TECHNICAL SPECIFICATIONS FOR SUPPLY OF AERIAL BUNCHED CABLE HAVING XLPE

INSULATED L.T. CABLE (3CX70(Ph)+1CX50(N)+1CX16(SL))FOR WORKING VOLTAGE


UPTO 1100VOLTS ALONG WITH ACCESSORIES REQUIRED FOR DRAWAL OF CABLE
ON TUBULAR/RCC POLE SUPPORTS
PART – A

1. SCOPE :

The specification covers design, manufacture, testing before despatch, transportation, supply and
delivery of ISI marked 1100V Aerial Bunched Cable of 3CX70(Ph)+1CX50(N)+1CX16(SL) having
XLPE insulated Cable (three Power Core) with stranded compact circular aluminium conductors
twisted over an insulated aluminium alloy messenger wire for use as overhead distribution feeders,
witht one street lighting core with stranded compacted circular aluminium conductor XLPE insulated
suitable for use on 3-Phase AC System conforming to IS-14255/1985 with up to date amendments
and associated accessories.

2. APPLICABLE STANDARDS :

Unless otherwise stipulated in this specification, the following standard with up to date
amendment shall be applicable.

1 IS14255-1995 Specification for AERIAL Bunched Cables for working Voltage up to


& including 1100 Volts.
2 IS : 8130 Specification for Conductors for Insulated Cables.
3 IS : 398 (Part-IV) Specification for Aluminium Alloy Conductor
4 IS : 10810 Methods of test for Cables
5 IS :10418 Drums for electric cables
6 IS7098 Part1 XLPE insulated cables

7 IEC :60502 (Part-I)2004 Power cables with Extruded insulation ,cables for related
voltages of 1KV and 3 KV
8 REC specification AB cable and Insulation Piercing connectors etc.
9 NFC33-020 Insulation piercing connector
10 NFC 20-540 Environment Testing for Outdoor
11 NFC 33-004 Electrical Ageing Test
12 NFC 33-040 Suspension Equipments
13 NFC 33-041 Anchoring Devices
14 IS 14255 LV LT Aerial Bunched Cables

3. CLIMATE CONDITIONS
The AB cable and accessories shall be suitable for satisfactory continuous operation under the
following Moderately hot and humid tropical climate

1 Climatic conditions Atmosphere is generally saline, hot and humid.

2 Altitude 3.0 M above MSL(Graded Level )


Ambient Air Temperature
Monthly Mean Maximum 32.6 Deg.C

1
Monthly Mean Minimum 24.9 Deg.C
3
Maximum Temperature ever recorded 39.2 Deg.C
Minimum Temperature ever recorded 21.0 Deg.C
Reference temperature for design of
50 Deg.C
electrical equipments
Relative Humidity
Monthly Mean Maximum 90%
4
Monthly Mean Minimum 60%
Maximum ever recorded 100%
Minimum ever recorded 17%
Rainfall
Highest monthly total in wettest month 487.5 mm
5
Lowest monthly total in driest month 0.9 mm
Highest rainfall ever 293.1 mm
Wind Velocity
Monthly mean Maximum 18.5 km/hr
6 Cyclonic Storms upto Approx. 2 per year with wind, velocity 200 km/hr
Design wind Pressure In accordance with IS:875

4. AERIAL BUNCHED CABLES

4.1 DEFINITION

The LT Aerial Bunched cable shall comprises of insulated phase conductors , insulated messenger
cum neutral wire and insulated street lighting conductor

Designation and Size

3C x 70(Ph)+1C x 50(N)+1C x 16(SL)


P- Insulated Phase conductor of 3X70 Sq.mm
M- Insulated Messenger cum neutral wire of 1X50Sq.mm
SL- Insulated Street Lighting Conductor of 1X16Sq.mm
5. SPECIFICATION FOR ABC CABLE
5.1 RATED VOLTAGE :
The rated Voltage of LT AB Cables shall be 1100 Volts.
5.2 CONDUCTORS :

The Aluminium Conductors for phase/street lightning conductor shall be H2 of H4 grade Aluminium
complying with the requirements of IS-8130-1984 with up to date amendments. For messenger wire
stranded All Aluminium Conductor shall be of heat treated Aluminium Magnesium-Silicon Alloy
Wires containing approximate 0.5% magnesium and 0.5% silicon conforming to IS-398 (Part-
IV)/1984 with up to date amendments. The stranded conductor shall be clean & reasonably uniform
in size and shape and its surface shall be free from sharp edges. Not more than two joints shall be
allowed in any of the wires forming every complete length of conductor and no joint shall be within
300 mm. of any other joint in the same layer. The joint shall be brazed, silver soldered or electric or
gas welded. No joint shall be made in the conductor, once it has been stranded.

