SE101 Module 1
SE101 Module 1
Module
In
SE 101
WPU-QSF-ACAD-82A
82A Rev. 00 (09.15.20)
Module No. 1
WPU-QSF-ACAD-82A
82A Rev. 00 (09.15.20)
Table of Contents
The course is concerned with the Designing of Steel Structures through step-by-step
procedural solutions. The design solutions will be based on the standards and codes of
the National Structural Code of the Philippines (NSCP 2015 Volume I, 7th Edition
Chapter 5), the National Building Code of the Philippines (NBCP), ASEP Steel
Handbook 2004, AISC Design Manual, ASCE 7, 1997 UBC and other relevant codes and
standards that supports the design of the steel structures.
Designing the steel structures means selecting the proper materials from the ASEP Steel
Manual Tables and AISC Steel Manual. By selecting from the tables, the economic
principles of the design will benefit the designer’s clients. The designer (Structural
Engineer by profession) therefore is opting to secure the applications for loads to be
carried by the structures.
The loads to be carried by the structure will define in this course mainly the dead loads,
live load, wind load, and seismic load. These loads will be taken as design criteria to the
design of the steel structures.
The design of steel structures in this course is not focusing only on the building but to
the other vertical structures like water tank support, transmission tower, and other non-
building structures.
The emphasis in this subject is to apply the structural analysis learned from the lower
year. The design principles will elaborate the use of steel materials.
Overview
Learning Outcomes
Pre-test
A. Learning Outcome
B. Time Allotment
C. Discussion
Introduction
Structural design may be defined as a mixture of art and science, combining the
experienced engineer’s intuitive feeling for the behavior of a structure with a sound
knowledge of the principles of statics, dynamics, mechanics of materials, and structural
analysis, to produce a safe, economical structure that will serve its intended purpose.
Until about 1850, structural design was largely an art relying on intuition to determine
the size and arrangement of the structural elements. Early man-made structures
essentially conformed to those which could also be observed in nature, such as beams
and arches. As the principles governing the behavior of structures and structural
materials have become better understood, design procedures have become more
scientific.
PRINCIPLES OF DESIGN
a. Minimum cost
b. Minimum weight
Usually several criteria are involved, each of which may require weighting. Observing
the above possible critera, it may be apparent that setting clearly measurable criteria
(such as weight and cost) for establishing an optimum frequently will be difficult, and
perhaps impossible. In most practical situations the evaluation must be qualitative.
Design Procedure
Steel is one of the most commonly used materials and is manufactured from iron ore
which is first converted to molten pig iron. The impurities are then removed and crefully
controlled proportions of carbon, silicon, manganese, etc., added the amounts
depending on the particular steel being manufactured.
Mild steel is the commonest type of steel and has a low carbon content. It is relatively
strong, cheap to produce and is widely used for the sections shown in Fig. 1.22. It is a
ductile material, is easily welded and because its composition is carefully controlled its
properties are known with reasonable accuracy.
High carbon steels posses greater strength than mild steel but are less ductile
whereas high yield steel is stronger than mild steel but has a similar stiffness. High yield
steel, as well as mild steel, is used for reinforcing bars in concrete construction and very
high strength steel is used for the wires in prestressed concrete beams.
Low carbon steels possessing sufficient ductility to be bent cold are used in the
manufacture of cold-formed sections. In this process unheated thin steel strip passes
through a series of rolls which gradually bend it into the required section contour.
Simple profiles, such as a channel section, may be produced in as few as six stages
whereas more complex sections may require 15 or more. Cold-formed sections are used
as ligthweight roof purlins, stiffeners for the covers and sides of box beams and so on.
Some typical sections are shown in Fig. 1.1.
Other special purpose steels are produced by adding different elements. For example,
chromium is added to produce stainless steel althrough this is too expensive for general
structural use.
Built-up Section
Built-up sections are made up by a fabricator from two or more shapes or plates.
Examples of common built-up sections are shown in Fig. 1.2. Built-up members are
specified by the designer when the desired properties or configuration cannot be
obtained in a single hot-rolled section. Built-up sections can be bolted or welded.
Welded members, in general are less expensive because much less handling is required
in the shop and because of more efficient utilization of material. The clean lines of
welded members are also produce a better appearance.
Cover-Plated Rolled Beams are used when the required bending capacity is not available
in a rolled standard beam or when depth limitations preclude use of a deeper rolled
beam or plate girder. Cover-plated beams are also used in composite construction to
obtain the efficiency of a nonsymmetrical section.
Figure 1.3
W Shapes
American wide-flange I or H-shaped steel beams are referred to as W shapes and are
designated by the letter W followed by their nominal depth in millimeters, with their
mass in kg/m as the last designation.
W 416 x 85 means that this W shape is 416 mm deep and has a mass of 85 kg/m. this
shape consists of two rectangular-shaped flanges connected by a rectangular plate and
symmetrical about the x and y axes.
Typical W shape
d = depth of beam
bf = width of flange
tf = thickness of flange
tw = thickness of web
The AISC units of steel members are express in English System which derived to Metric
and SI System to adapt the present trades.
Just like the problem in Example 1, the W 416 x 85 is derived from English System of
what Steel Section?
Derivation:
The note W is refers to section type and the number 416 refers to the depth of the steel
section in mm, while the last number 85 refers to weight in kilogram/meter:
Flange Web
Designation Theoretical Area Depth
Thickness
mass A d Width bf Thickness tw
(kg/m) (mm2) (mm) (mm) tf (mm) (mm)
W 416 x 85 85 10800 410 181 18.2 10.9
S Shapes
These shapes were formerly called I-beams and American Standard Beams. The
difference between W and S-shapes are.
Example 1.2
S 610 x 134
Deep of beam = 610 mm
Theoretical mass = 134 kg/m
These are doubly symmetrical shapes which are not classified as W or S-shapes. They
are symmetrical both x and y-axes.
Example 1.3
M 356 x 25.6
Deep of beam = 356 mm
Theoretical mass = 25.6 kg/m
Flange Web
Designation Theoretical Area Depth
Width Thickness Thickness
mass (kg/m) (mm2) (mm)
(mm) (mm) (mm)
M 356 x 25.6 25.6 3258 356 101.6 6.9 5.33
These are channel shapes formerly called American Standard Channels. The inner face
of the flange has the same slope as S-shapes.
S
Example 1.4
C 380 x 74
Flange Web
Designation Theoretical Area Depth
Width Thickness Thickness
mass (kg/m) (mm2) (mm)
(mm) (mm) (mm)
C 380 x 74 74.4 9480 381 94 16.5 18.2
MC Shapes
These were formerly called ship building or Miscellaneous Channels and are not
classified as C shapes.
Example 1.5
MC 458 x 86
WPU-QSF-ACAD-82A
82A Rev. 00 (09.15.20)
∟ Shapes
These are either equal or unequal leg angles. All angles have parallel flange faces.
Example 1.6
Example 1.7
WPU-QSF-ACAD-82A
82A Rev. 00 (09.15.20)
WT 300 x 119.3 (Structural Tee or Split Tee)
Structural tees are obtained by splitting W, S or M shapes such that each split section
has one half the area of the original shape. Nominal depth is 300 mm and a mass of
119.3 kg/m obtained by splitting W 600 x 238.6 kg/m
Example 1.8
WT 300 x 119.3
Most typical building construction is in this category. The multistory building usually
consists of beams and columns, either rigidly connected or having simple end
connections along with diagonal bracing to provide stability. Even though a
multistory building is three-dimensional,
three dimensional, it usually is designed to be much sti
stiffer in
one direction than the other; thus it may reasonably be treated as a series of plane
frames. However, if the framing is such that the behavior of the members in one
plane substantially influences the
the behavior in another plane, the frame must be
treated as a three-dimensional
dimensional space frame.
WPU-QSF-ACAD-82A
82A Rev. 00 (09.15.20)
b. Shell-type structures, where axial forces predominate;
Structural steel design of buildings in the United States is principally based on the
specification of the American Institute of Steel Construction (AISC). AISC is composed
of steel fabricator and manufacturing companies, as well as individuals’ interest in steel
design and research. The AISC Specification is the result of the combined judgment of
researchers and practicing engineers. The research efforts have been synthesized into
practical design procedures to provide a safe, economical structure. The advent of the
digital computer in design practice has made feasible more elaborate design rules. The
current specification which is referred throughout this module is the 2015 Volume I, 7th
Edition of the NSCP (National Structural Code of the Philippines) which derived from
the AISC Steel Construction Manual, 15th Edition.
Railroad bridges are designed in accordance with the specifications adopted by the
American Railway Engineering and Maintenance of Way Association (AREMA).
The term building code is sometimes used synonymously with specifications. More
correctly a building code is a broadly based document, either a legal document such as a
state or local building code, or a document widely recognized even though not legal
which covers the same wide range of topics as the state or local building code.
PHILOSOPHIES OF DESIGN
The 2005 AISC Specification for Structural Steel Buildings provides an integrated
treatment of Allowable Strength Design (previously referred to by AISC as the Allowable
Stress Method) and Load and Resistance Factor Design. The new specification combines
the two design methods and replaces earlier specifications that treated the two design
methods separately. Allowable Stress Design has been the principal philosophy used
during the past 100 years. During the past 20 years or so, structural design has been
moving toward a more rational and probability-based design procedure referred to as
“limit states” design. Limit states design includes the methods commonly referred to as
“ultimate strength design,” “strength design,” plastic design,” “load factor design,” limit
design,” and the more recent “load and resistance factor design (LRFD).”
Design must provide some reserve strength needed to carry the service loads, meaning
the structure must provide for the possibility of overload. Overloads can arise from
changing the use for which the particular structure was designed, from
The selected materials (steel members, bolts, and welds) in design may have less
strength used in the design calculations. A steel section may occasionally have a yield
stress below the minimum specified value, but still within the statistically acceptable
limits.
Structural design must provide for adequate safety no matter what philosophy of design
is used. Provision must be made for both overload and strength.
“Limit state” may rather use term for “failure”. Limit states means “those conditions of a
structure at which it ceases to fulfill its intended function”.
Both the loads acting on the structure and its resistance (strength) to loads are variables
that must be considered.
3. It can be used to vary in a rational manner the margins of safety for those
components and systems having a greater or lesser need for safety than that required
in ordinary situations.
