Guide For Cast-in-Place Low-Density Cellular Concrete: ACI 523.1R-06
Guide For Cast-in-Place Low-Density Cellular Concrete: ACI 523.1R-06
Guide For Cast-in-Place Low-Density Cellular Concrete: ACI 523.1R-06
com
ACI 523.1R-06
This guide provides information on the materials, properties, design, Chapter 3—Physical properties, p. 523.1R-4
proper handling, and applications of cast-in-place low-density cellular 3.1—As-cast density
concretes having oven-dry densities of 50 lb/ft 3 (800 kg/m3) or less. Roof 3.2—Oven-dry density 3.3
deck systems and geotechnical applications often incorporate these low- —Compressive strength 3.4
density cellular concretes.
—Drying shrinkage 3.5—
Keywords: cellular concrete; engineered fill; foaming agent; geotechnical Thermal expansion 3.6—
fill; insulating concrete; insulating concrete roof decks; low-density cellular Walkability 3.7—
concrete; low-density controlled low-strength material (LD-CLSM); Mechanical attachment 3.8
preformed foam. —Thermal conductivity 3.9
—Fire resistance 3.10—
CONTENTS Permeability
Chapter 1—General, p. 523.1R-2
1.1—Definition of cellular concrete 3.11—Freezing-and-thawing resistance
1.2—Definition of low-density, controlled low-strength
material (LD-CLSM) Chapter 4—Proportioning and testing, p. 523.1R-6
4.1—Proportioning
4.2—Ingredient compatibility
Chapter 2—Materials, p. 523.1R-2
2.1—Cement 4.3—Cast density 4.4—
2.2—Water 2.3— Physical properties
Preformed foam 2.4—
Aggregates 2.5— Chapter 5—Batching, mixing, placing, finishing,
and curing, p. 523.1R-7
Admixtures 2.6— 5.1—Storage of materials
Nonstandard materials 2.7 5.2—Batching
—Fiber reinforcement 5.3—Mixing
5.4—Placing
5.5—Finishing
ACI Committee Reports, Guides, Standard Practices, and 5.6—Curing
Commentaries are intended for guidance in planning,
designing, executing, and inspecting construction. This 5.7—Placement in cold-weather conditions
document is intended for the use of individuals who are 5.8—Placement in hot-weather conditions
competent to evaluate the significance and limitations of its
content and recommendations and who will accept
responsibility for the application of the material it contains. Chapter 6—Design considerations for roof decks,
The American Concrete Institute disclaims any and all p. 523.1R-8
responsibility for the stated principles. The Institute shall not 6.1—Form systems
be liable for any loss or damage arising therefrom.
Reference to this document shall not be made in contract ACI 523.1R-06 supersedes ACI 523.1R-92 and became effective August 15,
documents. If items found in this document are desired by the 2006. Copyright © 2006, American Concrete Institute.
Architect/Engineer to be a part of the contract documents, All rights reserved including rights of reproduction and use in any form or by any
means, including the making of copies by any photo process, or by electronic or
they shall be restated in mandatory language for mechanical device, printed, written, or oral, or recording for sound or visual reproduction
incorporation by the Architect/Engineer. or for use in any knowledge or retrieval system or device, unless permission in
writing
Provided by IHS under license with ACI
i s o`,b``t`a``i,n``e``d-
--```````,,,,,` ` `,
f r o,`m,,`,t`h,,e`--c-opyright
` -` ,
proprietors.
523.1R-1
Licensee=University of Texas Revised
Sub Account/5620001114,
User=yuyuio, rtyru
No reproduction or networking permitted without license from IHS Not for Resale, 01/26/2015 03:34:46 MST
Daneshlink.com
daneshlink.com
6.2—Roofing readiness 6.3 mixture is preformed foam, it is critical that all admixtures be
—Load-carrying capacity compatible with the preformed foam within the specific
6.4—Expansion and contraction joints
6.5—Relief of vapor pressure 6.6—
Standard roofing details
CHAPTER 1—GENERAL
1.1—Definition of cellular concrete
--
``
``
``
an oven-dry
``
-
`-
may `,
,`
--
1.2—Definition of low-density,
controlled low-strength material (LD-
CLSM)
Controlled low-strength material (CLSM) is a cementitious
material that is in a flowable state at the time of placement,
and that has a specified compressive strength of 1200 psi
(8.3 MPa) or less at the age of 28 days. This material is
discussed further in ACI 229R. Low-density CLSM (LD-
CLSM) meets this definition, and has a cast density that is
controllable from 20 to 50 lb/ft3 (320 to 800 kg/m3). The
quantity of preformed foam in the mixture determines the
mixture’s final density.
