Power Flow Analysis of Nigerian Power Sy
Power Flow Analysis of Nigerian Power Sy
BY
OGBUEFI UCHE C.
(PG/PH.D/07/43333)
AUGUST, 2013.
2
APPROVAL PAGE
POWER FLOW ANALYSIS OF NIGERIAN POWER
SYSTEM WITH COMPENSATION ON SOME BUSES
BY
OGBUEFI U. C.
REG. NO. (PG/Ph.D/07/43333)
AUGUST, 2013.
CERTIFICATION
OGBUEFI UCHE C., a doctorate degree postgraduate student in the department of
Electrical Engineering and with the registration number PG/Ph.D/07/43333 has
satisfactorily completed the requirements for the award of the degree of Doctor of
Philosophy in Electrical Engineering.
The work embodied in this thesis is original and has not been submitted in part or in
full for any other diploma or degree of this or any other university.
………………………. …………………….
Ven. Engr. Prof. T.C. Madueme Engr. Prof A. O. Ibe
(Supervisor) (External Examiner)
………………………
Engr. Dr. B.O. Anyaka
(Head of Department)
4
DEDICATION
To JEHOVAH the ALMIGHTY GOD through His Beloved Son JESUS CHRIST
To my late father Bro/Pa Samuel O. Ogbuefi, and
My beloved mother sister (Mrs.) Gladys A. Ogbuefi.
And to All OGBUEFI’s family
5
ACKNOWLEDGEMENTS
ABSTRACT
Management of reactive power and voltage control constitute part of the major challenge in power
system industry. Adequate reactive power control solves power quality problems like voltage
profile maintenance at all power transmission levels, transmission efficiency and system stability.
Power demand increases steadily while the expansion of power generation and transmission has
been severely limited due to the inadequate resources and environmental forces. These give cause
for concern as they contribute to the constant power failure in the Nigeria power system. In this
work the Nigeria 330KV network, 30 bus system is considered. To alleviate/eradicate some of
these problems mentioned, compensation in power system becomes very essential. Compensation
reduces generating MVA and MVAR. The reduction in MVAR helps electrical companies to
transmit more power and absorbing more customers without expanding their power networks.
Newton-Raphson’s solution method was used to carry out the analysis because of its sparsity, fast
convergence and simplicity attribute as compared to other solution methods using the relevant data
as obtained from power holding company of Nigeria (PHCN). MAT LAB/SIMULINK method
was used to carry out the simulation analysis. The results obtained showed that the bus voltages
outside the statutory limit of 0.95 – 1.05p.u that is 313.5 – 346.5KV were buses 14(Jos) with value
0.8171pu, bus 17(Gombe) 0.8144p.u bus 18(Abuja) 0.9402pu, bus 19(Maiduguri) 0.8268pu, bus
22(Kano) 0.7609pu, bus 29(Kaduna) 0.8738pu, and bus 30(Makurdi) 0.8247pu under normal
uncompensated condition. Capacitive shunt compensation because of its advantages was
implemented on these buses, and the results then came up to tolerable values. Results obtained
after compensation reveal acceptable voltage levels at the problem buses. For instance bus 14(Jos)
is now 0.9823p.u, bus 17(Gombe) 1.0242p.u, bus 18(Abuja) 0.9667p.u, bus 19(Maiduguri)
1.0455p.u, bus 22(Kano) which is heavily loaded was linked to Jos and a 60 percent compensation
on Kano bus yielded an increase of 0.7609pu to 0.947p.u. System efficiency improved from 65%
(uncompensated) to 85% after compensation. On the application of 20% over compensation,
overvoltages (>1.05pu) resulted which may cause system collapse if not controlled. From the
results obtained, installing compensation devices, make it possible to control the amount of active
and reactive power flowing through the lines thereby controlling the voltage. It is clear from the
results that the use or incorporation of system compensation will lead to many benefits like
increasing transmission lines loadability which enables electrical company to transmit more power
with the existing transmission lines as well absorb more customers without increasing the network.
7
TABLE OF CONTENT
Page
Cover Page
Approval Page i
Certification ii
Dedication iii
Acknowledgements iv
Abstract v
Table of Contents vi
List of Symbols and Abbreviations xii
List of Tables xiv
List of Figures xvi
CHAPTER 1. INTRODUCTION 1
1.1 Background of the Study 1
1.2 Statement of the Problem 3
1.3 Objective of the Research Work. 5
1.4 Significance of the Study 6
1.5 Scope of the Study 6
1.6 Definition of Terms 6
CHAPTER 2. LITERATURE 8
Gik , Bik Real and Imaginary Parts of the Admittance Connecting Buses (i) & (k)
P.F Power Factor
FDPF Fast-Decoupled Power Flow
Precision Index
V Voltage Magnitude Correction Factor
N Maximum Number of Buses
Ng Number of Generator Buses
Z C'1 Characteristic Impedance
GRNN Generalized Regression Neural Network Architecture
Electrical Angle
13
CHAPTER 1
INTRODUCTION
1.1 Background of the Study
The current incessant power failure in Nigeria has reached an
unprecedented level that the public is almost demanding for a state of
emergency in respect of electricity supply. The projected power demand for
the year 2009/2010 was 10,000 MW but the actual available supply was
3,500 MW. The various efforts made to rescue the power short fall did not
yield any meaningful outcome [1].
The research work is to provide a reversal of the above previous situation
by looking into the problems and proffer a solution that will minimize if
not completely eradicate the problems. In power flow study the frequency
should remain nearly constant, because considerable drop in frequency
could result in high magnetizing currents in induction motors and
transformers [2]. The flows of active and reactive powers in a transmission
network are fairly independent of each other and are influenced by
different control actions. Active power control is closely related to
frequency control, and reactive power control is closely related to voltage
control [3]. Since constancy of frequency and voltage are important factors
in determining the quality of power supply, then the control of active and
reactive power is vital to the satisfactory performance of power system [2].
In this work, the Nigeria integrated power network system is presented in
its current state and its parameters are tabulated and examined. After
compiling the generators, lines, load data, and other parameters,
equations for the power flow analysis are then formulated incorporating
these parameters. These equations are solved using MATLAB/SIMULINK
[3, 4].
Because electrical energy is normally generated at the power stations far
away from the urban areas where consumers are located and are delivered
19
magnitude and phase angle at each bus in a power system. They are
essential in planning the future expansion of the system because
satisfactory operation of the system depends on knowing the effects of
interconnections with other power stations and to have an idea of the
effect of new transmission lines before they are installed. It also involves
the determination of the voltage magnitude and angle at each bus of the
power system network under specified operating conditions. Main
consideration in this project will be focused on delivering the reactive
power directly to buses in a transmission system, by installing sources of
reactive power. The reason is that transmission lines can be operated with
varying load and nearly constant voltage at both ends if adequate sources
of reactive power are available at both ends.
We are required to find the voltage at all the buses and the real and
reactive power that flow in all the branches, the losses etc. The voltage
magnitude must lie between 0.95 Vi 1.05 pu and the angle should be very
small for a balanced steady state 50Hz power station to achieve the
desired result from the system. So in an interconnected power system of
n-buses the power injected into the nodes is given by a set of 2n nonlinear
simultaneous equations represented in Eqs.1.1 &1.2 below.
N
Pi ViVk Yik cos( ik k i ) 1.1
n 1
N
Qi ViVk Yik sin( ik k i ) 1.2
n 1
which are coupled via a dc link to allow a bidirectional flow of real power
between the series output terminals of the SSSC and the shunt output
terminals of the STATCOM. It has the unique ability to control real and
reactive power flow independently [7, 8].
Stability: It is the ability of the power system to remain at stable
operation after being subjected to a sudden power change [9].
FACTS controller: This is a power electronics-based system or other
static equipment that provides control of one or more AC transmission
system parameters [7].
Static synchronous compensator (STATCOM): Is a static synchronous
generator operated as a shunt connected static Var compensator whose
capacitive or inductive output current can be controlled independent of ac
system voltage. It is based on a voltage source or current-sourced
converter [7].
Transient stability limit refers to the maximum flow of power through a
point without loss of stability when sudden disturbance occurs [9].
25
CHAPTER 2
LITERATURE REVIEW
The origin of the formulation of the power-flow problem and the solution
based on Newton–Raphson and Gauss Seidel techniques are dated back to
the late 1960’s [10, 11] Since then a huge variety of studies have been
presented about the solution of the power flow problems addressing the
starting initial guess [12], computation efficiency [13, 14] robustness and
ill-conditional cases [15]. Power flow problems are classified into the
following categories;
I. Well-conditioned case. Here the power flow solution exists and is
reachable using a flat initial guess (like all load voltage magnitudes equal
to 1 and all bus voltage angles equal to 0o ) and a standard Newton-
Raphson’s method. This is the most common case.
II. Ill-conditioned case. Here the solution to the power flow problem
exists but standard solution method fails to get this solution starting from
a flat initial guess. This situation is due to the fact that the region of the
power flow solution is narrow or far away from the initial guess. In this
case, the failure of standard power flow solution method is due to
instability of the numerical method, not of the power flow equations.
Robust power flow methods have proved to be effective for solving this
case.
III. Bifurcation point: The solution of the power flow exists but it is
either a saddle-node bifurcation or a limited induced bifurcation [16].
(a) Saddle –node bifurcations are associated with the maximum loading
condition of a standard or robust power flow method since the power flow
Jacobin matrix is singular at the solution point
(b) Limited induced bifurcations are associated with a physical limit of
the system and as a shortage of generator reactive power although limit-
induced bifurcation can in some cases lead to the voltage collapse of the
26
system, the solution point is typically a well conditioned case and does not
show convergence issues [16]. However encountering a case whose
solution is exactly a bifurcation point is quite uncommon in practice.
IV. Unsolvable case: the power flow solution does not exist naturally;
the issue is that the loading level of the network is too high. A
continuation method or optimal power flow problems allow defining the
maximum loading level that the system can supply. Robust power flow
methods provide a solution close to the feasibility boundary rather than
diverging.
In power flow analysis the transmission system is modeled by a set of
buses or nodes interconnected by transmission links (lines). Generators
and loads connected to various nodes of the system inject or absorb power
from the transmission system. A given power system subjected to a given
set of power demand can be operated in an infinite number of states and
still satisfy the given demand. The system engineer is to select the best
possible state out of the various options available to ensure the smooth
operation of the system [9]. There may be problems that have no solution
or multiple solutions. Figure 2.1 represents a network with V1 and S2
known. If we have V1 & S 2 and are to find S1 and V2 we consider the
solution as a function of D 2 , for D 2 0 [17] where S1 S G1 S D1 and
S 2 S G2 S D2 .
27
QG2 = j1.0
SG1
V1 1.00 0
V2
ZL=j0.5
SD2 = PD2+j1.0
SD1 12
11 jQ2=j1.0
V1 1.00 0
V2
PD2=j1.0
The capacitor in this case injects a specified power in the system, while
the voltage is now controlled. Bus (2) is a PQ (load) bus [18].
S 2 SG 2 S D 2 D 2
So S 2 jQ2 D 2 j1.0
2 jQ2 V2 *2 j1.0 D 2 j1.0 D 2 2.0(a)
1
2 V (V2 V1 ) I1
j 0.5
j 2.0[ V2 2 1]
j 2.0[ V2 (cos 2 j sin 2 ) 1]
j 2.0[ V2 (cos 2 j V2 sin 2 1]
2[ V2 sin 2 j (2 2) * V2 cos 2 ]
*2 2[ V2 sin 2 j (1 V2 cos 2 )]
2.0(b)
but
S 2 2 jQ2 V2 (cos 2 j sin 2 )(2V V2 sin 2 j 2[1 V2 cos 2 )]
2 V2 cos 2 2 V2
2
(divide by 2V2 )
cos 2 V2 2.2
Squaring both side of Eqs. 2.1 & 2.2 we get
PD22
4 V2 sin 2 2 PD22 sin 2 2 2.3
2
2
4 V2
cos2 2 V2 2.4
2
4 V2 4 V2 PD22 0
4 2
1
This implies that (1 1 PD22 )
2
V2
2
Thus, if D 2 1 imaginary solution (i.e. no solution)
if D 2 1, V2 1
2
1
0.707
2
V2 pu Bifurcation
Point
0.5 V2 pu
0
D 2 P
This shows that the power system voltage problems may be classified as
follows
1) Excess voltage
2) Low voltage
3) No voltage ( or voltage collapse, bifurcation)
In conclusion, there is the possibility of no solution or at least no unique
solution to the mathematical problem. But, nevertheless, we expect that
most problems that arise in engineering practice have solutions and even
if non unique, we can identify the practical solution. Usually, the practical
solution is the one with voltage closest to 1.0p.u. Just as seen in Fig 2.1b,
suppose D 2 0.5 , we find two solutions for V2 0.97 15 0 and
V2 0.26 75 0 .
