1-Calculator For OC Tripping Time.

This document contains test results from power and current transducer testing. It provides the test points injected at various percentages of full scale current and power values. It also includes the expected outputs from the transducers based on the injections and the actual outputs measured. It calculates the percentage error between the expected and actual output values and indicates whether the results pass or fail based on the accuracy ratings of the transducers.

Uploaded by

m kh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
198 views7 pages

1-Calculator For OC Tripping Time.

This document contains test results from power and current transducer testing. It provides the test points injected at various percentages of full scale current and power values. It also includes the expected outputs from the transducers based on the injections and the actual outputs measured. It calculates the percentage error between the expected and actual output values and indicates whether the results pass or fail based on the accuracy ratings of the transducers.

Uploaded by

m kh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 7

Over Current / Earth Fault timing calculator

CT Secondary current 2A Prepared By

USMAN VAHORA
JAL International, Al-Khobar
Relay Setting Tolarances
I Setting 1.00 *In
% Error
± 1.00% ###
TMS 0.10 0.040 Sec 0
I Setting 2
Test Points
Timing at 2x fault Timing at 3x fault Timing at 5x fault User defined Test Point
I Fault 2.00 *In I Fault 3.00 *In I Fault 5.00 *In I Fault
I Inject 4.00 A I Inject 6.00 A I Inject 10.00 A I Inject
T Calc. 1.003 Sec. T Calc. 0.630 Sec. T Calc. 0.428 Sec. T Calc.
T Meas. 10.030 Sec. T Meas. 6.346 Sec. T Meas. 4.321 Sec. T Meas.
900.097% 906.993% 909.645%
% Error % Error % Error % Error
9.027 Sec. 5.716 Sec. 3.893 Sec.
Result Not Pass Result Not Pass Result Not Pass Result
Prepared By

USMAN VAHORA
JAL International, Al-Khobar

User defined Test Point


9.00 *In
18.00 A
0.312 Sec.
2.180 Sec.
599.536%
1.868 Sec.
Not Pass
Power Transducer Testing

Rating Ranges Accuracy Prepared By


Input Output Ratio MW inputs +05 -05 ± 0.20% -0.2%
VT Ratio 13800 115 120.00 mA/mV Outputs +01 -01 USMAN VAHORA
CT Ratio 1200 1 1200.00 JAL International, Al-Khobar

Actual primary value Secondary Injection


Exp. o/p Actual o/p
% Power Voltage Current Angle Voltage
COS phi Voltage Current from from %Eroor Results
Injection (MW) (KV) (Amp.) (°) Angle Transd. Transd.
100% 5.00 13800 418.382 60 0.500 66.397 0.349 60 01.00 0.9980 0.200% Pass
75% 3.75 13800 221.881 45 0.707 66.397 0.185 45 00.75 0.7515 -0.200% Pass
50% 2.50 13800 120.776 30 0.866 66.397 0.101 30 00.50 0.4990 0.200% Pass
25% 1.25 13800 54.143 15 0.966 66.397 0.045 15 00.25 0.2494 0.240% Not Pass
0% 0.00 13800 0.000 1 1.000 66.397 0.000 1 0 vn
-25% -1.25 13800 54.143 165 -0.966 66.397 0.045 165 -0.25 -0.2505 -0.200% Pass 0.25 0.25
-50% -2.50 13800 120.776 150 -0.866 66.397 0.101 150 -0.50 -0.4990 0.200% Pass 0.50 0.50
-75% -3.75 13800 221.881 135 -0.707 66.397 0.185 135 -0.75 -0.7486 0.187% Pass 0.75 0.75
-100% -5.00 13800 418.382 120 -0.500 66.397 0.349 120 -1.00 -1.0020 -0.200% Pass 1.00 1.00

Accessible cells
Not accessible cells
90°
-Watt +Watt
+VAR +VAR

180° 0° Vref.
Volt / Current Transducer Testing

Ratio Accuracy
Current Input O/P ± 0.20% -0.2%
5 1

Actual
Injected Expected Actual o/p
%Current Current o/p from from %Eroor
(Amp.) Transducer Transducer
0% 0 0.0000 0.0000
25% 1.25 0.2500 0.2500 0.000%
50% 2.5 0.5000 0.5010 -0.200%
75% 3.75 0.7500 0.7516 -0.213%
100% 5 1.0000 1.0020 -0.200%
80% 4 0.8000 0.8015 -0.187%