What Causes Error 199 When Using Modsoft and Modbus? - FAQs - Schneider Electric Brazil
What Causes Error 199 When Using Modsoft and Modbus? - FAQs - Schneider Electric Brazil
Modbus?
The following table shows causes and actions to take in order to alleviate Error 99 in Modsoft.
Desktop computers
programming 9-pin Modbus
RS232 port PLCs.
Alternate jumpered pinout. Note DTR and DSR are jumpered out.
This ties handshaking high so a laptop com port with lower voltage can connect to our
PLCs.
Laptop computers
programming 9-pin Modbus
RS232 port PLC.
You need to purchase a prewired kit adapter to build this pinout.
RJ45 to 9-pin Adapter 110XCA20300
RJ45 Programming Cable 110XCA2820x
where x = 1, 3 ft
2, 10 ft
3, 20 ft
FA213579 | 25-Jun-2020