CHAPTER 2—MATERIALS
The basic materials in low-density cellular concrete are
cement, water, and preformed foam. Because the main
ingredient by volume of a low-density cellular concrete
Copyright American Concrete Institute
Provided by IHS under license with ACI Licensee=University of Texas Revised Sub Account/5620001114, User=yuyuio, rtyru
No reproduction or networking permitted without license from IHS Not for Resale, 01/26/2015 03:34:46 MST
Daneshlink.com
daneshlink.com
2.1—Cement
The cement should meet the requirements of ASTM C 150
(portland cement), C 595 (blended cement), or C 1157
(hydraulic cement). Blended cements include cement
containing combinations of portland cement,
pozzolans, slag, other hydraulic cement, or some
combination of these. Blended cement may result in
lower rates of early strength
2.2 —Water
Mixing water for concrete should be clean and free from
detrimental amounts of oils, acids, alkalis, salts, organic
materials, or other substances deleterious to concrete or
reinforcement. Any nonpotable water should be tested for
hardness, pH, suspended solids, total salt content, and
other characteristics that might affect the preformed
foam, the setting time, and the strength of the low-density
cellular concrete.
--
``
``
2.4 —Aggregates
``
`,
,,
Low-density cellular concrete may include lightweight
aggregates such as vermiculite or perlite meeting the require-
,,
``
`,
`,
``
``
`,
ments of ASTM C 332 Group 1 to lower the slump to
achieve steeper roof slopes, and to maintain moisture in dry
``
``
-
`-
`,
,`
,,
climates. Wilson (1981) provides additional information on
the use of lightweight aggregates used in cellular concrete.
`,
`,
,`
--
-
Any proposed aggregates should be tested for physical
properties, pumpability, and compatibility in trial mixtures.
2.5—Admixtures
2.5.1 Chemical admixtures—Chemical admixtures, such
as water-reducing admixtures and set accelerators, are used
with cellular concretes. Water-reducing admixtures can
improve compressive strength for special mixtures or
Fig. 2.1—Diluting foam concentrate in water (click on pic- ture to
view video).
--
``
``
``
`,
,,
,,
``
`,
`,
``
``
`,
``
``
-
`-
`,
,`
,,
Fig. 3.1—Measuring as-cast density (click on picture to
`,
`,
,`
view video).
--
-
strength). As a result, these densities and compressive 0.30 to 0.60% after 6 months at 50% relative
strengths are lower than those for roof deck applications humidity and 73 °F (23 °C), and increases with
(Table 3.2). If standard materials are used, the density of decreasing density. Some of the effects of drying
the low-density cellular concrete has properties that fall shrinkage can be mitigated by adding
within ranges specified by the manufacturer of the foam
concentrate. If nonstandard materials are used, special test
batches may be required to confirm specific properties. To
define the general relationship between cast density and
--
``
``
compressive strength for specific applications, one
``
`,
,,
manufacturer has divided the cast density into convenient
ranges.
,,
``
`,
`,
3.4—Drying shrinkage
Drying shrinkage is not usually critical in cellular
concrete
used for roof deck insulation or geotechnical applications.
The reason for this is that when cellular concrete is used to
insulate roof decks, it is not considered to contribute structur-
ally; and when it is used in geotechnical applications, any
shrinkage cracking that it might undergo does not
significantly reduce bearing capacity. Drying shrinkage
is typically
fibers to the mixture (Section 2.7). Figure 3.2 relates drying
shrinkage at 56 days to the air-dry density of cellular concrete
(ASTM C 157).
