1. SCOPE :
The specification covers design, manufacture, testing before despatch, transportation, supply and
delivery of ISI marked 1100V Aerial Bunched Cable of 3CX70(Ph)+1CX50(N)+1CX16(SL) having
XLPE insulated Cable (three Power Core) with stranded compact circular aluminium conductors
twisted over an insulated aluminium alloy messenger wire for use as overhead distribution feeders,
witht one street lighting core with stranded compacted circular aluminium conductor XLPE insulated
suitable for use on 3-Phase AC System conforming to IS-14255/1985 with up to date amendments
and associated accessories.
2. APPLICABLE STANDARDS :
Unless otherwise stipulated in this specification, the following standard with up to date
amendment shall be applicable.
7 IEC :60502 (Part-I)2004 Power cables with Extruded insulation ,cables for related
voltages of 1KV and 3 KV
8 REC specification AB cable and Insulation Piercing connectors etc.
9 NFC33-020 Insulation piercing connector
10 NFC 20-540 Environment Testing for Outdoor
11 NFC 33-004 Electrical Ageing Test
12 NFC 33-040 Suspension Equipments
13 NFC 33-041 Anchoring Devices
14 IS 14255 LV LT Aerial Bunched Cables
3. CLIMATE CONDITIONS
The AB cable and accessories shall be suitable for satisfactory continuous operation under the
following Moderately hot and humid tropical climate
1
Monthly Mean Minimum 24.9 Deg.C
3
Maximum Temperature ever recorded 39.2 Deg.C
Minimum Temperature ever recorded 21.0 Deg.C
Reference temperature for design of
50 Deg.C
electrical equipments
Relative Humidity
Monthly Mean Maximum 90%
4
Monthly Mean Minimum 60%
Maximum ever recorded 100%
Minimum ever recorded 17%
Rainfall
Highest monthly total in wettest month 487.5 mm
5
Lowest monthly total in driest month 0.9 mm
Highest rainfall ever 293.1 mm
Wind Velocity
Monthly mean Maximum 18.5 km/hr
6 Cyclonic Storms upto Approx. 2 per year with wind, velocity 200 km/hr
Design wind Pressure In accordance with IS:875
4.1 DEFINITION
The LT Aerial Bunched cable shall comprises of insulated phase conductors , insulated messenger
cum neutral wire and insulated street lighting conductor
The Aluminium Conductors for phase/street lightning conductor shall be H2 of H4 grade Aluminium
complying with the requirements of IS-8130-1984 with up to date amendments. For messenger wire
stranded All Aluminium Conductor shall be of heat treated Aluminium Magnesium-Silicon Alloy
Wires containing approximate 0.5% magnesium and 0.5% silicon conforming to IS-398 (Part-
IV)/1984 with up to date amendments. The stranded conductor shall be clean & reasonably uniform
in size and shape and its surface shall be free from sharp edges. Not more than two joints shall be
allowed in any of the wires forming every complete length of conductor and no joint shall be within
300 mm. of any other joint in the same layer. The joint shall be brazed, silver soldered or electric or
gas welded. No joint shall be made in the conductor, once it has been stranded.
2
5.3 DIMENSIONAL AND ELECTRICAL PARAMETERS
Max. D.C.
Nominal Sectional Dia. of Compacted Approx. mass Minimum Tensile
resistance At 20C
Area (mm.) Conductor(mm.) (Kg./Km.) Strength (KN)
(Ohm./Km.)
50 7.9 127 0.689 14.0
5.4 INSULATION:
The Conductor (with protective barrier, wherever applied) shall be provided with cross linked
polyethylene applied by extrusion conforming to the standard Specification as per IS 14255/95.
The average thickness of insulation when measured in accordance with relevant clause of the
specification, shall not be less than standard value specified. Upper surface of Cable insulation
should be Ultra Violet Ray resistant. Colour of insulation shall be black.
The Phase Conductors shall be insulated with black weather resistant, XLPE suitable for 1100 Volt
insulation. The Phase Conductor shall be provided with one, two and three ridges for quick
identification. The individual cores thus formed shall then be laid up around insulated messenger
wire. The insulated messenger wire shall have four ridges as per IS 14255:1995. The insulated street
lighting conductor shall not have anyidentification mark.
