Manual For Solar Technician: November 2015
Manual For Solar Technician: November 2015
Manual For Solar Technician: November 2015
net/publication/284259337
CITATION READS
1 18,584
2 authors:
Some of the authors of this publication are also working on these related projects:
PARTICLE SWARM OPTIMIZATION APPROACH FOR DISTRIBUTED GENERATION PLANNING TO IMPROVE VOLTAGE PROFILE MARGIN View project
Micro-Grid Management and Control Systems to Provide Efficient Energy Solutions in the Mountainous Region of Nepal View project
All content following this page was uploaded by Ashish Shrestha on 21 November 2015.
Authors:
Ajay Singh
ME in Planning and Operation of Energy System, Kathmandu University
Assistant Lecturer
Khwopa College of Engineering
Bhaktapur, Nepal
E-mail: [email protected]
Ashish Shrestha
ME in Planning and Operation of Energy System, Kathmandu University
E-mail: [email protected]
Website: [email protected]
2014
Contents
INTRODUCTION ..................................................................................................... 7
INVERTER ............................................................................................................. 43
PV APPLICATIONS ............................................................................................... 69
13.1 The Need of Reliable Electricity .............. Error! Bookmark not defined.
14.3 Completing the solar site analysis ............ Error! Bookmark not defined.
14.4 C ............................................................................................................ 76
Maintenance ............................................................................................................ 81
15.1 Solar radiation fundamentals .................... Error! Bookmark not defined.
15.3 Completing the solar site analysis ............ Error! Bookmark not defined.
15.4 C ............................................................................................................ 81
16.3 Safety Testing High Voltage .................... Error! Bookmark not defined.
COSTING ............................................................................................................... 85
17.3 Completing the solar site analysis ............ Error! Bookmark not defined.
17.4 C ............................................................................................................ 85
INTRODUCTION
Energy exists in different form in nature and the most important is the electrical
energy. Electrical energy can be produced from the various source of energy available
in the nature and the primary source of the energy is sun. Different technologies are
used to produce electrical energy with the consideration of environmentally friendly
and sustainable form of energy. The newly growing renewable energy, which is
naturally replenished on a human timescale, technologies are more pronounced for
cleaner and sustainable energy. Among the renewable energy technologies, the
photovoltaic (PV) system is more pronounced.
Photovoltaic systems are the devices which converts light energy coming from sun to
the electrical energy.
In 1905, Albert Einstein explained his theory of photoelectric effect which explains
the science behind the photovoltaic cell and understanding the physical process of that
cell. Limited researches are continued on selenium solar cell despite its lower
efficiency and higher production costs. Jan Czochralski, a Polish scientist, figured out
a method to grow single-crystal silicon which laid the foundation for solar cells based
on silicon.
The year 1954 also called the birth of photovoltaics when world’s first photovoltaic
cell (solar cell) is created in the Bell laboratory. The efficiency achieved in that cell
was six percent. In 1957, Hoffman Electronics achieved 8% efficient photovoltaic
cells.
In 1958, the Vanguard I space satellite used a small (less than one watt) array to
power its radios. Later that year, Explorer III, Vanguard II, and Sputnik-3 were
launched with PV-powered systems on board. Despite faltering attempts to
commercialize the silicon solar cell in the 1950s and 60s, it was used successfully in
powering satellites. It became the accepted energy source for space applications and
remains so today. In 1963, Japan installs a 242-watt, photovoltaic array on a
lighthouse, the world’s largest array at that time. In 1972, the Institute of Energy
Conversion is established at the University of Delaware to perform research and
development on thin-film photovoltaic (PV) and solar thermal systems, becoming the
world’s first laboratory dedicated to PV research and development.
In 2000, first Solar begins production in Perrysburg, Ohio, at the world’s largest
photovoltaic manufacturing plant with an estimated capacity of producing enough
solar panels each year to generate 100 megawatts of power.
The expansion of PV system and technology at the turn of the twenty-first century
couldn’t have come at a time when it was more needed. People till uses more
conventional fuel which, fortunately, harnessing the sun for power presents a cleaner
and more efficient alternative to the dirtier source of energy. As the threat of global
warming and climate change increases, PV system and related technologies provide
opportunities that are impossible to ignore.
The emerging opportunities in PV system are growing rapidly. The expanding market,
increasing of its related job and useful applications continue to be developed. All the
corners of the glove, regardless of wealth or even abundant sunlight, are developing a
demand for solar power. This is not happening at some point in the distant future but
happening now so, it is great time to be a part of industry as a PV professional.
i) Cleanliness
ii) Reliability
iii) Safety
The PV systems require sunlight to operate. It do not require any materials that
can combust or explode when ignited, or remain toxic for several years so makes
PV system safer. However, some PV products use toxic materials which can
create an increased hazard in future.
PV systems do not require any fuel for run rather require only sun light, which
comes at no charge. Additionally, the minimum maintenance is required so
reduces maintenance costs. Hence overall running costs of PV system is much
more less.
v) Silence
Unlike generator and other sources of power and its generating system, PV makes
no any noise.
vi) Modularity
The size and scope of PV system is not fixed. PV systems are scalable and can be
expanded at any time to increase the amount of power. The growing trend towards
inverter of modular design. Components are individually replaceable in case of
failure.
vii) Independence
Because PV systems can be used for remote and small power generation plants,
they are more decentralized and consistent power grid that is less dependent on
utility companies. They are also for distributed power generation.
The PV systems are used for long term even 20-30 years, which provide long term
energy to the people, thus it is sustainable energy.
The efficiency of solar cell is improved and it is still in range of 14% to 40%
which is much less than the other sources of power. Due to its inefficiency, more
solar power is required to operate same device.
After installation, PV system is almost safe but their manufacturing, handling and
storage comes with various hazards. Potentially explosive gases like phosphine
and diborane are used in making PV module. Thin-film technologies uses
cadmium telluride and other hazardous materials may create long term hazardous
waste. PV system installer also needs proper training in handling the components.
