R & AC Lab Manual
R & AC Lab Manual
SEM
THEORY:
Vapour compression refrigeration cycle is very widely used cycle of refrigeration. The
domestic refrigerator, ice plants work on this cycle. It uses a variety of refrigerants such
as ammonia (NH3), freons (R12, R22). The vapour compression refrigeration has
fundamentally four basic components as shown in fig, and four basic processes. The
corresponding T-S, P-h diagrams are also indicated in fig. Normally in the case of
refrigeration T-S & P-h diagrams are extensively used for indicating various processes
and hence the significance of these diagrams is to be fully understood.
Figure 2: Representation of simple vapour compression cycle on T-s and P-h charts
Compressor:
The function of compressor is to draw the mech, energy and there by pressure &
temperature of refrigerant is increased before is supplied to the condenser.
Condenser :
In the condenser the high pressure vapours are condensed and the heat is rejected to
cooling medium (which is atmospheric air).
Expansion device:
High pressure liquid refrigerant from condenser is expanded to low pressure. A
thermostatic expansion value or capillary tube is an expansion device through which
liquid refrigerant is throttled
Evaporators:
The junction of evaporator is to contain food styles or such material to be pressured for
a long time. This is made possible by circulating refrigerant at low pressure and the
refrigerant gets evaporated by absorbing heat from the refrigerated space.
In the refrigeration cycle, heat is transferred from a colder region to a hotter
region. The refrigerant is used as the medium which absorbs and removes heat from the
space to be cooled and subsequently rejects that heat elsewhere.
The refrigerant enters the compressor[ driven by a motor] at low temperature and low
pressure in a gaseous state. Refrigerant is compressed in the compressor the
temperature and pressure is increased. The refrigerant leaves the compressor at
supersaturated condition and enters to the condenser. Types of Compressors are scroll,
screw, centrifugal and reciprocating.
The condenser is essentially a heat exchanger. Heat is transferred from the
refrigerant When the refrigerant enters the throttling valve, it expands and releases
pressure. Consequently, the temperature drops at this stage. Because of these changes,
the refrigerant leaves the throttle valve as a liquid vapor mixture, typically in
proportions of around 75 % and 25 % respectively.
Throttling valves play two crucial roles that it maintain a pressure differential between
low- and high-pressure sides. Second, they control the amount of liquid refrigerant
entering the evaporator. At this stage of the Vapor Compression Refrigeration Cycle,
the refrigerant is at a lower temperature than its surrounding, it evaporates and
absorbs latent heat of vaporization from the cold space. Heat extraction from the
refrigerant happens at low pressure and temperature. There are different evaporator
versions in the market, but the major classifications are liquid cooling and air cooling,
depending whether they cool liquid or air respectively.
DESCRIPTION:
All the components of refrigerator are displayed on a portable stand. The unit consists of ¼ HP
compressor, air cooled condenser with a fan for forced circulation of air, capillary tube,
expansion value and evaporator (cooled chamber). The hot vapour from the evaporator is
compressed in the compressor. The compressed vapour is sent to air cooled condenser, where
the condensation of the refrigerant takes place. Then the liquid refrigerant is passed either
through a capillary tube or a thermostatic expansion value, where the refrigerant is throttled to
low pressure and temperature. Now the refrigerant at low pressure cooling effect by the
absorption of heat energy, pressure gauges and thermometers are provided to measure pressure
and temperatures at suitable locations. The system is equipped with two energy meters to
measure the power consumption of compressor and the condenser fans respectively. The
system also consists of a voltmeter and an ammeter to measure the compressor.
PROCEDURE:
1. Check the values of the refrigerators
2. Power the water in evaporator section up to sufficient height.
3. Note the temperature of water in the evaporator.
4. Start one of the stop watches.
5. Simultaneously, switch on the main supply and system will start functioning. Note down
voltmeter and ammeter readings.
6. Note down the temperature readings and the pressure gauge readings after each component of
the refrigerator unit.
7. Calculate the compressor power consumption in the energy meter.
8. Calculate the power consumption to the compressor fan.
Run the refrigerator for a period, so that the water temperature in the evaporator decreased by
5°C, stop the stopwatch and the refrigerators unit.
