Discrete Output (P - DOut)
Discrete Output (P - DOut)
Discrete Output (P - DOut)
IMPORTANT This manual applies to the Rockwell Automation Library of Process Objects version 3.5 or earlier.
For Rockwell Automation Library of Process Objects version 4.0 or later, use the following manuals:
• PROCES-RM013 contains logic instructions
• PROCES-RM014 contains display elements
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required
to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that may cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances may lead to personal injury or death, property damage,
or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Table of Contents
Preface Software Compatibility and Content Revision. . . . . . . . . . . . . . . . . . . . 5
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Discrete Output (P_DOut) Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Controller File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Visualization Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Controller Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Input Structure for Discrete Output . . . . . . . . . . . . . . . . . . . . . . . . 11
Output Structure for Discrete Output. . . . . . . . . . . . . . . . . . . . . . . 15
Local Configuration Tags for Discrete Output . . . . . . . . . . . . . . . 19
Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Execution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Programming Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Status/Quality Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Mode Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Alarm Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Maintenance Bypass Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Using Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Quick Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Faceplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Discrete Output Faceplate Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Notes:
For the latest compatible software information and to download the Rockwell
Automation® Library of Process Objects, see the Product Compatibility and
Download Center at
http://www.rockwellautomation.com/rockwellautomation/support/pcdc.page.
Additional Resources These documents contain additional information concerning related products
from Rockwell Automation.
Resource Description
PlantPAx® Distributed Control System Selection Guide, Provides information to assist with equipment
publication PROCES-SG001 procurement for your PlantPAx system.
PlantPAx Distributed Control System Reference Manual, Provides characterized recommendations for
publication PROCES-RM001 implementing your PlantPAx system.
Rockwell Automation Library of Process Objects, Provides general considerations for the PlantPAx system
publication PROCES-RM002 library of process objects.
FactoryTalk® View Machine Edition User Manual, Provides details on how to use this software package for
publication VIEWME-UM004 creating an automation application.
FactoryTalk View Site Edition User Manual, Provides details on how to use this software package for
publication VIEWSE-UM006 developing and running human-machine interface
(HMI) applications that can involve multiple users and
servers, distributed over a network.
Logix5000™ Controllers Add-On Instructions Programming Provides information for designing, configuring, and
Manual, publication 1756-PM010 programming Add-On Instructions.
Rockwell Automation Library of Process Objects: Common Details how to monitor an input condition to raise an
Alarm Block (P_Alarm) Reference Manual, alarm. Information includes acknowledging, resetting,
publication SYSLIB-RM002 inhibiting, and disabling an alarm.
Rockwell Automation Library of Process Objects: Interlocks Explains how to collect (sum up) the interlock
with First Out and Bypass (P_Intlk) Reference Manual, conditions that stop or de-energize a running or
publication SYSLIB-RM004 energized piece of equipment or prevent it from
starting or being energized.
Process Add-On Instructions: Standard Modes (P_Mode) Explains how to select the Mode (owner) of an
Reference Manual, publication SYSLIB-RM005 instruction or control strategy. The Mode instruction is
usually embedded within other instructions to extend
their functionality. It is possible to use a standalone
Mode instruction to enhance a program where modes
are wanted.
Rockwell Automation Library of Process Objects: Permissives Details how to collect permissive conditions to start a
with Bypass (P_Perm) Reference Manual, piece of equipment.
publication SYSLIB-RM007
Faceplate
Add-On Instruction
Global Objects
Add-On Instructions are reusable code objects that contain encapsulated logic
that can streamline implementing your system. This lets you create your own
instruction set for programming logic as a supplement to the instruction set
provided natively in the ControlLogix® firmware. An Add-On Instruction is
defined once in each controller project, and can be instantiated multiple times in
your application code as needed.
Controller File
The P_DOut_3_5-00_AOI.L5X Add-On Instruction must be imported into
the controller project to be used in the controller configuration. The service
release number (boldfaced) can change as service revisions are created.
Visualization Files
This Add-On Instruction has associated visualization files that provide a
common user interface. These files can be downloaded from the Product
Compatibility and Download Center at
http://www.rockwellautomation.com/rockwellautomation/support/pcdc.page.
IMPORTANT The visualization file dependencies require Process Library content imports to
occur in a specific order as reflected in the following tables:
• Images
• Global Objects
• Standard Displays
• HMI Tags
• Macros
Images are external graphic files that can be used in displays. They must be
imported for FactoryTalk View to make use of them.