2
5.3 DIMENSIONAL AND ELECTRICAL PARAMETERS

CHARACTERISTIC OF PHASE AND STREET LIGHTING CONDUCTOR FOR LT ABC :

Nominal Sectional Area of Conductors (sq.mm.)


Parameters 16 70
No. of Strands 4 7
Dia. of Compacted Conductor (MM) 4.4 9.4
Approx. Mass (Kg./Km.) 42 170
Max. DC resistance at 200 C (ohm/km.) 1.91 0.443
Insulation Thickness (mm.) 1.2 1.5
Current rating at 400 C in air. 60 155

CHARACTERISTIC OF INSULATED MESSENGER-CUM-NEUTRAL WIRE FOR LT ABC :

Max. D.C.
Nominal Sectional Dia. of Compacted Approx. mass Minimum Tensile
resistance At 20C
Area (mm.) Conductor(mm.) (Kg./Km.) Strength (KN)
(Ohm./Km.)
50 7.9 127 0.689 14.0

5.4 INSULATION:

The Conductor (with protective barrier, wherever applied) shall be provided with cross linked
polyethylene applied by extrusion conforming to the standard Specification as per IS 14255/95.
The average thickness of insulation when measured in accordance with relevant clause of the
specification, shall not be less than standard value specified. Upper surface of Cable insulation
should be Ultra Violet Ray resistant. Colour of insulation shall be black.

5.5 CORE IDENTIFICATION :

The Phase Conductors shall be insulated with black weather resistant, XLPE suitable for 1100 Volt
insulation. The Phase Conductor shall be provided with one, two and three ridges for quick
identification. The individual cores thus formed shall then be laid up around insulated messenger
wire. The insulated messenger wire shall have four ridges as per IS 14255:1995. The insulated street
lighting conductor shall not have anyidentification mark.

5.6 MESSENGER-CUM-NEUTRAL WIRE :


The insulated messenger wire shall be of aluminium alloy, generally conforming to IS 398 (Part-
IV)/1994 and suitably compacted to have smooth round surface to avoid damage to the other
insulating sheath of phase conductor twisted around the messenger.

5.7 LAYING UP :
Three Power Cores having Ridges one, two and three and one street lighting without any ridge,
should be twisted over insulated messenger wire with right hand direction of lay. This will form the
Aerial Bunched Cable. Lay ratio shall be as specified in IS:14255/1995.

3
6. TESTS FOR CABLES :
6.1 TYPE TEST

Type test reports not older than 5 years obtained from any one of the Government /approved NABL
accredited independent laboratories for the Aerial Bunched Cables specified in relevant IS & other
international standards shall be furnished by the bidders along with the bid. The bid not accompanied
with test reports may not be considered forevaluation.

Type test reports shall contain details of following type tests as per IS 8130-1984 , IS 10810 & IS
14255/1995

1. Tests on Phase/Street Light Conductor :

i) Tensile Test
ii) Wrapping Test.
iii) Resistance Test.

2. Test on Messenger Conductor ;


i) Breaking Load.
ii) Elongation Test.
iii) Resistance Test.

3. Physical Test for XLPE insulation :


i) Tensile Strength and elongation at break.
ii) Ageing in on even.
iii) Hot Set Test.
iv) Shrinkage Test.
v) Water Absorption (Gavimetric)

4. Test for thickness insulation.


5. Insulation performance (Volume resistivity) Test.
6. High Voltage Test.

Report of above and any other type test provided in the relevant Indian Standards shall also be supplied.

6.2 ROUTINE TEST ;

These shall be carried out on all sizes of all drums of unamoured Cables by the supplier as given in
Clause 5.1 and shall be got approved before despatch.

