Difference Between Alternating Current
Difference Between Alternating Current
One of the major differences between the alternating and direct current is that in alternating
current the polarity and the magnitude of the current changes at the regular interval of time
whereas in direct current it remains constants. Some of the differences are explained below in
the form of the comparison chart by considering the various factors;
1. Comparison Chart
2. Definition
3. Key Differences
4. Point to Remember
Comparison Chart
Basis Alternating current Direct current
Definition The direction of the current reverse The direction of the current
periodically. remain same.
The graphical representation of the alternating current is shown in the figure below.
Key differences between Alternating Current and Direct Current
The current which changes its direction at a regular interval of time such type of
current is called alternating current. Direct current is unidirectional or flows only in one
direction.
The charges in the alternating current flow either by rotating a coil in the magnetic
field or by rotating a magnetic field within a stationary coil. In direct current, the charges
flow by keeping the constant magnetism along the wire.
The frequency of the alternating current is 50 to 60 hertz depends on the country
standard, whereas the frequency of the direct current always remains zero.
The power factor of the alternating current lies between zero to one, whereas the
power factor of the direct current always remains one.
The alternator current is generated by the alternator. The direct current is generated by
the generator, battery and cells.
The load of the alternating current is capacitive, inductive or resistive. The load of the
direct current is always resistive in nature.
The alternating current can be graphically represented through different irregular
wave shape such as triangular wave, square wave, periodic wave, the saw-tooth wave, sine
wave, etc. The direct current is graphically represented by the straight line.
The alternating current transmits over a long distance with some losses, whereas the
direct current transmits over very long distances with negligible losses.
The alternating current is converted into direct current with the help of rectifier
whereas the direct current is converted into alternating current with the help of the inverter.
Few substations require for the generation and transmission of the alternating current.
Extra substations require for the transmission of direct current.
The alternating current is used in industries, factories, and for the household purposes.
The direct current is mainly used in electronic equipment, flash lighting, hybrid vehicles,
electroplating, electrolysis, for exciting the field winding of the rotor, etc.
By the arc extinction medium, the circuit breaker is categorised into four
types. They are the air break circuit breaker, air blast circuit breaker, sulphur
hexafluoride circuit breaker and vacuum circuit breaker. The classification of
the circuit breaker is shown in the figure below.
The circuit breaker is mainly categorised into two types. They are the AC
circuit breakers and the DC circuit breakers.
Bulk Oil Circuit Breaker – The bulk oil circuit breaker uses transformer oil
as an arc extinction medium of the circuit breaker. The oil also acts as an
insulator between the two conducting parts of the circuit breaker. The rating
range of oil circuit breaker lies from 25MVA at 2.5KV to 5000 MVA at 230KV.
Minimum Oil Circuit Breaker – In the minimum oil circuit breaker, the oil
is used for arc extinction by blast action. The main function of the oil in the
minimum oil circuit breaker is to interrupt the arc formation, and it is not
used for insulating the live parts of the earth.
The oil impulse circuit breaker is the other type of minimum oil circuit
breaker. This circuit breaker used oil jet, which is produced by the piston
pump for extinguishing the arc. The jet of the oil is placed between the gaps
formed by the contacts of the circuit breaker
The four main types of oil circuit breaker are the air circuit breaker, air blast
circuit breaker, Sulphur hexafluoride circuit breaker and the vacuum circuit
breaker.
Air Circuit Breaker – In air circuit breaker the arc is initiated and extinct in
the static air in which the arc moves. Such types of breaker are used in the
range of low voltage up to 15KV, and the rupturing capacity of the breaker is
500 MVA.The classification of the air break circuit breaker depends on the
types of air breaking methods. The types of the air break circuit breaker are
shown below.
In the plain air break circuit breaker, the contacts are made in the shapes of
the horns. The magnetic blow type breaker uses magnetic field as an arc
interruption medium and in the arc-chute circuit breaker low and medium
voltage circuit are used for arc interruption.
Air Blast Circuit Breaker – The air blast circuit breaker uses a blast of air
to blow out the arc. In an air blast circuit breaker, compressed air is stored in
the form of the tank and release through the nozzles to produce a high-
velocity jet, which is used to extinguish the arc.
Such type of circuit breaker is used for indoor services which have a medium
high voltage field. The air blast circuit breaker is used for the low voltage up
to of 15 kV and rupturing capacities of 2500 MVA. Such types of breakers are
also used in outdoor switchyards for 220 kV lines. The types of the air blast
circuit breaker are shown below.
In axial blast
circuit breaker, the air flows longitudinally in the direction of the arc while in
the cross blast circuit breaker the air flows at the right angle of the arc.
The main problem of the HVDC circuit breaker is that the DC is unidirectional
and hence there is no zero point in the DC system. The fault current in the
HVDC circuit breaker should be reduced to zero by using some external
methods. The arc quenching medium of the air break circuit breaker is either
oil or air blast.