When PNG files are imported, they are renamed by FactoryTalk View with
a .bmp file extension, but retain a .png format.
Table 2 - Visualization Files: Images (.png)
FactoryTalk View SE Software FactoryTalk View ME Software Description
All .png files in the images folder All .png files in the images folder These are the common icons used in the global objects and
standard displays for all Process Objects.
The Global Object files (.ggfx file type) in the following table are Process Library
display elements that are created once and referenced multiple times on multiple
displays in an application. When changes are made to a Global Object, all
instances in the application are automatically updated.
Table 3 - Visualization Files: Global Objects (.ggfx)
FactoryTalk View SE Software FactoryTalk View ME Software Description
(RA-BAS) Common Faceplate Objects (RA-BAS-ME) Common Faceplate Objects Global objects used on process object faceplates.
(RA-BAS) P_DOut Graphics Library (RA-BAS-ME) P_DOut Graphics Library P_DOut global object device symbols used to build
process graphics.
(RA-BAS) Process Alarm Objects (RA-BAS-ME) Process Alarm Objects Global objects used for managing alarms on process
object faceplates.
The Standard Display files (.gfx file type) in the following table are the Process
Library displays that you see at runtime.
Table 4 - Visualization Files: Standard Displays (.gfx)
FactoryTalk View SE Software FactoryTalk View ME Software Description
(RA-BAS) Common-AnalogEdit N/A Faceplate used for analog input data entry. The FactoryTalk
View ME faceplates use the native analog input data entry
so no file is required.
(RA-BAS) P_Alarm-Faceplate (RA-BAS-ME) P_Alarm-Faceplate The faceplate that is used for managing alarms for
the object.
(RA-BAS) P_Alarm-Help (RA-BAS-ME) P_Alarm-Help Alarm Help information that is accessed from the
P_AIarm faceplate.
(RA-BAS) P_DOut-Faceplate (RA-BAS-ME) P_DOut-Faceplate The faceplate that is used for the object
(RA-BAS) P_DOut-Quick (RA-BAS-ME) P_DOut-Quick The Quick display that is used for the object
(RA-BAS) P_Mode-Config (RA-BAS-ME) P_Mode-Config The Configuration Display used to configure the
P_Mode object.
(RA-BAS) P_Mode-Help (RA-BAS-ME) P_Mode-Help Mode Help information that is accessed from the
Help faceplate.
(RA-BAS) Process Discrete Family-Help (RA-BAS-ME) Process Discrete Family-Help The Help display for Discrete objects
(RA-BAS) P_Intlk-Faceplate (RA-BAS-ME) P_Intlk-Faceplate Optional
The interlock faceplate used for the object.
Use this file if your Discrete Output has an associated
P_Intlk object and you enable navigation to its faceplate
from the Discrete Output faceplate.
(RA-BAS) P_Perm-Faceplate (RA-BAS-ME) P_Perm-Faceplate Optional
Permissive faceplate that is used for the object
Use this file if your object has an associated P_Perm object
and you enable navigation to the P_Perm faceplate from
the object faceplate.
(RA-BAS) Process Interlock Family-Help (RA-BAS-ME) Process Interlock Family-Help Optional
Interlock/permissives help display that is used for
the object
Use this file if you use the P_Intlk or P_Perm faceplate.
Controller Code This section describes the parameter references for this Add-On Instruction.
Cfg_OnFailSeverity INT OnFail.Cfg_Severity 1000 These parameters determine the severity of each alarm. This drives the color and
symbol that are used to indicate alarm status on the faceplate and global object.
Cfg_OffFailSeverity OffFail.Cfg_Severity 1000 The following are valid values:
Cfg_IntlkTripSeverity IntlkTrip.Cfg_Severity 500 1…250 = Low
251…500 = Medium
Cfg_IOFaultSeverity IOFault.Cfg_Severity 1000
501…750 = High
751…1000 = Urgent
IMPORTANT: For FactoryTalk View software, version 7.0, these severity
parameters drive only the indication on the global object and faceplate. The
Alarms and Event definition severity drives the color and symbol that is used on the
alarm banner and alarm summary as well as the value returned by FactoryTalk
Alarms and Events display commands.
Cfg_SimFdbkT DINT 2 Delay to echo back of On/Off status when in simulation (seconds).
