120MVA 132kV Power Transformer Loss Calculation

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 3

Shandong Taikai Transformer Co.

,LTD

120MVA132kVPower Transformer

Loss Calculation

Shandong Taikai Transformer Co., Ltd

May 2021
Shandong Taikai Transformer Co.,LTD

1. Basic parameters

Product 120MVA132kVPower Transformer

Phase Three
The voltage ratio (kV) 132  8  1.25% / 34.5
HV/LV(MVA
Technical MVA 120/120

parameter
Phase connection and displacement Dyn1
Regulating type With OLTC
Impedance UK(%) Uk12=12%
2 Load losses calculation

PK  I H2 RH  I L2 RL  P '

I ……………. Rated currents in A

R……………...Resistance in Ohm (75℃)

P’………… Stray losses in W (According to our sub-program calculation)

PK  I H2 RH  I L2 RL  P '
 3032  3  0.34071  2008.2 2  3  0.006959  29000
 93841  84194  29000
 207035 W
 207 kW

3 No load losses calculation

P0=K P 0 × Pt ×G Fe K P 0 … … … … … … ….. correction factor ( Considering exciting losses )

Pt ......................... coreloss @ 50 Hz , W /kgG Fe ...................... weig ht of core , kg

P0=K P 0 × Pt ×G Fe¿ 1.2× 0.763 × 48337/1000¿ 44.3 kW


Shandong Taikai Transformer Co.,LTD

4 Total losses calculation

P  P0  PK
 44.3  207
 251.3kW