VR
Generator V R 0 0
ABC
D
S S PS jQS Load
SR PR jQR
Fig 2.2: A Two-Bus System of Transmission Line
and the sending end voltage (VS VS ) which leads by an angle . The
S S PS jQS VS I * S 2.5
33
V S V R
1 A
IR 2.6(b)
B B
D 1
IS VS VR 2.7(b)
B B
Substituting for I R in Eq.2.5 we get
1 A
S R V R 0 VS V R
B B
V V A
S R V R
2
B B 2.8
S R and S S are per phase complex volt-amperes (in per phase volts). If VR
B B 2.10
Eq.2.9 is same as Eq.2.8 and the same result holds for S i . If we express
Eq.2.8 in real and imaginary part we have for real and reactive powers at
the receiving –end as:
34
VS V R A
PR cos cos( )
2
VR 2.11
B B
VS VR
sin
A
QR VR sin( )
2
B B 2.12
D VS V R
QS sin( ) sin
2
VS 2.14
B B
From Eq. 2.11 we can see that the receiving power PR will be maximum at
that is,
2
V V A VR
PR max S R cos
B B 2.15
2
A VR
And corresponding QR is, QR max sin 2.16
B
This means that the load must draw much leading MVAR in order to
receive the maximum real power. If we consider a case where we have a
short line with a series impedance Z, that is, D 10; B Z Z 0
Substituting these in Eqs. 1.11 and 2.14 we get the simplified results for
2
VS VR VR
the short line as; PR cos cos
Z Z 2.17
And
2
VS V R VR
QR sin sin 2.18
Z Z
2
VS VS V R 2.20
QS sin sin [6]
Z Z
35
The above short line equation will also apply for a long line when the line
is replaced by its equivalent -∏ or nominal- ∏ and the shunt admittances
are lumped with the receiving-end load and sending-end generation.
2
VS VR VR 2.21
PR max 2
R
Z Z
• Loads normally absorb reactive power. Both active power and reactive
power of the composite loads vary as a function of voltage magnitudes.
Loads at low-lagging power factors cause excessive voltage drops in the
transmission network and are uneconomical to supply.
must limit the voltage to acceptable levels, or the equipment must be rated
to withstand the highest voltage that might occur.
C C
D D C=capacitor
G G1
D= Damping Circuit
S S2 G2 G= Spark gap
S= Bypass breaker
S1
(a) G1= Spark gap, high-set
(b) G2= Spark gap, low-set
S1=Bypass breaker
Fig. 2.3 Protection Scheme (a) Single-gap, (b) Double-gap S2= Reinsertion breaker
39
R R
+ +
Ei E Ei E
- -
Fig 2.4 Equivalent Circuits for (a) the Synchronous generator and
(b) Synchronous motor
Va Ei I a Ra jI a X d
(a) (b)
Fig. 2.5 Phasor diagram of (a) overexcited generator delivering lagging current
, (b) under excited motor drawing lagging .
for duration of less than 1 second. It also helps to limit energization over
voltages (i.e. switching transients). Additional shunt reactors required to
maintain normal voltage under light-load condition may be connected to
the EHV bus to improve the voltage. During heavy loading conditions some
of the reactors may have to be disconnected and it is achieved by using
circuit-breakers [2, 6].
system stability problems. Studies show that by varying the Vars supply at
a stable point in the network, system stability is improved. The thyristor
switched shunt capacitors are useful for this purpose.
- Control of over voltage – shunt compensation can control over
voltages under transient and dynamic conditions thereby allowing a
reduction in designed insulation levels (thyristor controlled reactor is used
for this purpose).
- Reduction of Vars. flows - The provision of shunt compensation leads
to a reduction in the unnecessary circulation of Vars in the network
leading to reduction of system losses and increased availability of
equipment rating.
It controls temporary over voltage rapidly.
Disadvantages of shunt compensation are as follows:
- They are expensive
- It has limited over voltage capability
- at light load or no load, the receiving-end voltage may considerably
exceed the sending-end voltage
Shunt compensation has limit to which transmitted power can be
increased. For increasing power transmitted over the line, other better
means like series compensation can be adopted.
FACTS controllers can enable a line to carry power close to its thermal
rating. The existing networks are mostly mechanically controlled. Micro
electronics, computers and high-speed communications are widely used
for protection and control of transmission systems. Mechanical switching
has to be supplemented by rapid response power electronics. It may be
noted that FACTS is an enabling technology, and not a one-on-one
substitute for mechanical switch [6] that wears out quickly as to be
compared to static devices. FACTS employs high speed thyristors for
switching in or out transmission line components such as capacitors,
reactors or phase shifting transformer for some desirable performance of
the systems
Since 1990, a number of control devices were developed under the term
FACTS technology. FACTS technology opens up new opportunities for
controlling power and enhancing the usable capacity of existing and new
lines [32, 33]. FACTS technology is not a single high-power controller, but
rather a collection of controllers which can be applied individually or in
coordination with others to control one or more of the system parameters.
48
FACTS controllers can be divided into four categories, (i) Series (ii) Shunt
(iii) Combined series-series (iv) Combined series-shunt controller [6, 32].
The general symbol for a FACTS controller is given in fig.2.7a which shows
a thyristor arrow inside a box. The series controller of Fig. 2.7b could be
variable impedance such as capacitor, reactor etc, or a power electronics
based variable source. All series controllers inject voltage in series with the
line. If the voltage is in phase quadranture with the line, the series
controller supplies or consumes variable reactive power. Any other phase
relationship will involve real power also. The shunt controller of Fig.2.7c
may be variable impedance, variable source or combination of these. All
shunt controllers inject current into the system at the point of connection
[6, 33].
FC
Line Line
i
(a) General Symbol for
FACTS Controller (FC) (b) Series Controller
FC
FC
Coordinated
Controller
Fig 2.7. Different FACTS Controller (e) Coordinated Series and Shunt Controller
49
The real and reactive power delivered are given as; [2, 35]
Vt E g
P RS S sin 2.28
Xg
Vt
Q Im S ( E g cos Vt ) 2.29
Xg
Equation 2.28 reveals that the real power P increases when the power
angle increases. From the operational point, when the prime mover
increases the power input to the generator while the excitation voltage is
52
held constant, the rotor speed increases also. And as the rotor speed
increases, the power angle also increases, causing an increase in
generator real power output P. This causes a decrease in reactive power
output Q given by Eq.2.29 [35]. An increase in prime-mover corresponds
to an increase in P at the constant bus voltage to which the generator is
connected.
Equation 2.29 shows that reactive power output Q increases when the
and bus voltage equals ETH . After the bank is connected, the switch (sw.)
is closed, and the capacitor current leads the bus voltage Vt by 900. The
phasor diagram shows that Vt is larger than ETH when ‘sw’ is closed.
From the power flow stand point the addition of a shunt capacitor bank to
a load bus leads to or corresponds to the addition of negative reactive load,
since capacitor absorbs negative power. Also the addition of shunt reactor
corresponds to the addition of positive reactive load.
53
b1 SW
+ jX TH j
+
ETH
They are used for lagging power factor circuits created by heavy loads. The
effect is to supply the requisite reactive power to maintain the receiving
end voltage at a satisfactory level. The capacitors are connected either
directly to the bus bar or to the tertiary winding of the main transformer
and are disposed along the route to minimize the losses and voltage drops
along the line.
The values can be calculated as
I R VC 2.30
X' NC X ' NC
Series compensation j j
2 100
2 100
+ IS + R'
+ + + +
j IR
Y ' NL Y ' NL
+
Y'
+
Y'
2 100 2 100
Shunt compensation 2 2
VS VR
(a) Schematic (b) Equivalent circuit
Fig.2.10. Compensated Transmission Line Section
The stability and stability limit are applied to steady-state and transient
conditions of power system. Steady-state stability limit refers to the
58
Low computer storage like where minicomputer are used for on-line
application
Simplicity- that is, the algorithm can easily be coded in the computer
Reliability of solution – that is for ill conditioned and for real time
application solution will be possible.
The problem or difficulty is that no one method possesses all the desired
features or characteristics. Newton-Raphson’s method has gained more
popularity since the introduction of compact storage scheme. It assumes
an initial starting voltage that is used in computing the mismatch power.
This method is excellent for large systems but does not take advantage of
the radial structure of distribution. However the method fails when the
Jacobian matrix is singular or when the system becomes ill-conditioned as
in the case where the distribution of X R ratio is low [13].
It is a simple iterative method that was very popular in the early days of
digital computer-based power-flow analysis. It is used because of its
simplicity, and it is for small power system. It is also used in many cases
of large-scale system to obtain the first approximation solution for the
Newton-Raphson (NR) methods.
60
If P2 and Q2 are the scheduled real and reactive powers entering the
system at bus (2)
Pi jQi
Si Pi jQi Vi I i* ; I i 2.32
Vi*
Pk jQk N
Ik | Yik Vk | Yik Vk
Vk* k 1
P2 jQ2
I2 2.33
V2*
61
1 Pk jQk N
Vk *
Yik k
V
y kk Vk k 1
And from Eq.2.32, we know that current can be expressed in terms of self-
and mutual admittances, we then express
1 P2 jQ 2
V2 (Y V
21 1 Y V
23 3 Y 24 4
V ) 2.34
Y22 V2*
Where are scheduled real and reactive powers and can be
written as
1 P3 jQ3
V3 (Y V
31 1 Y V
32 2 Y34 4
V ) 2.36
Y33 V3*
1 P4 jQ 4
V4 (Y V
41 1 Y V
42 2 Y 43 3
V ) 2.37
Y44 V4*
If we equate real and imaginary parts, we have six equations in six state
1 Pk jQk N
Vk Yik Vk
y kk Vk *
k 1
2.38
k i
The values for the voltages on the RHS of the equation are the most
recently calculated values for the corresponding buses (or the
scheduled/estimated voltage if no iteration has been done at that
particular bus)
the admittances incident to node I, the off-diagonal element Yik Yki are
obtained as the negative of the admittance connecting node I and k.
For bus (2) in the first iteration, we have the acceleration value V2,acc
defined by the straight line formula;
V2(,1acc
)
(1 )V2(0) V2(1)
V2(,1acc
)
V2(,0acc
)
(V2(1) V2( 0) ) 2.39
Where ‘ is acceleration factor. In power flow studies ‘ ’ lies between 1.4
and 1.6 and cannot exceed 2 if convergence is to occur [11, 42]
Generally
Vi ,(acc
r)
(1 )Vi ,(acc
r 1)
Vi ( r )
r 1)
Vi ,(acc (Vi ( r ) Vi ,(acc
r 1)
) 2.40
bus (4) is voltage controlled bus, then | V4 | has a specified constant value
| V4 |
and its voltage correction must always be zero. Furthermore, since
| V4 |
64
1 Pi jQi N
Vi YikVk
Yii Vi *
k 1
k i
Thus
N
Qi Im{Vi *
Y V }
k 1
ik k 2.42
Eq. 2.42 is used to evaluate Qi for the best previous voltage value at the
1 P4,sch jQ4
(1) N
V4(1) Y4 kVk(1)
yii V4*
k 1
k i
So normalized
65
(1)
V4
V (1)
4 ,cor V4 2.43
V4(1)
We then proceed to the next step with V4,cor as the stored value of voltage
N
YiK VK ( K iK ) 2.45
K 1
N
Pi | Vi | | YiK Vk | cos( ik k i ) 2.50
K 1
N
Qi | Vi | | YiK Vk | sin( ik k i ) 2.51
K 1
These equations (i.e. Eqs. 2.50 & 2.51) are known as static or balanced
equations of real and reactive powers of bus (i). They are none-linear and
therefore only a numerical solution is possible. For each of the n-bus
system we have two of such equations giving a total of 2n equations.
Equation 2.48 can be expanded using rectangular | 1 j | or | cos j sin |
If we denote Pgi, sch as the scheduled power being generated at bus (i) and
These two equations 2.52 and 2.53 can be represented using arrow flow
diagram as in Fig 2.11 below
Q gi
gi i,Sch
Qi ,sch
i Qi
di Qdi
(b)
(a)
Fig. 2.11 Power Flow Illustrative Diagram (a) Active Power, (b) Reactive Power
67
When Pi ,calc and Qi ,clc match the scheduled values Pi , sch and Qi ,sch , we say
Buses can be load buses, generator buses or swing buses. A load bus is
also called PQ bus since the real and reactive are specified ( i and Qi ) and
it does not have a generator. A load bus need not have load; it may simply
be an interconnection point for two or more lines. The specified real i and
reactive Qi powers enable the voltage to be calculated. Real and reactive
powers supplied to the bus are positive quantities while that consumed
from power system are negative.
A generator or voltage controlled bus (PV bus) have a generator connected
to it and the generated power g i and voltage Vi are specified. The voltage
utility studies, a large generator is picked as the swing bus. The generator
at this bus supply the difference between the specified real power injected
into the system at other buses and the total system output plus losses.
Since the voltages throughout the system must be close to 1pu, we specify
the voltage at the swing bus equal to 1pu.
There are three class of buses; the slack or reference bus, voltage
controlled (PV) bus and load (or P.Q) bus.