Cfg_OnDelayT REAL 0.0 Delay before initially turning output On or Off (seconds).
Cfg_OffDelayT
Cfg_OnPulseT REAL 0.5 Output On time for pulse On or pulse continuous (seconds).
Cfg_OffPulseT REAL 0.5 Output Off time for pulse Off or pulse continuous (seconds).
Cfg_OnFailT DINT 10 Time after output On to get On feedback before fault (seconds).
Cfg_OffFailT DINT 10 Time after output Off to get Off feedback before fault (seconds).
PSet_Owner DINT 0 Program owner request ID (non-zero) or release (zero).
• Alarm data elements (Alm_) are outputs of the instruction that indicate a
particular alarm has occurred.
• Acknowledge data elements (Ack_) are outputs of the instruction that
indicate the corresponding alarm has been acknowledged.
• Ready data elements (Rdy_) are bit outputs of the instruction used by the
HMI to enable and disable Command buttons and Setting entry fields.
Table 7 - P_DOut Output Parameters
Output Parameter Data Type Alias For Description
EnableOut BOOL Enable output: The EnableOut signal is not manipulated by this instruction. Its output state
always reflects EnableIn input state.
Out BOOL Primary output:
1 = On
0 = Off
SrcQ_IO SINT I/O signal source and quality.
SrcQ Final device status source and quality.
GOOD 0 = I/O live and confirmed good quality
1 = I/O live and assumed good quality
2 = No feedback configured, assumed good quality
TEST 8 = Device simulated
9 = Device loopback simulation
10 = Manually entered value
UNCERTAIN 16 = Live input, off-specification
17 = Value substituted at device/bus
18 = Value substituted by maintenance (Has and not Use)
19 = Shed, using last good value
20 = Shed, using replacement value
BAD 32 = Signal failure (out-of-range, NaN, invalid combination)
33 = I/O channel fault
34 = I/O module fault
35 = Bad I/O configuration (for example, scaling parameters)
Val_Cmd SINT Device command:
0 = None
1 = Off
2 = On
3 = Pulse off
4 = Pulse on
5 = Pulse continuously
Val_Fdbk SINT Device feedback:
0 = Transition
1 = Off
2 = On
3 = Invalid
Val_Sts SINT Device status:
0 = Off
1 = On
2 = Pulse off
3 = Pulse on
4 = Pulse continuously
5 = Turning off
6 = Turning on
33 = Disabled
Configuration parameters that are arrayed, string, or structure data types cannot
be configured as parameters for Add-On Instructions. Configuration parameters
of these types appear as local tags to the Add-On Instruction. Local tags can be
configured through the HMI faceplates or in Studio 5000 Logix Designer®
application by opening the Instruction Logic of the Add-On Instruction instance
and then opening the Data Monitor on a local tag. These parameters cannot be
modified by using controller logic or Logix Designer application export/import
functionality.
Operations This section describes the primary operations for Add-On Instructions.
Modes
This instruction uses the following standard modes, which are implemented by
using an embedded P_Mode Add-On Instruction.
Table 9 - Modes
Mode Description
Operator The Operator owns control of the device. Operator commands (OCmd_) and Operator settings
(OSet_) from the HMI are accepted.
Program Program logic owns control of the device. Program commands (PCmd_) and Program settings
(PSet_) are accepted.
Override Priority logic owns control of the device and supersedes Operator and Program control. Override
Inputs (Inp_OvrdCmd and other Inp_OvrdXxxx values) are accepted. If so configured,
bypassable interlocks and permissives are bypassed.
Maintenance Maintenance owns control of the device and supersedes Operator, Program, and Override
control. Operator commands and settings from the HMI are accepted. Bypassable interlocks and
permissives are bypassed, and device timeout checks are not processed.
Hand Hardwired logic or other logic outside the instruction owns control of the device. The instruction
tracks the state of the device for bumpless transfer back to one of the other modes.
No Mode The device is disabled and has no owner because the EnableIn input is false. The main
instruction Logic routine is not being scanned. See Execution section for more information on
EnableInFalse processing.
Alarms
This instruction uses the following alarms, which are implemented by using
embedded P_Alarm and P_Gate Add-On Instructions.
Simulation
You must set the Inp_Sim parameter in the controller to ‘1’ to enable simulation.
You can use Cfg_SimFdbkT to delay the echo of the On/Off status of the device.