5.7 LAYING UP :
Three Power Cores having Ridges one, two and three and one street lighting without any ridge,
should be twisted over insulated messenger wire with right hand direction of lay. This will form the
Aerial Bunched Cable. Lay ratio shall be as specified in IS:14255/1995.
3
6. TESTS FOR CABLES :
6.1 TYPE TEST
Type test reports not older than 5 years obtained from any one of the Government /approved NABL
accredited independent laboratories for the Aerial Bunched Cables specified in relevant IS & other
international standards shall be furnished by the bidders along with the bid. The bid not accompanied
with test reports may not be considered forevaluation.
Type test reports shall contain details of following type tests as per IS 8130-1984 , IS 10810 & IS
14255/1995
i) Tensile Test
ii) Wrapping Test.
iii) Resistance Test.
Report of above and any other type test provided in the relevant Indian Standards shall also be supplied.
These shall be carried out on all sizes of all drums of unamoured Cables by the supplier as given in
Clause 5.1 and shall be got approved before despatch.
The Cable shall be inspected and tested at the manufacturer’s works before despatch as per ISS
mentioned in schedule of requirement. The manufacturer shall arrange all the necessary machinery,
apparatus and labour required for the testingpurpose.
The routine tests embodied in the respective ISS are as per list given below :
1. Conductor ResistanceTest.
2. High Voltage Test at roomtemperature.
3. Cold Bend Test (optional)
Any other routine test provided in the relevant Indian Standards shall also got conducted by the
suppler.
4
6.3 ACCEPTANCE TEST :
These tests as per relevant IS & IEC shall be carried out in the presence of the purchaser’s
representative if so desired by the purchaser. The following shall constitutethe acceptance tests.
(a) Tensile Test (for phase/street light conductor)
(b) Wrapping Test (for phase/street light conductor)
(c) Breaking Load Test for messenger Conductor.
(d) Elongation test for messenger conductor.
(e) Conductor resistance test.
(f) Test for thickness of insulation.
(g) Tensile Strength and Elongation at Break Test.
(h) Hot Set Test for XLPE insulation.
(i) Insulation resistance test and
(j) High Voltage Test.
7. SEQUENTIAL MARKING :
Supplier shall provide non erasable sequential marking of length of any one of the phase core by
painting /embossing /engraving for each meter length with sequential marking machine. Besides the
information of the Supply order shall also be provided on the supplies.
8. PACKING &MARKING :
The Cable shall be supplied on suitable sized wooden non-returnable drum of robust construction for
each length of Cables as per I.S. 10418. A layor of water proof paper shall be applied to the surface
of the drums and over the outer cable layer. A clear space at least 40 mm. shall be left between the
Cable and Logging. Wood preservative shall be applied to the entire drum. Each metre length shall
be embossed with the Trade Name of Manufacturer and the work ‘IPDS - PED’. Packing shall be
sturdy to protect the Cable from any injury during transportation handling and storage. Both Cable
ends shall be sealed with PVC/Rubber Caps to eliminate ingress of moisture. Each Cable Drum shall
have following information stenciled on it.
a) Manufacturer’s Name, Brand Name of Trade Mark.
b) Year of Manufacture.
c) Nominal Cross-Sectional area of the Cable Conductor.
d) Type of Cable and Voltage Grade.
e) Length of the Cable.
f) Number of the Cores.
g) ISI Certification Mark, IS reference.
h) Colour of outer sheath.
i) No. of lengths in Drum (if more than one)
j) Cable Code.
k) Direction of rotation of drum (by means of an arrow)
l) Approximate gross weight in Kg./Km.
The standard Drum Length will be 500 Meters. in each Drum for all sizes subject to a tolerance of +
5%.
