Chapter 4 - Power Distribution System Configuration
Chapter 4 - Power Distribution System Configuration
Chapter 4
Chapter 4.
Power Supply System
Configuration
Content
Chapter 4. PDS configuration
1. Introduction
Bạch quốc Khánh EE3420E – Power Supply Systems
1. Introduction
Chapter 4. PDS configuration
Factories, Towns
Distribution Distribution
substation Transformer
Transformer
3. Network configuration
Chapter 4. PDS configuration
3.1. Generality
1 2 0: Supply
1, 2: Load buses 1 2
⊗: Protection
3. Network configuration
Chapter 4. PDS configuration
3.1. Generality
Service Area:
Defined by customer layout, load distribution, distribution substation
Bạch quốc Khánh EE3420E – Power Supply Systems
6
3.VL − L 3 3 3 VL-L: Line-to-line voltage
3. Network configuration
Chapter 4. PDS configuration
3.1. Generality
3. Network configuration
Chapter 4. PDS configuration
3.2. Primary distribution feeder
Secondary selective
n.o.
Primary Loop
n.o. n.o. n.o.
Spot network
3. Network configuration
Chapter 4. PDS configuration
3.2. Primary distribution feeder Distribution
Substation
Circuit Breaker
Radial type
Primary feeder
Distribution
Transformer
− Common form of primary
Bạch quốc Khánh EE3420E – Power Supply Systems
distribution feeder.
− Lowest reliability. Faults
on any circuits results in
the outage of large
number of customers.
+ Simplest and cheapest. Sub-feeder Lateral tap
Applicable for rural areas,
normal loads.
3. Network configuration
Chapter 4. PDS configuration
3.2. Primary distribution feeder
Large loads
Substation
3. Network configuration
Chapter 4. PDS configuration
3.2. Primary distribution feeder
3. Network configuration
Chapter 4. PDS configuration
3.2. Primary distribution feeder
Substation
Loop type
+ High reliability
Bạch quốc Khánh EE3420E – Power Supply Systems
3. Network configuration
Chapter 4. PDS configuration
3.2. Primary distribution feeder
3. Network configuration
Chapter 4. PDS configuration
3.3. Secondary distribution feeder
Generality
Step down distribution transformer, secondary mains, service drop and
Bạch quốc Khánh EE3420E – Power Supply Systems
energy meter. Single phase for residential, 3-phase for industrial and
commercial customer with high load density.
3. Network configuration
Chapter 4. PDS configuration
3.3. Secondary distribution feeder
Secondary circuit
One (main)
customer
A group of customers
Radial system
A group of customers supplied by one distribution transformer and a
common secondary main.
3. Network configuration
Chapter 4. PDS configuration
3.3. Secondary distribution feeder
Secondary-banking system
Customers are served by a common secondary main is supplied several
Bạch quốc Khánh EE3420E – Power Supply Systems
Distribution Distribution
transformer transformer
3. Network configuration
Chapter 4. PDS configuration
3.3. Secondary distribution feeder
Configuration
Centralized layout with point to point link
Bạch quốc Khánh EE3420E – Power Supply Systems
4. Substations
Chapter 4. PDS configuration
4.1. Generality
Distribution substation
Substation Transformer (Voltage step-down HV/MV, MV/MV)
Bạch quốc Khánh EE3420E – Power Supply Systems
4. Substations
Chapter 4. PDS configuration
4.1. Generality
Distribution substation
Layout arrangement
Bạch quốc Khánh EE3420E – Power Supply Systems
Basic components of a distribution s/s. two transformers in two bays with feeders.
Substation components
Bạch quốc Khánh EE3420E – Power Supply Systems
4. Substations
Chapter 4. PDS configuration
4.1. Generality
Distribution transformer
Bạch quốc Khánh EE3420E – Power Supply Systems
Pole mounted
Indoor-type
DS
Fuse Surge
Arrester
Transformer
Box-type
(Container)
Distribution
panel
6
4. Substation
Chapter 4. PDS configuration
4.2. Location
Affected factors :
Voltage levels, voltage regulation, cost of subtransmission lines and
Bạch quốc Khánh EE3420E – Power Supply Systems
4. Substation
Chapter 4. PDS configuration
4.3. Capacity sizing
Rating
4. Substation
Chapter 4. PDS configuration
4.4. Bus arrangement
Supply
Lowest cost.
Simple bus protection
Low reliability: Load
Supply failure,
LV distribution
Bus failure, Power board ArTu K
Maintenance of bus outage (ABB)
and switching device
Applicable for normal load.
Used in low voltage system (Distribution
boards) for simple protection.
22
4. Substation
Chapter 4. PDS configuration
4.4. Bus arrangement Supply 1 Supply 2
ATS
Single bus with bus
Bus Bus
sectionalizer section 1 section 2
Bus-
Bạch quốc Khánh EE3420E – Power Supply Systems
4. Substation
Chapter 4. PDS configuration
4.4. Bus arrangement
1
Double bus – single circuit breaker
Two buses Bus 1 11
12
Bạch quốc Khánh EE3420E – Power Supply Systems
Bus-tie CB
1 circuit breaker - 2 Disconnecting Bus 2
switches each circuit
21 22
2
CB : 1,2
DS : 11-22
24
4. Trạm biến áp
Chương 4. Sơ đồ và kết cấu HTCCĐ
4.4. Sơ đồ phân phối điện
Bus Tie CB
25