Hart Communicator: Asset Management Solutions
Hart Communicator: Asset Management Solutions
HART® Communicator
• Connect to any HART® instrument
with the HART® Communicator–the
only communicator you’ll need
• Store over 100 device configurations
in just one HART Communicator–
ready to carry to the field
HART® Communicator
• Hook it up and turn it on–that’s how
easy it is to use the HART
Communicator
• Program the Hot Key for fast access
0275_007B
to routine tasks
Accessories-9
HART® Communicator
The only device you’ll ever need to get information Increase productivity with the ability to carry over
from your HART instruments. The Model 275 HART 100 device configurations to the field. The Model 275
Communicator has device HART Communicator has the ability to hold up to 10
descriptions built- Start here.... configurations in the Memory
in for all of the Module. But you told us you needed
devices available more. You needed a way to increase
today that are the productivity of your maintenance
HART capable. staff so the number of trips to the
275_DATA
Period. The HART field could be reduced. That is why
Communicator we introduced the Fisher-Rosemount
can “talk smart”! data pack 100. This compact data
That means you storage device plugs into the Memory
can reduce your Module and allows up to an
investment in additional 100 configurations to be
communications carried with the HART
HART® Communicator
275_HAND1
Streamline regulatory documentation preparation
configurations
through access to historic configuration and
into the field!
as found/as left data. It often takes longer to
document what is found in the field than it takes to The data pack
make a change in the device. Combine the 100 is totally
convenience of the portable handheld with the power modular and
of Asset Management Solutions software. Use your self-contained.
HART Communicator to upload and download You can easily
information to and from exchange data
download it....
all of your packs so that
HART you have a permanent, quickly accessible historical
devices. Use record of all of the data for each device in the field.
your Asset
Management
Solutions
0275_TRANS1
software to
simply upload
device and upload it....
information to your plant network
from your
HART
Communicator to your PC. You no longer have to dig
in file cabinet after file cabinet for device
information. All of the information you need to
satisfy regulatory requirements is at your fingertips,
0275_PHOTO1
Accessories-10
Rosemount Inc.
Online Menu
Function Keys When connected to a HART-compatible device,
simply press the On Key to display the online menu.
HART® Communicator
This menu contains the most critical information
about the connected device and your measurement,
LCD
including:
Alphanumeric • User-defined Tag
Keys
Action Keys
• Actual Input (process variable)
• Actual Analog Output
0275_DEVICE
Action Keys
FIGURE 2.The HART Communicator provides features that
Six Action Keys promote easy navigation through
make the communicator fast to learn and easy to use. the menu structure.
Hot Key
Customize the Hot Key to quickly access a menu of
0275_006B
Accessories-11
HART® Communicator
0275_EX;EX1
mode is a training tool that enables you to become
familiar with a device before configuring it in a
critical environment. Access the simulation mode
through the Utility Menu.
• Factory Mutual (FM) - Intrinsic Safety
Save Approval
Save allows you to quickly store the current
configuration data under the current Tag,
Descriptor, or Name by pressing the F2 key
0275_FM
when SAVE appears as a dynamic label. Save As
HART® Communicator
Data Type
0275_CSA
The HART Communicator allows you to specify
which variables to save under the current
configuration. The three choices are:
• Standard The set of all editable variables
defining a new device Memory Module
configuration. The Memory Module is programmed with the
• Partial The set of all marked device operating system software and the application
variables. software for a desired set of HART compatible
devices. This allows you to easily expand the
• Full The set of all variables. capability of your HART Communicator as new field
devices and product enhancements become available.
Polling The Memory Module also stores device configuration
The HART protocol allows for the connection of data for up to 10 HART compatible devices.
multiple HART devices on a single twisted pair of
wires, or over leased telephone lines. This concept is
0275_HAND;DATA
known as “multidropping.” A single HART
Communicator can interface with multiple devices
on one transmission line. Communication between a
host and a multidropped device takes place digitally,
with the analog output fixed. In a multidrop
installation, each device is identified by a unique
address (1-15). Use the Auto Poll option to direct the MEMORY MODULE FISHER-ROSEMOUNT
data pack 100
HART Communicator to search for a connected
device at an address other than zero. When Auto
Polling is on, the communicator finds every device in
the loop and lists them by tag. Fisher-Rosemount data pack 100
The data pack 100 allows the user to store up to 100
Hazardous Locations Certifications device configurations in removable, nonvolatile
The HART Communicator meets the Intrinsic memory. Users can easily store configuration data
Safety requirements of the listed regulatory for all their HART devices on a small number of data
agencies. Selecting one of the Hazardous Locations packs. Each data pack easily fits in the palm of your
Certification options provides for the required hand or shirt pocket. The data pack is installed at
labeling and information on the HART the top end of the memory module and can be simply
Communicator. The approval options currently accessed by removing the battery pack.
offered include:
Accessories-12
Rosemount Inc.
