Siemens 7SJ86 V7.00 Feeder PTT User Manual ENU
Siemens 7SJ86 V7.00 Feeder PTT User Manual ENU
Siemens 7SJ86 V7.00 Feeder PTT User Manual ENU
OMICRON PTL
User Manual
V1.000
Content
1. General ............................................................................................................................................ 3
2. Software and Hardware Requirements........................................................................................... 3
3. Hardware ......................................................................................................................................... 4
4. Functional Range ............................................................................................................................ 4
5. XRIO Converter ............................................................................................................................... 5
1. General
This user manual describes details of testing Siemens 7SJ86 relay with the OMICRON
Protection Test Template. General information on the usage of OMICRON Protection Testing Library
items can be found in the OMICRON PTL user manual.
Any CMC test set can be used with this Protection Test Template.
3. Hardware
There are multiple possibilities of wiring Siemens 7SJ86 relay to a CMC test set. The advised
connections are shown in Figure 1. These connections are the default settings in the
Hardware Configuration of the PTT.
VC
VN
VA
VB
IN
IC
IA
IB
Manual Close
CB aux (52a)
Start
Trip
I0_N*
I0*
* is for measured
current inputs
4. Functional Range
Supported functions:
Overcurrent protection, phases
Overcurrent protection, ground
Directional time-overcurrent protection, phases
Ground-Fault Protection for High-Resistance Ground Faults in Grounded Systems
Switch On To Fault SOTF protection (with Overcurrent protection)
Although the functions listed above are not supported by the Protection Test Template, the
Relay Parameter Section of the XRIO Converter includes all protection parameters of the relay.
5. XRIO Converter
The Test Object contains 7SJ86 XRIO Converter, which includes setting parameters of the modeled
protection relay. The setting parameters are built as an image of the Digsi5 V7.00 software.