ASSET MANAGEMENT SOLUTIONS

HART® Communicator
• Connect to any HART® instrument
with the HART® Communicator–the
only communicator you’ll need
• Store over 100 device configurations
in just one HART Communicator–
ready to carry to the field

HART® Communicator
• Hook it up and turn it on–that’s how
easy it is to use the HART
Communicator
• Program the Hot Key for fast access

0275_007B
to routine tasks

FIGURE 1.Plant maintenance is faster when over 100


configurations can be carried directly to the field.

INTRODUCTION to 10 configurations. But 10 configurations is often


not enough to meet your day to day requirements.
What would you say if you could carry the
The Fisher-Rosemount data pack 100 was designed
information for more than 100 HART compatible
to meet this need. The Fisher-Rosemount data pack
field devices in the palm of your hand? You can with
100 slips easily into the memory module to add
the HART Communicator. The HART
enough memory for up to an additional 100
Communicator, with one Fisher-Rosemount data
configurations. The data pack 100 may be removed
pack 100, empowers you to increase productivity,
and kept as a permanent historical record of
reduce trips to the field, and gather the kind of data
instrument activity. Whether you are taking
you need to reduce process downtime.
information from the field back to the shop, or from
How about using the HART Communicator? Is it the shop to the device, you have the information you
easy to use? How long does it take to learn? Can you need.
customize the screen to your specific needs? Yes, it’s
The HART Communicator is also a data input device
easy, fast to learn, and you can customize the Hot
for your plant database. With new Asset
Key for your most frequent tasks. In fact, when you
Management Solutions (AMS) software, you can
connect the HART Communicator to a HART device,
move information from your HART Communicator
the tag and model number of the connected device
directly to your PC. The combination of the HART
are automatically displayed on the top line of the
Communicator and a PC equipped with AMS
LCD screen!
software gives you an instrument database that
The standard HART Communicator, with 8 MB of enables you to more efficiently and effectively
memory, contains device descriptions for all HART manage the instrument assets that are the
devices, regardless of manufacturer. It also holds up foundation of the process.

Accessories-9
HART® Communicator

The only device you’ll ever need to get information Increase productivity with the ability to carry over
from your HART instruments. The Model 275 HART 100 device configurations to the field. The Model 275
Communicator has device HART Communicator has the ability to hold up to 10
descriptions built- Start here.... configurations in the Memory
in for all of the Module. But you told us you needed
devices available more. You needed a way to increase
today that are the productivity of your maintenance
HART capable. staff so the number of trips to the

275_DATA
Period. The HART field could be reduced. That is why
Communicator we introduced the Fisher-Rosemount
can “talk smart”! data pack 100. This compact data
That means you storage device plugs into the Memory
can reduce your Module and allows up to an
investment in additional 100 configurations to be
communications carried with the HART
HART® Communicator

devices because Communicator. That means that


get it ready....
the HART Communicator takes care of all your one maintenance person can carry
needs. Every maintenance person needs a HART the data for
Communicator. It’s an investment in productivity. more than 100
field device

275_HAND1
Streamline regulatory documentation preparation
configurations
through access to historic configuration and
into the field!
as found/as left data. It often takes longer to
document what is found in the field than it takes to The data pack
make a change in the device. Combine the 100 is totally
convenience of the portable handheld with the power modular and
of Asset Management Solutions software. Use your self-contained.
HART Communicator to upload and download You can easily
information to and from exchange data
download it....
all of your packs so that
HART you have a permanent, quickly accessible historical
devices. Use record of all of the data for each device in the field.
your Asset
Management
Solutions
0275_TRANS1

software to
simply upload
device and upload it....
information to your plant network
from your
HART
Communicator to your PC. You no longer have to dig
in file cabinet after file cabinet for device
information. All of the information you need to
satisfy regulatory requirements is at your fingertips,
0275_PHOTO1

from anywhere in the plant! Any PC in the plant


equipped with Asset Management Solutions
PERFORMANCE software applications can call up
information about any smart device in the plant.
That’s field power. That’s efficiency. And most of all,
that’s ease of use.

Accessories-10
Rosemount Inc.