T min
2. Carnot COP =
T max −T min
Where
Tmin = Minimum temperature of the cycle, °K
Tmax = Maximum temperature of the cycle, °K
ncf ×3600
3. W Condenser Fan =
N ×tcf
nc × 3600
4. W compressor =
N ×tc
RESULT
INFERENCE
TABULAR COLUMN
VAPOUR COMPRESSION REFRIGERATION CYCLE PERFORMANCE TEST
S.N Parameter Units Using Capillary
o tubes
1 2
1 Absolute pressure after the compressor, bar
P1
2 Absolute pressure after the condenser, bar
P2
3 Absolute pressure after the expansion, bar
P3
4 Absolute pressure after the evaporator, bar
P4
5 Temp. after the compressor, T1 °C
6 Temp. after the condenser, T2 °C
7 Temp. after the expansion, T3 °C
8 Temp. after the evaporator, T4 °C
9 Flow rate or the refrigerator, VR m3
/sec
10 Initial temp. of water , TWI °C
11 Final temp. of water , TWf °C
12 Time for draw 5°C temp of water, tw sec
13 Time for 2 rev temp of water, tcf sec
14 Time for 5rev temp of water, tc sec
15 Temp.difference of water °C
16 Work i/p of condenser fan KW
17 Work i/p of condenser KW
18 Total work i/p KW
19 Net refrigerating effect KW
20 Carnot COP
21 Actual COP
22 Theoretical COP, (h1-h4)/(h2-h1)
23 Relative COP
SAMPLE READINGS
S.N Parameter Units Using Capillary
o tubes
1 2
1 Absolute pressure after the compressor, P1 bar 12.054 3.789
2 Absolute pressure after the condenser, P2 bar 11.91 12.74
3 Absolute pressure after the expansion, P3 bar 3.44 12.39
4 Absolute pressure after the evaporator, P4 bar 3.44 3.78
5 Temp. after the compressor, T1 °C 62 22
6 Temp. after the condenser, T2 °C 40 59
7 Temp. after the expansion, T3 °C 2 39
8 Temp. after the evaporator, T4 °C 16 2
9 Flow rate or the refrigerator, VR m3
/sec
10 Initial temp. of water , TWI °C 20 24
11 Final temp. of water , TWf °C 15 19
12 Time for draw 5°C temp of water, tw sec 310 483
13 Time for 2 rev of condenser energy meter, sec 101 104
tcf
14 Time for 5rev of compressor energy meter, sec 34 35
tc
15 Temp.difference of water °C 5 5
16 Work i/p of condenser fan KW 0.0594 0.428
17 Work i/p of condenser KW 0.0411 0.05
18 Total work i/p KW 0.5005 0.4862
19 Net refrigerating effect KW 0.947 0.782
20 Carnot COP 4.55 4.49
21 Actual COP 1.892
22 Theoretical COP, (h1-h4)/(h2-h1)
23 Relative COP
The basic components of a heat pump in its heating mode are shown in Figure. A working
fluid such as a non-CFC refrigerant is used. In the outdoor coils (the evaporator), heat transfer
Qc occurs to the working fluid from the cold outdoor air, turning it into a gas. The electrically
driven compressor (work input W) raises the temperature and pressure of the gas and forces it
into the condenser coils that are inside the heated space. Because the temperature of the gas is
higher than the temperature inside the room, heat transfer to the room occurs and the gas
condenses to a liquid. The liquid then flows back through a pressure-reducing valve to the
outdoor evaporator coils, being cooled through expansion. (In a cooling cycle, the evaporator
and condenser coils exchange roles and the flow direction of the fluid is reversed.)
DESCRIPTION:
The Unit consists of following parts:
1. Compressor : Hermetically sealed
2. Condenser: A copper tube coil type water cooled condenser emerged in Stainless Steel tank
with the inlet and outlet of water. A rotameter is fitted to calculate the mass flow rate of water.
3. Receiver: 1 No. heavy duty sheet type receiver along with wall fittings provided to store the
liquid refrigerant R22.
4. Evaporator: Copper Tube type cooling coil of size: ¾” OD has been fixed inside the inner SS
Tank with outlet and inlet of water.
5. Control panel board : The following controls has been provided on Control Board:
Main switch, Voltmeter, Amperemeter, Energy meter, Digital Temperature Indicator, Suction
Gauge, Discharge Gauge, Capillary tube, Filter.
The whole unit is fitted on heavy Angle Iron base to accommodate the Condensing Unit, Brine
Tank and Compressor.
OBSERVATION AND CALCULATIONS:
P1’ PSI
Absolute suction pressure P1 = ---------- + 1 kg/cm2
14.22
= kg/cm2
P2′ PSI
Absolute Discharge pressure = ----------- + 1 kg/cm2
14.22
Refrigerating effect
C.O.P. = -----------------------------------
Work done by compressor
h1 – h4
C.O.P. = -----------
h2 – h1
(h1 – h4) m
Refrigerating cap in Ton = ---------------- Tons
50 x 4.184
RESULT:
INFERENCE:
AIM:
To determine of performance COP of the Air-Conditioning unit based on vapour
compression refrigeration cycle.