In general, the expression for the structural safety requirements may be written as
≤∅ (502.3 − 1)
Where
Ru = required strength (LRFD)
Rn = nominal strength, specified in Sections 502 through 511
ø = resistance factor, specified in Sections 502 through 511
øRn = design strength
The safety requirement of the LRFD Method is given by Equation 1.8.1. This means the
design strength øRn provided by the resulting design must at least equal the sum ∑γiQi
of the applied factored service loads. The subscript i indicates that there are terms for
1.4D (1.8.1)
1.2D+ 1.6L + 0.5(Lr or S or R) (1.8.2)
1.2D + 1.6(Lr or S or R) +(L or 0.5W) (1.8.3)
1.2D + 1.0W + 0.5(Lr or S or R) (1.8.4)
1.2D+ 1.0E + L + 0.2S (1.8.5)
0.9D+1.0W (1.8.6)
0.9D + 1.0E (1.8.7)
Where the nominal service loads indicated by Eqs. 1.8.2 through 1.8.7 are:
D= dead load (gravity load from the weight of structural elements and permanent
attachments)
E = earthquake load
L = live load (gravity occupancy and movable equipment load)
Lr = roof live load
W= wind load
R = rain load or ice load
Where
Ra = required strength (ASD)
Rn = nominal strength, specified in Sections 502 through 511
Ω = safety factor, specified in Sections 502 through 511
Rn/Ω = allowable strength
The “safety factor” Ω used in Eq. 1.8.8 was not determined consciously by using
probabilistic methods. The values used in the AISC ASD Specifications have been in use
for many years and are the result of experience and judgment. It is clear that the safety
required must be a combination of economics and statistics. Obviously, it is not
economically feasible to design a structure so that the probability of failure is zero. Prior
to the development of the 1986 AISC LRFD Specification, the AISC Specifications from
1924 through 1978 did not give a rationale for the allowable stresses prescribed.
One may state that the minimum resistance must exceed the maximum applied load by
some prescribed amount. Suppose the actual load exceeds the service load by an amount
ΔQ, and the actual resistance is less than the computed resistance by an amount ΔR. A
structure that is just adequate would have
− Δ = + ΔQ
(1 − Δ ⁄ ) = (1 + Δ ⁄ )(1.9.1)
The margin of safety, or “safety factor,” would be the ratio of the nominal strength Rn to
nominal service load Q; or
1+Δ ⁄
Ω= = (1.9.2)
1−Δ ⁄
Equation 1.9.2 illustrates the effect of overload (ΔQ/Q) and understrength (ΔRn/Rn);
However it does not identify the factors contributing to either. If one assumes that
occasional overload (ΔQ/Q) may be 40% greater than its normal value, and that an
occasional understrength (ΔRn/Rn) may be 15% less than its nominal value, then
1 + 0.4
Ω= = 1.65
1 − 0.15
The above is an oversimplification but it shows a possible scenario for obtaining the
traditional AISC value of FS = 1.67 used as the basic value in Allowable Stress Design.
The factor for overload are variable depending upon the type of load, and the factored
load combinations that must be considered are those given by the ASCE 7 Standard and
presented as Eqs. 1.8.1 through 1.8.7. The other part of the safety-related provisions is
the ø factor, known as the resistance factor. The resistance factor ø varies with the type
of member and with the limit state being considered. Some representative resistance
factors ø are as follows.
( ⁄ ) ≈ + (1.9.3)
Where
= ⁄
= ⁄
The distance representing the margin of safety may be approximated as
( ⁄ ) ≈ + = ln( ⁄ )(1.9.4)
Thus, the larger the distance the smaller the probability of reaching the limit state. The
multiplier β is called the reliability index. The expression for βfro Eq. 1.9.4 becomes
ln( ⁄ )
= (1.9.5)
+
Using the factored load combinations given by the ASCE 7 Standard, the AISC Task
Force and Specification Committee calibrated the 1986 LRFD Specification based on
Because of a lower probability of wind or earthquake occurring with full gravity load, the
reliability index β was made lower for those cases. The β values for connections stronger
than members.
ASCE 7-10 uses seven factored load combinations, given as Eqs. 1.8.1 through 1.8.7. This
was necessary to account for each of the separate loads (dead, live, roof, wind additive to
gravity, wind opposite to gravity, and earthquake) acting at its maximum lifetime value.
Loads other than dead load and the load being maximized will act at an “arbitrary point-
in-time” value.
Each factored load combination and its corresponding load occurring at its 50-year
maximum are as follows:
The original LRFD Specification values were calibrated to the 1978 ASD Specification at
a live load to dead load ratio of 3. To determine the relationship between ø and Ω, the
nominal strengths from ASD and LFRD are equated. Using the live load and dead load
combinations, with L = 3D, the required nominal strength can be expressed as follows:
From ASD: = + = +3 =4
Ω
=4 Ω
From LRFD: = 1.2 + 1.6 = 1.2 + 1.6 3 =6
6 1 1.5
Equating and solving for Ω: Ω= =
4
Therefore, for ø = 0.9, the value Ω = 1.67 and for ø = 0.75, Ω = 2.00
D. Activity / Exercise
1. Provide a photograph or picture of at least three types of steel structures for both
horizontal and vertical structures and even non-building type steel structure that this
course is applied for. Verify what these structures are.
E. Evaluation / Post-test
3. What the theoretical weight of angle ∟100 x 100 x 12 in kg? Consider a 1-meter
length.
B. Time Allotment
C. Discussion
Combination of Loads
Buildings, towers and other vertical structures and all portions thereof shall be designed
to resist the load combinations specified in Section 203.3, 203.4 and 203.5
The most critical effect can occur when one or more of the contributing loads are not
acting. All applicable loads shall be considered, including both earthquake and wind, in
accordance with the specified load combinations.
Where strength design or load and resistance factor design is used, structures and all
portions thereof shall resist the most critical effects from the following combinations of
factored loads:
1.4 (D + F) (203-1)
1.2(D + F + T) + 1.6(L + H) + 0.5(Lr or R) (203-2)
1.2D + 1.6(Lr or R) + (f1L or 0.5W) (203-3)
1.2D + 1.0W + f1L + 0.5(Lr or R) (203-4)
1.2D + 1.0E + f1L (203-5)
0.9D + 1.0W + 1.6H (203-6)
0.9D + 1.0E + 1.6H (203-7)
Where
f1 = 1.0 for floors in places of public assembly, for live load in excess of 4.8 kPa,
and for garage live load, or
= 0.5 for other live loads
Other loads
Where allowable stress or allowable strength design is used, structures and all portion
thereof shall resist the most critical effects resulting from the following combinations of
loads:
D+F (203-8)
D+H+F+L+T (203-9)
D + H + F + (Lr or R) (203-10)
No increase in allowable stresses shall be used with these load combinations except as
specifically permitted by Alternate Basic Load Combinations.
In lieu of the basic load combinations specified in Basic Load Combinations, structures
and portion thereof shall be permitted to be designed for the most critical effects
resulting from the following load combinations. When using theses alternate basic load
combinations, a one-third increase shall be permitted in allowable stresses for all
combinations, including W or E.
Exception:
Crane hook loads need not be combined with roof live load or with more than one-half
of the wind load.
Example 2.1
The interior floor system shown in Figure 2.1 has W24 x 55 sections spaced 2.5 m on
center and is supporting a floor dead load of 2.4 kPa and a live load of 3.83 kPa.
Determine the governing load in N/m that each beam must support.
Solution.
Note that each meter of the beam must support itself (a dead load) plus 2.5 x 1 = 2.5 m2
of the building floor.
Computing factored loads, using the LRFD load combinations. In this substitutions, the
terms having no values are omitted. Note that with a floor live load of 3.83 kPa a load
factor of 0.5 has been added to load combinations (3), (4), and (5) per the exception
stated in NSCP 2015 and this text for floor live loads.
1. Wu = 1.4 (6802.95) = 9524.13 N/m
2. Wu = 1.2(6802.95) + 1.6(9575) = 23483.5 N/m
3. Wu = 1.2(6802.95) + 0.5(9575) = 12951 N/m
4. Wu = 1.2(6802.95) + 0.5(9575) = 12951 N/m
5. Wu = 1.2(6802.95) + 0.5(9575) = 12951 N/m
6. Wu = 0.9(6802.95) = 6122.65 N/m
7. Wu = 0.9(6802.95) = 6122.65 N/m
Dead loads consist of the weight of all materials of construction incorporated into the
building or other structures, including but not limited to walls, floors, roofs, ceilings,
stairways, built-in partitions, finishes, cladding and other similarly incorporated
architectural and structural items, and fixed service equipment, including the weight of
the cranes.
The actual weights of materials and constructions shall be used in determining dead
loads for purposes of design. In the absence of definite information, it shall be permitted
to use the minimum values in Table 204-1 and 204-2 of NSCP 2015 Section 204.
Floors in office buildings and other buildings where partition locations are subject to
change shall be designed to support, in addition to all other loads, a uniformly
distributed dead load equal to 1.0 kPa.
Exception:
Access floor systems shall be designed to support, in addition to all other loads, a
uniformly distributed dead load not than 0.5 kPa.
Example 2.2
The floor beam in Figure 2.0 is used to support the 1.83 m width of a lightweight plain
concrete slab having a thickness of 102 mm. The slab serves as a portion of the ceiling
for the floor below, and therefore its bottom is coated with plaster.
Solution
Figure 2.2
The floor system of a building consists of a 125 mm thick reinforced concrete slab
resting on four steel floor beams, which in turn are supported by two steel girders, as
shown in Fig. 2.1. The cross-sectional areas of the floor beams and the girders are 9484
mm2 and 33419 mm2, respectively. Determine the dead loads acting on the beams CG
and DH and the girder AD.
Solution:
Refer to Table 204-1 for density of concrete materials to be carried by the floor beam.
The girder EH which is symmetrical with the girder AD will carry the same loadings.
The Figures (b), (c), and (d) below shows the beam loading as result of the dead loads
carried by the beam itself.
Table 204-1 Minimum Densities for Design Loads from Materials (kN/m3)
Material Density Material Density
Aluminum 26.7 Iron:
Bituminous products: Cast 70.7
Asphaltum 12.7 Wrought 75.4
Graphite 21.2 Lead 111.5
Paraffin 8.8 Lime:
Petroleum, crude 8.6 Hydrated, loose 5.0
Petroleum, refined 7.9 Hydrated, compacted 7.1
Petroleum, benzene 7.2 Masonry, Ashlar Stone:
Petroleum, gasoline 6.6 Granite 25.9
Pitch 10.8 Limestone, crystalline 25.9
Tar 11.8 Limestone, oolitic 21.2
Brass 82.6 Marble 27.2
Bronze 86.7 Sandstone 22.6
Cast-stone masonry (cement, stone, sand) 22.6 Masonry, Brick:
Cement, portland, loose 14.1 Hard, low absorption 20.4
Ceramic tile 23.6 Medium, medium absorption 18.1
Charcoal 1.9 Soft, high absorption 15.7
Cinder fill 9.0 Masonry, Concrete (solid portion):
Cinders, dry, in bulk 7.1 Lightweight units 16.5
Coal: Medium, weight units 19.6
Anthracite, piled 8.2 Normal, weight units 21.2
Bituminous, piled 7.4 Masonry grout 22.0
Lignite, piled 7.4 Masonry, Rubble Stone:
Peat, dry, piled 3.6 Granite 24.0
Concrete, plain: Limestone, crystalline 23.1
Tributary Area
In order to determine the dead load applied to a structural member, use is made of the
tributary area concept. As shown in Fig. 2.1, the second floor slab is supported on beams
which, in turn, are supported on either girders or columns. The girders carry the dead
load to columns that transfer the total load to the foundations. It may be assumed that
all beams have the same section with a weight of wB lb/ft and all girders have the same
section with a weight of wG lb/ft.