When you have finished in simulation, set the Inp_Sim parameter in the
controller to ‘0’. The output is re-energized and feedback is enabled.
Execution
Condition Description
EnableIn False (false rung) Handled the same as if the device were Disabled by
Command. The device output is de-energized and the
device is shown as Disabled on the HMI. The mode is
shown as ‘NO MODE’. All alarms are cleared.
Powerup (prescan, first scan) On Prescan, any Commands received before First Scan are
discarded. The device is de-energized. On first scan, the
device is treated as if it were returning from Hand mode:
the instruction state is set based on the feedback received
from the device.
Embedded P_Mode and P_Alarm instructions are
handled in accordance with their standard powerup
procedures. See the P_Mode and P-Alarm reference
manuals for details.
Postscan No SFC Postscan logic is provided.
Programming Example
This example uses the P_DOut instruction to control a heating jacket on a vent
filter. The heating jacket is being used in this case to keep the vent filter dry when
there is potential for condensate buildup.
In this example, the vent filter heater jacket does not provide the feedback on its
status. In normal operating conditions, the vent filter heater jacket is being
commanded on or off by the control sequence configured in the controller. If the
operating status of the sequence is not OK, always command the vent filter off.
In this example, the controlling sequence issues a single bit for the desired state of
the vent filter heater. The parameter P_CmdOn is connected to this bit to
command the vent filter heater on and off. The parameter Cfg_PCmdClear is set
to 0, indicating that the command bit does not need reset by the instruction. This
setting also indicates that the P_DOut instruction acts upon P_CmdOn based
on value (level) instead of acting only on transition to true (edge) so that
P_CmdOn can be used to command both the On and Off states.
The controlling sequence could be written to set the command bits P_CmdOn
and P_CmdOff directly (for example, by using structured text within a SFC), in
which case Cfg_PCmdClear could be left at its default of 1 to cause the
instruction to clear the commands once they have been acted upon.
Lastly, configure the following local configuration tags to drive the text on the
HMI faceplate. In this example, the vent filter P&ID tag is JV9010. In this
example, they are set as follows:
Cfg_Tag: ‘JV9010’
Cfg_Label: ‘Vent Filter Heater’
Cfg_Desc: ‘Vent Filter Heater Jacket’
Cfg_St0Text: ‘Off ’
Cfg_St1Text: ‘On’
Local tags can be configured through the HMI faceplates or in Logix Designer
application by opening the Instruction Logic of the Add-On Instruction instance
and then selecting the string on the displayed rung.
All strings in local tags are shown on the first rung of the Add-On Instruction's
Logic routine for your convenience.
Display Elements A display element (global object) is created once and can be referenced multiple
times on multiple displays in an application. When changes are made to the
original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, in conjunction with tag structures
in the ControlLogix system, aid consistency and save time.
Table 10 - P_DOut Display Elements Description
Display Element Name Display Element Description
GO_P_DOut Digital (2-state) device display
element for use on overview and
detail displays.
Status/Quality Indicators
One of these symbols appears on the graphic symbol when the described
condition is true.
Graphic Symbol Description
Invalid configuration.
TIP When the Invalid Configuration Indicator appears, you can find what
configuration setting is invalid by following the indicators. Click the graphic
symbol to open the faceplate. The Invalid Configuration indicator appears next
to the appropriate tab at the top of the faceplate to guide you in finding the
configuration error. Once you navigate to the tab, the misconfigured item is
flagged with this indicator or appear in a magenta box.
For the Discrete Output instruction, the Invalid Configuration indicator appears
under the following conditions:
• The output’s On Delay, Off Delay, On Pulse, Off Pulse, On Failure Check,
or Off Failure Check time is set to a value less than zero or greater than
2,147,483 seconds.
• The simulated feedback time is set to a value less than zero or greater than
2,147,483 seconds.
• An Alarm Minimum On Time is set to a value less than zero or greater
than 2,147,483 seconds.
• Alarm Severity is set to a value less than 1 or greater than 1000.
TIP When the Not Ready indicator appears, you can find what condition is
preventing operation by following the indicators. Click the graphic symbol to
open the faceplate. The Not Ready indicator appears next to the appropriate
tab at the top of the faceplate to guide you in finding the condition. When you
navigate to the tab, the condition preventing operation is flagged.
For the Discrete Output instruction, the Device Not Ready indicator appears
under the following conditions:
• The device has been disabled by Maintenance.
