Easergy P3
Catalog 2021
Network Protection Relays
se.com/easergy
Note: Electrical power systems are dangerous, protection relays are defined and governed
by international standards such as IEC 60255 “Measuring relays and protective equipment”
and IEEE C37.97 “Protective relay applications to power systems buses”. Never attempt to
install or operate protection relays or associated equipment without the necessary
qualifications, training and tools. Exposure to electrical arc-flash incidents can be life
threatening, no situation can ever be deemed fully safe. Standards such as NFPA 70E define
important risk categorization and such standards identify both distance from, and energy of
the arc incident to be important factors. In order to reduce the risk category and improve
safety during arc-flash incidents, functionality is available in Easergy P3 protection relays to:
i) to operate electrical panel from a safer distance via wireless communication, and ii) arc-
flash protection functionality to detect and limit the arc energy by tripping the connected
circuit breaker faster than in a conventional protection scheme.
Notice: This Catalog is for illustration purpose only. All connections mentioned in this
document must be made as instructed in the User Manuals.
General Contents
PM106568
Range description 6
Easergy P3 Standard 32
Easergy P3 Advanced 52
Ordering 111
EcoStruxure ready
EcoStruxure™ Architecture
Cloud and/or
On Premise
End to End
Edge Control
Connected Products
• Simple selection and ordering with • Simpler operation and maintenance • Embedded arc protection
EcoReal MV with the EcoStruxure™ Power • Built-in virtual injection testing
• Simplified configuration with the new Device app
• Compliant with international
eSetup Easergy Pro setting tool • 9 communication protocols in one standards (i.e. IEC 60255-1)
• Faster delivery with on-the-shelf box, including IEC 61850
availability of standard configurations • Increased number of inputs and
outputs for more possibilities
Range overview
DM105528
T U L L F U
G G U U U U U U M
T U L L G U M M
Selection guide 9
Capacitor application 20
Communication
21
Examples of network architectures
– Water
Easergy P3 Advanced
Easergy products are designed to be user friendly, a feature that is
proven in our customer reports day after day. You’ll benefit from features
that include:
• A complete set of protection functions, related to the application
• Arc detection (Easergy P3 Advanced)
• Dedicated circuit breaker control with single-line diagram, push buttons,
programmable function key and LEDs, and a customizable alarm
• Multilingual HMI for customized messaging
• Settings tool relay management software for setting parameters, configuring,
and network fault simulation
• Both serial and Ethernet communication, including redundancy
• IEC 61850 standard Ed.1 & Ed.2
P3F30
with directional
Feeder -
P3L30
line diff. & distance
P3U30 P3T32
Transformer P3U10 P3U20 with directional O/C - with differencial
with voltage protection
P3M32
Motor P3M30 with differencial
P3G32
Generator P3G30 with differencial
Characteristics
Phase current 1/5A CT or LPCT (x3) (5) 1/5A CT or LPCT (x3) (5) 1/5A CT (x6)
2 x (1/5A+0.2/1A) CT,
Measuring inputs Residual current 1/5A CT or 0.2/1A CT (1/5A+0.2/1A) CT
1 x (1/5A) CT
Voltage VT (x1) VT (x4) or LPVT (x4) (5) VT (x4) or LPVT (x4) (5) VT (x4)
Loop sensor: 1 Loop sensor: 1
Arc-flash sensor input -
Point sensor: 2, 4 or 6 (1) (2) Point sensor: 2, 4 or 6 (1)
Input 2 10/8 14/16 6 to 36 6 to 16
Digital
Output 5 + SF 5/8 + SF 11/8 + SF 10 to 21 + SF 10 to 13 + SF
Input - 0 or 4 (1) 0 or 4 (1)
Analogue
Output - 0 or 4 (1) 0 or 4 (1)
Temperature sensor input - 0 or 8 or 12 (1) 0 or 8 or 12 (1)
Front port USB type B USB type B
24V dc or 24-48V dc or 38.4-265V dc 24 to 48V dc or or 38.4-265V dc
Nominal power supply
or 48-230V ac (4) or 110-240V ac
Ambient temperature, in service -40 to 60°C (-40 to 140°F) -40 to 60°C (-40 to 140°F)
Communication
Rear ports
-
RS232, IRIG/B, RS485, Ethernet
IEC61850 ed1 & ed2 -
IEC 60870-5-101 & 103 -
DNP3 over Ethernet -
DNP3 serial -
Protocols Modbus serial -
Modbus over Ethernet -
Ethernet IP (6) -
Profibus DP -
SPAbus -
Redundancy protocols (RSTP/PRP) -
Others
1 object 4 objects 4 objects 8 objects
Control
1 display 4 display 8 display 3-8 display
Logic (Matrix + Logic equation)
Withdrawable CT connector with shorting -
Remote HMI -
Hardware dimensions (W/H/D) 171 x 176 x 214(3) mm / 6.73 x 6.93 x 8.43 in 264 x 177 x 208 mm / 10.39 x 6.97 x 8.19 in
(1) Depends on optional module
(2) P3L30 can have 1 loop or 2 point sensors only
(3) 226 mm (8.90 in) with ring-lug connectors
(4) Check the available power supply range from the device’s serial
number label
(5) P3U30, P3F30, P3M30 relays only. Consult us for other models
(6) Consult us for availability
DM105536
P3F30 P3F30
P3G30 P3G30
P3T32 P3T32
P3G32 P3G32
P3F30 P3M30
P3T32 P3M32
• Up to 4 light point sensors to monitor the busbar • Up to 4 light point sensors in each relay
• Transmission of light detection signals via digital I/O or
IEC 61850 GOOSE messages
Zone 1
light detection signal
signal sent to upstream relay for tripping
P3F30
P3G30 • Light detection in zone 2:
P3T32
P3G32 incomer Easergy P3 trips, if fault confirmed by overcurrent
Zone 1
• Light detection in zone 3:
corresponding outgoing Easergy P3 trips, if fault confirmed by
Zone 2 overcurrent
P3F30 P3M30
P3T32 P3M32
Outgoing protection
• Feeder overcurrent protection
• Feeder overload protection
Protection of low-capacitance feeders in Protection of high-capacitance feeders Protection of feeders with metering
impedance-earthed or solidly-earthed in impedance-earthed or compensated
neutral systems or isolated neutral systems
DM105538
DM105539
DM105540
P3U10 P3U10
P3U20 P3F30 P3U20 P3F30 P3U30 P3F30
P3U30 P3U30
• Feeder earth-fault overcurrent • Directional earth-fault overcurrent • Power and energy measurement
• Transient intermittent earth-fault • Min and max demand values over the last
31 days and 12 months
Incomer protection
• Busbar overcurrent protection
Incomer protection without voltage monitoring Incomer protection with voltage and
frequency monitoring
DM105541
DM105542
DM105543
P3U10 P3U10
P3U20 P3F30 P3U20 P3F30 P3U30 P3F30
P3U30 P3U30
DM105545
P3U30 P3F30
• Voltage and frequency min and max values • Directional phase overcurrent
• Voltage harmonic values and THD • Directional earth-fault overcurrent
• Voltage sags and swells
Line protection
• Overcurrent and earth-fault protection (directional and non-directional)
• Feeder overload protection
Overhead line protection Incomer protection with fault locator Line protection with line differential
and distance functions
DM105546
DM105547
DM105548
P3F30
P3U30 P3F30
P3L30
P3L30
Motor protection
• Motor overcurrent and earth-fault overcurrent
• Thermal overload
• Motor start-up supervision
• Motor restart inhibition
Motor protection without voltage Motor protection with voltage Motor protection with differential
monitoring monitoring function
DM105549
DM105550
DM105551
P3U20 P3M30
P3U30 P3U30 P3M30 P3M32
RTD
module
DM105553
P3U30 P3M30
P3M32
26
26 63
63 49T
49T
RTD
module
DM105555
DM105556
P3U10
P3U20 P3U30 P3F30
P3U20 P3F30 P3F30
P3U30
P3U30
26 26 26
63 63 63
49T 49T
RTD
module
• Directional earth-fault overcurrent for • Temperature measurement (ambient, oil) • Over and undervoltage protection
impedance earthed or compensated
neutral systems
Transformer feeder protection with additional current measurement Transformer feeder protection with
differential function
DM105559
DM105558
DM105557
26 26 26
63 63 63
49T 49T 49T
DM105561
DM105562
P3U10 P3U10
P3U20 P3F30 P3U20 P3F30 P3U30 P3F30
P3U30 P3U30
• Transformer earth-fault overcurrent • Earth-fault overcurrent for transformer • Over and undervoltage protection
and back-up protection • Power and energy measurement
• Min and max demand values over the last
31 days and 12 months
DM105564
P3T32
DM105566
DM105565
26
26
63
63
49T
49T
P3U30 P3G30
P3U30 P3G30
• Earth-fault overcurrent protection of the supplied network • Earth-fault overcurrent protection of the generator
Note: monitoring of generator insulation must be ensured by • Earth-fault overcurrent protection of the supplied network
another device
26
26
63
63
49T
49T
P3G30
P3U30 P3G30
• Earth-fault overcurrent protection of the transformer • Earth-fault overcurrent protection of the generator and the
• Neutral voltage displacement to detect transformer earth-fault transformer
when CB is open • Neutral voltage displacement to detect transformer earth-fault
• Synchro-check when CB is open
Note: monitoring of generator insulation must be ensured by • Synchro-check
another device
DM105570
DM105571
26
63
49T
• Earth-fault overcurrent protection of the • Stator earth-fault detection • Stator earth-fault detection
generator when coupled • Differential protection • Differential protection
• Neutral voltage displacement to detect • Restricted earth-fault protection
generator earth-fault when CB is open (high impedance)
• Synchro-check
DM105573
DM105574
P3U10
P3U20
P3U30 P3U30
P3F30
P3U10
P3U20
P3U30
HMI/
SCADA
This architecture allows you to connect HMI/SCADA to a set of Easergy
protection relays using a multi-drop serial communication link with master-slave
communication.
Serial Daisy chain
link
Available protocols:
• Modbus RTU
• IEC 60870-5-101
• IEC 60870-5-103
Relay 1 Relay 2 Relay n (n max= 32)
• DNP3
• Profibus
• SPAbus
HMI/ This architecture allows you to connect a set of Easergy protection relays directly to
SCADA
an Ethernet network.
Available protocols:
• IEC 61850
• IEC 60870-5-101
• DNP3
Ethernet
Network • Modbus
• EtherNet/IP
Ethernet Ethernet
switch switch Note: It is possible to mix on the same Ethernet network the IEC 61850 protocol
with any of the 4 other protocols.
This allows you to use the GOOSE messages between relays together with another
protocol for communication to SCADA.
The Easergy P3 relay handles the IEC 61850 station bus, in compliance with
standards IEC 61850-6, 7-1, 7-2, 7-3, 7-4 and 8-1 Ed.1 or Ed.2, according to
configuration.
Architecture example 1
DM102975
Panel Ethernet
switch Easergy
HMI Pro
Switchboard internal network
This architecture allows fast GOOSE communication between Easergy protection
Ethernet
relays of the switchboard, thus avoiding costly wiring. Typical uses are logic
discrimination, load shedding, etc.
GOOSE GOOSE
messages messages
In addition, a panel HMI featuring a web browser can be used to monitor and
control the entire switchboard.
A spare connection on the panel Ethernet switch can also be provided for
connecting the Easergy Pro.
Architecture example 2
DM105575
HMI/
SCADA
Connection to SCADA using serial lines and legacy protocols
This architecture allows you to connect HMI/SCADA to a set of Easergy
protection relays using a multi-drop serial communication link with master-slave
Daisy chain
Serial
link
communication protocols such as Modbus-RTU, DNP3, or IEC 61870-5-103.
The RS485 serial communication port of the Easergy protection relay enables
simple daisy chaining wiring thanks to its 2 RJ45 connectors, suited for 2-wire or
4-wire cabling. A termination module is plugged into the last connection. As an
alternative, the fiber optic serial communication port can be used.
Relay 1 Relay 2 Relay n (n max= 32)
Architecture example 3
DM105576
HMI/
SCADA
Sub-
Network
HMI/
SCADA
RSTP (Rapid Spanning Tree Protocol)
DM105577
The principle of RSTP is to virtually cut all links that are not necessary at a given
time, changing the meshed topology into a tree topology.
The main advantage of RSTP is that it is widespread and works on any network
Ethernet Ethernet
switch switch topology. On the other hand, RSTP takes seconds to reconfigure the network in
case of network interruption.
HMI/
SCADA
Network A Network B
The receiving device is in charge of eliminating the redundant frame if it is
received.
PRP features a 0 ms recovery time in case of lost of failed frame.
PRP is supported by Easergy P3 relays.