HART® Communicator
Battery holder for 5 disposable Flammable Atmospheres (BASEEFA/CENELEC) Intrinsic
AA 1.5 V batteries. Safety Certification:
Rechargeable Ni-Cad battery pack. I1 EEX ia IIC T4 (Tamb = 50 °C)
Recharger Service and Plug Type Certificate No. Ex 92C2516
110/120 VAC, 50/60 Hz, U.S. plug Factory Mutual (FM) Intrinsic Safety Approval:
220/230 VAC, European plug. I5 Intrinsically Safe for Class I, Division 1, Groups A, B, C,
and D; Non-incendive for Class I, Division 2, Groups A, B,
220/230 VAC, U.K. plug.
C, and D.
Microprocessors
Canadian Standards Association (CSA) Intrinsic Safety
32-bit Motorola type 68331. Approval
8-bit Motorola type 68HC05. I6 Class 2258 03; Process Control Equipment – Intrinsically
Connections Safe and Non-Incendive Systems; For Hazardous
Locations. Products Class I, Groups A, B, C, and D.
Leadset: Two 4 mm banana
plugs. Electromagnetic Compatibility (EMC)
*EMC compliant only when the CE logo appears on both the
Battery charger: 2.1 mm coaxial power
keypad assembly and Memory Module.
connector (optional).
EN50081-1:1992
Serial port: 9-pin D subminiature
EN50082-1:1992
socket.
Memory Module: 26-pin, 2-row, 0.1-inch
pitch connector.
PHYSICAL SPECIFICATIONS
Display
Leadset Jacks
Serial Port 8-line by 21-character (128 by 64 pixels) liquid crystal display.
Keypad
25 large keys including six Action keys, a complete
alphanumeric keypad, four software-defined Function Keys;
membrane design with tactile feedback.
Weight
Approximately 3 lb (1.4 kg) with Ni-Cad battery pack.
0275_BACK
Accessories-13
HART® Communicator
Still undecided? Let us tell you more... That’s why Fisher-Rosemount has created a family
The HART Communicator is the key to unlocking of PERFORMANCE software programs called Asset
the power of your intelligent instruments. But Management Solutions (AMS). This revolutionary
configuration, calibration, and maintenance of set of software applications is more than just a
intelligent devices in the field is only a small part of database of information about your field devices, it is
your job. You have to plan your maintenance a tool to help you manage the process better. You can
schedule, meet the day-to-day demands of problems simply drag and drop information from your
in the field that simply don’t allow you time for connected HART Communicator directly into your
preventative maintenance, and you still have database. The software does the rest. You have
another challenge–keeping accurate records of what instant access to all devices. And, with all device
you have done. This is the most time consuming part data at your fingertips, you can configure devices
of your job. In fact some days you spend more time quickly, download them to your HART
documenting what you have done than you spent Communicator and be ready to head out to the field.
doing it! What could be easier?
HART® Communicator
0275_AMEXPLO;275
Simply Drag and Drop information from the HART Communicator to the Asset Management Solutions Database or download data to the
HART Communicator and be ready to take the information to the field!
Accessories-14
Rosemount Inc.
Spare Parts
Part Number Description
HART® Communicator
➆ 00275-0096-0001 Ruggedized 250 Ohm Load Resistor
(1)Requires Asset Management Solutions (AMS) Software with 275 Interface Kit Option.
➆
➇ ➈
➀ ➃
➄
➁
0275_004B
Accessories-15
HART® Communicator
ORDERING INFORMATION
Model Product Description
275 HART Communicator(1)
Code Language
HART® Communicator
E English
G German
J Japanese
HART COMMUNICATIONS
The HART Communicator interfaces with any HART instrument from any wiring termination point in a
4–20 mA loop, provided a minimum load resistance of 250 ohms is present between the communicator and
power supply. The HART Communicator uses the Bell 202 frequency shift keying (FSK) technique. This
technique superimposes high-frequency digital communication signals on the standard 4–20 mA transmitter
current loop. Because the net energy added to the loop is zero, communication does not disturb the 4–20 mA
signal.