APPARATUS:
Air conditioning test rig, Stopwatch
THEORY:
Vapour compression refrigeration. The domestic refrigerator, i.e plants work on this
cycle. It uses a variety of refrigerants such as Ammonia (NH 3), freons (R12, R22). The
vapour compression refrigeration has fundamentally four basic components as shown
in fig, and four basic processes. The corresponding T-S, P-h diagrams are also indicated
in fig. Normally in the case of refrigeration T-S & P-h diagrams are extensively used for
indicating various processes and hence the significance of these diagrams is to be fully
understood. n air conditioner is able to cool a building because it removes heat from the
indoor air and transfers it outdoors. A chemical refrigerant in the system absorbs the
unwanted heat and pumps it through a system of piping to the outside coil. The fan,
located in the outside unit, blows outside air over the hot coil, transferring heat from the
refrigerant to the outdoor air.
Most air conditioning systems have five mechanical components:
• a compressor
• a condensor
• an evaporator coil
• blower
• a chemical refrigerant
Most central air conditioning units operate by means of a split system. That is, they
consist of a ‘hot’ side, or the condensing unit—including the condensing coil, the
compressor and the fan—which is situated outside your home, and a ‘cold’ side that is
located inside your home.
1. Compressor:
The function of compressor is to draw the mech, energy and there by pressure &
temperature of refrigerant is increased before is supplied to the condenser.
2. Condenser:
In the condenser the high pressure vapours are condensed and the heat is rejected to
cooling medium (which is atmospheric air).
3. Expansion device:
High pressure liquid refrigerant from condenser is expanded to low pressure. A
thermostatic expansion value or capillary tube is an expansion device through which
liquid refrigerant is throttled
4. Evaporator:
The function of evaporator is to take the heat from the air. The low temp and low
pressure refrigerant take the heat from the air passing through the evaporator and gets
evaporated to low pressure
refrigerant vapour. Thus cooling
of air takes place.
T min
2. Carnot COP =
T max −T min
Where
Tmin = Minimum temperature of the cycle, °K
Tmax = Maximum temperature of the cycle, °K
ncf X 3600
I. W Condenser Fan =
N X tcf
Where,
mR = mass your rate of refrigerant, Kg/sec = VR/vR
VR = volume your rate of the refrigerant, m3 /sec
vR =Sp. volume your rate of the refrigerant = 0.825 X 10-3 m3/Kg
h1 =Sp. enthalpy of the refrigerant at the exit of evaporator, KJ/Kg
h2= Sp. enthalpy of the refrigerant at the exit of compressor, KJ/Kg
h4= Sp. enthalpy of the refrigerant before entering the evaporator, KJ/Kg
8. Relative COP = Actual COP/ Theoretical COP.
TABULAR COLUMN:
AIR-CONDITIONER PERFORMANCE TEST
S.N Parameter Units Using Capillary
o tubes
1 2
1 Absolute pressure after the compressor, P1 bar
2 Absolute pressure after the condenser, P2 bar
3 Absolute pressure after the expansion, P3 bar
4 Absolute pressure after the evaporator, P4 bar
5 Temp. after the compressor, T1 °C
6 Temp. after the condenser, T2 °C
7 Temp. after the expansion, T3 °C
8 Temp. after the evaporator, T4 °C
10 Dry bulb temp. of air before evaporator °C
11 Wet bulb temp. of air before evaporator °C
12 Dry bulb temp. of air after evaporator °C
13 Wet bulb temp. of air after evaporator °C
14 Time for 2 rev of condenser energy meter, sec
tcf
15 Time for 5rev of compressor energy sec
meter, tc
16 Monometer difference m
17 Volume flow rate of air m3
/sec
18 Mass your rate of air Kg/Se
c
19 Work i/p of condenser fan KW
20 Work i/p of condenser KW
21 Total work i/p KW
22 Net refrigerating effect KW
23 Carnot COP
24 Actual COP
25 Theoretical COP, (h1-h4)/(h2-h1)
26 Relative COP
SAMPLE READINGS
S.N Parameter Units Using Capillary
o tubes
1 2
1 Absolute pressure after the compressor, P1 bar 3.44 3.789
2 Absolute pressure after the condenser, P2 bar 14.121 12.74
3 Absolute pressure after the expansion, P3 bar 14.129 12.39
RESULT:
INFERENCE:
INTRODUCTION
Vapour Absorption Refrigeration Systems (VARS) belong to the class of vapour
cycles similar to vapour compression refrigeration systems. However, unlike vapour
compression refrigeration systems, the required input to absorption systems is in the
form of heat. Hence these systems are also called as heat operated or thermal energy
driven systems. Since conventional absorption systems use liquids for absorption of
refrigerant, these are also sometimes called as wet absorption systems.
Similar to vapour compression refrigeration systems, vapour absorption refrigeration
systems have also been commercialized and are widely used in various refrigeration
and air conditioning applications. Since these systems run on low-grade thermal
energy, they are preferred when low-grade energy such as waste heat or solar energy is
available. Since conventional absorption systems use natural refrigerants such as water
or ammonia they are environment friendly
In the above Figure (a) and (b) show a continuous output vapours compression
refrigeration system and a continuous output vapour absorption refrigeration system.
