SM6 Protection & control monitoring

General characteristics LPCT protection chain

Standard
applications
TLP130, TLP190, CLP2 sensors for
Sepam series 20, 40, 60, 80 protection units
PE88012

LPCT sensors are voltage-output current sensors


(Low Power Current Transformer) compliant with the IEC 60044-8 standard.
These sensors are designed to measure rated current between 5 A and 630 A,
with a ratio of 100 A / 22.5 mV.
Sepam series 20, 40, 60 and 80 protection units are at the heart of the LPCT
protection chain.
Sepam series 20, 40, 60 and 80 performs the following functions:
•• acquisition of phase currents measured by the LPCT sensors
Sepam series 20 •• utilization of measurements by the protection functions
•• tripping of the breaking device in case of fault detection.

Advantages
Demanding
applications •• Consistent protection chain with the same sensor measures phase currents
from 5 A to 630 A
•• Simple to install and implement:
PE88011

-- installation of LPCT sensors


TLP130 and TLP190 are installed around MV cable
CLP2 is installed on the MV circuit
-- LPCT connected directly to Sepam series 20, 40, 60 and 80
-- accessories available to test the LPCT protection chain by secondary current
injection.
•• LPCTs range of use
LPCT measuring and protection function guaranteeing the accuracy up to
Sepam series 40 the short-time current.
Following the range of use of LPCT:
-- from 5 A up to 1250 A respecting the error limits imposed by the accuracy class 0.5
-- from 1250 A up to 50 kA respecting the error limits imposed by the accuracy class 5P.
Ratio error
DE58405EN

Custom 5.00
applications 4.75
4.50
4.25
4.00
3.75
PE88010

3.50
3.25 Protective class 5P
3.00
2.75 Measuring class 0.5
2.50
2.25
2.00
1.75
1.50
1.25
1.00
0.75
0.50
Sepam series 60 and 80 0.25 A

5 20 100 1000 1250 2000 3000 31500 40000 50000

•• Optimized integration of functions:


-- measurement of phase rated currents as of 25 A that is set by micro-switch
MT11325_LG

-- monitoring of LPCT sensor by Sepam series 20, 40, 60 and 80 (detection of


phase loss).

Connections
1 LPCT sensor, equipped with a shielded cable fitted with an RJ45 connector
to be connected directly to the card 3
2 Sepam series 20, 40, 60 and 80 protection unit
3 Card interface that adapts the voltage delivered by the LPCT sensors,
with microswitch setting of rated current.
-- CCA671 card for series 60 and 80
-- CCA670 card for series 20 and 40.

Testing and injection


4 CCA613 remote test plug, flush-mounted in front panel of cubicle, equipped
with a 3-m cord to be connected to the CCA670 connector test socket (9-pin Sub D)
5 ACE917 injection interface, used to test the LPCT protection chain with
a standard injection box
6 Standard 1A injection box.

schneider-electric.com SM6 catalogue 55