0% found this document useful (0 votes)
312 views2 pages

DIN 4705 Calculation Stack For Biodrying Boxes

The document contains a draft calculation according to DIN4705 standards for the design of a stack to ventilate 50 biodrying boxes. It details parameters such as the stack height and diameter, flue gas mass flow rate and temperature, duct length and diameter, surface roughness, and calculates values like frictional resistance, acceleration loss, static draft and pressure at various points in the system. The goal is to size the stack and ducting properly to ventilate the biodrying boxes efficiently and overcome flow resistance within the specified design parameters.

Uploaded by

aegean227
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
312 views2 pages

DIN 4705 Calculation Stack For Biodrying Boxes

The document contains a draft calculation according to DIN4705 standards for the design of a stack to ventilate 50 biodrying boxes. It details parameters such as the stack height and diameter, flue gas mass flow rate and temperature, duct length and diameter, surface roughness, and calculates values like frictional resistance, acceleration loss, static draft and pressure at various points in the system. The goal is to size the stack and ducting properly to ventilate the biodrying boxes efficiently and overcome flow resistance within the specified design parameters.

Uploaded by

aegean227
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

DIN 4705 Engelsk udskrift

Draft Calculation according to DIN4705

Project: Stack H=50 biodrying boxes

Stack:
Effective height 45 m

Cross-sectional area Ø 2,2 m 3,801 m2


Cross-sectional area reduction Ø 2,2 m 3,801 m2

Hydraulic diameter 2,2 m

Operation temperature 40 °C 313 °K

Outdoor temperature 25 °C 298 °K

Flue gas mass 165750 m3/h (IN) 190036 m3/h =


52,788 m3/s

Flue gas velocity 13,9 m/s


Outlet velocity (Düse) 13,9 m/s

Density - air ( 101300 N/m2 ) 1,184 kg/m3

Density - flue gas 1,156 kg/m3

Surface roughness 0,0005 m


Roughness value 0,012872

Single resistance 0,8

Flow technical security factor SE = 1

Frictional resistance 29,3 N/m2

Single resistance 89,2 N/m2

Acceleration loss 111,4 N/m2


Acceleration loss, reduction 0,0 N/m2

Static draft -12,6 N/m2


2
Pressure at inlet 217 N/m

Side 1
DIN 4705 Engelsk udskrift

Draft Calculation according to DIN4705

Project: Stack H=50 biodrying boxes

Kanal:
Effective height 0m
Length of flue gas duct 1m

Cross-sectional area Ø 0,8 m 0,503 m2

Hydraulic diameter 0,8 m

Flue gas velocity 105,0 m/s

Surface roughness 0,0005 m


Roughness value 0,019293

Single resistance 1,6

Flow technical security factor SE = 1

Frictional resistance 153,7 N/m2

Single resistance 10198,2 N/m2

Static draft 0,0 N/m2


2
Pressure loss in flue gas duct 10352 N/m