Slab Supports
Each slab panel is supported on its periphery by either a beam or a girder. For the
situation shown, the aspect ratio of a panel exceeds two, and the slab resists moments in
the direction of the shorter span between beams essentially as a one-way slab. Beams
are supported at each end by either a girder or a column. A further assumption is made
that beams are simply supported at each end. Then the tributary area of a beam is
defined as the area of the slab that is directly supported by the beam.
For a typical interior beam 25, the tributary area is the shaded area abcd, shown in
Fig. 2.1, which extends over its full length y and a distance of x/2 on either side. The
tributary area is
For a slab with a weight of q lb/ft2 and a beam with a self-weight of wB kN/m, the
uniformly distributed dead load on beam 25 is
= + = +
= + = ( )+ = ( + )
= ( + )⁄2 =
= + = ( + ⁄2) +
= + = [ ( + ⁄2) + ]
= + = ⁄2 +
= + = ( ⁄2 + )
= ( ⁄2 + )⁄2 =
The second floor layout of an office facility is shown in Fig. 2.4 and a detail of the floor
construction and of a typical interior beam is shown in Fig. 2.6. Dimension x = 3 m and
y = 9 m. The floor consists of composite steel-concrete construction with a 75-mm
concrete fill over a 75-mm high-formed steel deck. The lightweight concrete fill has a
weight of 17.4 kN/m3 and the formed steel deck is of 20 gage material. A 25 mm terrazzo
finish, and a suspended acoustic ceiling are provided. All beams are W14 × 22 and ribs
of the steel deck are perpendicular to the beams. Determine the dead load acting on a
typical interior beam 25.
The steel deck thickness of 20 gage is selected to support the concrete fill over a span of
3 m without requiring propping during construction. From the manufacturer’s
catalogue, the weight of the steel deck is obtained as 95.76 N/m2 and the weight of the
lightweight concrete fill as 1.964 kN/m2.
W14 x 22 = 22 lb/ft x 4.448 N/lb x 3.281 ft/m = 321.07 N/m ≈ 321 N/m
= = 3 9 = 27
(2969.7 x 27 + 321 x 9 )
= + = = .
1000
= ⁄2 = 83.07⁄2 = . =
As shown in Fig. 2.7, the tributary area of a typical interior girder 56 is the shaded area
efgh. The girder supports its own weight wG and also the end reactions of the beams
framing into each side of the girder. Girders are supported at each end by a column.
Since all beams are identical, the concentrated loads acting on the girder at third
points of the span are
= ( + )+3 ⁄2 =
The tributary area of girder 78 is shown shaded in Fig. 2.7. This is an edge girder
and beams frame into only one side of the girder. Since all beams are identical, the
concentrated loads acting on the girder at third points of the span are
= ( + )⁄2
The second floor layout of an office facility is shown in Fig. 2.1 and a detail of the floor
construction and of a typical girder 56 is shown in Fig. 2.9. Dimension x = 3m and y = 9
m. The floor consists of composite steel-concrete construction with a 75-mm concrete
fill over a 75-mm high-formed steel deck. The lightweight concrete fill has a weight of
17.4 kN/m3 and the formed steel deck is of 20 gage material. A 25 mm terrazzo finish,
and a suspended acoustic ceiling are provided. All beams are W14 × 22. All girders are
W18 × 40 and ribs of the steel deck are parallel to the girders. Determine the dead load
acting on a typical girder 56.
= 2969.7 N⁄m
Since all beams are identical, the concentrated loads acting on the girder at third points
of the span are
2 =2 41.535 = 83.07 kN
0.584 x 9
= 83.07 kN + = 85.70 kN =
2
As shown in Fig. 2.11, the tributary area of column 5 is the shaded area ijkl. Framing into
the column are beams 52 and 58 and girders 54 and 56, and the column supports the
end reactions from these members.
Hence, the total dead load applied to column 5 at the second floor is
= + + +
= ( + )⁄2
= ( + )⁄2
= ( + )+3 ⁄2
= ( + )+3 ⁄2
Alternatively, the weight of the beams and girders may be included in the distributed
floor load, since all beams are identical and all girders are identical. Thus, the total
distributed load on the floor is
= + ⁄ + ⁄
The dead load applied to column 5 at the second floor is, then
= (3 )
The tributary area of column 4 is the shaded area lmni shown in Fig. 2.11. This is a
side column that supports a cantilevered slab, and has beams framing into two sides
and a girder framing into only one side. Framing into the column are beams 41 and 47
and girder 45, and the column supports the end reactions from these members. Hence,
the total dead load applied to column 4 at the second floor is
= + +
= ( + )+3 ⁄2
Because of the cantilevered slab, the alternative method of calculating the column load
using the tributary area AT and the total distributed load qd does not apply.
The tributary area of column 9 is the shaded area opqk in Fig. 2.11. This is a corner
column that has a beam framing into only one side and a girder framing into only one
side. Framing into the column is beam 96 and girder 98, and the column supports the
end reactions from these members. Hence, the total dead load applied to column 9 at
the second floor is
= +
= ( ⁄2 + )/2
= ( + )/2 + 3 ⁄2
The floor layout of an office facility is shown in Fig. 2.4 and a detail of the column
framing is shown in Fig. 2.12. Dimension x = 3 m and y = 9 m. The floor consists of
= + + +
= = 41.535 kN = V
= 85.70 kN = V
= + ⁄ + ⁄
321 584 .
= 2969.70 + + 1000 = 3.142 kN⁄m
3 9
The area tributary to column 5 is
=3 =3 3 9 = 81 m
= 3.142 x 81 = .
Two-Way Slabs
When the aspect ratio of a slab is not more than two, the slab resists moments
essentially as a two-way slab. The tributary areas for the supporting beams are bounded
by 45° lines drawn from the corners of the panels and by the center lines of the panels
parallel to the long sides. A plan view of floor framing is shown in Fig. 2.13 with beams
⁄ =2
For a typical interior beam spanning east-west, the tributary area is the trapezoidal area
abcdef shown shaded in Fig. 2.13. The dead load acting on the beam is shown in Fig.
2.14, where q is uniformly distributed weight of the floor and y is 2x.
The dead load reaction at each end of the beam, including its own weight wB, is
= 0.75 +
For a typical interior girder spanning north-south, the tributary area is the double
triangular area ghij plus the area iklm shown shaded in Fig. 2.13. The dead load acting
on the girder is shown in Fig. 2.15.
The dead load reaction at each end of the girder, including its own weight wG, is
= 0.5 + +
Live loads shall be the maximum loads expected by the intended use or occupancy but in
no case shall be less than the loads required in the Section 205 of NSCP 2015. As
required by the code, a movable partition
These loads are composed of floor live loads, roof load, concentrated loads, and special
loads. Table 205-1 shows the minimum uniform and concentrated live loads and Table
205-2 for special loads.
Partial loading or “checkerboard” loading conditions that produce more critical loading
on a member must also be considered. A continuous beam with two partial loading
conditions is shown in Fig. 2.13. In loading condition 1, alternate spans are loaded. This
Influence Area
In the case of floor loads, the concept of influence area AI is introduced. Influence area
is defined in NSCP 2015 Section 205.6. The reduced live load shall not be less than 50%
of the unit live load Lo for members receiving load from one level only, nor less than
40% of the unit live load Lo for other members.
= ⁄
As shown in Fig. 2.14, the influence area for a typical interior beam 25 is the shaded area
abcd and the live load element factor is
= ⁄
=2 /
=2
The influence area for an edge girder 78 is the shaded area efgh, and the live load
element factor is
= ⁄
= 3 /1.5
=2
Where uniform floor loads are involved, consideration may be limited to full dead load
on all spans in combination with full live load on adjacent spans and alternate spans.
Concentrated Loads
Floors shall be designed to support safely the uniformly distributed live loads prescribed
in herein or the concentrated load given in Table 205-1 whichever produces the greatest
load effects. Unless otherwise specified the indicated concentration shall be assumed to
be uniformly distributed over an area 750-mm square and shall be located so as to
produce the maximum load effects in the structural member.
Provision shall be made in areas where vehicles are used or stored for concentrated
loads, L, consisting of two or more loads spaced 1.5 m nominally on center without
uniform live loads. Each load shall be 40 percent of the gross weight of the maximum
size vehicle to be accommodated. Parking garages for the storage of private or pleasure-
type motor vehicles with no repair or refueling shall have a floor system designed for a
concentrated load of not less than 9 kN acting on an area of 0.015 m2 without uniform
live loads. The condition of concentrated or uniform live load, combined in accordance
with Section 203.3 or 203.4 as appropriate, producing the greatest stresses shall govern.
Provision of special loads shall be made for the special vertical and lateral load as set
forth in Table 205-2 of NSCP 2015 Section 205.
footboards
9A horizontal load applied at right angles to the vehicle barrier at a height of 450 mm above
the parking surface. The force may be distributed over a 300-mm square.
10The mounting of handrails shall be such that the completed handrail and supporting
structure are capable of withstanding a load of at least 890 N applied in any direction at any
point on the rail. Theses loads shall not be assumed to act cumulatively with the Note 9.
Floors shall be designed for the unit live loads as set forth in Table 205-1 and Table 205-
3, Method 2 for reduction factor. These loads shall be taken as the minimum live loads
of horizontal projection to be used in the design of buildings for the occupancies listed,
and loads at least equal shall be assumed for uses.
Where it can be determined in designing floors that the actual live load will be greater
than the value shown in Table 205-1, the actual live load shall be used in the design of
such buildings or portions thereof. Special provisions shall be made for machine and
apparatus loads.
It is unlikely that all floors in a multistory building will be subjected to the full design
live load simultaneously. Similarly, a large floor area is unlikely to be subjected to as
high a loading intensity as a smaller area. For floors in places of public assembly and for
live loads greater than 4.8 kPa, in accordance with the following equation:
= ( − ) (205 − 1)
Where
A = area of floor or roof supported by the member, m2
D = dead load per square meter of area supported by the member, kPa
r = rate of reduction equal to 0.08 for floors. See Table 205-3 for roofs
The reduction shall not exceed 40% for members receiving load from one level only,
60% for other members or R, as determined by the following equation:
= . ( + ⁄ ) (205 − 2)
For storage loads exceeding 4.8 kPa, no reduction shall be made, except that design live
loads on columns may be reduced 20 percent.
The live load reduction shall not exceed 40 percent in garages for the storage of private
pleasure cars having a capacity of not more than nine passengers per vehicle.
As an alternate to Equation 205-1, the unit live loads set forth in Table 205-1 may be
reduced in accordance with Equation 205-3 on any member, including flat slabs, having
an influence area of 40 m2 or more.