The load-flow problem is to determine values for all the state variables by
solving an equal number of load-flow equations based on the input data
specifications. If there are Ng voltage-controlled buses (excluding the slack
state variables have been calculated, the complete state of the system is
known and all other quantities which depend on the state variable
( i , | Vi |) can be determined.
Load
)
Total
N 2N
69
The reactive power Qi injected into any bus (i) of the system during
normal operation is much less than the reactive power which would flow if
all lines from that bus were short circuited to reference; that is
Qi Vi 2 Bii 2.59
Qi
LiK V K ViV K YiK sin iK K i 2.60(a)
VK
i Qi
VK ViV K YiK sin iK K i (b)
i V K
Recall that
2.61
YiK cos iK GiK
H ii Qi Vi 2 Bii
yields.
Lii H ii Vi Bii 2.65(a)
2
Lii H ii Vi Bii
2
for i = k 2.65(b)
Substituting
71
V
Q L 2.66(b)
V
becomes
The following assumptions are made for further decoupling and the final
algorithm for the fast-decoupled method
1. Omit from B′ the representation of those network elements that
affect MVAr flows, that is shunt reactants and set taps ‘i’ of off-nominal
transformers equal to 1
2. Omit from B″ the angle-shifting effects of phase-shifters (by setting
t 1 00 0
3. Divide equations 2.67(a) and 2.67(b) by V i and assume Vk 1 p.u
The voltages can be removed from the entries of the coefficient matrix of
|V |
Eq. 2.70 by multiplying the first row by the correction vector k
and
| Vk |
then divide the resultant by│V2│ that is
V2V2 B22 V2 Q2 and so on, to obtain
V2 V2 V2
Q2
B22 V2 B23 V3 B24 V4 2.71
V2
Q3
B32 V2 B33 V3 B34 V4
V3
And so on
Each row of Eq. 2.70 can be treated similarly by representing the reactive
mismatch at bus ‘i’ by the quantity Qi . The coefficients in Eq. 2.71 are
Vi
constants equal to the negative of the susceptance in the row of bus which
correspond to bus 2. All the entries in the coefficient matrix of Eq. 2.70
become constants given by the susceptance of bus
73
Equation 2.69 can be modified as well by multiplying the first row by the
i
vector of angle corrections i.e.
Vi
2
V2V2 B22 ; V2V3 B23 3 ; etc
V2 V3
And rearranging the result to obtain
2
V2 B22 2 V2 B23 3 V2 B24 4
V2 2.73
3
V3 B32 2 V3 B33 3 V3 B34 4
V3
If we set │V2│, │V3│ and │V4│ equal to 1.0 p.u in the left-hand side of the
expression, we have constant coefficients as those in Eq. 2.71. The other
rows of Eq. 2.69 are treated in a similar manner to get the decoupled
system of equations for the four-bus network. Note that 2 represent
V2
In Eqs. 2.68(a) & 2.68(b), both B′ and B″ are real and sparse and have the
structure as [H] & [L] respectively. Since they contain only network
admittances, they are constant and need to be triangularized or inverted
only once at the beginning of the iterations and then used in all successive
iteration.
If phase-shifters are not present, both [B′] and [B″] are always
symmetrical, and their constant sparse. Upper triangular factor are
calculated and stored only once at the beginning of the solution. This
algorithm results in a very fast solution of ∆δ and ∆V and hence the name
fast-decoupled method [20, 43, 44].
As earlier stated Newton-Raphson solution method converges faster with
fewer iterations and better since the innovation of compact computer
system with large memory space in the market.
75
CHAPTER 3
3.2 Methodology
From Fig. 3.1 is the injected (Complex) generator powers and the
the complex load powers. The V1 is the complex (phasor) bus voltages.
Transformers are assumed to have been absorbed into the generator.
S i S gi S di
N
S i S ik , i 1,2,........,n 3.4
k 1
Where we sum over all the transmission links connected to the ith bus
and also define the bus current
N
I i I gi I di I ik ,.i 1,2,.......,n 3.5
k 1
Vi Vi e j Vi e j
ik . i k
N
ViVk (cos ik j sin ik )(Gik jBik ) 3.8
k 1
Equation 3.7 & 3.8 are the equivalent form of (complex) Power flow
equation. Eqn.3.8 can be splitted into real and imaginary part as,
N
Pi | Vi || Vk |(Gik cos ik Bik sin ik ) 3.9a
k 1
N
Qi | Vi || Vk |(Gik sin ik Bik cos ik ) 3.9b
k 1
V3 | V3 | 3
PQ
PL3 jQL3
Fig. 3.2 Three bus system
Complex power injected into the bus from the generators is given by
And at the ith bus, the net complex power injected into the bus is given by
S i Pi jQi gi di j Qgi Qdi 3.10b
While the real and reactive power injected into the ith bus are thus:
i gi di
Qi Qgi Qdi For i = 1, 2, …………..n
The total phasor current (Ii) entering the transmission line is given by
1 gi di 3.11
The nodal equations of the 3-bus network are; at bus 1, current entering
into the node is
At bus 2,
81
At bus 3 3 Y12V1 Y23V3 Y12V1 Y23V3 jYC jb12 b23 V3 3.14
Where
23 32 1
23
13 31 1 C 1
13 C
But complex power ‘S’ into the system is
S jQ VI *
*
jQ ;
jQ
*
V V*
jQ
:. 3.15
V*
1 jQ1
*
12 13 j b12 b13 V1 12V2 13V3 3.16
V1
2 jQ2
*
12V2 12 23 j b12 b23 V2 23V3 3.17
V2
3 jQ3
*
13V1 23V2 [13 23 jC j b13 b23 ]V3 3.18
V3
V3*
jQ
V
V
I
Z V*
So jQ VV * 3.20
Equating real and imaginary part of Eq. 3.19
We find that
1 Re 11V1V1* 12V2V1* 13V3V1* (i)
Bus 1: P1 , Q1 , V1 , 1
Bus 2: 2 , Q2 V2 , 2 Gives 12 variables from
three equations.
Bus 3: 3 , Q3 V3 , 3
g1 ( x1 , x2 , u) h1 ( x1 , x2 , u) b1 0 3.21
And another function such that
g 2 ( x1 , x2 , u) h2 ( x1 , x2 , u) b2 0 3.22
b1 & b2 - constant
U – independent control and also a constant,
84
to be X 1(0) and X 2(0) . The zero superscripts indicate the initial estimates,
X 1(1) & X 2(1) actual solution.
X 1( 0 ) & X 2( 0 ) are the correction values to be added to X 1( 0) & X 2( 0) to
yield the corrected solution X 1(1) & X 2(1) so equation 3.21 and 3.22
becomes
g1 (0) g
g1 ( X 11 , X 21 , U ) g1 ( X 1(0) , X 2(0) , U ) X 1(0) | X 2(0) 1 |(0) ..... 0
x1 x2
3.25(3.37)
g 2 (0) g
g 2 ( X 11 , X 21 , U ) g 2 ( X 1(0) , X 2(0) , U ) X 1(0) | X 2(0) 2 ..... 0 3.26
x1 x2
Neglecting the partial derivatives of the order greater than 1, the term
g 2 0
| indicates that the partial derivatives is evaluated at X 1( 0) and X 2( 0) .
x1
superscript indicates the initial estimate X 1(0) and X 2(0) which is used to
compute the numerical values of the partial derivatives. The mismatch
X 1(1) X 1( 0) X 1( 0)
3.29
X 2(1) X 2( 0) X 2( 0)
K 1
3.30
K i
N
Qi | Vi | Bii | ViVk Yik | sin( ik k i )
2
K 1
3.31
K i
Gii and Bii are the conductance and susceptance of a line joining two
transmission stations. Since transmission lines connect bus (i) to another
Let us assume that all buses are load buses except the slack bus (which
must be a generator bus) with known demand Pdi and Qdi . The slack bus
3.37
A similar mismatch equation can be written for reactive power Q,
voltage angle i(k ) and voltage magnitude | Vi (k ) | with the small changes
in real and reactive power Pi (k ) and Qi(k ) . Elements of the Jacobin
matrix are the partial derivatives of 3.30 and 3.31 evaluated at i(k ) and
P J 11 J 12 P H N
Q J OR 3.40
21 J 22 | V | Q M L |V |
The partioned form of Eq.3.39 shows the four different types of partial
derivative contained in the Jacobin matrix
For voltage-controlled buses, the voltage magnitudes are known.
Therefore, if ‘m’ buses of the system are voltage-controlled, ‘m’ equations
Pi N
| Vi || Vk || Yik | sin( ik k i )
i K 1 3.41
K i
Pi
| Vi || Vk || Yik | sin( ik k i )
k k i 3.42
Pi
| Vi || Yik | cos( ik k i )
| Vk | k 1 3.44
Qi
| Vi || Vk || Yik | cos( ik k i )
3.45 k 1
k
3.46
The diagonal and the off-diagonal elements of J 22 are
Qi N
2 | Vi || Yii | sin ii | Vi || Vk || Yik || sin( ik k i ) 3.47
| Vi | K 1
K i
Qi
| Vi || Yik | sin( ik k i ), k 1
| Vk | 3.48
The term Pi k and Qik are the difference between the scheduled and the
calculated values, known as the power mismatch (residuals), given by
Vi ( k 1) Vi ( D ) Vi ( k ) 3.52
(0) (0)
2. Use the estimate to calculate Pi ,calc and Qi ,calc using Eqs.3.30 and
3.31 then the mismatches Pi (0) and Qi( 0) using Eqs.3.35 and 3.36.
3. Evaluate the elements of the Jacobian matrix ( J11, J12 , J 21, J 22 )
using Eqs 3.43 – 3.48
Solve Eq.3.51 for initial corrections i and | Vi |
( 0) ( 0)
4. directly using
optimally ordered triangular factorization and Gaussian elimination
method.
5. The new voltage magnitudes and phase angles are computed using
Eqs.3.51 & 3.52.
i(1) and Vi
(1)
6. Use the new values obtained as a starting values for
the next iteration and so on.
The process is continued until the mismatches Pi and Qi
(k ) (k )
7. are
less than the specified tolerance i.e.
Pi (k )
3.53
Qi(k )
Has it
Yes
Converged
No
Output
Solve Jacobian Equation for Result
Voltages and Angle Update
The coefficient of the Jacobian matrix are not constant, they are functions
of the voltage variables V and and hence vary for each iteration.
However, after a few iterations as V and tends to their final values the
coefficients will tend to final values. The modification of the Newton’s
algorithm is to calculate the Jacobian for the first two iterations and then
use the final value for all the following iterations. On the other way, the
Jacobian can be updated every two or more iterations. None of these
affects the convergence of the algorithm, but much time is saved (but not
storage)
J V
93
For increments in the voltage, the direct method is to find the inverse of J
In power system J is usually sparse but J 1 is a full matrix. The method
of triangular factorization solves for the vector V by eliminating J to an
upper triangular matrix with a leading diagonal and then back-
substituting for V , i.e. eliminate U V
1
and back-substitute
U 1 V Triangulation of the Jacobian is best done by row. This
means that the maximum storage is that of the resultant upper triangular
and diagonal.
becomes very small, that is | Pi | and | Qi | where is very small
number.
During the iteration, the elements of the Jacobian matrix are calculated
since they depend upon the latest voltage estimate and calculated power.
The process is continued until the error becomes very small, that is
P , and Q where is a very small value.
at the nonzero terms in the diagonal sub-matrices J11 and J 22 , they are
not very small. The implication is that active power flow depends mostly
on the (and not very much on the | Vi | ), while reactive power flow
depends mostly on the | Vi | (and not very much on the ). That is, there is
fairly good decoupling between the equations for active and reactive
powers.
This decoupling feature is used in simplifying the N-R algorithm for solving
the power flow equations. So in the general iteration formula 3.52, instead
of picking
J J 12 J 0
A( x1 ) 11 , we chose A( x 1 ) 11
J 21 J 22 0 J 22
95
J 11 3.54
Q J 22 | V | 3.55
2 2
4 2 2
2
J 11
3.56
4 4
4 4
2 4
96
Q2 Q2 V2
V2 V4 Q2
V2 V4 V2
J 22
3.57
Q4 Q4 V4
V2 V4 Q4
V2 V4 V4
The equations are decoupled in the sense that the voltage-angle
corrections are calculated using only real power mismatch , while the
voltage-magnitude corrections are calculated using Q mismatch.