PRODUCT INFORMATION Function Keys


Use the four function keys, marked F1 through F4,
User Interface located below the LCD to perform software functions
A keypad, a liquid crystal display (LCD), and a as indicated by the dynamic labels. Different labels
software menu structure make up the HART appear over the four function keys as you move
Communicator user interface. Just press a few among the various menus. For example, the
buttons to become familiar with the Action Keys and label SAVE appears above the F2 key when
menu structure, and you begin to access all of the device information can be saved, and the
functions of your HART devices. label HELP appears above the F1 key when
access to online help is available. See Figure 2.

Online Menu
Function Keys When connected to a HART-compatible device,
simply press the On Key to display the online menu.

HART® Communicator
This menu contains the most critical information
about the connected device and your measurement,
LCD
including:
Alphanumeric • User-defined Tag
Keys
Action Keys
• Actual Input (process variable)
• Actual Analog Output
0275_DEVICE

• Lower Range Value (LRV)


Shift Keys • Upper Range Value (URV)

Action Keys
FIGURE 2.The HART Communicator provides features that
Six Action Keys promote easy navigation through
make the communicator fast to learn and easy to use. the menu structure.

LCD ON/OFF UP HOT KEY


The LCD is an eight-line by twenty-one-character
display that provides a window to all the functions of
a HART compatible device. When connected to a
HART device, the top line of each online menu
displays the model name of the device and its tag
number. The bottom line of each online menu is
reserved for a dynamic label for each function key,
F1 through F4.

OUT/LEFT DOWN 0275_005B


IN/RIGHT

FIGURE 4.Action Keys.

Hot Key
Customize the Hot Key to quickly access a menu of
0275_006B

your most frequently performed online tasks. The


Hot Key Menu is a user-definable menu containing
one permanent option, Range Values. Range Values
provides quick access to rerange capability. Up to 19
of your frequently performed tasks can also be added
to this menu. These tasks, stored even when the
FIGURE 3.The Online menu along with the Function Keys. communicator is off, are always readily available by
simply pressing the Hot Key.

Accessories-11
HART® Communicator

Simulation Mode • (BASEEFA)/CENELEC - Intrinsic Safety


The HART Communicator provides a mode that Certification
allows you to simulate an online connection to a
specific HART compatible device. The simulation

0275_EX;EX1
mode is a training tool that enables you to become
familiar with a device before configuring it in a
critical environment. Access the simulation mode
through the Utility Menu.
• Factory Mutual (FM) - Intrinsic Safety
Save Approval
Save allows you to quickly store the current
configuration data under the current Tag,
Descriptor, or Name by pressing the F2 key

0275_FM
when SAVE appears as a dynamic label. Save As
HART® Communicator

lets the user store configuration data under a user-


specified Name Location (Memory Module or Fisher-
Rosemount data pack 100) and Data Type
(Standard, Partial or Full). Data may be stored in • Canadian Standards Association (CSA) -
the Memory Module or in the removable data pack Intrinsic Safety Approval
as a portable, nonvolatile file.

Data Type

0275_CSA
The HART Communicator allows you to specify
which variables to save under the current
configuration. The three choices are:
• Standard The set of all editable variables
defining a new device Memory Module
configuration. The Memory Module is programmed with the
• Partial The set of all marked device operating system software and the application
variables. software for a desired set of HART compatible
devices. This allows you to easily expand the
• Full The set of all variables. capability of your HART Communicator as new field
devices and product enhancements become available.
Polling The Memory Module also stores device configuration
The HART protocol allows for the connection of data for up to 10 HART compatible devices.
multiple HART devices on a single twisted pair of
wires, or over leased telephone lines. This concept is

0275_HAND;DATA
known as “multidropping.” A single HART
Communicator can interface with multiple devices
on one transmission line. Communication between a
host and a multidropped device takes place digitally,
with the analog output fixed. In a multidrop
installation, each device is identified by a unique
address (1-15). Use the Auto Poll option to direct the MEMORY MODULE FISHER-ROSEMOUNT
data pack 100
HART Communicator to search for a connected
device at an address other than zero. When Auto
Polling is on, the communicator finds every device in
the loop and lists them by tag. Fisher-Rosemount data pack 100
The data pack 100 allows the user to store up to 100
Hazardous Locations Certifications device configurations in removable, nonvolatile
The HART Communicator meets the Intrinsic memory. Users can easily store configuration data
Safety requirements of the listed regulatory for all their HART devices on a small number of data
agencies. Selecting one of the Hazardous Locations packs. Each data pack easily fits in the palm of your
Certification options provides for the required hand or shirt pocket. The data pack is installed at
labeling and information on the HART the top end of the memory module and can be simply
Communicator. The approval options currently accessed by removing the battery pack.
offered include:

Accessories-12
Rosemount Inc.