= . + . (205 − 3)
AI = influence area, m2
L = reduced design live load per square meter of area supported by the member
Lo = unreduced design live load per square meter of area supported by the member
(Table 205-1)
The influence area AI is 4x the tributary area (AT) for a column, 2x the tributary area
(AT) for a beam, equal to the panel area for a two-way slab, and equal to the product of
the span and the full flange width for a precast T-beam.
The unit live load shall not be less than 50% of the unit live load Lo for members
receiving load from one level only, not less than 40% of the unit live load Lo for other
members.
The second floor layout of an office facility is shown in Fig. 2.1 and a detail of the floor
construction and of a typical interior beam is shown in Fig. 2.3. Dimension x = 3 m and
y = 9 m. Determine the live load acting on a typical interior beam 25. From NSCP Table
503-1, the unreduced live load is
= 2.4 kN⁄m
= 3 9 = 27
From NSCP 2015 Section 205.6, the influence area for beams is 2 times the tributary
area,
=2 =2 27 = 54 m > 40
= . + . (205 − 3)
= . . + . = . ⁄ > 0.5
√
Hence, the minimum permitted value for a member supporting only one floor of L =
0.5Lo is not applicable.
In accordance with NSCP 2015 Section 204.3, an additional 1.0 kPa must be added to
allow for weight of movable partitions. Hence the total live load intensity is
= 2.093 + 1.0 = . ⁄
= = 3.093 27 = .
The floor layout of a four-story office facility is shown in Fig. 2.8. Dimension x = 3 m
and y = 9 m. Determine the floor live load produced on a typical interior column 5 at
each story.
From NSCP Table 503-1, the unreduced live load for office building is
= 2.4 kN⁄m
From NSCP 2015 Section 205.6, the influence area for a column is 4 times the tributary
area,
=3
=4
The design live load on the column, in each storey, must account for the tributary floor
area by that story.
Third storey
The column supports the floor live from the 4th floor.
=3 = (3)(3)(9) = 81 m > 40
=4 = (4)(81) = 324 m > 40
= . + . (205 − 3)
= . . + . = . ⁄ > 0.5
√
The minimum L = 0.5Lo does not govern
In accordance with NSCP 2015 Section 204.3, an additional 1.0 kPa must be added to
allow for weight of movable partitions. Hence the total live load intensity is
= 1.209 + 1.0 = . ⁄
= = 2.209 81 = .
Second storey
The column supports the floor live from the 3rd and 4th floor.
=3 = (3)(3)(9) = 81 m > 40
= . + . (205 − 3)
= . . + . = . ⁄ > 0.4
√
The minimum L = 0.4Lo does not govern
= 1.031 + 1.0 = . ⁄
= = 2.031 81 = .
Bottom storey
The column supports the floor live from the 2nd, 3rd, and 4th floor.
= 3 = (3)(3)(9) = 81 m > 40
= (4 )( )(2) = (4)(81)(3) = 648 m > 40
= . + . (205 − 3)
Hence, use the minimum permitted value for a column supporting three floors of
In accordance with NSCP 2015 Section 204.3, an additional 1.0 kPa must be added to
allow for weight of movable partitions. Hence the total live load intensity is
= 0.96 + 1.0 = . ⁄
= = 1.96 3 81 = .
Roofs shall be designed for the unit live loads, Lr, set forth in Table 205-3. The live loads
shall be assumed to act vertically upon the area projected on a horizontal plane.
Provision of roof live loads shall be made by Method 1 or Method 2 under Section 205.4
of NSCP 2015.
The live loads shall be assumed to act vertically upon the area projected on a horizontal
plane.
Roof live loads account for loads imposed during construction of the roof and
subsequently by maintenance and re-roofing operations. Roof loads are assumed to act
on the horizontal projection of the roof surface. The design roof live load shall
determine by the following equation:
= ( − ) (205 − 15)
The reduction shall not exceed 40 percent for members receiving load from one level
only, 60 percent for other members or R, as determined by the following equation:
= . ( + ⁄ ) (205 − 2)
The roof framing layout of an office facility is similar to the second floor layout shown in
Fig. 2.1. Dimension x = 3 m and y = 9 m and the roof is nominally flat. Determine the
live load acting on a typical interior roof beam 25.
The roof framing layout of an office facility is similar to the second floor layout shown in
Fig. 2.1. Dimension x = 3 m and y = 9 m and the roof is nominally flat. Determine the
roof live load acting on a typical interior column 5.
R = 0.6
In the design of an element, nominal dead loads and live loads must be combined in
accordance with the LRFD or ASD requirements. The following example is an
illustration.
The roof framing layout of a four-story office facility is similar to the floor layout shown
in Fig. 2.1. Dimension x = 3 m and y = 9 m and the roof is nominally flat. The dead load
of the roof, including the weight of framing members is 2.92 kN/m2. The column weight
is 1.022 kN/m in all stories and the height of each story is 3.6 ft. Determine the total
dead load, floor live load, and roof live load acting on a typical interior column 5 and the
design load on the column footing.
= ℎ
= (1.022 kN/m)(3.6 m) (4) = .
= + +3
= 236.52 + 14.72 + 3(254.50)
= .
LRFD ASD
From NSCP 2015 Sec. 203.3.1 combination 3: From NSCP 2015 Sec. 203.4.1 combination 4:
= 1.2 + 1.6 + 0.5 = + 0.75 + 0.75
= 1.2(1014.74) + 1.6(48.9) + 0.5(476.28) = 1014.74 + 0.75(48.9) + 0.75(476.28)
= 1534.068 kN = 1408.625 kN
From NSCP 2015 Sec. 203.3.1 combination 2: From ASCE 7 Sec. 2.4.1 combination 2:
= 1.2 + 1.6 + 0.5 = +
= 1.2(1014.74) + 1.6(476.28) + 0.5(48.9) = 1014.74 + 476.28
= . . . . governs = . … . governs
= required strength = required strength
Combination of Loads
Example 2.10
A roof system with W16 x 40 sections spaced 2.7 m on center is to be used to support a
dead load of 1.92 kPa; a roof live load of 1.44 kPa; and wind load of ±1.54 kPa. Compute
the governing load in per linear meter.
Solution.
W16 x 40, the last number 40 is referring to section weight of 40 lb/ft. Here, we have to
convert the 40 lb/ft to N/m which calculated to 40 lb/ft multiply by 14.59318 N/m =
583.73 N/m.
Compute the factored loads, using the LRFD load combinations. In these substitutions,
the terms having no values are omitted. Note that with a floor live load of 3.83 kPa, a
load factor of 0.5 has been added to load combinations (3), (4), and (5) per the
exception stated in NSCP 2015 and this text for floor live loads.
1. Wu = 1.4 (5767.73) = 8074.82 N/m
2. Wu = 1.2(5767.73) + 0.5(3888) = 8865.28 N/m
3. Wu = 1.2(5767.73) + 1.6(3888) + 0.5(11226.6) = 18755.38 N/m
4. Wu = 1.2(5767.73) + 1.0(11226.6) + 0.5(3888) = 20091.88 N/m
5. Wu = 1.2(5767.73) = 6921.28 N/m
6. Wu = 0.9(5767.73) + 1.0(11226.6) = 16417.56 N/m
7. Wu = 0.9(5767.73) = 5190.96 N/m
Example 2.11
The various axial loads for a building column have been computed according to the
applicable building code, with the following results: dead load = 96 kN; load from roof =
2.4 kN (roof live load); live load from floors (reduced ass applicable for large floor area
and multistory columns) = 12 kN; compression wind = 6.144 kN; tensile wind = 4.992 k;
compression earthquake = 2.88 kN; and tensile earthquake = 3.36 kN.
Determine the critical design column load, Pu, using the LRFD load combinations.
Solution.
This problem solution assumes the column floor live load meets the exception for the
use of the load factor of 0.5 in load combinations (3.), (4.), and (5.).
1. Pu = (1.4)(9.6) = 13.44 kN
2. Pu = (1.2)(9.6) + 1.6(12) + (0.5)(2.4) = 31.92 kN
3. (a) Pu = (1.2)(9.6) + 1.6(2.4) + (0.5)(12) = 21.36 kN
(b) Pu = (1.2)(9.6) + (1.6)(2.4) + (0.5)(6.144) = 18.432 kN
4. (a) Pu = (1.2)(9.6) + (1.0)(6.144) + (0.5)(12) + (0.5)(2.4) = 24.144 kN
(b) Pu = (1.2)(9.6) – (1.0)(4.992) + (0.5)(12) +(0.5)(2.4) = 13.728 kN
5. (a) Pu = (1.2)(9.6) + (1.0)(2.88) + (0.5)(12) = 21.4 kN
(b) Pu = (1.2)(9.6) – (1.0)(3.36) + (0.5)(12) = 14.16 kN
6. (a) Pu = (0.9)(9.6) + (1.0)(6.144) = 14.784 kN
(b) Pu = (0.9)(9.6) – (1.0)(4.992) = 3.648 kN
The critical factored load combination, or design strength, required for this column
is 31.92 kN, as determined by load combination (2). It will be noted that the results
of combination (6a) and (6b) do not indicate an uplift problem.
Roofs to be used for special purposes shall be designed for appropriate loads as
approved by the building official. Greenhouse roof bars, purlins and rafters shall be
designed to carry a 0.45 kN concentrated load, Lr, in addition to the uniform live load.
In addition to the other design loads, structures shall be designed to resist the other
minimum loads and the special loads set forth in Table 205-2 of NSCP 2015. Wind loads
and Seismic loads are other loads to be part of the loads to be carried by the structure
and it will be tackled also in this course.
Buildings and other structures and portions thereof shall be designed to resist all loads
due to applicable fluid pressures, F, lateral soil pressures, H, ponding loads, P, and self-
straining forces, T.
Impact Loads
The live loads specified in Sections 205.3 shall be assumed to include allowance for
ordinary impact conditions. Provisions shall be made in the structural design for uses
and loads that involve unusual vibration and impact forces. See Section 206.9.3 for
impact loads for cranes, and Section 206.10 for heliport and helistop landing areas.
Elevators
Machinery
For the purpose of design, the weight of machinery and moving loads shall be increased
as follows to allow for impact:
Crane Loads
The crane load shall be the rated capacity of the crane. Design loads for the runway
beams, including connections and support brackets of moving wheel loads of the crane
and the vertical impact, lateral, and longitudinal forces induced by the moving crane.
The maximum wheel loads shall be the wheel loads produced by the weight of the
bridge, as applicable, plus the sum of the rated capacity and the weight of the trolley
with the trolley positioned on its runway where the resulting load effect is maximum.