P H 0
Q 0 | V |
L | V |
3.58
This is the Decoupled Newton Method
It can be further factored out as;
V
Q L 3.60
V
H ik Lik ViVk (Gik sin ik Bik cos ik ) i≠k
i Vi
H iK and LiK Qi
K Vi
From Eq. 2.50 & 2.51
Pi N
Pi | ViVk Yii | cos ii | ViVk Yik | cos( ik k i ) 3.61
k K 1, K i
N
Qi | ViVk Yii | sin ii | V V Y
K 1, K i
i k ik | sin( ik k i ) 3.62
Using Eqs. 3.61 and 3.62, the elements of the Jacobian matrices H & L are
obtained as follow:
Off-diagonal elements of H (i.e. when i≠k) are
i
H ik ViVK Yik sin iK K i
K
Expanding by trigonometric function yields,
= ViV K YiK sin iK cos K i sin YiK cos iK sin K i
N
| V V Y
K 1, K i
i k ik | sin( ik k i ) | ViVk Yik | sin ik
Vi K 1
N
Lii | 2Vi Yii | sin ii | ViVk Yik | sin( ik k i ) ViVk Yik sin ii
2
K 1
1
V IR cos r IX sin r [(Vr I cos r ) R (Vr I sin r ) X ]
Vr
RPr XQr
Vr 3.74
Then for a transmission line where X>>R and R is negligibly small,
therefore
XQr Vr
V , Qr r
V 3.75
Xr X
This relation shows that the reactive power Qr is proportional to the
magnitude of the voltage drop in the line. Thus voltage control and
reactive power control are interrelated. The voltage at the consumer’s
terminals must be maintained constant within prescribed limit irrespective
of the type and magnitude of the load. The maintenance of a constant
voltage is a complicated problem due to the fact the system is supplied
from many sources and it as well supplies many loads at several voltage
levels. In order to maintain the voltage at their prescribed values at all
times, it is necessary to maintain the balance of reactive power in the
system. That is the reactive power generated should be exactly equal to
the reactive power consumed (absorbed). Any mismatch in the reactive
power balance affects the bus voltage magnitudes.
I1 R 1 V
V
L
I1
(b)
(a)
Fig. 3.4a. (a) Circuit diagram, (b) Phasor diagram of an Inductive Load
3.4(d).
m n IC
k
I2 I1
IC R
0
C
V
2
1
V C L I2 b
I
I 1 aC
(d)
(c)
From Fig.3.4c above the total current drawn from the supply will be equal
to the phasor sum of I 1 and I c that is, I 2 I 1 I C 3.77
Then from the phasor diagram of Fig.3.5d, 0c I 1 cos1 I 2 cos 2
104
cos1
The new supply current is given by I 2 I 1 3.78
cos 2
Since cos 2 cos1 , I 2 I1 . Hence the new current drawn from the supply is
less than the load current I 1 as can be seen from the phasor diagram.
Also I 2 cos 2 I1 cos1
Therefore, VI 2 cos 2 VI1 cos1 , Or P2=P1 3.79
This relation shows that the power taken from the supply has not altered.
So by connecting a capacitor in parallel (shunt capacitor) with an
inductive load, the power factor is improved and the current taken from
the supply is reduced without altering either the current or the power
taken by the load.
3.17. Capacitor Rating Calculations.
Or QC Q1 Q2 3.82(a)
1
Capacitive Reactance X C 3.86
jC
10 6
C 3.87
2 fX C
Calculation of C:
The value of capacitor (C) can also be calculated by simplifying Eq. 3.85:
QC VI C
V
And I C VC
XC
QC
And C 3.88(b)
V 2
1
And for star connection where VP VL is given by
3
QC QC 3QC
CY 3.89(b)
VP (VL ) 2 VL2
2
R X
1
And X C with low Var in a system the voltage becomes low and vice
jC
versa [21]. These relationships were used for the result analysis.
107
Where KVAR rating is the size of the capacitor needed, KW is the average
power drawn, 1 is the trigonometric ratio for the present power factor and
2 is the trigonometric ratio for the desired power factor. 1 = Existing (cos-
1 PF1) and 2 = Improved (cos-1 PF2). Note, at high voltages power capacitors
or capacitor bank values are rated in Kilo Volt-Ampere Reactive (KVAr or
MVAr).
Table 3.2 Transmission Line Data (of Bison, two conductor per phase &
2x350 mm2 X-section Conductor) for 330KV Lines.
Source: [1]
Line Data
1 1
Converting line impedance to admittance Y
z R jX
MW jMVAr
The load and generation expressed in per unit values is given as .
base.value
Slack Bus = Egbin GS
CHAPTER 4
power demand and generation increases, so do the flow and losses on the
transmission lines as well as the flow and losses on the circuits and
devices that make up each generating unit. As the power flow on
transmission line increases this cause temperature rise of the conductors,
which results in loss of mechanical strength and increased sag.
Extended operation of a line beyond its thermal rating can permanently
reduce the strength of the line. Once lines become overloaded, generation
is re-dispatched to relieve the overloads, and in some cases, the lines are
interrupted to prevent permanent damage. This implies that every change
in load or generation, switching off a device, or tap change at a
transformer would be a disturbance to the entire power system. The
disturbance may also be as random events like lightning strike and short
circuit. If the system is stable, the control and dynamics will behave in
such a way as to move the system state towards a new equilibrium after
the disturbance.
show how the system output is affected by changes in the system input
because the aim of controlling the system is to reduce the error in output
by means of change in system input. Power flow analysis is a steady-state
problem and the modeling of system components like transformer,
generator, lines, and load will be carried out under steady-state conditions
[13, 48].
generated power condition, the torque angle (δ) decreases slightly, but the
phase of the armature current Ia will rotate such that the power factor
angle δ increases. Thus more reactive power is injected into the bus
(Q VI a sin )
The limit on the control of | Vt | occurs primarily due to the limit on the field
current (hence the limit on reactive power Q).
Ia Ra Ia
Ef
+
+ E f E a cos(ot )
Ef Vt
-
-
(b)
(a)
Vp Vs
Ip 4.1
jX jX
Vp Vs
Is 4.2
jX jX
Ip a:1 aI p Is
+ +
Vp = =
Vp a
Vt Vs
Vp
aI p y yVa 4.3
a
Vq
Iq y pVq 4.4
a
From Eq. 4.3
y V p y Vq
Ip
a a a a
Vp
Iq y yV p
a
It can be further simplified as
117
Vp Vp
Ip y y 4.5
a2 a2
y
I q V p yVq 4.6
a
Considering the coefficients of Eqs. 4.5 and 4.6, and in matrix form.
I p y
y V
a2 a2
p
y
I q y Vq
a
We can represent or draw the equivalent circuit of tapped transformer as
in Fig 4.4 below and the shunt element is got by adding the admittance.
y y (1 a)
2
y
a a a2
y (a 1)
y y
a a
Ip IS +
+ A
y
a
VP B y 1 a C y
a 1 VS
2
a 2
a
done on a per phase basis. A transmission line on a per phase basis can
be regarded as a two-port network, where the sending-end voltage 'VS '
and receiving current ' I S ' through ABCD constants are represented as [17]
VS AV R BI R 4.7
I S CVR DI R 4.8(a)
Power flow at any point through a transmission line can always be
determined if voltages, current and power factor are known or calculated.
Figure 4.5 represents transmission line between two buses (i & j) and its
admittance given in Eq. 4.8b.
Bus i Bus j
R + jX
B B
J J
2 2
B
Yii Y jj y j Y ji y Yij 4.8(b)
2,
4.2.6 Medium and Long Transmission Lines
Medium and long transmission lines are represented or modeled by its
nominal Pie-equivalent circuit as shown in Fig. 4.6. When the total shunt
admittance of the line is divided into two equal parts
jX L
R IR
Z j
VS VR
Y Y
2 2
Fig 4.6 Nominal circuit of medium and short length transmission line.
119
and placed at the receiving and sending ends of the lines, the circuit is
said to be a nominal equivalent.
In a transmission line, the total resistance and inductive reactance of the
line is included in the series arm of the equivalent - and the total
capacitance to neutral is divided between its short arms [17, 19].
1
We know that y and Z r jx or R j L 4.9
z
The Pie–model of the nominal - equivalent of medium/long transmission
line is represented as shown in Fig.4.7.
Y G jB
VS
b1 Jwc y Jwc VR
b2 , or
2 2 2
1 1
z R jwL
1 R jwL
Z
R jwL R jwL
R jwL
G jB 4.10
R 2 w 2 L2
Equation 4.10 can further be expanded thus,
R wL
G and B
R w 2 L2
2
R 2 w 2 L2
Usually our load is represented as
(i) S L PL QL
= VI* - where current is lagging behind voltage
(ii) S L PL QL
= V*I - where current is leading the voltage
120
P K PV m f m 4.11
Q K qV n f n
Where K p and K q are constants, which depend upon the nominal value of
the variable P and Q. The conventional power models are the exponential
function represented as
Pd PS V a 4.12
Qd QS V b
Pd PS ( 1V 2 2V 3 ) 4.13
Qd QS (q1V 2 q2V q3 )
Where Pd and Qd are active and reactive components of the load when the
impedance (z), constant current (I) or constant power (P). They have the
following properties.
1 2 3 1
4.14
q1 q 2 q 3 1
The exponents a & b of Eq. 4.12 are equal to 0.1 or 2 for constant power,
constant current and constant impedance characteristic respectively.
Dynamic load Model: The response of most composite loads to voltage
and frequency changes is fast, and so the steady state response is reached
very swiftly. Motors consume 60 to 70% of the total energy supplied by a
power system [49, 50]. Therefore, the dynamic effects due to motors are
usually the most significant aspects of dynamics characteristic of system
loads.
For some power system components their responses to disturbance do not
occur instantaneously but require some time lag. Such load are said to
have dynamic characteristic. Studies of systems with large concentration
of such predictable load require representation of load model [18, 43, 49,
51].
back to the year 1898 [48] when a small generating plant was installed in
Lagos. The first power interconnection was a 132KV link constructed in
1962 between Lagos and Ibadan. By 1968 the first National grid structure
emerged with the construction of the kainji hydro station which supplied
power via a 330KV, primarily radial type transmission network into the
three members’ 132KV subsystem then existing in the Western, Northern
and Eastern parts of the country. The 330KV and 132KV systems were
initially run by two separate bodies- “Nigeria Dams Authority (NDA)”, and
“Electricity Corporation of Nigeria (ECN)” respectively. Central control for
the 330KV Network was coordinated from kainji power supply control
room, while the 132KV Network was run by load dispatcher located at
Ijora Power Supply Lagos. These two bodies were merged formally into
single power utility known as National Electric Power Authority (NEPA) on
1st April, 1972 thus ushering in centralized regulation and coordination of
the entire rapid growing 330KV and 132KV National network in Nigeria.
These networks are characterized by many disturbances which cause
various hindrances and outages that call for research work.
and Sapele. The hydroelectric power stations are in the country’s middle
belt and are located at Kainji, Jebba and Shiroro. The transmission
network is made up of 5000km of 330KV lines, 6000km of 132KV lines, 23
of 330/132KV sub-stations and 91 of 132/33KV substations. The
distribution sector is comprised of 23,753km of 33KV lines 19,226km of
11kv lines, 679 of 33/11KV sub-station. There are also 1790 distribution
transformers and 680 injection substations [52].
Figure 4.8 shows the map of PHCN network with the Independent Power
Producers’ (IPP) contribution. With the incorporation or contribution of IPP and
or
Distributed Generation (DG) the problem of long distance in some Northern will
be addressed.
4.6 Overview of Nigeria 330kV Transmission Network used for the case study
The single-line diagram of the existing 330KV Nigeria transmission
network used as the case study is as shown in Fig.4.9. It has 30 buses
with nine generating station. The Egbin power station was chosen as the
slack bus because of its location in the network.
127
Kano
B. Kebbi Kaduna
310km 230km
Maiduguri
Kainji
Shiroro TS
GS 196km 284km
96km
Jebba GS
Jebba GS Gombe
Shiroro GS
81km
244km 264km
144km
8km
Jos
Abuja
Jebba TS Geregu 275km
Ajaokuta 5km Makurdi
157km
137km
Oshogbo
Ayede 195km
195km
251km
137km Benin N.Heaven
252km
280km
IKJ-West 137km
107km 96km
50km
62km Sepele PS
Are bus
voltages outside No
5% of normal
range
Apply Compensation
Stop
Fig. 4.10 Flow Chart for the Analysis of Shunt Capacitor Compensation Algorithm.
The results from the N.R. iterative solution method give the bus voltages,
line flows, and power losses under normal (uncompensated) condition are
130
as shown in Tables 5.1 and 5.4 respectively. The voltages at buses 14, 17,
18, 19, 22, 29 and 30 are low and in order to ensure that they are within
acceptable limits, shunt capacitive compensation were injected into the
buses. Based on Power Holding Company of Nigeria (PHCN) power factor of
0.85 for transmission lines the MVAr capacities of the various capacitors
required to carry out compensation of the network at the buses were
determined using Eq.3.90 and or Eq.3.91 as in Fig 4.11
KW , 200
2 0.95
1 0.85 Q2
KVAr2
Q
KVAr1
Q Q2
CHAPTER 5
RESULTS AND DISCUSSION
5.1 Presentation of Results
The results obtained using the source (m-file codes) as presented in
appendix 1 are recorded in Tables 5.1 to 5.17. The plots of the tables are
as shown in Figs. 5.1 to 5.10.