5
PART –B
1.1 Scope
This specification is for the supply of Insulation Piercing Connectors (IPC) making connections to
Insulated Messenger L.T XLPE insulated Aerial Bunched Cables rated up to1100 volts to L.T XLPE
insulated Aerial Bunched Cables
ii. NFC 33-041:1998 "Anchoring devices for Overhead Distribution with bundle assembled cores, of
rated voltage 0,6/1 kV"
iii. NFC 33-042:1998 "Service Anchoring devices for overhead and underground services with
insulated cables, of rated voltage 0,6/1 kV"
iv. NFC 33-020:1998 "Insulation piercing connectors for overhead distributions and services with
bundle assembled cores, of rated voltage 0,6/1 kV".
v. NFC 33-021:1998 "Pre-insulated compression type connecting equipment for bundle assembled
cores, of rated
1.3 The devices shall also be compatible with the cables of sizes & dimensions as defined in the cable
Specifications for the cables with which they are intended to be used
1.4 The standard sizes and characteristics of the phase and street lighting conductors, bare messenger
wires shall be as specified in IS: 14255-1995
1.5 Insulation Piercing Connectors (IPC) is used for making Tee/Tap-off/Service connectors to an ABC
Line. Insulation Piercing Connectors are designed to make a connection between the uncut main
conductor and a branch cable conductor without having to strip either cable to expose the conductor.
Instead, the tightening action of the IPC will first pierce the Insulation, and then make good electrical
contact between the main end and branch conductor while simultaneously insulating and sealing the
connection.
6
The size ranges for various applications are given below:
1.6.1 The connector bodies shall be made entirely of mechanical and weather resistant plastic
insulation material made of weather & UV resistant reinforced polymer and no metallic part outside
the housing is acceptable except for the tightening bolt or nuts.
1.6.2 Any metallic part that is exposed must not be capable of carrying a potential during or after connector
installation.
1.6.3. Screws or nuts assigned for fitting with IPC must be fitted with torque limiting shear heads to prevent
over tightening or under tightening While the min & max torque values are to be specified by
Manufacturer, these should not exceed 20 N mtr for IPC for main conductor < 95 sq mm.
1.6.4. The IPC must perform piercing of Tap insulated conductor connection on Main cable simultaneously
using single bolt for tightening as multiple bolts do not ensure even tightening. Design of connector
needs to avoid the stripping of insulated tap conductor and make the connection by piercing the
insulation.
1.6.5. The shear bolt/nut shall be suitable for tightening with a hexagonal spanner of 13 mm.
1.6.6. The contract blade of the connector is made of tinned copper/aluminum alloy.
1.6.7. The IPC shall be water proof and the water tightness shall be ensured by appropriate elastomer
materials and not by grease gel or paste alone. Grease can be applied to protect the contact blade alone
and shall not be visible of the outer surface of the connector. Connector should not be dipped in
grease.
1.6.8. Each IPBC should be provided with a cap to seal the cut end of the insulated Branch cable. It should
be of a design that once the connector id fitted, it shall not be possible to remove the cap without
dismantling the connector.
1.6.9. Design of IPBC should be such as to not cause damage to insulation of adjacent conductors due to
vibration and relative movement during service.
1.6.10. All the metallic parts of the connector should be corrosion resistant and there should not be
any appreciable change in contact resistance & temperature after overloads & load cycling and should
be confirm to the long duration tests specified in this standard.
2.1 Scope
7
This specification covers the design, manufacture, assembly, testing and supply of Accessories for
suspending Aerial Bunched Cables rated 1100 volts and insulated with cross-linked polyethylene and
aluminum alloy bare messenger.
2.1.2 The clamp should be designed to hang L.T – AB cable with insulated neutral messengers. The neutral
messengers should be fixed by an adjustable grip device. A movable link should allow longitudinal
and transversal movement of the clamp body.
2.1.3 No losable part in the process of clamping arrangement.
2.1.4 The clamp should conform to the standard NFC 33040 or equivalent I.S, if any.
2.1.5 The clamp and the link made of Polymer should provide an additional insulation between the cable
and the pole.
2.1.6 The clamps and movable links should be made of weather and UV resistant glassfibre reinforced
polymer.
2.1.7 Clamps should be fixed with pole by bracket. Bracket should be made of corrosion resistant
alluminium alloy.
2.1.8 Ultimate tensile strength of the clamp should not be less than 15 KN for 50/70 sq.mm. insulated
messenger wire
2.1.9 Maximum allowable load of the clamp should not be less than 20 KN for 50/70 sq.mm. insulated
messenger wire.