The Cable shall be inspected and tested at the manufacturer’s works before despatch as per ISS
mentioned in schedule of requirement. The manufacturer shall arrange all the necessary machinery,
apparatus and labour required for the testingpurpose.

The routine tests embodied in the respective ISS are as per list given below :
1. Conductor ResistanceTest.
2. High Voltage Test at roomtemperature.
3. Cold Bend Test (optional)

Any other routine test provided in the relevant Indian Standards shall also got conducted by the
suppler.

4
6.3 ACCEPTANCE TEST :

These tests as per relevant IS & IEC shall be carried out in the presence of the purchaser’s
representative if so desired by the purchaser. The following shall constitutethe acceptance tests.
(a) Tensile Test (for phase/street light conductor)
(b) Wrapping Test (for phase/street light conductor)
(c) Breaking Load Test for messenger Conductor.
(d) Elongation test for messenger conductor.
(e) Conductor resistance test.
(f) Test for thickness of insulation.
(g) Tensile Strength and Elongation at Break Test.
(h) Hot Set Test for XLPE insulation.
(i) Insulation resistance test and
(j) High Voltage Test.

7. SEQUENTIAL MARKING :
Supplier shall provide non erasable sequential marking of length of any one of the phase core by
painting /embossing /engraving for each meter length with sequential marking machine. Besides the
information of the Supply order shall also be provided on the supplies.

8. PACKING &MARKING :
The Cable shall be supplied on suitable sized wooden non-returnable drum of robust construction for
each length of Cables as per I.S. 10418. A layor of water proof paper shall be applied to the surface
of the drums and over the outer cable layer. A clear space at least 40 mm. shall be left between the
Cable and Logging. Wood preservative shall be applied to the entire drum. Each metre length shall
be embossed with the Trade Name of Manufacturer and the work ‘IPDS - PED’. Packing shall be
sturdy to protect the Cable from any injury during transportation handling and storage. Both Cable
ends shall be sealed with PVC/Rubber Caps to eliminate ingress of moisture. Each Cable Drum shall
have following information stenciled on it.
a) Manufacturer’s Name, Brand Name of Trade Mark.
b) Year of Manufacture.
c) Nominal Cross-Sectional area of the Cable Conductor.
d) Type of Cable and Voltage Grade.
e) Length of the Cable.
f) Number of the Cores.
g) ISI Certification Mark, IS reference.
h) Colour of outer sheath.
i) No. of lengths in Drum (if more than one)
j) Cable Code.
k) Direction of rotation of drum (by means of an arrow)
l) Approximate gross weight in Kg./Km.

The standard Drum Length will be 500 Meters. in each Drum for all sizes subject to a tolerance of +
5%.

5
PART –B

TECHNICAL SPECIFICATIONS OF ABC ACCESSORIES

1. INSULATION PIERCING CONNECTOR (IPC)

1.1 Scope
This specification is for the supply of Insulation Piercing Connectors (IPC) making connections to
Insulated Messenger L.T XLPE insulated Aerial Bunched Cables rated up to1100 volts to L.T XLPE
insulated Aerial Bunched Cables

1.2 Standard References


The supplier shall confirm to this specification and the following standards. However in case of any
conflict, the requirements of this specification shall prevail.
i. NFC 33-040:1998 "Suspension Equipments for Overhead distribution with Bundle assembled
cores, of rated voltage 0,6/1 kV

ii. NFC 33-041:1998 "Anchoring devices for Overhead Distribution with bundle assembled cores, of
rated voltage 0,6/1 kV"

iii. NFC 33-042:1998 "Service Anchoring devices for overhead and underground services with
insulated cables, of rated voltage 0,6/1 kV"

iv. NFC 33-020:1998 "Insulation piercing connectors for overhead distributions and services with
bundle assembled cores, of rated voltage 0,6/1 kV".

v. NFC 33-021:1998 "Pre-insulated compression type connecting equipment for bundle assembled
cores, of rated

vi. NFC 33-004:1998 "Electrical ageing test"


vii. NFC 33-003:1998 "Corrosion test"
viii. NFC 20-540:1998 "Climatic ageing test"
ix. REC Construction Standards E-34, E-35 and E-36

1.3 The devices shall also be compatible with the cables of sizes & dimensions as defined in the cable
Specifications for the cables with which they are intended to be used

1.4 The standard sizes and characteristics of the phase and street lighting conductors, bare messenger
wires shall be as specified in IS: 14255-1995
1.5 Insulation Piercing Connectors (IPC) is used for making Tee/Tap-off/Service connectors to an ABC
Line. Insulation Piercing Connectors are designed to make a connection between the uncut main
conductor and a branch cable conductor without having to strip either cable to expose the conductor.
Instead, the tightening action of the IPC will first pierce the Insulation, and then make good electrical
contact between the main end and branch conductor while simultaneously insulating and sealing the
connection.