Table 5.1: Per Unit Bus Voltages for Compensated and Uncompensated
With
Compensation Without Compensation
B/N Bus Name Volts (p.u) Volts (p.u)
1 Egbin-GS
(Slack) 1.0000 1.0000
2 Delta-PS 1.0000 1.0000
3 Okpai-PS 1.0000 1.0000
4 SAP /PS 1.0000 1.0000
5 AFAM-GS 1.0000 1.0000
6 Jebba-GS 1.0000 1,0000
7 KAINJI-GS 1.0000 1,0000
8 Shiroro-PS 1.0000 1,0000
9 Geregu(PS) 1.0000 1,0000
10 Oshogbo 1.0035 0.9919
11 Benin 0.9998 0.9957
12 Ikeja-West 0.9969 0.993
13 Ayede 0.9967 0.9792
14 Jos 0.9823 0.8171
15 Onitsha 0.9793 0.9748
16 Akangba 0.9931 0.9859
17 Gombe 1.0242 0.8144
18 Abuja
(Katampe) 0.9667 0.9402
19 Maiduguri 1.0455 0.8268
20 Egbin TS 0.9469 0.9816
21 Aladja 1.0006 0.9994
22 Kano 0.947* 0.7609
23 Aja 0.9692 0.9838
24 Ajaokuta 0.9999 0.9997
25 N-Heaven 0.9721 0.9582
26 Alaoji 0.9598 0.9564
27 Jebba-TS 0.9993 0.9988
28 B.Kebbi 1.0075 0.9873
29 Kaduna 0.9654 0.8738
30 Makurdi 0.9943 0.8247
132
Table 5.1 gives the per unit bus voltages of Newton-Raphson (N-R) for
compensated and uncompensated while Table 5.2 gives the actual values
in KV.
Table 5.2 Bus Voltages for Compensated and Uncompensated (KV)
With Without
Compensation Compensation
B/N Bus Name Volts (KV) Volts (KV)
1 Egbin-GS 330.000 330.000
(Slack)
2 Delta-PS 330.000 330.000
3 Okpai-PS 330.000 330.000
4 SAP /PS 330.000 330.000
5 AFAM-GS 330.000 330.000
6 Jebba-GS 330.000 330.000
7 KAINJI-GS 330.000 330.000
8 Shiroro-PS 330.000 330.000
9 Geregu(PS) 330.000 330.000
10 Oshogbo 331.155 327.327
11 Benin 329.934 328.581
12 Ikeja-West 328.977 327.69
13 Ayede 328.911 323.136
14 Jos 324.159 269.643
15 Onitsha 323.169 321.684
16 Akangba 327.723 325.347
17 Gombe 337.986 268.752
18 Abuja 319.011 310.266
(Katampe)
19 Maiduguri 345.015 272.844
20 Egbin TS 312.477 323.928
21 Aladja 330.198 329.802
22 Kano 312.510 251.097
23 Aja 319.836 324.654
24 Ajaokuta 329.967 329.901
25 N-Heaven 320.793 316.206
26 Alaoji 316.734 315.612
27 Jebba-TS 329.769 329.604
28 B.Kebbi 332.475 325.809
29 Kaduna 318.582 288.354
30 Makurdi 328.119 272.151
133
Table: 5.3 Bus Angle, Shunt (Y-shunt) and Injection Powers (Sg)
(Uncompensated)
B/N Sg(p.u)
BUS NAME Angle(rad) Yshunt Sg(p.u) Real Imaginary
1 Egbin-GS (Slack)
0.000 0.5140 0.0000 0.0000
2 Delta-PS 0.02565 0.4780 0.5500 0.2816
3 Okpai-PS 0.1437 0.1040 2.2000 1.1270
4 SAP /PS 0.0263 0.44700 0.7500 0.3842
5 AFAM-GS
0.3043 0.1040 4.7900 2.4539
6 Jebba-GS -0.1049 0.0200 3.2200 1.6496
7 KAINJI-GS -0.0484 1.4860 3.2300 1.6547
8 Shiroro-PS -0.5057 1.8150 2.8000 1.4344
9 Geregu(PS)
0.0992 0.0332 2.0000 1.0244
10 Oshogbo -0.1103 2.0770 1.2037 -0.6165
11 Benin 0.0198 2.8750 1.6056 -0.8224
12 Ikeja-West
-0.0961 1.7000 3.3400 -1.7111
13 Ayede -0.1373 0.9580 1.7665 -0.9049
14 Jos -0.8691 1.3000 -0.8223 -0.4212
15 Onitsha 0.135 1.5140 1.3051 -0.6686
16 Akangba
-0.1076 0.2570 2.3337 -1.1956
17 Gombe -0.9738 1.0500 -0.7448 -0.3814
18 Abuja (Katampe) -5964 0.2000 2.0000 -1.0244
19 Maiduguri -0.9903 0.6000 0.1000 -0.0511
20 Egbin TS
-0.1038 0.5140 -2.3500 -0.0200
21 Aladja 0.0214 0.4780 0.4800 -0.2459
22 Kano -0.9144 0.4000 2.5245 -1.2933
23 Aja
-0.0615 0.2570 1.1999 -0.6147
24 Ajaokuta 0.0972 0.7650 0.6322 -0.3238
25 N-Heaven 0.101 0.3650 -1.1305 -0.5791
26 Alaoji 0.2707 0.6280 1.6395 -0.8398
27 Jebba-TS
-0.1111 1.8650 -0.0744 -0.0379
28 B.Kebbi -0.1149 0.7000 0.6999 -0.3685
29 Kaduna -0.694 0.9000 1.4977 -0.7672
30 Makurdi
-0.8779 0.4000 -0.0744 -0.0379
134
Table 5.4: Line Current, Line Flows, and Line Losses
(Uncompensated)
Line Losses (p.u)
B/Sequence Line Current (p.u) Line Flows (p.u)
From To Real Imaginary Real Imaginary Real Imaginary
16 12 0.1598 -1.3584 0.1576 -1.3394 -0.0011 0.0095
12 1 0.0511 -0.3992 0.0507 -0.3965 0.0507 -0.3965
12 11 0.0046 -0.0358 0.0046 -0.0355 0.000 1E-04
12 13 -0.0386 0.328 -0.0384 0.3257 -0.0005 0.0045
13 10 0.0423 -0.3604 0.0415 -0.3529 -0.0005 0.0046
10 11 0.0059 -0.0506 0.0059 -0.0502 0.000 0.0002
10 27 0.0167 -0.1419 0.0165 -0.1407 -1E-04 0.001
12 6 1.5129 -1.1094 1.5023 -1.1017 -0.0106 0.0077
27 8 0.0016 -0.017 0.0016 -0.0169 0.000 0
27 7 0.0057 -0.0482 0.0057 -0.0481 0.000 1E-04
7 28 -0.0157 0.1328 -0.0157 0.1328 -0.0002 0.0017
8 29 -0.4964 4.263 -0.4964 4.263 -0.0626 0.5378
29 22 -0.1869 1.5934 -0.1633 1.3923 -0.0211 0.1799
14 17 -0.0039 0.0332 -0.0032 0.0271 0.000 1E-04
11 24 0.0085 -0.0677 0.0084 -0.0674 0.000 0.0003
11 4 0.038 -0.2933 0.0378 -0.2921 -0.0002 0.0012
11 15 -0.0587 0.4985 -0.0585 0.4964 -0.0012 0.0105
15 25 -0.058 0.5641 -0.0565 0.5499 -0.001 0.0094
15 26 -0.0508 0.4347 -0.0496 0.4238 -0.0009 0.008
26 5 3.0208 -2.3495 2.889 -2.247 -0.1318 0.1025
4 21 -0.004 0.0327 -0.004 0.0327 0.000 0.000
2 21 -0.004 0.0327 -0.004 0.0327 0.000 0.000
1 23 -0.1185 0.9261 -0.1185 0.9261 -0.0019 0.015
29 14 -0.1092 0.934 -0.0954 0.8162 -0.0062 0.053
14 30 0.0125 -0.1065 0.0102 -0.087 -1E-04 0.0008
10 12 0.003 -0.0257 0.003 -0.0254 0.000 0.000
11 2 0.026 -0.215 0.0259 -0.2141 -1E-04 0.0009
15 3 1.7426 -1.3554 1.6987 -1.3212 -0.0439 0.0341
8 18 -0.1486 1.3112 -0.1486 1.3112 -0.0089 0.0784
9 24 -0.0566 0.2832 -0.0566 0.2832 0.000 1E-04
19 17 -0.0363 0.1457 -0.03 0.1204 -0.0005 0.0018
20 23 0.0158 -0.1236 0.0155 -0.1214 0.000 0.0003
27 26 0.000 0.000 0.000 0.000 0.000 0.000
Fig. 5.1 and 5.2 represent the Plot of Bus Voltages under normal uncompensated
conditions. As can be seen from the plot the voltages that are outside the renge are
clearly seen from the plot.
1.15
1.1
1.05
1
0.95
0.9
0.85
0.8
Voltage (p.u) 0.75
0.7
0.65
0.6
0.55
0.5
0.45
0.4
0.35
0.3
0.25
0.2
0.15
0.1
0.05
0
1 2 3 4 5 6 7 8 9 101112131415161718192021222324252627282930
Bus No
1.2
0.8
Voltage (p.u)
0.6
0.4
0.2
0
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31
Bus No
Table: 5.7 Bus Angle, Shunt (Y-shunt) And Injection Powers (Sg) (Compensated in rad.)