2.1.10 Suspension Assembly is used for supporting an ABC by installation on the messenger at an
intermediate point of support such as a pole. It can accommodate small angles of deviation upto 30
degree.
2.2 Each Suspension Assembly shall consist of :
a. One number Suspension Bracket.
b. One number moveable (articulated) connecting link.
c. One number Suspension Clamp.
2.3 Suspension Assemblies shall be supplied in sets to ensure compatibility of the materials against
corrosion or wear of rotating/moving parts.
2.4.1. The Suspension Bracket shall be made from single piece aluminium alloy suitable for attachment to a
pole by either.
a) 16 mm galvanized steel bolt or b) Two stainless steel straps.
2.4.2 The Suspension Bracket shall be provided with an upper bulge to prevent the clamp from turning over
on the Bracket for more than 45 degree from the horizontal or to within less than 60 mm from the pole
/ fixing structure.
2.4.3 The Suspension Bracket should be so designed to ensure that the articulated link cannot slip out of it.
2.4.4 Suspension Brackets shall be designed to withstand a load applied at the anchoring point of the
movable link
Conductor Size Normal Load
Sq. mm. Dia. mm Rating (Newtons)
16-54 8-15 1500 Kg 12500
8
2.5 MOVABLE (ARTICULATED) LINK OF SA
2.5.1 Movable Links are used between the Suspension Bracket and Suspension Clamp to allow a degree of
movement and flexibility between the two.
2.5.2 Moveable Links should be made fully of insulating type of mechanical and weather resistant
thermoplastic. A metallic wear resistant ring should however be fitted at point of contact between the
Suspension Bracket and the movable link.
2.5.3 The Movable link should be un loosably fitted to the Bracket and the Clamp.
2.6.1 Suspension Clamps are used for locking the messenger of the ABC bundle without damaging the
insulation or allowing the messenger to become dismounted from the fitting.
2.6.2 The Suspension Clamp shall accommodate messenger wires for 50 sq.mm.
2.6.3 The Suspension Clamp shall be made fully of insulating type of mechanically strong and weather
resistant plastic.
2.6.4 Bolts should not be used for clamping / locking the messenger in the Clamp.
2.6.5 There shall be no losable parts in the Suspension clamp.
2.6.6 The Suspension Clamp should be unloosably fitted to the rest of the Suspension Assembly.
2.8 Test Certificate.
2.8.1 Type Test, Acceptance test, Routine test reports obtained from an NABL accredited Laboratory
should be furnished
NOTES.
I. Permissible tolerance shall be ± 5% on the indicated dimensions.
3.1 The clamps should be designed to Anchor LT-AB cable with insulated messenger. The clamp should
consists of an Aluminium alloy corrosion resistant castled body, bail of stainless steel and self
adjusting plastic wedges which shall anchor/hold the neutral messenger without damaging the
insulation
3.1.1 No losable part in the process of clamping arrangement
3.1.2 The clamp should conform to the standard NFC 33041 and 33042 or equivalent I.S. if any
3.1.3 The clamp body should be made of corrosion resistant Alluminium alloy, bail should be of stainless
steel and wedges should be weather and UV resistant polymer.
3.1.4 Ultimate tensile strength of the clamp should not be less than 15 km for 50/70 sq.mm insulated
messenger wire.
3.1.5 Slip load of the clamp should not be less than 3 KN for 50/70 sq.mm. messenger wire
3.1.6 Anchoring assemblies are used to firmly attach the messenger of ABC to a support and transmit the
mechanical tension.
A at the end of a run or to the supporting structures
B at a major change in direction.
9
3.2 Tension Bracket
3.2.1 The tension bracket shall be made out of a single piece of Aluminium alloy suitable for attachment to
a pole
3.2.3 Anchoring assemblies shall be supplied in sets to ensure compatibility of the materials against
corrosion or wear of moving parts.
3.2.4 The tension bracket should be designed to ensure the Flexible rope cannot slip out at any angle.
3.2.5 The tension bracket should be rated and tested for the loads . The load shall be applied at an angle of
45 degree from the normal to the surface of mounting of the bracket.