Ethernet ports
Protocol IEC 61850 Ethernet/IP FTP
Real-time data
Measurement -
Alarms and status -
Controls -
Time-stamped events -
Historical data
Disturbance records -
Setting management
Setting group change -
Serial Ports
Protocol IEC 60870-5-103 Profibus SPAbus
Real time data
Measurement
Alarms and status
Controls
Time-stamped events
Historical data
Disturbance records - -
Setting management
Setting group change
Settings - -
Engineering system
DM105579
Easergy web-HMI
In addition to eSetup Easergy Pro, most of the resources of the relay can be
Safe Repository and
Schneider Electric web accessed with a standard web browser, using the web pages embedded into the
relay.
System
.icd file configurator
.icd file
Safe Repository and When the configuration of an Easergy protection relay is done, setting tool can
Schneider Electric web
generate IED capability file. This file can be used by the system configurator.
ZONE 1
= Arc Sensor
ZONE 2
ZONE 3
T1
S1
F
T1
S2
S1 S3 S1 S1 S1 S1
T1
S2
T1
S2
T1
S2
T1
S2
T1
S2
A B C D E
S3 S3 S3 S3 S3
lncomer cable zone
lncomer circuit breaker zone
Busbar zone
Feeder circuit breaker zone
Feeder cable zone
Light information via BIO L> (feeder cable and circuit breaker)
Light information via BIO L> (incomer busbar and circuit breaker)
ln this application example, the arc flash sensor for zone is connected to device A. If the sensor
detects a fault and simultaneously, device A detects an overcurrent signal, zone is isolated by the
outgoing feeder breaker.
The arc flash sensor for the second feeder zone is connected to device B, and it operates the same
way. The arc flash sensors for zones and are connected to device A, B, C, D, E and F. If a sensor
detects a fault in zone or , the light-only signal is transferred to device F which also detects the
overcurrent and then trips the main circuit breaker.
An arc flash fault in zone or does not necessarily activate the current detection in device F.
However, arc flash detection can be achieved by using the light-only principle, or alternatively, the
light detection signal can be transferred to device G. If an arc flash occurs in the cable termination or
incomer circuit breaker in zone or , the fault is cleared by an overcurrent signal.
T1
DM107274
S1
T1
F
T1 T1 T1 T1 T1
S1 A S1 B S1 C S1 D S1 E
lncomer cable zone
Busbarzone
Feeder circuit breaker zone
Feeder cable zone
Light information via BIO L> (incomer busbar and circuit breaker)
Light information via BIO L> (feeder cable and circuit breaker)
The fiber-loop arc flash sensor for zone is connected to device A. If the sensor detects a fault and
simultaneously, device A detects an overcurrent signal, zone is isolated by the outgoing feeder
breaker.
For the other feeders, the fiber-loop arc flash sensors monitoring zone are connected to the
appropriate feeder relays and they operate the same way as feeder A.
The fiber loop arc flash sensors for zones , and are connected to device F. If a sensor detects a
fault in zone , or and simultaneously, device F detects an overcurrent signal, the fault is cleared
by the incoming breaker operation.
Device G measures the overcurrent and receives light detection signais from zones , , and . lt
trips the substation if device F is unable to measure the overcurrent.
Easergy P3 protection relays can work with both resistive divider and capacitive
divider LPVTs.
Low Power Current Transformer (LPCT) is a magnetic sensor with integrated shunt
providing a voltage output (mV) which represents the primary current (A). LPCTs
provide a low voltage output signal compatible with Easergy P3 protection relays.
Presentation 34
Functional view 36
Communication protocols 45
Programmable stages 46
Connection diagram 48
Model selection 51
The Easergy P3 Standard protection relay has been developed to meet your standard protection needs
for building, distribution utilities, and industrial applications. Thanks to its optimized and flexible design,
the Easergy P3 Standard provides an excellent solution for various protection applications.
Robust
• Best-in class reliability based on 100+ years of experience in Sepam,
MiCOM and Vamp relays
• Strong tests performed in international laboratories
• Compliant to IEC electro-mechanical standards
• Designed for demanding industrial conditions with conformal-coated
printed circuit boards
Easergy P3 Standard
with panel seal cover
REL52833
Easergy P3 is designed to cover all the standard applications with only one device: the
Universal Protection.
DM105529
U
Feeder
U
U U U U
M
Capacitor Motor Feeder Transformer
eSetup
Easergy Pro
REL52822
HMI interface
Function key F1 Mimic Diagram F2
I1: 0.0A
LED F1 LED F2 USB
I2: 0.0A
0 Local Port
ON I3: 0.0A Service
LED A P : 0.0W LED B
V : 0.0V
1 LED C LED D
LED E LED F
Control buttons LED G LED H
Programmable Logic
Setting groups:4
H2/H5
SOTF
79 74 86 60 99
CLPU
48
37 51LR 66
59C
50BF
59N
50 67NI
51
67N
51C
50N
49 50G X3 Connector
DI1 DI2
51N
46 51G SF T1 T2 T3 T4 A1
I1 / I2 / I3 Io V/V0
Analog measurement card Power Supply
Current input Voltage input
I1 I2 I3 Io - V1 - - -
eSetup
DM105584
Easergy Pro
REL52822
HMI interface
Function key F1 Mimic Diagram F2
I1: 0.0A
LED F1 LED F2 USB
I2: 0.0A Comm. interface - X4
0 Local Port
ON I3: 0.0A Service
Redundancy Protocols
LED A P : 0.0W LED B • RSTP • IEC 61850
V : 0.0V • PRP • Modbus
1 LED C LED D
• DNP3.0
LED E LED F Two protocols • IEC-101
at the same time WebServer • Ethernet/IP
Control buttons LED G LED H
Comm. interface - X4
Programmable Logic Redundancy LC LC Protocols
• RSTP • IEC 61850
• PRP • Modbus
Inputs AND TIMER OR COUNTER XOR Output • DNP3.0
Two protocols • IEC-101
at the same time WebServer • Ethernet/IP
RS232
50BF
59N Protocols
Modbus
Protocols
Modbus
DNP3.0 DNP3.0
IEC-103 IEC-103
50 67NI SPAbus
RS485
51 X4 Connector Serial
67N
Serial network
DI3 DI4 DI5 DI6 DI7 DI8 DI9 DI10
51C
OR REL52812 REL52813
REL52814
50N RS485 RS485
Rx
49 50G X3 Connector Tx
51N Rx
I1 I2 I3 Io - V1 - - - RTD CH06
mA In4
RTD CH06
eSetup
DM105585
Easergy Pro
REL52822
HMI interface
Function key F1 Mimic Diagram F2
I1: 0.0A
LED F1 LED F2 USB
I2: 0.0A Comm. interface - X4
0 Local Port
ON I3: 0.0A Service
Redundancy Protocols
LED A P : 0.0W LED B • RSTP • IEC 61850
V : 0.0V • PRP • Modbus
1 LED C LED D
• DNP3.0
LED E LED F Two protocols • IEC-101
at the same time WebServer • Ethernet/IP
Control buttons LED G LED H
Comm. interface - X4
Programmable Logic Redundancy LC LC Protocols
• RSTP • IEC 61850
• PRP • Modbus
Inputs AND TIMER OR COUNTER XOR Output • DNP3.0
Two protocols • IEC-101
at the same time WebServer • Ethernet/IP
RS232
59C
50BF X5 Connector
DI13 DI16
Protocols Protocols
59N Modbus Modbus
RS485
81R
51 X4 Connector Serial
67N 25
Serial network
81 DI3 DI4 DI5 DI6 DI7 DI8 DI9 DI10
51C 81U OR REL52812 REL52813
REL52814
50N RS485 RS485
Rx
49 50G 59 X3 Connector Tx
51N Rx
I1 I2 I3 Io V1 V2 V3 V0 RTD CH06
mA In4
RTD CH06
PM106501
PM106338
Easergy P3U10 Easergy P3U20 Easergy P3U30
Withdrawable connectors
PM106500
DM105587
DM105588
mm 13.25
in 0.52 144.5 6
5.69 12 6
Weight (maximum)
Easergy P3U10 / P3U20 / P3U30 2.5 Kg (5.519 Ib) 4.9
DM105590 9.25 5.0
Degree of protection (IEC 60529) 0.36 0.2
IP54 Front panel / IP20 Rear side
28.5
1.12
2 E a s e rg
y
9.5
0.37
120
139 4.72
5.47
OK
F2
9.5 F1
0.37 O
1.
0.040-10
I
- 0.3
9
Panel mounting
A 2.5 124.5
DM105638
0.1 4.90
A B 155
With screw 6.10
214 mm / 8.43’’ 192 mm / 7.6’’
connector
With ring-lug
connector
226 mm / 8.90’’ 204 mm / 8.0’’
137 B
5.39
A
DM105639
A B 124.5
With screw 110 4.90
connector
214 mm / 8.43’’ 147 mm / 5.8’’ 4.3
With ring-lug
226 mm / 8.90’’ 159 mm / 6.2’’
connector B
137
5.39
Raising frame
Ref: VYX860-
REL52834 2.5
0.1
Raising frame REL52834 Raising frame REL52834
Analog inputs
Measuring Input Consump- Rated 1-second 10-second
range Impedance tion thermal overload overload
withstand
Phase Current Input 5A CT 0.05 – 250 A 0.003 Ohm 0.075 VA 20 A 500 A 100 A
Configurable for CT secondaries 1 to 10A (Continuously)
Residual Current Input (I0) 5A CT 0.015 – 50 A 0.003 Ohm 0.075 VA 20 A 500 A 100 A
Configurable for CT secondaries 0.1 to 10A (Continuously)
Residual Current Input (I0) 1A CT 0.003 – 10 A 0.02 Ohm 0.02 VA 4A 100 A 20 A
Configurable for CT secondaries 0.1 to 10.0A (Continuously)
Residual Current Input (I0) 0.2A CSH sensor 0.0006 – 2 A 0.02 Ohm 0.02 VA 0.8 A 20 A 4A
Configurable for CT secondaries 0.1 to 10.0A (Continuously)
Voltage Input 0.5 – 190 V n.a. < 0.5 VA 250V n.a. 600 V
Configurable for VT secondaries 50 to 120V (100 V / 110 V) (Continuously)
Digital Input
Nominal operation voltage DI1 to DI16 24 to 230 V ac/dc 110 to 230 V ac/dc 220 to 230 V ac/dc
Typical switching threshold 12 V dc 75 V dc 155 V dc
At state 1 ≥ 19.2 V dc ≥ 88 V dc ≥ 176 V dc
Input limit voltage
At state 0 < 10.0 V dc < 60 V dc < 140 V dc
Frequency 45 to 65 Hz 45 to 65 Hz 45 to 65 Hz
Typical consumption <4 mA (typical approx. 3 mA)
Voltage withstand 255 V ac/dc
Digital Output
Type of contact Control and Trip contact, Tx Signal contact, A1 Signal Contact, SF
Rated Voltage 250 V ac/dc 250 V ac/dc 250 V ac/dc
Continuous current 5A 5A 5A
AC 2.000 VA 2.000 VA 2.000 VA
Breaking at 48 V dc 1.15 A 1A 1A
DC
capacity at 110 V dc 0.5 A 0.3 A 0.3 A
(L/R=40ms)
at 220 V dc 0.25 A 0.15 A 0.15 A
≤ 0.5 s 30 A 30 A -
Making capacity
≤ 3.0 s 15 A 15 A -
Minimum making capacity 100 mA @ 24 Vac/dc 100 mA @ 24 Vac/dc 100 mA @ 24 Vac/dc
Typical operation time <8 ms - -
Contact material AgNi 90/10 AgNi 0.15 gold plated AgNi 0.15
Power supply
Nominal Voltage 48 to 230 Vac/dc 24 to 48 Vdc (2)
Range -20% / +10% (38.4 to 253 Vac/dc) ±20% (19.2 to 57.6 Vdc) (2)
25 A with time constant of 1000 µs
Inrush current (DC) 25 A with time constant of 750 µs
15 A with time constant of 500 µs
Normal conditions <15 W (<30 VA)
Power consumption
Output relays activated <25 W (<50 VA)
Acceptable momentary outages <50 ms (110 V dc)
(1) 78,750 in
(2) Check the available power supply range from the device’s serial number label
Electromagnetic compatibility
Standard and test class/level Test value
Emission tests IEC/EN 60255-26 (ed3)
Conducted EN 55022, Class A / CISPR 22 0.15 – 30 MHz
Emitted EN 55011, Class A / CISPR 11 30 – 1000 MHz
Immunity IEC/EN 60255-26 (ed3)
Slow damped oscillatory wave 1MHz IEC/EN 61000-4-18 ±2.5kVp CM
±2.5kVp DM
Fast damped oscillatory wave 3MHz, 10 IEC/EN 61000-4-18 ±2.5kVp CM
MHz and 30 MHz
Static discharge (ESD) IEC/EN 61000-4-2 Level 4 ±8 kV contact
±15 kV air
Emitted HF field IEC/EN 61000-4-3 Level 3 80 - 2700 MHz, 10 V/m
Fast transients (EFT) IEC/EN 61000-4-4 Level 4 ±4 kV, 5/50 ns, 5 kHz
Surge IEC/EN 61000-4-5 Level 3 ±2 kV, 1.2/50 µs, CM
±1 kV, 1.2/50 µs, DM
Conducted HF field IEC/EN 61000-4-6 Level 3 0.15 - 80 MHz, 10 Vrms
Power-frequency magnetic field IEC/EN 61000-4-8 300 A/m (continuous) 1000 A/m 1 – 3s
Pulse magnetic field IEC/EN 61000-4-9 Level 5 1000A/m, 1.2/50 µs
ac and dc voltage dips IEC/EN 61000-4-29, IEC/EN 61000-4-11 0% of rated voltage
• ac: ≥ 0.5 cycle
• dc: ≥ 10 ms
40% of rated voltage
• ac: 10 cycles
• dc: 200 ms
70% of rated voltage
• ac: 25 cycles
• dc: 500 ms
ac and dc voltage interruptions IEC/EN 61000-4-29, IEC/EN 61000-4-11 100% interruption
• ac: 250 cycles
• dc: 5 s
Voltage alternative component IEC/EN 61000-4-17 15% of operating voltage (dc) / 10 min
Mechanical robustness
Standard and test class/level Test value
In operation
Vibrations IEC 60255-21-1, Class II / IEC 60068-2-6, Fc 1 Gn, 10 Hz – 150 Hz
Shocks IEC 60255-21-2, Class II / IEC 60068-2-27, Ea 10 Gn / 11 ms
Seismic IEC 60255-21-3 Method A, Class II 2G horizontal / 1G vertical , 1–35 Hz
De-energized
Vibrations IEC 60255-21-1, Class II / IEC 60068-2-6, Fc 2 Gn, 10 Hz – 150 Hz
Shocks IEC 60255-21-2, Class II / IEC 60068-2-27, Ea 30 Gn / 11 ms
Bump IEC 60255-21-2, Class II / IEC 60068-2-27, Ea 20 Gn / 16 ms
Environment tests
Standard and test class/level Test value
In operation
Dry heat EN / IEC 60068-2-2, Bd 70°C (158°F)
Cold EN / IEC 60068-2-1, Ad -40°C (-40°F)
Damp heat, cyclic EN / IEC 60068-2-30, Db From 25°C (77°F) to 55°C (131°F)
From 93% RH to 98% RH
Testing duration: 6 days
Damp heat, static EN / IEC 60068-2-78, Cab 40°C (104°F)
93% RH
Testing duration: 10 days
Change of temperature IEC / EN 60068-2-14, Nb Lower temp -40°C (-40°F)
Upper temp 70°C (158°F)
5 cycles
Flowing mixed gas corrosion test, method 1 IEC 60068-2-60, Ke 25°C (77°F), 75% RH, 21 days 100 ppb H2S,
500 ppb
Flowing mixed gas corrosion test, method 4 IEC 60068-2-60, Ke 25°C (77°F), 75% RH, 21 days 10 ppb H2S,
200 ppb , 10 ppb , 200 ppb
In storage
Dry heat EN / IEC 60068-2-2, Bb 70°C (158°F)
Cold EN / IEC 60068-2-1, Ab -40°C (-40°F)
Environmental conditions
Safety
Standard and test class/level Test value
Electrical safety tests
Impulse voltage withstand IEC/EN 60255-27 5 kV, 1.2/50 µs, 0.5 J
1 kV, 1.2/50 µs, 0.5 J Communication
Dielectric test IEC/EN 60255-27 2 kV, 50 Hz
0.5 kV, 50 Hz Communication
Insulation resistance IEC/EN 60255-27
Protective bonding resistance IEC/EN 60255-27
Clearance and creepage distance Design criteria for distances as per IEC 60255-27 Annex C
(pollution degree 2, overvoltage category 3)
Power supply burden IEC 60255-1
When the devices are connecting in Ethernet link and demand for higher availability,
Easergy P3 Standard can use Rapid Spanning Tree Protocol (RSTP) or Parallel
Redundancy Protocol (PRP) to recover from a network failure.