B/N Bus Name
Angle(rad) Y-Shunt Sg(p.u) Real Sg(p.u) Imaginary
1 Egbin-GS (Slack)
0 0.5140 0.0000 0.0000
2 Delta-PS
0.0284 0.4780 0.5500 0.4278
3 Okpai-PS 0.151 0.1040 2.200 1.7126
4 SAP /PS 0.0291 0.4470 0.7500 0.5838
5 AFAM-GS
0.3091 0.1040 4.7900 3.7292
6 Jebba-GS -0.0967 0.0200 3.2200 2.5069
7 KAINJI-GS
-0.0401 1.4860 3.2300 2.5146
8 Shiroro-PS
-0.4886 1.8150 2.8000 2.1798
9 Geregu(PS) 0.1016 0.0332 2.0000 1.5566
10 Oshogbo
-0.1067 2.0770 -1.2037 -0.2962
11 Benin 0.0221 2.8750 -1.6056 -0.3951
12 Ikeja-West -0.0936 1.7000 -3.3400 -0.8218
13 Ayede
-0.1345 0.9580 -1.7665 -0.4347
14 Jos -0.8059 1.3000 -0.8223 -0.2024
15 Onitsha 0.1365 1.5140 -1.3051 -0.3211
16 Akangba
-0.1054 0.2570 -2.3338 -0.5742
17 Gombe -0.8803 1.0500 -0.7448 -0.1833
18 Abuja (Katampe)
-0.5797 0.2000 -2.0000 -0.4922
19 Maiduguri
-0.8935 0.6000 -0.1000 -0.0247
20 Egbin TS
-0.1026 0.5140 -2.3500 -1.111
21 Aladja 0.024 0.4780 -0.4800 -0.1181
22 Kano
-0.8361 0.4000 -2.5245 -0.6212
23 Aja
-0.0606 0.2570 -1.1999 -0.2952
24 Ajaokuta 0.0996 0.7650 -0.6322 -0.1556
25 N-Heaven
0.1022 0.3650 -1.1305 -0.2782
26 Alaoji 0.2712 0.6280 -1.6395 -0.4035
27 Jebba-TS -0.1029 1.8650 -0.0744 -0.0184
28 B.Kebbi -0.1077 0.7000 -0.6999 -0.1677
29 Kaduna -0.667 0.9000 -1.4977 -0.3686
30 Makurdi -0.8127 0.4000 -0.0744 -0.0184
138
Table: 5.8 Bus Angle, Shunt (Y-shunt) and Powers (Sg) (Compensated)
Sg(MVar)
B/N Bus Name Angle(deg) Y-shunt Sg(MW) Real Imaginary
1 Egbin-GS (Slack) 0 0.5140 0.0000 0.0000
2 Delta-PS 1.626989 0.4780 55.0000 28.1600
3 Okpai-PS 8.650541 0.1040 220.0000 112.7000
4 SAP /PS 1.667091 0.4470 75.0000 38.4200
5 AFAM-GS 17.70783 0.1040 479.0000 245.3900
6 Jebba-GS -5.53978 0.0200 322.000 164.9600
7 KAINJI-GS -2.29726 1.4860 323.000 165.4700
8 Shiroro-PS -27.9911 1.8150 280.000 143.4400
9 Geregu(PS) 5.820496 0.0332 200.00 102.4400
10 Oshogbo -6.11267 2.0770 120.370 -61.6500
11 Benin 1.266073 2.8750 160.560 -82.2400
12 Ikeja-West -5.36219 1.7000 334.000 -171.1100
13 Ayede -7.70528 0.9580 176.650 -90.4900
14 Jos -46.1687 1.3000 82.2300 -40.9235
15 Onitsha 7.81986 1.5140 130.510 -66.8600
16 Akangba -6.03819 0.2570 233.376 -119.5600
17 Gombe -50.4309 1.0500 74.4800 -38.1400
18 Abuja (Katampe) -33.2101 0.2000 200.000 -44.230
19 Maiduguri -51.1871 0.6000 10.000 0 -5.1100
20 Egbin TS -5.87778 0.5140 235.000 -2.0000
21 Aladja 1.37492 0.4780 48.000 -24.5900
22 Kano -47.8988 0.4000 252.450 13.9560
23 Aja -3.47167 0.2570 119.990 -61.4700
24 Ajaokuta 5.70592 0.7650 63.2200 -32.3800
25 N-Heaven 5.85487 0.3650 113.050 -57.9100
26 Alaoji 15.5366 0.6280 163.950 -83.9800
27 Jebba-TS -5.89497 1.8650 7.4400 -3.7900
28 B.Kebbi -6.16996 0.7000 -69.9900 -36.8500
29 Kaduna -38.2113 0.9000 149.7700 -46.2070
30 Makurdi -46.5582 0.4000 7.4400 -3.6815
Table 5.10(a) MVAr and Capacitor Values at Various Percentage Compensation levels (in p.u)
B/N MVAR(pu) C(uF) MVAR(pu) C(uF) MVAR(pu) C(uF) MVAR(pu) C(uF) MVAR(pu) C(uF)
1 0.0000 0.0000 0.0000 0.0000 0.00000 0.0000 0.0000 0.0000 0.0000 0.0000
2 0.161318 0.471525 0.1714 0.500996 0.181483 0.530466 0.191565 0.559936 0.201647 0.589407
3 0.646232 1.888907 0.686621 2.006964 0.727011 2.125021 0.7674 2.243078 0.80779 2.361134
4 0.220299 0.643924 0.234068 0.68417 0.247836 0.724415 0.261605 0.76466 0.275374 0.804906
5 1.407205 4.113198 1.495155 4.370273 1.583106 4.627348 1.671056 4.884423 1.759006 5.141498
6 0.945979 2.765056 1.005103 2.937872 1.064227 3.110688 1.123351 3.283504 1.182474 3.45632
7 0.948881 2.773536 1.008186 2.946882 1.067491 3.120228 1.126796 3.293574 1.186101 3.46692
8 0.822535 2.404234 0.873944 2.554499 0.925352 2.704763 0.976761 2.855028 1.028169 3.005293
9 0.587251 1.716508 0.623954 1.82379 0.660657 1.931072 0.69736 2.038354 0.734064 2.145635
10 0.353381 1.032916 0.375467 1.097473 0.397553 1.162031 0.41964 1.226588 0.441726 1.291145
11 0.471464 1.378067 0.50093 1.464197 0.530397 1.550326 0.559863 1.636455 0.58933 1.722584
12 0.981272 2.868215 1.042602 3.047479 1.103931 3.226742 1.165261 3.406005 1.22659 3.585269
13 0.518847 1.516568 0.551275 1.611353 0.583703 1.706139 0.616131 1.800924 0.648559 1.895709
14 0.241477 0.705826 0.256569 0.74994 0.271662 0.794055 0.286754 0.838169 0.301846 0.882283
15 0.383415 1.120705 0.407378 1.190749 0.431342 1.260793 0.455305 1.330837 0.479269 1.400881
16 0.685648 2.00412 0.728501 2.129377 0.771354 2.254635 0.814207 2.379892 0.85706 2.50515
17 0.218554 0.638823 0.232213 0.678749 0.245873 0.718676 0.259533 0.758602 0.273192 0.798529
18 0.587251 1.716508 0.623954 1.82379 0.660657 1.931072 0.69736 2.038354 0.734064 2.145635
19 0.029171 0.085264 0.030994 0.090593 0.032817 0.095922 0.03464 0.101251 0.036463 0.10658
20 -1.20385 -3.51881 -1.27909 -3.73873 -1.35433 -3.95866 -1.42957 -4.17858 -1.50482 -4.39851
21 0.141011 0.412168 0.149824 0.437928 0.158637 0.463689 0.16745 0.489449 0.176263 0.51521
22 0.741659 2.167837 0.788013 2.303327 0.834367 2.438817 0.88072 2.574306 0.927074 2.709796
23 0.352499 1.030339 0.37453 1.094736 0.396561 1.159132 0.418593 1.223528 0.440624 1.287924
24 0.185609 0.542528 0.19721 0.576436 0.208811 0.610344 0.220411 0.644252 0.232012 0.67816
25 0.332036 0.970527 0.352788 1.031185 0.373541 1.091843 0.394293 1.152501 0.415045 1.213159
26 0.481476 1.407333 0.511568 1.495291 0.54166 1.583249 0.571753 1.671208 0.601845 1.759166
27 0.021513 0.062883 0.022858 0.066813 0.024203 0.070743 0.025547 0.074673 0.026892 0.078604
28 0.221526 0.647512 0.235372 0.687981 0.249217 0.728451 0.263063 0.76892 0.276908 0.80939
29 0.439888 1.285772 0.467381 1.366133 0.494874 1.446494 0.522367 1.526855 0.54986 1.607215
30 0.021513 0.062883 0.022858 0.066813 0.024203 0.070743 0.025547 0.074673 0.026892 0.078604
141
Table: 5.11(a) Line Current, Line Flows, and Line Losses (Compensated)
B/Sequence Line Current (p.u) Line Flows (p.u) Line Losses (p.u)
From To Real I(p.u) Imagi I(p.u) Real P(p.u) Imag P(p.u) Real L(p.u) Imag L(p.u)
16 12 0.0859 -0.7304 0.0853 -0.7254 -0.0003 0.0028
12 1 0.0226 -0.1768 0.0225 -0.1762 0.0225 -0.1762
12 11 0.0047 -0.036 0.0047 -0.0359 0.000 1E-04
12 13 -0.0006 0.0048 -0.0006 0.0048 0.0000 0.0000
13 10 0.0224 -0.1908 0.0223 -0.1901 -0.0002 0.0013
10 11 -0.0056 0.0477 -0.0056 0.0479 0.0000 0.0002
10 27 -0.01 0.085 -0.010 0.0853 0.0000 0.0003
12 6 0.6698 -0.4912 0.6677 -0.4897 -0.0021 0.0015
27 8 0.0009 -0.0093 0.0009 -0.0093 0.0000 0.0000
27 7 0.0031 -0.0263 0.0031 -0.0263 0.0000 0.0000
7 28 0.0093 -0.079 0.0093 -0.079 -1E-04 0.0006
8 29 -0.1362 1.1695 -0.1362 1.1695 -0.0047 0.0405
29 22 -0.0522 0.4453 -0.0504 0.4299 -0.0016 0.014
14 17 0.0599 -0.5103 0.0588 -0.5013 -0.0025 0.0214
11 24 0.0004 -0.0031 0.0004 -0.0031 0.0000 0.0000
11 4 0.0022 -0.0167 0.0022 -0.0167 0.0000 0.0000
11 15 -0.0571 0.4845 -0.0571 0.4844 -0.0012 0.0099
15 25 -0.0252 0.2455 -0.0247 0.2405 -0.0002 0.0018
15 26 -0.0539 0.4605 -0.0527 0.451 -0.0011 0.009
26 5 2.785 -2.1661 2.673 -2.079 -0.112 0.0871
4 21 0.0037 -0.0305 0.0037 -0.0305 0.0000 0.0000
2 21 0.0037 -0.0305 0.0037 -0.0305 0.0000 0.0000
1 23 -0.2254 1.7619 -0.2254 1.7619 -0.0069 0.0543
29 14 0.0326 -0.2792 0.0315 -0.2695 -0.0006 0.0047
14 30 0.0198 -0.1691 0.0195 -0.1661 -0.0002 0.0020
10 12 -0.0183 0.1552 -0.0183 0.1557 -1E-04 0.0010
11 2 0.0015 -0.0123 0.0015 -0.0123 0.0000 0.0000
15 3 1.431 -1.113 1.4014 -1.09 -0.0296 0.023
8 18 -0.0827 0.7296 -0.0827 0.7296 -0.0027 0.0243
9 24 -0.0117 0.0586 -0.0117 0.0586 0.0000 0.0000
19 17 -0.0623 0.2498 -0.0651 0.2612 -0.0013 0.0053
20 23 0.1632 -1.2761 0.1546 -1.2083 -0.0036 0.0285
27 26 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
With
Compensation
B/N Bus Name Volts (p.u) Angle(rad)
1 Egbin-GS
(Slack) 1.0000 0.0000
2 Delta-PS 1.0000 0.0284
3 Okpai-PS 1.0000 0.1510
4 SAP /PS 1.0000 0.0291
5 AFAM-GS 1.0000 0.3091
6 Jebba-GS 1.0000 -0.0967
7 KAINJI-GS 1.0000 -0.0401
8 Shiroro-PS 1.0000 -0.4886
9 Geregu(PS) 1.0000 0.1016
10 Oshogbo 1.0035 -0.1067
11 Benin 0.9998 0.0221
12 Ikeja-West 0.9969 -0.0936
13 Ayede 0.9967 -0.1345
14 Jos 0.9823 -0.8059
15 Onitsha 0.9793 0.1365
16 Akangba 0.9931 -0.1054
17 Gombe 1.0242 -0.8803
18 Abuja
(Katampe) 0.9667 -0.5797
19 Maiduguri 1.0455 -0.8935
20 Egbin TS 0.9469 -0.1026
21 Aladja 1.0006 0.024
22 Kano 0.9338 -0.8361
23 Aja 0.9692 -0.0606
24 Ajaokuta 0.9999 0.0996
25 N-Heaven 0.9721 0.1022
26 Alaoji 0.9598 0.2712
27 Jebba-TS 0.9993 -0.1029
28 B.Kebbi 1.0075 -0.1077
29 Kaduna 0.9654 -0.667
30 Makurdi 0.9943 -0.8127
143
1.15
1.1
1.05
1
0.95
0.9
0.85
0.8
0.75
Voltage (p.u)
0.7
0.65
0.6
0.55
0.5
0.45
0.4
0.35
0.3
0.25
0.2
0.15
0.1
0.05
0
1 2 3 4 5 6 7 8 9 101112131415161718192021222324252627282930
Bus No
1.2
0.8
Voltage (p.u)
0.6
0.4
0.2
0
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31
Bus No
Fig. 5.4: Bar Plot of Bus Voltages after Compensation
144
1.15
Table 5,13(a) Voltage Value at
1.1
1.05
20percent Comp.