6
The size ranges for various applications are given below:

Requirement Main Cable Size range Branch Cable Size


range
Insulation Piercing Connectors for 70&50 sq mm (AB 16-95 sq mm (AB
Tapping of phase & Neutral core Cable) Cable)
Insulation Piercing Connectors for 16 sq mm (AB Cable) 2.5 -10 sq mm
Street light core (PVC Al street
light service
Cable)

1.6 CONSTRUCTIONAL FEATURES OF INSULATION PIERCING CONNECTORS


The following features of Insulation piercing bare connectors are to be met for the qualification
criteria

1.6.1 The connector bodies shall be made entirely of mechanical and weather resistant plastic
insulation material made of weather & UV resistant reinforced polymer and no metallic part outside
the housing is acceptable except for the tightening bolt or nuts.
1.6.2 Any metallic part that is exposed must not be capable of carrying a potential during or after connector
installation.
1.6.3. Screws or nuts assigned for fitting with IPC must be fitted with torque limiting shear heads to prevent
over tightening or under tightening While the min & max torque values are to be specified by
Manufacturer, these should not exceed 20 N mtr for IPC for main conductor < 95 sq mm.
1.6.4. The IPC must perform piercing of Tap insulated conductor connection on Main cable simultaneously
using single bolt for tightening as multiple bolts do not ensure even tightening. Design of connector
needs to avoid the stripping of insulated tap conductor and make the connection by piercing the
insulation.
1.6.5. The shear bolt/nut shall be suitable for tightening with a hexagonal spanner of 13 mm.
1.6.6. The contract blade of the connector is made of tinned copper/aluminum alloy.
1.6.7. The IPC shall be water proof and the water tightness shall be ensured by appropriate elastomer
materials and not by grease gel or paste alone. Grease can be applied to protect the contact blade alone
and shall not be visible of the outer surface of the connector. Connector should not be dipped in
grease.
1.6.8. Each IPBC should be provided with a cap to seal the cut end of the insulated Branch cable. It should
be of a design that once the connector id fitted, it shall not be possible to remove the cap without
dismantling the connector.
1.6.9. Design of IPBC should be such as to not cause damage to insulation of adjacent conductors due to
vibration and relative movement during service.
1.6.10. All the metallic parts of the connector should be corrosion resistant and there should not be
any appreciable change in contact resistance & temperature after overloads & load cycling and should
be confirm to the long duration tests specified in this standard.

1.7 Test Certificate.


1.7.1 Type Test, Acceptance test, Routine test reports obtained from an NABL accredited Laboratory
should be furnished.

2.0 SUSPENSION CLAMPS

2.1 Scope
7
This specification covers the design, manufacture, assembly, testing and supply of Accessories for
suspending Aerial Bunched Cables rated 1100 volts and insulated with cross-linked polyethylene and
aluminum alloy bare messenger.

Description Application Application

For supporting a length of ABC at


Suspension Clamp an intermediate pole in a length,
with small angle of deviation.