The maximum wheel loads of the crane shall be increased by the percentages shown
below to determine the induced vertical impact or vibration force:
D. Activity / Exercise:
1. The office building is made of steel framing system and is carrying the following live
load of 2.4 kPa and materials weight at every floor as follows:
Reinforced concrete floor = 23.6 kN/m3
Floor finishes ceramic tile on 25 mm mortar fill = 1.10 kPa
Steel decking of ga. 20 = 0.12 kPa
Suspended steel channel system (ceiling) = 0.10 kPa
Mechanical duct allowance = 0.20 kPa
Acoustical fiber board = 0.05 kPa
a. Determine the unit live load on beam B-2
b. Determine the unit dead load on beam B-2
c. Determine the live load on column at B-1
d. Determine the dead load on column at B-1
2. Compute the unit loads of the roof systems having 3.0 m spans of beam W16 x 50
using LRFD load combinations:
a. Dead load, wu = 2.26 kPa
b. Live load, roof = 1.98 kPa
c. Wind load = ± 1.32 kPa
d. Draw the loading diagram in both LRFD and ASD.
3. From the given loads in problem 1, calculate the load in LRFD and ASD using the
following loads combinations to apply at steel column:
a. 1.4 (D + F) (203-1)
b. 1.2(D + F + T) + 1.6(L + H) + 0.5(Lr or R) (203-2)
c. 1.2D + 1.6(Lr or R) + (f1L or 0.5W) (203-3)
d. 1.2D + 1.0W + f1L + 0.5(Lr or R) (203-4)
e. 1.2D + 1.0E + f1L (203-5)
f. 0.9D + 1.0W + 1.6H (203-6)
LATERAL LOADS
A. Learning Outcome
After completing this lesson, the student will:
1. Learn to calculate the wind loads acting to the structure
2. Learn to calculate the earthquake/seismic loads acting to the structure
3. Learn to calculate the rain load applied to the building
B. Time Allotment
C. Discussion
Introduction
The National Structural Code of the Philippines by reference adopts the American
Society of Civil Engineers/Structural Engineers Institute (ASCE/SEI 7-10) the Minimum
Design Loads for Building and Other Structures.
Basic Components
The basic function of a lateral force-resisting system is to transfer the lateral forces
acting on the structure to the foundation. Vertical and horizontal resisting components
are used to provide a continuous and competent load path from the top of the structure
to the foundation.
For the single-story, light-framed steel structure shown in Fig. 3.1, the steel roof deck
forms the horizontal resisting component or diaphragm.6 The lateral wind or seismic
force acting on the south wall of the structure delivers a line load of w (in units of N/m)
to the roof diaphragm. The diaphragm acts as a deep beam with end reactions of
=
2
These reactions produce a maximum unit shear at the ends of the diaphragm of
= =
2
The edges of the diaphragm normal to the direction of the lateral force are known as
chords and act in a manner similar to the flanges of a steel beam to resist the bending
moment produced by the lateral force. As shown in Figure 3.1, one chord is in tension
and the other in compression. The force in a chord is given by the equation
The diaphragm shear force is transferred by the collector elements, or drag struts, to the
vertical resisting components. In Fig. 3.1, these are the bracing elements in the end
walls. The bracing elements transfer the lateral force to the structure’s foundation.
Buildings and other vertical structures shall be designed and constructed to resist wind
loads as specified and presented in Section 207A through 207F of the NSCP 2015.
Another lateral loads is the earthquake loads or seismic loads that the buildings and
other vertical structures are subject to resist and will presented as per Section 208 of the
NSCP 2015. The purpose of the succeeding earthquake provisions is primarily to design
seismic-resistant structures to safeguard against major structural damage that may lead
to loss of life and property. These provisions are not intended to assure zero-damage to
structures nor maintain their functionality after a severe earthquake.
When the code-prescribed wind design produces greater effects, the wind design shall
govern, but detailing requirements and limitations prescribed in Earthquake Load
section and referenced sections of the NSCP 2015 shall be made to govern.
Wind Load
When wind strikes an enclosed building the wind flows around the sides and over the
roof and either a pressure or suction is produced on the external surfaces of the
building. As shown in Fig. 3.2, the windward wall that is perpendicular to the wind
direction experiences an inward, positive pressure. As wind flows round the corners of
the windward wall, the turbulence produced separates the air flow from the walls and
causes an outward, negative pressure or suction on the side walls and the leeward wall.
As wind flows over a high-sloping gable roof, a positive pressure is produced on the
windward side of the ridge and suction on the leeward side of the ridge. However, for
gable roofs with shallow slopes, suction also develops on the windward side of the ridge
and for flat roofs; suction develops over the whole roof.
• The directional procedure determines the wind loads on buildings for specific wind
directions, in which the external pressure coefficients are based on wind tunnel
testing of prototypical building models for the corresponding direction of wind.
• The envelope procedure determines the wind load cases on buildings, in which
pseudo external pressure coefficients are derived from wind tunnel testing of
prototypical building models successively rotated through 360°, such that the
pseudo pressure cases produce key structural actions (uplift, horizontal shear,
bending moments, etc.) that envelope their maximum values among all possible
wind directions.
Exposure category accounts for the effect of terrain roughness on wind speed and is
defined and illustrated in NSCP 2015 Section 207A.7. The exposure category is
dependent on surface roughness category and the upwind fetch distance. The exposure
category assigned to each surface roughness category is listed in Table 1. Buildings and
other structures, including the Main Wind-Force Resisting System (MWFRS) and all
components and cladding (C&C) thereof, shall be designed and constructed to resist the
wind loads determined in accordance with Section 207A through 207F. The provisions
of section 207 define the basic wind parameters for use with other provisions contained
in the NSCP 2015 code.
Surface Roughness B: Urban or suburban areas, wooded areas, or other terrain with
numerous closely spaced obstruction having the size of single-family dwellings or larger.
Surface Roughness D: Flat, unobstructed areas and water surfaces. This category
includes smooth mud flats, salt flats, and unbroken ice.
The basic wind speed, V, used in the determination of design wind loads on buildings
and other structures shall be determined from Figure 207.5-1 as follows, except as
provided in NSCP 2015 Section 207A.5.2 and 207A.5.3.
The wind shall be assumed to come from any horizontal direction. The basic wind speed
shall be increased where records or experience indicate that the wind speeds are higher
than those reflected in Figure 207A.5-1A through 207A.5-1C.
Figure 207A.5-1A Occupancy Category III, IV and V buildings and other structures
Figure 207A.5-1C Basic Wind Speeds for Occupancy Category I buildings and other
structures
Applying the analytical method to low-rise buildings, requires the use of specific velocity
pressure exposure coefficients.
Regular Building
A regular building is defined in NSCP 2015 Section 207A.2 as a building having no
unusual geometrical irregularity in spatial form.
Table 207B.3-1
Velocity Pressure Exposure Coefficients, Kh and Kz
Main Wind Force Resisting System – Part 1
Height above ground level, z Exposure
(m) B C D
0-4.5 0.57 0.85 1.03
6.0 0.62 0.9 1.08
7.5 0.66 0.94 1.12
9.0 0.7 0.98 1.16
12.0 0.76 1.04 1.22
15.0 0.81 1.09 1.27
18.0 0.85 1.13 1.31
21.0 0.89 1.17 1.34
24.0 0.93 1.21 1.38
27.0 0.96 1.24 1.4
30.0 0.99 1.26 1.43
36.0 1.04 1.31 1.48
42.0 1.09 1.36 1.52
48.0 1.13 1.39 1.55
54.0 1.17 1.43 1.58
60.0 1.2 1.46 1.61
Notes:
1. The velocity pressure coefficient Kz, may be determined for the following
formula:
For 4.5 m ≤ z ≤ zg For z < 4.5 m
⁄ ⁄
= 2.01 ⁄ = 2.01 4.5⁄
2. α and zg are tabulated in Table 209A.9.1
3. Linear interpolation for intermediate values of height z is acceptable.
4. Exposure categories are defined Section 207A.7.
Table 207C.3-1
Velocity Pressure Exposure Coefficients, Kh and Kz
Height above ground level, z Exposure
(m) Exposure B Exposure C Exposure D
0-4.6 0.70 0.85 1.03
6.1 0.70 0.90 1.08
7.6 0.70 0.94 1.12
9.1 0.70 0.98 1.16
12.2 0.76 1.04 1.22
15.2 0.81 1.09 1.27
18 0.85 1.13 1.31
α 7 9.5 11.5
Zg 365.76 274.32 213.36
Notes:
1. The velocity pressure coefficient Kz, may be determined for the following formula:
Site Topography
Topographic Effects
NSCP 2015 Section 207A.8 commentary: as an aid to the designer, this section was
rewritten in ASCE 7-98 to specify when topographic effects need to be applied to a
particular structure rather than when they do not as in the previous version.
Wind speed-up effects at isolated hills, ridges, and escarpments constituting abrupt
changes in the general topography, located in any exposure category, shall be included
in the design when buildings and other site conditions and locations of structures
meet all of the following conditions:
1. The hill, ridge, or escarpment is isolated and unobstructed upwind by other similar
topographic features of comparable height for 100 times the height of the
topographic feature (100H) or 3.2 km, whichever is less. This distance shall be
measured horizontally from the point at which the height H of the hill, ridge, or
escarpment is determined.
1. The hill, ridge, or escarpment protrudes above the height of upwind terrain
features within a 3.2 km radius in any quadrant by a factor of two or more.
2. The structure is located as shown in Figure 207A.8-1 in the upper one-half of a hill
or ridge or near the crest of an escarpment.
3. ⁄ ≥ 0.2
4. H is greater than or equal to 4.5 m for Exposure C and D and 18 m for Exposure B.
Topographic Factor
The wind speed-up effect shall be included in the calculation of design wind loads by
using factor Kzt:
= (1 + + + ) (207 . 8 − 1)
Figure 207A.8-1
Topographic Factor, Kzt
Note:
1. For values of hill or escarpment relative than those shown, linear interpolation is
permitted.
Equation:
= (1 + + + )
determined from table below
| |
= 1−
⁄
=
Directionality Factor
The directionality factor Kd is obtained from NSCP 2015 Table 207A.6-1 and for
buildings is given as 0.85. The directionality factor accounts for the reduced probability
Velocity Pressure
The basic wind speed is converted to a velocity pressure at height z by NSCP 2015
Equation which is
Where
Kd = wind directionality factor, as defined in Section 207A.6
Kz = velocity pressure exposure coefficient defined in Section 207B.3.1
Kzt = topographic factor defined in Section 207A.8.2
V = basic wind speed defined in Section 207A.5
qz = velocity pressure calculated using Equation 207B.3-1 at height z
qzt = velocity pressure calculated using Equation 207B.3-1 at mean roof height h
The two-story office building, shown in Fig. 3.3, is located in a suburban area with a
wind speed V of 185 km/h. Determine the wind velocity pressure at roof height for the
main wind-force resisting system.
ℎ=6 < 18
Hence, the building qualifies as a low-rise building and Table 207C.3-1 values for the
velocity pressure exposure coefficients are applicable for a building designed using
NSCP 2015 Figure 207C.4-1.
