SD8B 3 Part3
SD8B 3 Part3
Company Directive
Policy Summary
This document contains 33kV cable ratings of the various types of 33kV cables used within
Western Power Distribution South West and South Wales areas. It assumes that the cables
will be subjected to the cyclic load as given by the load curve shown in figure one. If other
load curves are required contact the Company Cable Engineer.
This Standard Technique should be used when designing any 33kV electricity distribution
network that has underground cables in it.
© Western Power Distribution (South West) plc Produced All Rights Reserved 2009
This Part 3 document of ST: SD 8B sets out the all the WPD, 33kV underground
cable Sustained ratings, Cyclic ratings and Distribution ratings for winter, spring,
summer and autumn which are to be applied. These ratings are based on Electrical
Network Association Engineering Recommendation P17, Crater for MV Cables,
ERA Report F/T 183 and manufacturers’ data.
Duct dimensions
3.0 CRITERIA
3.1 General criteria for 33kV cables (applies to Paper, EPR and XLPE cables)
A winter soil resistivity of 0.9oCm/W and a summer soil resistivity of 1.2oCm/W are
considered realistic for the South West and South Wales, although the possibility of
localised higher values may need to be taken into account. To control the thermal
resistivity of the surrounding medium then the best example would be to use cement
bound sand (CBS) backfill for a cable route, but this is expensive. Generally crushed
Limestone dust or crushed Granite dust 3mm to dust is suitable as this gives a Tr of
1.2oCm/W.
Ground ambient temperatures across the South West and South Wales vary between
7oC in the winter and 15oC in the summer. These values apply in most locations, but
winter ground temperatures in the city centres such as Bristol, Cardiff, Exeter,
Plymouth and Swansea will be about 2oC higher.
3.2 The current ratings quoted in this document are maximum values based on balanced
loads.
3.4 The current ratings specified are to be adjusted where the conditions are known to
vary from those quoted in this instruction i.e. high summer loads or grouping.
3.5 The maximum conductor temperature for MIND paper cable is 65oC. The maximum
conductor temperature for Oil filled and impregnated pressure gas cable is 85oC. The
maximum conductor temperature for EPR and XLPE cables is 90oC.
3.6 When two or more cables or trefoil groups are laid in the same trench then a derating
factor needs to be applied to both circuits. The amount of derating is dependant upon
the spacing of the circuits. All spacing distances quoted in this document are centre-
to-centre spacing’s of the cables or trefoil groups.
3.8 The ratings are detailed as Sustained - Winter, Spring, Summer and Autumn; Cyclic
- Winter, Spring, Summer and Autumn; Distribution - Winter, Spring, Summer and
Autumn; for each of the cable types included in this document.
3.9 Each cable type for which ratings have been generated the typical assumed
installation conditions are given in the formation shown below: -
Maximum conductor temperature of 65oC for 33kV for 3 core MIND paper
cables and 70oC for 33kV single core PILC cables. The maximum conductor
temperature for Oil filled and impregnated pressure gas cable is 85oC. All
polymeric cables e.g. EPR and XLPE have a maximum conductor
temperature of 90°C.
4.0 DEFINITIONS
All 33kV EPR triplex circuits, for the purpose of this document, have been assumed
to be three single-core polymeric cables laid touching, throughout their length, in
trefoil formation. That the copper wire screens or the lead sheaths of the cables have
been solidly bonded together and earthed at both ends of the circuit.
It should be noted that when triplex or single core cable, which has been laid in
trefoil, a maximum of 12% of the TOTAL ROUTE LENGTH, can be laid in flat
space configuration without affecting the trefoil rating. If more than 12% of the Total
Route Length is laid in flat space configuration then high circulating currents will
flow in the copper wire screens or the lead sheath of the single core cables. This must
be avoided. If the 12% cannot be achieved then contact the Company Cable Engineer
at Avonbank.
ST:SD8B/3 (Part 3) March 2009 - 3 of 159 -
4.1 Sustained, Continuous or Steady-State rating
The sustained rating is the maximum current that can be carried, in defined
conditions, without the assumed maximum conductor temperature being exceeded.
A cyclic rating is the maximum current that maybe carried during the prolonged
application of a succession of identical 24-hour load cycles, without the assumed
maximum conductor temperature being exceeded.
Distribution ratings are ratings calculated for stated conditions commonly occurring
on distribution systems. The tabulated ratings given are 3 to 5 day limited time cyclic
ratings.
The percentage of a cable's distribution rating which is not exceeded during its
normal operational condition. Distribution ratings are based on an initial cable
utilisation of 50%; if a circuit has a higher utilisation factor such as 75% then the
Distribution rating must be reduced by 2.5%.
The ratio of the number of units supplied during a given period, to the number of
units that would be supplied, had the maximum demand been maintained throughout
that period. This is usually expressed as a percentage.
The soil thermal conductivity is the thermal transmission in unit time through unit
area of homogeneous soil of unit thickness, when unit difference of temperature is
established between its surfaces.
The ratings given are calculated for a damp thermal resistivity, which is suitable for
rating cables for winter-peak loads.
Where a cable circuit carries a sustained load and does not have a seasonal variation
it should be rated for the maximum summer value of ground temperature.
4.9 Ducts
A duct up to 15m in length can be used without derating the cable. Two or more duct
lengths can be used on a section, provided that there is no more than 30m of duct in a
particular 250m cable section and that there is a minimum of 10m separation
between each duct length. See the example given below.
The correct duct rating shall be used if 15m or more of continuous duct is installed
on a particular 250m-cable section. This rating is dependant upon the type of ducting
used, for this reason the ratings given in the tables contain values for both smooth
walled “PVC” and “Rigiduct” (Rigiduct is a twin walled duct) type ducting.
The rating of the cable section can be restored if the ducts are bentonited after the
cables have been installed. To ensure the thermal equivalence to the direct buried
parts of the route, the ducts shall be completely filled with a bentonite-sand-cement
mixture.
The filling medium shall be prepared by adding 20 parts of sand and 8 parts of
cements, by weight, to 100 parts of a 10:1 water/bentonite mixture.
Ducts, which are filled with a bentonite mixture, shall be installed wherever possible
in a concrete surround but if not, any joints in the duct run must be effectively
sealed. At the duct ends, the gap around the cable must be effectively sealed to
prevent migration of the bentonite mixture and preserve its moisture content under
service conditions.
In general duct lengths of up to 100m can be filled where a standard 150mm nominal
bore duct is installed.
No allowance has been made for grouping in the ratings listed in the tables. Use the
correction factors given in Table 1 for various grouping arrangements.