Easergy P3 web-HMI
A webserver is available in Easergy P3 Standard to get information from the device
to monitor all data, send commands, and change protection settings.
Easergy web-HMI
MV network
DM105591
HMI interface
Function key F1 Mimic Diagram F2
I1: 0.0A
LED F1 LED F2 USB
I2: 0.0A
CT 0 Local Port
ON I3: 0.0A Service
LED A P : 0.0W LED B
V : 0.0V
I LED C LED D
LED E LED F
Control buttons LED G LED H
Nominal voltage
Alarm contact
Trip Circuit for Trip circuit
Supervision failure
Latching contact Trip control
ANSI 86 Order contact
A1
DI 2 DI 1
T3
This electrical schematic
can facilitate the IEC
61850 implementation 0
52a 52b
because all the logics
are determined by the 1
protection unit that will
Open/Close
make the decisions and Mechanical CLOSE OPEN
if necessary can send command COIL COIL
Circuit Breaker
GOOSE messages to
other units.
DM105593
- NEVER work alone.
- turn off all power supplying this equipment before
1
working on or inside it. Consider all sources of
0
power, including the possibility of backfeeding.
- always use a properly rated voltage sensing
device to confirm that all power is off.
- start by connecting the device to the protective
earth and to the functional earth.
3 20
- screw tight all terminals, even those not in use. DI1
4 V1 19
Failure to follow these instructions will result in 5 USB 18
death or serious injury. DI2
Local Port V2 17
6 16
17 V3 15
T1
16
T5 14
15
T2
13
14
X3 T6 12
13 T3
11
12
11 X5 T7 10
T4
10 9
8
8 DI16 7
9 A1
DI15 6
7 Easergy DI14 5
19
20
SF P3U30 4
DI13 3
18
DI12 2
X1 DI11 1
1
2 I1 14
3 DI10 13
4 I2 DI9 12
5 11
6 I3 DI8 10
DI7 9
7 8
8 5A DI6
7
9 OR Io X4 6
1A DI5
OR 10 5
4
DI4
1 3
2
V4
2 DI3
1
3
X2
4
X4
COM
Note: Dangerous environment, make sure to read the all information, including
warning instructions (left).
DM105594
- NEVER work alone.
- turn off all power supplying this equipment before
working on or inside it. Consider all sources of 1
3
4
X2
X4
Note: Dangerous environment, make sure to read the all information, including
warning instructions (left).
DM105595
after reading this entire set of instructions.
- NEVER work alone. 1
0
14
Failure to follow these instructions will result in 15
T2
T5
13
death or serious injury. 14
13
X3 T6 12
T3
11
12
11 X5 T7 10
T4
10 9
8
8 DI16 7
9 A1
DI15 6
7 Easergy DI14 5
19
20
SF P3U30 4
DI13 3
18
DI12 2
X1 DI11 1
1
2 I1 14
3 DI10 13
4 I2 DI9 12
5 11
6 I3 DI8 10
DI7 9
7 8
8 5A DI6
7
9 OR Io X4 6
OR DI5
10 1A 5
4
DI4
1 3
2
V4
2 DI3
1
3
X2
4
X4
Note: Dangerous environment, make sure to read the all information, including
warning instructions (left).
PM106367
P3U10
Page 115
Standard application
PM106367
P3U20
Page 116
Standard application
PM106367
P3U30
Page 117
Standard application
Go to web configurator
Presentation 54
Functional view 56
Communication 73
Communication protocols 73
Programmable stages 74
Connection diagrams 77
Model selection 80
The Easergy P3 advanced is a protection relay developed to satisfy the protection needs for buildings,
distribution utilities, and industrial applications. Thanks to a wide scope of functionality and Ethernet
communication, Easergy P3 advanced provides a cost-effective solution for the upper end of
protection requirements in these applications.
efficiency with rapid ordering, • All communication protocols embedded on serial and Ethernet links,
including IEC 61850 ed.1 and ed. 2
configuration, and operations for an
• Increased number of inputs and outputs
unparalleled digital experience provided
with Easergy P3.
Robust
• Best-in class reliability based on 100+ years of experience in Sepam,
MiCOM and Vamp relays
• Strong tests performed in international laboratories
• Compliant with IEC electro-mechanical standards
DM105530
Line Differential
& Distance G
Generator
L G Differential
U M T
Feeder
M Motor
Differential
Transformer
Differential
eSetup
Easergy Pro
REL52822
HMI interface ON Service
Mimic Diagram
LED A LED B
I 0 LED C LED D USB
LED E I1: 0.0A LED F Local Port Comm. interface - Slot 9
Control buttons LED G I2: 0.0A LED H Redundancy Protocols
• RSTP • IEC 61850
LED I I3: 0.0A LED J
• PRP • Modbus
LED K P : 0.0W LED L • DNP3.0
Two protocols • IEC-101
LED M LED N
F1 V : 0.0V F2 at the same time WebServer • Ethernet/IP
Function key
LED F1 LED F2
Comm. interface - Slot 9
Programmable Logic Redundancy LC LC Protocols
• RSTP • IEC 61850
• PRP • Modbus
Inputs AND TIMER OR COUNTER XOR Output • DNP3.0
Two protocols • IEC-101
at the same time WebServer • Ethernet/IP
67 21FL 37P
I/O card G - Slot 5
DI19 DI20 DI21 DI22 DI23 DI24
32 Connect to RS232 port
T25 T26 T27 T28
REL52820 REL52816
REL52819
RS232
RS232
47
50BF I/O card G - Slot 4
DI13 DI14 DI15 DI16 DI17 DI18 Protocols Protocols
59N Modbus Modbus
DNP3.0 DNP3.0
50 T21 T22 T23 T24 IEC-103 IEC-103
67NI SPAbus
RS485
81R
51 I/O card G - Slot 3 Serial
67N 25 DI7 DI8 DI9 DI10 DI11 DI12
Serial network
51C 81 T17 T18 T19 T20
81U OR REL52812 REL52813
REL52814
50N RS485 RS485
Rx
49 50G I/O card G - Slot 2
59 Tx
PTC
DI1 DI2 DI3 DI4 DI5 D6 Fiber
51N Rx
eSetup
Easergy Pro
REL52822
HMI interface ON Service
Mimic Diagram
LED A LED B
I 0 LED C LED D USB
LED E I1: 0.0A LED F Local Port Comm. interface - Slot 9
Control buttons LED G I2: 0.0A LED H Redundancy Protocols
• RSTP • IEC 61850
LED I I3: 0.0A LED J
• PRP • Modbus
LED K P : 0.0W LED L • DNP3.0
Two protocols • IEC-101
LED M LED N
F1 V : 0.0V F2 at the same time WebServer • Ethernet/IP
Function key
LED F1 LED F2
Comm. interface - Slot 9
Programmable Logic Redundancy LC LC Protocols
• RSTP • IEC 61850
• PRP • Modbus
Inputs AND TIMER OR COUNTER XOR Output • DNP3.0
Two protocols • IEC-101
at the same time WebServer • Ethernet/IP
RS232
RS232
50BF I/O card G - Slot 4
DI13 DI14 DI15 DI16 DI17 DI18 Protocols Protocols
59N Modbus Modbus
DNP3.0 DNP3.0
50 T21 T22 T23 T24 IEC-103 IEC-103
SPAbus
RS485
81R
51 I/O card G - Slot 3 Serial
67N 25 DI7 DI8 DI9 DI10 DI11 DI12
Serial network
51C 81 T17 T18 T19 T20
81U OR REL52812 REL52813
REL52814
50N RS485 RS485
Rx
49 50G I/O card G - Slot 2
59 Tx
PTC
DI1 DI2 DI3 DI4 DI5 D6 Fiber
51N Rx
M RTD CH12
OR
RTD CH12
eSetup
Easergy Pro
REL52822
HMI interface ON Service
Mimic Diagram
LED A LED B
I 0 LED C LED D USB
LED E I1: 0.0A LED F Local Port Comm. interface - Slot 9
Control buttons LED G I2: 0.0A LED H Redundancy Protocols
• RSTP • IEC 61850
LED I I3: 0.0A LED J
• PRP • Modbus
LED K P : 0.0W LED L • DNP3.0
Two protocols • IEC-101
LED M LED N
F1 V : 0.0V F2 at the same time WebServer • Ethernet/IP
Function key
LED F1 LED F2
Comm. interface - Slot 9
Programmable Logic Redundancy LC LC Protocols
• RSTP • IEC 61850
• PRP • Modbus
Inputs AND TIMER OR COUNTER XOR Output • DNP3.0
Two protocols • IEC-101
at the same time WebServer • Ethernet/IP
RS232
RS232
47
50BF Analog measur. card - Slot 4
Protocols Protocols
59N
IL1 IL2 IL3 Io3
Modbus Modbus
DNP3.0 DNP3.0
50 IEC-103 IEC-103
SPAbus
RS485
81R
51 I/O card G - Slot 3 Serial
67N 25 DI7 DI8 DI9 DI10 DI11 DI12
Serial network
51C 81 T17 T18 T19 T20
81U OR REL52812 REL52813
REL52814
50N RS485 RS485
Rx
49 50G I/O card G - Slot 2
59 Tx
PTC
DI1 DI2 DI3 DI4 DI5 D6 Fiber
51N Rx
M RTD CH12
OR
RTD CH12
eSetup
Easergy Pro
REL52822
HMI interface ON Service
Mimic Diagram
LED A LED B
I 0 LED C LED D USB
LED E I1: 0.0A LED F Local Port Comm. interface - Slot 9
Control buttons LED G I2: 0.0A LED H Redundancy Protocols
• RSTP • IEC 61850
LED I I3: 0.0A LED J
• PRP • Modbus
LED K P : 0.0W LED L • DNP3.0
Two protocols • IEC-101
LED M LED N
F1 V : 0.0V F2 at the same time WebServer • Ethernet/IP
Function key
LED F1 LED F2
Comm. interface - Slot 9
Programmable Logic Redundancy LC LC Protocols
• RSTP • IEC 61850
• PRP • Modbus
Inputs AND TIMER OR COUNTER XOR Output • DNP3.0
Two protocols • IEC-101
at the same time WebServer • Ethernet/IP
RS232
RS232
24
50BF Analog measur. card - Slot 4
Protocols Protocols
RS485
81R
51 I/O card G - Slot 3 Serial
67N 25 DI7 DI8 DI9 DI10 DI11 DI12
Serial network
81 T17 T18 T19 T20
81U OR REL52812 REL52813
REL52814
50N RS485 RS485
Rx
49 50G I/O card G - Slot 2
59 Tx
PTC
DI1 DI2 DI3 DI4 DI5 D6 Fiber
51N Rx
46 51G 27
RTD CH01
Tx
RTD CH01
T13 T14 T15 T16
27P RTD CH02 RTD CH02
mA In1
RTD CH03 RTD CH03
Analog measurement card - Slot 8 Power Supply - Slot 1 mA In2
eSetup
Easergy Pro
REL52822
HMI interface ON Service
Mimic Diagram
LED A LED B
I 0 LED C LED D USB
LED E I1: 0.0A LED F Local Port Comm. interface - Slot 9
Control buttons LED G I2: 0.0A LED H Redundancy Protocols
• RSTP • IEC 61850
LED I I3: 0.0A LED J
• PRP • Modbus
LED K P : 0.0W LED L • DNP3.0
Two protocols • IEC-101
LED M LED N
F1 V : 0.0V F2 at the same time WebServer • Ethernet/IP
Function key
LED F1 LED F2
Comm. interface - Slot 9
Programmable Logic Redundancy LC LC Protocols
• RSTP • IEC 61850
• PRP • Modbus
Inputs AND TIMER OR COUNTER XOR Output • DNP3.0
Two protocols • IEC-101
at the same time WebServer • Ethernet/IP
RS232
RS232
50BF I/O card G - Slot 4
59N DI13 DI14 DI15 DI16 DI17 DI18 Protocols Protocols
Modbus Modbus
DNP3.0 DNP3.0
50 67NI T21 T22 T23 T24 IEC-103 IEC-103
