1-Calculator For OC Tripping Time.
1-Calculator For OC Tripping Time.
USMAN VAHORA
JAL International, Al-Khobar
Relay Setting Tolarances
I Setting 1.00 *In
% Error
± 1.00% ###
TMS 0.10 0.040 Sec 0
I Setting 2
Test Points
Timing at 2x fault Timing at 3x fault Timing at 5x fault User defined Test Point
I Fault 2.00 *In I Fault 3.00 *In I Fault 5.00 *In I Fault
I Inject 4.00 A I Inject 6.00 A I Inject 10.00 A I Inject
T Calc. 1.003 Sec. T Calc. 0.630 Sec. T Calc. 0.428 Sec. T Calc.
T Meas. 10.030 Sec. T Meas. 6.346 Sec. T Meas. 4.321 Sec. T Meas.
900.097% 906.993% 909.645%
% Error % Error % Error % Error
9.027 Sec. 5.716 Sec. 3.893 Sec.
Result Not Pass Result Not Pass Result Not Pass Result
Prepared By
USMAN VAHORA
JAL International, Al-Khobar
Accessible cells
Not accessible cells
90°
-Watt +Watt
+VAR +VAR
180° 0° Vref.
Volt / Current Transducer Testing
Ratio Accuracy
Current Input O/P ± 0.20% -0.2%
5 1
Actual
Injected Expected Actual o/p
%Current Current o/p from from %Eroor
(Amp.) Transducer Transducer
0% 0 0.0000 0.0000
25% 1.25 0.2500 0.2500 0.000%
50% 2.5 0.5000 0.5010 -0.200%
75% 3.75 0.7500 0.7516 -0.213%
100% 5 1.0000 1.0020 -0.200%
80% 4 0.8000 0.8015 -0.187%