When two or more circuits of the same voltage are laid in close proximity the ratings
of the cables must be reduced by multiply the group-rating factor given in Table 1
with the relevant cable rating selected from this document. It should be noted that if
thermally independence of both the circuits is required, then the circuits need a
centre-to-centre spacing of 2.5m.
All spacing quoted in Table 1, are a centre-to-centre spacing for the relevant circuits.
All the ratings listed in this document are calculated for a particular typical
domestic/commercial daily load curve, having a loss load factor of 0.5. See Figure 1
for the load curve.
Ratings given for cables installed in air and clipped direct to a wall are the steady-
state ratings. Cables installed in this manner do NOT have a Cyclic or Distribution
rating just their sustained or steady state rating.
If required, further guidance should be sought from the Company Cable Engineer,
Policy Section, Avonbank, Feeder Road, Bristol where necessary.
TABLE DESCRIPTION
S S
33kV SINGLE CORE X.L.P.E. INSULATED LEAD SHEATH & M.D.P.E. OUTER
SHEATH CABLES, LAID IN TREFOIL. (Dry design)
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
33kV SINGLE CORE X.L.P.E. INSULATED LEAD SHEATH & M.D.P.E. OUTER
SHEATH CABLES, LAID IN TREFOIL. (Dry design)
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
33kV SINGLE CORE X.L.P.E. INSULATED LEAD SHEATH & M.D.P.E. OUTER
SHEATH CABLES, LAID IN TREFOIL. (Dry design)
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
33kV SINGLE CORE X.L.P.E. INSULATED LEAD SHEATH & M.D.P.E. OUTER
SHEATH CABLES, LAID IN TREFOIL. (Dry design)
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
33kV SINGLE CORE X.L.P.E. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Parameters
Maximum depth of lay 1m
33kV SINGLE CORE X.L.P.E. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Parameters
Maximum depth of lay 1m
33kV SINGLE CORE X.L.P.E. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Parameters
Maximum depth of lay 1m
33kV SINGLE CORE X.L.P.E. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Parameters
Maximum depth of lay 1m
33kV SINGLE CORE X.L.P.E. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Parameters
Maximum depth of lay 1m
33kV SINGLE CORE X.L.P.E. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Parameters
Maximum depth of lay 1m
33kV SINGLE CORE X.L.P.E. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Parameters
Maximum depth of lay 1m
33kV SINGLE CORE X.L.P.E. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Dry design)
Parameters
Maximum depth of lay 1m
33kV SINGLE CORE X.L.P.E. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Parameters
Maximum depth of lay 1m
33kV SINGLE CORE X.L.P.E. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Parameters
Maximum depth of lay 1m
33kV SINGLE CORE X.L.P.E. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Parameters
Maximum depth of lay 1m
33kV SINGLE CORE X.L.P.E. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Parameters
Maximum depth of lay 1m
33kV SINGLE CORE E.P.R. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Parameters
Maximum depth of lay 1m
33kV SINGLE CORE E.P.R. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Parameters
Maximum depth of lay 1m
33kV SINGLE CORE E.P.R. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Metric sizes
Copper conductors
70mm2 Copper 351 281 261 326
95mm2 Copper 424 338 314 395
120mm2 Copper 487 386 257 456
150mm2 Copper 549 436 402 517
185mm2 Copper 625 495 455 591
240mm2 Copper 729 575 527 694
300mm2 Copper 829 653 596 795
400mm2 Copper 954 748 679 922
500mm2 Copper 1090 853 770 1064
630mm2 Copper 1240 967 868 1223
Aluminium conductors
70mm2 Al 273 218 203 253
240mm2 Al 570 451 413 543
300mm2 Al 651 513 468 623
Parameters
Maximum depth of lay 1m
33kV SINGLE CORE E.P.R. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Metric sizes
Copper conductors
70mm2 Copper 274 240 227 326
95mm2 Copper 328 287 272 395
120mm2 Copper 373 326 308 456
150mm2 Copper 418 365 345 517
185mm2 Copper 473 412 389 591
240mm2 Copper 547 476 448 694
300mm2 Copper 617 536 504 795
400mm2 Copper 702 609 570 922
500mm2 Copper 794 688 643 1064
630mm2 Copper 893 772 719 1223
Aluminium conductors
70mm2 Al 213 186 177 253
240mm2 Al 428 373 351 543
300mm2 Al 485 422 396 623
Parameters
Maximum depth of lay 1m
Soil Thermal Resistivity (g) 1.05oC m/W
33kV SINGLE CORE E.P.R. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Metric sizes
Copper conductors
70mm2 Copper 307 262 246 326
95mm2 Copper 370 315 295 395