As shown in the figure in a continuous absorption system, low temperature and low
pressure refrigerant with low quality enters the evaporator and vaporizes by producing
useful refrigeration Qe.
From the evaporator, the low temperature, low pressure refrigerant vapour
enters the absorber where it comes in contact with a solution that is weak in refrigerant.
The weak solution absorbs the refrigerant and becomes strong in refrigerant. The heat
of absorption is rejected to the external heat sink at To.
The solution that is now rich in refrigerant is fed to the generator. In the
generator heat at high temperature Tg is supplied, as a result refrigerant vapour is
generated at high pressure. This high pressure vapour is then condensed in the
condenser by rejecting heat of condensation to the external heat sink at To.
The condensed refrigerant liquid is then throttled in the expansion device and is
then fed to the evaporator to complete the refrigerant cycle.
On the solution side, the hot, high-pressure solution that is weak in refrigerant is
throttled to the absorber pressure in the solution expansion valve and fed to the
absorber where it comes in contact with the refrigerant vapour from evaporator. Thus
continuous refrigeration is produced at evaporator, while heat at high temperature is
continuously supplied to the generator. Heat rejection to the external heat sink takes
place at absorber and condenser. If we neglect pressure drops, then the absorption
system operates between the condenser and evaporator pressures. Pressure in absorber
is same as the pressure in evaporator and pressure in generator is same as the pressure
in Condenser.
It can be seen from Fig, that as far as the condenser, expansion valve and
evaporators are concerned both compression and absorption systems are identical.
However, the difference lies in the way the refrigerant is compressed to condenser
COP (VCRS) = Qe
Wc
thermodynamics to the system. Figure shows the various energy transfers and the
corresponding temperatures in an absorption refrigeration system.
OPERATING PROCEDURE:
TABULAR COLUMN:
Sl. Time taken Cooling Act. Th.
no V I T1 T2 T3 T4 T5 T6 T7 T8 t sec effect COP COP
OBSERVATIONS:
V = voltage in volts
I = current in Amps
T1 = Refrigerant temperature at inlet of generator in degree C
T2 = Refrigerant temperature at outlet generator
T3 = Refrigerant temperature at outlet of condenser
T4 = Refrigerant temperature at inlet of evaporator (after expansion)
V × I ×time ratio
Q g= kW
1000
Where,
V =voltage in volts
I =current in Amps
5. ACTUAL COP
COP = Refrigeration Effect = Qe
Power input Qg
RESULT:
INFERENCE:
SAMPLE CALCULATIONS:
1 220 0.24 47.9 150 38.8 -9.2 14.2 19 26.3 26.6 600
1. THEORETICAL COP
COP th = Qe = -9.2 + 273 x (150-38.8) = 1.44
Qg (38,8-(-9.2)) 423
Compressed air is passed through the nozzle as shown in figure above. Here, air
expands and acquires high velocity due to particular shape of the nozzle.
A vortex flow is created in the chamber and air travels in spiral like motion along the
periphery of the hot side. This flow is restricted by the valve. When the pressure of the
air near valve is made more than outside by partly closing the valve, a reversed axial
flow through the core of the hot side starts from high-pressure region to low-pressure
region. During this process, heat transfer takes place between reversed stream and
forward stream. Therefore, air stream through the core gets cooled below the inlet
temperature of the air in the vortex tube, while air stream in forward direction gets
heated up. The cold stream is escaped through the diaphragm hole into the cold side,
while hot stream is passed through the opening of the valve. By controlling the opening
of the valve, the quantity of the cold air and its temperature can be varied.
DESCRIPTION
Introduction
A Vortex Tube is a device which, when supplied with filtered compressed air at 100
psig (6.9 Bar) and 700 F (210 C), converts the air into two streams. One stream is
adjustable up to 2500 F (1210 C) and the other is adjustable down to -50o F (-48o C).
Models ranging in air consumption from 2 SCFM to 100 SCFM are available.
TABULAR COLUMN
S.N Air inlet Cold air Hot air FRL unit Cold air Cold
o temperature(T1) temperature(T temperature(T pressure(P1) pressure(P2) fractio
2) 3) n
RESULT:
INFERENCE:
Sample calculation
EXCERCISES
1. A vapour compression system using NH 3 works between -15℃ and 40℃ as
evaporator and condenser temperature respectively. The vapour is superheated by 5℃
before entering the compressor and the liquid is subcooled by 5℃. Determine
i) C.O.P
ii) Mass flow of refrigerant per TR
iii) Piston displacement per TR using volumetric efficiency = 80%
iv) Heat rejected in the condenser per TR
v) Ideal C.O.P.