SPAbus
RS485
81R
51 I/O card G - Slot 3 Serial
67N 25 DI7 DI8 DI9 DI10 DI11 DI12
Serial network
51C 81 T17 T18 T19 T20
81U OR REL52812 REL52813
OR
Circuit Breaker control
eSetup
Easergy Pro
REL52822
HMI interface ON Service
Mimic Diagram
LED A LED B
I 0 LED C LED D USB
LED E I1: 0.0A LED F Local Port Comm. interface - Slot 9
Control buttons LED G I2: 0.0A LED H Redundancy Protocols
• RSTP • IEC 61850
LED I I3: 0.0A LED J
• PRP • Modbus
LED K P : 0.0W LED L • DNP3.0
Two protocols • IEC-101
LED M LED N
F1 V : 0.0V F2 at the same time WebServer • Ethernet/IP
Function key
LED F1 LED F2
Comm. interface - Slot 9
Programmable Logic Redundancy LC LC Protocols
• RSTP • IEC 61850
• PRP • Modbus
Inputs AND TIMER OR COUNTER XOR Output • DNP3.0
Two protocols • IEC-101
at the same time WebServer • Ethernet/IP
RS232
RS232
47
50BF I/O card G - Slot 4
DI13 DI14 DI15 DI16 DI17 DI18 Protocols Protocols
Modbus Modbus
59N DNP3.0 DNP3.0
50 T21 T22 T23 T24 IEC-103 IEC-103
SPAbus
RS485
81R
51 I/O card G - Slot 3 Serial
67N 25 DI7 DI8 DI9 DI10 DI11 DI12
Serial network
27N 81 T17 T18 T19 T20
64G 81U OR REL52812 REL52813
REL52814
50N RS485 RS485
Rx
49 50G I/O card G - Slot 2
51V 59 Tx
PTC
DI1 DI2 DI3 DI4 DI5 D6 Fiber
51N Rx
46 51G 40 27
RTD CH01
Tx
RTD CH01
T13 T14 T15 T16
32Q 27P RTD CH02 RTD CH02
mA In1
RTD CH03 RTD CH03
Analog measurement card - Slot 8 Power Supply - Slot 1 mA In2
G RTD CH12
OR
RTD CH12
eSetup
Easergy Pro
REL52822
HMI interface ON Service
Mimic Diagram
LED A LED B
I 0 LED C LED D USB
LED E I1: 0.0A LED F Local Port Comm. interface - Slot 9
Control buttons LED G I2: 0.0A LED H Redundancy Protocols
• RSTP • IEC 61850
LED I I3: 0.0A LED J
• PRP • Modbus
LED K P : 0.0W LED L • DNP3.0
Two protocols • IEC-101
LED M LED N
F1 V : 0.0V F2 at the same time WebServer • Ethernet/IP
Function key
LED F1 LED F2
Comm. interface - Slot 9
Programmable Logic Redundancy LC LC Protocols
• RSTP • IEC 61850
• PRP • Modbus
Inputs AND TIMER OR COUNTER XOR Output • DNP3.0
Two protocols • IEC-101
at the same time WebServer • Ethernet/IP
RS232
RS232
47
50BF Analog measur. card - Slot 4
Protocols Protocols
Modbus Modbus
59N IL'1 IL'2 IL'3 Io3 DNP3.0 DNP3.0
50 IEC-103 IEC-103
SPAbus
RS485
81R
51 I/O card G - Slot 3 Serial
67N 25 DI7 DI8 DI9 DI10 DI11 DI12
Serial network
27N 81 T17 T18 T19 T20
64G 81U OR REL52812 REL52813
REL52814
50N RS485 RS485
Rx
49 50G 51V 59 I/O card G - Slot 2 Tx
PTC
46 51G 40 27
RTD CH01
Tx
RTD CH01
G RTD CH12
OR
RTD CH12
DM102188
Easergy P3 Advanced measures fault
current, and with arc protection, also
Arc flash sensors
light via arc sensor channels that provide
1
monitoring for the whole switchgear.
PM106502
An arc flash is a mass of heat and pressure
caused by a switchgear fault. It not only
causes power outages but can also
result in loss of business and extensive
material damage. If an arc fault occurs in 2
Example of application
The four arc flash sensors can be installed in specific
parts of the switchgear:
1. Busbars compartment
2. Circuit breaker compartment IEC 61850 (GOOSE)
or by wire
3. Current/voltage transformers compartment 4
Cable
1
DM105582
BB
CB CB
2 2
Cable Cable
3 3
Mimic Diagram
operation
All the data you require for a local equipment operation can be displayed on
I1: 0.0A demand:
I2: 0.0A • Display the single line diagram and freely assignable analog values
I3: 0.0A • Display of all measurements
• Display of operation and alarm messages
P : 0.0W • Display and setting of all parameters
V : 0.0V • Password entry to protect parameter and protection settings
Slot 1 2 3 4&5 6 8
PM106503
Slot 1 2 3 4&5 6 8
PM106342
Easergy P3L30 9
PM106504
P3x30 units
This mounting technique allows for a lighter door because the relay’s frame is
installed in the back of the secondary compartment. Communication, DI, and DO
cabling is easier, too, as the door movement does not need to be considered.
In this case, only the communication between IED base and display has to be
wired.
DM105604
Ea se rg y
DM105605
in 264 8.18
10.37
183
Easergy 7.20
177 150
6.97 5.91
247
9.72
Remote HMI 180 199
DM105606
7.09 7.81
199
7.83 150
180 5.91
7.09
Weight (maximum)
Easergy P3 Advanced 4.2 Kg (9.272 Ib) or higher (depends of options)
DM105607
225
8.86
(REL52832) around the collar. This arrangement
reduces the depth inside the compartment by 45 mm
(1.77 in).
Ease rgy
Eas ergy
Eas ergy
152
5.98
1.0
-60
269 253.40
10.59 9.97 24.60
45 223.33 0.97
224
1.77 9.17
8.82
152 153
5.98 6.02
Raising frame REL52832 177 Mounting frame
183
7.0 7.20
Wall mounting
210
DM105608
8.27
Ø5
0.2
18
0.71
11.5
0.45
20 34
0.79 1.34 Eas erg y
3
180
7.09
Ø7
0.28
min. 2.5mm2
Ø 5-8mm
180
7.09
Nut M5
1.5 Nm, 13.3 Ib in
Analog inputs
Rated phase Measuring Input Rated thermal 1-second 10-second
Consumption
current range Impedance withstand overload overload
Phase Current Input (I) 1 A CT 0.02 – 50 A 0.02 Ohm 0.02 VA 4A 100 A 20 A
Slot 8 5 A CT 0.05 – 250 A 0.003 Ohm 0.075 VA 20 A 500 A 100 A
Residual Current Input (I0)
Slot 8 - 5 A CT 0.015 – 50 A 0.003 Ohm 0.075 VA 20 A 500 A 100 A
Configurable for CT secondaries 0.1 to 10A
Residual Current Input (I0’)
Slot 8 - 1 A CT 0.003 – 10 A 0.02 Ohm 0.02 VA 4A 100 A 20 A
Configurable for CT secondaries 0.1 to 10.0A
Residual Current Input (I0’)
Slot 8 - 0.2 A CSH sensor 0.0006 – 2 A 0.02 Ohm 0.02 VA 0.8 A 20 A 4A
Configurable for CT secondaries 0.1 to 10.0A
Phase Current Input - (I’) 1A CT 0.02 – 50 A 0.02 Ohm 0.02 VA 4A 100 A 20 A
Slot 4 (Only for device with
differential overcurrent) 5A CT 0.05 – 250 A 0.003 Ohm 0.075 VA 20 A 500 A 100 A
Residual Current Input (I0’’) 1A CT 0.02 – 50 A 0.02 Ohm 0.02 VA 4A 100 A 20 A
Slot 4 (Only for device with
differential overcurrent) 5A CT 0.05 – 250 A 0.003 Ohm 0.075 VA 20 A 500 A 100 A
Voltage Input 0.5 – 190 V 250 V
n.a. < 0.5 VA n.a. 600 V
Configurable for VT secondaries 50 to 120 V (100V / 110 V) (Continuously)
Maximum current 20 mA
Digital Input
Nominal operation voltage DI1 to DI16 24 to 230 Vac/dc 110 to 230 Vac/dc 220 to 230 Vac/dc
Typical switching threshold 12 Vdc 75 Vdc 155 Vdc
Input limit voltage At state 1 ≥ 19.2 Vdc ≥ 88 Vdc ≥ 176 Vdc
At state 0 < 10.0 Vdc < 60 Vdc < 140 Vdc
Frequency 45 to 65 Hz 45 to 65 Hz 45 to 65 Hz
Typical consumption <4 mA (typical approx. 3 mA)
Voltage withstand 255 V ac/dc
Digital Output
Type of contact Control and Trip contact, Tx Signal contact, A1 Signal Contact, SF
Rated Voltage 250 Vac/dc 250 Vac/dc 250 Vac/dc
Continuous current 5A 5A 5A
Breaking AC 2.000 VA 2.000 VA 2.000 VA
capacity DC at 48 V dc 1.15 A 1A 1A
(L/R=40ms) at 110 V dc 0.5 A 0.3 A 0.3 A
at 220 V dc 0.25 A 0.15 A 0.15 A
Making capacity ≤ 0.5 s 30 A 30 A -
≤ 3.0 s 15 A 15 A -
Minimum making capacity 100 mA @ 24 Vac/dc 100 mA @ 24 Vac/dc 100 mA @ 24 Vac/dc
Typical operation time <8 ms - -
Contact material AgNi 90/10 AgNi 0.15 AgNi 0.15
Power supply
Nominal Voltage 110-240 V ac/dc 24-48 Vdc
Range -20% / +10% (88 to 264 Vac/dc) -20% / +20% (19.2 to 57.6 Vdc)
Inrush current (DC) 25 A with time constant of 1000 µs
25 A with time constant of 750 µs
15 A with time constant of 500 µs
Power consumption Power consumption increases when more I/O or optional I/O or communication cards are used
Max. 50 W
Acceptable momentary outages <50 ms (110 Vdc)
(1) 78,740 in
Disturbance tests
Standard and test class/level Test value
Emission IEC/EN 60255-26 (ed3)
Conducted EN 55022, Class A / CISPR 22 0.15 – 30 MHz
Emitted EN 55011, Class A / CISPR 11 30 – 1000 MHz
Immunity IEC/EN 60255-26 (ed3)
Slow damped oscillatory wave 1MHz IEC/EN 61000-4-18 ±2.5kVp CM
±2.5kVp DM
Fast damped oscillatory wave 3MHz, 10 MHz IEC/EN 61000-4-18 ±2.5kVp CM
and 30 MHz
Static discharge (ESD) IEC/EN 61000-4-2 Level 4 ±8 kV contact
±15 kV air
Emitted HF field IEC/EN 61000-4-3 Level 3 80 - 2700 MHz, 10 V/m
Fast transients (EFT) IEC/EN 61000-4-4 Level 4 ±4 kV, 5/50 ns, 5 kHz
Surge IEC/EN 61000-4-5 Level 4 ±4 kV, 1.2/50 µs, CM
±2 kV, 1.2/50 µs, DM
Conducted HF field IEC/EN 61000-4-6 Level 3 0.15 - 80 MHz, 10 Vrms
Power-frequency magnetic field IEC/EN 61000-4-8 300A/m (continuous) 1000 A/m 1 – 3 s
Pulse magnetic field IEC/EN 61000-4-9 Level 5 1000A/m, 1.2/50 µs
ac and dc voltage dips IEC/EN 61000-4-29, IEC/EN 61000-4-11 0% of rated voltage
• ac: ≥ 0.5 cycle
• dc: ≥ 10 ms
40% of rated voltage
• ac: 10 cycles
• dc: 200 ms
70% of rated voltage
• ac: 25 cycles
• dc: 500 ms
ac and dc voltage interruptions IEC/EN 61000-4-29, IEC/EN 61000-4-11 100% interruption
• ac: 250 cycles
• dc: 5 s
Voltage alternative component IEC/EN 61000-4-17 15% of operating voltage (dc) / 10 min
Mechanical
robustness
Standard and test class/level Test value
In operation
Vibrations IEC 60255-21-1, Class II / IEC 60068-2-6, Fc 1 Gn, 10 Hz – 150 Hz
Shocks IEC 60255-21-2, Class II / IEC 60068-2-27, Ea 10 Gn / 11 ms
Seismic IEC 60255-21-3 Method A, Class II 2G horizontal / 1G vertical , 1–35 Hz
De-energized
Vibrations IEC 60255-21-1, Class II / IEC 60068-2-6, Fc 2 Gn, 10 Hz – 150 Hz
Shocks IEC 60255-21-2, Class II / IEC 60068-2-27, Ea 30 Gn / 11 ms