120mm2 Copper 423 359 335 456
150mm2 Copper 476 403 376 517
185mm2 Copper 540 457 425 591
240mm2 Copper 627 529 491 694
300mm2 Copper 711 599 553 795
400mm2 Copper 813 684 629 922
500mm2 Copper 926 776 711 1064
630mm2 Copper 1048 875 799 1223
Aluminium conductors
70mm2 Al 239 204 191 253
240mm2 Al 491 415 385 543
300mm2 Al 558 471 435 623
Parameters
Maximum depth of lay 1m
33kV SINGLE CORE E.P.R INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Metric sizes
Copper conductors
70mm2 Copper 336 277 258 326
95mm2 Copper 406 333 310 395
120mm2 Copper 465 381 353 456
150mm2 Copper 524 429 396 517
185mm2 Copper 596 486 448 591
240mm2 Copper 694 565 519 694
300mm2 Copper 789 641 586 795
400mm2 Copper 906 734 668 922
500mm2 Copper 1035 835 757 1064
630mm2 Copper 1176 945 852 1223
Aluminium conductors
70mm2 Al 261 215 201 253
240mm2 Al 543 443 407 543
300mm2 Al 619 503 461 623
Parameters
Maximum depth of lay 1m
33kV SINGLE CORE E.P.R. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Metric sizes
Copper conductors
70mm2 Copper 257 229 218 326
95mm2 Copper 307 274 260 395
120mm2 Copper 350 311 295 456
150mm2 Copper 392 349 330 517
185mm2 Copper 442 393 372 591
240mm2 Copper 511 454 428 694
300mm2 Copper 576 511 481 795
400mm2 Copper 654 579 545 922
500mm2 Copper 740 653 613 1064
630mm2 Copper 831 732 686 1223
Aluminium conductors
70mm2 Al 200 178 170 253
240mm2 Al 400 356 336 543
300mm2 Al 453 402 379 623
Parameters
Maximum depth of lay 1m
33kV SINGLE CORE E.P.R. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Metric sizes
Copper conductors
70mm2 Copper 291 254 238 326
95mm2 Copper 350 304 285 395
120mm2 Copper 399 347 324 456
150mm2 Copper 449 389 364 517
185mm2 Copper 509 441 411 591
240mm2 Copper 591 510 474 694
300mm2 Copper 669 577 535 795
400mm2 Copper 765 658 607 922
500mm2 Copper 870 745 686 1064
630mm2 Copper 984 840 770 1223
Aluminium conductors
70mm2 Al 226 197 185 253
240mm2 Al 463 400 372 543
300mm2 Al 526 433 420 623
Parameters
Maximum depth of lay 1m
33kV SINGLE CORE E.P.R. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Metric sizes
Copper conductors
70mm2 Copper 320 271 253 326
95mm2 Copper 386 326 303 395
120mm2 Copper 442 372 345 456
150mm2 Copper 498 419 388 517
185mm2 Copper 566 475 438 591
240mm2 Copper 658 551 507 694
300mm2 Copper 748 624 573 795
400mm2 Copper 858 714 652 922
500mm2 Copper 979 811 738 1064
630mm2 Copper 1111 917 830 1223
Aluminium conductors
70mm2 Al 249 211 197 253
240mm2 Al 516 432 398 543
300mm2 Al 587 490 450 623
Parameters
Maximum depth of lay 1m
33kV SINGLE CORE E.P.R. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Metric sizes
Copper conductors
70mm2 Copper 270 238 226 326
95mm2 Copper 323 284 269 395
120mm2 Copper 367 323 306 456
150mm2 Copper 412 362 342 517
185mm2 Copper 465 408 385 591
240mm2 Copper 538 471 444 694
300mm2 Copper 607 531 499 795
400mm2 Copper 690 603 565 922
500mm2 Copper 780 680 636 1064
630mm2 Copper 877 763 712 1223
Aluminium conductors
70mm2 Al 210 185 175 253
240mm2 Al 421 370 348 543
300mm2 Al 477 418 393 623
Parameters
Maximum depth of lay 1m
33kV SINGLE CORE E.P.R. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Metric sizes
Copper conductors
70mm2 Copper 304 261 245 326
95mm2 Copper 365 313 293 395
120mm2 Copper 417 357 334 456
150mm2 Copper 470 401 374 517
185mm2 Copper 533 454 422 591
240mm2 Copper 618 526 488 694
300mm2 Copper 701 595 550 795
400mm2 Copper 802 679 626 922
500mm2 Copper 912 770 707 1064
630mm2 Copper 1032 869 794 1223
Aluminium conductors
70mm2 Al 236 203 190 253
240mm2 Al 484 412 383 543
300mm2 Al 550 468 433 623
Parameters
Maximum depth of lay 1m
33kV SINGLE CORE E.P.R. INSULATED COPPER WIRE SCREEN & M.D.P.E.
OUTER SHEATH CABLES, LAID IN TREFOIL. (Wet design)
Metric sizes
Copper conductors
70mm2 Copper 333 276 258 326
95mm2 Copper 402 333 310 395
120mm2 Copper 460 380 352 456
150mm2 Copper 519 428 396 517
185mm2 Copper 590 485 448 591
240mm2 Copper 686 564 518 694
300mm2 Copper 780 639 585 795
400mm2 Copper 895 731 667 922
500mm2 Copper 1022 832 755 1064
630mm2 Copper 1161 941 850 1223
Aluminium conductors
70mm2 Al 259 215 201 253
240mm2 Al 537 370 406 543
300mm2 Al 612 502 460 623
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Aluminium conductors
0.1in2 Al 196 163 154 194
0.15in2 Al 244 202 189 243
0.2in2 Al 287 235 221 286
0.3in2 Al 367 298 278 369
0.4in2 Al 432 349 324 439
0.5in2 Al 483 388 359 494
Metric sizes
Aluminium conductors
95mm2 Al 247 204 191 244
120mm2 Al 283 232 217 280
150mm2 Al 320 260 243 318
185mm2 Al 363 295 274 363
240mm2 Al 424 342 317 427
300mm2 Al 479 385 355 486