The durability of proper designed and installed PV systems often justifies and
overweighs the associated costs and risks.
The PV system installation requires large area for the deployment. If installed on
land the cause associated land use problems because it is used for 25 years or
longer. The large area exposure to light is not always available on roof of the
buildings to meet the required area of installation.
Sun doesn’t always shine in day time. In addition to this, geographic location,
climate and other environmental conditions affect the amount of exposure to any
available sunlight. Thus it creates inconsistent source of energy.
The more technology and its knowledge, the more power will receive society from
sun in affordable and practical way. The lack of knowledge slows the growth of
alternative energy market as well as PV system.
1.6 Environment, health and safety issue
The cleaner energy as electricity can be available from the PV system without
affecting the environment and health because it doesn’t produces GHG gases and
toxic materials when under operation. PV system has many environmental advantages
for generation of electricity over other conventional sources. However, if the life-
cycle of PV system is considered then there are environmental, health and safety
hazards associated with the manufacture of solar cells and installation of PV system.
The PV industry uses toxic chemicals in manufacturing process of the PV cells. The
hazards differ for different thin film technologies and deposition process. The
environmental issues are related to the generation of liquid- and solid-wastes during
wafer slicing, cleaning, and etching, and during processing and assembling of solar
cells. In thin-film technologies, Silane used in bulk quantities which may facilities
may pose hazards to the surrounding community if adequate separation zones do not
exist. PV modules will have to be decommissioned at the end of their useful life, 20 to
30 years after their initial installation. In decommissioning these devices, the principal
concern will be associated with the presence many hazardous chemicals.
The different health problems are associated with the toxic materials. In production
facilities, workers may be exposed to Cd compounds through the air they breathe, as
well as by ingestion from hand-to-mouth contact. Inhalation is probably the most
important pathway, because of the larger potential for exposure, and higher absorption
efficiency of Cd compounds through the lung than through the gastrointestinal tract.
Although elemental selenium has only a mild toxicity associated with it, hydrogen
selenide is highly toxic. It has an Immediately Dangerous to Life and Health
concentration of only 1 ppm. Potential public health issues are related to the use of
hydrogen selenide in facilities that use hydrogen selenide as a major feedstock
material. Associated hazards can be minimized by using safer alternatives, limiting
inventories, using flow restricting valves and other safety options.
The manufacture of photovoltaic modules uses some hazardous materials which can
present health and safety hazards, if adequate precautions are not taken. Routine
conditions in manufacturing facilities should not pose any threats to health and the
environment.
Some of hazardous chemicals used in PV manufacturing and it health hazards are
shown in table below:
i) Photovoltaic Cell
The basic unit of PV system is called photovoltaic cell which can generate
electricity when exposed to light. It is usually semiconductor and square or disc
shape or tiny particle of powder.
ii) Module
The module is the integration of PV cells. When the PV cells are wired in
organized form which provide electric power in PV system is called module.
When there is one or more than one module then it is refer as panel. The PV cells
are laminated between two layers or substrate.
iii) Array
It is the electronic device which controls the charge of the battery. In other words,
the controller regulates the charge to maintain specific battery voltage. It is the
intermediate part between battery and solar panel.
v) Battery
vi) Inverter
Inverter is the electrical device which converts the DC signals of voltage and
current to AC signals of voltage and current. The array produces DC which is
used to charge the battery and lastly converted to AC by means of inverter.
These are the electrical devices which consume electrical energy in either DC or
AC form and gives output energy in different forms for the end-use services.
When the load consumes DC electrical power then the load is DC load and
consumes AC power then called AC load. For example, DC loads; DC motor, DC
LED lamp, TV operates on DC power etc. AC loads; ac fan, ac motors, ac lights
etc.
The PV systems are categorized on the basis of its use whether used with AC system
or with storage system or standalone system.
The types of Solar PV systems are:
i) Standalone PV system
i) Standalone PV system
Since the solar modules only produce electric energy during daytime, it is necessary
to store energy for the night or for cloudy days. Such storage systems mostly use
rechargeable lead batteries, due to their ability to accept with high efficiency both low
and high input voltages. A battery regulator prevents over-charging; a load shedding
circuit prevents deep discharges.
PV Direct systems are usually very simple systems where the photovoltaic panel
is connected directly to a motor or pump which matches the voltage and amperage
output of the panel. When the sun shines and the PV panel produces electricity,
the device runs--when the sun is not available, the device stops. This system is
often used for livestock where a well-pump lifts water out of the ground to a
watering trough in remote locations. Other applications include solar
powered attic fans, irrigation systems and small day-time garden waterfalls or
fountains.
iii) Grid Tied PV system
The simplest and most cost effective PV design for most sites is the "Grid-
Tie" (sometimes referred to as intertied or utility-interactive) system. This
system does not provide backup power during a power outage (even if the
sun is shining) but for sites with reliable grid power, this is usually
the logical system choice.
2.1 Terminology
The basic terminology in photovoltaic system includes the following:
i) Electricity
ii) Conductor
Conductor is the any material which allows the electrons to flow through it.
iii) Circuit
When there is closed path in which circuit current flows and provide power to the
load is called closed circuit. When power to the load cannot be provided with
electrical network configuration or current cannot be allowed to flow in the circuit
is called closed circuit.
iv) Current
v) Voltage
It is the driving force which causes the flow of electron or electric charge through
the circuit. It is measured with voltmeter and its unit is volt (V).
vi) Ampere-hour(Ah)
It is the unit of energy which is equivalent to the power consumed by 1000 Watt
load in one hour.
While choosing appliance for the PV system, we must consider the following points:
- The voltage level of supply side (generation side) and the demand side
(appliances of the consumer side) must be matched and are of same type either
AC or DC.
- The power of the energy produced and used must be matched and under safety
level.
- The appliances must be compatible with the type of power and current. The
appliance may be either AC of DC type load so must be supplied with
corresponding type of source signals.
12 V Load
i) Series combination
I. Series connection
- The total circuit voltage is the algebraic sum of individual source voltage.
