Design Conditions Datasheet: Unit Tag Qty Model No Net Cooling Capacity (Ton.r) Nominal Voltage Refrigerant Type
Design Conditions Datasheet: Unit Tag Qty Model No Net Cooling Capacity (Ton.r) Nominal Voltage Refrigerant Type
Net Cooling
Unit Tag Qty Model No Nominal Voltage Refrigerant Type
Capacity (ton.R)
CH-1 1 YCAL0019EE46XEBSXXX 16.04 460-3-60.0 R410A
PIN:
YCAL0019EE 46XEBSXXXH XXRLXXXX40 XXXXXXXXXX SXXXXXX1XX XXXXXXXXXX
....5...10 ....5...20 ....5...30 ....5...40 ....5...50 ....5...60 ....5...70 ....5...80 ....5...90
Electrical Data
Circuit 1 2 3 4
Compressor RLA 19 / 19
Fan QTY/FLA (each) 2 / 1.3
High LRA Current 114 / 114
Single Point
Min. Circuit Ampacity 44
Recommended Fuse/CB Rating 60
Max. Inverse Time CB Rating 60
Max. Dual Element Fuse Size (A) 60
Unit Short Circuit Withstand (STD) 5 [kA] Operating Condition Electrical Data
Wire Lugs Per Phase 1 Compressor kW 14.15
Wire Range (Lug Size) 14 AWG - 2/0 Total Fan kW 1.000
Starter Type Across The Line Total kW 15.15
Notes:
Outside the scope of AHRI Air-Cooled Water-Chilling Packages Using Vapor Compression Cycle
Certification Program, but is rated in accordance with AHRI Standard 550/590 (I-P) and AHRI
Standard 551/591 (SI). Auxiliary components included in total KW - Oil heaters, Chiller controls.
Auxiliary power is already included in the compressor and fan power