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Aluminium conductors
0.1in2 Al 187 158 149 194
0.15in2 Al 232 195 183 243
0.2in2 Al 272 228 214 286
0.3in2 Al 348 288 269 369
0.4in2 Al 410 337 313 439
0.5in2 Al 457 374 347 494
Metric sizes
Aluminium conductors
95mm2 Al 235 197 185 244
120mm2 Al 269 224 210 280
150mm2 Al 303 251 235 318
185mm2 Al 344 284 265 363
240mm2 Al 400 329 306 427
300mm2 Al 452 370 342 486
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Aluminium conductors
0.1in2 Al 177 147 143 194
0.15in2 Al 219 181 176 243
0.2in2 Al 257 211 205 286
0.3in2 Al 327 274 257 369
0.4in2 Al 385 321 299 439
0.5in2 Al 429 356 331 494
Metric sizes
Aluminium conductors
95mm2 Al 221 188 177 244
120mm2 Al 253 214 201 280
150mm2 Al 285 240 225 318
185mm2 Al 323 271 253 363
240mm2 Al 376 314 292 427
300mm2 Al 424 352 327 486
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Aluminium conductors
0.1in2 Al 185 157 148 194
0.15in2 Al 230 194 183 243
0.2in2 Al 270 226 213 286
0.3in2 Al 344 286 267 369
0.4in2 Al 405 334 311 439
0.5in2 Al 452 371 345 494
Metric sizes
Aluminium conductors
95mm2 Al 233 196 184 244
120mm2 Al 266 223 206 280
150mm2 Al 300 250 234 318
185mm2 Al 340 283 264 363
240mm2 Al 396 327 304 427
300mm2 Al 447 367 340 486
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Parameters
Maximum depth of lay 1m
Aluminium conductors
120mm2 Al. 297 245 232 289
150mm2 Al. 333 276 261 329
185mm2 Al. 379 315 297 382
240mm2 Al. 439 365 343 450
260mm2 Al. 459 382 360 474
300mm2 Al. 498 415 390 522
350mm2 Al. 535 446 418 564
400mm2 Al. 566 474 444 605
500mm2 Al. 638 535 500 693
630mm2 Al. 726 609 567 811
Parameters
Maximum depth of lay 1m
Aluminium conductors
120mm2 Al. 340 267 250 289
150mm2 Al. 382 301 282 329
185mm2 Al. 438 345 322 382
240mm2 Al. 509 402 373 450
260mm2 Al. 534 421 391 474
300mm2 Al. 582 459 425 522
350mm2 Al. 626 494 457 564
400mm2 Al. 665 526 486 605
500mm2 Al. 753 596 548 693
630mm2 Al. 864 682 624 811
Parameters
Maximum depth of lay 1m
Aluminium conductors
120mm2 Al. 277 235 224 289
150mm2 Al. 310 265 251 329
185mm2 Al. 353 301 285 382
240mm2 Al. 409 349 330 450
260mm2 Al. 428 366 345 474
300mm2 Al. 463 397 374 522
350mm2 Al. 497 426 401 564
400mm2 Al. 527 452 425 605
500mm2 Al. 593 510 478 693
630mm2 Al. 674 579 542 811
Parameters
Maximum depth of lay 1m
Aluminium conductors
120mm2 Al. 321 259 244 289
150mm2 Al. 360 293 274 329
185mm2 Al. 413 335 313 382
240mm2 Al. 480 389 363 450
260mm2 Al. 503 408 380 474
300mm2 Al. 548 444 412 522
350mm2 Al. 589 478 443 564
400mm2 Al. 626 509 471 605
500mm2 Al. 708 575 531 693
630mm2 Al. 812 658 604 811
Parameters
Maximum depth of lay 1m
Aluminium conductors
120mm2 Al. 258 225 214 289
150mm2 Al. 289 252 240 329
185mm2 Al. 329 287 272 382
240mm2 Al. 380 332 315 450
260mm2 Al. 398 348 329 474
300mm2 Al. 431 377 356 522
350mm2 Al. 462 405 382 564
400mm2 Al. 490 429 405 605
500mm2 Al. 551 453 455 693
630mm2 Al. 626 548 515 811
Parameters
Maximum depth of lay 1m
Aluminium conductors
120mm2 Al. 301 250 236 289
150mm2 Al. 339 282 265 329
185mm2 Al. 388 322 302 382
240mm2 Al. 450 374 350 450
260mm2 Al. 472 393 366 474
300mm2 Al. 514 427 397 522
350mm2 Al. 553 459 427 564
400mm2 Al. 587 488 453 605
500mm2 Al. 664 552 511 693
630mm2 Al. 761 630 581 811
Parameters
Maximum depth of lay 1m
Aluminium conductors
120mm2 Al. 272 233 222 289
150mm2 Al. 305 262 249 329
185mm2 Al. 347 299 283 382
240mm2 Al. 401 346 327 450
260mm2 Al. 420 362 342 474
300mm2 Al. 455 393 370 522
350mm2 Al. 489 422 398 564
400mm2 Al. 518 448 421 605
500mm2 Al. 583 504 474 693
630mm2 Al. 662 573 537 811
Parameters
Maximum depth of lay 1m
Aluminium conductors
120mm2 Al. 316 258 243 289
150mm2 Al. 355 291 273 329
185mm2 Al. 407 333 311 382
240mm2 Al. 473 387 361 450
260mm2 Al. 496 406 378 474
300mm2 Al. 540 441 410 522
350mm2 Al. 581 475 441 564
400mm2 Al. 617 505 468 605
500mm2 Al. 698 571 528 693
630mm2 Al. 800 653 600 811
Parameters
Maximum depth of lay 1m
Copper conductors
0.1 in2 Cu 275 228 217 261
0.15in2 Cu. 342 283 269 333
0.2in2 Cu. 398 330 312 390
0.25in2 Cu 455 378 356 457
0.3in2 Cu. 505 419 395 510
0.35in2 Cu 555 461 434 569
0.4in2 Cu 590 492 463 611
0.45in2 Cu 627 524 491 657
0.5in2 Cu 657 549 515 691
0.55in2 Cu. 688 575 539 731
0.6in2 Cu 728 608 569 781
Aluminium conductors
0.1 in2 Al. 100 83 79 95
0.15in2 Al. 138 114 108 134
0.2in2Al. 171 142 134 168
0.25in2 Al. 227 189 178 228
0.3in2 Al. 276 229 216 279
0.35in2 Al. 323 268 252 331
0.4in2 Al. 362 302 284 374
0.45in2 Al 405 338 317 424
0.5in2 Al. 469 392 368 493
0.55in2 Al. 521 436 409 554
0.6in2 Al 526 440 411 564