• There is a configuration error.
• An interlock or permissive is not OK.
Mode Indicators
One of these symbols appears on the right side of the graphic symbol to indicate
the mode of the object instruction.
Graphic Symbol Description
Transparent Operator mode (if the default mode is Operator and the current mode is Operator, the mode
indicator is transparent).
Operator mode (if the default mode is Program).
Transparent Program mode (if the default mode is Program and the current mode is Program, the mode
indicator is transparent).
Program mode (if the default mode is Operator).
Override mode
Maintenance mode.
Hand mode
No mode.
TIP The images provided for the Operator and Program default modes are
transparent; therefore, no mode indicators are visible if the device is in its
default mode. This behavior can be changed by replacing the image files for
these mode indicators with images that are not transparent.
Alarm Indicators
One of these symbols appears on the left side of the label to indicate the described
alarm condition and the alarm border and label background change color. The
alarm border and label background blink if acknowledgement of an alarm
condition is required. Once the alarm is acknowledged, the alarm border and
label background remain the color that corresponds to the severity of the alarm.
Symbol Border and Label Background Description
No change in color Alarm Inhibit: an alarm is suppressed by the Program,
disabled by Maintenance, or shelved by the Operator.
No symbol No change in color No alarm or alarm inhibit condition, and all alarms
are acknowledged.
TIP When the Maintenance Bypass Indicator appears, you can find what condition
was bypassed by following the indicators. Click the graphic symbol to open the
faceplate. The Maintenance Bypass Indicator appears next to the appropriate
tab at the top of the faceplate to guide you in finding the
bypass. Once you navigate to the tab, the bypassed item is flagged with this
indicator.
• A feedback input that Engineering has configured to exist has been set by
Maintenance not to be used.
• Maintenance has bypassed the bypassable interlocks and permissives.
The global objects for P_DOut can be found in the global object file
(RA-BAS) P_DOut Graphics Library.ggfx. Do the following to use a
global object.
1. Copy it from the global object file and paste it in the display file.
2. In the display, right-click the global object and choose Global Object
Parameter Values.
3. Type the tag or value in the Value column as specified in the Description
column.
TIP You can click the ellipsis (. . .) to browse and select a tag.
Values for items marked ‘(optional)’ can be left blank.
4. Click OK.
Quick Display The Quick Display screen provides means for operators to perform simple
interactions with the P_DOut instruction instance. From the Quick Display,
you can navigate to the faceplate for full access for operation, maintenance, and
configuration for operation, maintenance, and configuration.
Faceplate The P_DOut faceplate consists of five tabs and each tab consists of one or more
pages.
The faceplate contains the value of local configuration tags Cfg_Tag and
Cfg_Desc in the title bar.
The Operator tab is displayed when the faceplate is initially opened. Click the
appropriate icon at the top of the faceplate to access a specific tab.
Maintenance Diagnostics Help
The faceplate provides the means for operators, maintenance personnel, and
others to interact with the P_DOut instruction instance, including viewing its
status and values and manipulating it through its commands and settings.
Operator Tab
The Faceplate initially opens to the Operator (‘Home’) tab. From here, an
operator can monitor the device status and manually operate the device when it is
in Operator mode.
Continuous Pulse
Button Single Pulse 'Off' Button
The following table shows the functions included on the Operator tab.
Table 11 - Operator Tab Description
Function Action Security
Click to unlock Operator mode. Function unlocks Operator Manual Device
mode, allowing the program to take control. Operation (Code B)
If the object is configured to have permissive and interlock objects (for example,
Cfg_HasIntlkObj is true), the permissive and interlock indication become
buttons that open the faceplates of the source objects used as a permissive or
interlock (often this is a P_Intlk interlock object or a P_Perm permissive object).
If the object is not configured in this way, the permissive or interlock are
indicators only.
Non-bypassed conditions OK
All conditions OK
Alarm indicators appear on the Operator tab when the corresponding alarm
occurs.
On Fail Alarm
The following table shows the alarm status on the Operator tab.
Table 12 - Operator Tab Alarm Status
Graphic Symbol Alarm Status
In Alarm (Active Alarm).
Maintenance Tab
Maintenance personnel use the information and controls on the Maintenance tab
to adjust device parameters, troubleshoot and temporarily work around device
problems, and disable the device for routine maintenance.
The following table shows the functions on page 1 of the Maintenance tab.