Bump IEC 60255-21-2, Class II / IEC 60068-2-27, Ea 20 Gn / 16 ms
Electrical safety
Standard and test class/level Test value
In operation
Impulse voltage withstand IEC/EN 60255-27 5 kV, 1.2/50 µs, 0.5 J
1 kV, 1.2/50 µs, 0.5 J Communication
Dielectric test IEC/EN 60255-27 2 kV, 50 Hz
0.5 kV, 50 Hz Communication
Insulation resistance IEC/EN 60255-27
Protective bonding resistance IEC/EN 60255-27
Clearance and creepage distance Design criteria for distances as per IEC 60255-27 Annex C
(pollution degree 2, overvoltage category 3)
Power supply burden IEC 60255-1
Environmental tests
Standard and test class/level Test value
In operation
Dry heat EN / IEC 60068-2-2, Bd 70°C (158°F)
Cold EN / IEC 60068-2-1, Ad -40°C (-40°F)
Damp heat, cyclic EN / IEC 60068-2-30, Db From 25°C (77°F) to 55°C (131°F)
From 93% RH to 98% RH
Testing duration: 6 days
Damp heat, static EN / IEC 60068-2-78, Cab 40°C (104°F)
93% RH
Testing duration: 10 days
Change of temperature IEC / EN 60068-2-14, Nb Lower temp -40°C (-40°F)
Upper temp 70°C (158°F)
5 cycles
Flowing mixed gas corrosion test, method 1 IEC 60068-2-60, Ke 25°C (77°F), 75% RH, 21 days 100 ppb
H2S, 500 ppb
Flowing mixed gas corrosion test, method 4 IEC 60068-2-60, Ke 25°C (77°F), 75% RH, 21 days 10 ppb H2S,
200 ppb , 10 ppb , 200 ppb
In storage
Dry heat EN / IEC 60068-2-2, Bb 70°C (158°F)
Cold EN / IEC 60068-2-1, Ab -40°C (-40°F)
Environmental
conditions
(1) with 1 x raising frame -> maximum ambient temperature 55°C (+131°F)
with 2 x raising frame -> maximum ambient temperature 50°C (+122°F)
When the devices are connecting in Ethernet link and demand for higher availability,
Easergy P3 Advanced can use Rapid Spanning Tree Protocol (RSTP) or Parallel
Redundancy Protocol (PRP) to recover from a network failure.
Easergy P3 web-HMI
A webserver is available in all Easergy P3 Advanced to get information from the
device to monitoring all data, send command and change protection setting.
Easergy P3 web-HMI
MV network
DM105592
Nominal voltage
Alarm contact
Trip Circuit for Trip circuit
Supervision failure
This electrical schematic Latching contact Trip control
can facilitate the IEC 61850 ANSI 86 Order contact
implementation because all
the logics are done by the
protection unit that will make A1
the decisions and, if necessary,
T2 T1 Digital Input 2 Digital Input 1
send GOOSE messages to Trip circuit Trip circuit Trip circuit
other units. supervision supervision failure alarm
Close contact
Order contact
DI 2 DI 1
T3
0
52a 52b
1
Open/Close
Mechanical CLOSE OPEN
command COIL COIL
Circuit Breaker
Power quality
DM105651
DM105609b
Arc Flash Sensor
DANGER
HAZARD OF ELECTRIC SHOCK, ELECTRIC 1
0
ARC OR BURNS
- only qualified personnel should install this
equipment. Such work should be performed only Arc Flash
Sensor 1
9 DI16 6
8
18 DI11 7
19 T16 10 DI22
DI17
11 8
10
20 DI12 11 DI23
12
1 DI18 10
T17 13 12
I1 11
2 T21 13
14 DI24
3 12
T18 15 14
4 I2 T25 13
5 T22 15
16
I3 T19 17 14
6 16
T26 15
Arc Flash T23 17
7 8/1 18
Sensor
8 5A T20 19 18 16
Io1 T27 17
9
20 T24 19
10
18
11 1 A 20
Io2 T28 19
12
20
Arc T12 20
A
1
A Arc 19
2 T11 18
Arc 6
A
3 T1, T9, T10,
Arc Flash 17
Sensor A Arc T11 and T12:
4 T10 16
5 heavy duty
15 trip relay for
T9 14 arc protection
13
T1 12
11
A1 10
9
8
SF 7
6
5
1 2
1
Note: Dangerous environment, make sure to read the all information, including
warning instructions (left).
DM105610b
DANGER 1
0
HAZARD OF ELECTRIC SHOCK, ELECTRIC
ARC OR BURNS
- only qualified personnel should install this Arc Flash
Sensor 1
7 8/1 18
8 5A T20 19
Io1
Io
9
20
10
11 1 A
Io2
12
Arc T12 20
A
1
A Arc 19
2 18
Arc
6 T11
A
3 T1, T9, T10,
Arc Flash 17
Sensor A Arc T11 and T12:
4 T10 16
5 heavy duty
15 trip relay for
T9 14 arc protection
13
4 T1 12
1 11
2 5A
3 1A I’1 10
A1
4 9
5 5A 8
6 1A I’2
SF 7
7 6
8 5A
5
9 1A I’3
1 2
1
10
11 5A
12 1A Io3
Note: Dangerous environment, make sure to read the all information, including
warning instructions (left).
DANGER
DM105611b
HAZARD OF ELECTRIC SHOCK, ELECTRIC 1
ARC OR BURNS 0
8/2
8/2
- always use a properly rated voltage sensing 6
7
device to confirm that all power is off. 8
DI4 3
9 4
- start by connecting the device to the protective DI5
DI7
1
1
5
earth and to the functional earth. 10
11
2
3
DI13
2
DI6 1
- screw tight all terminals, even those not in use. 12 P3L30 DI8
4
3 DI19
2
T13 DI14
Failure to follow these instructions will result in 13
14 DI9
5 4
5
3
DI20
death or serious injury. 15
T14 6
7
DI15 4
16 6
5
DI10 7
T15 8 DI21
17
9 DI16 6
8
18 DI11 7
19 T16 10 DI22
DI17
11 8
10
20 DI12 11 DI23
12
DI18 10
1 T17 13 12
11
2 I1 T21 13
14 DI24
3 12
T18 15 14
4 I2 T25 13
T22 15
5 16
T19 17 14
6 I3 16
T26 15
T23 17
7 8/1 18
8 5A T20 19 18 16
Io1 T27 17
9 T24 19
20
10 18
11 1 A 20
Io2 T28 19
12
20
T12 20
19
T11 18
T1, T9, T10,
17
T11 and T12:
T10 16
5 heavy duty
15 trip relay
T9 14
13
T1 12
11
6
Diff. Comms.
RX A1 10
9
Card
8
SF 7
TX 6
5
1 2
1
Note: Dangerous environment, make sure to read the all information, including
warning instructions (left).
P3F30
Page 118
Feeder application
PM106371
P3L30
Page 119
Line application
P3M30
Page 120
Motor application
P3G30
Page 121
Generator application
P3T32 Transformer
PM106371
Page 122
with differential application
P3M32 Motor
Page 123
with differential application
P3G32 Generator
Page 124
with differential application
Go to web configurator
Easergy P3 software 84
Presentation 84
Easergy web-HMI 89
Mobile application 90
DM105614
DM105613
eSetup
DM105612
eSetup eSetup
Easergy Pro Easergy Pro Easergy Pro
Use eSetup Easergy Pro in standalone Connect the PC running eSetup Easergy Connect the PC running eSetup Easergy
mode during engineering to prepare the Pro to the USB port of the Easergy Pro to the Ethernet network during
configuration. protection relay during commissioning to operation to retrieve data from the relays
adjust the settings and test the relay. and update the system.
Com
mi
ss
g
io
rin
nin
Enginee
O p e r at i o n
• Create the configuration of the Easergy P3 relay: select the appropriate options
and receive the order code
• Set the characteristics of the CTs, VTs, or sensors connected to the relay, and
select the protection functions that will be activated and their settings
• Build a specific logic, if required, using a graphic editor
• Map the digital inputs of the relay and different internal signals to the relevant
functions, LEDs, and digital outputs, using a straightforward matrix format.
• Draw the single-line diagram that will appear on the front display of the relay for
switchgear control and select the measurements that will be displayed. If any,
build the interlocking logic using a matrix format
• For IEC 61850 protocol, configure the data set and the report control blocks that
will be published and select the GOOSE data to which you want to subscribe
• Complete the setting of additional functions (disturbance recorder, event logging
system, clock synchronization, etc.).
EM106160
EM106161
EM106162
• Connect to the front panel of one single relay or access several relays by
connecting to Ethernet
• Open the Digital Inputs menu to check the status of inputs. Reverse the polarity
or add a filtering delay if necessary
• Open the Relays menu and force the status change of the output relays in order
to check the wiring.
• Open the Phasor Diagram menu to see in real time the phasor of injected
currents and voltages and the value
• Use virtual injection for testing protection settings and circuit breaker tripping
and for checking LEDs and connected outputs
• Open the Logic or the Matrix menu if the logic needs to be tested. The active
signals appear in a different color and are updated in real time. Changes in the
logic or in the matrix can be made and applied to the relay smoothly.
EM106163
EM106164
EM106165
• Connect to the front panel of a single relay or gain access to several relays by
connecting to Ethernet
• During normal operation, get the most of the metering capabilities of the
Easergy protection relay:
– Open the different Measurements menus to access the power monitoring
and power quality data.
– Open the disturbance recorder menu to get a waveform capture or program
the recording of a power trend.
• After a trip, use eSetup Easergy Pro to understand the fault:
– Check the fault log of the protection that has tripped the circuit breaker
– Download the disturbance record from the Easergy P3 and display it with a
disturbance recorder evaluation tool, eg. Wavewin.
EM106166
EM106167
EM106168
Free download
EcoStruxure Power Device on:
(1) Wi-Fi is not embedded in Easergy P3, a separate Wi-Fi router connected to an Ethernet port of
the device is required.
Communication modules 96
REL52825
A remote port is available when a REL52825 cable is used. The cable contains a
connector for the RS-232 interface of the Easergy P3 Standard and a D9-
connector for the external option module.
REL52827
The cable contains a connector for the RS-232 interface of the Easergy P3
Standard and a D9-connector for the REL52815 Profibus interface module.
