Features: Input Voltage: 40 60V Output Voltage: 12V Output Power: 600W
Features: Input Voltage: 40 60V Output Voltage: 12V Output Power: 600W
Features
Electrical
Peak Efficiency up to 97.3% @54Vin
PMBus communication
Fully regulated output voltage
Fully protected: Input UVLO. Output OVP, OCP
and OTP
Monotonic and pre-biased startup
No minimum load required
Non-isolated
Mechanical
Size: 58.4x22.8x12.7mm
Recommended Layout
Vin+(1) Vout+(5)
Sig_GND(7)
C2,Pgood(6)
Addr0(12)
Addr1(11)
Clock(10)
Alert(9)
Data(8)
Vin-(3) Vout-(4)
3.3V
1k×3
R1 R2 R3
Data
3.3V
Alert
MCU Clock 1k
SGND Power good
C1 C2 C3
R1/R2/R3/C1/C2/C3 value are 49.9ohm/49.9ohm/49.9ohm /10p/10p/10p, and should be close to brick in application.
/ 16V/22uF/X7R/1206/MLCC 6 /
Near to the Vo+ and
Cout
Vo- pin of the Module
PCR1C102MCL1GS 16V/1000uF/10*12.7 1 Nichicon
TA=25°C
Figure 1: Efficiency vs. Output Power Figure 2: Loss vs. Output Power
Figure 3: Full Load Input Characteristics Figure 4: Output Voltage vs. Load Current
TA=25°C,
Figure 5: Remote On/Off (negative logic) at full load Figure 6: Input Voltage Start-up at full load
Vin=54V, Iout = Io, max Vin=54V, Iout = Io, max
Time: 10ms/div. Time: 40ms/div.
Vout (top trace): 4V/div; Vout (top trace): 4V/div;
Vremote On/Off signal (bottom trace): 2V/div. Vin (bottom trace): 30V/div.
TA=25°C, Vin=54Vdc
Figure 9: Test Setup Diagram for Input Ripple Current Figure 10: Input Terminal Ripple Current, ic, at max output
Note: Measured input reflected-ripple current with a simulated current and nominal input voltage with 12µH source impedance
source Inductance of 12μH. Measure current as shown above. and 100µF electrolytic capacitor (100 mA/div, 2us/div).
Figure 11: Test Setup for Output Voltage Noise and Ripple Figure 12: Output Voltage Ripple and Noise at nominal
input voltage and max load current (20 mV/div, 2us/div)
Load cap: 1000uF, 20% ceramic, 80% Oscon.
Bandwidth: 20MHz.
Safety Considerations
The power module must be installed in compliance with the
spacing and separation requirements of the end-user’s safety
agency standard, i.e., IEC 62368-1: 2014 (2nd edition), EN
62368-1: 2014 + A11: 2017, UL 62368-1, 2nd Edition, 2014- Figure 14: Remote On/Off Implementation
12-01 and CSA C22.2 No. 62368-1-14, 2nd Edition, 2014-12.
IEC 60950-1: 2005, 2nd Edition + A1: 2009 + A2: 2013, EN Over-Current Protection
60950-1: 2006 + A11: 2009 + A1: 2010 + A12: 2011 + A2:
2013, UL 60950-1, 2nd Edition, 2019-05-09 and CSA C22.2 The modules include an internal output over-current
No. 60950-1-07, 2nd Edition, 2014-10, if the system in which protection circuit, which will endure current limiting for an
the power module is to be used must meet safety agency unlimited duration during output overload. If the output
requirements. current exceeds the OCP set point, the modules will shut
down (hiccup mode). The modules will try to restart after
shutdown. If the overload condition still exists, the module will
For IEC/EN/UL/CSA 60950-1:
shut down again. This restart trial will continue until the
DC input and DC output are considered as SELV circuits,
overload condition is corrected.
functional insulation is investigated between input circuit
and output circuit.
Over-Temperature Protection
The over-temperature protection consists of circuitry that
provides protection from thermal damage. If the temperature
exceeds the over-temperature threshold the module will shut
down. The module will restart after the temperature is within
specification.
Exponent Resolution
Vin -3 0.125V
Vo -9 19.53mV
Io -4 62.5mA
Temperature -2 /
Switching frequency -2 1Khz
Time -1 0.5ms
Compatible
Command Command Transfer with standard Data Default Range Data Expon
Command Note
Code description type PMBUS or Format value limit units -ent
not?