Table 13 - Maintenance Tab Page 1 Description
Function Action Security Configuration Parameters
Click for Maintenance mode. Equipment None
Maintenance
(Code C)
Page 2 of the Maintenance tab page shows the time settings for
activating/deactivating the device and output.
The following table shows value settings on page 2 of the Maintenance tab.
Table 14 - Maintenance Tab Page 2 Description
Function Action Security Configuration Parameters
Time after Output Type the amount of time to allow for Configuration Cfg_OnFailT
ON for feedback the device to get feedback for the On and Tuning
before Fault setting before setting a fault. Maintenance
(seconds) (Code D)
Time after Output Type the amount of time to allow for Cfg_OffFailT
OFF for Feedback the device to get feedback for the Off
before Fault setting before setting a fault.
(seconds)
Delay before Type the amount of time before the Cfg_OnDelayT
initially turning output activates.
output ON
(seconds)
Delay before Type the amount of time before the Cfg_OffDelayT
initially turning output deactivates.
output OFF
(seconds)
Engineering Tab
On page 1 of the Engineering tab, you can configure textual descriptions and
feedback parameters.
The following table lists the functions on page 1 of the Engineering tab.
Table 15 - Engineering Tab 1 Description
Function Action Security Configuration Parameters
Click to navigate to the Mode None See Mode Configuration display on
Configuration display. page 41.
This display lets you select the default mode for the object by selecting the
appropriate mode.
IMPORTANT If no mode is being requested, changing the default mode changes the mode
of the instruction.
You must have FactoryTalk View security code E to select the default mode on
this display.
On Page 2 of the Engineering tab, you can select operator command options,
finish pulse, navigation options, and De-energize Output.
The following table shows the functions on page 2 of the Engineering tab.
Table 16 - Engineering Tab Page 2 Description
Function Action Security Configuration Parameters
Operator command Check to reset a fault upon a operator Engineering Cfg_OCmdResets
resets fault command. Configuration
Clear this checkbox to reset faults by (Code E)
using only the reset code.
Operator ‘Off’ Check to make the Operator Off Cfg_OperOffPrio
command available command available in any mode.
in any mode Clear this checkbox to make the
Operator Off command available only
in Operator or Maintenance mode.
Finish Pulse when Check to finish pulse when Cfg_CompletePulse
commanded ON commanded ON or OFF.
or OFF
On Page 3 of the Engineering tab, you can set the feedback delay.
The following table shows the functions on page 3 of the Engineering tab.
Table 17 - Engineering Tab Page 3 Description
Function Action Security Configuration Parameters
Feedback delay for Sets the time delay (in seconds) for Engineering Cfg_SimFdbkT
loopback test or the On or Off status to be echoed back Configuration
when feedback not when Simulation is enabled or when (Code E)
used (seconds) On and Off feedbacks are not used.
Diagnostics Tab
Alarms Tab
The Alarms tab displays each configured alarm for the P_DOut instruction. The
icon on the tab for the alarms page changes color based on the current active
alarms. A blinking alarm icon indicates that one or more alarms must be
acknowledged or the device must be reset.
Alarm Acknowledge
Command Button
Alarm Names
Click an alarm name to open the P_Alarm faceplate for that alarm. From the
P_Alarm faceplate, you can configure and perform additional operations on
the alarm.
If an alarm is active, the panel behind the alarm changes color to match the
severity of the alarm. The color of the bell icon at the top of the faceplate shows
the severity of the highest active alarm, and the icon blinks if any alarm is
unacknowledged or requires reset.
When the Reset and Acknowledge All Alarms button is enabled, the panel
behind the alarm blinks, indicating the alarm requires acknowledgement or reset.
The Alarm Acknowledge button is enabled if the alarm requires
acknowledgment. Click the button with the check mark to acknowledge the
alarm.
In addition, we offer multiple support programs for installation, configuration, and troubleshooting. For more
information, contact your local distributor or Rockwell Automation representative, or visit
http://www.rockwellautomation.com/services/online-phone.
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this
manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada 1.440.646.3434
Outside United States or Canada Use the Worldwide Locator at http://www.rockwellautomation.com/rockwellautomation/support/overview.page, or contact your local
Rockwell Automation representative.
Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the
manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your
distributor to complete the return process.
Outside United States Please contact your local Rockwell Automation representative for the return procedure.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this
document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400