When the same terminals are joined at a point i.e. positive terminal of all source
are connected at a point and negative terminals are connected together at a point
then the combination of sources is called parallel connection of source.
This type of connection of source combines both the series and parallel
combination of sources. It is the mixed type connection which includes both series
and parallel combination of sources. The voltage and current of the circuit is
depends upon how the connections are made.
I. Series connection
When the loads are connected end-to-end then the connection of loads is called
series connection of load. In this type of connection, one terminal of load is
connected to other terminal of another load. The current flowing through each
load is same but different voltage.
When the same terminals of each load connected at a point then the connection is
said to be parallel. The voltage across the each load is same but current is
different.
III. Series-Parallel connection
This is the mixed type connection of both series and parallel connection
2.6 Exercise
Problem1. Calculate the total voltages and current in the following cases:
a) Three panels having 12V DC nominal and 1.3A rated current are connected in
series.
b) Three panels having 12V DC nominal and 1.3A rated current are connected in
parallel.
c) Four panels having 12V DC nominal and 1.3A rated current are connected in
series and three types of this connection is connected in parallel.
d) Three panels having 24V DC nominal and 7.2A rated current are connected in
(i) series and (ii) parallel.
Problem2. You are given with a panel having 12V DC nominal and 1.3 A rated
current.
a) Design a 12 V DC system with these panels which gives circuit current 13A.
b) Design a 24 V DC system with these panels which gives circuit current 13A.
c) Design a 48 V DC system with these panels which gives circuit current 13A.
d) Connect the four panels to get 24V, eight panels to get 48V system voltages
and calculate the current in each case.
e) How can you design the system voltage as 120 V with these panels?
Problem3. Repeat the above problem2 by replacing the panel with 12V, 13Ah
battery.
SOLAR RESOURCES
3.1 General
The energy that can be received in the form of heat and light is called Solar Energy.
Generally the earth receives the energy from sun as visible light and other forms of
electromagnetic radiation which further divided into following three categories;
Photovoltaic System:
A photovoltaic system or PV system is a power system used to supply usable solar
energy in the form of electricity by means of photovoltaic. An arrangement of
different components is designed to perform such task including Photovoltaic Cell to
convert solar energy to electricity, Module to encapsulate substrate, Panel, Array,
Charge Controller to regulate the system voltage, Battery to store electrical energy,
Inverter to convert DC to AC, DC Loads, AC Loads etc.
3.2 Solar Radiation Fundamental
Solar light is a portion of the electromagnetic radiation given off by the solar system,
in particular invisible and visible spectrums of light, radiation and more. The radiant
energy emitted by sun is deflects and filters on Earth’s atmosphere, and obvious as
daylight when Sun is above the horizon. In other word, the energy that radiated from
sun is higher than that earth absolves. Majority of the sun’s harmful and poisonous
radiation are filtered by the earth’s atmosphere and our near-perfect positioning in the
solar system allows us to receive the benefits proximity to the Sun without being
broiled.
100%
Reflected
Reflection by
from
Atmosphere
Reflected by
Absorbed by
Atmosphere &
Earth
Solar Radiation mechanism is the important process for human as well as the entire
living beings. The whole life cycle of living beings is dependent on the solar
radiation. Organisms that produce their food from direct sun light use solar energy
along with carbon dioxide and water to produce starch in a process known as
photosynthesis. Similarly, other organisms depend on the explained organisms to
form the bottom level of the food chain. No any living beings exist without the sun, so
life as we know it depends on the solar radiation.
Generally, the tall trees, poles, construction, structure etc. play vital role to create
unwanted shadow. To get better performance the PV panel should be placed at such
location where solar access from 9am to 3pm. This optimum time frame is known as
solar window. Similarly, the panel should be placed in such place, where the sun light
strikes directly during winter season too.
All the loads must not run as peak load. Peoples must aware about load peaking and
efficiency of the appliances. The both peak load and low efficient devices increases
the cost and size of the PV system. The load must shifts peak time to off-peak time for
reduce peak demand of PV system which can reduce the size of PV system and hence
cost.
The power rating of load is available in the name plate of the device or manufacturer
provides a manual in which the power rating is given. If the power rating is not given
then the power can be calculated as:
For DC load,
The Voltage and current ratings are given in name plate in Volt and Ampere.
For AC load,
Refrigerator are automatic and auto power on and off o usually considers total energy
consumption while designing. It is recommended that these loads are used for
minimum time by use of automatic switches.
Quality of light is critical. There are several general categories of lighting and each
requirement is different from person to person. The lights are used for ambient
lighting, general lighting or task lighting. In ambient lighting, person require
minimum light, in general lighting, light require is for viewing objects, reading etc.
and in task lighting, the light is used for specific task which requires excess light.
It is convenient to find the use of light and appropriate device for lighting. Today, a
wide variety of lights at affordable costs are found with better efficiency in the
market. Solar lanterns are used which incorporate a solar module, battery and a light
in a single unit. The DC WLED light used in PV system increases the efficiency and
low size and cost PV system.
i) Use of manufacturer’s manual for the energy consumption of load and power
rating of load.
ii) The type of load either it may be AC of DC type loads.
vi) The duty cycle of load and energy conservation taken into account.
vii) The future expansion of load because of people, social and seasonal change.
While calculating these loads, we must consider the seasonal variation of loads, low
efficient loads, and standby power consumption of certain loads. The loads are
variable and under certain conditions some loads are prohibited to use in PV system to
reduce the size and cost of the PV systems. The mixed technology and improved
efficiency technique can be used to replace those loads.
For example, we consider the following loads in a building listed below with the
power rating and operation of hours:
4.6 Exercise
PHOTOVOLTAIC MODULE
Photovoltaic cell is the basic unit of the PV module. A photovoltaic cell comprises P-
type and N-type semiconductors with different electrical properties, joined together.