R/W Refer to below
OPERATION 0x01 Turn on or off Bit field 0x80 / / / /
byte description;
Configures primary R/W 0x1D (Neg Logic);
ON_OFF_CONFIG 0x02 Yes Bit field 0x1D / / /
on/off & command byte 0x1F (Pos Logic);
Clear any fault bits Send
CLEAR_FAULTS 0x03 Yes / / / / / /
that have been set byte
Control writing to R/W To protect accidental
WRITE_PROTECT 0x10 Yes / 0x80 / / /
the PMBUS device. byte changes.
The FLASH must be
unlocked (referring to
Command 0xEC) before
Stores operating
Send sending this command.
STORE_DEFAULT_ALL 0x11 parameters from Yes / / / / /
byte This command is effective
RAM to data flash
to the parameter of all
command in the table
except 0xEC
Restores operating This command can't be
Send
RESTORE_DEFAULT_ALL 0x12 parameters from Yes / / / / / issued when the power unit
byte
data flash to RAM is running.
Read the PMBUS Read Only for
PMBUS_CMD_CAPABILITY 0x19 Yes / 0xB0 / / /
capability byte E50SN12051NKDHF
Read Vo data Read
VOUT_MODE 0x20 Yes mode+exp 0x17 / / / /
format byte
Read the output Read
VOUT_COMMAND 0x21 Yes Vout Linear 12.2 / V -9 /
voltage word
Read the switching Read Frequency
FREQUENCY_SWITCH 0x33 Yes 250 / KHz -2 /
frequency word linear
Read the turn on
VIN_ON should be higher
voltage threshold of R/W
VIN_ON 0x35 Yes Vin Linear 39 38~40 V -3 than VIN_OFF, and keep
Vin under voltage word
2V hysteresis.
lockout
Read the turn off
VIN_ON should be higher
voltage threshold of R/W
VIN_OFF 0x36 Yes Vin Linear 37 36~38 V -3 than VIN_OFF, and keep
Vin under voltage word
2V hysteresis.
lockout
OPERATION [0x01]
Bit number Purpose Bit Value Meaning Default Settings, 0x80
7: Enable/Disable the module 1 Output is enabled 1
0 Output is disabled
6:0 Reserved 0000000
7:6 Response settings 11 Unit shuts down and responds according to the 11
retry settings
5:3 Retry setting 111 Unit continuously restarts while fault is present 111
until commanded off
000 Unit does not attempt to restart on fault
2:0 Delay time setting 000 No delay supported 000
STATUS_WORD [0x79]
High byte
Bit number Purpose Bit Value Meaning
1 Occurred
7 An output over voltage fault or warning
0 No Occurred
1 Occurred
6 An output over current fault or warning
0 No Occurred
An input voltage fault, including over voltage and under 1 Occurred
5
voltage 0 No Occurred
4 Reserved
1 is negated
3 Power_Good
0 ok
2:0 Reserved
Low byte
Bit number Purpose Bit Value Meaning
7 Reserved
OFF (The unit is not providing power to the output, 1 Occurred
6
regardless of the reason) 0 No Occurred
1 Occurred
5 An output over voltage fault
0 No Occurred
1 Occurred
4 An output over current fault
0 No Occurred
1 Occurred
3 An input under voltage fault
0 No Occurred
1 Occurred
2 A temperature fault or warning
0 No Occurred
1 Occurred;
1 CML (A communications, memory or logic fault)
0 No Occurred
0 Reserved
STATUS_VOUT [0x7A]
Bit number Purpose Bit Value Meaning
7 1 Occurred
Output over voltage fault
0 No Occurred
1 Occurred
6 Output over voltage warning
0 No Occurred
5:0 Reserved
STATUS_IOUT [0x7B]
Bit number Purpose Bit Value Meaning
1 Occurred
7 Output over current fault
0 No Occurred
6 Reserved
1 Occurred
5 Output over current warning
0 No Occurred
4:0 Reserved
STATUS_INPUT [0x7C]
Bit number Purpose Bit Value Meaning
1 Occurred
7 Reserved
0 No Occurred
6: 5 Reserved
1 Occurred;
4 Input under voltage fault
0 No Occurred
3:0 Reserved
STATUS_TEMPERATURE [0x7D]
Bit number Purpose Bit Value Meaning
1 Occurred
7 Over temperature fault
0 No Occurred
1 Occurred
6 Over temperature warning
0 No Occurred
5:0 Reserved
STATUS_CML [0x7E]
Bit number Purpose Bit Value Meaning
7 1 Occurred
Invalid/Unsupported Command Received
0 No Occurred
1 Occurred
6 Invalid/Unsupported Data Received
0 No Occurred
1 Occurred
5 Packet Error Check Failed
0 No Occurred
4:0 Reserved
Hence, the choice of equipment to characterize the thermal performance of the power module is a wind tunnel.