For a suburban area the exposure is category B and the relevant parameters are
obtained as
The velocity pressure qh at the roof height of 6.1 m above the ground is given by NSCP
2015 Equation 207C.3-1 as
=
= (0.7)(1.0)(0.85)(51.39)
= . ⁄
Note: The wind speed, V, which is in kilometer per hour, must convert to meter per
second.
Envelope Procedure
This procedure is outlined in NSCP 2015 207C.4 and is applicable to low-rise buildings
that meet the following requirements:
• The structure does not have response characteristics making it subject to across
wind loading, vortex shedding, and instability due to galloping or flutter.
The gust effect factor accounts for along-wind loading effects caused by dynamic
amplification in flexible structures and for wind turbulence-structure interaction. For a
rigid structure, the gust effect factor may be taken as 0.85. Alternatively, the gust effect
factor may be calculated using the procedures given in NSCP 2015 Sections 207A.9.4
and 207A.9.5.
Enclosure Classifications
The internal pressure produced in a structure by wind depends on the size and location
of openings in the external walls of the structure. As shown in Fig. 3.4, an opening in
the windward wall of a structure produces an internal pressure. An opening in the
leeward wall of a structure produces an internal suction.
Glazing that is breached by missiles must be treated as openings, as this may result
in the development of high internal pressures. In accordance with NSCP 2015 Section
207A.10 in a wind-borne debris region, glazing in the lower 18 m of structures shall be
assumed to be openings unless such glazing is impact resistant or protected with an
impact resistant covering. The same requirement applies to glazing that is less than 9 m
above aggregate surface roofs located within 457 m of the structure. A wind-borne
debris area is defined in NSCP 2015 207A.2 as being a hurricane prone area:
An open building is defined in NSCP 2015 207A.2 as a building having each wall at least
80 percent open. This is given for each wall by the expression
≥ 0.8
Where Ao is total area of openings in a wall that receives positive external pressure and
Ag is the gross area of the wall in which Ao is identified.
1. The total area of openings in a wall that receives positive external pressure
exceeds the sum of the areas of openings in the balance of the building envelope
(walls and roof) by more than 10 percent.
2. The total area of openings in a wall that receives positive external pressure
exceeds the smaller of 0.37 m2 or 1 percent of the area of the wall, and the
percentage of openings in the balance of the building envelope does not exceed
20 percent.
> 1.10
⁄ ≤ 0.20
And either
> 0.01
Or
> 0.37 m
where
Aoi = the sum of the areas of openings in the building envelope (walls and roof) not
including Ao, in m2 and
Agi = the sum of the gross surface area of the building envelope (walls and
roof) not including Ag, in m2
An enclosed building is defined as one that does not comply with the requirements for
open or partially enclosed buildings.
For the envelope procedure of NSCP 2015 207B Part 1, the gust effect factor is combined
with the external and internal pressure coefficients. The design wind pressure on the
main wind-force resisting system is given NSCP 2015 as
where
In accordance with NSCP 2015 207AC.4.4 the wind load to be used in design shall not
be less than +766 Pa multiplied by the wall area of the building and 383 kN/m2
multiplied by the roof area of the building projected on a plane normal to the wind
direction as shown in NSCP 2015 Figure C207B.4-1.
Example 3.2. Design Wind Pressure for Main Wind-Force Resisting System
For the transverse wind direction, determine the design wind pressure acting on the end
frames of the two-story office building analyzed in Example 3.1. The building may be
From Example 3.1, the velocity pressure at mean roof height is obtained as
= . ⁄
ℎ 6
= = 0.63 < 1
9.6
h/L = 6/9.6 = 0.63 < 4 ... rigid structure as defined by NSCP 2015 Section 207A.2
h = 6.1 m < 18 m ... low-rise building as defined by NSCP 2015 Section 207A.2.
Hence, the low-rise building analytical method of NSCP 2015 Section 207C.4 is
applicable and values of (GCpf) may be obtained from NSCP 2015 Figure 207C.4-1.
For a two-story building with flexible diaphragms, NSCP 2015 Figure 207C.4-1 Note 5
specifies that torsional load cases may be neglected. To design the end frame of the
building, the pressures on surfaces 1E, 2E, 3E, and 4E must be determined. For an
enclosed building the product of the internal pressure coefficient and gust effect factor is
For surface 1E the product of the equivalent external pressure coefficient and gust effect
factor is
= − (N⁄m )
= 963.24[(0.61) – (±0.18)]
= 760.96 N/m2 for negative internal pressure (suction)
= 414.19/m2 for positive internal pressure
For surface 2E the product of the equivalent external pressure coefficient and gust effect
factor is
= − (N⁄m )
= 963.24[(-1.07) – (±0.18)]
= - 857.28 N/m2 for negative internal pressure (suction)
= - 1204.05/m2 for positive internal pressure
For surface 3E the product of the equivalent external pressure coefficient and gust effect
factor is
=− . … from NSCP 2015 . −
= − (N⁄m )
= 963.24[(-0.53) – (±0.18)]
= - 337.13 N/m2 for negative internal pressure (suction)
= - 683.9/m2 for positive internal pressure
= − (N⁄m )
= 963.24[(-0.43) – (±0.18)]
= - 240.81 N/m2 for negative internal pressure (suction)
= - 587.58/m2 for positive internal pressure
The wind pressure diagrams for both cases, internal suction and internal pressure, are
shown in Figure 3.5.
NSCP 2015 Section 207E provides six separate procedures for the determination of wind
pressure on components and cladding. All procedures require compliance with the
following conditions:
2. The simplified envelope design method of NSCP 2015 Part 2 (Low-Rise Buildings,
Simplified) Section 207E.5 (Building Types). This is applicable to enclosed low-rise
buildings and buildings with h ≤ 18 m having flat roofs, gable roofs, and hip roofs.
This method is based on the procedure of Part 1. Wind pressures are determined
from a Table 207E.5-1 and adjusted where necessary.
3. The analytical directional design method of NSCP 2015 Part 3 Section 207E.6. This is
applicable to enclosed and partially enclosed buildings with h > 18 m having flat
roofs, pitched roofs, gable roofs, hip roofs, mansard roofs, arched roof, and domed
roof. Wind pressures are determined from the specified equation applicable to each
building surface. The determination of wind loads for these types of building is
shown in Table 207E.6-1.
4. The simplified directional design method of NSCP 2015 Part 4 Section 207E.7. This
is applicable to enclosed buildings with h ≤ 49 m having flat roofs, gable roofs, hip
roofs, monoslope roofs, and mansard roofs. This method is based on the procedure
of Part 3. Wind pressures are determined from the Table 207E.7-1 and adjusted
where necessary.
5. The analytical directional design method of NSCP 2015 Part 5 Section 207E.8
(Building Types). This is applicable to open buildings of all heights having pitched
free roofs, monoslope free roofs and troughed free roofs. Wind pressures are
determined from the specified equation applicable to each roof surface. The
determination of wind loads is in Table 207E.8-1
6. The analytical directional design method of NSCP 2015 Part 6 Section 207E.9. This is
applicable to building appurtenances such as roof overhangs and parapets. Wind
pressures are determined from the specified equation applicable to each roof
overhang or parapet surface. Wind loads determination for C&C is shown in the
Table 207E.10-1.
The design wind pressure on components and cladding for low-rise building and
buildings with a height not exceeding 60 ft is given by NSCP 207E.4 as
= − ( ⁄ ) (207. 4 − 1)
Where
qh = wind velocity pressure at mean roof height h for the applicable exposure
category
(GCp) = product of the equivalent external pressure coefficient and gust effect
factor as given in NSCP 2015 Figures 207E.4.1 through 207E.4-7.
In accordance with ASCE 7 Sec. 30.2.2 the design wind pressure shall not be less than a
net pressure of 16 lb/ft2 applied in either direction normal to the surface.
The velocity pressure exposure coefficients Kz are given in NSCP Table 207E.3-1.
Local turbulence at corners and at the roof eaves produces an increase in pressure in
these areas. Hence, as shown in NSCP 2015 Figures 207E.4-1 and 207E.4-2, walls are
divided into two zones and roofs are divided into three zones with a different wind
= 0.04 ( ℎ
Or
= 0.9 m
The values of (GCp) depend on the effective area attributed to the element considered.
Because of local turbulence that may occur over small areas of buildings, components
and cladding are designed for higher wind pressures than the main wind-force resisting
system. An effective wind area is used to determine the external pressure coefficient.
This is defined in NSCP 2015 Section 207A.2 as
= ℓ
where
ℓ = element span length
be = effective tributary width
≥ ℓ/3
For cladding fasteners, the effective wind area shall not be greater than the area that is
tributary to an individual fastener. In accordance with NSCP 2015 Figure 207E.4-1
Note 5, the values of (GCp) may be reduced by 10% for the walls of buildings with a roof
slope of 10° or less.
The roof framing of the building analyzed in Example 3.1 consists of open web joists
spaced at 1.2 m centers and spanning 9 m parallel to the long side of the building. For
the transverse wind direction, determine the design wind pressure acting on a roof joist
in interior zone 1 of the building and determine the width of the eave zone. The building
may be considered enclosed.
From Example 3.1, the velocity pressure at mean roof height using Case 1 values for
Kz is obtained as
= 963.24 N⁄m
h = 6 m < 18 m
Hence, the low-rise building method of NSCP 2015 Section 207E.3 is applicable.
= ±0.18
The width of the eave zone 2 is given by NSCP 2015 Table 207E.4-1 Note 6 as the lesser
of
= 0.1 = 0.1 9.6 = 0.96 m
or
= 0.4ℎ = 0.4 6 = 2.4 m
Or = 0.9 m
Hence, = . . . . governs
The effective tributary width of a roof joist is defined in NSCP 2017A.2 as the larger of
= ℓ=3 9=
The negative external pressure coefficient for roof interior zone 1 is obtained from NSCP
2015 Figure 207E.4-2A as
= −0.9
The negative design wind pressure on a roof joist for interior zone 1 is obtained from
NSCP 2015 Equation 207E.4-1 as
= −
= 963.24[(−0.9) − (0.18)]
=− . ⁄
=
= − 1040.87 1.2
=− /
(GCp) = 0.2
The positive design wind pressure on a roof joist for interior zone 1 is obtained from
NSCP 2015 Equation 207E.4-1 as
= −
= 963.24[(0.2) − (−0.18)]
= ⁄
=
= 366 1.2
= . /
The wind loading acting on the roof joist is shown in Fig. 2.35.
Example 3.4
Calculate the external wind forces based on NSCP 2015 wind load calculation for main
wind force resisting system of the rigid enclosed building with dimension of 18 m in
width, 81 m in length, ridge height of 8.85, and the height of wall is 6.6 m. The building
has a fundamental frequency of greater or equal to 1 Hz.
Note: Refer to Section 207C discussion about Envelope Procedure for Enclosed &
Partially Enclosed Low-Rise Building in NSCP 2015 Method 2.