An extension port is available for the REL52827 in Easergy P3 Standard.
REL52826
REL52823
Remote and extension ports are available when the REL52823 cable is used. The
REL52823 cable contains a connector for the RS232 interface of Easergy P3
Advanced and 2-piece D9-connector for the external option modules.
REL52838
PM106943
REL52824
The cable contains a connector for the RS232 interface of Easergy P3 Advanced
and D9-connector for the REL52815 Profibus interface module. An extension port
is available for the REL52824 in Easergy P3 Advanced.
Characteristics
Distance (maximum) 200 m (7,874.02 in)
Devices (maximum) 32
Type of fiber optic connector PIN (3)
Type of RS232 connector 9-pin DSUB connector
RS485 type 2-wire
Serial protocols Modbus, DNP3.0, IEC870-5-103 and SpaBus
Power supply From RS232 port or external – 12Vdc
To connect the interface with:
Easergy P3 Standard devices, use REL52825 cable
Easergy P3 Advanced devices, use REL52823 cable if needed
Characteristics
Interface 9-pin DSUB connector (Female)
Transfer method RS485, Half-duplex
Transfer cable Twisted pair (1 pair and shield)
Electrical isolation 500 Vdc
Serial protocols Profibus DP
Baud rate 9.6 kBaud to 12 Mbaud
Power supply
Easergy P3 Standard: External – 12Vdc
Easergy P3 Advanced: From RS232 port or external – 12Vdc
To connect the interface with:
Easergy P3 Standard devices, use REL52827 cable
Easergy P3 Advanced devices, use REL52824 cable
Tx Tx Tx
PTC
Fiber
Rx
PM108157
PM108155
Easergy P3 Standard Easergy P3 Advanced
The LPVT hub connector is a simple passive device that combines three LPVT
signals coming from 3 different connectors into one single RJ45 connections.
PM106130
The output of the LPVT hub connector is directly connected to the LPVT input of the
Easergy P3 protection relay.
This accessory is indispensable when connecting Easergy P3 Protection relays to
LPVTs.
Characteristics
Input voltage < 10 V
Input voltage limits < 30 V
Network frequency 50/60 Hz
Electrical connection output: RJ45 connector
inputs: 3 x RJ45 connectors
Dimension (L x W x H) 95 x 40 x 40 mm (3.74 x 1.57 x 1.57 in)
Weight 0.25 kg (0.55 lb)
Mounting support DIN Rail
Operating altitude ≤ 3000 m (1.86 miles)
Voltage adapter
PM106126
The voltage transformer adapter is made with 4 resistor bridges used to interface
conventional voltage transformers (VTs) with the Easergy P3 protection relay
equipped for LPCT/LPVT sensors.
Characteristics
Input voltage 50 Vac to 200 Vac (line-to-line)
Voltage max 600 V max permanent
Network frequency 50/60 Hz
Weight 0.15 kg (0.33 lb)
Mounting support Symmetrical DIN Rail
(1) Contact us for availability
Sensors description
The sensor is used by an arc flash protection device (Easergy P3 Advanced) or
system to detect the light coming from the arc flash incident.
The Easergy P3 Advanced arc sensor is activated by strong light. The sensor
transforms the light information into the current signal, which is used by the
protection device to indicate arc flash.
REL52802
REL52803
REL52804
REL52805
REL52806
REL52807
REL52808
REL52809
REL52810
Characteristics
Material Plastic
Type Standard Pipe
Weight 1,000 g 1,300 g 1,300 g 300 g 400 g 400 g 1,000 g 1,300 g 300 g 400 g
2.20 lb 2.87 lb 2.87 lb 0.66 lb 0.88 lb 0.88 lb 2.20 lb 2.87 lb 0.66 lb 0.88 lb
Cable length (m) 6 20 20 6 6 6 20 20 6 6
Shielded cable - - - - - -
Halogen free - - - - - - - -
Environment Pollution Degree 2
Operation temperature -25°C (-13°F) to +70°C (+158°F)
Light spectrum sensitive area 400 – 1100 nm
Detection time 1 ms
Light sensitivity 8 000 – 10 000 lux
Loop supervision Yes
mm 22.2
DM105632
in 0.83 20
14 0.79
0.55
0.39
10
25
1.83
46.4
0.98
8
0.31
4.2
0.17
REL52807 - 52810 dimensions
mm 11 62
Sensitivity area
DM105636
in 2.44
0.43
DM105637
plate for sensor L-shape), or it can be mounted in
in 10
customer drilled holes.
0.39
PM106971
PM106972
15 59 15
0.59 2.32 0.59
Before
3
DM105633
0.12
30 Mounting plate
1.18 for sensor L-shape
30
1.18
REL52828 dimensions
mm
DM105637
50 51
After in 1.97 25 2.0
15
0.59 0.98
DM105634
59
2.32 2.5
42 0.1
1.65
10
0.39
15
50 0.59
7
1.97
0.28
Mounting plate
for sensor Z-shape
The P3UWAF wall assembly frame, REL52836, enables mounting P3Ux models on
the wall. By removing one of the hinge bolts, the frame can be turned 90 degrees
for easier access to connections.
The P3UPSC panel seal cover, REL52833, enables using a mechanical seal or lock
to prevent unwanted operation of the device. With the seal cover, only the “User”
user account can be used. The cover disables the front USB interface as well.
Install
Life Cycle Services
Life cycle services
Schneider Electric will help you to install more efficient, more reliable and safer
solutions based on your plans.
DM408843
Install Operate
How do I install and commission? Schneider Electric helps you maximize your installation uptime and control your
capital expenditures through its services offering.
• Asset operation solutions: Provide the information you need to increase
Operate
safety, enhance installation performance, and optimize asset maintenance and
How do I operate and maintain?
investment
• Advantage service plans: Customize service plans that include preventive,
Optimize predictive and corrective maintenance
How do I optimize? • On-site maintenance services: Deliver extensive knowledge and experience
in electrical distribution maintenance
• Spare parts management: Ensures spare parts availability and optimized
Renew maintenance budget of your spare parts
How do I renew my solution? • Technical training: Builds necessary skills and competencies to properly and
safety operate your installations.
Optimize
When it comes to your electrical
Schneider Electric proposes recommendations for improved safety, availability,
distribution installation, we can reliability and quality.
help you:
• MP4 electrical assessment: Define an improvement and risk management
• Increase productivity, reliability and safety program.
• Mitigate risk and limit downtime
• Keep equipment up to date and extend
lifespan
• Cut cost and increase savings
Renew
• Improve your return on investment Schneider Electric’s end-of-life solutions may extend the life of your system while
providing upgrades. Under specific service agreements, our service team can
CONTACT US! take full responsibility for the end-of-life processing of old electrical equipment:
https://www.schneider-electric.co.in/ • Retrofit: Keep up to date and improve the performance of electrical
en/work/services/ installations
1999
ECOFITTM 2000 2017 2020 2028 (*)
for your MV Switchboard
MiCOM Px20
• Extend your switchgears lifetime
Sepam S20 and S40
• Access asset and energy management with
digitization Easergy P3
• Reduce your environmental impact
ECOFIT™ solution
• Enhance your process dependability
• Optimize your maintenance service costs and End of full spare parts
limit your investment Sales End of sales availability
• New ECOFIT™ spare parts availability.
(*) Please consult Schneider electric
ECOFIT™ offers:
Sepam S20 Sepam S40 MiCOM Px20 Easergy P3
Green Premium
TM
Accessories 125
Tools 127
Easergy P3 Standard
Easergy P3 Standard
Go to web configurator
Easergy P3 Advanced
REL52103 P3F30-CGGGI-DAECA-BBAAA Power C 110-230 V 110-230 Vac/dc 4 28 DI / 17 DO 4 Arc sensors RS232 + RJ45
REL52109 P3F30-CGIAA-AAECA-BAAAA Power C 110-230 V 24-230 Vac/dc 4 16 DI / 9 DO 4 Arc sensors RS232 + RJ45
Go to web configurator
U10 Application
U10 Feeder & Motor, 4xI, 1xU. 2DI, 5DO
Phase currents & voltage input, X1
X1
5 1 A / 5 A & 1U (100/110 V), pluggable clamp connector
6 1 A / 5 A & 1U (100/110 V), pluggable ring lug connector
Earth-fault current input, X1
X1
A 1A/5A
B 0,2 A / 1 A
Nominal power supply voltage [V], X2
X2
A Power A 48 - 230 V (range: 40 ... 265 Vac/dc)
(1 Always check the power supply range from the relay’s serial number
B Power B 24 - 57V (range: 18 ... 60 Vdc) (1
sticker
A Future option
A None
Nominal Digital Input voltage (voltage withstand)
1 24 Vac/dc (255 Vac/dc)
2 110 Vac/dc (255 Vac/dc)
3 220 Vac/dc (255 Vac/dc)
Easergy P3 U10 A A A
Slot numbers X1 X1 X2 X5 X4
U20 Application
U20 Feeder & Motor, 4xI, 1xU. 2DI, 5DO
Phase currents & voltage input, X1
X1
5 1 A/ 5 A & 1U (100/110 V), pluggable clamp connector
6 1 A / 5 A & 1U (100/110 V), pluggable ring lug connector
Earth-fault current input, X1
X1
A 1A/5A
B 0,2 A / 1 A
Nominal Supply Voltage [V], X2
X2
A Power A 48 - 230 V (range: 40 ... 265 Vac/dc)
1) Always check the power supply range from the relay’s serial number
B Power B 24 - 57 V (range: 18 ... 60 Vdc) (1
sticker
A Future option
A None
Nominal Digital Input voltage (voltage withstand)
1 24 Vac/dc (255 Vac/dc)
2 110 Vac/dc (255 Vac/dc)
3 220 Vac/dc (255 Vac/dc)
4 24 Vac/dc for DI -DI2, 110 Vac/dc for DI3-DI16 (255 Vac/dc)
5 24 Vac/dc for DI -DI2, 220 Vac/dc for DI3-DI16 (255 Vac/dc)
Easergy P3 U20 A A
Slot numbers X1 X1 X2 X5 X4
U30 Application
U30 Feeder & Motor, 4xI, 4xU. 2DI, 5DO
Phase currents & voltage input, X1
X1
5 1 A/ 5 A & 1U (100/110 V), pluggable clamp connector X5 = B
6 1 A / 5 A & 1U (100/110 V), pluggable ring lug connector X5 = B
7 3 LPCT & 4 LPVT, Io clamp connector X5 = C
8 3 LPCT & 4 LPVT, Io ring-lug connector X5 = C
