Broken Conductor Protection
Broken Conductor Protection
Another type of unbalanced fault which can occur on the system is the series or open circuit fault.
These can arise from broken conductors, maloperation of single phase switchgear, or the operation
of fuses. Series faults will not cause an increase in phase current on the system and hence are not
readily detectable by standard overcurrent relays. However, they will produce an unbalance and a
resultant level of negative phase sequence current, which can be detected.
It is possible to apply a negative phase sequence overcurrent relay to detect the above condition.
However, on a lightly loaded line, the negative sequence current resulting from a series fault
condition may be very close to, or less than, the full load steady state unbalance arising from CT
errors, load unbalance etc. A negative sequence element therefore would not operate at low load
levels.
The Broken Conductor Protection relay incorporates an element which measures the ratio of
negative to positive phase sequence current (I2/I1). This will be affected to a lesser extent than the
measurement of negative sequence current alone, since the ratio is approximately constant with
variations in load current. Hence, a more sensitive setting may be achieved.
In the case of a single point earthed power system, there will be little zero sequence current flow
and the ratio of I2/I1 that flows in the protected circuit will approach 100%. In the case of a multiple
earthed power system (assuming equal impedances in each sequence network), the ratio I2/I1will
be 50%.
It is possible to calculate the ratio of I2/I1 that will occur for varying system impedances, by referring
to the following equations below.
Therefore, for an open circuit in a particular part of the system, I2/I1 can be determined from the
ratio of zero sequence to negative sequence impedance. It must be noted that this ratio may vary
depending upon the fault location. It is desirable therefore to apply as sensitive a setting as
possible. In practice, this minimum setting is governed by the levels of standing negative phase
sequence current present on the system. A minimum value of 8% negative phase sequence current
is required for successful Broken Conductor relay operation.
Since sensitive settings have been employed, it can be expected that the element will operate for
any unbalance condition occurring on the system for example, during a single pole autoreclose
cycle. Hence, a long time-delay is necessary to ensure co-ordination with other protective devices.
Normally 5 second time-delay is provided for Broken Conductor Protection.
SOTF Protection gets enabled whenever all the three poles of a Circuit Breaker is open for more
than a settable time say 110s (This time can be changed and configured as per the design.)
SOTF is enabled in two cases. They are mentioned below.
Here VNand IN are Nominal Voltage and Nominal Current respectively. Thus if the phase voltages
are below 75 % and if phase current increases from the setting then SOFT will sense it a fault and
will issue three phase trip command provided all other conditions as mentioned in case1 and case2
for SOTF are met.