The joint between these two semiconductors is called the "P-N junction."Sunlight
striking the photovoltaic cell is absorbed by the cell. The energy of the absorbed light
generates particles with positive or negative charge (holes and electrons), which move
about or shift freely in all directions within the cell. Most of PV cell produce 0.5V and
thus 36 PV cells are connected in series to get 18V at STC. This string used for total
12 V nominal in application. The desired current is increased by increasing surface
area of the individual cell. This can be achieved by joining string in parallel.
The output characteristic of any module is characterized by its I-V curve. The most of
the I-V curves are provided at STC condition. This standard test conditions (STC)
relate to the IEC 60904 standards.
Open Circuit Voltage (Voc) is the maximum voltage which can be produced by the
solar panel. At this voltage, the current is zero.
Short Circuit Current (Isc) is the maximum current flows in the wire when the module
terminals are short circuited.
Maximum Power Point is the point in power curve of solar panel I-V characteristics
where the power output by the panel is maximum.
Module output reduces as temperature increases. Solar cells perform better in cold
rather than in hot climate and as things stand, panels are rated at 25˚C which can
be significantly different from the real outdoor situation. For each degree rise in
temperature above 25˚C the panel output decays by about 0.25% for amorphous
cells and about 0.4-0.5% for crystalline cells.
ii) Shading
A shadow on even a small part of the panel can have a surprisingly large effect on
the output. The cells within a panel are normally all wired in series and the shaded
cells affect the current flow of the whole panel. But there can be situations where
it cannot be avoided, and thus the effects of partial shading should be considered
while planning. If the affected panel is wired in series (in a string) with other
panels, then the output of all those panels will be affected by the partial shading of
one panel. In such a situation, an obvious solution is to avoid wiring panels in
series if possible.
Dirt and dust can accumulate on the solar module surface, blocking some of the
sunlight and reducing output.
6.1 General
A battery is a electrochemical device that can store electrical energy in chemical form.
It contains cell and each cell contains a positive terminal, or cathode and negative
terminal, or anode. Electrolyte allows the ion to flow between terminals.
Battery is used in PV system to store the energy produced from PV array because PV
cannot store the charge. The energy produced by PV array stored in battery is used at
night when no sunlight is available or minimal sunlight at day time. In order to use the
energy continuously, the energy storage mechanism should be incorporated with the
solar panel.
The lead-acid battery cell consists of positive and negative lead plates of different
composition suspended in a sulfuric acid solution called electrolyte. When cells
discharge, sulfur molecules from the electrolyte bond with the lead plates and
releases electrons. When the cell recharges, excess electrons go back to the
electrolyte. A battery develops voltage from this chemical reaction. Electricity is
the flow of electrons.
These are liquid-tight batteries that can operate in any position without leaking
acid. Because of the seal construction, you cannot check cell conditions with a
hydrometer. Vents prevent pressure build-up in case of gassing. Recommended
only for situations where hydrogen gassing during charging cannot be tolerated, or
the battery is going to be moved a great deal, or to be fit in tight spaces. Require
lower voltage charge controls. Most AGM batteries (absorbed glass mat) have a
life expectancy of 2-5 years, and 5-10 years for higher quality Gel cell batteries.
Most sealed batteries are AGM.
6.5 Sizing
6.7 Safety
6.8 Exercise
Charge Controller
7.1 Introduction
Generally the solar energy generation takes place during day and consumers consume
at evening hours. So, there is requirement of some device that used to store the solar
energy into batteries called PV charge controller. It is similar t the voltage regulator
and regulates the voltage and current that is coming from the solar panels and stored t
the batteries. Most f the batteries are fully charged at 14 to 15 volts. On nest side,
battery’s life time rapidly decreases due to the discharge over the level of 70 to 80%.
At this discharge level the battery voltage goes down to 11.5 volts. Each storage
battery has a certain limit of storage capacity. In this manner the battery life reduces
drastically due to overcharging and deep discharging. Since, battery is one of the
expensive components, it is necessary to protect the battery from being over charged
or deeply discharged. Hence, a device is required to control such voltage level and
called charge controller.
The main purpose of charge controller in this system is to prevent the battery from
being overcharged and deeply discharged. Feedback about the battery’s state is
designed to spot conditions that would leave the battery undercharged. The easiest
way to instantly know the state of charge of a battery is to measure the battery’s
voltage. Generally, charge controllers stop charging a battery when they exceed a set
high voltage level, and re-enable charging when battery voltage drops back below that
level. The following table shows a clear idea about the battery status that are generally
used including charging and discharging both.
Above 13 100%
12 67%
11 34%
Below 10 1%
Panel tracking; this is where the panel are on a mount that follows the sun. These
optimize output by following the sun across the sky for maximum sunlight. These
increase the total generation of the solar panel by absorbing more energy from sun
and converts it into best voltage such that we can get optimum current into the battery.
The modern MPPT is highly efficient in nature. Normally, the MPPT are most
effective in winter, cold condition when more energy is required t generated.
The MPPT is a high frequency DC to DC converter which takes the DC input from
the resources, change it to high frequency AC and convert it back down to different
DC voltage and current to match the panels to the batteries.
PWM CC MPPT CC
OFF- Grid or Grid-Tie Mostly used in OFF-Grid Enable the use of lower
system at low voltage cost/grid-tie PV Modules
system helping bring down the
overall PV system cost
Finally, when we select one of the charge controllers over next one, we evaluate its
reward in the overall system cost. The main goal is to supply the power with high
efficiency and reliability.
7.5 Sizing a Charge Controller
The charge Controller sizing involves the following formula and in this step, calculate
the short circuit current of PV module and then charge controller minimum power
current:
Charge controller Size = short circuit current of PV module*no. of modules in
parallel*Factor of safety
Where Factor of Safety can be taken to be 1.2 to 1.3.
Then, you can select the appropriate charge controller from the market.