3.5—Thermal expansion
The coefficient of thermal expansion for cellular concrete varies
directly with density, and is typically 5.0 to 7.0 × 10–6
per °F (9.0 to 12.6 × 10–6 per °C) as evaluated using a linear
thermal expansion test with strain gauges. The designer should
consider thermal expansion in applications with
significant variation in placing temperatures, operating
temperatures, or both. These conditions could occur in appli-
cations such as roof decks, power plants, ovens, and steam lines.
3.6—Walkability
Walkability, a term developed to describe the ability of low-
density concrete to sustain normal construction foot traffic without
damage, is best judged by examining surface distress. Walkability
improves with increased density. When heavy construction traffic
is expected (such as from wheel- barrows, scaffolds, material
storage, or pathways), the surface of the roof deck should be
protected with wooden boards or by a similar method.
3.7—Mechanical attachment
For roof deck applications, the roofing base sheet should be
mechanically attached to the low-density cellular concrete roof
deck using specifically designed nails or screws (Fig. 3.3).
Fastening within 2 to 7 days of concrete placement is possible if
the fastener can be installed without shattering or spalling the
cellular concrete and if an installed fastener has a minimum
specified withdrawal resistance of 40 lb (180 N), which is
consistent with required wind-uplift resistance and typical nailing
patterns (such as three rows,
523.1R-6 ACI COMMITTEE REPORT
4.3—Cast density
Measuring the cast density at the point of placement is
the simplest and most convenient test for monitoring the
quality of the placed material. Cylinder specimens for
compressive strength tests, usually measuring 3 x 6 in. (76
x 150 mm), should be cast at the same time that periodic
density tests are performed. These samples should be
covered and stored in a protected area for at least 24 hours
before they are trans- ported to the testing laboratory for
testing in accordance with ASTM C 796.
4.4—Physical properties
--
``
``
``
`,
,,
,,
For standard mixtures made from standard materials, cast
density determines the physical properties of the cellular
``
`,
`,
``
5.2—Batching
Materials for low-density cellular concrete are typically
proportioned and batched on site, directly into a specialized
mixer. The cement, fly ash, and other dry materials are
weighed on a calibrated scale, and the mixing water is
metered. The preformed foam is metered into the mixture
through a cali- brated nozzle. The accuracy of each batching
device is critical to the final mixture density and its
subsequent reproducibility. Each batching device (scales,
water meter, foam-generating nozzle) should be calibrated
before starting a project, and during a project if there is a
reason to believe it is necessary.
5.3—Mixing
Mechanically mixing cellular concrete produces a
uniform distribution of materials with a suitable
consistency at the specified as-cast density. Excessive
In batch mixing, the mixer should be charged with mixture water
and dry ingredients, followed by special admixtures and the
preformed foam. The as-cast density should be monitored at the
point of placement every 30 to 60 minutes based on consistency of
results. Allowance should be made for any density changes that
result from placing methods or conditions, such as pumping
distances and extreme weather conditions. Ingredients should be
added in the proper propor- tions and sequence during continuous
mixing operations. This is necessary to ensure reasonable
uniformity and achieve the required as-cast density at the point of
placement.
Standard concrete mixing equipment is normally not acceptable
for low-density cellular concrete mixtures because the action of the
mixer does not combine the ingredi- ents with the correct speed and
mixing action. A high-speed paddle mixer is preferable because it
properly combines the ingredients and blends the preformed foam
rapidly and efficiently to produce a uniformly consistent low-
density cellular concrete mixture. Other mixers and processes that
produce uniform mixtures include high-shear mixers.
5.4—Placing
Cellular concrete should be placed by a progressive-cavity pump
or a peristaltic pump. The pump hose should be large enough in
diameter (usually 2 to 2.5 in. [51 to 64 mm]) to ensure uniform
delivery of cellular concrete at the point of placement without
damage to the structure or substrate. Low-density cellular concrete
can be pumped over long distances (over 1500 ft [460 m]). This is
a major advantage for low-density cellular concrete over other
materials and placing methods, and is important on large,
congested projects with difficult access.
5.5—Finishing
For roof deck applications, cellular concrete should be finished
to the slope and thickness specified on the project drawings. A
minimum slope for proper roof drainage is 2% (equivalent to 1/4
in./ft [21 mm/m]). It is possible to place this material on steeper
slopes. The cellular concrete surface is usually finished with a
darby or screeded to the specified slope (Fig. 5.1). The surface
should be smooth and free from ridges, projections, and
depressions that might adversely affect the roofing membrane.