3.6.1 Wedge type clamps shall be used for clamping the messenger without damaging the insulation.
3.6.2 The clamp shall be capable of clamping an uncut messenger so that it can continue without break to
the connecting point or next span.
3.6.3 The clamp shall be fully insulating type of mechanical and weather resisting thermoplastic.
3.6.4 No bolts or loose parts are allowed as part of the Clamping system.
3.6.5 No tools shall be needed for fitting the messenger into the clamp.
3.6.6 The clamp shall be self tightening and capable of holding without slippage the load
NOTES
I. Permissible tolerance shall be ± 5% on the indicated dimensions.
4.0 TECHNICAL SPECIFICATIONS FOR 3 PHASE L.T. DISTRIBUTION BOX FOR AERIAL
BUNCHED CABLE
4.1 The L.T. Distribution Box is used for connection through overhead ABC line and for giving
connections to the consumers. The L.T. Distribution Box will be installed at the poles and it should
have anti-corrosive, dust proof, rust proof, shock proof, vermin proof, U.V. stabilized and flame
retardant property. Base door or other joint should not bend, soften on heating and it should be of
tamper proof construction the material of box should withstand temperature rise, hot
spot temperature and occasional arcing of bus bar system.
4.1.1 The Box/Kiosk shall be made out of thermosetting plastic i.e. Glass Fiber Reinforced Polyester Sheet
Moulding Compound (SMC) as per IS: 13410-1992 having properties as given in GTP.
4.1.2 The box should have sealing as well as pad locking arrangement. One M.S. Flat with 12 mm dia hole
should be provided for pole mounting.
1
0
4.1.3 The Distribution Box shall have 3 phase Bus bars of EC grade Aluminium of size 25x6 x 300 mm
long and neutral bus bar shall be of size 40x6x 300 mm. The Bus bars shall be provided with colour
coding for identification. Each Bus bar shall be provided with facility of cable termination as under:
4.1.4 To facilitate easy working on termination on bus bar, the arrangement for termination of each lead
should be have 6 mm dia holes duly fitted with M 6 x 20 screw, I custom designed Aluminum palm
.washer, 1 washer, 1 spring washer and I fly nut as shown in drawing.
4.1.5 In order to restrict entry of tool from unused (cable entry) holes, partition plate should be provided
between wall of the box and bus bar system. The service wire/cables will be taken from entry hole,
suitably bent and taken to bus bar and' finally the wire/cable shall be terminated and lightened using
fly nut.
4.1.6 The assembly of four nos. Al. Busbars shall be mounted on one SMC Step mounting arrangement.
The mounting arrangement of Bus bars shall be such that minimum clearance of 50 mm is maintained
between Busbar and Box wall on all sides. This clearance will provided adequate space for working as
well as bending of wires. Also there should be minimum clearance of 40 mm between each bus bar so
as to take care of clearance and creepage distance requirements in line with IS: 13947.
4.1.7 The dimension of box shall be 450 x 375 x 200 mm. Thickness of box shall be 3 mm. The colour of
box shall be Off White such that it does not absorb heat of solar radiation. Reprocessible plastics and
of dark colour will not acceptable.
1
2
2 Name and address of
manufactured of ABC
accessories
3 Product Designation
4 Standard As per NFC 33 020-1998
Range of Cable sizes Main: 50-150 Sq. mm.
5 accommodated for main &
branch
Branch: 6-35(50) Sq.
mm.
6 Application KV 1.1
7 System Frequency Hz 50
8 Material Composition a)Body: Weather & UV
resistance glass fibre
reinforced polymer
b)contact plates-
Aluminium alloy
c)Bolt-Dechromatized
steel
d)Seats & end caps:
Elastomer
9 Voltage withstand under KV 6 KV for 1 min
water emersion
10 Electrical Ageing Type Test
11 No. of cycles 200
12 Max. Temperature for each 90oC
cycle
13 Min. & Max. Torque Nm Max. 12.1
defined
Min. 9.9
14 Rated Tightening Torque Nm 11
15 Marking Main Range
Tap Range
16 Dimensions mm
17 Approximate weight Kg 0.12
1
5