SPECIFICATIONS PERFORMANCE SPECIFICATIONS

Memory Operating Limits


Program (and Device Descriptions):8 32 to 122 °F (0 to 50 °C).
MB (standard). Storage Limits
Program (and Device Descriptions): –4 to 158 °F (–20 to 70 °C).
4 MB (optional).
Humidity Limits
Transmitter data (standard):2 KB.
Operates in 0–95% relative humidity under noncondensing
Transmitter data conditions over the entire operating range of 32 to 122 °F (0 to
(optional data pack 100): 32 KB 50 °C).
removable nonvolatile memory.
Hazardous Location Certification
Battery Pack Option
British Approvals Service for Electrical Equipment in

HART® Communicator
Battery holder for 5 disposable Flammable Atmospheres (BASEEFA/CENELEC) Intrinsic
AA 1.5 V batteries. Safety Certification:
Rechargeable Ni-Cad battery pack. I1 EEX ia IIC T4 (Tamb = 50 °C)
Recharger Service and Plug Type Certificate No. Ex 92C2516
110/120 VAC, 50/60 Hz, U.S. plug Factory Mutual (FM) Intrinsic Safety Approval:
220/230 VAC, European plug. I5 Intrinsically Safe for Class I, Division 1, Groups A, B, C,
and D; Non-incendive for Class I, Division 2, Groups A, B,
220/230 VAC, U.K. plug.
C, and D.
Microprocessors
Canadian Standards Association (CSA) Intrinsic Safety
32-bit Motorola type 68331. Approval
8-bit Motorola type 68HC05. I6 Class 2258 03; Process Control Equipment – Intrinsically
Connections Safe and Non-Incendive Systems; For Hazardous
Locations. Products Class I, Groups A, B, C, and D.
Leadset: Two 4 mm banana
plugs. Electromagnetic Compatibility (EMC)
*EMC compliant only when the CE logo appears on both the
Battery charger: 2.1 mm coaxial power
keypad assembly and Memory Module.
connector (optional).
EN50081-1:1992
Serial port: 9-pin D subminiature
EN50082-1:1992
socket.
Memory Module: 26-pin, 2-row, 0.1-inch
pitch connector.
PHYSICAL SPECIFICATIONS

Display

Leadset Jacks
Serial Port 8-line by 21-character (128 by 64 pixels) liquid crystal display.
Keypad
25 large keys including six Action keys, a complete
alphanumeric keypad, four software-defined Function Keys;
membrane design with tactile feedback.
Weight
Approximately 3 lb (1.4 kg) with Ni-Cad battery pack.
0275_BACK

Battery Charger Jack


(“R” option only)

Accessories-13
HART® Communicator

Still undecided? Let us tell you more... That’s why Fisher-Rosemount has created a family
The HART Communicator is the key to unlocking of PERFORMANCE software programs called Asset
the power of your intelligent instruments. But Management Solutions (AMS). This revolutionary
configuration, calibration, and maintenance of set of software applications is more than just a
intelligent devices in the field is only a small part of database of information about your field devices, it is
your job. You have to plan your maintenance a tool to help you manage the process better. You can
schedule, meet the day-to-day demands of problems simply drag and drop information from your
in the field that simply don’t allow you time for connected HART Communicator directly into your
preventative maintenance, and you still have database. The software does the rest. You have
another challenge–keeping accurate records of what instant access to all devices. And, with all device
you have done. This is the most time consuming part data at your fingertips, you can configure devices
of your job. In fact some days you spend more time quickly, download them to your HART
documenting what you have done than you spent Communicator and be ready to head out to the field.
doing it! What could be easier?
HART® Communicator

Ask your Fisher-Rosemount Sales Representative to


tell you more about AMS applications and how to
put them to work for you.