For geotechnical applications, lift thicknesses ranging from 2 to
4 ft (0.6 to 1.2 m) are typical. The lift thickness is job-specific and
related to the project layout and casting procedure. A greater lift
thickness is acceptable for specific job conditions. The heat of
hydration developed within the mass, the material density, the
cement content, and the ambient temperature also influence the lift
thickness. Thinner castings reduce the heat buildup from hydration
of the cement. It is desirable to cast material in a formed area
within 1 or 2 hours to permit an undisturbed setting. In general,
low-density cellular concrete should be cast to final grade with a
tolerance of 0.1 ft (0.03 m). It is not necessary to scarify
intermediate lift surfaces. A darby finish is acceptable for the final
lift.
523.1R-8 ACI COMMITTEE REPORT
insulation
5.6—Curing for concrete roof deck fills. The cellular concrete is cast over
--```````,,,,,```,`,`````,````-`-`,,`,,`,`,,`---
Water curing or use of a curing compound is advisable the structural deck system of the building. Typical deck
for
roof deck applications when rapid drying is anticipated.
Curing compounds should be compatible with the final
roofing system. Traffic should not be permitted on freshly
placed cellular concrete roof decks until adequate
walkability (Section 3.6) is demonstrated. Check with the
manufacturer of foaming agent for specific
recommendations to ensure compatibility with subsequent
roofing membrane material.
6.2—Roofing readiness
A roof membrane can generally be installed 2 to 5
days after a cellular concrete roof deck has been cast if
the mois- ture content is deemed to be acceptable for
roofing membrane application. The surface hardness of
the cellular concrete should be adequate to withstand
foot traffic and other light roofing operations without
damage. The screeded surface of the cellular concrete
should be smooth and free from ridges or depressions
that would adversely affect the integrity of the roofing
membrane. Ridges should be scraped flat. Roofing base
sheets are commonly attached to the roof deck by
nailing. The roofing membrane is commonly attached
to the base sheet by mopping or torch-heating. Other
roofing-attachment systems should be compatible with
CAST-IN-PLACE LOW-DENSITY CELLULAR CONCRETE 523.1R-9
--```````,,,,,```,`,`````,````-`-`,,`,,`,`,,`---
Fig. 6.2—EPS insulation board placed in cellular concrete
Fig. 6.1—Casting cellular concrete over vented steel slurry over structural concrete deck.
deck.
Fig. 6.3—Typical roofing details for cellular concrete roof decks.
523.1R-10 ACI COMMITTEE REPORT
--
``
``
``
`,
,,
,,
``
`,
`,
``
``
`,
``
``
-
`-
`,
,`
,,
`,
`,
,`
--
-
the cellular concrete and with the substrate (the structure that roof
provides the required wind uplift resistance).
7.1 —Backfill
Low-density cellular concrete placed around and
next to structures such as bridge abutment and
retaining and building walls significantly reduces the
dead load over poor soils (Fig. 7.1 and 7.2).
Once low-density cellular concrete sets, it does not
exert active lateral pressure against the wall structure,
as does standard granular backfill. Because low-density
cellular
CAST-IN-PLACE LOW-DENSITY CELLULAR CONCRETE 523.1R-11
concrete is cementitious, it does not require compaction, that are to be abandoned rather than demolished
and because it has low density, settlement is minimal. (Fig. 7.5).
Bridge approach applications may often be from 10 to 40 ft
(3.0 to 12 m) or more in height. A low-density fill that does
not require compaction is often a preferred alternative to
heavy, compacted fill.
Most of the fill thickness of cellular concrete should be
cast at a density of 30 lb/ft3 (480 kg/m3). The top 2 to 3 ft
(610 to 910 mm) is usually 42 lb/ft 3 (675 kg/m3) cellular
concrete, which has excellent resistance to freezing and
thawing and provides a solid base for an approach slab or
pavement structure.
--```````,,,,,```,`,`````,````-`-`,,`,,`,`,,`---
Fig. 7.4—Geotechnical fill around steel culvert under existing bridge.