2.1.2 The clamp should be designed to hang L.T – AB cable with insulated neutral messengers. The neutral
messengers should be fixed by an adjustable grip device. A movable link should allow longitudinal
and transversal movement of the clamp body.
2.1.3 No losable part in the process of clamping arrangement.
2.1.4 The clamp should conform to the standard NFC 33040 or equivalent I.S, if any.
2.1.5 The clamp and the link made of Polymer should provide an additional insulation between the cable
and the pole.
2.1.6 The clamps and movable links should be made of weather and UV resistant glassfibre reinforced
polymer.
2.1.7 Clamps should be fixed with pole by bracket. Bracket should be made of corrosion resistant
alluminium alloy.
2.1.8 Ultimate tensile strength of the clamp should not be less than 15 KN for 50/70 sq.mm. insulated
messenger wire
2.1.9 Maximum allowable load of the clamp should not be less than 20 KN for 50/70 sq.mm. insulated
messenger wire.
2.1.10 Suspension Assembly is used for supporting an ABC by installation on the messenger at an
intermediate point of support such as a pole. It can accommodate small angles of deviation upto 30
degree.
2.2 Each Suspension Assembly shall consist of :
a. One number Suspension Bracket.
b. One number moveable (articulated) connecting link.
c. One number Suspension Clamp.
2.3 Suspension Assemblies shall be supplied in sets to ensure compatibility of the materials against
corrosion or wear of rotating/moving parts.

2.4 SUSPENSION BRACKET OF SUSPENSION ASSEMBLIES (SA)

2.4.1. The Suspension Bracket shall be made from single piece aluminium alloy suitable for attachment to a
pole by either.
a) 16 mm galvanized steel bolt or b) Two stainless steel straps.
2.4.2 The Suspension Bracket shall be provided with an upper bulge to prevent the clamp from turning over
on the Bracket for more than 45 degree from the horizontal or to within less than 60 mm from the pole
/ fixing structure.
2.4.3 The Suspension Bracket should be so designed to ensure that the articulated link cannot slip out of it.
2.4.4 Suspension Brackets shall be designed to withstand a load applied at the anchoring point of the
movable link
Conductor Size Normal Load
Sq. mm. Dia. mm Rating (Newtons)
16-54 8-15 1500 Kg 12500
8
2.5 MOVABLE (ARTICULATED) LINK OF SA

2.5.1 Movable Links are used between the Suspension Bracket and Suspension Clamp to allow a degree of
movement and flexibility between the two.
2.5.2 Moveable Links should be made fully of insulating type of mechanical and weather resistant
thermoplastic. A metallic wear resistant ring should however be fitted at point of contact between the
Suspension Bracket and the movable link.
2.5.3 The Movable link should be un loosably fitted to the Bracket and the Clamp.

2.6 SUSPENSION CLAMP OF SA

2.6.1 Suspension Clamps are used for locking the messenger of the ABC bundle without damaging the
insulation or allowing the messenger to become dismounted from the fitting.
2.6.2 The Suspension Clamp shall accommodate messenger wires for 50 sq.mm.
2.6.3 The Suspension Clamp shall be made fully of insulating type of mechanically strong and weather
resistant plastic.
2.6.4 Bolts should not be used for clamping / locking the messenger in the Clamp.
2.6.5 There shall be no losable parts in the Suspension clamp.
2.6.6 The Suspension Clamp should be unloosably fitted to the rest of the Suspension Assembly.
2.8 Test Certificate.
2.8.1 Type Test, Acceptance test, Routine test reports obtained from an NABL accredited Laboratory
should be furnished

NOTES.
I. Permissible tolerance shall be ± 5% on the indicated dimensions.

3.0 ANCHORING / DEAD END CLAMP FOR INSULATED MESSENGER :

3.1 The clamps should be designed to Anchor LT-AB cable with insulated messenger. The clamp should
consists of an Aluminium alloy corrosion resistant castled body, bail of stainless steel and self
adjusting plastic wedges which shall anchor/hold the neutral messenger without damaging the
insulation
3.1.1 No losable part in the process of clamping arrangement
3.1.2 The clamp should conform to the standard NFC 33041 and 33042 or equivalent I.S. if any
3.1.3 The clamp body should be made of corrosion resistant Alluminium alloy, bail should be of stainless
steel and wedges should be weather and UV resistant polymer.
3.1.4 Ultimate tensile strength of the clamp should not be less than 15 km for 50/70 sq.mm insulated
messenger wire.
3.1.5 Slip load of the clamp should not be less than 3 KN for 50/70 sq.mm. messenger wire
3.1.6 Anchoring assemblies are used to firmly attach the messenger of ABC to a support and transmit the
mechanical tension.
A at the end of a run or to the supporting structures
B at a major change in direction.

3.1..7 Each Anchoring Assembly shall include.


A One number tension bracket.
B One number wedge type tension clamp
C Flexible Rope for fixing tension clamp to bracket.

