minimum time (usually within
24 hours of the request), providing a suitable unit is available at the time of the
request, thereby minimizing costly downtime.
This option allows you to call your Full-Service Distributor in the event of an
unexpected outage, or in advance of a scheduled outage, to request a
replacement control unit. If the unit is available at the time of the call, it can
usually be shipped out within 24 hours. You replace your field control unit with
the like-new replacement and return the field unit to the Full-Service Distributor.
Flat Rate Repair: Flat Rate Repair is available for many of the standard
mechanical products and some of the electronic products in the field. This
program offers you repair service for your products with the advantage of
knowing in advance what the cost will be.
Flat Rate Remanufacture: Flat Rate Remanufacture is very similar to the Flat
Rate Repair option, with the exception that the unit will be returned to you in “like-
new” condition. This option is applicable to mechanical products only.
When shipping the item(s), attach a tag with the following information:
return number;
name and location where the control is installed;
name and phone number of contact person;
complete Woodward part number(s) and serial number(s);
description of the problem;
instructions describing the desired type of repair.
Packing a Control
Use the following materials when returning a complete control:
protective caps on any connectors;
antistatic protective bags on all electronic modules;
packing materials that will not damage the surface of the unit;
at least 100 mm (4 inches) of tightly packed, industry-approved packing material;
a packing carton with double walls;
a strong tape around the outside of the carton for increased strength.
Replacement Parts
When ordering replacement parts for controls, include the following information:
the part number(s) (XXXX-XXXX) that is on the enclosure nameplate;
the unit serial number, which is also on the nameplate.
28 Woodward
Manual 26691 2300E Digital Control
Engineering Services
Woodward’s Full-Service Distributors offer various Engineering Services for our
products. For these services, you can contact the Distributor by telephone or by
email.
Technical Support
Product Training
Field Service
Technical Support is available from your equipment system supplier, your local
Full-Service Distributor, or from many of Woodward’s worldwide locations,
depending upon the product and application. This service can assist you with
technical questions or problem solving during the normal business hours of the
Woodward location you contact.
You can also contact the Woodward Customer Service Department at one of the
following Woodward facilities to obtain the address and phone number of the
nearest facility at which you can obtain information and service.
Woodward 29
2300E Digital Control Manual 26691
Technical Assistance
If you need to contact technical assistance, you will need to provide the following information.
Please write it down here before contacting the Engine OEM, the Packager, a Woodward
Business Partner, or the Woodward factory:
General
Your Name
Site Location
Phone Number
Fax Number
Number of Cylinders
Type of Fuel (gas, gaseous, diesel,
dual-fuel, etc.)
Power Output Rating
Application (power generation, marine,
etc.)
Control/Governor Information
Control/Governor #1
Serial Number
Control/Governor #2
Serial Number
Control/Governor #3
Serial Number
Symptoms
Description
If you have an electronic or programmable control, please have the adjustment setting positions or
the menu settings written down and with you at the time of the call.
30 Woodward
Manual 26691 2300E Digital Control
Appendix A.
2300E Control Specifications
Woodward Part Numbers:
8273-1011 2300E Load Sharing and Speed Control, 24 Vdc input,
Ordinary Locations
8273-1012 2300E Load Sharing and Speed Control, 24 Vdc input,
Hazardous Locations
8928-5014 Control Assistant
8928-1303 2300E Toolkit Service Tool
Woodward 31
2300E Digital Control Manual 26691
Revision History
Changes in Revision E—
Updated Regulatory Compliance section
Revised Declaration of Conformity
Changes in Revision D—
Added information clarifying the memory structure of the 2300E.
Revise Australia and New Zealand compliance information
Changes in Revision C—
Corrected 3-phase PT Burden in Specifications section to 90–240 Vac line-
to-line, 45–66 Hz
Changes in Revision B—
Added new Marine certifications (BV, NKK, CCS)
Added product weight
Changes in Revision A—
Removed references to configurable inputs/outputs
32 Woodward
Manual 26691 2300E Digital Control
Declarations
Woodward 33
We appreciate your comments about the content of our publications.
Send comments to: [email protected]