CHAPTER 8—REFERENCES
`,
,,
,,
``
`,
`,
``
8.1—Referenced standards and reports
``
`,
``
The standards and reports listed below were the latest
editions at the time this document was prepared. Since
``
-
`-
`,
,`
,,
`,
frequent revisions occur with some of these documents, the
reader is advised to contact the appropriate sponsoring
`,
,`
--
-
E 119 Test Methods for Fire Tests of Building Kearsley, E. P., and Wainwright, P. J., 2001a, “Porosity
Construction and Materials and Permeability of Foamed Concrete,” Cement and
Concrete Research, V. 31, No. 5, May, pp. 805-812.
The above publications may be obtained from:
Kearsley, E. P., and Wainwright, P. J., 2001b, “The
Effect of High Fly Ash Content on the Compressive
American Concrete Institute
Strength of Foamed Concrete,” Cement and Concrete
38800 Country Club Drive Research, V. 31, No. 1, Jan., pp 105-112.
Farmington Hills, MI 48331
Kearsley, E. P., and Wainwright, P. J., 2002a, “Ash
www.concrete.org
Content for Optimum Strength of Foamed Concrete,”
Cement and Concrete Research, V. 32, No. 2, Feb., pp.
ASTM International
241-246.
100 Barr Harbor Drive
Kearsley, E. P., and Wainwright, P. J., 2002b, “The
West Conshohocken, PA 19428-2959
Effect of Porosity on the Strength of Foamed Concrete,”
www.astm.org
Cement and Concrete Research, V. 32, No. 2, Feb., pp.
233-239.
8.2—Cited references
Abrams, M. S., and Gustaferro, A. H., 1969, “Fire Legatski, L. A., 1994, “Chapter 49—Cellular Concrete,”
Endur- Significance of Tests and Properties of Concrete and
ance of Two-Course Floors and Roofs,” ACI JOURNAL, Concrete-Making Materials, ASTM STP 169C, ASTM
Proceedings V. 66, No. 2, Feb., pp. 92-102. International, West Conshohocken, Pa.
ACI Committees 213 and 523, 1971, Lightweight MacDonald, W.; Pospisil, J.; and Tikalsky, P. J., 2004,
Concrete, SP-29, American Concrete Institute, Farmington “A Method for Assessment of the Freeze-Thaw Resistance
Hills, Mich., 321 pp. of Preformed Foam Cellular Concrete,” Cement and
ANSI/SPRI FX-1-2001, 2001, “Standard Field Test Concrete Research, V. 34, No. 5, May, pp. 889-893.
Procedure for Determining the Withdrawal Resistance of National Bureau of Standards, 1955, “Thermal
Roofing Fasteners.” Conductivity Versus Oven-Dry Density,” Technical News,
Engineered Fill, 2001, “Elastizell EF (Engineered Fill) V. 39, Bulletin 39, No. 3, Mar., U. S. Department of
Geotechnical Applications,” Elastizell Corp., 16 pp. Commerce.
Giannakou, A., and Jones, M. R., 2004, “Thermally Insu- National Roofing Contractors Association, 2001, The
lating Foundations and Ground Slabs Using Highly- NRCA Roofing and Waterproofing Manual, 5th Edition,
Foamed Concrete,” ASTM Special Technical Publication Rosemont, Ill.
No. 1459, pp. 100-112. Wilson, H. S., 1981, “Lightweight Aggregates—Vermic-
Gustaferro, A. H.; Abrams, M. S.; and Litvin, A., 1970, ulite, Perlite, Pumice—for Insulating Concretes,”
“Fire Resistance of Lightweight Insulating Concretes,” CANMET Report No. 81-15E, Energy Mines and Resources
Research and Development Bulletin No. RD004B, Portland Canada, Ottawa, 28 pp.
Cement Association, Skokie, Ill., 12 pp. Zollo, R. F., and Hays, C. D., 1998, “Engineering
Material Properties of a Fiber-Reinforced Cellular
Concrete,” ACI Materials Journal, V. 95, No. 5, Sept.-Oct.,
pp. 631-635.
--```````,,,,,```,`,`````,````-`-`,,`,,`,`,,`---