Siemens 7SK85 V7.90 Motor PTT User Manual ENU
Siemens 7SK85 V7.90 Motor PTT User Manual ENU
Siemens 7SK85 V7.90 Motor PTT User Manual ENU
OMICRON PTL
User Manual
V1.000
Content
1. General ...................................................................................................................................................3
2. Software and Hardware Requirements ...............................................................................................3
3. Hardware ................................................................................................................................................4
4. Functional Range...................................................................................................................................5
5. XRIO Converter ......................................................................................................................................5
6. Specific Protection Tests ......................................................................................................................6
6.1 Motor Starting .......................................................................................................................................6
6.1.1 Locked Rotor Trip Time ..................................................................................................................6
6.1.2 Load-Jam protection .......................................................................................................................6
6.2 87M Motor Differential Protection .........................................................................................................6
6.3 32 Power Protection .............................................................................................................................6
6.3.1 Pickup Test .....................................................................................................................................6
6.3.2 Trip Times .......................................................................................................................................6
1. General
This user manual describes details of testing Siemens 7SK85 relays with the OMICRON
Protection Test Template. General information on the usage of OMICRON Protection Testing Library
items can be found in the OMICRON PTL user manual.
A CMC test set with six current and three voltage outputs is required to use the full functionality of this
PTT.
3. Hardware
There are multiple possibilities of wiring a Siemens 7SK85 relay to a CMC test set. The advised
connections are shown in
Figure 1. These connections are the default settings in the Hardware Configuration of the PTT.
Almost all functions use by default Current Output A. The only exceptions which use Current Output B are
the functions 49 Thermal overload protection and 87M Differential protection.
Connection Diagram for Siemens 7SK85
4. Functional Range
Supported functions:
• 87M Motor differential
• Load-Jam Protection Motor
• 48 Motor-Starting Time Supervision
• 32 Power (2 stages for P<, P>, Q< and Q>)
• 50/51 Overcurrent, phase 3ph (1 inverse and 2 definite time stages)
• 50N/51N Overcurrent, ground 1 inverse and 2 definite time stages)
• 49 Thermal Overload
• 49R Thermal Overload, Rotor
• 37 Undercurrent
• 46 Unbalanced Load (Therm. stage 1)
• 46 Negative-Sequence (1 inverse and 2 definite time stages)
• 59 Overvoltage-3ph (2 definite time stages)
• 59 Overvoltage-V1 (2 definite time stages)
• 59 Overvoltage-V0 (1 definite time stage)
• 59 Overvoltage-V2 (2 definite time stages)
• 47 Overvoltage-V2/V1 (1 definite time stage)
• 27 Undervoltage-3ph (2 definite time stages)
• 27 Undervoltage-V1 (2 definite time stages)
Although the functions listed above are not supported by the Protection Test Template, the
Relay Parameter Section of the XRIO Converter includes most protection parameters of the relay.
5. XRIO Converter
The Test Object already contains the Siemens 7SK85 XRIO Converter, which includes setting
parameters of the modelled protection relay. The setting parameters are built as an image of the Siemens
DIGSI5 V7.90 software.
General information about the converter structure can be found in the OMICRON PTL user manual.
Set the "Prefault time" longer than the value of the parameter Max. perm. Start. time (_:11041:109) and
adjust the "Prefault current" if necessary.