9
3.2 Tension Bracket
3.2.1 The tension bracket shall be made out of a single piece of Aluminium alloy suitable for attachment to
a pole
3.2.3 Anchoring assemblies shall be supplied in sets to ensure compatibility of the materials against
corrosion or wear of moving parts.
3.2.4 The tension bracket should be designed to ensure the Flexible rope cannot slip out at any angle.

3.2.5 The tension bracket should be rated and tested for the loads . The load shall be applied at an angle of
45 degree from the normal to the surface of mounting of the bracket.

Conductor Rating Load for Load for


Size deformation deformation
(Sq.mm.) <10mm (Newtons) <30mm & no-break
(Newtons)
50-95 2000 Kg. 15,600 19,500

3.6 Wedge Type Tension Clamp

3.6.1 Wedge type clamps shall be used for clamping the messenger without damaging the insulation.
3.6.2 The clamp shall be capable of clamping an uncut messenger so that it can continue without break to
the connecting point or next span.
3.6.3 The clamp shall be fully insulating type of mechanical and weather resisting thermoplastic.
3.6.4 No bolts or loose parts are allowed as part of the Clamping system.
3.6.5 No tools shall be needed for fitting the messenger into the clamp.
3.6.6 The clamp shall be self tightening and capable of holding without slippage the load

3.7 Test Certificate.


3.7.1 Type Test, Acceptance test, Routine test reports obtained from an NABL accredited Laboratory
should be furnished

NOTES
I. Permissible tolerance shall be ± 5% on the indicated dimensions.

4.0 TECHNICAL SPECIFICATIONS FOR 3 PHASE L.T. DISTRIBUTION BOX FOR AERIAL
BUNCHED CABLE

4.1 The L.T. Distribution Box is used for connection through overhead ABC line and for giving
connections to the consumers. The L.T. Distribution Box will be installed at the poles and it should
have anti-corrosive, dust proof, rust proof, shock proof, vermin proof, U.V. stabilized and flame
retardant property. Base door or other joint should not bend, soften on heating and it should be of
tamper proof construction the material of box should withstand temperature rise, hot
spot temperature and occasional arcing of bus bar system.

4.1.1 The Box/Kiosk shall be made out of thermosetting plastic i.e. Glass Fiber Reinforced Polyester Sheet
Moulding Compound (SMC) as per IS: 13410-1992 having properties as given in GTP.

4.1.2 The box should have sealing as well as pad locking arrangement. One M.S. Flat with 12 mm dia hole
should be provided for pole mounting.

1
0
4.1.3 The Distribution Box shall have 3 phase Bus bars of EC grade Aluminium of size 25x6 x 300 mm
long and neutral bus bar shall be of size 40x6x 300 mm. The Bus bars shall be provided with colour
coding for identification. Each Bus bar shall be provided with facility of cable termination as under:

a) Incoming: 1 No lead per phase, thus 4 polymeric gland of 25 mm dia at bottom.


b) Outgoing: Twelve leads per phase, thus 12 nos., 10 mm dia holes with rubber gromets i.e. 6 holes
on each Side wall with rubber covers.

4.1.4 To facilitate easy working on termination on bus bar, the arrangement for termination of each lead
should be have 6 mm dia holes duly fitted with M 6 x 20 screw, I custom designed Aluminum palm
.washer, 1 washer, 1 spring washer and I fly nut as shown in drawing.

4.1.5 In order to restrict entry of tool from unused (cable entry) holes, partition plate should be provided
between wall of the box and bus bar system. The service wire/cables will be taken from entry hole,
suitably bent and taken to bus bar and' finally the wire/cable shall be terminated and lightened using
fly nut.

4.1.6 The assembly of four nos. Al. Busbars shall be mounted on one SMC Step mounting arrangement.
The mounting arrangement of Bus bars shall be such that minimum clearance of 50 mm is maintained
between Busbar and Box wall on all sides. This clearance will provided adequate space for working as
well as bending of wires. Also there should be minimum clearance of 40 mm between each bus bar so
as to take care of clearance and creepage distance requirements in line with IS: 13947.