1
0.95
0.9
B/N Bus Name Volts(p.u)
0.85
0.8 Egbin-GS
0.75
1 (Slack) 1.000
Voltage (p.u)
0.7
0.65
0.6
0.55 2 Delta-PS 1.000
0.5
0.45
0.4
3 Okpai-PS 1.000
0.35
0.3
0.25
4 SAP/PS 1.000
0.2
0.15
0.1
5 AFAM-GS 1.000
0.05
0
1 2 3 4 5 6 7 8 9 101112131415161718192021222324252627282930
6 Jebba-GS 1.000
Bus No
7 KAINJI-GS 1.000
Fig.5.5 Graph of Voltage at 20percent 8 Shiroro-PS 1.000
Compensation 9 Geregu(PS) 1.000
Table 5.13(b) Cap Values at 10 Oshogbo 1.0015
20percent Comp 11 Benin 0.9991
B/N C(uF) 12 Ikeja-West 0.9962
1 0.0000 13 Ayede 0.9937
2 0.353644 14 Jos 0.9603
3 1.416681 15 Onitsha 0.9786
4 0.482943 16 Akangba 0.9919
5 3.084899
17 Gombe 0.9963
6 2.073792
Abuja
7 2.080152 18 (Katampe) 0.9623
8 1.803176
19 Maiduguri 1.0164
9 1.287381
20 Egbin TS 0.9531
10 0.774687
11 1.033551
21 Aladja 1.0004
12 2.151161 22 Kano 0.9107
13 1.137426 23 Aja 0.9718
14 0.52937 24 Ajaokuta 0.9999
15 0.840529 25 N-Heaven 0.9697
16 1.50309 26 Alaoji 0.9592
17 0.479117 27 Jebba-TS 0.9993
18 1.287381 28 B.Kebbi 1.0041
19 0.063948 29 Kaduna 0.9531
20 -2.63911 30 Makurdi 0.9717
21 0.309126
22 1.625878
23 0.772754
24 0.406896
25 0.727895 Slack Bus
26 1.055499 Real Imaginary
27 0.047162 0.233882 1.571485p.u
28 0.485634
29 0.964329
30 0.047162
145
0.7
0.65
0.6
1 (Slack) 1.0000
0.55
0.5 2 Delta-PS 1.000
0.45
0.4
0.35
3 Okpai-PS 1.000
0.3
0.25 4 SAP/PS 1.000
0.2
0.15
0.1
5 AFAM-GS 1.000
0.05
0
1 2 3 4 5 6 7 8 9 101112131415161718192021222324252627282930
6 Jebba-GS 1.000
Bus No
7 KAINJI-GS 1.000
Fig.5.6 Graph of Voltages 30percent Comp
8 Shiroro-PS 1.000
9 Geregu(PS) 1.000
10 Oshogbo 1.0023
Table 5. 14(b) Cap. Values at 11 Benin 0.9994
30percent 12 Ikeja-West 0.9965
B/N C(uF) 13 0.9949
Ayede
1 0.000
2 0.383114 14 Jos 0.9693
3 1.534737 15 Onitsha 0.9789
4 0.523189 16 Akangba 0.9924
5 3.341973 17 Gombe 1.0077
6 2.246608 Abuja
7 2.253498 18 (Katampe) 0.9641
8 1.95344
19 Maiduguri 1.0283
9 1.394663
10 0.839244 20 Egbin TS 0.9506
11 1.11968 21 Aladja 1.0005
12 2.330425 22 Kano 0.9202
13 1.232211 23 Aja 0.9708
14 0.573484
15 0.910573
24 Ajaokuta 0.9999
16 1.628347 25 N-Heaven 0.9707
17 0.519044 26 Alaoji 0.9594
18 1.394663 27 Jebba-TS 0.9993
19 0.069277 28 B.Kebbi 1.0055
20 -2.85903
29 Kaduna 0.9581
21 0.334886
22 1.761368 30 Makurdi 0.9809
23 0.837151
24 0.440804
25 0.788553
26 1.143458 Slack
27 0.051092 Real Imaginary
28 0.526103 0.239485 1.615285p.u
29 1.04469
30 0.051092
146
0.7
0.65
0.6
0.55 1 (Slack) .0001
0.5
0.45 2 Delta-PS .0001
0.4
0.35
0.3
3 Okpai-PS 1.000
0.25
0.2 4 SAP/PS 1.000
0.15
0.1
0.05
5 AFAM-GS 1.000
0
1 2 3 4 5 6 7 8 9 101112131415161718192021222324252627282930 6 Jebba-GS 1.000
Bus No
7 KAINJI-GS 1.000
Fig. 5.7 Graph of Voltage at 50percent 8 Shiroro-PS 1.000
Compensation 9 Geregu(PS) 1.000
Table 5.15(b) Cap Values at 10 Oshogbo 1.0039
50percent 11 Benin 0.9999
B/N C(uF) 12 Ikeja-West 0.997
1 0 13 Ayede 0.9973
2 0.442055 14 Jos 0.9866
3 1.770851
15 Onitsha 0.9795
4 0.603679
16 Akangba 0.9934
5 3.856123
6 2.59224 17 Gombe 1.0296
7 2.60019 Abuja
8 2.253969 18 (Katampe) 0.9676
9 1.609227 19 Maiduguri 1.0511
10 0.968359 20 Egbin TS 0.9456
11 1.291938 21 Aladja 1.0006
12 2.688952 22 Kano 0.9383
13 1.421782 23 Aja 0.9687
14 0.661712 24 Ajaokuta 0.9999
15 1.050661
25 N-Heaven 0.9726
16 1.878862
26 Alaoji 0.9599
17 0.598896
18 1.609227 27 Jebba-TS 0.9994
19 0.079935 28 B.Kebbi 1.0082
20 -3.29888 29 Kaduna 0.9678
21 0.386407 30 Makurdi 0.9987
22 2.032347
23 0.965943
24 0.50862
Slack Bus
25 0.909869
Power Imaginary
26 1.319374
27 0.058953 0.2508327 1.703993p.u
28 0.607042
29 1.205412
30 0.058953
147
Kano 312.510KV
B. Kebbi 332.475KV Kaduna 318.582KV
310k
m Shiroro TS 230km
325.813KV Maiduguri
Maiduguri
Kainji GS 196km 284km
345.015KV
330KV
96km
Jebba 330KV 337.986KV Gombe
GS 330KV Shiroro GS
81km 319.011KV Jos
244km 144km 264km
264km
8km
330KV 324.159KV
Abuja
Jebba TS Geregu 275km
329.769KV 157km Ajaokuta 5km Makurdi
157km
137km 329.967KV 328.119KV
Oshogbo
Ayede 195km
328.911KV 331.155KV 195km
251km
329.934KV N.Heaven
137km Benin
252km
320.793KV
280km
328.977KV 137km
IKJ-West
107km 96km
50km
Delta PS 138km
330KV 330KV
63km
86km
32km 80km Alaoji 316.734KV
327.723KV 330.198KV
27.5km Okpai
Akamgba GS
5km
Aladja 330KV
319.836KV
312.477KV 25km
Aja
Egbin TS 330KV
Afam
GS
Fig. 5.8. One Line Diagram of the PHCN 330KV 30 Bus Interconnected Network with
Compensated Voltage Values.
148
1.15
1.1
1.05
1
0.95
0.9
0.85
0.8
0.75
Voltage (p.u)
0.7
0.65
0.6
0.55
0.5
0.45
0.4
0.35
0.3
0.25
0.2
0.15
0.1
0.05
0
1 2 3 4 5 6 7 8 9 101112131415161718192021222324252627282930
Bus No
1.15
1.1
1.05
1
0.95
0.9
0.85
0.8
0.75
Voltage (p.u)
0.7
0.65
0.6
0.55
0.5
0.45
0.4
0.35
0.3
0.25
0.2
0.15
0.1
0.05
0
1 2 3 4 5 6 7 8 9 101112131415161718192021222324252627282930
Bus No
This thesis analyzed the Nigerian 330KV, 30 bus system using N-R power
flow algorithm with MATLAB/SIMULINK software. The power flow analysis
was carried out using the data collected from Power Holding Company of
Nigeria (PHCN). The results obtained showed that the weak buses with
values outside the statutory limit of 0.95pu or 313.5KV and 1.05pu or
346.5KV were buses 14 (Jos) with value 0.8171pu , bus 17 (Gombe)
0.8144p.u bus 18 (Abuja) 0.9402p.u, bus 19 (Maiduguri) 0.8268p.u,
bus 22 (Kano) 0.7609p.u, bus 29 (Kaduna) 0.8738pu, and bus 30
(Makurdi) 0.8247p.u under normal uncompensated condition as shown in
Table 5.1 with the corresponding angles as buses14(0.869rad), 17(-
0.973rad), 18(-0.596rad), 19(-0.990rad), 22(-0.914rad), 29(-0.694rad), and
bus 30(-0.877rad). These buses with low voltage values were examined
and shunt capacitive compensation was carried out and the output
results were recorded as in Table 5.1 with the corresponding angles at
buses 14(0.805rad), 17(-0.880rad), 18(-o.579rad), 19(-0.893rad), 22(-
0.836rad), 29(-0.667rad), and bus 30(-0.812rad) as shown in Table 5.7.
The graphs of the corresponding voltage values versus bus number were
plotted as shown in Figs.5.1 and 5.2. We could see from the graph that
bus (22) which is Kano has the highest voltage dip because of its distance
from the grid, followed by Jos, Gombe, Kaduna, Makurdi, Maiduguri and
Abuja respectively. On gradual application of 5percent compensation
intervals, it was found out that at 45 percent compensation most of the
problem buses came up to a tolerable range except bus (22), which is
Kano and it came up to appreciable value at sixty percent compensation
as shown in Tables 5.18 and Fig 5.5 respectively. With 45 percent
capacitive shunt compensation on these buses, bus 14 (Jos) became
0.9823.u, bus 17 (Gombe) 1.0242p.u, bus 18(Abuja) 0.9667pu, bus 19
(Maiduguri) 1.0455p.u, 29 (Kaduna) 0.9654 and 30 (Makurdi) 0.9943.
153
Kano which is heavily loaded was provided with additional line between
Jos and Kano, and this made compensation effect very fast. Bus 22 (Kano)
at 60 percent compensation yielded an increase from 0.7609p.u to 0.947
p.u. Tables 5.10(a) and 5.10(b) presented the values of reactive powers
(MVAR), and voltages at various compensation levels.
The analysis from the compensated results shows that a reasonable and
appreciable values better than when uncompensated with improved
network performance was recorded as shown in Table 5.1. The graphs of
the corresponding compensated voltage values versus bus number were
plotted as shown in Figs.5.3 and 5.4. From the values recorded in Table
5.7 it could be seen that the values of the angles are improved to the
acceptable values. System efficiency improved from 65 percent
(uncompensated) to 85 percent after compensation. The losses in the
system are minimal as can be seen through Table 5.5 and 5.11(b) which
show the summary of total loss in the system for both uncompensated and
compensated conditions.
On further analysis of the system at the compensated stage, various
percentages of compensation were carried out on the network to see the
effect and the results were as recorded in Tables 5.13(a) to 5.115(b) and
corresponding graphs were plotted as represented in Figs. 5.5 to 5.7, On
the application of 20 percent overcompensation, overvoltages (>1.05pu)
resulted in buses (17) & (19) which could cause system collapse if
uncontrolled, this implies that this system cannot be compensated above
20 percent as can be seen in Figs.5.9 and 5.10. The explanation from
literature that ‘compensation of transmission networks results in
improving the system stability and voltage control, and also increasing the
efficiency of power transmission, reducing temporary and transient over
voltages stands. It was also observed that compensating the whole
network jointly affects some of the other buses that are normal, like buses
(20) and (23) as seen in Tables A2.1 and A2.2. The voltage values reduce
154
CHAPTER 6
CONCLUSION, CONTRIBUTION AND RECOMENDATION
6.1 Conclusion
The Nigerian 330KV transmission system associated with various
challenges like instability of the system as a result of voltage profile
violation, transmission line inefficiency, problem of long transmission
lines, network being stretched beyond thermal limit, and poor power
quality that causes constant power failure in Nigeria power system were
discussed. Various solution methods were examined and Newton-
Raphson’s solution method because of its sparsity, fast convergence and
simplicity attributes compared to other solution methods was chosen.
Various compensation techniques were reviewed. Shunt and series
reactive compensation using capacitors has been widely recognized as
powerful methods to combat the problems of voltage drops, power losses,
and voltage flicker in power system networks. Though each compensating
technique has its area and limit of application, but shunt capacitor
compensation method was used because of its outstanding performance in
long transmission lines and its control of reactive power flow. Though they
are expensive but they control voltage directly and also control temporary
over voltage rapidly.
The Newton-Raphson’s solution algorithm was used to carry out the base
power flow solution as shown in Table 5.1, and separate functions or
routine to solve certain task like compensation, fphase, fvgen, xlswrite etc
were developed. MATLAB/SIMULINK simulation method was used for the
analysis. The results of the compensated and uncompensated were
obtained and recorded as in Tables 5.1 & 5.2. Compensation was carried
out on the problem buses and the computer program results were as
recorded. The bus voltages outside the statutory limit of 0.95 – 1.05p.u
that is 313.5 – 346.5KV were buses 14(Jos) with value of 0.8171p.u, bus
17 (Gombe) 0.8144p.u, bus 18(Abuja) 0.9402p.u, bus 19 (Maiduguri)
156
6.3 Recommendations
Recommendations for future work includes;
1. Develop Graphical User Interface (GUI) that can be deployed in the
existing power station to aid the operators to study and analyze power flow
problems.
2. To research on the automatic detection of increase in reactive power
influencing the voltage which causes system failure in the national grid as
used in the developed countries of America, Britain and Japan.
3. Substation and additional lines should be introduced into the network
to assist in the strengthening of the long lines especially Kano, Kaduna
and Maiduguri lines for effective voltage profile.
158
REFERENCES
[1] NIPP In-House Grid Studies 330kVand 132kV Transmission Line
Data, 2006
[2] P. Shankar and Kundur, “Power System Stability and Control II”, 2nd
Ed New York, McGraw-Hill Books pp581, 1994.
[3] J. Arrilaga, and Arnoid, C.P. “Computer Analysis of Power System”,
John Wiley and Sons UK pp 135 1994.
[4] M. Samma and Glove, J.D. “Power System Analysis and Design”,
PWS publishers company pp 295. 1993.
[5] J.B Gupta, “A Course in Electrical Power”, Published by Sanjeev
Kumai Kataria, Sarak Delhi 2007- 2008.
[6] J.D Glover and M.S. Sarma, “Power System Analysis and Design”,
3rd Ed. Wadsworth Group Books Cole, a division of Thomson
learning Inc, 2002.
[7] A. Husain, “Electrical Power Systems”, 5th Revised Edition, CBS
Publisher & Distributor Pvt, Ltd. Aligora (India). 2011.
[8] M. Aredes, “Static Series Compensators Applied to very Long
Distance Transmission Lines”, original Paper, Mumbai Publishers,
Mumbai India. 2003.
[9] D. P. Kothari, and J. Nagrath, “Modern Power System Analysis”,
Third Edition Tata McGraw-Hill publishing Company Ltd. New
DELHI, 2006.
[10] W.F. Tinney and C.E. Hart. “Power Flow Solution by Netwons
Method”. IEEE Trans power app. System vol. PAS-86. pp 1449.
Nov 1967.
[11] F. Milaro. “Continuous Newton’s Method for Power Flow Analysis”,
IEEE Trans on Power systems. Vol. 24 No.1, Feb 2009.