Delta’s DC/DC power modules are characterized in heated vertical wind tunnels that simulate the thermal environments
encountered in most electronics equipment. This type of equipment commonly uses vertically mounted circuit cards in cabinet racks
in which the power modules are mounted.
The following figure shows the wind tunnel characterization setup. The power module is mounted on a 185mmX185mm, 105μm
(3Oz), 6 layers’ test PWB and is vertically positioned within the wind tunnel. The airflow channel width is 73.6mm (2.90”), and the
gap between the airflow channel and top side of the power module is constantly kept at 6.35mm (0.25’’).
MODULE
AIR VELOCITY
AND AMBIENT 50.8(2.00")
TEMPERATURE
SURED BELOW
THE MODULE
AIR FLOW
Note: Wind Tunnel Test Setup Figure Dimensions are in millimeters and (Inches)
Thermal Derating
Heat can be removed by increasing airflow over the module. To enhance system reliability, the power module should always be
operated below the maximum operating temperature. If the temperature exceeds the maximum module temperature, reliability of
the unit may be affected.
Air Flow
Air Flow
Figure 16: Hot spot 1 temperature measurement location Figure 18: Hot spot 2 temperature measurement location
The allowed maximum hot spot1 temperature is defined at 118℃. The allowed maximum hot spot2 temperature is defined at 118℃.
E50SN12051(Standard) Output Power vs. Ambient Temperature and Air Velocity E50SN12051(Standard) Output Power vs. Ambient Temperature and Air Velocity
Output Power (W) @Vin = 54V (Transverse Orientation,With Heat Spreader) Output Power (W) @Vin = 54V (Transverse Orientation,With 0.5" Height Heat Sink ETL050A)
600 600
500 500
100LFM 100LFM
200LFM
400 400
300LFM 200LFM
400LFM 300LFM
300 300
400LFM
500LFM
200 200
600LFM 500LFM
600LFM
100 100
0 0
25 30 35 40 45 50 55 60 65 70 75 80 85 25 30 35 40 45 50 55 60 65 70 75 80 85
Ambient Temperature (℃) Ambient Temperature (℃)
Figure 17: Output Power vs. Ambient Temperature and Air Figure 19: Output Power vs. Ambient Temperature and Air
Velocity @Vin = 54V (Transverse Orientation, Airflow from Vin- Velocity @Vin = 54V (Transverse Orientation, Airflow from Vin-
to Vin+, With Base-plate) to Vin+, With 0.5” Height Heat Sink ETL050A)
Reflow soldering is not a suggested method for through-hole power modules due to many process and reliability
concerns. If you have this kind of application requirement, please contact Delta sales or FAE for further confirmation.
The typical recommended (for double-side circuit board) preheat temperature is 115+/-10 ℃ on the top side
(component side) of the circuit board. The circuit-board bottom-side preheat temperature is typically recommended to
be greater than 135℃ and preferably within 100℃ of the solder-wave temperature. A maximum recommended
preheat up rate is 3℃/s. A maximum recommended solder pot temperature is 255+/-5℃ with solder-wave dwell time
of 3~6 seconds. The cooling down rate is typically recommended to be 6℃/s maximum.
Hand-Soldering Guideline
Shielding cap is requested to mount on DCDC module if with heat-spreader/heat-sink, to prevent the customer
side high temperature of reflow to re-melt the DCDC module’s internal component’s soldering joint.
Temp.
Peak Temp. 240 ~ 245 ℃
CONTACT US:
Website: www.deltaww.com/dcdc Email: [email protected]
USA: Europe: Asia & the rest of world:
Telephone: Telephone: +31-20-655-0967 Telephone: +886 3 4526107
East Coast: 978-656-3993 Fax: +31-20-655-0999 Ext. 6220~6226
West Coast: 510-668-5100 Fax: +886 3 4513485
Fax: (978) 656 3964
WARRANTY
Delta offers a two (2) year limited warranty. Complete warranty information is listed on our web site or is available upon request
from Delta.
Information furnished by Delta is believed to be accurate and reliable. However, no responsibility is assumed by Delta for its use,
nor for any infringements of patents or other rights of third parties, which may result from its use. No license is granted by implication
or otherwise under any patent or patent rights of Delta. Delta reserves the right to revise these specifications