4.1.7 The dimension of box shall be 450 x 375 x 200 mm. Thickness of box shall be 3 mm. The colour of
box shall be Off White such that it does not absorb heat of solar radiation. Reprocessible plastics and
of dark colour will not acceptable.

4.2 Test Certificate.


4.2.1 Type Test, Acceptance test, Routine test reports obtained from an NABL accredited Laboratory
should be furnished

GUARANTEED TECHNICAL PARTICULARS

SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR L.T. ABCCABLES


Sl.No. Description Required Bidder to
Confirm
1. Manufacturer’s Name & Address
2. Lists of Standard applicable.
3. Power/Neutral-Cum-Messenger Core Conductors.
Nominal cross sectional area, no. of standards and strand dia.
i) Power Cross(mm.)n/mm. 70 Sq. mm
ii) Neutral-Cum-Messenger Core(mm)/n/mm. 50 Sq. mm
iii) Street Lighting Core(mm.)/n/mm. 16 Sq. mm
B. Max. DC resistance of conductor at 200 C
i) Power Cross(Ohm/Km.) 0.443
3.1
Ohm/Km
ii) Neutral-Cum-Messenger Core (Ohm/Km.) 0.689
Ohm/Km
iii) Street Lighting Core (Ohm/Km.) 1.91 Ohm/Km
C. Approximate diameter of Conductor.
i) Power Cross(mm.) 9.4 mm.
1
1
ii) Neutral-Cum-Messenger Core (mm.) 7.9 mm.
iii) Street Lighting Core (mm.) 4.4 mm.
3.2 Insulation Minimum Thickness
i) Power Cross(mm.) 1.5 mm.
ii) Neutral-Cum-Messenger Core (mm.) 1.2 mm.
iii) Street Lighting Core (mm.) 0.98 mm.
4. Messenger Wire (Insulated)
i) Nom. Cross Sectional area(sq.mm.) 50 sq.mm.)
ii) Approx.Tention load (KN) 14 KN
5. Current ratings
Continuous current carrying capacity of Cable in Air at
Ambient
Temp. 400 C (Amp.)
i) Power Cores 155 A
ii) Neutral-Cum-Messenger Core -
iii) Street Lighting Core 60 A
6. Approx. Weight (Kg./Km.) -
7. No. of Cores
i) Power Core (No.) 3
ii) Street Lighting Core (No.) 1
iii) Insulated Messenger (No.) 1
8. Derating factor
Derating factors for variation in Air Temp.
Air Temp. °C -
9. Rating Factor. -
9.1 Identification of Power Cores, Neutral-Cum- Messenger -
Core & Street Lighting Core.
10. Details of Power/Neutral-Cum-Messenger Core
10.1 Conductor :
a) Material Aluminium
b) Flexibility Class as per IS : 8130/84 -
c) Form of Conductor. -
10.2Insulation -
a) Material. XLPE
b) Form of Conductor -
11. Voltage of Cable.
a) Voltage Class 1.1 KV
b) Neutral Earthing. Solid
12.
Maximum Conductor Temperature.
a) Continuous (in Deg.C) 90 0C

GTP FOR INSULATION PIERCING CONNECTORS

Sl. Description Unit Required Bidder to Confirm


No.
1 Type of Clamp Insulation piercing
connector

1
2
2 Name and address of
manufactured of ABC
accessories
3 Product Designation
4 Standard As per NFC 33 020-1998
Range of Cable sizes Main: 50-150 Sq. mm.
5 accommodated for main &
branch
Branch: 6-35(50) Sq.
mm.
6 Application KV 1.1
7 System Frequency Hz 50
8 Material Composition a)Body: Weather & UV
resistance glass fibre
reinforced polymer
b)contact plates-
Aluminium alloy
c)Bolt-Dechromatized
steel
d)Seats & end caps:
Elastomer
9 Voltage withstand under KV 6 KV for 1 min
water emersion
10 Electrical Ageing Type Test
11 No. of cycles 200
12 Max. Temperature for each 90oC
cycle
13 Min. & Max. Torque Nm Max. 12.1
defined
Min. 9.9
14 Rated Tightening Torque Nm 11
15 Marking Main Range
Tap Range
16 Dimensions mm
17 Approximate weight Kg 0.12