Also, see NSCP 2015 Method 1 for MWFRS applicable to the MWFRS of enclosed
simple diaphragm building less than 18m in height.
Solution:
PARAMETERS
Wind Speed, V 150 kph
total height, z 8.85 m
height bottom of roof 6.6 m
horizontal dim. Parallel to wind dir., L 81 m
horizontal dim. Normal to wind dir., B 18 m
mean roof height , h 7.725 m
Roof Angle, θ 14 degrees
1ℎ 1000
= 150 ℎ = 150 = 41.667 /
ℎ 3600 1
To find the value of Kzt, topographic factor, shall see Section 207A.8 and Figure 207A.8-
1. Since the location of the project is not specified the terrain, let us consider the location
as flat terrain and the value of Kzt = 1.0.
As for wind directionality factor, Kd stated in NSCP 2015 Section 207A.6 and Table
207A.6-1
= 0.613
= 0.613(0.975517743)(1.0)(0.85)(4.16667)
= 882.45
= 0.613
= 0.613(0.947992044)(1.0)(0.85)(4.16667)
= .
LOW-RISE BUILDING
Alternatively, design wind pressures for the MWFRS of Low-Rise Building shall be
determined by the following equation:
= − Equation 207C. 4 − 1
ℎ :
qh = velocity pressure evaluated at mean roof height as defined in Section 207A.3
= external pressure coef icient from Figure 207C. 4 − 1
= internal pressure coef icient from Table 207A. 11 − 1
5 0.40
1. Surface 1 : 15 9.036 14.036 = 0.13
20 0.53
9.036
= ; = 0.078 ≈ 0.08
0.13 15
5 −0.69
2. Surface 2 : 15 9.036 14.036 = 0
20 −0.69
9.036
= ; =0
0 15
14.036 = −0.69 + 0 = − .
5 −0.37
3. Surface 3 : 15 9.036 14.036 = − 0.11
20 −0.48
9.036
= ; = −0.066 ≈ −0.07
−0.11 15
5 −0.29
4. Surface 4 : 15 9.036 14.036 = − 0.14
20 −0.43
9.036
= ; = −0.084 ≈ −0.08
−0.14 15
5 0.61
5. For 1E : 15 9.036 14.036 = 0.19
20 0.8
9.036
= ; = 0.1144 ≈ 0.11
0.19 15
5 −1.07
6. For 2E : 15 9.036 14.036 = 0
20 −1.07
9.036
= ; =0
0 15
14.036 = −1.07 − 0 = − .
5 −0.53
7. For 3E : 15 9.036 14.036 = − 0.16
20 −0.69
9.036
= ; = −0.096 ≈ −0.1
−0.16 15
5 −0.43
8. For 4E : 15 9.036 14.036 = − 0.21
20 −0.64
9.036
= ; = −0.1265 ≈ −0.13
−0.21 15
External Pressure Coefficient, GCpf on Low-Rise Walls & Roofs Enclosed, Partially
Enclosed Building <= 18 m, (LOAD CASE A)
ROOF BUILDING SURFACE LOAD CASE A
ANGLE,
θ 1 2 3 4 1E 2E 3E 4E
5 0.4 -0.69 -0.37 -0.29 0.61 -1.07 -0.53 -0.43
14.036 0.48 -0.69 -0.44 -0.37 0.72 -1.07 -0.63 -0.56
20 0.53 -0.69 -0.48 -0.43 0.8 -1.07 -0.69 -0.64
Now, we will calculate the wind pressure based on the calculated external pressure coefficient.
= −
2. For surface 2
= −
= 857.55 N⁄m [(−0.69) − (∓0.18)]
= −437.4 N⁄m ( )
= −746.1 N⁄m
3. For surface 3
= −
= 857.55 N⁄m [(−0.44) − (∓0.18)]
= −223 N⁄m ( )
= −531.7 N⁄m
4. For surface 4
= −
= 857.55 N⁄m [(−0.37) − (∓0.18)]
= −162.9 N⁄m ( )
= −471.7 N⁄m
= −
= 857.55 N⁄m [(0.72) − (∓18)]
= 771.8 N⁄m ( )
= 463.08 N⁄m
WPU-QSF-ACAD-82A
82A Rev. 00 (09.15.20)
Now, we will calculate the wind pressure based on the calculated external pressure
coefficient of Load Case B.
= −
= 857.55 N⁄m [(−0.45) − (∓0.18)]
= −231.5 N⁄m ( )
= −540.3 N⁄m
2. For surface 2
= −
= 857.55 N⁄m [(−0.69) − (∓0.18)]
= −437.4 N⁄m ( )
= −746.1 N⁄m
3. For surface 3
= −
= 857.55 N⁄m [(−0.37) − (∓0.18)]
= −162.9 N⁄m ( )
= −471.7 N⁄m
4. For surface 4
= −
= 857.55 N⁄m [(−0.45) − (∓0.18)]
= −231.5 N⁄m ( )
= −540.3 N⁄m
5. For surface 5
= −
= 857.55 N⁄m [(0.40) − (∓0.18)]
= 497.4 N⁄m ( )
6. For surface 6
= −
= 857.55 N⁄m [(−0.29) − (∓0.18)]
= −94.3 N⁄m ( )
= −403 N⁄m
= −
= 857.55 N⁄m [(−0.48) − (∓0.18)]
= −257.3 N⁄m ( )
= −566 N⁄m
-0.18 -0.23 -0.44 -0.16 -0.23 0.50 -0.09 -0.57 -0.76 -0.30 -0.26
0.26 0.68 -0.21
WPU-QSF-ACAD-82A
82A Rev. 00 (09.15.20)
Cf = net force coefficients from Figure 207D.4-1
As = the gross area of the solid freestanding wall or freestanding solid sign, m2
Example 3.6:
Determine the resultant force acting perpendicular to the face of the billboard and
through its center if it is located in Coastal Road near Asian Mall in Paranaque, Manila
which is an open flat terrain. The sign is rigid and has a width of 12 m and a height of 3
m. Its top side is 15 m from the ground.
Solution:
= 0.613
Since z = h = 15 m,
kz = 1.09 (Exposure Category C for an open flat terrain, see Table 207D.3-1)
Kzt = 1.0
Kd = 1.0
V = 75 m/s
= 0.613(1.09)(1.0)(1.0)(75)
To calculate the value of Net Force Coefficient, Cf, refer to Figure 207D.4-1
=
= (3758.46)(0.85)(1.80)(12 3)
= 207015.77 N = .
Seismic loads on a structure are generated by the effects that an earthquake has on
the structure. Earthquakes are the result of an abrupt rupture along a fault zone below
the earth’s surface. The ground vibrations created as a result of this rupture produce
inertial forces in a structure that may cause severe damage unless the structure is
appropriately designed and constructed. In accordance with Newton’s second law of
motion, the inertial force produced equals the mass of the structure multiplied by the
imposed acceleration. The seismic load must be accurately estimated in order to design
the structure to withstand an earthquake.
The minimum design strength shall be based on the Design Seismic Forces determined
in accordance with the static lateral force procedure of Section 208.5, except as modified
by Section 208.5.3.5.4.
Where strength design is used, the load combinations of Section 203.3 shall apply.
Where Allowable Stress Design is used, the load combination of Section 203.4 shall
apply.
Allowable Stress Design may be used to evaluate sliding or overturning at the soil-
structure interface regardless of the design approach used in the design of the structure,
provided load combinations of Section 203.4 are utilized.
Occupancy Categories
For purposes of earthquake-resistant design, each structure shall be placed in one of the
occupancy categories listed I Table 103-1. Table 208-1 assigns importance factors, I and
Ip, and structural observation requirements for each category.
Each site shall be assigned a soil profile type based on properly substantiated
geotechnical data using the site categorization procedure set forth in Section 208.4.3.1.1
and Table 208-2
Exception:
When the soil properties are not known in sufficient detail to determine the soil profile
type, Type SD shall be used. Soil Profile Type SEor SF need not be assumed unless the
building official determines that Type SE or SF may be present at the site or in the
event that Type SE or SF is established by geotechnical data.
Soil Profile Type SA, SB, SC, SD and SE are defined in Table 208-2 and Soil Profile Type
SF is defined as soils requiring site-specific evaluation as follows:
1. Soils vulnerable to potential failure or collapse under seismic loading, such as liquefiable
soils, quick and highly sensitive clays, and collapsible weakly cemented soils.
2. Peats and/or highly organic clays, where the thickness of peat or highly organic clays, where
the thickness of peat or highly organic clays exceeds 3.0 m.
3. Very high plasticity clays with a plasticity index, PI > 75, where the depth of clay exceeds 7.5
m.
4. Very thick soft/medium stiff clays, where the depth of clay exceeds 35 m.
5. The criteria set forth in the definition for Soil Profile Type SF requiring site-specific
evaluation shall be considered. If the site corresponds to those criteria, the site shall be
classified as Soil Profile Type SF and a site-specific evaluation shall be conducted.
Seismic hazard characteristics for the site shall be established based on the seismic zone and
proximity of the site to active seismic sources, site soil profile characteristics and the structure’s
importance factor.
Seismic Zone
The Philippine archipelago is divided into two seismic zones only. Zone 2 covers the provinces of
Palawan (except Busuanga), Sulu and Tawi-tawi while the rest of the country is under Zone 4 as
shown in Table 208-1. Each structure shall be assigned a seismic zone factor Z, in accordance
with Table 208-3.
ZONE 2 4
Z 0.20 0.40
In Seismic Zone 4, each site shall be assigned near-source factors in accordance with
Table 208-4 and 208-5 based on the Seismic Source Type as set forth in Section
208.4.4.4.
The value of Na used to determine Ca need not exceed 1.1 for structures complying with
all the following conditions:
1. The soil profile type is SA, SB, SC or SD.
2. ρ = 1.0
3. Except in single-storey structures, residential buildings accommodating 10 or fewer
persons, private garages, carports, sheds and agricultural buildings, moment frame
systems designated as part of the lateral-force-resisting system shall be special
moment-resisting frames.
4. The exceptions to Section 515.6.5 shall not apply, except for columns in one-storey
buildings or columns at the stop storey of multi-storey buildings.
5. None of the following structural irregularities is present: Type 1, 4 or 5 of Table 208-
9, and Type 1 or 4 of Table 208-10.
Table 208-6 defines the types of seismic sources. The location and type of seismic
sources to be used for design shall be established based on approved geological data;
see Figure 208-2A. Type A sources shall be determined from Figure 208-2B, 2C, 2D,
2E or the most recent mapping of active faults by Philippine Institute of Volcanology
and Seismology (PHILVOCS)
In Seismic Zone 4, each site shall be assigned near-source factors in accordance with
Tables 208-5 and 208-6 based on the Seismic Source Type as set forth in Section
208.4.4.2
For high rise structures and essential facilities within 2.0 km of a major fault, a site
specific seismic elastic design response spectrum is recommended to be obtained for the
specific data.