INVERTER
8.1 General
The inverter has been widely used in many fields such as the UPS, electronic circuit
and the solar inverter systems. Inverter is the electronic device that operates from dc
voltage source or a dc current source and converts it into ac voltage or current. It is a
balance of system (BOS) component in PV system, allowing the use of ordinary AC-
powered equipment. Generally the inverters use the principle of Pulse Width
Modulation (PWM) to produce output, which may be a variable voltage or variable
frequency supply. The modern inverters use power semiconductor devices such as
power transistors, power MOSFETs, IGPTs etc.
DC current or
Inverter AC
lt t
The simplest dc voltage source for a voltage source Inverter (VSI) may be a battery
storage, which may consists number of cells in series-parallel combinations. Solar PV
cells can be taken as next example of dc voltage source. Similarly, an ac voltage
supply, after rectification into dc will also take as dc voltage source.
Fig: Output as AC
When the S1 and S4 are turned ON, the current flows in the bulb in the
direction of A.
When the S2 and S3 are turned ON, the current flows in the bulb in the
direction of B.
If these operations are done for number of times, the AC is generated since the
direction of the current flowing in the load alters.
Generally, if S1/S4 and S2/S3 are respectively turned ON for the same period and
the total time for one cycle is t0 sec, the frequency becomes;
f = 1/t0 Hz
Fig: Frequency
Three phase AC
The circuitry diagram of the three phase inverter and the method of creation of three
phase AC are shown in figure below:
Fig: Circuitry diagram of three phase inverter
To get the three phase AC, the switches S1 to S6 are to be connected and
simultaneously turn ON/OFF all the six switches at the timing shown in second figure
above. If the order of turning ON/OFF six switches is changed, the phase order is
changed between U-V, V-W, W-U and the rotation direction can be changed.
In this type of inverter, the main source is current in which input (DC) current is
chopped to obtain AC output current. Normally they are integrating boost converter,
inverter and charging functionality that enables a low voltage battery to regulate the
control circuit. It performs regulation functions and important to improve fault
tolerance. Generally it includes high inductance value and substantially reduces
capacitor requirements.
Positive power flow indicates power transfer from input (Vdc.Idc) to load.
Similarly inverter can produce square wave, sine wave, modified sine wave etc
depending on the design of the circuits. The two dominant commercialized waveform
types of inverters as of 2007 are modified sine wave and sine wave.
Square Wave
This is one of the simplest waveforms an inverter design can produce and is useful for
some applications. The output wave form is of square shape.
Sine Wave
Where power inverter devices substitute for standard line power, a sine wave output is
desirable because many electrical products are engineered to work best with a sine
wave ac power source. The standard electric utility power attempts to provide a power
source that is a good approximation of a sine wave.
A "modified sine wave" inverter has a non-square waveform that is a useful rough
approximation of a sine wave for power translation purposes.
i. Battery back-up
ii. OFF Grid
iii. Battery back-up Grid Tie
iv. Straight Grid Tie
v. AC Coupled
Battery back-up system
This is the system in which there is battery back-up with no solar/ wind source. This
is one of the most basic systems that used in occasional grid failures. The batteries
are kept at full charge at all times from the national grid supply. This system uses a
sub-panel to power critical loads during a black out. A generator can also be
installed with a transfer switch to recharge batteries and run the critical loads. This
system does not require a grid tie inverter. This system does not require an
agreement with the utility because it cannot sell back to the grid.
AC Coupled system
In this method, the grid system is interconnected with battery based inverter to
increase the reliability of the energy system. It is useful in such condition where the
grid is shut down for number of reason, when grid power is inadequate or
problematic, or when utility power is costly making it advantageous to offset the
grid using solar/ wind generated stored energy. The battery based inverter works
backwards as the battery controller and passes the power to the utility from the grid
tie inverter. When the grid power goes shut down, the battery based inverter
disconnects from the grid and starts powering the backed up critical loads panel.
9.1 Introduction
The PV system is installed must insure that they will be safe and functional with
greater reliability. Reliable power can be achieved with less voltage drop in wire and
avoid leakage current from the wire. The different types of wire used in the electrical
installation. For outer region or in open, UV cable is used which is wire with coated
with UV protection materials and for inner region, normal PVC cables are used.
Direct current (DC) system lines are different from the Alternating current (AC)
system because DC system has lower voltage and current flows through one direction
only. The DC system requires larger size of wire than the AC system.
In NEPQA, the allowable voltage drop is 3% for PV array to charge controller and
1% for charge controller to battery and battery to inverter.
Where,
ρ – Resistivity of wire, Ω-mm
After calculation of the area of conductor, the conductor of area equal to or greater
than the calculated value can be selected from the table of conductor table (in
APPENDIX).
For example, let us consider, the length between PV array and charge controller is
10m, system voltage be 48V and maximum current flow through it is 43A. The
resistivity of copper at 480C is 1.86*10-5 Ω-mm then wire size can be calculated as:
A = 1.86*10-5*2*10*103*32/(0.03*48)
= 8.27 mm2
9.5 Disconnects
9.6 Grounding
9.7 Exercise
STANDALONE PV SYSTEM SIZING
10.1 Introduction
The PV system which supplies utility for the off-grid application, the grid is not
connected at that place, is called stand-alone PV system. In this type of system, whole
energy utilized by the consumer is supplied with PV system. This type of system may
be connected in telecommunications applications, pumping system and solar home
system. This type of system is low maintenance system for supplying power to the
consumer of rural areas where enough exposure of sunlight is available.
PV system has high initial cost and hence greater mind exercise must be involved in
PV system sizing which meets the energy demanded under reliable conditions. PV
system sizing for a home is not complex but there can be some difficulty in sizing the
solar PV system which supplies the more consumers from one generating station with
reliable power.
The system can be made reliable with minimized cost with proper sizing which
involves the following steps:
i) Efficiency
The solar PV system is costly so can be lowered considering maximum system
efficiency which can be achieved by using efficient devices in PV system. It can
also be achieved by replacing efficient load such as fluorescent lamps and
incandescent lamps can be replaced by LED lamps.
ii) Shading
Shading has major effect on panel or array efficiency. One hour shade on array
creates one hour less in peak sun time. For example, the solar peak sun time is 4.5
hours and when there is one hour shading effect then the peak sun is 3.5 which
higher the size of PV system for same output.
iv) Modules
In installing the battery bank then careful decision must be taken for ventilation,
place of installation with proper size of battery bank. The improper installation in
battery bank creates unsafe for human health and environment.
vi) Controller
The wire size must be in proper manner so to reduce the voltage drop in the wire.