GTP FOR SUSPENSION ASSEMBLY

SL.No. Description Required Bidder to Conform


1 Type of Clamp Suspension Clamp
Assembly
2 Name & Address of the
Manufacturer
3 Standard NFC 33-040.
4 Range of messenger size 50 sq.mm
5 Installation (with / without Without disassembling
disassembly) (Ready-to-use)
6 Is bracket & movable link Yes
included
7 Type & grade Metallic / Non- Al alloy for Bracket
metallic Material &Thermo plastic for
Suspension Clamp body,
Movable link & Lever
8 Colour of Non metallic parts Black
9 Dimensions (mm)
10 Approximate weight (Kg)
1
3
11 Breaking Load (KN) 12 KN
12 Di-Electric test (Min 6 KV AC Yes. Withstand Min 6
for 1 minute) KV AC for1minute
13 Maximum load holding
capacity (KN)
14 Max. vertical load sustained by
clamp (KN.)
15 Are all type test reports as per Yes.
NFC 33-040 enclosed

GTP FOR DEAD-END (ANCHORING ASSEMBLY)

SL.No. Description Required Bidder to Conform


1 Type of Clamp Dead end clamp Assembly
2 Name & Address of the
Manufacturer
3 Standard NFC 33-041.
4 Range of messenger size 50sqmm
5 Type of design Wedge Type
6 Installation (with / without Without disassembling
disassembly) (Ready-to-use)
7 Type & grade Metallic / Non- Al alloy for Body and
metallic Material Thermo plastic for
Wedges
8 Colour of Non metallic parts Black
9 Dimensions (mm) GA Drawing enclosed
10 Approximate weight (Kg)
11 Breaking Load (KN)
12 Di-Electric test (Min 6 KV AC Yes. Withstand Min 6 KV
for 1 minute) AC for1minute
13 Maximum load holding capacity
(KN)
14 Max. vertical load sustained by
clamp (KN.)
15 Is type test report enclosed as Yes
per NFC 33-041

GUARANTEED TECHNICALPARTICULARS FOR THREE PHASE L.T.DISTRIBUTION BOX

Sl. No. Particulars Detailed Particulars Offered


1 Material Thermosetting Plastic
2 Grade of Material SMC IS :13410 Grade S1
3 Thickness of Base/door (min) 3 mm (min)
4 Properties of Material of SMC
(a) Heat Deflection Temp. 150 ° C
(Ref. Standard ISO 75-III)
(b) Exposure to flame Self Extinguishing
(Ref. Standard IS:4249)
(c) Melting Point (Test up to 250°C) Does Not Melt
IS: 13360 part 6 Sec 10, 1992
Section 1 method `A'. Capillary
Tube Method
5 Dimensions of Box Refer Drawing
(a) Height 450 mm
(b) Width 375 mm
(c) Depth 200 mm
1
4
6 Earthing Arrangement
(a) No. of earth bolts 1 No.
(b) Material of earthing bolt MSZP
(c) Dia. & length of bolts M 6 x 25
7 Sealing Arrangement 2 Nos. on door
8 Facility of locking Hole for locking
arrangement
9 Colour of box Off white
10 Cable Entry and Exit
Arrangement
(a) Incoming 1 No lead per phase, thus 4
polymeric gland of 25 mm
dia at bottom.
(b) Outgoing Twelve leads per phase,
thus 12 nos., 10 mm dia
holes with rubber gromets
i.e. 6 holes on each Side
wall with rubber covers.
11 Bus Bars
(a) Bus Bars MoC E.C. Grade Aluminum
(b) Phase & Neutral Bus bar Size & 25 x 6 mm size: 300 mm
Quantity long 3 nos.(R,Y,B)
40 x 6 mm size: 300 mm
long 1 no. (N)
(c) No. of connection on each Bus O/G. 4 Nos. for service
Bar connection
I/C: 1 no. for ABC
(d) Connection arrangement As per drawing
12 Clearances
(a) Bus Bar & Box wall Min 50 mm on all sides
(b) Between Bus Bars Min 40 mm
13 Bus Bar Mounting
arrangement
(a) Arrangement Stepped mounting
14 Pole Mounting Arrangement
(a) Back strips for pole/wall 25 x 3 mm, Zinc
structure mounting passivated MS flats with
hole for 12 mm dia
bolts

1
5

You might also like