Parameters
Maximum depth of lay 1m
Copper conductors
0.1 in2 Cu 312 247 232 261
0.15in2 Cu. 391 309 289 333
0.2in2 Cu. 455 360 337 390
0.25in2 Cu 525 414 386 457
0.3in2 Cu. 584 460 429 510
0.35in2 Cu 645 508 472 569
0.4in2 Cu 686 543 504 611
0.45in2 Cu 733 579 536 657
0.5in2 Cu 768 607 562 691
0.55in2 Cu. 807 638 589 731
0.6in2 Cu 857 676 623 781
Aluminium conductors
0.1 in2 Al. 113 90 84 95
0.15in2 Al. 157 124 116 134
0.2in2Al. 196 155 145 168
0.25in2 Al. 262 207 193 228
0.3in2 Al. 319 252 235 279
0.35in2 Al. 375 295 274 331
0.4in2 Al. 420 333 309 374
0.45in2 Al 473 374 346 424
0.5in2 Al. 548 433 401 493
0.55in2 Al. 612 484 447 554
0.6in2 Al 619 489 450 564
Parameters
Maximum depth of lay 1m
Copper conductors
0.1 in2 Cu 258 219 209 261
0.15in2 Cu. 320 272 259 333
0.2in2 Cu. 371 316 300 390
0.25in2 Cu 424 362 343 457
0.3in2 Cu. 471 402 380 510
0.35in2 Cu 517 441 417 569
0.4in2 Cu 550 471 444 611
0.45in2 Cu 584 500 471 657
0.5in2 Cu 611 524 494 691
0.55in2 Cu. 640 549 516 731
0.6in2 Cu 676 580 545 781
Aluminium conductors
0.1 in2 Al. 94 80 76 95
0.15in2 Al. 129 110 104 134
0.2in2Al. 160 136 129 168
0.25in2 Al. 212 181 171 228
0.3in2 Al. 257 220 208 279
0.35in2 Al. 301 257 242 331
0.4in2 Al. 337 289 273 374
0.45in2 Al 377 323 304 424
0.5in2 Al. 436 374 352 493
0.55in2 Al. 485 416 392 554
0.6in2 Al 489 419 394 564
Parameters
Maximum depth of lay 1m
Copper conductors
0.1 in2 Cu 295 240 226 261
0.15in2 Cu. 369 300 282 333
0.2in2 Cu. 430 349 328 390
0.25in2 Cu 495 402 375 457
0.3in2 Cu. 550 446 417 510
0.35in2 Cu 607 492 458 569
0.4in2 Cu 646 526 489 611
0.45in2 Cu 690 560 520 657
0.5in2 Cu 723 588 545 691
0.55in2 Cu. 759 617 571 731
0.6in2 Cu 805 653 604 781
Aluminium conductors
0.1 in2 Al. 107 87 82 95
0.15in2 Al. 148 121 113 134
0.2in2Al. 185 150 141 168
0.25in2 Al. 247 200 187 228
0.3in2 Al. 301 244 228 279
0.35in2 Al. 353 286 266 331
0.4in2 Al. 396 322 300 374
0.45in2 Al 445 362 336 424
0.5in2 Al. 516 419 389 493
0.55in2 Al. 576 468 433 554
0.6in2 Al 582 472 437 564
Parameters
Maximum depth of lay 1m
Copper conductors
0.1 in2 Cu 241 210 200 261
0.15in2 Cu. 298 260 248 333
0.2in2 Cu. 346 302 287 390
0.25in2 Cu 395 345 328 457
0.3in2 Cu. 438 383 363 510
0.35in2 Cu 481 420 398 569
0.4in2 Cu 511 448 424 611
0.45in2 Cu 543 475 449 657
0.5in2 Cu 568 498 471 691
0.55in2 Cu. 595 521 492 731
0.6in2 Cu 628 550 519 781
Aluminium conductors
0.1 in2 Al. 87 76 73 95
0.15in2 Al. 120 105 100 134
0.2in2Al. 149 130 124 168
0.25in2 Al. 197 172 163 228
0.3in2 Al. 240 209 199 279
0.35in2 Al. 279 244 231 331
0.4in2 Al. 314 275 260 374
0.45in2 Al 350 307 290 424
0.5in2 Al. 406 355 336 493
0.55in2 Al. 451 395 373 554
0.6in2 Al 454 398 375 564
Parameters
Maximum depth of lay 1m
Copper conductors
0.1 in2 Cu 278 232 219 261
0.15in2 Cu. 347 289 272 333
0.2in2 Cu. 404 337 317 390
0.25in2 Cu 465 387 362 457
0.3in2 Cu. 517 430 402 510
0.35in2 Cu 570 473 442 569
0.4in2 Cu 607 506 472 611
0.45in2 Cu 647 538 501 657
0.5in2 Cu 679 565 525 691
0.55in2 Cu. 712 592 550 731
0.6in2 Cu 755 627 581 781
Aluminium conductors
0.1 in2 Al. 101 84 80 95
0.15in2 Al. 140 116 110 134
0.2in2Al. 174 145 136 168
0.25in2 Al. 232 193 181 228
0.3in2 Al. 283 235 220 279
0.35in2 Al. 331 275 257 331
0.4in2 Al. 372 310 289 374
0.45in2 Al 418 348 324 424
0.5in2 Al. 484 403 375 493
0.55in2 Al. 540 449 417 554
0.6in2 Al 546 453 420 564
Parameters
Maximum depth of lay 1m
Copper conductors
0.1 in2 Cu 254 217 207 261
0.15in2 Cu. 315 270 257 333
0.2in2 Cu. 365 314 298 390
0.25in2 Cu 417 359 340 457
0.3in2 Cu. 463 398 377 510
0.35in2 Cu 508 437 413 569
0.4in2 Cu 540 466 440 611
0.45in2 Cu 574 495 467 657
0.5in2 Cu 601 519 489 691
0.55in2 Cu. 629 543 512 731
0.6in2 Cu 664 574 540 781
Aluminium conductors
0.1 in2 Al. 92 79 75 95
0.15in2 Al. 127 109 103 134
0.2in2Al. 157 135 128 168
0.25in2 Al. 208 179 170 228
0.3in2 Al. 253 218 206 279
0.35in2 Al. 295 254 240 331
0.4in2 Al. 331 286 270 374
0.45in2 Al 370 320 302 424
0.5in2 Al. 429 370 349 493
0.55in2 Al. 477 412 388 554
0.6in2 Al 480 415 390 564
Parameters
Maximum depth of lay 1m
Copper conductors
0.1 in2 Cu 291 239 225 261
0.15in2 Cu. 364 298 280 333
0.2in2 Cu. 424 347 326 390
0.25in2 Cu 488 399 373 457
0.3in2 Cu. 542 444 415 510
0.35in2 Cu 599 489 456 569
0.4in2 Cu 637 522 486 611
0.45in2 Cu 680 556 517 657
0.5in2 Cu 713 584 542 691
0.55in2 Cu. 748 612 568 731
0.6in2 Cu 794 648 600 781
Aluminium conductors
0.1 in2 Al. 106 87 82 95
0.15in2 Al. 146 120 113 134
0.2in2Al. 182 149 140 168
0.25in2 Al. 244 199 186 228
0.3in2 Al. 297 243 227 279
0.35in2 Al. 348 284 265 331
0.4in2 Al. 391 320 298 374
0.45in2 Al 439 359 334 424