[12] B. Stott, “Effective Starting Process for Newton –Raphson Load
Flows”, Proc. Inst. Elect Eng. Vol. 118. No. 8, pp 983 August 1971.
[13] B. Stott and O. Alsac. “Fast decoupled Load Flow”, IEEE trans
power app. Syst. Vol. PAS – 93, pp 859, Jan 1974.
[14] V. Chen and C. Shen, “A Jacobian Free Mewton GMRES (M) Melhed
with Adaptive Pre-Conditioner and Its Application for Power Flow
Calculation”, IEEE trans power syst. Vol. 21 No. 3 pp 1096. Aug
2006.
[15] S. Iwamoto and Y. Tamura “A Fast Load Flow Method Retaining
Non- Linearity”, IEEE trans power app syst. Vol. PAS – 97
pp1886 1978.
[16] C.A. Canizare, “Voltage Stability Assessment; Concepts, Practices
and Tool”, IEEE/PES power system stability subcommittee, final
document, 2002.
[17] R. A. Bergen and Vijay. “Power System Analysis”, second edition.
John Wiley and Sons,1992.
159
[18] T.C Nwodo, Load flow Analysis (M-Tech. Lecture Material RSUST)
2001.
[19] A. James Momoh [1] “Electrical Power Systems Application of
Optimization”, Howard University Washington D.C. Marcel Dekker
Inc. 20 01.
[20] J. J. Grainger and William D. Stevenson Jr. “Power System
Analysis”, McGraw. Hill Inc. 1994.
[21] H.E Brown, Person, C.E. Kirchmayer, L.E. and Stagg G.W. “Digital
Calculation of Three-Phase Short Circuit by Matrix Method”, Trans
AIEE 97, part III, pp 1277, 1960.
[22] W. Glem Stagg and Ahmed H El-Abiad; “Computer Methods in
Power Systems Analysis”, McGraw Hill Book Company, 1968.
[23] T.B. Gupta, S.K. Kotari & Sons, “ A Course in Electrical Power,” ®
Publishers Sarak Delhi.
[24] F. IIiceto and E Cinieri, “Comparative Analysis of Series and Shunt
Compensation Schemes for A.C Transmission Systems,” IEEE
Trans, Vol, PAS-96, pp1819, May/June 1991.
[25] H. Saadat, “Power System Analysis”, “Milwaukee School of
Engineering, Tata McGrew-Hill Publishing Company Ltd New
DELHI, pp189, 2002.
[26] ABB Information Publication, “An Introduction to ABB Seris
Capacitors”, Sept 1991.
[27] B. S. AshokKumari,K. Porthasarathy, F.S. Probhakara and H. P.
Kincha, “Effectiveness of Series Capacitorsin Long Distance
Transmission Lines,” IEEE Trans, Vol, PAS-89, pp941, May/June
1970.
[28] A.O. Aduloju, “Electrical power System”, vol 2. Evidence Nigeria
Publishing Venture. 2003.
[29] S.S. Venkata, Willien C. Guyker & Willien K. Booth; “Six-phase
(mult-phase) Power Transmission Systems, Fault Analysis”, – IEEE
trans in power app and syst. Vol. PAS-96, No. 3, May/June 1977.
[30] D. Williem Steverson Jr. “Elements of Power System Analysis”,
McGraw Hill Kogakusha Ltd, Singapore pp 304, 1962.
[31] P.O.Ewesor, ”Practical Electrical Systems Installation Work &
Practice”, 2nd Ed. Electrical Inspectorate Services Department,
Federal Ministry of Power Abuja, Petvirgin Partners Publishing Co.
Benin City, pp279, 2010.
[32] A. Husain, “Electric Power Systems”, 5th Ed. CBS Publisher &
Distributors New Delhi Aligarh (India) pp332, 2011.
[33] Dr. B.R. Gupta, “Power System Analysis and Design”, E/E Dept.
Punjab Engineering Collage Chandigarh, S CHAND & COMPANY
LTD, pp473, 2011.
[34] B.R. Gupta. “Power Analysis And Design”, 2nd edition wheeler
publishing pp 1999, 1993.
160
[35] J.D. Glover, M.S. Sarma & Overbye, “Power System Analysis and
Design”, 3rd Ed. Wadsworth Group Books Cole, a division of
Thomson learning Inc pp322, 2008.
[36] R.S. Er. Dahiya, “Sub-Station Engineering, Design, Concepts &
Computer Applications”, S.K. Kateria & Sons® Publishers of
Engineering and Computer Books 4760-61/23, Ansari Road,
Daryaganj, New Deili, pp202, 2010.
[37] S Onahaebi and S. T. Apeh, “Voltage Instability in Electrical
Network”, A case study of the Nigeria 330KV Transmission
Network”, Research Journal of Applied Sciences (RJAS), ISSN 1815-
932X Vol 2(8), pp 855-874, 2007.
[38] C.C. Young, “Equipment and System Modelling for Large-Scale
Stability Studies”, Publication of Institute of Electrical/Electronics
Engineering (IEEE) Trans PP 99-101, 1971.
[39] H. Badrul, Chowdhury, “Load flow analysis in power system”,
electrical and computer engineering department University of
Missouri – Rolla pp 11.1, 1998.
[40] J.A. Momoh, ”Electric Power Distribution, Automation, Protection,
and Control”, Haword University DC, USA, pp47, 2010.
[41] K. Brameller and J.K. Denmead, “Some Improved Methods for
Digital Network Analysis”, Proc. IEE 109, pp 109, 1962.
[42] V.A. Kimtshy, “Calculation of Internal Fault Currents in
Synchronous Machines”. IEEE int. conf. records Pt III, power, pp
13, 1964.
[43] L. Seymour, and Poe, A: “Theorem and Problems of Programming
with Fortran”, McGraw – Hill Inc. New York, 1982.
[44] B.M. Weedy, “Electric Power Systems”, 3RD Ed John Wiley and Sons,
London. 1979.
[45] B. Caven, “A Study of Voltage Profile in the NEPA Network: Analysis
and Recommendation”, Engineering Focus, Jan/April 1992.
[46] J.R. Hubbard, “Theory and problems of Programming with C++”, 2nd
Ed, Schaums Outline Series, McGraw- Hill, 1996.
[47] S.A. Marshall. “Introduction to Control Theory”, MacMillian Press,
1998.
[48] F.O. Enemuoh, “Simulation Modeling of Voltage Stability of an
Interconnected Electric Power Network” Ph.D Thesis, Electrical
Engineering Dept. UNN, pp22, April 2012.
[49] A.O. Ibe, “Power System Principles and Analysis”, University of Port
Harcourt (M-Tech. Lecture Series). pp 7-9, 2001.
[50] J.D. Glove, Thamos J Overbye etal. “Power System Analysis and
Design”, Fourth Edition, SI Printed and Edited by N.P. Padby USA,
pp323, 2008.
[51] E Clarke, “Circuit Analysis of A.C. Power Systems”, vol 11 John
Wiley and sons pg 23, 1943.
161
APPENDIX
A2 Simulation Result
70 80 90 100
B/N Volts(p.u) Volts(p.u) Volts(p.u) Volts(p.u)
1 1.0000 1.0000 1.0000 1.0000
2 1.0000 1.0000 1.0000 1.0000
3 1.0000 1.0000 1.0000 1.0000
4 1.0000 1.0000 1.0000 1.0000
5 1.0000 1.0000 1.0000 1.0000
6 1.0000 1.0000 1.0000 1.0000
7 1.0000 1.0000 1.0000 1.0000
8 1.0000 1.0000 1.0000 1.0000
9 1.0000 1.0000 1.0000 1.0000
10 1.0054 1.0062 1.007 1.0078
11 1.0004 1.0007 1.001 1.0012
12 0.9976 0.9979 0.9982 0.9984
13 0.9997 1.0009 1.0021 1.0033
14 1.003 1.011 1.0187 1.0264
15 0.9801 0.9804 0.9807 0.981
16 0.9944 0.9949 0.9954 0.9959
17 1.0504 1.0605 1.0703 1.0799
18 0.9712 0.9729 0.9747 0.9764
19 1.0728 1.0833 1.0935 1.1035
20 0.9406 0.938 0.9355 0.9329
21 1.0008 1.0009 1.001 1.001
22 0.9555 0.9639 0.972 0.98
23 0.9665 0.9655 0.9644 0.9633
24 1.000 1.000 1.000 1.000
25 0.9745 0.9754 0.9763 0.9773
26 0.9604 0.9606 0.9608 0.9611
27 0.9994 0.9995 0.9995 0.9995
28 1.0109 1.0123 1.0137 1.015
29 0.9769 0.9814 0.9857 0.99
30 1.0156 1.0237 1.0317 1.0396
164
1.15 1.15
1.1 1.1
1.05 1.05
1 1
0.95 0.95
0.9 0.9
0.85 0.85
0.8 0.8
0.75 0.75
Voltage (p.u)
Voltage (p.u)
0.7 0.7
0.65 0.65
0.6 0.6
0.55 0.55
0.5 0.5
0.45 0.45
0.4 0.4
0.35 0.35
0.3 0.3
0.25 0.25
0.2 0.2
0.15 0.15
0.1 0.1
0.05 0.05
0 0
1 2 3 4 5 6 7 8 9 101112131415161718192021222324252627282930 1 2 3 4 5 6 7 8 9 101112131415161718192021222324252627282930
Bus No Bus No
5% 10%
1.15 1.15
1.1 1.1
1.05 1.05
1
1
0.95
0.95
0.9
0.85
0.9
0.8 0.85
0.8
0.75
0.75
Voltage (p.u)
0.7
Voltage (p.u)
0.65 0.7
0.6 0.65
0.55 0.6
0.5 0.55
0.45 0.5
0.4 0.45
0.35 0.4
0.3 0.35
0.25 0.3
0.2 0.25
0.15 0.2
0.1 0.15
0.05 0.1
0 0.05
1 2 3 4 5 6 7 8 9 101112131415161718192021222324252627282930 0
Bus No 1 2 3 4 5 6 7 8 9 101112131415161718192021222324252627282930
Bus No
20% 30%
1.15
1.1
1.05 1.15
1 1.1
0.95 1.05
0.9 1
0.95
0.85 0.9
0.8 0.85
0.75 0.8
Voltage (p.u)
0.7 0.75
Voltage (p.u)
0.65 0.7
0.6 0.65
0.55 0.6
0.5 0.55
0.5
0.45 0.45
0.4 0.4
0.35 0.35
0.3 0.3
0.25 0.25
0.2 0.2
0.15 0.15
0.1 0.1
0.05
0.05
0
0 1 2 3 4 5 6 7 8 9 101112131415161718192021222324252627282930
1 2 3 4 5 6 7 8 9 101112131415161718192021222324252627282930 Bus No
Bus No
40%
50%
Fig. A2.1 Graph of Voltage Vs Bus No. at Different levels of
Percentage Compensation
165
1.15 1.15
1.1 1.1
1.05 1.05
1 1
0.95 0.95
0.9 0.9
0.85 0.85
0.8 0.8
0.75 0.75
Voltage (p.u)
Voltage (p.u)
0.7 0.7
0.65 0.65
0.6 0.6
0.55 0.55
0.5 0.5
0.45 0.45
0.4 0.4
0.35
0.35
0.3
0.3 0.25
0.25 0.2
0.2 0.15
0.15 0.1
0.1 0.05
0.05 0
0 1 2 3 4 5 6 7 8 9 101112131415161718192021222324252627282930
1 2 3 4 5 6 7 8 9 101112131415161718192021222324252627282930 Bus No
Bus No
60% 70%
1.15 1.15
1.1 1.1
1.05 1.05
1 1
0.95 0.95
0.9 0.9
0.85 0.85
0.8 0.8
0.75 0.75
Voltage (p.u)
0.7
Voltage (p.u)
0.7
0.65 0.65
0.6 0.6
0.55
0.55
0.5
0.5
0.45
0.45
0.4
0.4 0.35
0.35 0.3
0.3 0.25
0.25 0.2
0.2 0.15
0.15 0.1
0.1 0.05
0.05 0
0 1 2 3 4 5 6 7 8 9 101112131415161718192021222324252627282930
1 2 3 4 5 6 7 8 9 101112131415161718192021222324252627282930 Bus No
Bus No
80% 90%
1.15 1.15
1.1 1.1
1.05 1.05
1 1
0.95 0.95
0.9 0.9
0.85 0.85
0.8 0.8
0.75 0.75
Voltage (p.u)
0.7
Voltage (p.u)
0.7
0.65 0.65
0.6 0.6
0.55
0.55
0.5
0.5
0.45
0.45
0.4
0.4 0.35
0.35 0.3
0.3 0.25
0.25 0.2
0.2 0.15
0.15 0.1
0.1 0.05
0.05 0
0 1 2 3 4 5 6 7 8 9 101112131415161718192021222324252627282930
1 2 3 4 5 6 7 8 9 101112131415161718192021222324252627282930 Bus No
Bus No
100% Uncompensated