It also meets all safety conditions.
10.3 Sizing worksheet
The PV system sizing worksheet provides all the information required for complete
sizing of the solar PV system. The sizing involves following steps:
All the loads connected are estimated with their power rating and operation hour. If
the power rating is not provided then the power can be calculated by
For DC load,
The Voltage and current ratings are given in name plate in Volt and Ampere.
For example, a DC LED lamp of 12V takes current of 0.25A from battery supply then
the power is
Power = 12 x 0.25 = 3W
If this device operates for 5 hour a day then the energy consumption can be estimated
as,
For AC load,
For example, an AC load works on 220V, 50Hz ac supply and current flowing
through it is 1.4 A then the power is
If this device operates for 5 hour a day then the energy consumption can be estimated
as,
The energy consumption of the load can be determined by multiplying the power of
device and hours of operation.
The active and passive power is also considered in the load as computer, telephone
etc.
For calculating the battery sizing, the AC energy consumption can be converted in DC
by dividing AC energy consumption by inverter efficiency.
The considerations for battery sizing are autonomy days, depth of discharge (DoD),
efficiency of battery and system voltage at which battery is configured.
To meet the battery bank size, batteries are configured in series and parallel. The total
battery bank size (Ah) is divided by battery Ampere-Hour (Ah) which gives total
number of battery in parallel. Batteries required in series can be calculated by dividing
the system voltage by battery voltage. The total number of battery required is product
of number of batteries in parallel and number of batteries in series.
For example, let the total DC watt- hour is 4500 Wh, autonomy days to be 2 days,
depth of discharge be 80% , system efficiency is 80% and system voltage is 48V, then
= 292.96 Ah
= 1.95 = 2 nos.
Number of battery connected in series = 48/12 = 4 nos
The solar array sizing results total Wp provided to meet the demand. In sizing the PV
array, the losses due to dust, temperature etc must be considered. The safety factor
and efficiency of panel are also considered. The average daily peak sun time play
major role in sizing the PV system. It may vary with geographic conditions and
location. The average daily peak sun in Nepal is considered to be 4.5 hours by AEPC.
All the losses are included in loss factor which is considered to be 0.6 to 0.7. The
array is required to charge the battery so it must be in such that it provides total
current required to charge the battery.
For Example, we have to charge the battery bank system of 300Ah. So,
= 95.23 A
Let we use the panel of KDP205WP (specification given in APPENDIX) whose rated
current at STC 7.90A and nominal voltage is 24V.
No. of panel in parallel = 95.23/7.90 = 12 nos.
The controller required must met the system voltage and also controls the charge of
the battery. The controller is sized as:
The controller sized must meet the rated current also. i.e. I rated of Controller must be
equal or greater than I rated coming from panel.
The size of inverter does not depend upon the energy consumption rather it depends
on the load. Hence in determining the size of inverter, we use total watt of load
connected. The size of inverter calculated must met the voltage level and acceptable
efficiency. The inverter size can be calculated as:
Let us consider, the connected load is 1400 W and the efficiency of inverter is 0.9
then,
= 1.94 KVA
In wire sizing, length of wire, voltage drop in the wire and current rating of the wire
are the major factors which determines the wire size. The voltage drop in the wire is
in permissible limit which is taken from 1% to 3%.
The increasing in current flow increases the cross-section of the wire. The rating of
current used in calculation for wire sizing is the short circuit current which can flow
in the wire under short circuit condition.
From the calculated X-section of wire, the table is used (given in APPENDIX) to find
the wire size. The wire X-section chosen is equal to or higher than the calculated
value. The resistivity of copper is 1.68 x 10-8 Ω-m at 200C.
For example, the allowable voltage drop is 3% in 48V system where the maximum
current flow in the wire must is 43A in 10m length. So, X-section of wire is,
= 10 mm2
Therefore, the wire of X-section 10 mm2 or greater is used which can be evaluated
from the wire data sheet.
GRID-TIED PV SYSTEM
11.1 Introduction
Most residential photovoltaic (PV) systems consist of PV modules, a battery bank to
store the electricity, a charge controller to regulate the charging of the batteries, and
an inverter to change the solar-generated direct current electricity into the more
commonly used alternating current. People living in remote areas, off the grid, have
been relying on these types of PV systems for years. However, more and more people
who are already connected to the grid are turning to renewable energy for part or all
of their electricity needs. These grid-tied PV systems send solar-generated electricity
back into the already existing utility grid. Grid-tied PV systems typically consist of
PV modules connected in series to string inverters that convert DC power to AC
power, which is then fed directly to the grid. As a building receives this AC energy, it
is distributed to appliances and lighting, or other devices where needed.
The photovoltaic system can be used in many types and when it is used to fed the
energy in the grid utility then called grid-tied PV system. A grid-tied PV system or
grid connected PV system is the PV system which is connected to the utility grid. The
grid-tied PV system ranges from small residential system and commercial rooftop
system to the solar power stations. The grid-connected system rarely uses the
integrated battery system.
• The constant reliable power can be promised to the consumer when exposure
of sunlight is not available.
Step I: Determine objective that how much energy, E ac (AC electrical energy in kWh)
is required over one year.
Step II: Calculate or find the average sunshine hours (S) based on location,
geographic conditions etc. It is the peak sun time.
Step III: Calculate overall efficiency (η), from PV to AC grid, also called DC to AC
derate factor.
Step IV:
For example, a grid tied system wants to generate 7200 kWh per year energy with
peak sun time 5.44 hours and efficiency 75%.