Drag and drop information


from a connected device on
the bench to your Plant Database
Upload device data
easily from your
HART Communicator

0275_AMEXPLO;275

View all devices


in your database

Simply Drag and Drop information from the HART Communicator to the Asset Management Solutions Database or download data to the
HART Communicator and be ready to take the information to the field!

Accessories-14
Rosemount Inc.

Spare Parts
Part Number Description

➁ 00275-0003-0500 Memory Module 8 MB (Standard)

➁ 00275-0003-0300 Memory Module 4 MB

➂ 00275-0006-0100 Fisher-Rosemount data pack 100

00275-0007-0001 Recharger 220/230 VAC (U.K. plug)

00275-0007-0002 Recharger 220/230 VAC (European plug)

00275-0007-0003 Recharger 100/120 VAC, 50/60 Hz (U.S. plug)

➇ 00275-0093-0001 Lead Set with Connectors

➄ 00275-0094-0001 Hanger (mounts on belt clip option)

➃ 00275-0095-0001 Belt Clip with Screws

HART® Communicator
➆ 00275-0096-0001 Ruggedized 250 Ohm Load Resistor

➈ 00275-0100-0001 Carrying Case

➀ 00275-1070-0100 AA Alkaline Battery Pack for Code I0

➀ 00275-0170-0101 AA Alkaline Battery Pack for Code I1

➀ 00275-0170-0102 AA Alkaline Battery Pack for Code I5

➀ 00275-0170-0103 AA Alkaline Battery Pack for Code I6

➀ 00275-0171-0100 NiCad Battery Pack for Code I0

➀ 00275-0171-0101 NiCad Battery Pack for Code I1

➀ 00275-0171-0102 NiCad Battery Pack for Code I5

➀ 00275-0171-0103 NiCad Battery Pack for Code I6

00275-8026-0002 Pocket-sized Product Manual

00275-0013-0001 PC Communication Adapter(1)

00275-8072-0001 PC Cable (DB9 to DB25)(1)

(1)Requires Asset Management Solutions (AMS) Software with 275 Interface Kit Option.


➇ ➈

➀ ➃



0275_004B

Accessories-15
HART® Communicator

ORDERING INFORMATION
Model Product Description
275 HART Communicator(1)

Code Battery Pack Option

D Battery Holder for Disposable AA Batteries


R Rechargeable Ni-Cad Battery Pack

Code Recharger Service and Plug Type

1 100/120 V ac, 50/60 Hz, U.S. Plug


2 220/230 V ac, European Plug
3 220/230 V ac, U.K. Plug
9 None (Use this code when Battery Pack Option “D” is selected)

Code Language
HART® Communicator

E English
G German
J Japanese

Code Hazardous Locations Certifications


I0 No Approval
I1 CENELEC—Intrinsic Safety Certification
I5 Factory Mutual (FM)—Intrinsic Safety Approval
I6 Canadian Standards Association (CSA)—Intrinsic Safety Approval

Code Memory Module Type


B 4 MB
C 8 MB (Standard)

Code Device Descriptor Options


00 Standard Factory Loading

Code data pack 100 Options


D1 Shipped with (1) data pack 100 installed
D2 Shipped with (2) data pack 100s
00 Shipped without data pack 100

Typical Model Number: 275 D 9 E I0 C 00 00


(1) The Typical Model 275 D 9 E I0 C 00 00 includes HART Communicator, AA battery pack with batteries, Lead Set with MINIGRABBER™ and
alligator clips, carrying case, and pocket size manual. Options include NiCad battery pack, recharger, language, certifications, and data pack
100. If the Ni-Cad battery pack is selected, one spare battery pack per HART Communicator is recommended.

HART COMMUNICATIONS
The HART Communicator interfaces with any HART instrument from any wiring termination point in a
4–20 mA loop, provided a minimum load resistance of 250 ohms is present between the communicator and
power supply. The HART Communicator uses the Bell 202 frequency shift keying (FSK) technique. This
technique superimposes high-frequency digital communication signals on the standard 4–20 mA transmitter
current loop. Because the net energy added to the loop is zero, communication does not disturb the 4–20 mA
signal.