0.5in2 Al. 508 417 387 493
0.55in2 Al. 567 464 431 554
0.6in2 Al 574 469 434 564
Parameters
Maximum depth of lay 1m
Copper conductors
0.1 in2 Cu 274 226 215 257
0.15in2 Cu. 336 278 278 322
0.2in2 Cu. 394 326 326 383
0.25in2 Cu 449 371 371 442
0.3in2 Cu. 503 415 415 501
0.35in2 Cu 548 454 454 552
0.4in2 Cu 589 487 487 600
0.45in2 Cu 621 515 515 637
0.5in2 Cu 650 541 541 672
0.55in2 Cu. 678 565 565 706
0.6in2 Cu 713 595 595 746
Aluminium conductors
0.1 in2 Al. 99 82 78 93
0.15in2 Al. 136 112 106 129
0.2in2Al. 170 140 133 165
0.25in2 Al. 224 185 175 221
0.3in2 Al. 275 227 215 274
0.35in2 Al. 319 264 249 321
0.4in2 Al. 361 299 281 367
0.45in2 Al 401 332 313 411
0.5in2 Al. 464 386 363 479
0.55in2 Al. 514 428 402 535
0.6in2 Al 515 430 403 538
Parameters
Maximum depth of lay 1m
Copper conductors
0.1 in2 Cu 309 244 230 257
0.15in2 Cu. 354 302 284 322
0.2in2 Cu. 450 355 333 383
0.25in2 Cu 515 403 379 442
0.3in2 Cu. 580 455 424 501
0.35in2 Cu 634 498 464 552
0.4in2 Cu 684 536 499 600
0.45in2 Cu 722 567 527 637
0.5in2 Cu 757 597 554 672
0.55in2 Cu. 791 624 578 706
0.6in2 Cu 832 658 609 746
Aluminium conductors
0.1 in2 Al. 112 89 84 93
0.15in2 Al. 155 121 114 129
0.2in2Al. 194 153 143 165
0.25in2 Al. 257 202 189 221
0.3in2 Al. 317 249 232 274
0.35in2 Al. 368 289 270 321
0.4in2 Al. 419 329 306 367
0.45in2 Al 466 366 340 411
0.5in2 Al. 540 425 395 479
0.55in2 Al. 600 473 438 535
0.6in2 Al 601 475 440 538
Parameters
Maximum depth of lay 1m
Copper conductors
0.1 in2 Cu 256 217 207 257
0.15in2 Cu. 316 268 255 322
0.2in2 Cu. 368 313 298 383
0.25in2 Cu 419 356 338 442
0.3in2 Cu. 468 398 377 501
0.35in2 Cu 511 435 411 552
0.4in2 Cu 548 467 441 600
0.45in2 Cu 578 493 465 637
0.5in2 Cu 605 517 488 672
0.55in2 Cu. 631 540 509 706
0.6in2 Cu 664 569 536 746
Aluminium conductors
0.1 in2 Al. 93 79 75 93
0.15in2 Al. 127 108 102 129
0.2in2Al. 158 135 128 165
0.25in2 Al. 209 178 169 221
0.3in2 Al. 256 218 206 274
0.35in2 Al. 297 253 239 321
0.4in2 Al. 336 286 270 367
0.45in2 Al 373 318 300 411
0.5in2 Al. 432 369 348 479
0.55in2 Al. 478 409 386 535
0.6in2 Al 479 411 387 538
Parameters
Maximum depth of lay 1m
Copper conductors
0.1 in2 Cu 293 238 224 257
0.15in2 Cu. 363 293 277 322
0.2in2 Cu. 425 345 324 383
0.25in2 Cu 486 393 369 442
0.3in2 Cu. 546 441 413 501
0.35in2 Cu 597 483 451 552
0.4in2 Cu 644 520 484 600
0.45in2 Cu 680 549 512 637
0.5in2 Cu 713 578 537 672
0.55in2 Cu. 745 604 561 706
0.6in2 Cu 784 637 591 746
Aluminium conductors
0.1 in2 Al. 106 86 82 93
0.15in2 Al. 146 118 111 129
0.2in2Al. 183 148 139 165
0.25in2 Al. 242 196 184 221
0.3in2 Al. 299 241 226 274
0.35in2 Al. 347 281 262 321
0.4in2 Al. 395 318 297 367
0.45in2 Al 439 355 330 411
0.5in2 Al. 508 412 383 479
0.55in2 Al. 564 458 425 535
0.6in2 Al 566 460 427 538
Parameters
Maximum depth of lay 1m
Copper conductors
0.1 in2 Cu 239 208 199 257
0.15in2 Cu. 295 256 244 322
0.2in2 Cu. 343 299 285 383
0.25in2 Cu 390 340 323 442
0.3in2 Cu. 436 379 360 501
0.35in2 Cu 475 414 393 552
0.4in2 Cu 509 444 421 600
0.45in2 Cu 537 469 444 637
0.5in2 Cu 563 492 466 672
0.55in2 Cu. 587 513 486 706
0.6in2 Cu 617 540 511 746
Aluminium conductors
0.1 in2 Al. 87 76 72 93
0.15in2 Al. 118 103 98 129
0.2in2Al. 148 129 123 165
0.25in2 Al. 194 169 161 221
0.3in2 Al. 238 207 197 274
0.35in2 Al. 276 241 228 321
0.4in2 Al. 312 272 258 367
0.45in2 Al 347 303 287 411
0.5in2 Al. 401 351 332 479
0.55in2 Al. 445 389 368 535
0.6in2 Al 446 390 369 538
Parameters
Maximum depth of lay 1m
Copper conductors
0.1 in2 Cu 276 230 217 257
0.15in2 Cu. 341 283 268 322
0.2in2 Cu. 400 333 313 383
0.25in2 Cu 457 379 356 442
0.3in2 Cu. 513 425 398 501
0.35in2 Cu 561 465 435 552
0.4in2 Cu 604 500 467 600
0.45in2 Cu 637 529 493 637
0.5in2 Cu 669 556 518 672
0.55in2 Cu. 699 580 541 706
0.6in2 Cu 736 612 570 746
Aluminium conductors
0.1 in2 Al. 100 83 79 93
0.15in2 Al. 137 114 108 129
0.2in2Al. 172 143 135 165
0.25in2 Al. 228 189 178 221
0.3in2 Al. 280 232 218 274
0.35in2 Al. 326 270 253 321
0.4in2 Al. 370 306 286 367
0.45in2 Al 411 341 318 411
0.5in2 Al. 477 396 369 479
0.55in2 Al. 529 440 410 535
0.6in2 Al 531 442 411 538
Parameters
Maximum depth of lay 1m
Copper conductors
0.1 in2 Cu 252 216 206 257
0.15in2 Cu. 311 265 253 322
0.2in2 Cu. 362 311 295 383
0.25in2 Cu 411 353 335 442
0.3in2 Cu. 460 394 374 501
0.35in2 Cu 502 431 408 552
0.4in2 Cu 538 462 437 600
0.45in2 Cu 567 488 461 637
0.5in2 Cu 595 512 484 672
0.55in2 Cu. 620 534 504 706
0.6in2 Cu 652 563 531 746
Aluminium conductors
0.1 in2 Al. 92 78 75 93
0.15in2 Al. 125 107 102 129
0.2in2Al. 156 134 127 165
0.25in2 Al. 205 176 167 221
0.3in2 Al. 252 216 204 274