= 4.83 kWp
12.1 Introduction
There are several ways to install a PV array at a residence. Most PV systems produce
5-to-10 Watts per square foot of array area. This is based on a variety of different
technologies and the varying efficiency of different PV products. A typical 2kW PV
system will need 200-400 square feet of unobstructed area to site the system.
Consideration should also be given for access to the system.
i) Roof Mounting
Proper roof mounting can be labor intensive. Particular attention must be paid to
the roof structure and the weather sealing of roof penetrations. If the panels are
planned to be mounted before the construction of the roof, the roof can be
designed accordingly by installing support brackets for the panels before the
materials for the roof are installed. Masonry roofs are often structurally designed
near the limit of their weight-bearing capacity. In this case, the roof structure must
be enhanced to handle the additional weight of the PV system.
ii) Ground Mounted
The PV modules are mounted on ground usually in large scale photovoltaic power
stations. The modules are held with racks or frames that are attached to the ground
based supporting structures. In this type of mounting of PV system, the base is
made with concrete or steel structures to fix the structure of PV mounting system.
This mounting system is best suitable but uses land which can be used in other
works (farming, forest etc).
13.1 Introduction
As we know, solar energy is converted into electrical energy using PV cells. The cells
are connected and assembled in different combination to absorb the solar radiation
and generates electricity that system designed. Generally, the electricity is required in
different areas and used in regular activities, the PV system can be used in various
applications:
Agriculture
Industry
Telecommunications system
Public services
Health
Residential
Others
Residential PV system can meet the load of most consumers. They can feed excess
power from the grid when they consumed more energy by other appliances. The PV
wattage may be less than average consumption, in which condition consumer tends to
purchase grid energy, but a lesser amount than previously. If PV wattage significantly
exceeds average consumption, the energy produced by panels will be much in surplus
of the demand. In this manner, the total system energy consumption is reduced and
increases the reliability of the whole supply system.
Similarly, the PV system supply the energy during shut down of the grid system.
13.3 Lighting
PV lighting is the lighting that is at least partially powered by electricity generated
from solar panels. For example, house hold PV lighting system, solar garden, pathway
light etc. These PV lighting systems are generally off-grid or stand-alone system
where there only power source is solar energy.
A PV lighting system collects the energy using numbers of cells, stores that energy in
a battery and releases the energy to light load. Typically, PV lighting system
components include PV panels, batteries, converters/ inverters and light loads. The
initial/ maintenance cost for this system are higher as compared to traditional lighting
systems powered by a grid. Designing and installing a PV system are also more
complicated than traditional grid system. As a result, lighting applications suitable for
PV lighting system are currently somewhat limited. However, successful PV lighting
applications can be developed through a carefully planned design procedure and
educated choices between PV power and grid power. PV lighting applications are
normally most used where low light levels and limited electricity are acceptable and
where access to a grid is expensive or difficult. Some experiments are done in
Kathmandu valley at the road side as pilot project.
TV 1 3.3 4 6 79.2
Weekly DC 495.2
Load(Ah)
In given condition, the rating of TV is considered as 40W. Then, we found that, the
weekly demand of the whole system is equal to 495.2 Ah. Hence, to supply the
demand, the system should be designed so that it produce and store at least 600 Ah
amount of energy.
As shown in block diagram, a solar panel is used t generate electricity from solar
energy. The size of PV panel is directly dependent on the size of the pump or the
amount of the required water. The charge controller is used to regulate the system and
increases the efficiency and life time of the system.
The nature of the solar motors may be AC or DC. Generally, DC motors are used for
small applications and AC in large applications.
Some of the basic specifications of solar water pumping system are given below:
A solar PV water pumping system is available with a PV panel f capacity in
the range of 200 W to 3000 W.
A solar PV water pumping system is expected to deliver a minimum of 65,000
liters per day with a 900 W panel and 135,000 liters per day with a 1800 W
panel from a depth of 7 m on a clear day.
In case of deep well submersible pumps, the water output will be about 45,000
liters from a 1200 W system.
The discharge from the pump station would vary with the intensity of the sun
rays from morning till evening. It would be max around mid day. The water
output from the pumping would significantly drop with the increase in the
depth from which water needs to be pumped.
13.7 Determining solar access with a sun chart
The sun crosses the horizon with regular motions. Its movement is caused by the
regular rotation of the earth. Solar access is the ability of one property to continue to
receive solar radiation across property lines without any disturbance from other
objects. Solar access can be calculated by using a sun chart. The sun chart can be used
to provide the information about the solar patterns at the site:
Data on the sun’s position at any time
The quantity of radiation
Performance data on specific shading device applications
The extent of shading at a specific location from surrounding site obstacles.
To know how the sun rays will strike a building and how far the rays will penetrate
through the opening, to shade certain areas and irradiate others, to know the effect of
sun on air conditioning capacity and operation, we must have the following data:
The Angle of the Sun above the horizon
The direction of the Sun
The angle of incidence
These data must be known for a particular area, no matter what its orientation, for at
least several hours of each day reported.
14.1 Introduction
In a theoretically well designed system, if the equipment is not installed properly, the
system could fail. Weak communications between installers and system designer can
lead to damage time span and money resulting failure project.
Some of the basic points that should be considered in system design are given below:
As a PV panel’s orientation or tilt varies from optimal, potential energy yield reduces.
The optimal combination of panel tilt and direction will depend on a few factors such
as geographical location, seasonal weather and system application. During the
designation of the system, you must have the data of tilt and direction. With the
designed components, such as annual insolation tool, you can create a chart for
quickly evaluating potential energy production as it changes with the panel positions.
The results will reveal the ideal panel orientation and till for an unshaded panel in that
particular location.