1. The Near-Source Factor may be based on the linear interpolation of values for
distances other than those shown in the table.
2. The closest distance to seismic source shall be taken as the minimum distance
between the site and the area described by the vertical projection of the source on
the surface (i.e., surface projection of fault plane). The surface projection need not
include portions of the source at depths of 10 km or greater. The largest value of the
Near- Source Factor considering all sources shall be used for design.
The value of Na used to determine Ca need not exceed 1.1 for structures complying with
all the following conditions:
Seismic Zone Z
Soil Profile Type
Z = 0.2 Z = 0.4
SA 0.16 0.32Na
SB 0.20 0.40Na
SC 0.24 0.40Na
SD 0.28 0.44Na
SE 0.34 0.44Na
SF See Footnote 1 of Table 208-8
Seismic Zone Z
Soil Profile Type
Z = 0.2 Z = 0.4
SA 0.16 0.32Nv
SB 0.20 0.40Nv
SC 0.32 0.56Nv
SD 0.40 0.64Nv
SE 0.64 0.96Nv
A structural system with an essentially complete space frame providing support for
gravity loads. Moment-resisting frames provide resistance to lateral load primarily by
flexural action of members.
Determination of R
The total design base shear in a given direction shall be determined from the following
equation:
= (208 − 5)
where the value of Ca shall be based on Table 208-7 for the soil profile type. When the
soil properties are not known in sufficient detail to determine the soil profile type, Type
SD shall be used in Seismic Zone 4, and Type SE shall be used in Seismic Zone 2. In
Seismic Zone 4, the Near-Source Factor, Na, need not be greater than 1.2 if none of the
following structural irregularities are present:
Vertical Distribution
The forces at each level shall be calculated using the following equation:
= (208 − 6)
The design storey shear, , in any storey is the sum of the forces Ft and Fx above that
storey. shall be distributed to the various elements of the vertical lateral force-
resisting system in proportion to their rigidities, considering the rigidity of the
Where diaphragms are not flexible, the mass at each level shall be assumed to be
displaced from the calculated center of mass in each direction a distance equal to 5
percent of the building dimension at that level perpendicular to the direction of the force
under consideration. The effect of this displacement on the storey shear distribution
shall be considered.
Diaphragms shall be considered flexible for the purposes of distribution of storey shear
and torsional moment when the maximum lateral deformation of the diaphragm is more
than two times the average storey drift of the associated storey. This may be determined
by comparing the computed midpoint in-plane deflection of the diaphragm itself under
lateral load with the storey drift adjoining vertical- resisting elements under equivalent
tributary lateral load.
The total design base shear in a given direction shall be determined from the following
equation:
= (208 − 8)
The total design base shear need not exceed the following:
.
= (208 − 9)
The total design base shear shall not be less than the following:
= . (208 − 10)
In addition, for Seismic Zone 4, the total base shear shall also not be less than the
following:
.
= (208 − 11)
Structure Period
The value of T shall be determined from one of the following methods:
1. Method A:
For all buildings, the value T may be approximated from the following equation:
WPU-QSF-ACAD-82A Rev. 00 (09.15.20)
= ( ) (208 − 12)
Alternatively, the value of Ct for structures with concrete or masonry shear walls may
be taken as . / .
= ∑ [ . + ( ⁄ ) ] (208 − 13)
Example 3.7
In designing a 21.95-m steel frame structure, the natural period is calculated to be 0.8
sec using the NSCP 2015 approximate method, what is the natural period for this
building?
Solution:
The approximate formula (Method A) is given in the NSCP 2015 208.5.2.2 (Structure
Period) Item 1 with the formula:
= ( )
⁄
= 0.0853(21.95)
T = 0.49 sec.
2. Method B:
The fundamental period T may be calculated using the structural properties and
deformational characteristics of the resisting elements in a properly substantiated
analysis. The analysis shall be in accordance with the requirements of Section 208.6.2.
The value of T from Method B obtained from Method A in Seismic Zone 4, and 40
percent in Seismic Zone 2.
Example 3.8
A 30.5 m, ten-storey office building has a total weight of 66,723 kN. The building is in
seismic zone 4 at a location 5 km from a seismic source with a high rate of seismic
activity. It is designed with a special moment-resisting steel frame system and is
constructed on rock (soil type SB). Use the NSCP 2015 static lateral-force procedure to
calculate the total design base shear.
Solution:
The total design base shear (V) can be determined from equation 208-8
= ( )
For special moment-resisting steel frame systems, Ct = 0.0853 and hn = 30.48 m
= 0.0853(30.5)
= .
From Table 208-11B for special moment-resisting steel frame systems, R = 8.0.
From Table 208-1 importance factor for office building is I = 1.00 (Standard
Occupancy).
Ca = 0.40Na
Cv = 0.40Nv
From table 208-2, the soil profile type is producing a high rate of seismic activity, then
the seismic source type is Type A. So, the Near-Source Factor Na = 1.2 which is in 5 km
radius, and the Near-Source Factor Nv = 1.6 from the seismic source.
(0.64)(1.00)
= (66723) = 4808.86 kN ≈
(8.0)(1.11)
The total design base shear need not exceed the following:
.
= (208 − 9)
2.5(0.48)(1.00)
= (66723) = 10008.45 kN ≈
8.00
= . → (208 − 10)
= 0.11(0.48)(1.00)(66723) = 3522.97 ≈
The structure is built in Zone 4, the required total base shear shall also not be less than
the following:
.
= (208 − 11)
0.8(0.4)(1.6)(1.00)
= (66723) = 4270.27 kN ≈
8.00
Since = < 4809 < 10008
Therefore:
= = is governs
The total force shall be distributed over the height of the structure in conformance with
Equations 208-15, 208-16 and 208-17 in the absence of a more rigorous procedure.
= + (208 − 15)
= . (208 − 16)
The value of T used for the purpose of calculating shall be the period that
corresponds with the design base shear as computed using Equation 208-4. need not
exceed . and may be considered as zero where T is 0.7 s or less. The remaining
portion of the base shear shall be distributed over the height of the structure, including
Level , according to the following equation:
( − )
= (208 − 17)
∑
Example 3.9
From Example 3.8, the design base shear is 4809 kN and the structure period T = 1.11,
and the weight carried by the structure at each level from 2 to 10 is 7000 kN while the
top level is 3723 kilo Newton.
1. Determine Ft
2. Calculate the vertical distribution of forces and label to the structure at every level.
Solution:
b. @ level 10,
h9 = 30.5 – 3.05 = 27.45 m
Wxhx = 7000(27) = 192150
c. @ level 9
H8 = 27.45-3.05=24.4
Wxhx = 7000(24.4) = 170800 kN
e. @ level 7
H8 = 21.35 - 3.05 = 18.3 m
Wxhx = 7000(18.3) = 128100 kN
f. @ level 6
H8 = 18.3 - 3.05 = 15.25 m
Wxhx = 7000(15.25) = 106750 kN
g. @ level 5
H8 = 15.25 - 3.05 = 12.2 m
Wxhx = 7000(12.2) = 85400 kN.m
h. @ level 4
H8 = 12.20 - 3.05 = 9.15 m
Wxhx = 7000(9.15) = 64050 kN.m
i. @ level 3
H8 = 9.15 - 3.05 = 6.10 m
Wxhx = 7000(6.10) = 42700 kN.m
j. @ level 2
H8 = 6.10 - 3.05 = 3.05 m
Wxhx = 7000(3.05) = 21350 kN.m
. ( )
=
∑
4435.34(113,551.5)
= + 373.66 = 842.47 kN
1,074,301.5
4435.34(170,800)
= = 705.16 kN
1,074,301.5
4435.34(149,450)
= = 617.02 kN
1,074,301.5
4435.34(128,100)
= = 528.87 kN
1,074,301.5
4435.34(106,750)
= = 440.73 kN
1,074,301.5
4435.34(85,400)
= = 352.58 kN
1,074,301.5
4435.34(64,050)
= = 264.44 kN
1,074,301.5
4435.34(42,700)
= = 176.29 kN
1,074,301.5
4435.34(21,350)
= = 88.15 kN
1,074,301.5
Σ = + + + + + + + + + =
Other Loads
Rain Loads
Design rain loads are addressed in ASCE 7 Chapter 8 and in IBC Sec. 1611. A primary
drainage system is provided to cope with the anticipated rainfall intensity produced
during short, intense rainfall events. In the event that the primary drainage system
becomes blocked by debris or ice, a secondary overflow drain must be provided with a
capacity not less than that of the primary system. A free discharge system is the
preferred method of emergency drainage.
The roof must be capable of resisting the maximum water depth that occurs when the
primary drainage system is blocked. As shown in Fig. 2.30, the maximum depth is the
sum of the static head developed at the inlet of the overflow drain plus the hydraulic
head that develops above the inlet at its design flow.
The design load for rain loads is express by the formula form NSCP 2015 Section 210.2
as
= . ( + ) ( − )
Symbols
R = rain load on the undeflected roof, in kN/m2. When the phrase “undeflected roof”
is used, deflections from loads (including dead loads) shall not be considered
when determining the amount of rain on the roof.
ds = depth of water on the undeflected roof up to the inlet of the secondary drainage
system when the primary drainage system is blocked (i.e., the static head), mm.
dh = additional depth of water on the undeflected roof above the inlet of the secondary
drainage system at its design flow (i.e., the hydraulic head), mm
= .
where
The required flow rate for the overflow scupper is given by ASCE 7 Eq. (C8-1) as
= .
= . ( )( / )
= . ⁄
(0.00262 − 0.0011)
ℎ = 1 +
(0.0032 − 0.0011)
dh = 1.74 in = 44.2 mm
= 0.0098( + )
= 0.0098(50 + 44.2)
R = 0.923 kN/m2
D. Activity/Exercise:
1. A five-storey building is constructed with 3.6 m in heights. The base shear has been
calculated as 710 kN. Each storey floor has a weight of 3600 kN, and the roof has
weight of 3100 kN. The natural period of oscillation is 0.5 sec. what are the storey
forces?
2. The building is to build at the seismic zone 4 with a total height of 53 m. the
building is 15 storey with 3.5 m from 2nd floor to roof top, and the 1st storey is 4
m from the ground floor. The building is a standard occupancy and a steel special
moment-resisting frame. The building distance from the seismic activity is about
8 kilometers. the soil profile type is SD for being stiff. Determine the following:
a. Near-source factor Na
b. Near-source factor Nv
c. The seismic coefficient Ca
d. The seismic coefficient Cv
4. From the problem 3 draw the building frame and indicate the computed lateral
force at each storey.
References:
Student’s Information
Name:
Program:
Year and Section:
Contact No.:
E-mail address:
Facebook Account:
Messenger Account:
Mission
WPU commits to develop quality human resource and green
technologies for a dynamic economy and sustainable
development through relevant instruction,
research and extension services.