Peak Value, Average Value and RMS Value
Peak Value
Definition: The maximum value attained by an alternating quantity during one cycle is called
its Peak value. It is also known as the maximum value or amplitude or crest value. The
sinusoidal alternating quantity obtains its peak value at 90 degrees as shown in the figure
below.
The peak values of alternating voltage and current is represented by Em and Im respectively.
Average Value
Definition: The average of all the instantaneous values of an alternating voltage and currents
over one complete cycle is called Average Value.
If we consider symmetrical waves like sinusoidal current or voltage waveform, the positive
half cycle will be exactly equal to the negative half cycle. Therefore, the average value over a
complete cycle will be zero.
The work is done by both, positive and negative cycle and hence the average value is
determined without considering the signs.
So, the only positive half cycle is considered to determine the average value of alternating
quantities of sinusoidal waves. Let us take an example to understand it.
Divide the positive half cycle into (n) number of equal parts as shown in the above figure
In other words, the R.M.S value is defined as the square root of means of squares of
instantaneous values.
Let I be the alternating current flowing through a resistor R for time t seconds, which
produces the same amount of heat as produced by the direct current (Ieff). The base of one
alteration is divided into n equal parts so that each interval is of t/n seconds as shown in the
figure below.
Let i1, i2, i3,………..in be the mid ordinates
Root Mean Square is the actual value of an alternating quantity which tells us an energy
transfer capability of an AC source.
The ammeter records the RMS value of alternating current and voltmeter record’s the root
mean square (R.M.S) value of alternating voltage. The domestic single-phase AC supply is
230 V, 50 hertz, where 230 V is the R.M.S value of alternating voltage.
The values of voltage and the current system in a DC circuit is constant, so there is no issue
in evaluating their magnitudes, but in an AC system, the alternating voltage and current vary
from time to time and hence it is necessary to evaluate their magnitudes.
The following three ways (peak value, Average value and R.M.S value) given above are
adopted to express the magnitude of the voltage and current.
Electrical Bus-Bar and its Types
Definition: An electrical bus bar is defined as a conductor or a group of conductor used for
collecting electric power from the incoming feeders and distributes them to the outgoing
feeders. In other words, it is a type of electrical junction in which all the incoming and
outgoing electrical current meets. Thus, the electrical bus bar collects the electric power at
one location.
The bus bar system consists the isolator and the circuit breaker. On the occurrence of a fault,
the circuit breaker is tripped off and the faulty section of the busbar is easily disconnected
from the circuit.
The electrical bus bar is available in rectangular, cross-sectional, round and many other
shapes. The rectangular bus bar is mostly used in the power system. The copper and
aluminium are used for the manufacturing of the electrical bus bar.
The most
common of the bus-bars are 40×4mm (160 mm2); 40×5 mm (200 mm2) ; 50×6 mm
(300mm2) ; 60×8 mm (480 mm2) ; 80×8 (640 mm2) and 100×10 mm (1000 mm2).
The various types of busbar arrangement are used in the power system. The selection of the
bus bar is depended on the different factor likes reliability, flexibility, cost etc. The following
are the electrical considerations governing the selection of any one particular arrangement.
The small substation where continuity of the supply is not essential uses the single bus bar.
But in a large substation, the additional busbar is used in the system so that the interruption
does not occur in their supply. The different type of electrical busbar arrangement is shown in
the figure below.
Drawb
acks of Single Bus-Bars Arrangement
The only disadvantage of such type of arrangement is that the complete supply is
disturbed on the occurrence of the fault.
The arrangement provides the less flexibility and hence used in the small substation
where continuity of supply is not essential.
The faulty section is removed without affecting the continuity of the supply.
The maintenance of the individual section can be done without disturbing the system
supply.
The system has a current limiting reactor which decreases the occurrence of the fault.
1. The potential of both the bus bar kept same by closing the bus coupler.
2. The bus bar on which the load is transferred is kept close.
3. Open the main bus bar.
Thus, the load is transferred from the main bus to reserve bus.
In such type of arrangements, two bus bars are used which increases the cost of the
system.
The fault on any of the bus would cause the complete shutdown on the whole
substation.
This type of arrangement provides the maximum reliability and flexibility in the
supply. Because the fault and maintenance would not disturb their continuity.
The continuity of the supply remains same because the load is transferrable from one
bus to another on the occurrence of the fault.
In such type of arrangement two buses and two circuit breakers are used which
increases the cost of the system.
Their maintenance cost is very high.
Because of its higher cost, such type of bus-bars is seldom used in substations.
Such type of arrangement will provide two paths for the supply. Thus the fault will
not affect their working.
The fault is localized for the particular section. Hence the complete circuit is not
affected by the fault.
In this arrangement, a circuit breaker can be maintained without interrupting the
supply.
Mesh Arrangement
In such type of arrangement, the circuit breakers are installed in the mesh formed by the
buses. The circuit is tapped from the node point of the mesh. Such type of bus arrangement is
controlled by four circuit breakers.
When a
fault occurs on any section, two circuit breakers have to open, resulting in the opening of the
mesh. Such type of arrangement provides security against bus-bar fault but lacks switching
facility. It is preferred for substations having a large number of circuits.