14.4
14.5 Installation Final Checklist
Project Information
Property Address
Brief System
Description
System Capacity
Number of
Modules
Number of Panels
Panel Tilt
Inverter Capacity
Estimated
Capacity Annual
KWh
Designation
Installer
Date
Inspection Checklist
Yes No N/A Prior to the Field Inspection Note
Utility has given permission to interconnect the PV system
System installed by a qualified installer
Inspection have been passed: Permit ……………………. Date
…………………………
As built electrical drawing
Final electrical design has professional engineer's stamp
PV system plans and drawings received (showing panel layout,
BOS locations, components, disconnects, wiring and conduit
specifications)
PV module specifications
Inverter specifications
resource is documented from location where array shading will
be most significant
Total Solar Resource Fraction (TSRF) is 75% or greater at points on
the collector
PV modules are physically installed per plans (number and layout)
Array is optimized for performance without sacrificing aesthetics
Trees and plants will not grow tall enough to shade array
Panel installation is neat and permanent
Roof penetrations are secure and weather tight
PV module model number matches design
PV module warranted
PV panel are new, qualified
Panel is spaced a minimum of 1.5 inches off the roof, or is
properly flashed into roof
String fuses of circuit breakers are DC- rated and no larger than
module fuse rating
PV modules are in good conditions
Module connectors tight and secure
Module interconnection conductors sunlight resist, wet rated
Wire and conduit sizes installed per design
Wiring is installed with shortest distance from PV panels to
inverter or where aesthetically suitable
Wiring is neat and secure
Wiring is not readily accessible
Conductors are not in contact with roof surface
Conduit supported properly
Electrical boxes are accessible and suitable for environment
No potential for wire damage
Confirm metallic PV module frame grounding uses a dedicated
grounding conductor
Proper grounding of all other metallic surface that might possibly
become energize
Dissimilar metals are electrically isolated to avoid galvanic
corrosion
Aluminum is not placed in direct contact with concrete
Protective fencing installed and will not shade array (if required)
Yes No N/A Field Inspection- Inverter and Electrical Note
Inverter is installed per work order
Confirm inverter module number matches plans
Inverter is warranted (recommended 10 years minimum)
Inverter is new and CEC approved
Wire and conduit sizes installed per design
AC disconnect is permanent installed and accessible
Inverter is easily accessible
DC disconnect is DC- rated and permanently installed and readily
accessible
Penetrations to building shell are sealed and fire resistance
maintained
Sum of PV breaker and panel main breaker less than 120% of
panel rating
Utility power connected
Internet connection operational (if applicable)
Yes No N/A Field Inspection- System Labeling Note
All equipment and parts are labeled as required
Label identifies PV power source attributes at DC disconnect
Label identifies AC point of connection
Outdoor labels designed to withstand the elements
Emergency and maintenance contact information
Yes No N/A System Documentation Note
Customer Manual is provided and mounted in a preserved
location near the unit controls
Operation and maintenance instructions including home owner's
responsibilities
Electrical design showing modules and meters
System & contractor warranty
Manufacturer's warranties
Permit
Parts and source list
Emergency and maintenance contact information
Yes No N/A Owner Education Note
Basic system operation
Proper system disconnect sequence and safety procedures
Reading meters and inverter display
Required maintenance
Emergency contact
Yes No N/A Post Inspection- Performance Testing Note
Performance tests performed by:
Date:
Solar irradiance level:
Ambient temperature:
Panel temperature:
Measure and record open-circuit voltage and polarity of each
string
Measure and record short-circuit current of each string
Inverter startup sequence-follow manufacturer's instructions for
initial startup
Owner should check system AC power output monthly near solar
non on a clear day
Maintenance
16.1 Introduction
A PV typical system can produce about 3 amperes of current when exposed to full
sunlight. It takes only a fraction of amount to kill a person. If the modules are used to
make array, then produces higher voltage and possesses more of a safety hazard.
Various safety hazards result from PV systems being installed on roofs, or other
higher places.
Basically, the safety hazards come from due to workmanship failure and equipment
failure. Even the best intentioned employers and employees get it wrong. This is due
to either lack of knowledge or they may allow other goals or provide with some
limitations. If one can never have knowledge in PV system then this affects not only
safety but every aspect of the system. The PV system installer must have knowledge
about the installation knowledge with safety needs. Thus with better knowledge, safe
work environment can be acquired. It is also not to underestimate the importance of
planning and communication to establishing safe working conditions. Installer should
plan for safety to avoid or reduce the probability of the accidents likely to be
happened. Communication of those plans with others is also important. For any
change in plan of work then communicate these changes to the team.
Before learning about the specific hazards working with PV system, personal safety is
most important. The equipments for personal protection should use against
unexpected accidents. A proper planning and preparations ensures for protection
against any specific hazards. The equipments include any equipment designed to
minimize injury resulting from hazards such as protection equipment against chemical
exposure and electrical shock.
The hazard related to PV system is electricity and it’s related. Various hazards are
existing related with electricity and its related work. The electrical hazards related
with installation of PV systems are:
i) Electrical Shock
When a person gets contact with live wire then they get electric shock. Shock and
its effect vary with the amount of current passes through the body. Current can
cause from tingling sensation to the cease of heart and burning of skin by varying
or increasing the amount of current. The cease of heart can lead to instant death.
Generally, when a person get electric shock then separate the person from live
conductor and perform CPR on him/her.
Arc flash occurs between connections when closed circuit has been opened or
circuit breaker is trip out. Spark, arc flash, results in fire which can damage many
more. Arc flash is more likely to occur in high voltage systems. Arc flash can
damage even eye of a person by emitting UV rays.
The safety goggles, proper clothes are used for the safety from arc flashes.
iii) Batteries
The safety equipments used regarding to chemical hazards are the personal
protective equipments such as gloves, apron boots made with rubbers that
physically protects the body from leaks of acid. Carrying straps are to be used
properly to lift the battery.
It must be care about the place where the system equipments are installed. It must be
checked that the installing of battery bank in room creates threat of fire. For example,
battery bank must not installed near kitchen because hydrogen gas is emitted at
charging condition of battery which cause fire.
When installing the PV system on roof of steel then before installation, check about
the weight bearing of steel that it can bear weight of panels or not and also check
about the steel roof that no other equipments hazards a person. The installation place
of junction box is checked because if it is opened then can be serious place of hazards.
So junction boxes are installed where people cannot touch it easily.