0.35in2 Al. 292 250 237 321
0.4in2 Al. 330 283 268 367
0.45in2 Al 366 315 298 411
0.5in2 Al. 424 365 345 479
0.55in2 Al. 470 405 382 535
0.6in2 Al 471 406 383 538
Parameters
Maximum depth of lay 1m
Copper conductors
0.1 in2 Cu 289 236 224 257
0.15in2 Cu. 358 292 275 322
0.2in2 Cu. 419 343 323 383
0.25in2 Cu 479 391 367 442
0.3in2 Cu. 539 439 411 501
0.35in2 Cu 589 480 449 552
0.4in2 Cu 634 516 482 600
0.45in2 Cu 670 546 509 637
0.5in2 Cu 702 574 534 672
0.55in2 Cu. 734 600 558 706
0.6in2 Cu 772 632 588 746
Aluminium conductors
0.1 in2 Al. 105 86 81 93
0.15in2 Al. 144 117 111 129
0.2in2Al. 180 148 139 165
0.25in2 Al. 239 195 183 221
0.3in2 Al. 294 240 224 274
0.35in2 Al. 342 279 261 321
0.4in2 Al. 389 316 295 367
0.45in2 Al 432 352 328 411
0.5in2 Al. 501 409 381 479
0.55in2 Al. 556 455 423 535
0.6in2 Al 557 457 424 538
Parameters
Maximum depth of lay 1m
Aluminium conductors
120mm2 Al. 299 247 234 294
150mm2 Al. 336 277 262 335
185mm2 Al. 379 313 295 382
240mm2 Al. 436 362 340 448
260mm2 Al. 456 378 355 471
300mm2 Al. 491 407 382 514
350mm2 Al. 529 439 411 559
400mm2 Al. 557 463 433 594
500mm2 Al. 622 518 484 676
630mm2 Al. 696 581 541 774
Parameters
Maximum depth of lay 1m
Aluminium conductors
120mm2 Al. 344 270 252 294
150mm2 Al. 388 304 284 335
185mm2 Al. 440 344 320 382
240mm2 Al. 508 398 370 448
260mm2 Al. 532 417 387 471
300mm2 Al. 576 451 417 514
350mm2 Al. 622 487 449 559
400mm2 Al. 656 514 474 594
500mm2 Al. 737 578 531 676
630mm2 Al. 830 651 596 774
Parameters
Maximum depth of lay 1m
Aluminium conductors
120mm2 Al. 279 237 225 294
150mm2 Al. 313 266 252 335
185mm2 Al. 353 300 284 382
240mm2 Al. 406 346 326 448
260mm2 Al. 424 361 341 471
300mm2 Al. 457 389 367 514
350mm2 Al. 491 419 394 559
400mm2 Al. 517 441 415 594
500mm2 Al. 577 494 463 676
630mm2 Al. 645 552 517 774
Parameters
Maximum depth of lay 1m
Aluminium conductors
120mm2 Al. 324 262 246 294
150mm2 Al. 366 295 276 335
185mm2 Al. 414 333 311 382
240mm2 Al. 478 386 359 448
260mm2 Al. 500 404 375 471
300mm2 Al. 541 436 405 514
350mm2 Al. 584 470 436 559
400mm2 Al. 616 497 459 594
500mm2 Al. 692 558 515 676
630mm2 Al. 779 627 576 774
Parameters
Maximum depth of lay 1m
Aluminium conductors
120mm2 Al. 260 226 215 294
150mm2 Al. 291 253 241 335
185mm2 Al. 328 286 271 382
240mm2 Al. 377 329 312 448
260mm2 Al. 394 343 325 471
300mm2 Al. 424 370 350 514
350mm2 Al. 456 398 375 559
400mm2 Al. 479 419 395 594
500mm2 Al. 535 468 441 676
630mm2 Al. 598 523 492 774
Parameters
Maximum depth of lay 1m
Aluminium conductors
120mm2 Al. 304 253 237 294
150mm2 Al. 343 284 266 335
185mm2 Al. 388 321 300 382
240mm2 Al. 448 371 346 448
260mm2 Al. 469 388 362 471
300mm2 Al. 507 419 390 514
350mm2 Al. 547 452 420 559
400mm2 Al. 577 477 442 594
500mm2 Al. 647 535 495 676
630mm2 Al. 728 601 554 774
Parameters
Maximum depth of lay 1m
Aluminium conductors
120mm2 Al. 274 235 223 294
150mm2 Al. 308 263 250 335
185mm2 Al. 347 297 281 382
240mm2 Al. 398 342 324 448
260mm2 Al. 416 358 338 471
300mm2 Al. 448 385 363 514
350mm2 Al. 482 414 390 559
400mm2 Al. 507 437 411 594
500mm2 Al. 567 488 459 676
630mm2 Al. 633 546 512 774
Parameters
Maximum depth of lay 1m
Aluminium conductors
120mm2 Al. 319 260 244 294
150mm2 Al. 360 293 274 335
185mm2 Al. 408 331 310 382
240mm2 Al. 471 384 357 448
260mm2 Al. 492 401 373 471
300mm2 Al. 533 433 402 514
350mm2 Al. 575 467 433 559
400mm2 Al. 607 493 457 594
500mm2 Al. 681 554 511 676
630mm2 Al. 766 622 578 774
Parameters
Maximum depth of lay 1m
Copper conductors
0.1 in2 Cu 257 217 207 246
0.15in2 Cu. 316 267 255 307
0.2in2 Cu. 377 317 301 373
0.25in2 Cu 429 361 342 430
0.3in2 Cu. 480 404 382 487
0.35in2 Cu 519 437 413 532
0.4in2 Cu 559 472 445 578
0.45in2 Cu 594 502 473 619
0.5in2 Cu 613 521 491 645
0.6in2 Cu 677 573 539 726
Aluminium conductors
0.1 in2 Al. 199 168 161 191
0.15in2 Al. 245 207 198 238
0.2in2Al. 293 247 234 290
0.25in2 Al. 334 281 266 335
0.3in2 Al. 375 316 298 381
0.35in2 Al. 411 346 327 421
0.4in2 Al. 439 371 350 454
0.45in2 Al 469 396 373 488
0.5in2 Al. 488 413 389 511
0.6in2 Al 544 460 432 580
Parameters
Maximum depth of lay 1m
Copper conductors
0.1 in2 Cu 285 235 222 246
0.15in2 Cu. 354 291 275 307
0.2in2 Cu. 425 348 327 373
0.25in2 Cu 487 398 373 430
0.3in2 Cu. 547 448 419 487
0.35in2 Cu 594 487 455 532
0.4in2 Cu 641 526 492 578
0.45in2 Cu 684 561 524 619
0.5in2 Cu 709 584 544 645
0.6in2 Cu 789 646 601 726
Aluminium conductors
0.1 in2 Al. 222 182 172 191
0.15in2 Al. 274 225 213 238
0.2in2Al. 330 270 254 290
0.25in2 Al. 379 309 290 335
0.3in2 Al. 427 349 327 381
0.35in2 Al. 470 385 359 421