Earth-fault current input, X1
X1
A 1A/5A
B 0,2 A / 1 A
Nominal Supply Voltage [V], X2
X2
(1 Always check the power supply range from the relay’s serial number
A Power A 48 - 230 V (range: 40 ... 265 Vac/dc)
sticker
B Power B 24 - 48 V (range: 18 ... 57 Vdc) (1
A Future option
A None
Nominal Digital Input voltage (voltage withstand)
1 24 Vac/dc (255 Vac/dc)
2 110 Vac/dc (255 Vac/dc)
3 220 Vac/dc (255 Vac/dc)
4 24 Vac/dc for DI -DI2, 110 Vac/dc for DI3-DI16 (255 Vac/dc)
5 24 Vac/dc for DI1-DI2, 220 Vac/dc for DI3-DI16 (255 Vac/dc)
Voltage measurements + I/O, X5
X5
B 3U (100 / 110 V) + 6DI + 3DO X1 = 5 or 6
C 6 DI + 3 DO X1 = 7 or 8
I/O with comms, X4
X4
B RS-485 + 8DI
C 2 x RJ-45 + 8DI
D 2 x LC + 8DI
E RJ + 232 + 8DI with IRIG-B
F LC + 232 + 8DI with IRIG-B
G RS-485 + 6DI + 3DO X1 = 5 or 6
H 2 x RJ-45 + 6DI + 3DO X1 = 5 or 6
I 2 x LC + 6DI + 3DO X1 = 5 or 6
Product version
A Version 2.1, newest FW
Region
A English, IEC
1. Choose your option B English, ANSI Slot X1 = 6
C Chinese
2. Mark your choice in the box below
R Russian
3. Check your order code:
Easergy P3 U30 A
Slot numbers X1 X1 X2 X5 X4
Application
F30 F30 Feeder protection relay
1 Nominal Supply Voltage [V]
C Power C 110 - 230 V (80 .. 265 Vac/dc, 5 x DO heavy duty, A1, SF)
D Power D 24 - 48 V (18 .. 60 Vdc, 5 x DO heavy duty, A1, SF)
2 I/O Card I
G 6DI+4DO (6 x DI, 4 x DO) or 6 Slot 3 = A, G, H or I
B 3BIO+2Arc (3 x BI/BO, 2 x Arc point sensor, T2, T3, T4) Slot 3 = A, G, H or I
C F2BIO+1Arc (Fibre 2 x BI/BO, 1 x Arc loop sensor, T2, T3, T4) Slot 3 = A, G, H or I
3 I/O Card II
A None Slot 4 = A
G 6DI+4DO (6 x DI, 4 x DO) Slot 4 = A, G, H or I
H 6DI+4DO (6 x DI, 4 x DO(NC)) Slot 4 = A, H or I
I 10DI (10 x DI) Slot 4 = A or I
4 I/O Card III
A None Slot 5 = A or D
G 6DI+4DO (6 x DI, 4 x DO) Slot 5 = A, G or I
H 6DI+4DO (6 x DI, 4 x DO(NC)) Slot 5 = A, H or I
I 10DI (10 x DI) Slot 5 = A or I
5 I/O Card IV
A None
D 2IGBT (2 x IGBT High speed outputs), excludes I/O Card III, slot 4
G 6DI+4DO (6 x DI, 4 x DO)
H 6DI+4DO (6 x DI, 4 x DO(NC))
I 10DI (10 x DI)
6 Option card I
A None
D 4Arc (4 x Arc sensor)
K RS232, IRIG-B
7 Future option
A A None
8 Analog measurement card (See application)
E 3L(5/1A) + 2Io(5/1A+1/0,2A) + 4U Region = A, C or R
F 3L(1A) + 2Io(5/1A+1/0.2A) + 4U Region = A, C or R
M 3LPCT + 2Io(5/1A+1/0,2A) + 4LPVT Region = A, C or R
1 3L(5/1A) + 2Io (5/1A+1/0,2A) ringlug + 4U
2 3L(1A) + 2Io (5/1A+1/0.2A) ringlug + 4U
9 Communication interface I
A None
B RS232 (RS232, IRIG-B)
C RS232+RJ (RS232, IRIG-B + Ethernet RJ-45 100 Mbs)
D RS232+LC (RS232, IRIG-B + Ethernet LC 100 Mbs)
E 2xRS485 (2-wire)
F RS485+RJ (RS485 2-wire + Ethernet RJ-45 100Mbs)
G RS485+LC (RS485 2-wire + Ethernet LC 100Mbs)
N 2xRJ (Ethernet RJ 100 Mbs, RSTP, PRP)
O 2xLC (Ethernet LC 100 Mbs, RSTP, PRP)
P PP (Plastic / Plastic serial fibre)
R GG (Glass / Glass serial fibre)
10 Reserved
A A Reserved
Display type
B 128x128 (128 x 128 LCD matrix)
(4 By default cable length is 2 m. In case other legth is needed C 128x128Ext (128 x 128 LCD matrix, detachable) (4
order separately VX001-1, Vx001-3 or VX001-5 for 1 m, 3 m and 5 m Nominal Digital Input voltage (voltage withstand)
respectively. A 24 Vdc/ac, (255 Vac/dc)
B 110 Vdc/ac, (255 Vac/dc)
C 220 Vdc/ac, (255 Vac/dc)
Product version
A A Version 2.1, newest FW
Future option
A A None
Region
A English, IEC
1. Choose your option B English, ANSI Slot 8 = 1 or 2
C Chinese
2. Mark your choice in the box below R Russia
Easergy P3 F30 - A A - A A
Slot numbers 1 2 3 4 5 - 6 7 8 9 10
Application
L30 L30 Feeder protection relay with Line differential and distance protection
1 Nominal Supply Voltage [V]
C Power C 110 - 230 V (80 .. 265 Vac/dc, 5 x DO heavy duty, A1, SF)
D Power D 24 - 48 V (18 .. 60 Vdc, 5 x DO heavy duty, A1, SF)
2 I/O Card I
G 6DI+4DO (6 x DI, 4 x DO) Slot 3 = A, G, H or I
B 3BIO+2Arc (3 x BI/BO, 2 x Arc point sensor, T2, T3, T4) Slot 3 = A, G, H or I
C F2BIO+1Arc (Fibre 2 x BI/BO, 1 x Arc loop sensor, T2, T3, T4) Slot 3 = A, G, H or I
3 I/O Card II
A None Slot 4 = A
G 6DI+4DO (6 x DI, 4 x DO) Slot 4 = A, G, H or I
H 6DI+4DO (6 x DI, 4 x DO(NC)) Slot 4 = A, H, or I
I 10DI (10 x DI) Slot 4 = A or I
4 I/O Card III
A None Slot 5 = A or D
G 6DI+4DO (6 x DI, 4 x DO) Slot 5 = A, G, H or I
H 6DI+4DO (6 x DI, 4 x DO(NC)) Slot 5 = A, H or I
I 10DI (10 x DI) Slot 5 = A or I
5 I/O Card IV
A None
D 2IGBT (2 x IGBT High speed outputs), excludes I/O Card III, slot 4 Slot 4 = A
G 6DI+4DO (6 x DI, 4 x DO)
H 6DI+4DO (6 x DI, 4 x DO(NC))
I 10DI (10 x DI)
6 Option card I
A None, Distance protection included
S Line diff and distance FW with integrated optical diff comms. card
T Line diff and distance FW with RS232 for external diff comms. converter
7 Future option
A A None
8 Analog measurement card (See application)
E 3L(5/1A) + 2Io(5/1A+1/0,2A) + 4U Region = A, C or R
F 3L(1A) + 2Io(5/1A+1/0.2A) + 4U Region = A, C or R
1 3L(5/1A) + 2Io (5/1A+1/0,2A) ringlug + 4U
2 3L(1A) + 2Io (5/1A+1/0.2A) ringlug + 4U
9 Communication interface I
A None
B RS232 (RS232, IRIG-B)
C RS232+RJ (RS232, IRIG-B + Ethernet RJ-45 100 Mbs)
D RS232+LC (RS232, IRIG-B + Ethernet LC 100 Mbs)
E 2xRS485 (2-wire)
F RS485+RJ (RS485 2-wire + Ethernet RJ-45 100Mbs)
G RS485+LC (RS485 2-wire + Ethernet LC 100Mbs)
N 2xRJ (Ethernet RJ 100 Mbs, RSTP)
O 2xLC (Ethernet LC 100 Mbs, RSTP)
P PP (Plastic / Plastic serial fibre)
R GG (Glass / Glass serial fibre)
10 Reserved
A A Reserved
Display type
B 128x128 (128 x 128 LCD matrix)
C 128x128Ext (128 x 128 LCD matrix, detachable) (4
(4 By default cable length is 2 m. In case other length is needed Nominal Digital Input voltage (voltage withstand)
order separately VX001-1, VX001-3 or VX001-5 for 1 m, 3 m and 5 m A 24 Vdc/ac, (255 Vac/dc)
respectively. B 110 Vdc/ac, (255 Vac/dc)
C 220 Vdc/ac, (255 Vac/dc)
Product version
A A Version 2.1, newest FW
Future option
A A None
Region
A English, IEC
1. Choose your option B English, ANSI Slot B = 1 or 2
C Chinese
R Russia
2. Mark your choice in the box below
Easergy P3 L30 - A A - A A
Slot numbers 1 2 3 4 5 - 6 7 8 9 10
Application
M30 M30 Motor protection relay
1 Nominal Supply Voltage [V]
C Power C 110 - 230 V (80 .. 265 Vac/dc, 5 x DO heavy duty, A1, SF)
D Power D 24 - 48 V (18 .. 60 Vdc, 5 x DO heavy duty, A1, SF)
2 I/O Card I
G 6DI+4DO (6 x DI, 4 x DO) Slot 3 = A, G, H or I
B 3BIO+2Arc (3 x BI/BO, 2 x Arc point sensor, T2, T3, T4) Slot 3 = A, G, H or I
C F2BIO+1Arc (Fibre 2 x BI/BO, 1 x Arc loop sensor, T2, T3, T4) Slot 3 = A, G, H or I
3 I/O Card II
A None Slot 4 = A
G 6DI+4DO (6 x DI, 4 x DO) Slot 4 = A, G, H, or I
H 6DI+4DO (6 x DI, 4 x DO(NC)) Slot 4 = A, H or I
I 10DI (10 x DI) Slot 4 = A or I
4 I/O Card III
A None Slot 5 = A or D
G 6DI+4DO (6 x DI, 4 x DO) Slot 5 = A, G, H or I
H 6DI+4DO (6 x DI, 4 x DO(NC)) Slot 5 = A, H or I
I 10DI (10 x DI) Slot 5 = A or I
5 I/O Card IV
A None
D 2IGBT (2 x IGBT High speed outputs), excludes I/O Card III, slot 4 Slot 4 = A
G 6DI+4DO (6 x DI, 4 x DO)
H 6DI+4DO (6 x DI, 4 x DO(NC))
I 10DI (10 x DI)
6 Option card I
A None
D 4Arc (4 x Arc sensor)
K RS232, IRIG-B
7 Future option
A A None
8 Analog measurement card (See application)
E 3L(5/1A) + 2Io(5/1A+1/0,2A) + 4U Region = A, C or R
F 3L(1A) + 2Io(5/1A+1/0.2A) + 4U Region = A, C or R
M 3LPCT + 2Io(5/1A+1/0,2A) + 4LPVT Region = A, C or R
1 3L(5/1A) + 2Io (5/1A+1/0,2A) ringlug + 4U
2 3L(1A) + 2Io (5/1A+1/0.2A) ringlug + 4U
9 Communication interface I
A None
B RS232 (RS232, IRIG-B)
C RS232+RJ (RS232, IRIG-B + Ethernet RJ-45 100 Mbs)
D RS232+LC (RS232, IRIG-B + Ethernet LC 100 Mbs)
E 2xRS485 (2-wire)
F RS485+RJ (RS485 2-wire + Ethernet RJ-45 100Mbs)
G RS485+LC (RS485 2-wire + Ethernet LC 100Mbs)
N 2xRJ (Ethernet RJ 100 Mbs, RSTP)
O 2xLC (Ethernet LC 100 Mbs, RSTP)
P PP (Plastic / Plastic serial fibre)
R GG (Glass / Glass serial fibre)
10 Reserved
A A Reserved
Display type
B 128x128 (128 x 128 LCD matrix)
(4 By default cable length is 2 m. In case other length is needed C 128x128Ext (128 x 128 LCD matrix, detachable) (4
order separately VX001-1, VX001-3 or VX001-5 for 1 m, 3 m and 5 m Nominal Digital Input voltage (voltage withstand)
respectively. A 24 Vdc/ac, (255 Vac/dc)
B 110 Vdc/ac, (255 Vac/dc)
C 220 Vdc/ac, (255 Vac/dc)
Product version
A A Version 2.1, newest FW
Future option
A A None
Region
A English, IEC
1. Choose your option
B English, ANSI Slot 8 = 1 or 2
C Chinese
2. Mark your choice in the box below R Russia
Easergy P3 M30 - A A - A A
Slot numbers 1 2 3 4 5 - 6 7 8 9 10
Application
M32 M32 Motor protection relay with differential protection
1 Nominal Supply Voltage [V]
C Power C 110 - 230 V (80 .. 265 Vac/dc, 5 x DO heavy duty, A1, SF)
D Power D 24 - 48 V (18 .. 60 Vdc, 5 x DO heavy duty, A1, SF)
2 I/O Card I
G 6DI+4DO (6 x DI, 4 x DO) Slot 3 = A, G, H or I
B 3BIO+2Arc (3 x BI/BO, 2 x Arc point sensor, T2, T3, T4) Slot 3 = A, G, H or I
C F2BIO+1Arc (Fibre 2 x BI/BO, 1 x Arc loop sensor, T2, T3, T4) Slot 3 = A, G, H or I
3 I/O Card II
A None
G 6DI+4DO (6 x DI, 4 x DO)
H 6DI+4DO (6 x DI, 4 x DO(NC))
I 10DI (10 x DI)
4 I/O Card III
T 3xI (5/1A) + Io (5/1A) for motor differential protection Slot 8 = E or F
1 3xI (5/1A) ringlug + Io (5/1A) for generator differential protection Slot 8 = 1 or 2