0.4in2 Al. 504 414 386 454
0.45in2 Al 539 442 412 488
0.5in2 Al. 562 462 430 511
0.6in2 Al 632 517 480 580
Parameters
Maximum depth of lay 1m
Copper conductors
0.1 in2 Cu 242 209 200 246
0.15in2 Cu. 298 257 246 307
0.2in2 Cu. 354 305 290 373
0.25in2 Cu 402 347 329 430
0.3in2 Cu. 449 387 367 487
0.35in2 Cu 486 419 397 532
0.4in2 Cu 523 452 428 578
0.45in2 Cu 556 481 454 619
0.5in2 Cu 577 499 471 645
0.6in2 Cu 636 547 515 726
Aluminium conductors
0.1 in2 Al. 188 162 155 191
0.15in2 Al. 231 200 191 238
0.2in2Al. 275 237 226 290
0.25in2 Al. 313 270 257 335
0.3in2 Al. 351 303 287 381
0.35in2 Al. 385 332 315 421
0.4in2 Al. 411 355 336 454
0.45in2 Al 439 379 358 488
0.5in2 Al. 457 395 373 511
0.6in2 Al 509 439 414 580
Parameters
Maximum depth of lay 1m
Copper conductors
0.1 in2 Cu 272 228 217 246
0.15in2 Cu. 336 283 268 307
0.2in2 Cu. 403 338 318 373
0.25in2 Cu 462 386 363 430
0.3in2 Cu. 518 434 407 487
0.35in2 Cu 562 471 442 532
0.4in2 Cu 607 509 477 578
0.45in2 Cu 648 543 508 619
0.5in2 Cu 673 565 527 645
0.6in2 Cu 748 624 581 726
Aluminium conductors
0.1 in2 Al. 211 177 168 191
0.15in2 Al. 261 219 208 238
0.2in2Al. 314 262 247 290
0.25in2 Al. 360 300 282 335
0.3in2 Al. 405 338 317 381
0.35in2 Al. 445 373 349 421
0.4in2 Al. 477 400 374 454
0.45in2 Al 510 428 400 488
0.5in2 Al. 532 446 417 511
0.6in2 Al 597 499 465 580
Parameters
Maximum depth of lay 1m
Copper conductors
0.1 in2 Cu 228 200 192 246
0.15in2 Cu. 279 246 236 307
0.2in2 Cu. 331 291 278 373
0.25in2 Cu 376 331 315 430
0.3in2 Cu. 420 369 351 487
0.35in2 Cu 454 399 379 532
0.4in2 Cu 488 430 408 578
0.45in2 Cu 519 457 433 619
0.5in2 Cu 538 474 449 645
0.6in2 Cu 592 521 493 726
Aluminium conductors
0.1 in2 Al. 176 155 149 191
0.15in2 Al. 217 191 183 238
0.2in2Al. 257 227 216 290
0.25in2 Al. 293 258 246 335
0.3in2 Al. 328 289 275 381
0.35in2 Al. 359 316 300 421
0.4in2 Al. 384 338 321 454
0.45in2 Al 409 361 342 488
0.5in2 Al. 426 376 356 511
0.6in2 Al 474 417 394 580
Parameters
Maximum depth of lay 1m
Copper conductors
0.1 in2 Cu 258 221 210 246
0.15in2 Cu. 319 273 259 307
0.2in2 Cu. 381 326 308 373
0.25in2 Cu 436 372 350 430
0.3in2 Cu. 489 418 393 487
0.35in2 Cu 530 453 426 532
0.4in2 Cu 573 490 459 578
0.45in2 Cu 610 522 489 619
0.5in2 Cu 634 542 508 645
0.6in2 Cu 703 599 560 726
Aluminium conductors
0.1 in2 Al. 200 171 163 191
0.15in2 Al. 247 212 201 238
0.2in2Al. 296 253 239 290
0.25in2 Al. 339 289 273 335
0.3in2 Al. 382 326 306 381
0.35in2 Al. 420 359 336 421
0.4in2 Al. 450 385 361 454
0.45in2 Al 481 411 385 488
0.5in2 Al. 502 429 402 511
0.6in2 Al 562 479 447 580
Parameters
Maximum depth of lay 1m
Copper conductors
0.1 in2 Cu 239 207 199 246
0.15in2 Cu. 293 255 244 307
0.2in2 Cu. 348 302 288 373
0.25in2 Cu 396 344 327 430
0.3in2 Cu. 442 384 364 487
0.35in2 Cu 478 415 394 532
0.4in2 Cu 515 448 424 578
0.45in2 Cu 547 476 450 619
0.5in2 Cu 567 494 467 645
0.6in2 Cu 625 543 513 726
Aluminium conductors
0.1 in2 Al. 185 161 154 191
0.15in2 Al. 228 198 189 238
0.2in2Al. 271 235 224 290
0.25in2 Al. 308 268 255 335
0.3in2 Al. 345 300 285 381
0.35in2 Al. 378 329 312 421
0.4in2 Al. 405 352 333 454
0.45in2 Al 432 375 355 488
0.5in2 Al. 449 391 370 511
0.6in2 Al 500 435 410 580
Parameters
Maximum depth of lay 1m
Copper conductors
0.1 in2 Cu 269 227 216 246
0.15in2 Cu. 333 282 267 307
0.2in2 Cu. 399 336 317 373
0.25in2 Cu 456 384 361 430
0.3in2 Cu. 512 431 405 487
0.35in2 Cu 555 468 439 532
0.4in2 Cu 600 506 474 578
0.45in2 Cu 639 539 505 619
0.5in2 Cu 664 561 524 645
0.6in2 Cu 738 621 578 726
Aluminium conductors
0.1 in2 Al. 209 176 167 191
0.15in2 Al. 258 218 207 238
0.2in2Al. 310 261 246 290
0.25in2 Al. 355 299 281 335
0.3in2 Al. 400 336 316 381
0.35in2 Al. 439 370 347 421
0.4in2 Al. 471 398 372 454
0.45in2 Al 504 425 398 488
0.5in2 Al. 525 443 415 511
0.6in2 Al 590 495 462 580
Parameters
Maximum depth of lay 1m
SUPERSEDED DOCUMENTATION
This document supersedes ST:SD8B/2 dated September 2003 which should now be
withdrawn.
APPENDIX B
ASSOCIATED DOCUMENTATION
APPENDIX C
This Standard Technique has been updated to add all four seasons to the cable rating
document instead of just having one season as given in the previous document. In addition
the document has been broken up into manageable parts, with each part being for a
particular voltage level.
APPENDIX D
IMPLEMENTATION OF POLICY
This Standard Technique shall be communicated to all relevant WPD Planning and Control
staff at the next Team Briefing by the relevant Team Manager.
APPENDIX E
KEY WORDS
33kV Group Derating, Sustained Rating, Cyclic Rating, Distribution Rating, Laid Direct
Rating, Duct Rating, Air Rating.