5 I/O Card IV
A A None
6 Option card I
A None
D 4Arc (4 x Arc sensor)
K RS232, IRIG-B
7 Future option
A A None
8 Analog measurement card (See application)
E 3L(5A) + 2Io(5/1A+1/0,2A) + 4U Slot 4 = T and Region = A or C or R
F 3L(1A) + 2Io(5/1A+1/0.2A) + 4U Slot 4 = T and Region = A or C or R
1 3L(5A) + 2Io (5/1A+1/0,2A) ringlug + 4U Slot 4 = 1
2 3L(1A) + 2Io (5/1A+1/0.2A) ringlug + 4U Slot 4 = 1
9 Communication interface I
A None
B RS232 (RS232, IRIG-B)
C RS232+RJ (RS232, IRIG-B + Ethernet RJ-45 100 Mbs)
D RS232+LC (RS232, IRIG-B + Ethernet LC 100 Mbs)
E 2xRS485 (2-wire)
F RS485+RJ (RS485 2-wire + Ethernet RJ-45 100Mbs)
G RS485+LC (RS485 2-wire + Ethernet LC 100Mbs)
N 2xRJ (Ethernet RJ 100 Mbs, RSTP)
O 2xLC (Ethernet LC 100 Mbs, RSTP)
P PP (Plastic / Plastic serial fibre)
R GG (Glass / Glass serial fibre)
10 Reserved
A A Reserved
Display type
B 128x128 (128 x 128 LCD matrix)
(2 By default cable length is 2 m. In case other length is needed C 128x128Ext (128 x 128 LCD matrix, detachable) (2
order separately VX001-1, VX001-3 or VX001-5 for 1 m, 3 m and 5 m Nominal Digital Input voltage (voltage withstand)
respectively. A 24 Vdc/ac, (255 Vac/dc)
B 110 Vdc/ac, (255 Vac/dc)
C 220 Vdc/ac, (255 Vac/dc)
Product version
A A Version 2.1, newest FW
Future option
A A None
Region
A English, IEC
B English, ANSI Slot 4 = 1 and Slot 8 = 1 or 2
C Chinese
R Russia
Easergy P3 M32 A - A A - A A
Slot numbers 1 2 3 4 5 - 6 7 8 9 10
Application
T32 T32 Transformer protection relay with differential protection
1 Nominal Supply Voltage [V]
C Power C 110 - 230 V (80 .. 265 Vac/dc, 5 x DO heavy duty, A1, SF)
D Power D 24 - 48 V (18 .. 60 Vdc, 5 x DO heavy duty, A1, SF)
2 I/O Card I
G 6DI+4DO (6 x DI, 4 x DO)
B 3BIO+2Arc (3 x BI/BO, 2 x Arc point sensor, T2, T3, T4) Slot 3 = A, G, H or I
C F2BIO+1Arc (Fibre 2 x BI/BO, 1 x Arc loop sensor, T2, T3, T4) Slot 3 = A, G, H or I
3 I/O Card II
A None
G 6DI+4DO (6 x DI, 4 x DO)
H 6DI+4DO (6 x DI, 4 x DO(NC))
I 10DI (10 x DI)
4 I/O Card III
T 3xI (5/1A) + Io (5/1A) for transformer differential protection Slot 8 = E or F
1 3xI (5/1A) ringlug + Io (5/1A) for transformer differential protection Slot 8 = 1 or 2
5 I/O Card IV
A A None
6 Option card I
A None
D 4Arc (4 x Arc sensor)
K RS232, IRIG-B
7 Future option
A A None
8 Analog measurement card (See application)
E 3L(5A) + 2Io(5/1A+1/0,2A) + 4U Slot 4 = T and Region = A or C or R
F 3L(1A) + 2Io(5/1A+1/0.2A) + 4U Slot 4 = T and Region = A or C or R
1 3L(5A) + 2Io (5/1A+1/0,2A) ringlug + 4U Slot 4 = 1
2 3L(1A) + 2Io (5/1A+1/0.2A) ringlug + 4U Slot 4 = 1
9 Communication interface I
A None
B RS232 (RS232, IRIG-B)
C RS232+RJ (RS232, IRIG-B + Ethernet RJ-45 100 Mbs)
D RS232+LC (RS232, IRIG-B + Ethernet LC 100 Mbs)
E 2xRS485 (2-wire)
F RS485+RJ (RS485 2-wire + Ethernet RJ-45 100Mbs)
G RS485+LC (RS485 2-wire + Ethernet LC 100Mbs)
N 2xRJ (Ethernet RJ 100 Mbs, RSTP)
O 2xLC (Ethernet LC 100 Mbs, RSTP)
P PP (Plastic / Plastic serial fibre)
R GG (Glass / Glass serial fibre)
10 Reserved
A A Reserved
Display type
B 128x128 (128 x 128 LCD matrix)
(2 By default cable length is 2 m. In case other length is needed C 128x128Ext (128 x 128 LCD matrix, detachable) (2
order separately VX001-1, VX001-3 or VX001-5 for 1 m, 3 m and 5 m Nominal Digital Input voltage (voltage withstand)
respectively. A 24 Vdc/ac, (255 Vac/dc)
B 110 Vdc/ac, (255 Vac/dc)
C 220 Vdc/ac, (255 Vac/dc)
Product version
A A Version 2.1, newest FW
Future option
A A None
Region
A English, IEC
B English, ANSI Slot 4 = 1 and Slot 8 = 1 or 2
C Chinese
R Russia
Easergy P3 T32 A - A A - A A
Slot numbers 1 2 3 4 5 - 6 7 8 9 10
Application
G30 G30 Generator protection
1 Nominal Supply Voltage [V]
C Power C 110 - 230 V (80 .. 265 Vac/dc, 5 x DO heavy duty, A1, SF)
D Power D 24 - 48 V (18 .. 60 Vdc, 5 x DO heavy duty, A1, SF)
2 I/O Card I
G 6DI+4DO (6 x DI, 4 x DO) Slot 3 = A, G, H or I
B 3BIO+2Arc (3 x BI/BO, 2 x Arc point sensor, T2, T3, T4) Slot 3 = A, G, H or I
C F2BIO+1Arc (Fibre 2 x BI/BO, 1 x Arc loop sensor, T2, T3, T4) Slot 3 = A, G, H or I
3 I/O Card II
A None Slot 4 = A
G 6DI+4DO (6 x DI, 4 x DO) Slot 4 = A, G, H or I
H 6DI+4DO (6 x DI, 4 x DO(NC)) Slot 4 = A, H or I
I 10DI (10 x DI) Slot 4 = A or I
4 I/O Card III
A None Slot 5 = A or D
G 6DI+4DO (6 x DI, 4 x DO) Slot 5 = A, G, H or I
H 6DI+4DO (6 x DI, 4 x DO(NC)) Slot 5 = A, H or I
I 10DI (10 x DI) Slot 5 = A or I
5 I/O Card IV
A None
D 2IGBT (2 x IGBT High speed outputs), excludes I/O Card III, slot 4 Slot 4 = A
G 6DI+4DO (6 x DI, 4 x DO)
H 6DI+4DO (6 x DI, 4 x DO(NC))
I 10DI (10 x DI)
6 Option card I
A None
D 4Arc (4 x Arc sensor)
K RS232, IRIG-B
7 Future option
A A None
8 Analog measurement card (See application)
E 3L(5/1A) + 2Io(5/1A+1/0,2A) + 4U Region = A, C or R
F 3L(1A) + 2Io(5/1A+1/0.2A) + 4U Region = A, C or R
1 3L(5/1A) + 2Io (5/1A+1/0,2A) ringlug + 4U
2 3L(1A) + 2Io (5/1A+1/0.2A) ringlug + 4U
9 Communication interface I
A None
B RS232 (RS232, IRIG-B)
C RS232+RJ (RS232, IRIG-B + Ethernet RJ-45 100 Mbs)
D RS232+LC (RS232, IRIG-B + Ethernet LC 100 Mbs)
E 2xRS485 (2-wire)
F RS485+RJ (RS485 2-wire + Ethernet RJ-45 100Mbs)
G RS485+LC (RS485 2-wire + Ethernet LC 100Mbs)
N 2xRJ (Ethernet RJ 100 Mbs, RSTP)
O 2xLC (Ethernet LC 100 Mbs, RSTP)
P PP (Plastic / Plastic serial fibre)
R GG (Glass / Glass serial fibre)
10 Reserved
A A Reserved
Display type
B 128x128 (128 x 128 LCD matrix)
C 128x128Ext (128 x 128 LCD matrix, detachable) (4
(4 By default cable length is 2 m. In case other length is needed Nominal Digital Input voltage (voltage withstand)
order separately VX001-1, VX001-3 or VX001-5 for 1 m, 3 m and 5 m A 24 Vdc/ac, (255 Vac/dc)
respectively. B 110 Vdc/ac, (255 Vac/dc)
C 220 Vdc/ac, (255 Vac/dc)
Product version
A A Version 2.1, newest FW
Future option
A A None
Region
A English, IEC
B English, ANSI Slot 8 = 1 or 2
1. Choose your option C Chinese
R Russia
2. Mark your choice in the box below
Easergy P3 G30 - A A - A A
Slot numbers 1 2 3 4 5 - 6 7 8 9 10
Application
G32 G32 Generator protection with differential protection
1 Nominal Supply Voltage [V]
C Power C 110 - 230 V (80 .. 265 Vac/dc, 5 x DO heavy duty, A1, SF)
D Power D 24 - 48 V (18 .. 60 Vdc, 5 x DO heavy duty, A1, SF)
2 I/O Card I
G 6DI+4DO (6 x DI, 4 x DO) Slot 3 = A, G, H or I
B 3BIO+2Arc (3 x BI/BO, 2 x Arc point sensor, T2, T3, T4) Slot 3 = A, G, H or I
C F2BIO+1Arc (Fibre 2 x BI/BO, 1 x Arc loop sensor, T2, T3, T4) Slot 3 = A, G, H or I
3 I/O Card II
A None
G 6DI+4DO (6 x DI, 4 x DO)
H 6DI+4DO (6 x DI, 4 x DO(NC))
I 10DI (10 x DI)
4 I/O Card III
T 3xI (5/1A) + Io (5/1A) for generator differential protection Slot 8 = E or F
1 3xI (5/1A) ringlug + Io (5/1A) for generator differential protection Slot 8 = 1 or 2
5 I/O Card IV
A A None
6 Option card I
A None
D 4Arc (4 x Arc sensor)
K RS232, IRIG-B
7 Future option
A A None
8 Analog measurement card (See application)
E 3L(5A) + 2Io(5/1A+1/0,2A) + 4U Slot 4 = T and Region = A or C or R
F 3L(1A) + 2Io(5/1A+1/0.2A) + 4U Slot 4 = T and Region = A or C or R
1 3L(5A) + 2Io (5/1A+1/0,2A) ringlug + 4U Slot 4 = 1
2 3L(1A) + 2Io (5/1A+1/0.2A) ringlug + 4U Slot 4 = 1
9 Communication interface I
A None
B RS232 (RS232, IRIG-B)
C RS232+RJ (RS232, IRIG-B + Ethernet RJ-45 100 Mbs)
D RS232+LC (RS232, IRIG-B + Ethernet LC 100 Mbs)
E 2xRS485 (2-wire)
F RS485+RJ (RS485 2-wire + Ethernet RJ-45 100Mbs)
G RS485+LC (RS485 2-wire + Ethernet LC 100Mbs)
N 2xRJ (Ethernet RJ 100 Mbs, RSTP)
O 2xLC (Ethernet LC 100 Mbs, RSTP)
P PP (Plastic / Plastic serial fibre)
R GG (Glass / Glass serial fibre)
10 Reserved
A A Reserved
Display type
B 128x128 (128 x 128 LCD matrix)
(2 By default cable length is 2 m. In case other length is needed C 128x128Ext (128 x 128 LCD matrix, detachable) (2
order separately VX001-1, VX001-3 or VX001-5 for 1 m, 3 m and 5 m Nominal Digital Input voltage (voltage withstand)
respectively. A 24 Vdc/ac, (255 Vac/dc)
B 110 Vdc/ac, (255 Vac/dc)
C 220 Vdc/ac, (255 Vac/dc)
Product version
A A Version 2.1, newest FW
Future option
A A None
Region
A English, IEC
B English, ANSI Slot 4 = 1 and Slot 8 = 1 or 2
C Chinese
R Russia
Easergy P3 G32 A - A A - A A
Slot numbers 1 2 3 4 5 - 6 7 8 9 10
Additional modules
Part No. Qty. Designation
Sensors
59635 Core balance CT, Ø=120 mm (CSH120)
59636 Core balance CT, Ø=200 mm (CSH200)
59637 Core balance CT, Ø=300 mm (CSH300)
EMS59572 VT adapter
EMS59573 LPVT hub connector
03813519N0 1 phase LPCT TLP130 0,72 kV 130 mm diam 4m cable with intermediary connection
03818034N0 1 phase LPCT TLP130/a 0,72 kV 130 mm diam 6.5 m cable
03811060N0 1 phase LPCT TLP160 0,72 kV 160 mm diam 6.5 m cable
03811061N0 1 phase LPCT TLP190 0,72 kV 190 mm diam 6.5 m cable
03816498N0 1 phase LPVT 24 kV GIS type C
03816686N0 1 phase LPVT 12 kV GIS type C
03816695N0 1 phase LPVT 24 kV GIS type C
LPVT36GC 1 phase LPVT 36 kV GIS type C
LPVT17GNKT 1 phase LPVT 17,5 kV GIS type NKT
LPVT24GNKT 1 phase LPVT 24 kV GIS type NKT
LPVT36GNKT 1 phase LPVT 36 kV GIS type NKT
LPVT17GNE 1 phase LPVT 17,5 kV GIS type NEXANS, short cone
LPVT24GNE 1 phase LPVT 24 kV GIS type NEXANS, short cone
LPVT36GNE 1 phase LPVT 36 kV GIS type NEXANS, short cone
LPVT17A 1 phase LPVT 17,5kV AIS
LPVT17A 1 phase LPVT 17,5kV AIS
Web selector
contacts
Training